SPDN1 OY2 CLK Q1_SA1 RM Report for FMSR signature.xlsx

XLSX spreadsheet 377 KB Posted

Attached to
Government-Owned, Contractor-Operated (GOCO) Fuel Services at NAWS China Lake, California
Solicitation number
SPE60326R0530
Issued by

About this file

This is a Reliability and Maintenance (RM) Event Report documenting the quarterly maintenance completion status for fuel system infrastructure at Naval Air Weapons Station (NAWS) China Lake under Contract No. 47QSHA18D002M, Order Number W912DY24F0012. The report dated February 13, 2026, covers the second operational year (OY2) Q1 performance for GSA Region SPD-N1 and details maintenance activities across multiple fuel farm facilities including the pump house, storage tanks, aircraft issue stands, and tank truck offload areas.

The maintenance report documents the completion status of numerous system inspections and maintenance tasks organized by component type and UFC (Unified Facilities Criteria) section reference. Key components inspected include signage and markings, filter separators, basket strainers, positive displacement meters, centrifugal pumps, loading and offloading fuel hoses, air eliminator tanks, dual rate-of-flow control valves, defuel/flush valves, pressure control valves, fueling nozzles, aboveground piping, ball valves, double block and bleed valves, thermal and pressure relief valves, fire valves, motor operators, various gauges, sight flow indicators, EFSO (Emergency Fuel Shutoff) systems, aboveground storage tanks (both field-erected and shop-fabricated), floating roofs, and mechanical tape gauges. The majority of inspections at bulk storage facilities were marked as "Completed" with dates between February 10-12, 2026, completed by personnel identified as Tremayne Dale and Roland Despres. Several items at the Flight Line Hot Pit A/C Refuel facility were marked "Not Available" with notation that the facility is "under modernization." Notable deficiencies documented include three offloading hoses with leaking issues and one ball valve that required repairs during the maintenance event, while two floating roof tanks showed deteriorating chime seals requiring a service order. The report indicates compliance with established maintenance schedules and identifies items requiring service order completion or future contract work.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RM Format

ContractContract No. 47QSHA 18D002M Order Number: W912DY24F0012GSA Region:SPD-N1
SiteNAWS China Lake (CLK)
Date13-Feb-26
RM Event(s)OY2 Q1-SA1
Applicable Facility AssetsUFC System Level Maintenance FrequencyResponsibilityRM Completion Record ResultDate CompletedCompleted ByDeficienciesResponsible FMSRNotesAdd to Def List?
UFC Section ReferenceReal Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)MakeModelCapacity/Size
HSignage and Markings (Section 2-7)
TA. Check permanent signs and markings for adequacy and readability. Repair or replace deteriorated or illegible signs and markings.MonthlyOM
TB. Inspect the location of Department of Transportation (DOT) regulated underground pipelines and ensure they are marked in accordance with 49 Code of Federal Regulations (CFR) 195.410.MonthlyOM
TC. Check that all non-DOT regulated pipelines, tanks, valves, pumps, meters, and other equipment are marked in accordance with UFC 3- 460-01 Section 2-18. If markings are missing or insufficient, repair or add markings in accordance with UFC 3-460-01.MonthlyOM
TD. Ensure petroleum fuel system Emergency Fuel Shutoff (EFSO) push buttons are properly identified at each location. Ensure that signage is properly secured and that the lettering is legible from 25 feet (7.5 meters) away and not faded.MonthlyOM
TE. Verify enough movable or temporary signs are maintained in good condition to serve anticipated needs; for example: "DANGER," "CLOSED TO TRAFFIC," "KEEP FLAMES AWAY," "MEN WORKING," "NO SMOKING," "DANGER NO OPEN FLAME OR IGNITION SOURCE BEYOND THIS POINT." Use bilingual signs when appropriate.AnnuallyOM
I2-7201FUEL FARM BRANCH OFFICEAdministrative AreaSIGNSignage/MarkingsCLK-0000020286-SIGN-0488_miscellaneous_miscellaneous_miscellaneousCompleted2/12/26TREMAYNE DALEROLAND DESPRES
HFilter Separators (Section 3-6.2)
TG. Refer to Section 6-7.2 Differential Pressure Gauges for inspection and maintenance requirements of differential pressure gauges.Reference to OtherSM
TH. Refer to Section 3-10.2 Automatic Air Vents for inspection and maintenance requirements of automatic air vents.Reference to OtherSM
TI. Refer to Section 6-6.3 Thermal and Pressure Relief Valves for inspection and maintenance requirements of thermal and pressure relief valves.Reference to OtherSM
TJ. Refer to Section 4-4.2.2 Filter Separator Control Valves for inspection and maintenance requirements of filter separator control valves.Reference to OtherSM
TA. Open drain under flow conditions until clear fuel is observed from the drain valve.DailyOM
TB. Monitor differential pressure of coalescer cartridges. The acceptable maximum differential pressure for a specific filter/separator is dependent on the system flow rate. Monitor and chart differential pressure measurements of filter separators from readings taken during normal operations. Investigate sudden drops or spikes in differential pressure measurement readings.DailyOM
TC. Operate filter separator isolation valves.QuarterlySM
TD. Inspect components and check operation of water shutoff system.QuarterlySM
TE. Change coalescer cartridges. Refer to Section 3-6.2.2 Replacement of Coalescer Cartridges for general instructions on replacement of coalescer cartridges. Military Service-specific SCP may extend the coalescer cartridge replacement frequency based on differential pressure if filters separators are used on high throughput systems. Check expiration date of replacement coalescer cartridges before installation.
Frequency: Routine coalescer changes shall be performed as part of the FFP maintenance activities. Coalescer cartridge changes required due to a repair or other circumstance beyond normal system operation shall be performed by service order.See DescriptionSM
TF. Inspect and clean separator cartridges at time of coalescer cartridge change in accordance with Section 3-6.2.3 Separator Cleaning. Worn or damaged separator cartridges shall be replaced.
Frequency: Every 36 months or sooner if required by differential pressure. Every 36 months or sooner if required by differential pressure. Routine separator cartridge cleaning shall be performed as part of the FFP maintenance activities. Separator cartridge changes shall be performed by service order.See DescriptionSM
TK. Conduct inspections of code rated vessels that meet the requirements of UFC 3-430-07 Operations and Maintenance: Inspection and Certification of Boilers and Unfired Pressure Vessels.
Frequency: As required by UFC 3-430-07. This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.See DescriptionSM
I3-6.2201FUEL FARM PUMP HOUSEBulk StorageFLSPFS #1 FiltrationCLK-0000020317-FLSP-0036FacetVCS-543-236 Serial #95363600GPMCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-6.2201FUEL FARM PUMP HOUSEBulk StorageFLSPFS #2 FiltrationCLK-0000020317-FLSP-0037FacetVCS-543-236 Serial #95367600GPMCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-6.2201FUEL FARM PUMP HOUSEBulk StorageFLSPFS #3 FiltrationCLK-0000020317-FLSP-0038FacetVCS-543-236 Serial #95365600GPMCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-6.2201FUEL FARM PUMP HOUSEBulk StorageFLSPFS #4 FiltrationCLK-0000020317-FLSP-0039FacetVCS-543-236 Serial #95366600GPMCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-6.2201FUEL FARM PUMP HOUSEBulk StorageFLSPFS #5 FiltrationCLK-0000020317-FLSP-0042FacetVCS-543-236 Serial #95364600GPMCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-6.2201FUEL FARM HOT PIT A/C REFUELFlight LineFLSPFiltrationCLK-0000020309-FLSP-0057VelconSHVM2033150MT Serial #67987600GPMNot Available2/10/206TREMAYNE DALEROLAND DESPRESFlight Line under modernization
HBasket Strainers (Section 3-6.4)
TA. Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. Investigate sudden drops or spikes in differential pressure measurement reading.DailyOM
TB. Clean and inspect basket and strainer screen. Basket strainer isolation valves shall be closed and the strainer body shall be drained before removing the cover. After cleaning, the strainer screen shall be inserted in the strainer body, and the head tightened and checked for leakage. If strainer is not equipped with means to measure differential pressure, unit shall be opened monthly and inspection.
Frequency: Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlySee DescriptionOM
TC. Refer to Section 6-7.2 Differential Pressure Gauges for inspection and maintenance requirements of differential pressure gauges.Reference to OtherSM
I3-6.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBSTRFiltrationCLK-0000020315-BSTR-0082TitanBS85 12103013 612103016"Completed2/12/26TREMAYNE DALEROLAND DESPRES
I3-6.4201FUEL FARM HOT PIT A/C REFUELFlight LineBSTRFiltrationCLK-0000020309-BSTR-0345Morrison Brothers Co286FDI3"Not Available2/12/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I3-6.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBSTRFiltrationCLK-0000020329-BSTR-0068TitanBS85 12103013 612103016"Completed2/12/26TREMAYNE DALEROLAND DESPRES
I3-6.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBSTRFiltrationCLK-0000020315-BSTR-0069TitanBS85 12103013 612103016"Completed2/12/26TREMAYNE DALEROLAND DESPRES
I3-6.4201FUEL FARM PUMP HOUSEBulk StorageBSTRFiltrationCLK-0000020317-BSTR-0070TitanBS85 H562600GPMCompleted2/12/26TREMAYNE DALEROLAND DESPRES
I3-6.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBSTRFiltrationCLK-0000020329-BSTR-0074TitanBS85 12103013 61210301600GPMCompleted2/12/26TREMAYNE DALEROLAND DESPRES
I3-6.4201FUEL FARM PUMP HOUSEBulk StorageBSTRFiltrationCLK-0000020317-BSTR-0076TitanBS85 H562600GPMCompleted2/12/26TREMAYNE DALEROLAND DESPRES
HPositive Displacement Meters (Section 3-7.1)
TA. Inspect counter head for unusual noises and smooth operation.MonthlyOM
TB. Positive displacement meters shall be inspected and calibrated semi-annually or when improper performance is suspected; when unusual sounds or register actions develop; or after repairs have been made which may affect performance. Positive displacement meters are satisfactory when the measurement error in the normal flow direction is within ±0.3% of actual quantity delivered (e.g., ±1.8 gallons for a 600-gallon test (±6.8 liters for a 2275-liter test)). Adjustment of the meter’s register will be in accordance with manufacturer’s instructions. Identify the next calibration date on meters (example: Mar 14 for March 2014). Use weather resistant label that will remain legible and affixed for at least one year.
Frequency: Calibration shall be done by SO if QAE requests an out of cycle calibration due to circumstances beyond normal operation.Semi-annuallySM
TC. Inspect temperature element operation of meters equipped with temperature compensation feature per manufacturer"s operation and maintenance manual.
Frequency: Or as required by manufactures" operation and maintenance manual.Semi-annuallySM
I3-7.1201FUEL FARM TNK TRCK OFF LOADBulk StoragePDMTMeter/calibrationsCLK-0000020329-PDMT-0096LectroCountE2658 48-166856350gpmCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM ARCRFT ISSUE STANDBulk StoragePDMTMeter/calibrationsCLK-0000020315-PDMT-0104LectroCountE2658 48-166856600GPMCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM TNK TRCK OFF LOADBulk StoragePDMTMeter/calibrationsCLK-0000020329-PDMT-0105LectroCountE2658 48-166856350GPMCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM TNK TRCK OFF LOADBulk StoragePDMTMeter/calibrationsCLK-0000020329-PDMT-0110LectroCountE2658 48-166856350GPMCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM ARCRFT ISSUE STANDBulk StoragePDMTMeter/calibrationsCLK-0000020315-PDMT-0117LectroCountE2658 48-166856600GPMCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM HOT PIT A/C REFUELFlight LinePDMTMeter/calibrationsCLK-0000020309-PDMT-0404Veeder-Root845693-2112885Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I3-7.1201FUEL FARM ARCRFT ISSUE STANDBulk StoragePDMTMeter/calibrationsCLK-0000020315-PDMT-0423LectroCountE2658 48-166856600GPMCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM TNK TRCK OFF LOADBulk StoragePDMTMeter/calibrationsCLK-0000020329-PDMT-0436LectroCountE2658 48-166856350gpmCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM TNK TRCK OFF LOADBulk StoragePDMTMeter/calibrationsCLK-0000020329-PDMT-0072LectroCountE2658 48-166856350gpmCompleted2/11/26TREMAYNE DALEROLAND DESPRES
I3-7.1201FUEL FARM TNK TRCK OFF LOADBulk StoragePDMTMeter/calibrationsCLK-0000020329-PDMT-0073LectroCountE2658 48-166856350gpmCompleted2/11/26TREMAYNE DALEROLAND DESPRES
HCentrifugal Pumps (Section 3-8.1)
TJ. Refer to Section 9-1.7 Electric Motors for inspection and maintenance requirements of electric motors.Reference to OtherSM
TA. Check for proper operations while pump is in use. Check suction and discharge pressure gauge for abnormal readings.QuarterlySM
TB. Check for unusual noise, vibration, overheating of bearings or case.QuarterlySM
TC. If equipped with lubricating oil charge, check oil level and adjust as necessary.QuarterlySM
TD. Tighten or replace loose, missing or damaged nuts, bolts, or screws.QuarterlySM
TE. Inspect suction and discharge isolation dampeners for misalignment and wear.QuarterlySM
TF. Inspect mechanical seals, if possible, for proper operating temperature, drips, leaks and dirt.QuarterlySM
TG. Check alignment, clearances, and rotation of shaft and coupler (requires removal of coupler shroud or cover).AnnuallySM
TH. Lubricate pump bearings.AnnuallySM
TI. If equipped with lubricating oil charge, drain old oil, and fill with new to full mark on sight indicator (also fill bulb).AnnuallySM
I3-8.1201FUEL FARM POL PIPELINE PUMPSBulk StorageCENPPumpCLK-00020317PS-CENP-0432Union PumpCM95343A-2UNKCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-8.1201FUEL FARM PUMP HOUSEBulk StorageCENPPumpCLK-0000020317-CENP-0433Union PumpCM95343A-1UNKCompleted2/10/26TREMAYNE DALEROLAND DESPRES
I3-8.1201FUEL FARM PUMP HOUSEBulk StorageCENPPumpCLK-0000020317-CENP-0437Union PumpCM95343A-1UNKCompleted2/10/26TREMAYNE DALEROLAND DESPRES
HLoading Fuel Hoses (Section 3-9.1)
TA. Visually inspect hoses for loose covers, cracks, brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement.WeeklyOM
TB. Pressurize hose to normal working pressure. Check flanged and threaded connections for leaks and inspect hose couplers for fluid seepage by pushing at the base of the coupling with your thumbs; a hose softened by fluid seepage must be replaced.WeeklyOM
TC. Check for coupling slippage. Replace hose that shows signs of coupling slippage.QuarterlySM
TD. Refer to Appendix D, Section D-2.1 Loading Hose Hydrostatic Test for loading hose hydrostatic testing requirements and procedures. The date of testing shall be stenciled on each hose. Hoses shall be removed from the system, and all accessories shall be removed from hoses prior to testing.AnnuallySM
TE. Conduct test of fuel hose electrical resistivity using an electrostatic meter in accordance with NFPA 77 & API 2003.AnnuallySM
I3-9.1201FUEL FARM HOT PIT A/C REFUELFlight LineLDHSHosesCLK-0000020309-LDHS-0041AlemitePREMIER3"X75'Not Available2/10/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I3-9.1201FUEL FARM ARCRFT ISSUE STANDBulk StorageLDHSHosesCLK-0000020315-LDHS-0047AlemitePREMIER3"X75'Completed2/10/26TREMAYNE DALEROLAND DESPRES
I3-9.1201FUEL FARM ARCRFT ISSUE STANDBulk StorageLDHSHosesCLK-0000020315-LDHS-0050AlemitePREMIER3"X10'Completed2/10/26TREMAYNE DALEROLAND DESPRES
HOffloading Fuel Hoses (Sections 3-9.2)
TA. Visually inspect hoses for cracks brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement.WeeklyOM
TB. Check flanged and threaded connections for leaks and inspect hose couplers for fluid seepage by pushing at the base of the coupling with thumbs; a hose softened by petroleum fluid seepage must be replaced. Damaged or leaking hoses shall be replaced immediately or isolated and taken out of service.
Note: Repairs should be performed by service order unless the repair is covered by the requirements of PWS Section 3.2.1.QuarterlySM
TC. Conduct test of offloading fuel hose electrical resistivity as directed in NFPA 77 and API 2003.AnnuallySM
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0043GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0044GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0046GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0049GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0059GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0060GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0061GOODYEARAPI 1529/20053"X10'Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0062GOODYEARAPI 1529/20053"X10'Repaired @ RM2/11/26TREMAYNE DALEEagle Drop Hose CPLD LeakingROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0065GOODYEARAPI 1529/20053"X10'Repaired @ RM2/11/26TREMAYNE DALEOffload Rack #1- Hose #2 (10 ft.) Eagle Drop Hose CPLD LeakingROLAND DESPRES
I3-9.2201FUEL FARM TNK TRCK OFF LOADBulk StorageOLHSHosesCLK-0000020329-OLHS-0066GOODYEARAPI 1529/20053"X10'Repaired @ RM2/11/26TREMAYNE DALEOffload Rack #1- Hose #3 (10 ft.) Eagle Drop Hose CPLD LeakingROLAND DESPRES
HAir Eliminator Tanks (Section 3-10.1)
TC. Refer to Section 8-9.3 Tank Pressure/Vacuum Vents for inspection and maintenance requirements of pressure vacuum vents.Reference to OtherSM
TA. Inspect operation of fuel level probes. Ensure probes operate correctly when the level of fuel in the tank rises to the level of the probe sensing unit.AnnuallySM
TB. Remove the float vent valve from the air eliminator tank. Clean and inspect the sealing surfaces of the float vent valve. Ensure the float is buoyant in fuel and test the valve to ensure it closes properly.AnnuallySM
I3-10.1201FUEL FARM PUMP HOUSEBulk StorageAELTPressure/Temperature ControlCLK-0000020317-AELT-0305Armstrong11AV4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM PUMP HOUSEBulk StorageAELTPressure/Temperature ControlCLK-0000020317-AELT-0308Armstrong11AV4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM PUMP HOUSEBulk StorageAELTPressure/Temperature ControlCLK-0000020317-AELT-0309Armstrong11AV4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM PUMP HOUSEBulk StorageAELTPressure/Temperature ControlCLK-0000020317-AELT-0310Armstrong11AV4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM PUMP HOUSEBulk StorageAELTPressure/Temperature ControlCLK-0000020317-AELT-0311Armstrong11AV4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM PUMP HOUSEBulk StorageAELTPressure/Temperature ControlCLK-0000020317-AELT-0330Armstrong11AV4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM TNK TRCK OFF LOADBulk StorageAELTPressure/Temperature ControlCLK-0000020329-AELT-0421ME Industries IncAEV3663008904"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I3-10.1201FUEL FARM TNK TRCK OFF LOADBulk StorageAELTPressure/Temperature ControlCLK-0000020329-AELT-0422ME Industries IncAEV3663008904"Completed2/11/26TREMAYNE DALEROLAND DESPRES
HDual Rate-of-Flow Control Valves (Section 4-3.2.8)
TC. Refer to Section 4-3.2.1 General System Control Valves for additional inspection and maintenance requirements.Reference to OtherSM
TA. Verify dual rate-of-flow control valve is set to maintain a flow rate of 200 gpm (12.5 lps).QuarterlySM
TB. Verify check valve feature is operational.QuarterlySM
I4-3.2.8201FUEL FARM PUMP HOUSEBulk StorageDRFCVLValvesCLK-0000020317-DRFCVL-0085Cla-Val150 PN166"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-3.2.8201FUEL FARM ARCRFT ISSUE STANDBulk StorageDRFCVLValvesCLK-0000020315-DRFCVL-0350Cla-Val150 PN164"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-3.2.8201FUEL FARM ARCRFT ISSUE STANDBulk StorageDRFCVLValvesCLK-0000020315-DRFCVL-0353Cla-Val150 PN166"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-3.2.8201FUEL FARM PUMP HOUSEBulk StorageDRFCVLValvesCLK-0000020317-DRFCVL-0354Cla-Val150 PN166"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-3.2.8201FUEL FARM PUMP HOUSEBulk StorageDRFCVLValvesCLK-0000020317-DRFCVL-0358Cla-Val150 PN166"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-3.2.8201FUEL FARM PUMP HOUSEBulk StorageDRFCVLValvesCLK-0000020317-DRFCVL-0360Cla-Val150 PN166"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-3.2.8201FUEL FARM PUMP HOUSEBulk StorageDRFCVLValvesCLK-0000020317-DRFCVL-0362Cla-Val150 PN166"Completed2/11/26TREMAYNE DALEROLAND DESPRES
HDefuel/Flush Valves (Section 4-4.2.3)
TF. Refer to Section 4-3.2.1 General System Control Valves for additional inspection and maintenance requirements.Reference to OtherSM
TA. Ensure Solenoids A and B are de-energized with system in automatic mode and lead pump operating.QuarterlySM
TB. Ensure Solenoid A is energized and Solenoid B is de-energized to allow main valve to open and drop system pressure to 80 psig (550 kPa) (typical set pressure) with system in automatic mode and lead pump off.QuarterlySM
TC. Ensure Solenoid A is de-energized and Solenoid B is energized when system is in flush mode.QuarterlySM
TD. Ensure Solenoids A and B are de-energized when system is in tightness test mode.QuarterlySM
TE. Check opening and closing speed. Speed should be as fast as possible while still maintaining smooth operation.QuarterlySM
I4-4.2.3201FUEL FARM TNK TRCK OFF LOADBulk StorageDFFCVLValvesCLK-0000020329-DFFCVL-0370Cla-Val3-72-35ACQSTKY6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
HPressure Control Valves (Section 4-4.2.7)
TG. Refer to Section 4-3.2.1 General System Control Valves for additional inspection and maintenance requirements.Reference to OtherSM
TA. Ensure Solenoid A is energized and Solenoid B is de-energized while system is in automatic mode and lead pump is operating.QuarterlySM
TB. Ensure Solenoids A and B are de-energized while system is in automatic mode and lead pump is off. Verify valve opens to maintain system pressure at 75 psig (515 kPa).QuarterlySM
TC. Ensure Solenoid A is energized and Solenoid B is de-energized while system is in flush mode and lead pump is operating.QuarterlySM
TD. Ensure Solenoids A and B are de-energized while system is in flush mode and pumps are off.QuarterlySM
TE. Ensure Solenoids A and B are energized while system is in tightness test mode.QuarterlySM
TF. Verify closing speed control. Valve should close as fast as possible while still maintaining smooth operation.QuarterlySM
I4-4.2.7201FUEL FARM TNK TRCK OFF LOADBulk StoragePCVLValvesCLK-0000020329-PCVL-0115Cla-Val4-59-14-KX4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-4.2.7201FUEL FARM TNK TRCK OFF LOADBulk StoragePCVLValvesCLK-0000020329-PCVL-0312Cla-Val4-59-14-KX4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-4.2.7201FUEL FARM PUMP HOUSEBulk StoragePCVLValvesCLK-0000020317-PCVL-0387Cla-Val2683101GNOT LEGIBLECompleted2/11/26TREMAYNE DALEROLAND DESPRES
I4-4.2.7201FUEL FARM HOT PIT A/C REFUELFlight LinePCVLValvesCLK-0000020309-PCVL-0413Cla-Val431-01-180600GPMNot Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I4-4.2.7201FUEL FARM PUMP HOUSEBulk StoragePCVLValvesCLK-0000020317-PCVL-0444Cla-Val2683101G6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-4.2.7201FUEL FARM PUMP HOUSEBulk StoragePCVLValvesCLK-0000020317-PCVL-0473Cla-Val2683101G6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-4.2.7201FUEL FARM PUMP HOUSEBulk StoragePCVLValvesCLK-0000020317-PCVL-0478Cla-Val2683101G6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I4-4.2.7201FUEL FARM PUMP HOUSEBulk StoragePCVLValvesCLK-0000020317-PCVL-0481Cla-Val2683101G6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
HFueling Nozzles (Section 4-7.4)
TA. Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use.QuarterlyOM
TB. Test leak resistance of poppet valve against full pump pressure. Unusual conditions found during this test indicate that repair is necessary and the nozzle shall be removed from service.QuarterlyOM
TC. Inspect storage racks for moisture or dirt accumulation. Correct conditions that may be attributing to accumulation of moisture or dirt in the storage racks.QuarterlyOM
TD. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. If a strainer ball valve is installed upstream of the nozzle only the strainer in the strainer ball valve needs to be check. Nozzles should not be used while strainers are removed from upstream strainer ball valves.QuarterlyOM
TE. Tests nozzle interlocks. Ensure interlocks prevent release of fuel when the fueling nozzle is not properly connected. Adjust the seating of the poppet valve if required.QuarterlyOM
TF. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand.QuarterlyOM
I4-7.4201FUEL FARM HOT PIT A/C REFUELFlight LineSRGSPPressure/Temperature ControlCLK-0000020309-SRGSP-0118Cla-ValD33"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I4-7.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageSRGSPPressure/Temperature ControlCLK-0000020315-SRGSP-0121Cla-ValD33/4"Completed2/11/206TREMAYNE DALEROLAND DESPRES
I4-7.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageSRGSPPressure/Temperature ControlCLK-0000020315-SRGSP-0124Cla-ValD33/4"Completed2/11/206TREMAYNE DALEROLAND DESPRES
HAboveground Piping (Section 6-1.3)
TD. Conduct cleaning of petroleum fuel piping in accordance with Section 6-2 General Pipeline Cleaning.
Note: This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.Reference to OtherSM
TA. Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.WeeklyOM
TB. Conduct petroleum fuel piping annual test as specified in Appendix G - Petroleum Fuel Pipeline Pressure Testing Guidelines and Criteria.
Note: This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.AnnuallySM
TC. Conduct petroleum fuel piping API 570 inspection in accordance with Section 6-1.9 API 570 Inspections.

Frequency: Every 5 or 10 years depending on API class piping or in accordance with Pipeline Integrity Management Plan (PIMP).

Note: This task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.See DescriptionSM
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0170Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0171Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0172Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0173Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0176Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0178Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM POL PIPELINEBulk StorageAGPLPipingCLK-0000020326-AGPL-0179Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0183Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0184Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0185Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
I6-1.3201FUEL FARM TNK TRCK OFF LOADBulk StorageAGPLPipingCLK-0000020329-AGPL-0186Cla-ValSTAINLESS STEEL4"Inspection OK2/10/26TREMAYNE DALEROLAND DESPRESThis task shall be performed by SO or another contract. The contractor shall identify when this task is required in the Facility Maintenance Plan.
HBall Valves (Section 6-6.2.4)
TE. Refer to Section 6-6.2.10 Manual Valve Gear Operators for inspection and maintenance of gear operators if equipped.Reference to OtherSM
TA. Open and close valve to check for ease of operation.QuarterlySM
TB. Lubricate overhead ball valve chain operator gears.QuarterlySM
TC. Adjust packing per manufacturer’s specifications.QuarterlySM
TD. Inspect valve exterior for corrosion and tightness of bolts. Repaint/tighten as required.
Note: Coating repairs performed under this item count as part of the requirement in PWS Section 3.2.1.2.QuarterlySM
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0086Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0089Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0094Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0095Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0098Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0101FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0102Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0103Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0106Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0112Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0116Velan200WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0119FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0120FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0122FLOTEKW8F34951Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0123FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0125FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0126FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0128FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0130Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0131FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0132FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0133FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0134FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0139Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0144Velan200WOG4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0145Velan200WOG4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0146Velan200WOG4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0147VelanCF8M6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0148Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0150VelanCF8111"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0151FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0156FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0157FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0161Velan200 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0162Velan200 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0164Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0165Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0167Velan200 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0168Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0169Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0174Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0177Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0181Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0182Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0187VelanCFM-83/4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0189Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0190FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0191Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0192Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0193Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0194Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0195Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0199Velan200 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0201Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0202Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0204FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0213FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0214FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0215FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0216Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0217Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0218FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0219FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0220FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0221FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0222Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0224Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0225Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0227Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0230Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0236Velan200 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0238FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0239FLOTEKSERIES 50005"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0240Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0243Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0244Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0245Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0246Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0248FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0249FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0250FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM HOT PIT A/C REFUELFlight LineBLVLValvesCLK-0000020309-BLVL-0251FLOTEKSERIES 50005"Not Available2/11/26TREMAYNE DALEROLAND DESPRESFlight Line under modernization
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0253Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0254Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0255Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0256FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0257FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0260FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0261Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020319-BLVL-0262FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM JP-8 STORAGE TANKBulk StorageBLVLValvesCLK-0000020318-BLVL-0267FLOTEKW8F34951"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0275Velan9996-0014"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0276Velan9996-0014"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0277Velan9996-0014"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0278Velan9996-0014"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0279Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0280Velan6-1506"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0281Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0282Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0284ApolloCF8M-TFE-3164"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0287Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0288Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0290CameronB8118"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0291Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0294Velan6-1506"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM ARCRFT ISSUE STANDBulk StorageBLVLValvesCLK-0000020315-BLVL-0295VelanCFM-83/4"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0296Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM PUMP HOUSEBulk StorageBLVLValvesCLK-0000020317-BLVL-0297Velan2000 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES
I6-6.2.4201FUEL FARM TNK TRCK OFF LOADBulk StorageBLVLValvesCLK-0000020329-BLVL-0299Velan200 WOG6"Completed2/11/26TREMAYNE DALEROLAND DESPRES

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .