Submittal_KCC-131147.1745862691001.pdf

PDF 133 KB Posted

Attached to
FCI Big Spring - HVAC Package Units
Solicitation number
15B50325PR000159
Issued by

About this file

This document is a detailed technical submittal for a KCC Manufacturing curb adapter (Drawing #KCC-131147) designed to replace an existing HVAC unit at the Federal Correctional Institution (FCI) Big Spring. The submittal provides comprehensive dimensional drawings and specifications for transitioning from an existing Trane YCD150D unit to a new YSK150 unit, with specific details including an adapter weight of 233 lbs, pressure loss measurements, and installation requirements. Key features of the adapter include being fully assembled, insulated, and having internal duct transitions, with all welds coated in rust inhibitor.

The technical submittal is part of a solicitation (15B50325PR000159) by the Department of Justice Bureau of Prisons to purchase three 12.5-ton HVAC package units for FCI Big Spring. The new units must meet specific requirements: 460v/60hz/3ph power, R-410A refrigerant, two-stage cooling, gas heat (150 MBH), and include hail guards. The document emphasizes that contractors must carefully compare existing curb dimensions and ensure structural integrity of the installation site, with any modifications to the standard design potentially incurring additional charges and extending lead times.

View the file

Other files

File Type Posted
HVAC PACKING Q-A-3.pdf PDF
HVAC UPDATED QA.pdf PDF
HVAC PACKING Q-A.pdf PDF
Statement of Work.pdf PDF
HVAC Packing Units.pdf PDF
Submittal_YSK150A4S0L0000.1745862663000.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R/A S/A

KCC-131147

OEM CURB

55 1/2"

20 7/8"

14"

101 7/8" 63"

59 7/8"

83 7/8"

28 1/2"

66 5/8"

PHONE: 800-382-2872

FAX: 502-491-1739

NEW UNIT: YSK150

EXISTING UNIT: YCD150D

ADAPTER WEIGHT: 233lbs

DRAWING #: KCC-131147

TAG:

PRESSURE LOSS

NEW UNIT CFM INCHES OF H20

0.047

0.000

0.000

INSTALLATION INFORMATION:

CONTRACTOR MUST COMPARE THE

DIMENSIONS OF THE EXISTING CURB ON

THE PROJECT TO THE DRAWING(S)

PROVIDED.

THE INSTALLATION CONTRACTOR IS

RESPONSIBLE FOR THE STRUCTURAL

INTEGRITY OF THE INSTALLATION SITE.

WHEN CALCULATING THE UNIT

REQUIREMENTS, THE EXTERNAL STATIC

PRESSURE MUST BE TAKEN INTO

CONSIDERATION.

ANY DIMENSIONAL MODIFICATIONS TO

STANDARD KCC ADAPTER DESIGNS WILL

RESULT IN A MINIMUM ADDITIONAL

CHARGE OF $100 PER DESIGN AND WILL

RESULT IN A MINIMUM OF (3) DAYS TO

THE STATED LEAD TIME.

FEATURES:

ADAPTERS ARE ASSEMBLED BUT MAY

HAVE REMOVABLE FILLER PANS FOR

FIELD INSTALLATION.

ALL WELDS ARE COATED WITH A RUST

INHIBITOR.

ADAPTERS ARE FULLY INSULATED.

INTERNAL DUCT TRANSITIONS

INCLUDED.

KCC RESERVES THE RIGHT TO MAKE

DESIGN MODIFICATIONS WITHOUT

NOTIFICATIONS.

APPROVED

Print Name: ___________________________________

Signature: ____________________________________

Date: ________________________________________

2716 Grassland Drive Louisville, Kentucky 40299 Phone: 800-382-2872 Fax: 502-491-1739

For Office Use: TB31 | TT95 | GTGAdapter: Height:KCC-131147 16"

Old Model: YCD150D

New Model: YSK150

PRESSURE LOSS

NEW UNIT CFM INCHES OF H20

0.047

0.000

0.000

KCC curb adapters allow 1.5" (3/4" on every side) clearance around existing curb as shown. Any modification to KCC design will require extended lead times and result in additional engineering charges

The new and old curb prints are provided for dimensional verification only and do Not indicate new unit orientation.

KCC will Not be responsible for field clearance issues.