ST CLOUD VA BLDG. 51_103896_SET_B.pdf
PDF 493 KB Posted
- Attached to
- Y1DA--656-19-307 Remodel of Building 51-1, Eastside at the Saint Cloud VA, Saint Cloud, MN
- Solicitation number
- 36C26325B0007_0003
About this file
These technical drawings detail a ceiling lift system installation project for Room 111, Room 117, Room 124/125, and Room 127 at the St. Cloud VA Healthcare facility in Building 51. The documents specify precise installation requirements for Guldmann Inc. ceiling lift systems, including rail configurations, transformer specifications, and load capacities. Key technical specifications include system load testing at 1.5 times capacity (ranging from 825 lbs to 1650 lbs), electrical power requirements, and detailed mounting instructions for ceiling brackets and stabilizers.
The project documents outline critical installation notes, such as facility structure capacity requirements, electrical power source verification, and Guldmann's right to modify track layouts. The drawings provide comprehensive technical details for each room, including room dimensions, rail positioning, and specific installation guidelines. The project is identified with Project ID 103896, with recent revisions made in June 2024, including updates to backgrounds, top rail changes, and extended lift installations in specific rooms. The installation is part of a broader renovation of Building 51 at the St. Cloud VA Healthcare facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment B VAAR 852.219-75 Limitations on Subcontracting Cert of Compliance.pdf | ||
| 20250520_Bid Doc Addendum.pdf | ||
| 656-19-307_GI001.pdf | ||
| 36C26325B0007 0003.pdf | ||
| Bid questions B51-1 E AE VA.doc | DOC document | |
| Drawings.pdf | ||
| S04 - Site Visit Agenda 36C26325B0007 2.docx | DOCX document | |
| 20240823_STC-B51_CP_SpecVol2.pdf | ||
| Pre bid site visit sign in sheet.pdf | ||
| Volume 3 Specs.pdf | ||
| 20240823_STC-B51_CP_SpecVol1.pdf | ||
| Wage Determination Stearns MN20250099 05.02.2025.pdf | ||
| photos for bid questions B51-1.docx | DOCX document | |
| Bed.Lift.Detail.4.png | PNG image |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
SIGNOFF / APPROVAL NOTES
1. The facility structure capacity must be able to support the load specified on the installation drawing.
2. Electrical power source provided by the facility, position to be verified in the field.
3. Guldmann Inc. reserves the right to slightly modify the track layout if necessary without Facility approval.
This includes lowering the system to avoid ceiling objects.
4. Guldmann Inc. will not be held responsible for any damages, inconvenience, resulting from hitting any non visible conduits during our installation process of which we have not been advised.
5. Modifications of door headers by the facility.
6. Signed drawings are required prior to ordering and installation of ceiling lifts.
This signature of each drawing confirms agreement of all the conditions listed above.
7. Systems are tested at 1.5 times capacity.
550 lbs. tested at 825 lbs.; 770 lbs. tested at 1155 lbs.; 825 lbs. tested at 1238 lbs.; 1100 lbs. tested at 1650 lbs.
MY SIGNATURE BELOW VERIFIES THAT I HAVE:
Reviewed all _____ pages, with a total quantity of _____ room(s), _____ system(s) for the approbation of layout for each room and the approbation of structure for each room.
CUSTOMER
APPROVAL: _____________________________________ DATE: _______________
DATE: DRAWN BY:
ACCURATE TO 4" BASED
ON PDF CONVERSION
St. Cloud VA Healthcare St. Cloud VA Bldg. 51 L1 East
4801 Veteran Dr.
St. Cloud, MN 56303
PROJECT ID:103896
St. Cloud VA Bldg. 51 L1 East
FACILITY SIGNOFF
GUL101
MGE01/24/2024
8 5 5
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
CONCRETE BEAM
SPAN = 2' - 0"
Revision Schedule
Date Issued by Letter Description
06/02/2024 TRC A UPDATED BACKGROUNDS, MINOR ADJUSTMENTS TOP RAILS FOR WALL,DOOR
CHANGES
06/17/2024 MGE B EXTENDED LIFTS RM 111, RM 117, RM 127. UPDATED CHART. MATERIAL
EACH FIXED RAIL TO
HAVE x1 PARALLEL & x2 PERPENDICULAR
STABILIZERS
ALL JOINTS MUST HAVE x1 PARALLEL & x1
PERPENDICULAR STABILIZER
SEE SPAN CHART
S E
E S
P A
N C
H A
R T
SEE SPAN CHART
± 22°
STABILIZERS CAN BE ROTATED 180°
Fixed rail systems Fixed rail systems must be connected by Guldmann Service Team or by a qualified installer.
A Guldmann class I transformer must be used.
Installation to follow existing rules for authorized electricians and according to IEC/UL 60601-1.
Terminals on transformers Class I Double-insulated UL approved cable must be used (Cable specification: UL category: AVLV2, min.300V, min.
80° C, min. 18AWG (1 mm2 )) Transformer DK-13991 In:
Terminal 1 = N Terminal 2 = 100-115V AC Terminal 3 = 230V AC Terminal 4 = Protective ground Out:
Terminal 5 = 33V AC Terminal 6 = 33V AC
POWER TO BE WITHIN 15 FT OF END OF FIXED RAIL
Guldmann permanent mounted ceiling aluminium rail
Hoist with trolleys movable in rail
Protective Plast Enclosure
UL approved 400V cable, green, min. 14 AWG
Protective Ground
M1
UL approved 400V double isolated cable, min. 18 AWG
ON/OFF
UL approved 400V double isolated cable, min. 18 AWG
T ra n s fo rm e r
D K
-1
Main power Permanent installation Specification of breaker:
≥ 2.5 Amp capacity Line must always be broken
L1
AC/DC charger
Main Motor Control
Emergency Stop
Safety Circuit Emergency down
Motor Function Selector Switch0 1
V
A C
U
S
V
A C
P ro te c tiv e G ro u nd
V
A C
V
A C1 A
T
.5
A T
Green Light ON (or ON / OFF - sign)
Licensed Electrician to perform hardwire to transformer
B-RAIL
WEIGHT: 5.0 KG/M
(3.36 LBS/FT)
(2 1/2")
62 mm.
(5 m m
A
B
C
D
E
F
G
H
I
J
K
Ceiling bracket standard
A / B / C
Basic High M
Basic High M
Dimensions
205 mm
580 mm
345 mm
24 mm
58.5 / 125 / 170 mm
156 mm
184 mm
425 mm
2500 mm
970 mm
340 mm
8"
22.8"
13.5"
1.0"
2.2 / 4.9 / 6.6"
6.29"
7.2"
16.75"
98"
38"
13.3"
H
A
E D
F
C
G I
B
K J
SPRING PLATE
AVAILABLE FOR A & B RAIL
FLUSH CEILING PROFILE LIP IS 7/16" X 3/8"
CUT 12 - 15 MM OF THE 2 LONGITUDE
SCREW FOR
PROFILE END
LOAD LIMIT
KG LBS
CANTILEVER (SNGL)
MM INCHES
175 565 22 ¼
205 525 20 ½
255 485 19
275 485
300 455
350 445
375 425
400 425
SPAN (BETWEEN SUPPORTS)
MM INCHES
5500 215
5250 205
4750 186
4500 176
4000 157
3750 147
CANTILEVER (PAR)
MM INCHES
715 28
675 26 ½
635 25
630 24 ¾
605 23 ¾
595 23 ¼
SPAN CHART B-RAIL
16 ½
17 ¾
575 22 ½
22 ½16 ½
17 ¾
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
St. Cloud VA Bldg. 51 L1 East
GEN. INFO
GUL102
MGE01/24/2024
PROJECT ID:103896
NTS
BRACING + SUPPORT
NTS
GH3 TRANSFORMER
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
NTS
B-RAIL SPAN CHART / WEIGHT / DIMS
Revision Schedule
Date Issued by Number
06/02/2024 TRC A
06/17/2024 MGE B
CONCRETE BEAM
NTS
GH3 PATIENT SLING DIMS
SPAN = 2' - 0"
NTS
FLUSH CEILING PROFILE
40° T O 90°
0°
90°
1A B
8,9
DRAWINGS APPROVED FOR THE GULDMANN
GH-3 LIFTER SYSTEM STANDARD INSTALLATION
OF SUPPORT AND CONNECTION TO WAFFLE
DECK.
SYSTEMS INSTALLED FOR 770 POUNDS WILL BE
TESTED AT 1155 POUNDS.
V A
R
IE
S
M A
X
9,11
HVAC / MECH
BASEPLATE x4
STABILIZERS x3
STABILIZERS
± 22°
BRIDGE / RAIL TOP
BRIDGE SECTION
GULDMANN RAIL
SPAN
OPTIONAL B
DETAIL B
DETAIL A
OPTIONAL A
8,9
WAFFLE DECK / CONCRETE BEAM
DESCRIPTIONITEM NUMBERTAG
2-7/16" X 10' B2B STRUT SLOTTEDP5501-T1
3/8" B7 THREADED ROD1234602
STABILIZER BRACKET KIT - GULDMANN5504393
1" Ø-6013-T6 AL TUBE - GULDMANN550481-US4
CEILING BRACKET KIT - GULDMANN5504355
2 HOLE 90 DEG. BRACKETP10266
MQM-F WINGNUT 3/8"3778827
3/8" X 1-1/4" HEX BOLT4117648
3/8" X 1-1/4" X 1/8" WASHER (THICK)111012739
3/8" X 3-3/4" KB-TZ2 ANCHOR223145610
3/8" NYLOCK NUT113702411
3/8" BEVELLED WASHER3387312
3/8" HEX NUT41175213
MQZ-L BASEPLATE 3/8"37063214
MQA-F SADDLE NUT 3/8"37788515
( USED AS NEEDED )
( OPTIONAL )
MIN EMBEDMENT OF 2"
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS
St. Cloud VA Bldg. 51 L1 East
ATTACHMENT
GUL103
MGE01/24/2024
PROJECT ID:103896
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
Revision Schedule
Date Issued by Number
06/02/2024 TRC A
CONCRETE BEAM
SPAN = 2' - 0"
GUL104
GUL104
/8
B .O
H
O
IS
T
/2
B .O
T
R A
V E
R S
E /L
IN
E
A R
R A
IL
C E
IL
IN
G
/8
B .O
C
O M
B I G
A T
E
/2
/8
17" MAX
/8
8" MIN
COMBI-BRACE
/2
/8
/4
/2
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS
St. Cloud VA Bldg. 51 L1 East
PROJECT DETAILS
GUL104
MGE01/24/2024
PROJECT ID:103896
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
Revision Schedule
Date Issued by Number
06/02/2024 TRC A
CONCRETE BEAM
SPAN = 2' - 0"
3/4" = 1'-0"
TYP ELEVATION
1 1/2" = 1'-0"
CEILING / HOIST DETAIL
1 1/2" = 1'-0"
CEILING / COMBI-LOCK DETAIL
COMBI-LOCK
90 SF
142 SF
RESIDENT
ROOM
48 SF
111A
TOILET
ROOM
LINEN
A
90°L
/2
EQ EQ
/4
8' - 11 1/8" 1"
/8
7 1/4"
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS
ACCURATE TO 4" BASED
ON PDF CONVERSION
St. Cloud VA Bldg. 51 L1 East
RM 111
GUL105
MGE01/24/2024
PROJECT ID:103896
B rail
Ceiling bracket, Extended
Hoist
Stabilizers
KEY
Hoist Transformer
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
CONCRETE BEAM
VERIFY SIZE AND LOCATION IN FIELD.
SPAN = 2' - 0"
1/2" = 1'-0"
RM 111
Revision Schedule
Date Issued by Number
06/02/2024 TRC A
06/17/2024 MGE B
54 SF
117A
TOILET
ROOM
142 SF
RESIDENT
ROOM
A
90°L
/8
1" 9' - 0 7/8"
EQ EQ
/8
/8
/4
3 3/4"
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS
ACCURATE TO 4" BASED
ON PDF CONVERSION
St. Cloud VA Bldg. 51 L1 East
RM 117
GUL106
MGE01/24/2024
PROJECT ID:103896
B rail
Ceiling bracket, Extended
Hoist
Stabilizers
KEY
Hoist Transformer
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
CONCRETE BEAM
VERIFY SIZE AND LOCATION IN FIELD.
SPAN = 2' - 0"
1/2" = 1'-0"
RM 117
Revision Schedule
Date Issued by Number
155 SF
RESIDENT
ROOM
155 SF
RESIDENT
ROOM
64 SF
125A
TOILET
ROOM
64 SF
124A
TOILET
ROOM
A
A
GUL104
45°
45°
45°
45°
EQ EQ
5' - 3 1/4"
/8
/8
12' - 0" 10 1/4"
/4
/8
/8
EQ EQ
/8
10 1/4" 12' - 0"
5' - 3 1/4"
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS
ACCURATE TO 4" BASED
ON PDF CONVERSION
St. Cloud VA Bldg. 51 L1 East
RM 124 & 125
GUL107
MGE01/24/2024
PROJECT ID:103896
B rail
Ceiling bracket, Extended
Hoist
Stabilizers
KEY
Hoist Transformer
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT = 8' - 0"3.
AFF TO DECK = 11' - 11"
ATTACHMENT TYPE =4.
CONCRETE BEAM
VERIFY SIZE AND LOCATION IN FIELD.
SPAN = 2' - 0"
1/2" = 1'-0"
RM 124 & 125
Revision Schedule
Date Issued by Number
FD
219 SF
127C
BATH
67 SF
127C
10' - 4 5/8" 1"
/8
2' - 10 3/8"
/8
/4
Guldmann Inc.
14401 McCormick Drive Tampa FL, 33626 Unit A
Toll Free: 1(800)-664-8834 Fax: 1(813)-880-9558
Email: Info@Guldmann.net
NOTES
APPROVED BY:
PROJECT NAME:
SHEET DESCRIPTION:
SHEET NO:
DATE: DRAWN BY:
SEE 3/GUL102 FOR RAIL SPANS & ADDITIONAL DIMENSIONS
ACCURATE TO 4" BASED
ON PDF CONVERSION
St. Cloud VA Bldg. 51 L1 East
RM 127
GUL108
MGE01/24/2024
PROJECT ID:103896
B rail
Ceiling bracket, Extended
Hoist
Stabilizers
KEY
Hoist Transformer
HOIST = 770 LBS1.
FLUSHED RECESSED / TYPE - P2.
CEILING HEIGHT =3.
AFF TO DECK = UNKNOWN
ATTACHMENT TYPE = UNKNOWN4.
CONCRETE BEAM
VERIFY SIZE AND LOCATION IN FIELD.
SPAN = 2' - 0"
1/2" = 1'-0"
RM 127
CURTAIN TO BE SPLIT OR5.
WALLMOUNTED SWING AWAY
Revision Schedule
Date Issued by Number
| Sheets |
| GUL101 - FACILITY SIGNOFF |
| GUL102 - GEN. INFO |
| GUL103 - ATTACHMENT |
| GUL104 - PROJECT DETAILS |
| GUL105 - RM 111 |
| GUL106 - RM 117 |
| GUL107 - RM 124 & 125 |
| GUL108 - RM 127 |
File details come from the government source that posted it. Updated .