STAR_CENTER_CH-2_100%CD_MECH_08-08-2023_SS.pdf
PDF 6 MB Posted
- Attached to
- STAR Center Chiller 2 Replacement
- Solicitation number
- 23-1128-ITB-C
- Issued by
- Pinellas County, Florida
About this file
The document is a comprehensive mechanical design and replacement plan for Chiller #2 at the Young-Rainey STAR Center in Largo, Florida, prepared by Brady & Anglin Consulting Engineers of Florida, Inc. The project involves replacing an existing failed chiller with a new 900-ton water-cooled chiller, critical to maintaining the central energy plant's operations and providing air conditioning services to STAR Center tenants. The design set includes multiple technical drawings dated July 14, 2023, covering demolition plans, new mechanical layouts, control system integration, and detailed specifications for the chiller replacement.
The replacement chiller is a Carrier model 19XRV7274C09VHE64 with specific performance requirements, including a variable frequency drive (VFD), BACnet communication capabilities, and compliance with ASHRAE 90.1 standards. The project includes provisions for integrating the new chiller with the existing Trane Summit control system, extending control points, and capturing existing control wiring. The contractor is required to provide breakout pricing for control point integration and will need to ensure compatibility with the existing infrastructure. The specification includes detailed warranty terms, with first-year comprehensive coverage and an extended 10-year warranty on parts, refrigerant, and labor, along with provisions for annual maintenance and preventative service visits.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
100% CONSTRUCTION DOCUMENTS
LIST OF DRAWINGS
JULY 14, 2023
GENERAL
G0.1 COVER SHEET
MECHANICAL
ELECTRICAL
SITE
LOCAL MAP
YOUNG-RAINEY STAR CENTER
CHILLER #2 REPLACEMENT
LARGO, FL 33777
PROJECT TEAM
MECHANICAL, ELECTRICAL, PLUMBING
BRADY & ANGLIN
CONSULTING ENGINEERS
OF FLORIDA, INC.
2713 N. FALKENBURG ROAD SUITE "B"
TAMPA, FLORIDA 33619M1.1 FIRST FLOOR PLAN DEMOLITION - MECHANICAL
M2.1 FIRST FLOOR PLAN NEW - MECHANICAL
M3.1 NOTES, SCHEDULES & DETAILS - MECHANICAL
M4.1 CONTROLS - MECHANICAL
E1.1 FIRST FLOOR PLAN DEMOLITION - ELECTRICAL
E2.1 FIRST FLOOR PLAN NEW - ELECTRICAL
YOUNG-RAINEY STAR CENTER
7887 BRYAN DAIRY ROAD
LARGO, FL 33777
CODE REFERENCES
- FLORIDA BUILDING CODE - BUILDING - SEVENTH EDITION (2020)
- FLORIDA BUILDING CODE - MECHANICAL - SEVENTH EDITION (2020)
- FLORIDA BUILDING CODE - PLUMBING - SEVENTH EDITION (2020)
- FLORIDA BUILDING CODE - ENERGY CONSERVATION - SEVENTH EDITION (2020)
- NATIONAL ELECTRIC CODE - 70-2017
- NATIONAL FIRE ALARM AND SIGNALING CODE - 72-16
GENERAL NOTE
CONTRACTOR TO PROVIDE BREAKOUT PRICING FOR EXTENDING EXISTING
AND NEW CONTROL POINTS FOR THE INTEGRATION OF NEW CHILLER #2 TO
EXISTING TRANE CONTROLS IN THEIR BID. REFER TO MECHANICAL
SPECIFICATIONS AND MECHANICAL SHEET M4.1
BLDG. 500
AREA OF WORK
N.T.S.
B rya n D air y R oa d La rg o, Flo rid a 3
Yo un g- Ra ine y S tar C en ter
Ch ille r # 2 R ep lac em en t
Drawing Date:
Revisions:
Dr aw ing P ath
St aff
Ar ch ite ct:
Pr oje ct Nu mb er
Sc ale
TH
IS
D
R
AW
IN
G
IS
T
H E
PR
O
PE
R
TY
O
F
BR
AD
Y
AN
G
LI
N
AN
D M
AY
N
O T
BE
R
EP
R
O D
U C
ED
O
R U
SE
D
W
IT
H O
U T
W R
IT
TE
N
PE
R M
IS
SI
O N
07.14.2023
0.1G
Cover Sheet
SC
O
TT
A
. W R
U C
H A
N o.
Th is ite m ha s b ee n d igi tal ly sig ne d a nd se ale d b y S co tt
A.
W ru ch a on th e d ate ad jac en t to th e s ea
l. P rin ted co pie s of thi s d oc um en t a re no t c on sid er ed si gn ed an d s ea led an d t he si gn atu re m us t b e v er ifie d o n a ny el ec tro nic co pie s.
AutoCAD SHX Text N
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text N
AutoCAD SHX Text Phone (813) 621-2000
AutoCAD SHX Text Brady & Anglin
AutoCAD SHX Text Consulting Engineers
AutoCAD SHX Text of Florida, Inc.
AutoCAD SHX Text Business No. 4794
AutoCAD SHX Text 2713 N. Falkenburg Road. Suite 'B' Tampa, Florida 33619
G
EN
ER
AT
O R
G
EN
ER
AT
O R
G
EN
ER
AT
O R
STORAGE CAGE
E
MEZZANINE
GE
NE
RA
TO
R
AR
EA
MAIN FLOOR
COMPRESSOR AREA
SCALE: 1/4" = 1'-0"
DEMOLITION NOTES
REFURBISH/MODIFY EXISTING CONCRETE PAD AS REQUIRED TO
ACCOMMODATE NEW CHILLED WATER PUMP.
EXISTING MANUAL ISOLATION VALVE.
EXISTING CHWR
EXISTING CHWS
OVERHEAD PIPING
SHOWN OFFSET FOR
CLARITY
12"Ø CWS
12"Ø CWR
12"Ø CWR
12"Ø CWS
NEW LOCATION FOR
NEW CHILLER #2
EXISTING CHILLER #3
EXISTING CHILLER #2 SHALL
BE ABANDONED
EL
EC
TR
IC
P
G
EN
ER
AT
O R
G
EN
ER
AT
O R
G
EN
ER
AT
O R
WOMAN'S
MEN'S
STORAGE
COMMUNICATION
STORAGE CAGE
STORAGE CAGE
STORAGE CAGE
STORAGE CAGE
MEZZANINE
OFFICE
STORAGE AREA
ELECTRICAL ROOM 1ST
FLRGE
NE
RA
TO
R
AR
EA
BREAK ROOM
STORAGE
OFFICE
MAIN FLOOR
MAIN FLOOR
SHEDSHED
COMPRESSOR AREA
CONC. PADCONC. PAD
SCALE: N.T.S.
SCOPE OF WORK AREA
EXISTING CHILLER #4
B rya n D air y R oa d La rg o, Flo rid a 3
Yo un g- Ra ine y S tar C en ter
Ch ille r # 2 R ep lac em en t
Drawing Date:
Revisions:
Dr aw ing P ath
St aff
Ar ch ite ct:
Pr oje ct Nu mb er
Sc ale
TH
IS
D
R
AW
IN
G
IS
T
H E
PR
O
PE
R
TY
O
F
BR
AD
Y
AN
G
LI
N
AN
D M
AY
N
O T
BE
R
EP
R
O D
U C
ED
O
R U
SE
D
W
IT
H O
U T
W R
IT
TE
N
PE
R M
IS
SI
O N
07.14.2023
SC
O
TT
A
. W R
U C
H A
N o.
Th is ite m ha s b ee n d igi tal ly sig ne d a nd se ale d b y S co tt
A.
W ru ch a on th e d ate ad jac en t to th e s ea
l. P rin ted co pie s of thi s d oc um en t a re no t c on sid er ed si gn ed an d s ea led an d t he si gn atu re m us t b e v er ifie d o n a ny el ec tro nic co pie s.
1.1M
Demolition - Mechanical First Floor Plan
AutoCAD SHX Text
FIRST FLOOR PLAN DEMOLITION - MECHANICAL
AutoCAD SHX Text N
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
KEYPLAN
AutoCAD SHX Text Phone (813) 621-2000
AutoCAD SHX Text Brady & Anglin
AutoCAD SHX Text Consulting Engineers
AutoCAD SHX Text of Florida, Inc.
AutoCAD SHX Text Business No. 4794
G
EN
ER
AT
O R
G
EN
ER
AT
O R
G
EN
ER
AT
O R
STORAGE CAGE
E
MEZZANINE
GE
NE
RA
TO
R
AR
EA
MAIN FLOOR
COMPRESSOR AREA
SCALE: 1/4" = 1'-0"
MECHANICAL NOTES
EXISTING SUPPORT FOR OVERHEAD PIPING.
CONNECT REFRIGERANT RELIEF VALVE(S) TO NEW 3-1/2"Ø REFRIGERANT
VENT PIPING. TERMINATE 3-1/2"Ø REFRIGERANT VENT PIPING AT EXTERIOR
WALL AND TURN DOWN OPEN ENDED. PROVIDE PIPE SUPPORTS AS
REQUIRED.
PROVIDE WEATHERTIGHT SEAL AROUND ALL NEW PIPING PENETRATIONS
THROUGH EXTERIOR WALL.
PROVIDE NEW Y-STRAINER IN PIPE RISE. PROVIDE NEW 12"Ø CWS PIPING
FROM OUTLET OF NEW STRAINER TO CHILLER CONDENSER INLET.
EXTEND NEW 10"Ø CHWS PIPING TO CHILLER OUTLET.
EXISTING ISOLATION VALVE.
NEW MOTORIZED CONTROL VALVE IN 12"Ø CONDENSER WATER RETURN
PIPING.
PROVIDE NEW SUCTION DIFFUSER WITH INTEGRAL STRAINER ON SUCTION
SIDE OF CHILLED WATER PUMP.
MODIFY EXISTING 4-1/2" THICK CONCRETE PAD AS REQUIRED TO
ACCOMMODATE NEW CHILLER FOOTPRINT.
PROVIDE NEW ISOLATION VALVE.
PROVIDE NEW MOTORIZED ISOLATION VALVE IN CHILLED WATER SUPPLY
PIPING (IN PIPE RISE AHEAD OF NEW MANUAL ISOLATION VALVE).
REFURBISH/MODIFY EXISTING CONCRETE PAD AS REQUIRED TO
ACCOMMODATE NEW CHILLED WATER PUMP.
EXISTING CHILLER PLANT EXHAUST FAN SHALL REMAIN.
PROVIDE NEW CHILLED WATER FLOW METER LOCATED IN VERTICAL PIPE
RISE. INTERFACE WITH EXISTING HVAC CONTROL SYSTEM.
EXTEND NEW 10"Ø CHWR PIPING THROUGH EXTERIOR WALL TO CHILLER
INLET. UTILIZE EXISTING WALL PENETRATION.
EXISTING CONTROL WIRING ASSOCIATED WITH ABANDONED CHILLER SHALL
BE CAPTURED AND EXTENDED TO NEW CHILLER #2 LOCATION.
EXISTING HONEYWELL REFRIGERANT MONITOR (MODEL 301C) AND
EXPANSION MODULES.
NEW R-134A REFRIGERANT SENSOR(S) SHALL INTERFACE WITH EXISTING
HONEYWELL REFRIGERANT MONITORING SYSTEM CONTROLLER (MODEL
301C).
10"Ø CHWR
10"Ø CHWR
EXISTING
CHWS&R
PCHP
CH
SUCTION DIFFUSER
WITH INTEGRAL
STRAINER
EXISTING CONCRETE
PUMP PAD
EXTERIOR WALL
SCALE: 1/4" = 1'-0"
12"Ø CWS (EX.)
12"Ø CWR (EX.)
12"Ø CWR (EX.)
12"Ø CWS (EX.)
"Ø
C H
W R
PCHP
EXISTING CHWR
EXISTING CHWS
OVERHEAD PIPING
SHOWN OFFSET FOR
CLARITY
10"Ø CHWR
OVERHEAD PIPING
SHOWN OFFSET FOR
CLARITY
10"Ø
CHWS
12"Ø CWS
12"Ø CWR
"Ø
C H
W R
10"Ø CHWS
12"Ø CWR (EX.) 12"Ø CWS (EX.)
3-1/2"Ø REFRIGERANT
VENT PIPING
3-1/2"Ø REFRIGERANT
VENT PIPING
12"Ø CWS
"Ø
C W
R 7
CH
EXISTING CHILLER #3
EXISTING CHILLER #2 SHALL
BE ABANDONED
EL
EC
TR
IC
P
G
EN
ER
AT
O R
G
EN
ER
AT
O R
G
EN
ER
AT
O R
WOMAN'S
MEN'S
STORAGE
COMMUNICATION
STORAGE CAGE
STORAGE CAGE
STORAGE CAGE
STORAGE CAGE
MEZZANINE
OFFICE
STORAGE AREA
ELECTRICAL ROOM 1ST
FLRGE
NE
RA
TO
R
AR
EA
BREAK ROOM
STORAGE
OFFICE
MAIN FLOOR
MAIN FLOOR
SHEDSHED
COMPRESSOR AREA
CONC. PADCONC. PAD
SCALE: N.T.S.
SCOPE OF WORK AREA
EXISTING CHILLER #4
B rya n D air y R oa d La rg o, Flo rid a 3
Yo un g- Ra ine y S tar C en ter
Ch ille r # 2 R ep lac em en t
Drawing Date:
Revisions:
Dr aw ing P ath
St aff
Ar ch ite ct:
Pr oje ct Nu mb er
Sc ale
TH
IS
D
R
AW
IN
G
IS
T
H E
PR
O
PE
R
TY
O
F
BR
AD
Y
AN
G
LI
N
AN
D M
AY
N
O T
BE
R
EP
R
O D
U C
ED
O
R U
SE
D
W
IT
H O
U T
W R
IT
TE
N
PE
R M
IS
SI
O N
07.14.2023
SC
O
TT
A
. W R
U C
H A
N o.
Th is ite m ha s b ee n d igi tal ly sig ne d a nd se ale d b y S co tt
A.
W ru ch a on th e d ate ad jac en t to th e s ea
l. P rin ted co pie s of thi s d oc um en t a re no t c on sid er ed si gn ed an d s ea led an d t he si gn atu re m us t b e v er ifie d o n a ny el ec tro nic co pie s.
2.1M
New - Mechanical First Floor Plan
AutoCAD SHX Text N
AutoCAD SHX Text
CHILLER ELEVATION
AutoCAD SHX Text
FIRST FLOOR PLAN NEW - MECHANICAL
AutoCAD SHX Text
COND.
AutoCAD SHX Text
COND.
AutoCAD SHX Text
COOLER
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
KEYPLAN
AutoCAD SHX Text Phone (813) 621-2000
AutoCAD SHX Text Brady & Anglin
AutoCAD SHX Text Consulting Engineers
AutoCAD SHX Text of Florida, Inc.
AutoCAD SHX Text Business No. 4794
CHWS & CHWR
AFF
MECHANICAL LEGEND
EXIST. EXISTING
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
CONDENSER WATER SUPPLY AND RETURNCS & CR
CHILLED WATER SUPPLY AND RETURN
ABOVE FINISHED FLOOR
CONNECTION POINT OF NEW TO EXISTING
SHUT-OFF VALVE
EXISTING TO BE REMOVED
PROVIDE SINGLE POINT 460/3PH POWER TO CHILLER.
PROVIDE VFD DRIVEN, DIRECT DRIVE MULTIPLE-STAGE COMPRESSOR,
MULTI-STAGE CAPACITY CONTROL GUIDE VANES.
PROVIDE WITH BACNET MSTP COMMUNICATION CAPABILITY (UPC OPEN) WITH
MICROPROCESSOR BASED (DDC) CHILLER CONTROL SYSTEM THAT PROVIDES
COMPLETE STAND ALONE SYSTEM CONTROL AND MONITORING.
PROVIDE WITH UNIT MOUNTED VFD STARTER.
PROVIDE VFD ENCLOSURE WITH 65K SCCR (SHORT CIRCUIT CURRENT RATED)
ENCLOSURE. THE VFD TOTAL HARMONIC DISTORTION (THD) AND HARMONIC
CURRENT TOTAL DEMAND DISTORTION (TDD) SHALL NOT EXCEED IEEE-519
REQUIREMENTS.
PROVIDE 0.75" CLOSED CELL FOAM INSULATION ON EVAPORATOR SHELL,
SUCTION PIPING, COMPRESSOR INLET, MOTOR BARREL AND EVAPORATOR
CONNECTION HEADS.
PROVIDE SURGE PROTECTION, PHASE LOSS, REVERSAL, AND UNBALANCE
PROTECTION, UNDER VOLTAGE AND OVER VOLTAGE PROTECTION.
10.4" COLOR LCD, TOUCH-SCREEN PANEL.
PROVIDE RUBBER-IN-SHEAR 3/8" THICK NEOPRENE RIBBED ISOLATION.
FACTORY INSTALLED WATER FLOW PROVING SENSORS IN CONDENSER AND
EVAPORATOR NOZZLES.
PROVIDE VFD WITH DOOR-MOUNTED CIRCUIT BREAKER/SHUNT TRIP WITH AIC
RATING OF 65,000 AMPS.
CHILLER PERFORMANCE SHALL MEET ASHRAE 90.1.
PROVIDE CHILLER PERFORMANCE DATA CERTIFIED IN ACCORDANCE WITH AHRI
550/590 AND AHRI STANDARD 575 SOUND DATA.
PROVIDE WITH FIRST YEAR PARTS, REFRIGERANT AND LABOR FROM DATE OF
START-UP, NOT TO EXCEED EIGHTEEN (18) MONTHS FROM DATE OF SHIPMENT.
PROVIDE 2ND THROUGH 10TH YEAR COMPLETE UNIT WARRANTY INCLUDING
PARTS, REFRIGERANT AND LABOR WARRANTY FROM DATE OF EQUIPMENT
START-UP NOT TO EXCEED ONE HUNDRED TWENTY-SIX (126) MONTHS FROM
DATE OF SHIPMENT.
WATER SIDE OF CONDENSER VESSEL AND EVAPORATOR VESSEL DESIGN
PRESSURE IS 150 PSI.
PROVIDE R-134A REFRIGERANT SENSOR(S). SENSOR SHALL INTERFACE WITH
EXISTING HONEYWELL REFRIGERANT MONITORING SYSTEM CONTROLLER
(MODEL 301C).
10 YEAR PREVENTATIVE MAINTENANCE - PROVIDE SERVICE FOR (1) ANNUAL
COMPREHENSIVE VISIT, (3) QUARTERLY VISITS AND CONDENSER TUBE
CLEANING. PROVIDE BASE LINE EDDY CURRENT TEST BEFORE START-UP.
PROVIDE MARINE WATER BOX ON CONDENSER AND STANDARD WATER BOX ON
EVAPORATOR. COORDINATE FINAL PIPING CONNECTIONS/ORIENTATION WITH
CONTRACTOR.
PRE-APPROVED SUBSTITUTES: TRANE, DAIKIN & YORK. PROPOSED CHILLER
SUBSTITUTES SHALL NOT REQUIRE ANY STRUCTURAL MODIFICATIONS TO
EXISTING SUPPORTS LOCATED ADJACENT TO THE CHILLER IN ORDER TO AVOID
CONFLICTS. IF A PRE-APPROVED CHILLER SUBSTITUTE IS PROPOSED AND ANY
ADDITIONAL STRUCTURAL, PIPING AND/OR ELECTRICAL MODIFICATIONS ARE
REQUIRED, THE CONTRACTOR SHALL INCLUDE THOSE COSTS ASSOCIATED WITH
THE SUBSTITUTE CHILLER IN THEIR BID.
PERFORMANCE VERIFICATION VIA TEAMS. REFER TO SPECIFICATIONS.
NOTES:
1.
2.
3.
4.
5.
6.
MAXIMUM PRESSURE DROP
TOTAL POWER INPUT @ RATED CAPACITY
REFRIGERANT
ELECTRICAL CHARACTERISTICS
WATER TEMPERATURE, ENT/LVG
EFFICIENCY
NPLV
OPERATING WEIGHT
NOTES
REFRIGERANT CHARGE
UNIT LOCATION
25% LOAD
100% LOAD
75% LOAD
50% LOAD
LBS.
LBS
KW/TON
KW/TON
KW/TON
KW/TON
KW @ FL
KW/TON
V/Ø/HZ
°F
MARK
CAPACITY
WATER TEMPERATURE, ENT/LVG
WATER FLOW
MAXIMUM WATER PRESSURE DROP
WATER FLOW
MODEL NUMBER
MANUFACTURER
EVAPORATOR
CONDENSER
GPM
°F
GPM
TONS
7.
8.
9.
10.
11.
CH-2
CARRIER
19XRV7274C09VHE64
14.1
55/43
15.3
85/94.3
R-134A
460/3/60
487.6
0.5417
0.3515
47080
CHILLER ROOM
1-21
12.
13.
14.
NOTES
1.
2.
3.
PROVIDE PREMIUM EFFICIENCY MOTORS AND MECHANICAL SEALS.
FURNISH WITH EPDM COUPLER SLEEVE.
PROVIDE SERVICE DISCONNECTS BY ELECTRICAL (DIVISION 16) CONTRACTOR
IN NEMA 4 NON-METALIC ENCLOSURE OR 304 STAINLESS STEEL ENCLOSURE
WITH 24 VOLT CONTROL TRANSFORMER, H.A.O. SWITCH. COMBINATION
MOTOR STARTER / DISCONNECT BY DIV 16. SEE ELECTRICAL SHEET E2.1
PUMPS MUST BE SUITABLE FOR OUTDOOR INSTALLATION AND OPERATION.
SUITABLE FOR CASE WORKING PRESSURE OF 175 PSI. (ANSI CLASS 150).
FTNPSHR
PUMP TYPE
SYSTEM
MARK
MANUFACTURER
MODEL NUMBER
TOTAL DYNAMIC HEAD
SUCTION SIZE
DISCHARGE SIZE
GPM
V/Ø/HZ
LBS.
INCHES
MINIMUM PUMP EFFICIENCY %
FT
RPM
HP
WATER FLOW RATE
IMPELLER SIZE (DIAMETER)
LXWXH
NOTES #
INCHES
INCHES
VFD (YES/NO) -
ELECTRICAL CHARACTERISTICS
MOTOR SIZE
MOTOR SPEED
DIMENSIONS (INCHES)
OPERATING WEIGHT
-LOCATION
15.
CHILLER DIMENSIONS L X W X H 212"X101"X125"
16.
4.
5.
N.T.S. (CENTRIFUGAL LIQUID CHILLER)
PROVIDE ALL PIPING
NECESSARY TO MANIFOLD
RELIEF PIPING CONNECTIONS
AS DICTATED BY CHILLER
MANUFACTURER.
1/4"FL X 1/4"NPT CAPPED.
DRAIN VALVE
DRIP LEG MIN./ 1 GAL.
CAPACITY. EXTEND PAST
CHILLER TO PREVENT SPILLAGE
ONTO CHILLER.
REFRIG. RELIEF PIPE
TO OUTSIDE OF BLDG.
CONDENSER
WATER SUPPLY &
RETURN
NOTE: PROVIDE OIL COOLER PIPING AS
DIRECTED BY CHILLER MANUFACTURER
EXISTING 4.5" HIGH CONCRETE
HOUSEKEEPING PADVIBRATION ISOLATORS
(NUMBER AS RECOMMENDED
BY CHILLER MANUF.)
FLEXIBLE STEEL
CONNECTION
RUPTURE DISC
ASSEMBLY
EXTERIOR
CHILLED WATER
SUPPLY &
RETURN
N.T.S.
NOTES:
N.T.S.
SEPERABLE HALVES
SPLIT CASE PUMPS SHALL BE ENCASED IN ELASTOMERIC FOAM INSULATION
WHICH CAN BE REMOVED AND REUSED. BOX FRAME IS CONSTRUCTED OF LIGHT
GAUGE METAL TO WHICH ELASTOMERIC INSULATION IS APPLIED.
MATERIALS: METAL ANGLES, ELASTOMERIC INSULATION AND ADHESIVE.
PUMP
ELASTOMERIC FOAM INSULATION CUT TO FIT METAL FRAME WITH CUT-OUTS
METAL FRAME CONSTRUCTED TO FIT BASE OF PUMP
REMOVABLE TOP SHALL BE CONSTRUCTED ON A FRAME AND FOAM FITTED AS
SHOWN.
STAINLESS STEEL LATCH. (TYPICAL OF BOTH ENDS)
16.7
8.375
PCHP-2
CHILLED WATER
460/3/60
NO
69X26X33
80.2
OUTSIDE
E-HSC 8X10X9.5
B&G
HORIZONTAL
SPLIT CASE
1-5
EXISTING CONCRETE PAD
(19.75" HEIGHT)
PIPE STANCHION (TYPICAL)
FINISHED GRADE
ISOLATION VALVE
(TYPICAL)
17.
18.
STRAINER PULL AREA
SUCTION DIFFUSER
N.T.S.
PIPE SADDLE 12" LONG AT EACH SUPPORT
NEOPRENE BETWEEN PAD & BASE (TYPICAL)
BOLT BASE PLATE TO PAD AT EACH CORNER
PIPE
PIPE INSULATION
PIPE SUPPORT ADJUSTER (GALV.)
THREADED BASE STAND (HOT DIPPED GALV.)
CONCRETE PAD
MOTOR AMPS AMPS 746.6
MIN. CIRCUIT AMPACITY AMPS 797
MAX OVERCURRENT PROTECTION AMPS 1200
0.4161
0.2984
0.3877
19.
20.
EXISTING CONDITIONS AT NEW
CHILLER #2 LOCATION
(FOR REFERENCE)
CL
CONNECT TO
STRUCTURE
OF PIPE
N.T.S.
HEAVY DUTY
CLEVIS HANGER
SUPPORT LOCK
NUT
LOCK NUT
THREADED
HANGER ROD
EXISTING CONDITIONS AT
CHILLED WATER PUMP LOCATION
(FOR REFERENCE)
21.
FT. H2O
FT. H2O
B rya n D air y R oa d La rg o, Flo rid a 3
Yo un g- Ra ine y S tar C en ter
Ch ille r # 2 R ep lac em en t
Drawing Date:
Revisions:
Dr aw ing P ath
St aff
Ar ch ite ct:
Pr oje ct Nu mb er
Sc ale
TH
IS
D
R
AW
IN
G
IS
T
H E
PR
O
PE
R
TY
O
F
BR
AD
Y
AN
G
LI
N
AN
D M
AY
N
O T
BE
R
EP
R
O D
U C
ED
O
R U
SE
D
W
IT
H O
U T
W R
IT
TE
N
PE
R M
IS
SI
O N
07.14.2023
SC
O
TT
A
. W R
U C
H A
N o.
Th is ite m ha s b ee n d igi tal ly sig ne d a nd se ale d b y S co tt
A.
W ru ch a on th e d ate ad jac en t to th e s ea
l. P rin ted co pie s of thi s d oc um en t a re no t c on sid er ed si gn ed an d s ea led an d t he si gn atu re m us t b e v er ifie d o n a ny el ec tro nic co pie s.
3.1M
Mechanical Legend, Schedules & Details
AutoCAD SHX Text
CHILLER SCHEDULE
AutoCAD SHX Text
WATER COOLED CENTRIFUGAL
AutoCAD SHX Text
PUMP SCHEDULE
AutoCAD SHX Text
TYPICAL WATER COOLED CHILLER PIPING DIAGRAM
AutoCAD SHX Text
FS
AutoCAD SHX Text
FS
AutoCAD SHX Text
WALL
AutoCAD SHX Text
IN
AutoCAD SHX Text
TYPICAL HORIZONTAL SPLIT CASE PUMP PIPING DIAGRAM
AutoCAD SHX Text
TYPICAL SPLIT CASE PUMP - INSULATION COVER
AutoCAD SHX Text
PIPE STAND DETAIL
AutoCAD SHX Text
PIPE SUPPORT DETAIL
AutoCAD SHX Text Phone (813) 621-2000
AutoCAD SHX Text Brady & Anglin
AutoCAD SHX Text Consulting Engineers
AutoCAD SHX Text of Florida, Inc.
AutoCAD SHX Text Business No. 4794
DO
SS
AO
WR
AI
PF
DO
SS
AO
VM
FS
FS
T
AI
PF
DP
AI
PF
T
AI
PF
T
AI
PF
T
AI
PF
CH-2 (NEW)
900 TONS
1798 CHW GPM (55/43)
2671 CW GPM (85/94.3)
10"Ø CHWS (EX.)
"Ø
C H
W R
PCHP-2 (NEW)
30 HP
1798 GPM
10"Ø 10"Ø
SUCTION DIFFUSER/INTEGRAL
STRAINER WITH BLOW DOWN
AND VALVE
DI
FF
DO
SS
CT
PROPORTIONAL FEEDBACKPF
TEMPERATURE SENSOR
FLOW METER
DIFFERENTIAL PRESSURE TRANSMITTER
FLOW SWITCH
CHILLED WATER RESET
VALVE MODULATION
START/STOP
VM
SS
DIGITAL OUT
ANALOG IN
DIGITAL IN
CONTROLS LEGEND
DO
AI
AO
DI
ANALOG OUT
NOTE: NOT ALL SYMBOLS USED
WR
FS
FM
DP
T
CURRENT TRANSMITTERCT
AIR MONITORAM
MOTORIZED DAMPERM
FM
AI
PF
NEW STRAINER
12"Ø CWS (EX.)
12"Ø CWR (EX.)
CHILLER MANUFACTURER SHALL PROVIDE A THERMAL
DISPERSION-TYPE FLOW SWITCH (FACTORY INSTALLED
AND WIRED TO CHILLER CONTROL PANEL).
FLOW DIAGRAM NOTES
SEQUENCE OF OPERATION
WATER COOLED CHILLER(S) SYSTEM CONTROL
CHILLER SHALL BE CONTROLLED BY THE EXISTING CHILLER PLANT TRANE SUMMIT
CONTROL SYSTEM OR IN A STAND ALONE MODE VIA THE MICROPROCESSOR BASED CHILLER
CONTROL PANEL.
THE CHILLER SHALL RECEIVE ENABLE/DISABLE SIGNALS EITHER THROUGH A COMMAND VIA A
COMMUNICATION LINK OR VIA A HARDWIRED BINARY INPUT.
A CHILLER BINARY OUTPUT SHALL CONTROL THE OPERATION OF THE CHILLER EVAPORATOR
ISOLATION VALVE AND/OR CALL FOR PUMP OPERATION.
INITIAL SYSTEM START-UP - UPON A CALL FOR CHILLED WATER THE CHILLER SYSTEM CONTROL
SHALL:
1. SEND AN ENABLE SIGNAL TO THE LEAD CHILLER.
2. UPON RECEIVING THE ENABLE SIGNAL THE CHILLER SHALL ENABLE THE CHILLER EVAPORATOR
ISOLATION VALVE AND CALL FOR THE LEAD CHILLED WATER PUMP OPERATION VIA A BINARY
OUTPUT.
3. UPON CONFIRMATION OF EVAPORATOR FLOW, THE CHILLER SHALL ENABLE THE CONDENSER
ISOLATION VALVE TO OPEN. PLANT SHALL ENABLE / DISABLE CONDENSER PUMP BASED ON
NUMBER OF CHILLERS OPERATING (EXISTING SEQUENCE).
4. AFTER WATER FLOW HAS BEEN CONFIRMED, THE CHILLER SHALL START AND OPERATE VIA ITS
OWN CONTROL SYSTEM TO MAINTAIN CHILLED WATER SUPPLY TEMPERATURE OF 43° F
(ADJUSTABLE).
5. THE CHILLER CONTROLLER PANEL SHALL NOT SHUT DOWN IT'S PRIMARY PUMP UNTIL ALL
CHILLER COMPRESSORS ARE PROVEN OFF.
NOTE: ALL OF THE EXISTING CHILLERS AND ASSOCIATED PUMPS SEQUENCING IS
EXISTING ON THE TRANE SUMMIT SYSTEM EXCEPT ANYTHING THAT IS CHANGED DUE TO
RELOCATION AND / OR ADDITIONAL VALVES / SENSORS ADDED FOR THIS PROJECT.
NTS
10"Ø CHWS
NOTES TO CONTRACTOR
NEW HVAC EQUIPMENT SHALL INTERFACE WITH EXISTING BUILDING
AUTOMATION SYSTEM - TRANE SUMMIT. PROVIDE ALL CONTROL SYSTEM
COMPONENTS (I.E. WIRING, HARDWARE, SOFTWARE, GRAPHICS, ETC.)
NECESSARY FOR NEW EQUIPMENT AND CONTROL DEVICES.
CONTRACTOR SHALL UTILIZE AVAILABLE EXISTING CONTROL POINTS
ASSOCIATED WITH ABANDONED CHILLER #2. CAPTURE AND EXTEND ALL
EXISTING CONTROL WIRING FROM ABANDONED CHILLER #2 TO NEW CHILLER
#2 LOCATION.
PROVIDE ALL NEW SENSORS, CHILLED WATER AND CONDENSER WATER
ISOLATION VALVE, ETC.
PROVIDE SEPARATE LINE ITEM COST FOR ALL HVAC CONTROL SCOPE OF
WORK. THIS COST WILL BE INCLUDED IN THE TOTAL BID.
1.
2.
3.
4.
CHILLER #2 CONTROL POINTS (EXISTING)
AI AO DI DO
CHW FLOW CHW SUPPLY SETPOINT CHW FEED PUMP 2 STATUS AVAILABLE
CHW RET TEMP KILOWATTS FLOW CW STATUS START/STOP
CHW SUP TEMP FLOW CHW STATUS CONDENSER WATER FLUSH
ACTIVE TONS PURGE RUNNING CONDENSER WATER ISOLATION VALVE
CURRENT DRAW ACTIVE MODE
KW PER TON PRESENT VALUE OCCU/UNOCCUPIED
CHILLER RUNTIME MANUAL RESET REQUIRED?
CW ENT TEMP AUTOMATIC RESET OCCURRED?
CW LEAV TEMP
CHILLER STARTS
KILOWATTS
CHILLER VFD%
INFO WARNING
NEW CHILLER #2 CONTROL POINTS (NEW)
AI AO DI DO
CHILLED WATER ISOLATION VALVE
NOTES
1. UTILIZE ALL EXISTING TRANE CONTROL POINTS PROGRAMMING FOR ABANDONED CH#2 AND APPLY TO NEW CH#2.
2. CAPTURE AND EXTEND ALL EXISTING CONTROL WIRING FROM ABANDONED CH#2 TO NEW CH#2 LOCATION ADJACENT TO IT.
3. PROVIDE ALL NEW SENSORS, CHW ISOLATION VALVE, CW ISOLATION VALVE, ETC. SEE SPECIFICATIONS.
B rya n D air y R oa d La rg o, Flo rid a 3
Yo un g- Ra ine y S tar C en ter
Ch ille r # 2 R ep lac em en t
Drawing Date:
Revisions:
Dr aw ing P ath
St aff
Ar ch ite ct:
Pr oje ct Nu mb er
Sc ale
TH
IS
D
R
AW
IN
G
IS
T
H E
PR
O
PE
R
TY
O
F
BR
AD
Y
AN
G
LI
N
AN
D M
AY
N
O T
BE
R
EP
R
O D
U C
ED
O
R U
SE
D
W
IT
H O
U T
W R
IT
TE
N
PE
R M
IS
SI
O N
07.14.2023
SC
O
TT
A
. W R
U C
H A
N o.
Th is ite m ha s b ee n d igi tal ly sig ne d a nd se ale d b y S co tt
A.
W ru ch a on th e d ate ad jac en t to th e s ea
l. P rin ted co pie s of thi s d oc um en t a re no t c on sid er ed si gn ed an d s ea led an d t he si gn atu re m us t b e v er ifie d o n a ny el ec tro nic co pie s.
4.1M
Mechanical Controls
AutoCAD SHX Text
CHILLER#2 - FLOW DIAGRAM
AutoCAD SHX Text Phone (813) 621-2000
AutoCAD SHX Text Brady & Anglin
AutoCAD SHX Text Consulting Engineers
AutoCAD SHX Text of Florida, Inc.
AutoCAD SHX Text Business No. 4794
| Sheets and Views |
| COVER SHEET-Layout1 |
| M1.1-Layout1 |
| M2.1-Layout1 |
| M3.1-Layout1 |
| M4.1-Layout1 |
| 2023-08-08T10:47:41-0400 | |