This document is a comprehensive set of electrical calculations for the Togus VA Medical Center Laundry HVAC Replacement project, prepared by Miller-Remick LLC. The calculations include a detailed electrical load calculation and a lightning protection risk assessment. The electrical load calculation breaks down power requirements for multiple equipment tags, including HVAC units, heating units, and other mechanical systems, with voltages ranging from 120V to 208V and loads varying from 2.2 to 331.8 amps. The total new mechanical connected load is calculated at 176.47 kVA, with a grand total building demand of 246.26 kVA, using an existing service transformer sized at 300.00 kVA. The lightning protection risk assessment, using NFPA 780 standards, indicates that a lightning protection system is not required for this facility based on the calculated risk factors.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Standard Mounting Hole Pattern Typical for single or double wide panel
Standard Mounting Hole Pattern with Corner Holes Typical for single or double wide panel
DEPARTMENT OF VETERANS AFFAIRS VA PROJECT NO. 402-22-755
TOGUS VA MEDICAL CENTER REPLACE LAUNDRY HVAC
AUGUSTA, ME 90% DESIGN SUBMISSION: 01/27/23
MILLER-REMICK LLC D2-1 CHERRY HILL, NEW JERSEY
APPENDIX D2
MECHANICAL - LOADS
Project Information
System Checksums
Zone Checksums
Room Checksums
Peak Cooling Load
Engineering Load
Load Airflow Summary
DEPARTMENT OF VETERANS AFFAIRS VA PROJECT NO. 402-22-755
TOGUS VA MEDICAL CENTER REPLACE LAUNDRY HVAC
AUGUSTA, ME 90% DESIGN SUBMISSION: 01/27/23
MILLER-REMICK LLC D2-2 CHERRY HILL, NEW JERSEY
THIS PAGE INTENTIONALLY LEFT BLANK