XRF Lead Report_WH-16_ p.1

Defense Logistics Agency - San Joaquin Tracy, California

XRF Lead Evaluation

Date: 14 June 2017 Subject: Field Analysis for Suspect Lead Paint Bulk Sample Collected from the DLASJ Tracy, Warehouse 16

Evaluation

On 14 June 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Warehouse 16. Robert Miller, Certified Industrial Hygienist, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Warehouse 16 is provided in Table 1 of this report.

Table 1 Sample Number

Coating / Paint Description Lead Concentration

0614-16-01 Building Interior: Beige on drywalls (Cafeteria) Non-Detect (ND) 0614-16-02 Building Interior: Beige on drywalls (Kitchen) ND 0614-16-03 Building Exterior: Tan on guardrails ND 0614-16-04 Building Exterior: Blue on trim on north windows and door metal

ND

0614-16-05 Building Exterior: Yellow on stair rails ND 0614-16-06 Warehouse Exterior: Blue on trim around roll-up doors >5.0 mg/cm2 0614-16-07 Warehouse Exterior: White on concrete walls ND 0614-16-08 Warehouse Exterior: Yellow on steel dock bumpers >5.0 mg/cm2 0614-16-09 Warehouse Exterior: Yellow on wood bumpers on docks ND 0614-16-10 Warehouse Exterior: Yellow on steel stair railings ND 0614-16-11 Warehouse Interior: White on concrete walls ND 0614-16-12 Warehouse Interior: Blue on concrete walls ND 0614-16-13 Warehouse Interior: Red on floors ND 0614-16-14 Warehouse Interior: Tan on bollards ND 0614-16-15 Warehouse Interior: Safety yellow on concrete floors ND 0614-16-16 Warehouse Interior: Yellow columns by former fire doors >5.0 mg/cm2 0614-16-17 Warehouse Interior: Yellow on metal spiral stairs (Section

A3)

ND

0614-16-18 Warehouse Interior: Blue on perimeter metal pedestrian doors

ND

0614-16-19 Warehouse Interior: Yellow on concrete floor (Section 5;

worn)

>4.3 mg/cm2

XRF Lead Report_WH-16_ p.2

0614-16-20 Warehouse Interior: Black coating on floor (Section 5;

worn)

>5.0 mg/cm2

0614-16-21 Warehouse Interior: Green on floor (eyewash) >1.5 mg/cm2 0614-16-22 Warehouse Interior: Black paint on floor (Sections B4 &

B3)

ND

0614-16-23 Warehouse Interior: Green chips on wall ND 0614-16-24 Warehouse Interior: Black paint on floor (Section B2;

worn) >1.0 mg/cm2

0614-16-25 Warehouse Interior: Yellow on floor (Section B2; worn) >2.70 mg/cm2

Discussion

The field testing of the coatings associated with the DLASJ Tracy, Warehouse 16, did identify Lead concentrations that are described in Table 1 of this report. The Federal OSHA 16 CFR

1926.62 and 16 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.

Recommendations

• Any activity that may include the disturbance of Lead-containing materials must be performed within the regulations set forth in Federal OSHA 16 CFR 1926.62, 16 CFR

1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.

• Disposal of any building materials that are coated with Lead-containing paint must be disposed of per the requirements of the DS-FJ Installation Support Environmental Office.

Robert Miller, CIH Certified Industrial Hygienist

Lonny Jones

Industrial Hygiene Technician

XRF Lead Report_WH-22_ p.1

Date: 06 July 2017

Warehouse 22

Evaluation

On 06 July 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Warehouse 22. Robert Miller, Certified Industrial Hygienist, and Lonny Jones, Industrial Hygiene Technician, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Warehouse 22 is provided in Table 1 of this report.

Number

Coating / Paint Description Lead Concentration

0706-22-01 Exterior: Steel support for canopy Non-Detect (ND) 0706-22-02 Exterior: Light gray on concrete wall, Section 1 >1.0 mg/cm2 0706-22-03 Exterior: Yellow on handrail by stairs > 5.0 mg/cm2 0706-22-04 Exterior: Yellow on stairs to Box Shop entrance ND 0706-22-05 Exterior: Yellow on stair risers to dock ND 0706-22-06 Exterior: Blue on metal pedestrian door >5.0 mg/cm2 0706-22-07 Exterior: Blue on downspout 2.60 mg/cm2 0706-22-08 Exterior: Yellow on metal dock trim >5.0 mg/cm2 0706-22-09 Exterior: Yellow on wooden bumpers on dock >5.0 mg/cm2

0706-22-10 & 0706-22-33

Exterior: Yellow on floor around conveyors, on exterior dock and interior floor

1.17 mg/cm2

0706-22-11 Exterior: Blue on overhead door trim >5.0 mg/cm2 0706-22-12 Exterior: Light blue on concrete walls ND

-- Exterior: Blue paint on the steel beams at 450 angles located above canopy

Assumed Lead- Containing

-- Exterior: Gray coated steel I-beams beneath canopy, significant blistering

Assumed Lead- Containing

-- Exterior: Light gray throughout underside of canopy, significant blistering

Assumed Lead- Containing

0706-22-13 Bubble Interior: White on concrete walls ND 0706-22-14 Bubble Interior: Blue on concrete walls ND 0706-22-15 Bubble Interior: Blue on restroom door frames ND

XRF Lead Report_WH-22_ p.2

0706-22-16 Bubble Interior: White on interior downspouts ND 0706-22-17 Bubble Interior: Blue on metal pedestrian doors ND 0706-22-18 Bubble Interior: White on drywall in Breakroom ND 0706-22-19 Bubble Interior: White on concrete walls in Breakroom ND 0706-22-20 Bubble Interior: White on door frames in Offices ND 0706-22-21 Bubble Interior: White on walls in South Breakroom ND 0706-22-22 Bubble Interior: White on restroom walls ND 0706-22-23 Warehouse Interior: Coated steel I-Beams >5.0 mg/cm2 0706-22-24 Warehouse Interior: White on concrete walls 1.58 mg/cm2 0706-22-25 Warehouse Interior: Blue on concrete walls 2.60 mg/cm2 0706-22-26 Warehouse Interior: Fire red on concrete floors ND 0706-22-27 Warehouse Interior: Yellow on metal trims on former fire door frames >5.0 mg/cm2

0706-22-28 & 0706-22-31

Warehouse Interior: Black on concrete floors ND

0706-22-29 Warehouse Interior: Red on fire risers ND 0706-22-30 Warehouse Interior: Safety yellow on concrete floors ND 0706-22-32 Warehouse Interior: Green on concrete wall by former fire doors

ND

The field testing of the coatings associated with the DLASJ Tracy, Warehouse 22, did identify Lead concentrations that are described in Table 1 of this report. The Federal OSHA 29 CFR

1926.62 and 29 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.

Recommendations

• Any activity that may include the disturbance of Lead-containing materials must be performed within the regulations set forth in Federal OSHA 29 CFR 1926.62, 29 CFR

1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.

XRF Lead Report_WH-28_ p.1

Date: 27 June 2017

Warehouse 28

Evaluation

On 27 June 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Warehouse 28. Robert Miller, Certified Industrial Hygienist, and Lonny Jones, Industrial Hygiene Technician, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Warehouse 28 is provided in Table 1 of this report.

Number

Coating / Paint Description Lead Concentration

0627-28-01 Warehouse Exterior: Blue on concrete walls Non-Detect (ND) 0627-28-02 Warehouse Exterior: Yellow on handrails at stairwell ND 0627-28-03 Warehouse Exterior: Yellow on I-beam bumpers on west dock

ND

0627-28-04 Warehouse Exterior: Blue on metal pedestrian door ND 0627-28-05 Warehouse Exterior: Blue on dock leveler ND 0627-28-06 Bubble Interior: White on walls ND 0627-28-07 Bubble Interior: White on pedestrian doors ND 0627-28-08 Warehouse Interior: White on walls ND 0627-28-09 Warehouse Interior: Yellow on former fire door columns >5.0 mg/cm2 0627-28-10 Warehouse Interior: Yellow on bumper around vent ND 0627-28-11 Warehouse Interior: Yellow on cargo door (peeling) ND 0627-28-12 Warehouse Interior: Red on fire risers ND 0627-28-13 Warehouse Interior: Red on steel I-beams ND 0627-28-14 Warehouse Interior: Red on concrete base of I-beam >5.0 mg/cm2 0627-28-15 Warehouse Interior: Yellow on guardrails ND 0627-28-16 Warehouse Interior: Safety yellow on floor ND 0627-28-17 Warehouse Interior: Yellow on steel beams, “Recoup” area ND 0627-28-18 Warehouse Interior: White on walls, “Recoup” hallway ND 0627-28-19 Warehouse Interior: Yellow on wood bumpers on docks ND 0627-28-20 Warehouse Interior: Yellow on steel I-beams (Section 4A) ND

XRF Lead Report_WH-28_ p.2

The field testing of the coatings associated with the DLASJ Tracy, Warehouse 28, did identify

Lead concentrations that are described in Table 1 of this report. The Federal OSHA 29 CFR

1926.62 and 29 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.

Recommendations

• Any activity that may include the disturbance of Lead-containing materials must be performed within the regulations set forth in Federal OSHA 29 CFR 1926.62, 29 CFR

1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.