20250520_Bid Doc Addendum.pdf
PDF 11 MB Posted
- Attached to
- Y1DA--656-19-307 Remodel of Building 51-1, Eastside at the Saint Cloud VA, Saint Cloud, MN
- Solicitation number
- 36C26325B0007_0003
About this file
This document is an Update to Bid Documents dated May 20, 2025, for the VA Medical Center Remodel Project 656-19-307 located in St. Cloud, Minnesota. The addendum includes comprehensive updates to multiple architectural and engineering specification sections and drawing sheets for Building 51-1 Eastside, covering modifications to various project areas such as specifications for sheet waterproofing, door hardware, wire mesh partitions, and multiple drawing revisions across architectural, finish, electrical, and systems plans.
Key updates include adding and revising specification sections (07 13 00 Sheet Waterproofing, 08 71 00 Door Hardware, 10 22 23 Wire Mesh Partitions), modifying drawing sheets like GI001, GC110, and GC500, and making specific changes to room details, floor plans, demolition plans, and electrical/systems layouts. The addendum affects multiple building zones, with changes ranging from updating room finishes and floor plans to revising electrical and systems configurations, all aimed at preparing for the comprehensive remodeling of the VA Medical Center's Building 51-1 Eastside.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment B VAAR 852.219-75 Limitations on Subcontracting Cert of Compliance.pdf | ||
| ST CLOUD VA BLDG. 51_103896_SET_B.pdf | ||
| 656-19-307_GI001.pdf | ||
| 36C26325B0007 0003.pdf | ||
| Bid questions B51-1 E AE VA.doc | DOC document | |
| Drawings.pdf | ||
| S04 - Site Visit Agenda 36C26325B0007 2.docx | DOCX document | |
| 20240823_STC-B51_CP_SpecVol2.pdf | ||
| Pre bid site visit sign in sheet.pdf | ||
| Volume 3 Specs.pdf | ||
| 20240823_STC-B51_CP_SpecVol1.pdf | ||
| Wage Determination Stearns MN20250099 05.02.2025.pdf | ||
| photos for bid questions B51-1.docx | DOCX document | |
| Bed.Lift.Detail.4.png | PNG image |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
656-19-307 Remodel B51-1 Eastside for St Cloud VA Addendum Page 1 of 2
Update to Bid Documents – May 20, 2025
SPECIFICATION ITEMS:
1. 00 01 10 – Table of Contents
a. ADD specification section with 07 13 00
b. REVISE date section 08 71 00
2. 07 13 00 – Sheet Waterproofing
a. ISSUE specification section
3. 08 71 00 – Door Hardware
a. REISSUE specification section
4. 10 22 23 – Wire Mesh Partitions
a. REVISE specification section 2.2.A.1.
DRAWING ITEMS:
5. Sheet GI001
a. Update to sheet index
6. Sheet GC110
a. Update room 106B
b. REVISE Detail 4
7. Sheet GC500
a. REVISE ideal plan – remove supply and return and cap at main duct.
8. Sheet 48-AD111
a. OMIT keyed notes 20 and 22 at rooms. Keyed note 20 to remain at Rooms 103 and 104. Keyed note 22 to apply at room 106B.
b. REVISE keyed note 20
c. REVISE keyed note 22
d. REVISE keyed note 23
e. REVISE keyed note 24
9. Sheet 51-AD111
a. REVISE drawing 1 - keyed note 20 shall apply to all spaces not hatched.
b. REVISE drawing 1 – (7) overhead lifts identified for removal and salvage.
c. REVISE keyed note 20
d. REVISE keyed note 22
e. REVISE keyed note 23
f. REVISE keyed note 24
10. Sheet 51-AE110 – Sheet not reissued
a. OMIT accessible note
11. Sheet 51-AE111
a. REVISE keyed note 8
b. REVISE drawing 1 – showing interior windows at bath 127C
c. REVISE drawing 1 – showing floor slop at bath 127C
12. Sheet 51-AE112
a. REVISE keyed note 8
b. REVISE drawing 1 – east partition medication room 107
13. Sheet AE550
a. REVISE drawing 13
14. Sheet AE601
a. ADD partition B6 detail
b. ADD grab bar detail 1
c. ADD grab bar detail 2
15. Sheet AE602
a. REVISE door schedule – door 51-127D
b. REVISE door schedule – door 51-127E
c. REVISE door schedule – door 51-128
656-19-307 Remodel B51-1 Eastside for St Cloud VA Addendum Page 2 of 2
d. REVISE door schedule – door 51-C1NE
16. Sheet 48-AF110
a. REVISE floor finish at 103A
b. REVISE floor finish at 103B
c. REVISE floor finish at 104
17. Sheet 51-AF110
a. REVISE floor finish at toilet rooms
b. REVISE floor finish at soiled utility
18. Sheet AF600
a. ADD paint and resilient base wall finish at 48-106B
b. REVISE finish schedule floor finish at 48-103A
c. REVISE finish schedule floor finish at 48-103B
d. REVISE finish schedule floor finish at 48-104
e. REVISE finish schedule floor finish at 51 toilet rooms
f. REVISE finish schedule floor finish at 51-127E
19. Sheet 48-EL110
a. ADD keynote 1
20. Sheet 51-EE100
a. Add 51-MDP equipment tag
21. Sheet 51-EL110
a. Add lighting requirements to 127B-1
22. Sheet 51-EP111
a. Add approximate location of 51-L2-2 on floor above
23. Sheet 51-ES110
a. Show WAP locations
24. Sheet 51-ES110
a. Show WAP locations
REFERENCE ITEMS:
None
END OF REVISION
Enclosures 00 01 10, 08 71 00, 07 13 00, 10 22 23, GI001, GC110, GC500, 48-AD111, 51-AD111, 51-AE111, 51-AE112, AE550, AE601, AE602, 48-AF110, 51-AF110, AF600
48-EL110
51-EE100
51-EL110
51-EP111
51-ES110
51-ES110
VAMC St. Cloud, MN VA Project 656-19-307 Remodel Building 51-1 Eastside May 20, 2025 4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303
00 01 10-1
TABLE OF CONTENTS
DEPARTMENT OF VETERANS AFFAIRS
VHA MASTER SPECIFICATIONS
TABLE OF CONTENTS
Section 00 01 10
SECTION NO DIVISION AND SECTION TITLES DATE
DIVISION 00 - SPECIAL SECTIONS
00 01 15 List of Drawing Sheets 05-20
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements SCVA
12-23 01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 01-24 01 33 23 Shop Drawings, Product Data, and Samples 02-23 01 35 26 Safety Requirements for Major Projects 09-22 01 42 19 Reference Standards 11-20 01 45 00 Quality Control 02-21 01 45 29 Testing Laboratory Services 11-18 01 45 35 Special Inspections 06-21 01 57 19 Temporary Environmental Controls 01-21 01 58 16 Temporary Interior Signage 07-15 01 74 19 Construction Waste Management 04-22 01 81 13 Sustainable Construction Requirements 10-17 01 91 00 General Commissioning Requirements 04-22
DIVISION 02 – EXISTING CONDITIONS
02 41 00 Demolition 08-17 02 82 13.13 Glovebag Asbestos Abatement 01-21 02 82 13.19 Asbestos Floor Tile and Mastic Abatement 01-21 02 83 33.13 Lead-Based Paint Removal and Disposal 01-21
DIVISION 04 – MASONRY
04 41 21 Stone Finish 07-24
DIVISION 05 – METALS
05 40 00 Cold Formed Metal Framing – Reference Only 09-23 05 50 00 Metal Fabrications 08-18
DIVISION 06 - THERMAL AND MOISTURE PROTECTION
06 10 00 Rough Carpentry 01-17
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303
00 01 10-2
TABLE OF CONTENTS
SECTION NO DIVISION AND SECTION TITLES DATE
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 13 00 Sheet Waterproofing 01-21 07 21 13 Thermal Insulation 01-21 07 84 00 Firestopping 01-21 07 92 00 Joint Sealants 04-22
DIVISION 08 - OPENINGS
08 11 13 Hollow Metal Doors and Frames 01-21 08 14 00 Interior Wood Doors 01-21 08 31 13 Access Doors and Frames 04-22 08 51 13.11 Side-Hinged Aluminum Windows 01-21 08 56 66 Detention Window Screens 01-21 08 71 00 Door Hardware 03-24 08 80 00 Glazing 01-21
DIVISION 09 – FINISHES
09 05 16 Subsurface Preparation for Floor Finishes 01-21 09 22 16 Non-Structural Metal Framing 06-18 09 29 00 Gypsum Board 04-20 09 30 00 Specialty Moldings and Trims 07-24 09 30 13 Ceramic/Porcelain Tiling 01-21 09 51 00 Acoustical Ceilings 12-18 09 65 13 Resilient Base and Accessories 01-21 09 65 16 Resilient Sheet Flooring 06-22 09 65 19 Resilient Tile Flooring 05-18 09 91 00 Painting 01-21
DIVISION 10 – SPECIALTIES
10 14 00 Signage 01-21 10 21 23 Curtain Tracks 01-21 10 22 13 Wire Mesh Partitions 01-21 10 26 00 Wall and Door Protection 01-21 10 28 00 Toilet, Bath, and Laundry Accessories 01-21 10 44 13 Fire Extinguisher Cabinets 08-18
DIVISION 11 – EQUIPMENT – See Appendix
DIVISION 12 – FURNISHINGS
12 31 00 Manufactured Metal Casework 01-21 12 32 00 Manufactured Wood Casework 01-21 12 36 00 Countertops 12-23
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303
00 01 10-3
TABLE OF CONTENTS
SECTION NO DIVISION AND SECTION TITLES DATE
DIVISION 21- FIRE SUPPRESSION
21 13 13 Wet-Pipe Sprinkler Systems 06-15
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 01-23 22 05 19 Meters and Gages for Plumbing Piping 09-20 22 05 23 General-Duty Valves for Plumbing Piping 09-20 22 07 11 Plumbing Insulation 09-19 22 11 00 Facility Water Distribution 05-21 22 13 00 Facility Sanitary and Vent Piping 09-20 22 40 00 Plumbing Fixtures 05-24 22 63 00 Gas Systems for Laboratory and Healthcare Facilities 05-23
DIVISION 23 – HEATING, VENTILATING, AND AIR
CONDITIONING (HVAC)
23 05 11 Common Work Results for HVAC 03-23 23 05 93 Testing, Adjusting, and Balancing for HVAC 03-23 23 08 00 Commissioning of HVAC Systems 03-23 23 09 23 Direct-Digital Control System for HVAC 03-23 23 21 13 Hydronic Piping 03-23 23 22 13 Steam and Condensate Heating Piping 08-23 23 31 00 HVAC Ducts and Casings 03-23 23 36 00 Air Terminal Units 03-23 23 37 00 Air Outlets and Inlets 03-23 23 82 16 Air Coils 03-23
DIVISION 26 – ELECTRICAL
26 05 11 Requirements for Electrical Installations 11-22 26 05 19 Low-Voltage Electrical Power Conductors and Cables 11-22 26 05 26 Grounding and Bonding for Electrical Systems 11-22 26 05 33 Raceway and Boxes for Electrical Systems 11-22 26 09 23 Lighting Controls 11-22 26 24 16 Panelboards 11-22 26 27 26 Wiring Devices 11-22 26 29 11 Motor Controllers 11-22 26 51 00 Interior Lighting 11-22
DIVISION 27 – COMMUNICATIONS
27 05 11 Requirements for Communications Installations 09-19 27 05 26 Grounding and Bonding for Communications Systems 12-22 27 05 33 Conduits and Backboxes for Communications Systems 12-22 27 10 00 Structured Cabling 12-22 27 11 19 Communications Termination Blocks and Patch Panels 12-22 27 13 13.13 Communications Copper Cable Splicing and Terminations 12-22
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303
00 01 10-4
TABLE OF CONTENTS
SECTION NO DIVISION AND SECTION TITLES DATE
27 13 23.13 Communications Optical Fiber Splicing and Terminations 12-22 27 15 13 Communications Copper Horizontal Cabling 12-22 27 16 19 Communications Patch Cords, Station Cords, and Cross-
Connect Wire 12-22
27 51 16 Public Address and Mass Notification Systems 11-22 27 52 23 Nurse Call and Code Blue Systems 10-18
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 05 00 Common Work Results for Electronic Safety and Security 04-18 28 05 13 Conductors and Cables for Electronic Safety and
Security 10-18
28 05 26 Grounding and Bonding for Electronic Safety and Security
09-11
28 05 28.33 Conduits and Backboxes for Electronic Safety and Security
09-11
28 13 00 Physical Access Control System 10-11 28 31 00 Fire Detection and Alarm 10-11
APPENDICES
Appendix A - Report: Asbestos and Lead Inspection
Profile
Appendix B – Mounted Patient Lift Specifications 11 73 00 Ceiling Mounted Patient Lift System 08-20 11 73 00.1 Lift Installation Checklist Guldmann User Manual
- - - E N D - - -
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 01-01-21
07 13 00 - 1
SHEET WATERPROOFING
SECTION 07 13 00
SHEET WATERPROOFING
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies sheet waterproofing materials used for shower pan waterproofing in showers and at floors sloped to floor drain.
1.2 QUALITY CONTROL
A. Approval by the COR is required of products of proposed manufacturers.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Sheet waterproofing.
2. Printed installation instructions.
C. Certificates:
1. Sheet waterproofing manufacturer's approval of adhesive used.
2. Waterproofing tests report indicating that water test as specified has been made for each shower area and that each area was found to be watertight.
D. Samples:
1. Sheet waterproofing, 150 mm (6 inches) square.
2. Waterproofed building paper, 150 square mm (6 inches square).
3. Adhesive, 0.24 L (1/2 pint).
1.4 PRODUCT DELIVERY, STORAGE AND HANDLING:
A. Deliver materials to job in manufacturer's original unopened containers with brand name marked thereon.
B. Unload and store to prevent injury to materials.
1. Do not store material in areas where temperature is lower than 10 degrees C (50 degrees F), or where prolonged temperature is above 32 degrees C (90 degrees F).
1.5 WARRANTY
A. Waterproofing is subject to the terms of Article titled "Warranty of
Construction”, FAR clause 52.246-21, except that warranty period is extended to two years.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 01-01-21
07 13 00 - 2
SHEET WATERPROOFING
1.6 APPLICABLE PUBLICATIONS:
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced by basic designation only.
B. Federal Specification (Fed. Spec.):
UU-B-790A INT AMD 1.....Building Paper, Vegetable Fiber: (Kraft, Waterproof, Water Repellent and Fire Resistant)
PART 2 - PRODUCTS
2.1 SHOWER PAN WATERPROOFING SHEET:
A. Rubber type sheet formed of non-reinforced, homogeneous, impermeable, sheeting compound reduced to thermoplastic state, resistant to fungus, mildew and bacteria, not less than 1.5 mm (60 mils) thick.
B. Asphaltic sheet formed with a laminated asphalt construction consisting of eight plies of Kraft paper bonded and saturated by seven layers of asphalt, reinforced with three layers of glass fibers and faced with polyethylene sheet; total weight 1.9 kilogram/square meter (0.40 pounds per square foot).
2.2 ADHESIVES:
A. As furnished by the manufacturer of the sheet waterproofing.
B. Compatible with adjacent materials where contact occurs.
2.3 WATERPROOFED BUILDING PAPER:
A. Fed. Spec. UU-B-790, Type I, Grade C.
2.4 CONCRETE PATCHING COMPOUND:
A. Portland cement base, acrylic polymer compound, manufactured specifically for resurfacing and leveling concrete floors.
B. Have not less than the following physical properties:
1. Compressive strength - 25 mPa (3500 psi).
2. Tensile strength - 7 mPa (1000 psi).
3. Flexural strength - 7 mPa (1000 psi).
4. Density - 1.9.
C. Capable of being applied in layers up to 50 mm (two inches) thick, being brought to a feather edge, and being troweled to a smooth finish.
D. Ready for use in 48 hours after application.
PART 3 - EXECUTION
3.1 PREPARATION:
A. Before installing shower pan waterproofing, adjoining surfaces shall be clean, smooth, firm and dry.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 01-01-21
07 13 00 - 3
SHEET WATERPROOFING
B. Concrete surfaces shall be cured a minimum of seven days and be free from release agents, concrete curing agents, and other contaminates.
C. Remove all high spots and loose and foreign particles and fill all voids, depressions joints and cracks with concrete patching compound.
D. Ensure vertical surfaces have a continuous supportive back substrate for waterproofing.
3.2 INSTALLATION:
A. Coat entire surfaces to receive shower pan waterproofing with adhesive spread at rate of 1 liter/square meter (one gallon per 40 square feet).
B. Butt joints and cover with a strip of the waterproofing sheeting material eight inches in width and seal with adhesive.
C. Carry sheeting up vertical surfaces not less than 4 inches above surface of shower floor. Carry over tops of curbs.
D. Roll entire horizontal surfaces with 23 to 45 kg (50 to 100 pounds) roller and roll corners and vertical sections with a rubber roller to insure solid anchorage.
E. Make cut out for floor drains and fit to drain for watertight assembly, coordinating with drain installation.
3.3 PROTECTION:
A. When finish floor will not be immediately installed, protect waterproofing pan.
B. Cover with 2 inches of sand or waterproofed building paper.
C. Maintain protection until finished floor is placed.
3.4 WATER TEST:
A. Test in presence of COR for leaks before permanent finish is applied over shower pan waterproofing.
B. Seal floor drain watertight and fill waterproofing pan with water to within approximately 25 mm (1 inch) of top of its vertical surfaces.
C. When leakage occurs, repair waterproofing and repeat testing until no leakage occurs.
D. Submit certificate to COR of test results.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-1
DOOR HARDWARE
SECTION 08 71 00
DOOR HARDWARE
Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
Caulking: Section 07 92 00 JOINT SEALANTS.
Application of Hardware: Section 08 14 00, WOOD DOORS: Section 08 11 13, HOLLOW METAL DOORS AND FRAMES; Section 08 71 13, AUTOMATIC DOOR
OPERATORS; Section 08 71 13.11, LOW ENERGY DOOR OPERATORS.
Finishes: Material Schedule.
Painting: Section 09 91 00, PAINTING.
Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.
Electrical: Division 26, ELECTRICAL.
Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
All hardware shall comply with ABAAS, (Architectural Barriers Act
Accessibility Standard) unless specified otherwise.
Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-2
DOOR HARDWARE
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
All double doors shall be spec'd with "Z" shape, metal astragal and door coordinator.
1.4 WARRANTY
Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled
"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:
Hardware Item
Quantity Size Reference Publication Type No.
Finish Mfr.
Name and Catalog No.
Key Control Symbols
UL Mark (if fire rated and listed)
ANSI/BHMA
Finish Designation
Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-3
DOOR HARDWARE
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
Record of opening force measurement for all doors equipped with closers.
1.7 DELIVERY AND MARKING
Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
COR for reference purposes. Tag shall identify items by Project
Specification number and manufacturer's catalog number. These items shall remain on file in COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and
Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-4
DOOR HARDWARE
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number.
Each number designates a set of hardware items applicable to a door type.
Keying: All cylinders shall be keyed into existing Best Great Grand
Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset.
Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR. Provide brass temporary construction cores
Keying: A new Great Grandmaster key shall be established for this project. The key system shall be small format (Best size and profile) removable core type as previously described. The key blanks shall be protected by a utility patent with a minimum seven years remaining on the patent from the start of construction, and protected by contract-controlled distribution. The manufacturer shall furnish code pattern listings in both paper and electronic formats so keys may be reproduced by code.; provide electronic format in file type required by project’s key control software. The manufacturer shall design the new key system with the capacity to rekey the existing system and also provide for 25 percent expansion capability beyond this requirement. Submit a keying chart for approval showing proposed keying layout and listing expansion capacity.
1. Keying information will be furnished to the Contractor by the COR.
2. Supply information regarding key control of cylinder locks to manufacturers of equipment having cylinder type locks. Notify COR immediately when and to whom keys or keying information is supplied.
Return all such keys to the COR.
1.10 APPLICABLE PUBLICATIONS
The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-5
DOOR HARDWARE
basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
ASTM International(ASTM):
F883-13.................Padlocks
E2180-18................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.11-14..............Cabinet Locks
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-6
DOOR HARDWARE
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
Architectural Barriers Act Accessibility Standards (ABAAS)
PART 2 - PRODUCTS
2.1 BUTT HINGES
Hinges- Hager BB1279 4.5" x 4.5" 5 knuckle ball bearing US 26 D HT.
ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Exterior Doors: Type A2112/A5112 for doors 900 mm (3 feet) wide or less and Type A2111/A5111 for doors over 900 mm (3 feet) wide. Hinges for exterior outswing doors shall have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless steel material.
2. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.
Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.
Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210 mm (4 feet) high: 2 hinges.
2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.
4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm
(4-1/2 inches x 4-1/2 inches) hinges.
5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-7
DOOR HARDWARE
7. Provide heavy-weight hinges where specified.
8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.
9. Approved manufacturers:
a. Hager
b. McKinney
c. Stanley
See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
2.2 CONTINUOUS HINGES
ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete
Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a
Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.
1. Base Metal for Exterior Hinges: Stainless steel.
2. Base Metal for Interior Hinges: Stainless steel
3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel
4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-8
DOOR HARDWARE
9. Approved manufacturers:
a. Markar
b. Pemko
c. Stanley
2.3 DOOR CLOSING DEVICES
Closing devices shall be products of one manufacturer for each type specified.
Detex -ECL-230D
Closer - Corbin Russwin DC6210
2.4 OVERHEAD CLOSERS
Conform to ANSI A156.4, Grade 1.
Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, 4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-9
DOOR HARDWARE
drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
15. Approved manufacturers:
a. Corbin Russwin
b. LCN
c. Sargent
2.5 FLOOR CLOSERS AND FLOOR PIVOT SETS
Comply with ANSI A156.4. Provide stainless steel floor plates for floor closers and floor pivots, except where metal thresholds occur. Provide cement case for all floor closers. Floor closers specified for fire doors shall comply with Underwriters Laboratories, Inc., requirements for concealed type floor closers for classes of fire doors indicated on drawings. Hold-open mechanism, where required, shall engage when door is opened 105 degrees, except when door swing is limited by building construction or equipment, the hold-open feature shall engage when door is opened approximately 90 degrees. The hold-open mechanism shall be selectable on/off by turning a screw through the floor plate. Floor closers shall have adjustable hydraulic back-check, adjustable close speed, and adjustable latch speed. Provide closers with delayed action where a hold-open mechanism is not required. Floor closers shall be multi-sized. Single acting floor closers shall also have built in dead stop. Where required, provide closers with special cement cases appropriate for shallow deck installation or where concrete joint lines run through the floor blockout. At offset-hung doors installed in deep reveals, provide special closer arm and spindle to allow for
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-10
DOOR HARDWARE
installation. Where stone or terrazzo is applied over the floor closer case, provide closer without floor plate and with extended spindle
(length as required) and special cover pan (depth as required) to allow closer to be accessed without damaging the material applied over the closer. Pivots for non-labeled doors shall be cast, forged or extruded brass or bronze.
Where floor closer appears in hardware set provide the following as applicable.
1. Double Acting Floor Closers: Type C06012.
2. Single Acting Floor Closer: Type C06021 (center pivoted).
(Intermediate pivot is not required).
3. Single Acting Floor Closers: Type C06041 (offset pivoted).
4. Single Acting Floor Closer for Labeled Fire Doors: Type C06051
(offset pivoted).
5. Single Acting Floor Closers For Lead Lined Doors: Type C06071 (offset pivoted).
2.6 DOOR STOPS
Conform to ANSI A156.16.
Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.
Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-11
DOOR HARDWARE
concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.
Omit stops where floor mounted door holders are required and where automatic operated doors occur.
Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
Approved Manufacturers:
Rockwood
Trimco
Hager
2.7 OVERHEAD DOOR STOPS AND HOLDERS
Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
Approved Manufacturers:
Norton Rixson
Sargent
Rockwood
2.8 FLOOR DOOR HOLDERS
Conform to ANSI Standard A156.16. Provide extension strikes for Types
L01301 and L01311 holders where necessary.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-12
2.9 LOCKS AND LATCHES
Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Use Mortise Locks only, no cylindrical locks. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
In addition to above requirements, locks and latches shall comply with following requirements:
1. Corbin or Best Mortise locks. Best cylinders 7-pin TE keyway. Mortise
Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel.
Provide sectional (lever x rose) lever design matching [Corbin LWA].
No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension.
Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.
2. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
3. Locks on designated doors in Psychiatric (Mental Health) areas shall be paddle type with arrow projection covers and be UL Listed. Provide these locks with paddle in the down position on both sides of the door. Locks shall be fabricated of wrought stainless steel.
4. Approved Manufactuers:
a. Corbin Russwin
5. Corbin ML2000 SERIES- ML2055 Classroom, ML2057 Storeroom
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-13
DOOR HARDWARE
6. ML2069 Patient Bathroom, ML2065 Dormitory (Deadbolt Feature)
7. Public restrooms shall have occupied latch identification.
2.10 PUSH-BUTTON COMBINATION LOCKS
ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry.
Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA
A156.13, Grade 1. Lever handles and operating components in compliance with the ABAAS and the ADA Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors.
Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.
Approved manufacturers:
Sargent
2.11 ELECTROMAGNETIC LOCKS
ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product
Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 500 pound force (2224 N).
3. Inductive Kickback Peak Voltage: Not more than 0 V.
4. Residual Magnetism: Not more than 4 pound force (18 N) to separate door from magnet.
Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's
"Certified Product Directory".
1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 pound force (67 N) for not more than 3 seconds, as required by NFPA 101.
2. Security Grade: Activated from secure side of door by initiating device.
3. Movement Grade: Activated by door movement as initiating device.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-14
DOOR HARDWARE
4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.
2.12 ELECTRIC STRIKES
ANSI/ BHMA A156.31 Grade 1.
General: Use fail-secure electric strikes at fire-rated doors.
Prefer electric strike located in door frame. Discourage use of electric mortise inside doors - maintenance issues with wiring failures when routing through hinge and door. No wires shall run through door hinges and door slabs.
No wire conductors within hinge assemblies. All wire conductors for door hardware shall be on the latch side with latch activation. Electronic plungers not allowed.
Approved Manufacturers:
Hes
Folger Adam
Von Duprin
2.13 KEYS
Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks
100 each different key way
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
Psychiatric keys shall be cut so that first two bittings closest to the key shoulder are shallow to provide greater strength at point of greatest torque.
2.14 KEY CABINET
ANSI Standard A156.11. Provide key cabinet made of cold rolled, 1.2 mm
(0.0478 inch) thick furniture steel electro-welded. Doors shall have "no sag" continuous brass-pin piano type hinge and be equipped with chrome plated locking door handles, hook cam and mechanical pushbutton door
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-15
DOOR HARDWARE
lock. Key Cabinet and Key Control System shall accommodate all keys for this project plus 25 percent. Provide minimum number of multiple cabinets where a single cabinet of largest size will not accommodate the required number of keys.
Key tags shall consist of two sets: Permanent self-locking and loan key snaphook type with tag colors as follows: Red fiber marker of the permanent self-locking type approximately 32 mm (1-1/4 inch) in diameter engraved with the legend "FILE KEY MUST NOT BE LOANED." Also furnish for each hook a white cloverleaf key marker with snap-hooks engraved with the legend "LOAN KEY."
The manufacturer of the lock cylinders and locks shall attach a key tag to keys of each lock cylinder and shall mark thereon the respective item number and key change number. Provide each group of keys in a key gathering envelope (supplied by Key Cabinet Manufacturer) in which the lock manufacturer shall include the following information: Item number, key change number and door number. The contractor shall furnish the Key
Cabinet Manufacturer the hardware and keying schedules and change keys.
The Key Cabinet Manufacturer shall set up a three-way cross index system, including master keys, listing the keys alphabetically, the hooks numerically and the key changes numerically on different colored index cards. Index cards shall be typewritten and inserted in a durable binder. Attach the keys to the two sets of numbered tags supplied with the cabinet. (The permanent tag and the loan key tag). Instruct the owner in proper use of the system. Install cabinet as directed by the
COR.
2.15 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
Conform to ANSI Standard A156.6.
Provide protective plates as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be
152 mm (6 inches) high. Both kick and mop plates shall be minimum
1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch)
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-16
DOOR HARDWARE
less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.
5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.
6. Provide stainless steel edge guards where so specified at wood doors.
Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
7. Approved Manufacturers:
a. Burns
b. Rockwood
c. Trimco
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-17
2.16 EXIT DEVICES
Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building.
Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.
Surface vertical rod panics shall only be provided less bottom rod;
provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.
Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.
Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.
At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.
Exit devices for fire doors shall comply with Underwriters Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.
Approved Manufacturers:
Corbin Russwin
Sargent
Von Duprin
Exit push bar - Von Duprin #98/99 series
2.17 FLUSH BOLTS (LEVER EXTENSION)
Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI
A156.16, for flush bolts required on lower part of doors.
Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-18
DOOR HARDWARE
Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).
Approved Manufacturers:
Hager
2.18 FLUSH BOLTS (AUTOMATIC)
Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI
A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
Approved Manufacturers:
Hager
2.19 DOOR PULLS WITH PLATES
Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by
381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.
Approved Manufcturers:
Hager
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-19
2.20 PUSH PLATES
Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by
406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.
Approved Manufacturers:
Hager
2.21 COMBINATION PUSH AND PULL PLATES
Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
Approved Manufacturers:
Hager
2.22 COORDINATORS
Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
4801 Veterans Drive Update to Bid Documents St. Cloud, MN 56303 VERSION 03-01-24
08 71 00-20
DOOR HARDWARE
Approved Manufacturers:
Hager
2.23 THRESHOLDS
Conform to ANSI A156.21, mill finish…