Sprinkler Deficiency log .pdf
PDF 53 KB Posted
- Solicitation number
- BD-26-1069-MILDV-30000-129014
- Issued by
- Massachusetts
About this file
This document is a Sprinkler Deficiency Log prepared for the Commonwealth of Massachusetts in support of ITB 260328, which solicits fire sprinkler system inspection, testing, and maintenance services at Camp Edwards facilities. The deficiency log catalogs required repairs across twelve building locations (Buildings 1200, 2806, 2812, 2816, 3132, 3140, 4180, 4682, 5220, 5221, and 5223), detailing specific work items that must be completed during the first year of the contract term. Deficiencies include replacement of outdated gauges, installation of missing FDC (Fire Department Connection) signs and caps, replacement of leaking valves and main drains, installation of missing sprinkler heads and piping, provision of spare head wrenches, replacement of non-indicating valves with os&y (outside stem and yoke) valves, and system surveys for specific operational issues. The contract is structured as a three-year service agreement with two one-year renewal options, requiring annual inspection, testing, and maintenance services throughout the contract duration.
The deficiency log provides the baseline scope of corrective work that responding contractors must address as a component of their overall service proposal, establishing the remediation requirements that must be completed prior to ongoing annual maintenance operations. Pricing and other contractual terms are to be submitted by bidders in response to the formal invitation to bid. The document serves as critical reference material for contractors to understand the extent of initial repairs needed across the Camp Edwards facilities and to develop accurate cost estimates for both the first-year remediation work and subsequent years of routine inspection and maintenance services.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg # Deficiencies
1200 Missing FDC Sign Replace 2 water/air gauge 4"
2806 Replace Ball drip assembly with mechanical tee missing head wrench Replace 2 out of date gauges
(12) missing heads for spare head box Office area has no sprinkler heads - needs 14 heads and piping Replace (2)-4" os&y valves
2812 Replace (2) outdated gauges Install FDC sign Install spare head wrench in spare head box
2816 Install (2) missing FDC signs Install (2) missing FDC caps Install (1) missing head wrench for spare head box Install (4) missing control valve signs Replace West end system 2" main drain (leaking) Replace gauge valves on risers that are leaking Remove and replace 6" non-indicating valves to os&y on risers Replace ITC valve in fitness area Survey why standpipe system is not active provide upright spare heads for spare head box
3132 Replace (8) Outdated gauges Pipe inspectors test drain outside for testing and drainage Install (1) FDC sign
3140 Replace (3) outdated gauges Install (1) missing FDC sign Install new AMD for proper compressor operation Install Ball drip assembly on FDC Survey galvy pipe replacement
4180 Install (2) missing FDC signs Replace (1) missing head wrench Replace (3) outdated gauges System has no hydraulic calc plate
4682 Replace (8) outdated gauges Replace (2) outdated Fire pump gauges
APPENDIX A
Replace non working WMG Install FDC sign Install ITV on dry system for proper testing Install Ball drip assembly on FDC Provide missing spare head wrench for 3/4" heads
5220 Replace outdated 4" water/air gauge Install missing FDC sign
5221 Replace (4) outdated gauges Install missing FDC sign Provide (1) missing head wrench for spare head box
5223 Install missing FDC sign at back of bldg Replace (4) outdated gauges