Atch 3 Gen Spec.pdf
PDF 7 MB Posted
- Attached to
- Replace Generators Building 600
- Solicitation number
- SolFA2550-10-R-1001
About this file
Questions Answers Attachment 3
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SolFA2550-10-R-1001-0002.doc | DOC document | |
| SOW 1 April 2010.rtf | RTF text file | |
| SOW Install Three Generators B600 | — | |
| FA2550-10-R-1001-0001.doc | DOC document | |
| SolFA2550-10-R-1001 Questions Answers.docx | DOCX document | |
| Atch 2 Tech Sub.pdf | ||
| Atch 4 Gen Serv Inf.pdf | ||
| Atch 1 Elevation Drawing.pdf | ||
| SOW Install Three Generators B600.rtf | RTF text file | |
| Wage Determination 01-08-2010.docx | DOCX document | |
| SOLFA2550-10-R-1001.doc | DOC document | |
| PAST PERFORMANCE QUESTIONNAIRE.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A P P L I C A T I O N A N D I N S T A L L A T I O N G U I D E
EMCP 3.1, 3.2, 3.3
GENERATOR SET CONTROL
LEBE5255-01
Table of Contents
1 GENERAL INFORMATION
1.1 COMPANION MEDIA NUMBER
1.2 INTRODUCTION
1.3 APPLICATIONS
1.4 REFERENCES
2 SAFETY INFORMATION
2.1 ELECTRICAL SAFETY
2.2 ELECTROSTATIC DISCHARGE AWARENESS
3 INSTALLATION
3.1 MOUNTING LOCATION
3.2 OPERATING TEMPERATURE RANGE
3.3 POWER REQUIREMENTS
3.4 BATTERY CHARGER
3.5 ELECTRICAL CONNECTIONS
3.6 EUI ENGINES
3.7 EMCP 3.1, 3.2, 3.3 ELECTRICAL DIAGRAMS
3.8 WINDING CONNECTIONS
3.9 TRANSFORMER CONNECTIONS
3.10 WIRING REQUIREMENTS
3.11 SHIELDED WIRING
4 INITIAL OPERATION AND USER ORIENTATION
4.1 VIEWING SYSTEM PARAMETERS
SUPPORTED PARAMETERS
Engine Parameters AC Parameters
4.2 SETTING USER PREFERENCES
Setting The Preferences Using The EMCP 3 Display Changing To Technician English Changing To Primary Language Setting the Preferences using the Service Tool
4.3 CONFIGURING TIME/DATE (EMCP 3.2 AND 3.3)
Changing Date Format Changing The Time / Date
4.4 ADJUSTING GENERATOR SET PARAMETERS
Engine Speed Generator Output Voltage Idle/Rated
4.5 STARTING AND STOPPING THE GENERATOR SET
Starting The Engine Stopping The Engine
4.6 ENGINE SETPOINT VERIFICATION
Procedure For Overspeed Verification Procedure For Low Oil Pressure Verification Procedure For High Coolant Temperature Verification
4.7 ENGINE SPEED TIMING CALIBRATION - PREPARATION
4.8 ENGINE OPERATING HOURS
Updating Engine Operating Hours
5 HANDLING EVENTS
5.1 CONFIGURING EVENT RESPONSES
5.2 CHANGING AN EVENT RESPONSE CONFIGURATION
5.3 RESETTING INDIVIDUAL EVENTS FOR THE EMCP 3 GSC
5.4 RESETTING ALL EVENTS FOR A SINGLE MODULE
5.5 RESETTING ALL EVENTS FOR ALL MODULES
5.6 RESETTING EVENTS FOR ENGINE ECMS WITHOUT J1939 SUPPORT
5.7 TROUBLESHOOTING RESETTING EVENTS
Not in Auto Service Maintenance Interval
6 SECURITY
7 SETPOINTS
7.1 THREE TYPES OF SETPOINTS
7.2 SETPOINT SUB-MENUS
7.3 SETPOINTS ON THE CATERPILLAR SERVICE TOOL
8 DIGITAL INPUTS
8.1 PROGRAMMING THE DIGITAL INPUTS
9 ANALOG INPUTS
Programming Using Display Programming Using Caterpillar Service Tool
9.1 SPARE ANALOG INPUT (EMCP 3.2 & 3.3)
10 OUTPUTS
10.1 DIGITAL SELECTOR OPTIONS
10.2 PROGRAMMING OUTPUTS USING THE SERVICE TOOL
10.3 PROGRAMMING OUTPUTS USING THE DISPLAY
11 MODIFIABLE TEXT STRINGS
11.1 LANGUAGE SUPPORT
11.2 MODIFIABLE TEXT STRING CONFIGURATION FILE
11.3 PROGRAMMING MODIFIABLE TEXT STRINGS USING CATERPILLAR SERVICE TOOL
11.4 TROUBLESHOOTING MODIFIABLE TEXT STRINGS
12 SAVING AND RESTORING SETPOINTS
12.1 SAVING EMCP 3 CONFIGURATION DATA
Fleet Configuration Option ECM Replacement option
12.2 LOADING EMCP 3 CONFIGURATION DATA
13 PROGRAMMABLE CYCLE TIMER (EMCP 3.2 & 3.3)
13.1 CONTROLLING THE OUTPUTS
Internal Outputs
14 REDUCED POWER MODE
15 PROGRAMMABLE TRIP POINT FUNCTION
16 J1939 DATA LINKS
16.1 PRIMARY J1939 DATA LINK
Primary J1939 Wiring Network Topology
16.2 ACCESSORY J1939 DATA LINK (EMCP 3.2 & 3.3)
Accessory J1939 Wiring Network Topology
17 OPTIONAL MODULES
J1939 compliance
17.1 ANNUNCIATOR
Annunciator Features Annunciator Specifications Annunciator Wiring LED Colors Annunciator Software Configuration
17.2 THERMOCOUPLE MODULE (EMCP 3.3)
Thermocouple Features Thermocouple Specifications Thermocouple wiring Thermocouple Physical Layout Thermocouple Module – Configuration Configuring Thermocouple Inputs
17.3 RTD MODULE (EMCP 3.3)
RTD Features RTD Specifications RTD Wiring RTD Module – Configuration Configuring RTD Inputs
17.4 DISCRETE I/O MODULE
Discrete I/O Features Discrete I/O Specifications Discrete I/O Software Configuration Configuring Digital Inputs Configuring Relay Outputs
18 SCADA (MODBUS) DATA LINK (EMCP 3.2 & 3.3)
Wiring Line Termination Software Configuration Message Data Structure Communication Supported Function Codes Data Link Register Addresses Error Checking Exception Responses Fault Identifiers (FID)
19 MONITORING SOFTWARE (EMCP 3.2 & 3.3)
19.1 SOFTWARE SETUP
19.2 QUICK START GUIDE
19.3 CREATING A CONTROL PANEL VIEW
19.4 LOGGING DATA TO A FILE
20 INSTALLING & UPGRADING SOFTWARE
20.1 UPGRADING SOFTWARE
20.2 INSTALLING SOFTWARE INTO A BLANK MODULE
21 SCADA PARAMETER INFORMATION (EMCP 3.2 & 3.3)
21.1 DATA LINK SECURITY
21.2 SPARE ANALOG INPUT
21.3 DISCRETE INPUTS AND OUTPUTS
21.4 GENERATOR AC PARAMETERS
21.5 EXTERNAL DEVICE PARAMETERS
21.6 GENERATOR SET STATE CONTROL
21.7 TIMERS AND COUNTERS
21.8 EVENT SYSTEM
21.9 ENGINE MONITORING
21.10 EMCP 3 GSC SETPOINTS
21.11 MISCELLANEOUS
APPENDIX A SCADA PROGRAMMING EXAMPLES
Reading Data Registers Engine Status SCADA Security Levels More notes on SCADA passwords Setpoint Interpretation and Calculation Reading and Writing AVR Registers and Setpoints
APPENDIX B ALPHABETIC REFERENCE OF MODBUS REGISTERS
APPENDIX C BLOCKS FOR SETPOINT CONFIGURATION
APPENDIX D SETPOINT INFORMATION FOR CONFIGURATION
APPENDIX E SETPOINT VALUE LISTS
APPENDIX F BITMASK VALUE LISTS
APPENDIX G MENU STRUCTURES
APPENDIX H EMCP 3 GSC WIRING DIAGRAMS
APPENDIX I EMCP 3 GSC FRONT VIEW & NAVIGATION KEYS
GLOSSARY OF TERMS ……………………………...…………..………...…………………
Foreword
This Application and Installation Guide describes the EMCP 3.1, 3.2, and 3.3 series electrical power generator set controls.
Some data used in this guide is generalized and is provided only for the purpose of comparison or illustration. Also, PC application screenshots and EMCP 3 GSC screen images may be actual screens or simulated and are shown for illustrative purposes only. These images may not be identical to those seen by the user. Screen images of the EMCP 3 GSC may differ from the actual screens depending on flash file language, setpoint configuration, or series of the GSC (3.1 versus 3.2 versus 3.3).
In various places throughout this document, reference is made to the release date of the EMCP 3 software. This information can be found by connecting to the subject module using the Caterpillar® Service Tool, and viewing the ECM Summary (this is the default startup screen).
The release date is found in the field entitled Software Group Release Date. See the sample screenshot below, showing the release date for a Thermocouple module.
Other product specific information and data is available from a variety of sources. For more information contact to the Caterpillar dealer or dealer TC nearest you.
To visit the Cat® Electronics website: www.catelectronics.com
The information in this document is the property of Caterpillar Inc. and/or its subsidiaries. Any copying, distribution, transmission to others, and any use except that for which it is loaned is prohibited without written permission.
CAT®, CATERPILLAR®, EMCPTM, ADEMTM, their respective logos and Caterpillar Amber, as well as corporate and product identity used herein, are trademarks of Caterpillar Inc. and may not be used without permission.
1 GENERAL INFORMATION
1.1 COMPANION MEDIA NUMBER
This document has media number, LEBE5255.
It also has a companion media number, LERE5255. If only one of the media numbers is ordered, the other is shipped automatically, but separately. LERE5255 is a mini-CD that contains printable files of schematics found in this document on pages 112,13,14 1, APPENDIX H (page 248).
1.2 INTRODUCTION
Caterpillar® has developed a product line of Generator Set Controls for use in the Electronic Modular Control Panel 3 (EMCP 3). They are available in three versions based on Generator Set Control feature sets.
The EMCP 3 Generator Set Control, or GSC, is the primary controller within the Generator Set Control system. It contains the primary operator and service interface. The inset photo shows an up-close view of the EMCP 3.3. The EMCP 3 line of Generator Set Controllers includes EMCP 3.1, 3.2, and 3.3. APPENDIX I shows a full view of the EMCP 3.3.
This Application and Installation Guide is intended to cover the EMCP 3 Generator Set Control and its application in generator set systems. The intended audience for this guide includes Caterpillar generator set system designers, Caterpillar service support personnel, Caterpillar Dealers and Service Technicians, contractors, and customers.
1.3 APPLICATIONS
The EMCP 3 GSC product line of generator set controllers is designed for use in a wide range of applications. They can be used on standby and prime power diesel generator sets including Caterpillar®, FG Wilson®, and Olympian® brands. The configurability of the controllers allows them to be used, in some cases, on other applications such as Marine auxiliary generators, switchgear applications, industrial engines and generator sets, and gas generator sets.
Most of the information in this document applies to all applications. However, the document was written with Caterpillar brand diesel generator sets in mind. Please contact your Caterpillar support representative for questions regarding different applications.
1.4 REFERENCES
The following list of literature is available for EMCP 3 Generator Sets.
RENR7902 EMCP 3 Systems Operation Troubleshooting Testing and Adjusting SEBU7898 C18 Generator Set Operation and Maintenance Manual SEBU7509 3500 Generator Sets Operation and Maintenance Manual SEBU7508 3500B Generator Sets Operation and Maintenance Manual
2 SAFETY Information
2 SAFETY INFORMATION
2.1 ELECTRICAL SAFETY
DO NOT operate or work on a generator set unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings could result in injury or death. Contact any Caterpillar dealer for replacement manuals. Proper care is your responsibility.
2.2 ELECTROSTATIC DISCHARGE AWARENESS
EMCP 3 GSC control contains components that are sensitive to ELECTROSTATIC DISCHARGE (ESD). An electrostatic charge can damage the control resulting in EMCP 3 GSC breakdown or improper operation.
Take the following precautions while installing/removing/handling the control:
• Handle equipment correctly. Use ESD protective packaging and material handling containers that are anti-static and provide discharge protection and electric field suppression.
• Use protective devices: ESD-protective workstations and/or work surfaces (grounding mat, anti-static wrist strap, etc).
• Keep all plastic items away from the devices. Any plastic item is a potential static generator. This includes candy wrappers, foam cups, synthetic carpet, foam cushions, etc.
• The anti-static bag cannot function as a static dissipating mat.
• DO NOT use an anti-static bag for any other purpose than to enclose a product.
CAUTION: The 70-pin connector on the back of the control is the most vulnerable area to ELECTROSTATIC DISCHARGE (ESD). While handling the EMCP 3 GSC, extra attention is required to the back of the control. The control may become damaged or inoperable if extra care is not taken.
Consult the Electrostatic Discharge Association for proper procedure during particular situations: http://www.esda.org http://www.esda.org/
3 INSTALLATION
3 INSTALLATION
3.1 MOUNTING LOCATION
When selecting a mounting location for the EMCP 3 GSC, consider the following:
• Protection from high-voltage and high-current devices.
• Protection from devices which may produce electromagnetic interference.
• Protection from excessive vibration. The controls are designed to withstand normal generator set vibrations. The controls should not be mounted directly to the engine block.
• Protection from direct exposure to water. Once installed, the EMCP 3.1, 3.2, and 3.3 are sealed to a level of IP Level 22 for resistance to moisture.
3.2 OPERATING TEMPERATURE RANGE
EMCP 3 GSC has a continuous operating temperature range of –20°C to +70 °C ambient.
3.3 POWER REQUIREMENTS
The EMCP 3 GSC requires a nominal voltage of 12 V DC or 24 V DC. If batteries are used for operating power, a charging source such as an alternator or dual-mode battery charger is necessary to maintain a stable supply voltage. Under steady state operation, the EMCP 3 GSC will draw approximately 0.5 A to 1.5 A current draw (not including any relay loads).
Regional electrical codes must be followed. In the case of standby operation, follow the regional requirements for installing standby power systems. An example of this is the National Fire Protection Association (NFPA) guidelines for emergency power systems.
When connecting the EMCP 3 GSC to the DC power source, make sure that there is only one common connection to the negative potential of the power source. Make extra effort to avoid any ground loops in the DC electrical system. A single point common ground for sensitive electronics is recommended at the negative battery terminal or Power Distribution Box.
Avoid daisy-chaining power supply connections from one device to another. This builds resistance from one (-)Battery point to the next, effectively building a potential difference between two different reference points. Each electronics subsystem and major engine subsystem should have its own DC network so that they do not interfere with each other (see
FIGURE 1).
As shown in FIGURE 1, all sensitive electronics are electrically isolated from higher current loads, such as the starter motor. All electronics have a COMMON POWER BUS and SINGLE POINT REFERENCE. The CHASSIS GROUND is a common POWER AND TRANSIENT GROUND.
The sensitive electronics, such as sensors and control modules, have isolated power source paths. High current loads such as starters and solenoids can cause interference and possibly damage to low current loads, such as controllers and sensors.
CAUTION: Extra effort must be made to keep the high current and low current loads electrically separated.
FIGURE 1: GENERATOR SET NETWORK ISOLATION
The two types of loads may share common Battery (+) and Battery (–) connections but, they should not be electrically connected at any other point. This strategy ensures maximum isolation between high current and low current loads.
The battery DISCONNECT SWITCH is located on the negative leg of the battery supply.
3.4 BATTERY CHARGER
If a battery charger is to be used, it should be connected on the battery side of the disconnect switch, so as not to power the electronics. Most battery chargers are not to be used as power supplies. Proper battery charger operation requires that the actual battery load is present.
3.5 ELECTRICAL CONNECTIONS
The EMCP 3 GSC has one 70-pin connector on the back of the control and not all of the 70 pins are used.
FIGURE 2, FIGURE 3, and FIGURE 4 show:
• All possible connections
• What pins are used for connections
• How each pin is connected for each control version
3.6 EUI ENGINES
For EUI engines, the PASSIVE ANALOG INPUTS #1 and #2 will NOT be used. These are for discrete oil pressure and coolant temperature sensors, respectively. These sensors will be wired to the engine ECM and the EMCP 3 GSC will get that information from the engine ECM via the Primary J1939 Data Link.
For more information about the passive inputs, see Chapter 9, ANALOG INPUTS.
ANALOG CONNECTIONS
The 70-pin connector wiring diagrams below, also, show two different ways to connect the analog inputs.
• Connections for 2-wire sensors are shown (including all of the other connections).
• Connections for 1-wire sensors are shown at the bottom right hand side of the figures.
DISCRETE INPUTS
The discrete inputs are shown connected through NORMALLY OPEN contacts to battery negative.
These inputs can also be connected through NORMALLY CLOSED contacts to battery negative. To do this the ACTIVE STATE of the input will need to be set to ACTIVE HIGH.
For information on software configuration of the digital inputs see Chapter 8, Digital Inputs.
3.7 EMCP 3.1, 3.2, 3.3 ELECTRICAL DIAGRAMS
FIGURE 2: EMCP 3.1 ELECTRICAL DIAGRAM
(Refer to APPENDIX H EMCP 3 GSC for printable image)
FIGURE 3: EMCP 3.2 ELECTRICAL DIAGRAM
FIGURE 4: EMCP 3.3 ELECTRICAL DIAGRAM
3.8 WINDING CONNECTIONS
The connections between the generator and the EMCP 3 GSC depend on the winding configuration as shown in the connection diagrams below.
FIGURE 5: THREE PHASE FOUR WIRE (SERIES OR PARALLEL) WYE (STAR)
FIGURE 6: THREE PHASE FOUR WIRE DELTA
FIGURE 7: THREE PHASE THREE WIRE DELTA
FIGURE 8: SINGLE PHASE THREE WIRE (DOUBLE DELTA)
FIGURE 9: SINGLE PHASE TWO WIRE (DOUBLE DELTA)
3.9 TRANSFORMER CONNECTIONS
In order to monitor generator output voltages greater than 600 Volts, external potential transformers must be used.
NOTE: The EMCP 3 GSC must be programmed for the correct winding ratios when connecting external potential transformers. See Chapter 7, Setpoints for more information on how to program the winding ratios.
CAUTION: The WYE configuration of external potential transformers is preferred for 4-wire wye generators because of the greater accuracy when loads are unbalanced.
With the open delta configuration, some power parameters can not be determined. These parameters are real power phase A, B, C and power factor phase A, B, C. For maximum accuracy, the open delta configuration of external potential transformers should be used only for 3-wire delta generators. Refer to Table 1: Power Values Valid by Generator Configuration, page 17.
FIGURE 10: WYE CONFIGURATION OF EXTERNAL POTENTIAL TRANSFORMERS
(PT) on the 4-Wire Wye Connected Generator
FIGURE 11: OPEN DELTA CONFIGURATION OF EXTERNAL POTENTIAL TRANSFORMERS
(PT) on the 3-Wire Delta Connected Generator
FIGURE 12: OPEN DELTA CONFIGURATION OF EXTERNAL POTENTIAL TRANSFORMERS
(PT) on the 4-Wire Wye Connected Generator
TABLE 1: POWER VALUES VALID BY GENERATOR CONFIGURATION
TRANSFORMER CONNECTIONS
Parameter Modbus Register STAR 3-WIRE
DELTA
4-WIRE
DELTA
2-WIRE
1-PHASE
3-WIRE
1-PHASE
Gen Freq 102 OK OK OK OK OK
VL-L AVG 100 OK OK OK OK OK
VA-B 108 OK OK OK OK OK
VB-C 109 OK OK OK Invalid Invalid VC-A 110 OK OK OK Invalid Invalid VL-N AVG 148 OK Invalid OK Invalid OK VA 114 OK Invalid OK Invalid OK VB 115 OK Invalid OK Invalid OK VC 116 OK Invalid OK Invalid Invalid
IAVG 101 OK OK OK OK OK
IA 111 OK OK OK OK OK
IB 112 OK OK OK OK OK
IC 113 OK OK OK Invalid Invalid
3.10 WIRING REQUIREMENTS
Use the tables below for wiring requirements at 50 and 300 foot lengths.
TABLE 2: 50 FOOT REQUIREMENTS
50 FOOT REQUIREMENTS
Component Wire Size
(AWG)
Type of Wire Connections (1)
Three-Wire Sensors (when applicable.
Not used on all systems)
Shielded twisted triad cable is recommended.
For conduits inside facilities, use Belden 8618. For the engine harness, use the 4G- 2556 Shielded Cable. The cable must be resistant to fuel and oil. The cable must have a temperature range from -40ºC (-40ºF) to plus 125ºC (257ºF).
Two-Wire Components (Magnetic Speed Sensors) or
Shielded twisted pair cable is recommended.
For conduits inside facilities, use the 123- 2376 Electrical Cable or the 3E-4594 Electrical Cable. For the engine harness, use the 6V-2744 Wire. The cable must be resistant to fuel and oil. The cable must have a temperature range of -40ºC (-40ºF) to plus 125ºC (257ºF).
Deutsch DT type of connectors are recommended. If Spring Spade or Ring Terminals are used, the connection between the terminals and the wire should be crimped and soldered.
Engine Solenoids (Air Shutoff)
Power 10
Stranded wire normally used on engine harnesses. The cable must be resistant to fuel and oil. The cable must have a temperature range of -40ºC (-40ºF) to plus 125ºC (257ºF).
The leads of the cable should have Spring Spade Terminals or Ring Terminals. The Connection between the wire and the terminal should be
(1) The number of connections must be kept to a minimum.
TABLE 3: 300 FOOT REQUIREMENTS
300 FOOT REQUIREMENTS
Component Wire Size
(AWG)
Type of Wire Connections (1)
Three-Wire Sensors (when applicable.
Not used on all systems)
Shielded twisted triad cable is recommended.
For conduits inside facilities, use Belden 8618.
For the engine harness, use the 4G-2556 Shielded Cable. The cable must be resistant to fuel and oil. The cable must have a temperature range from -40ºC (-40ºF) to plus 125ºC (257ºF).
Deutsch DT type of connectors are recommended. If Spring Spade or Ring Terminals are used, the connection between the terminals
300 FOOT REQUIREMENTS
Component Wire Size
(AWG)
Type of Wire Connections (1)
Two-Wire Components (Magnetic Speed Sensors) or
Shielded twisted pair cable is recommended.
For conduits inside facilities, use the 123-2376 Electrical Cable or the 3E-4594 Electrical Cable. For the engine harness, use the 6V- 2744 Wire. The cable must be resistant to fuel and oil. The cable must have a temperature range of -40ºC (-40ºF) to plus 125ºC (257ºF).
and the wire should be
J1939 Data Link cable or
Part number 153-2707 is available for lengths of up to 200ft. The cable has a temperature range of -40ºC (-40ºF) to plus 125ºC (257ºF).
For longer runs, select a cable that meets SAE J1939-11 requirements.
Deutsch DT type of connectors are recommended. If Spring Spade or Ring Terminals are used, the connection between the terminals and the wire should be crimped and soldered.
Engine Solenoids (Air Shutoff)
Power
Stranded wire normally used on engine harnesses. The cable must be resistant to fuel and oil. The cable must have a temperature range of -40ºC (-40ºF) to plus 125ºC (257ºF).
The leads of the cable should have Spring Spade Terminals or Ring Terminals. The Connection between the wire and the terminal should be crimped and soldered.
(1) The number of connections must be kept to a minimum.
3.11 SHIELDED WIRING
Shielded twisted pair cable is required for the J1939 datalink and the magnetic speed sensor.
This cable is used for maximum protection against inductive noise, electromagnetic interference, and radio frequency interference. The shield greatly reduces the amplitude of any unwanted voltages on the signal wire. If the shields are connected to sheet metal, the connections are susceptible to loose bolts, corrosion, etc. The faulty connections increase the resistance of the shield. Faulty connections also reduce the effectiveness of the shield.
All the shields of the shielded cable must be connected to the common battery negative terminal of the generator set only. The shields should not be connected to the sheet metal. Sheet Metal connections corrode over time, increasing the resistance on the shield. When the cable terminates at junction boxes, the shields must be connected to each other in order to maintain a continuous path. Wire exposed beyond the shield should be as short as possible and not exceeding two inches. To avoid ground loops, shields should be grounded at one point only.
To avoid electromagnetic interference, do not run shielded signal wires near other wires carrying large currents. In installations with unavoidable risk of electromagnetic interference (EMI), shielded wire run in conduit, extra shielding, or other precautions may be necessary.
4 INITIAL Operation and User Orientation
4 INITIAL OPERATION AND USER ORIENTATION
4.1 VIEWING SYSTEM PARAMETERS
Many generator and engine parameters are accessible from both from the Caterpillar Service Tool, and the EMCP 3 display.
FROM THE CATERPILLAR SERVICE TOOL
Parameters are accessed by selecting Information > Status from the menu, or by clicking on the STATUS TOOL icon in the toolbar. Refer to the Caterpillar Service Tool help from the Help > Contents menu for more information on the Status Tool.
FROM THE EMCP 3 DISPLAY
Parameters are accessed (irrespective of the current screen position) by pressing the AC
OVERVIEW or ENGINE OVERVIEW buttons located below the screen. Detail screens provide even more information by pressing the SCROLL DOWN button from each of the overview screens.
SUPPORTED PARAMETERS
Different revisions of the EMCP 3 support different numbers of parameters. EMCP 3.3 supports several parameters not supported on the EMCP 3.2, which supports several parameters not supported on the EMCP 3.1. Some parameters are only available in certain configurations, for example, electronic engine ECMs provide more engine data than what is available from mechanical engines. The sections below list all of the parameters available, and on which level of EMCP 3 they may be available.
Parameters are displayed with units, some of which are configurable. For changing units or setting other user preferences see Chapter 4.2, Setting User Preferences.
Parameters that are not available to the EMCP 3 are shown as (four asterisks). This may indicate an incorrect software configuration, a wiring problem, or a problem with the sensor.
ENGINE PARAMETERS
ENGINE OVERVIEW SCREEN
• Engine Oil Pressure
• Engine Coolant Temperature
• Battery Voltage, as measured at the 70-pin connector entering the EMCP 3 GSC
• Engine Speed
• Engine Operating Hours
• Engine Operating State (Initialization, Pre-Crank, Starting, Running, Pre-Cooldown, Cooldown, Stopping, Stopped, Idling; many states are transient and only briefly active, and some states may not occur in some configurations)
ENGINE SCREEN 1
• Engine Oil Pressure (same as in Engine Overview Screen)
• Engine Coolant Temperature (same as in Engine Overview Screen)
• Engine Speed (same as in Engine Overview Screen)
ENGINE SCREEN 2
• Battery Voltage (same as in Engine Overview Screen)
• Engine Operating Hours (same as in Engine Overview Screen)
• Spare Analog Input parameter (configurable using the Spare Analog Input Suspect
Parameter Number; for configuration, see Chapter 9.1, Spare Analog Input)
ENGINE SCREEN 3
• Engine Hours remaining until Service
Maintenance Interval expires
• Calendar Days remaining until Service
Maintenance Interval expires
(option to reset the Service Maintenance Interval countdown timer)
ENGINE SCREEN 4
• Total engine Cranks since last reset (a crank is defined as the number of times the starter motor switches on)
• Total engine Starts since last reset (a start is defined as the number of times the engine transitions from below the Crank Terminate speed setpoint to above it)
(option to reset the crank and start counters)
ENGINE SCREEN 5 †
• Cylinder #1 Temperature
UP TO
• Cylinder #20 Temperature
ENGINE SCREEN 6 †
• Left Exhaust Manifold Temperature
• Right Exhaust Manifold Temperature
• Intake Manifold Temperature
• Exhaust Temperature
• Turbocharger #1 Compressor Inlet Temperature
UP TO
• Turbocharger #4 Compressor Inlet Temperature
• Turbocharger #1 Turbine Inlet Temperature
UP TO
• Turbocharger #4 Turbine Inlet Temperature
• Turbocharger #1 Turbine Outlet Temperature
UP TO
• Turbocharger #4 Turbine Outlet Temperature
ENGINE SCREEN 7 †
† Only shown if these parameters are supported by the engine ECM, and if the EMCP 3 setpoint Engine J1939 Support is set to Enhanced J1939.
• Engine Oil Temperature
• Engine Fuel Temperature
ENGINE SCREEN 8 †
• Fuel Pressure
• Crankcase Pressure
• Boost Pressure
ENGINE SCREEN 9 †
• Oil Filter Differential Pressure
• Fuel Filter Differential Pressure
ENGINE SCREEN 10 †
• Air Filter Differential Pressure
ENGINE SCREEN 11 †
• Total Fuel Consumption
• Instantaneous Fuel Consumption
AC PARAMETERS
AC OVERVIEW SCREEN
• Average Line-Line AC Voltage
• Average Current
• AC Frequency
• Power Factor (EMCP 3.2-3.3 only)
• Power Factor Lead/Lag status (EMCP 3.2-3.3 only)
• Total Generator Real Power – kW – (EMCP 3.2-3.3 only)
• Percent Real Power – as a percent of Generator Rated Power setpoint – (EMCP 3.2-
3.3 only)
AC SCREEN 1
• Line-Line Voltages: A-B, B-C, C-A
• Phase Currents: A, B, C
• AC Frequency
AC SCREEN 2
• Line-Neutral Voltages: A-N, B-N, C-N
• Phase Currents: A, B, C (same as AC Screen 1)
• AC Frequency (same as AC Screen 1)
AC SCREEN 3 (EMCP 3.2-3.3 ONLY)
• Per Phase Generator Real Power: A, B, C
• Per Phase Generator Apparent Power: A, B, C
• Per Phase Generator Reactive Power: A, B, C
AC SCREEN 4 (EMCP 3.2-3.3 ONLY)
• Per Phase Generator Real Power: A, B, C (same as AC Screen 3)
• Per Phase Generator Apparent Power: A, B, C (same as AC Screen 3)
† Only shown if these parameters are supported by the engine ECM, and if the EMCP 3 setpoint Engine J1939 Support is set to Enhanced J1939.
• Per Phase Power Factor: A, B, C
AC SCREEN 5 (EMCP 3.2-3.3 ONLY)
• Total Generator Real Power (same as AC
Overview Screen)
• Percent Real Power (as a percent of
Generator Rated Power setpoint)
• Total Generator Apparent Power
• Percent Apparent Power (as a percent of Generator Rated Apparent Power setpoint)
• Total Generator Reactive Power
• Percent Reactive Power (as a percent of the rated reactive power, as calculated by using the other two rated power setpoints and the power triangle:
22 )()( kWkVAkVAr −= )
AC SCREEN 6 (EMCP 3.2-3.3 ONLY)
• Generator Real Energy produced since last meter reset
• Generator Reactive Energy produced since last meter reset
• (option to reset energy meters)
AC SCREEN 7
• Average Line-Line AC Voltage (same as
AC Overview Screen)
• Average Line-Neutral AC Voltage
• Power Factor (EMCP 3.2-3.3 only) (same as AC Overview Screen)
• Power Factor Lead/Lag status (EMCP 3.2-3.3 only) (same as AC Overview Screen)
AC SCREEN 8 (EMCP 3.3 ONLY) ‡
• Generator Front Bearing Temperature
• Generator Rear Bearing Temperature
AC SCREEN 9 (EMCP 3.3 ONLY) ‡
• Generator Phase A Winding Temperature
• Generator Phase B Winding Temperature
• Generator Phase C Winding Temperature
AC SCREEN 10 (EMCP 3.3 ONLY) ‡
• Generator Excitation Field Voltage
• Generator Excitation Field Current
4.2 SETTING USER PREFERENCES
The EMCP 3 GSC display can be used for monitoring the generator status, viewing and resetting events, and configuring setpoints. There are several preferences to alter how you view the data on the display. These include: display contrast, units used to display pressure, units used to display temperature, units used to display volume (EMCP 3.3 only), and display
‡ Only shown on the EMCP 3.3, and only if an optional Thermocouple or RTD module is connected and configured for one of these parameters.
language (to select between the customer language and Technician English).
NOTE: These preferences do not affect operation of the EMCP 3 or the data as viewed in the Caterpillar Service Tool. They only affect how the text and data is converted and displayed on the EMCP 3 GSC display.
SETTING THE PREFERENCES USING THE EMCP 3 DISPLAY
On the EMCP 3 display, the Preferences menu is located at the bottom of the Main Menu.
The preferences are listed, with the current settings shown to the right (except language, whose current setting is usually obvious).
For any preference, press ENTER KEY to accept the change (or ESCAPE KEY to reject the change) and return to the Preferences menu.
PREFERENCES
CONTRAST This determines the darkness of the pixels on the display. A contrast setting of zero (reached by pressing and holding the down or left arrow) effectively blanks the screen, and a contrast setting of 100 (reached by pressing and holding the up or right arrow) effectively darkens the entire screen.
PRESSURE This allows pressure parameters (such as Engine Oil Pressure) and setpoints (such as Low Engine Oil Pressure Event Threshold) to be shown in either kPa, psi, or bar. Select the desired unit with the left or right arrows.
TEMPERATURE This allows temperature parameters (such as Engine Coolant Temperature) and setpoints (such High Engine Coolant Temperature Event Threshold) to be shown in either Celsius (Centigrade) or degrees Fahrenheit.
VOLUME
(EMCP 3.3 only)
This allows volume parameters (such as Fuel Volume) to be shown in either Liters, Imperial Gallons, or US Gallons.
LANGUAGE This allows the display to be switched between Technician English (always listed first) and the customer language (always listed second, and written in the font of the customer language). The below example shows the language selection in the German language flash file.
The LANGUAGE setting has been conveniently located at the bottom of the Preferences menu, which is at the bottom of the Main Menu.
If an EMCP 3 which is set to display an unknown language, the following steps will change the language to Technician English, regardless of the current screen, and without needing to read the text.
CHANGING TO TECHNICIAN ENGLISH
Press the ENGINE OVERVIEW key
Press the ESCAPE KEY (this will take you to the top of the Main Menu)
SCROLL DOWN until the scrolling stops
Press the ENTER KEY (this will take you into the Preferences Menu)
SCROLL DOWN until the scrolling stops
Press the ENTER KEY (this will take you into the language selection)
Press the ENTER KEY to select TECHNICIAN ENGLISH (shows as TECH ENGLISH on the EMCP 3.1 or 3.2)
The EMCP 3 language setting is changed back to TECHNICIAN ENGLISH.
Similar steps can be followed by a customer who is unfamiliar with English, to change the language setting back to their primary language:
CHANGING TO PRIMARY LANGUAGE
Press the ENGINE OVERVIEW key
Press the ESCAPE KEY (this will take you to the top of the Main Menu)
SCROLL DOWN until the scrolling stops
Press the ENTER KEY (this will take you into the Preferences Menu)
SCROLL DOWN until the scrolling stops Press the ENTER KEY (this will take you into the language selection)
Press the SCROLL DOWN arrow to select the customer language
Press ENTER KEY to change to the customer language
The EMCP 3 language setting is changed back to the customer language.
SETTING THE PREFERENCES USING THE SERVICE TOOL
Only the preferences for units configuration can be configured using the Caterpillar Service Tool. They are located in the Configuration Tool. Select Display Preferences from the left pane.
FIGURE 13: DISPLAY PREFERENCES
The display units can be changed the same way other setpoints are changed with the Service Tool.
PRESSURE
This allows pressure parameters (such as Engine Oil Pressure) and setpoints (such as Low Engine Oil Pressure Event Threshold) to be shown in either kPa, psi, or bar. Select the desired unit with the left or right arrows.
TEMPERATURE This allows temperature parameters (such as Engine Coolant Temperature) and setpoints (such High Engine Coolant Temperature Event Threshold) to be shown in either Celsius (Centigrade) or degrees Fahrenheit.
VOLUME This allows volume parameters (such as Fuel Volume) to be shown in either Liters, Imperial Gallons, or US Gallons.
4.3 CONFIGURING TIME/DATE (EMCP 3.2 AND 3.3)
The EMCP 3.2 and 3.3 have an internal clock that is used for time-stamping events. The timestamps for the first date and time an event has occurred and the last date and time the event has occurred are viewed by selecting an Event and pressing Enter, then scrolling down.
See FIGURE 14 below.
FIGURE 14: EVENT DETAILS SCREENS – LAST OCCURRENCE (LEFT) AND FIRST OCCURRENCE (RIGHT)
CHANGING DATE FORMAT
The data format can be set to either display in the form Month/Day/Year or the form Day/Month/Year. This procedure must be performed on the EMCP 3 GSC display; it cannot be done using the Caterpillar Service Tool.
NOTE: This preference does not affect operation of the EMCP 3 or the data as viewed in the Caterpillar Service Tool. It only affects how the date is displayed on the EMCP 3 GSC display.
To change the date format, do the following:
At MAIN MENU
ENTER KEY
SCROLL DOWN
to CONFIGURE to TIME/DATE
Highlight FORMAT MM/DD/YY
(or FORMAT DD/MM/YY, depending on the current setting)
Select the format using the
LEFT ARROW or RIGHT
ARROW
CHANGING THE TIME / DATE
The EMCP 3 clock allows the time/date to be modified. Changing the time/date will change the timestamp on all future events, but not for existing events. (For example, an event that has occurred previously will still show the same FIRST time/date, but if it occurs again after the time/date has been adjusted, the LAST time/date will reflect the change.)
This procedure must be performed on the EMCP 3 GSC display; it cannot be done using the Caterpillar Service Tool. In order to update time/date, LEVEL 1 ACCESS is required. Refer to Chapter 6, Security for information on obtaining LEVEL 1 ACCESS.
To change the time/date, do the following:
TO CHANGE THE TIME
At MAIN MENU to CONFIGURE to TIME/DATE
With the box around the time, press
(if the time cannot be selected, and a padlock is shown on the screen, then Level 1 access has not been obtained)
To begin editing the time press
Select a digit using the
LEFT ARROW or RIGHT
ARROW
To change the selected digit use the
UP ARROW or DOWN ARROW
To accept change:
Press ENTER KEY
To reject, change:
ESCAPE KEY
TO CHANGE THE DATE
Press ESCAPE KEY again to return to the SET TIME/DATE screen.
Press the RIGHT ARROW key to put the box around the date ENTER KEY .
Press ENTER KEY again to begin editing the date.
Use the LEFT ARROW or RIGHT ARROW keys to select a digit and the
UP ARROW or DOWN ARROW keys to change it.
Press ENTER KEY to accept, or ESCAPE KEY to reject, your change.
Press ESCAPE KEY again to return to the SET TIME/DATE screen.
4.4 ADJUSTING GENERATOR SET PARAMETERS
On some gensets, the engine speed, generator output voltage, and idle/rated status can be adjusted from the display of the EMCP 3 GSC.
ENGINE SPEED
To program the Engine Speed of a genset it must have an electronic engine controlled by an ADEM III or newer ECM. The Primary Desired Speed Input Configuration Setpoint in the ADEM is programmed to CAN INPUT, then the engine speed can be adjusted from the display of the EMCP 3 GSC. The Engine Type Configuration setpoint must be programmed to ELECTRONIC.
PROGRAMMING THE ENGINE SPEED
From the MAIN MENU select CONTROL
Once in that screen the first option will be highlighted and it will display one of the following: SPEED, VOLTAGE, or SPEED & VOLTAGE. The engine speed can only be controlled if SPEED or SPEED & VOLTAGE is displayed. If the EMCP 3 GSC is not programmed for an electronic engine, speed will not show up as an option.
Press the ENTER KEY The speed and voltage adjust screen will be displayed. To adjust the engine speed from this screen
Adjust Engine Speed:
Press RIGHT ARROW KEY To INCREASE the engine speed
Press LEFT ARROW KEY To DECREASE the engine speed
The EMCP 3 GSC will broadcast an engine speed bias based on the adjustment that is made.
If the engine speed is adjusted, that value will remain until either it is adjusted again or until the control is power-cycled.
GENERATOR OUTPUT VOLTAGE
If the genset is equipped with a Caterpillar Digital Voltage Regulator (CDVR), then the generator output voltage can be adjusted from the display of the EMCP 3 GSC.
PROGRAMMING THE GENERATOR OUTPUT VOLTAGE
Once in that screen the first option will be highlighted and it will display one of the following: SPEED, VOLTAGE, or SPEED & VOLTAGE. The generator output voltage can only be controlled if VOLTAGE or SPEED & VOLTAGE is displayed.
Press the ENTER KEY The speed and voltage adjust screen will be displayed. To adjust the generator output voltage from this screen
Adjust Output Voltage:
Press UP ARROW KEY To INCREASE the generator output voltage.
Press DOWN ARROW KEY To DECREASE the generator output voltage.
NOTE: In order for the VOLTAGE ADJUST to work, the AVR VOLTAGE CONTROL DESIRED INPUT CONFIGURATION setpoint in the CDVR must be programmed for CAN INPUT. If that setpoint is set to SWITCH, the VOLTAGE CONTROL from the EMCP 3 GSC will NOT WORK.
IDLE/RATED
The engine speed can be toggled between LOW IDLE and RATED SPEED from the display of the control.
Press DOWN ARROW Highlight IDLE/RATED.
The IDLE/RATED screen will be displayed and the current state will be shown.
To change the state, Press UP ARROW or DOWN
ARROW Then select the value.
Press ENTER KEY
4.5 STARTING AND STOPPING THE GENERATOR SET
STARTING THE ENGINE
Once the control is configured correctly, the control panel is powered up, and the generator set is ready to be operated, the generator set can be started. Refer to FIGURE 15, Stopping The Engine. There are several ways the generator set can be started from the control panel.
To START the engine in MANUAL OPERATION:
1. Press the RUN KEY or
2. Place the control in AUTO mode then
3. The engine can be started THREE DIFFERENT WAYS.
a: Activate DIGITAL INPUT #2, which is the REMOTE INITIATE INPUT.
b: Activate a REMOTE INITIATE over the MODBUS data link.
c: Configure a PROGRAMMABLE CYCLE TIMER.
When the control panel initiates a start command on a diesel engine, the control checks to make sure there are no SHUTDOWN EVENTS present (labeled PRESENT) or that there are no latched SHUTDOWN EVENTS (labeled ACTIVE).
If there are no shutdown events that are active or present, and after any pre-crank or start-aid activities have completed, the starter motor and fuel control will be activated. The EMCP 3 GSC will activate Relay Output #1 to activate the starter motor magnetic switch, and Relay Output #2 to activate the fuel enable circuit.
On electronic engines with ADEM™ A3 or newer engine ECM, the start command and fuel enable signals will be sent from the EMCP 3 GSC to the engine ECM via the J1939 data link.
After receiving the signals, the engine ECM will operate the fuel control relay and starter motor magnetic switch. Relay outputs #1 and #2 will not be used on those engines.
Relay Output #1 will remain active until the programmed ENGINE CRANK TIME has been reached, or until the engine speed has reached the programmed CRANK TERMINATE SPEED setpoint value.
NOTE: the EMCP 3 GSC Crank setpoints: number of cranks, crank duration, and crank terminate speed are not used on engines using the ADEM™ A4 with the Common Engine Interface option or newer engine ECM. These values must be adjusted in the engine ECM.
CAUTION: To determine the exact starting sequence for your engine, consult your engine’s Operation and Maintenance Manual.
STOPPING THE ENGINE
Once the engine is started, the engine can be stopped by pressing the STOP KEY on the control panel. If the control is in AUTO, the engine can also be stopped by DEACTIVATING all of the remote initiate commands. There are three possible sources for this command:
1. The remote initiate input (digital input #2)
2. The remote initial command over the Modbus datalink (register number 1055)
3. The Programmable Cycle Timer
Once the STOP command is issued, the control will go into COOLDOWN MODE. Cooldown mode will run for the duration of time that it is programmed in the COOLDOWN DURATION setpoint. If the cooldown time is set for zero minutes, the engine will stop immediately.
On engines with ADEM™ A4 or newer engine ECM, the cooldown timer in the EMCP 3 GSC should be set to 0 (Zero) minutes because the cooldown time is controlled from the engine ECM (if this is not done, both cooldown timers will run in sequence). Also, the ENGINE OPERATING STATE INPUT CONFIGURATION parameter must be set to CAN INPUT.
The cooldown timer can be overridden by pressing and holding the STOP KEY for 5 seconds. The display will show a splash screen that will ask if you want to BYPASS COOLDOWN?
or continue with the cooldown cycle.
If the ENTER KEY is pressed from the splash screen, the cooldown timer will be bypassed.
If the ESCAPE KEY is pressed from the splash screen, the cooldown cycle will continue until the programmed cooldown time has elapsed.
When the cooldown timer has elapsed or has been bypassed, Relay Output #2 will open. The STOP command will also be sent over the J1939 data link for those engines that require it. At that point, the fuel injection will be DISABLED and the engine will stop.
Any time, while the engine is RUNNING:
The EMCP 3 GSC detects a condition where an engine or generator parameter is ABOVE or BELOW programmed thresholds for a programmed amount of time or another SHUTDOWN EVENT occurs, then the EMCP 3 GSC will attempt to shut the engine down
Depending on how a specific EVENT RESPONSE configuration is programmed, the EMCP 3 GSC will either put the engine in COOLDOWN, followed by a soft shutdown or shut the engine down immediately (a HARD SHUTDOWN).
FIGURE 15: STOPPING THE ENGINE
4.6 ENGINE SETPOINT VERIFICATION
The engine setpoint verification procedure verifies that the EMCP 3 GSC operates correctly when OIL PRESSURE, HIGH COOLANT TEMPERATURE, LOW OR ENGINE OVERSPEED events occur.
On an ENGINE OVERSPEED EVENT, the EMCP 3 GSC will shut the engine down.
LOW OIL PRESSURE and HIGH COOLANT TEMPERATURE each have two events, WARNING and SHUTDOWN. The EMCP 3 GSC will issue a WARNING whenever the warning threshold is reached and a SHUTDOWN whenever the shutdown threshold is reached. The configuration setpoints used in normal operation will be modified.
During this procedure
Each configuration setpoint should be recorded prior to adjustment.
Returned back to the original setting after the setpoint has been verified.
The following conditions are required before the ENGINE SETPOINTS are verified:
REQUIRED CONDITIONS
The setpoints must be correct for the engine application.
No shutdown events should be present. If necessary, troubleshoot, correct, and reset any and all shutdown events.
PROCEDURE FOR OVERSPEED VERIFICATION
NOTE: Adjustment of ENGINE OVER SPEED SHUTDOWN THRESHOLD setpoint requires a level 3 password. For details on changing security levels refer to Chapter 6, Security.
The Security Level only affects changing parameters from the EMCP 3 GSC. Changing parameters with the Caterpillar Service Tool does not require passwords.
1. Start the engine and run the engine at rated speed.
2. Adjust the setpoint value for Engine Over Speed Shutdown Threshold to a value that is below the speed that the engine is running at. An Engine Overspeed Shutdown event will occur immediately after the setpoint is changed, and the engine will shut down.
3. View the event by going to the Genset Control event log. Reset the event. For more information about how to view and reset the event, refer to Chapter 5, Handling Events.
4. Return setpoint value for Engine Over Speed Shutdown Threshold to the original value.
PROCEDURE FOR LOW OIL PRESSURE VERIFICATION
NOTE: Low oil pressure shutdown is disabled during start-up and while the engine is not running by the Fault Protection Timer (FPT). The fault protection timer starts timing when the crank terminate RPM is reached during the starting sequence. The fault protection timer will then run for a programmed time which is determined by the Engine Start Fault Protection Activation Delay Time setpoint. Make sure the fault protection timer has elapsed before starting the Low Oil Pressure Verification.
1. Start the engine and run the engine at rated speed.
2. Adjust the setpoint value for Low Engine Oil Pressure Shutdown Event Threshold to a value that is above the oil pressure that the engine is operating at. The shutdown event will occur after the programmable time delay (the Low Engine Oil Pressure Shutdown Delay Time setpoint).
3. View the event by going to the Genset Control event log. Reset the event. For more information about how to view and reset the event, refer to Chapter 5, Handling Events.
4. Return setpoint value for Low Engine Oil Pressure Shutdown Event Threshold to the original value.
PROCEDURE FOR HIGH COOLANT TEMPERATURE VERIFICATION
NOTE: High Coolant Temperature shutdown is disabled during start-up and while the engine is not running by the Fault Protection Timer (FPT). The fault protection timer starts timing when the crank terminate RPM is reached during the starting sequence. The fault protection timer will then run for a programmed time (the Engine Start Fault Protection Activation Delay Time setpoint). Make sure the fault protection timer has elapsed before starting the High Coolant Temperature Verification.
1: Start the engine and run the engine at rated speed.
2: Adjust setpoint value for High Engine Coolant Temperature Shutdown Event Threshold to a value that is below the engine coolant temperature that the engine is operating at. The minimum value for this setpoint is 49ºC (120ºF), so you may have to run the engine for a few minutes to get the temperature above the minimum value.
The shutdown event will occur after the programmable time delay (the High Engine Coolant Temperature Shutdown Event Notification Delay Time setpoint).
3: View the event by going to the Genset Control event log.
4: Reset the event. Refer to Handling Events for more information about how to view and reset the event.
5: Return setpoint value for High Engine Coolant Temperature Shutdown Event Threshold to the original value.
4.7 ENGINE SPEED TIMING CALIBRATION - PREPARATION
The following procedure describes the required steps before an ENGINE SPEED TIMING CALIBRATION procedure is performed. After this procedure has been completed, the engine can be started and the engine can be run at rated speed.
NOTE: This procedure does NOT include the instructions for performing the actual calibration. For instructions on performing the calibration procedure, refer to the Testing and Adjusting Manual for your engine.
NOTE: Before changing any value per this procedure, RECORD THE ORIGINAL VALUE!
1: Stop the engine.
2: In the main menu scroll down until CONTROL is highlighted. Press the ENTER KEY . Scroll through the options in the control menu. If there is an option called
IDLE/RATED, go to Step 3. If not go to Step 5.
3: Make sure the IDLE/RATED option is highlighted and press ENTER KEY . If the display shows RUN AT IDLE in the IDLE/RATED screen, go to Step 10. If the display shows RUN AT RATED in the IDLE/RATED screen, go to Step 4.
4: Press the ENTER KEY and then use the UP ARROW and DOWN ARROW keys in order to select RUN AT IDLE. Press ENTER KEY to accept the new value. Go to step 10.
5: Set the ENGINE START FAULT PROTECTION ACTIVATION DELAY TIME setpoint (under Control > Auto Start/Stop) in the EMCP 3 GSC to 300 seconds.
6: If a device such as a load share module is supplying a PWM signal in order to bias the engine speed, then disconnect the PWM signal wires from the device. Go to Step 7. If there is not a device supplying a PWM signal and the engine speed bias is controlled from the EMCP 3 GSC, go to Step 9.
7: Set the PRIMARY DESIRED SPEED setpoint in the Engine ECM to PWM.
8: Set the SECONDARY DESIRED SPEED setpoint in the Engine ECM to DISABLED.
9: Start the engine and run the engine at idle speed.
10: Perform the Engine Speed Timing Calibration. See the Systems Operation, Testing and Adjusting manual for your engine for more information on how to perform the calibration procedure.
11: Stop the engine.
12: Return any modified setpoints to the original values.
13: Reconnect any wires that were disconnected in Step 6.
14: If steps 3 and 4 were performed, set the idle/rated status back to RUN AT RATED.
4.8 ENGINE OPERATING HOURS
One of the features of the EMCP 3 is the ability to maintain the ENGINE OPERATING HOURS, which is the cumulative amount of time that the engine has run above the Crank Terminate speed. This time is displayed on the Engine Overview screen, just below Battery Voltages shown in FIGURE 16.