Text version
Substitution Requests Response Project:
PHASE 1A LABORATORY MODERNIZATION
at the ORD-NHEERL, WESTERN ECOLOGY DIVISION, CORVALLIS, OR Project Number:
0130523.03 Date:
July 21, 2015
This review is only for general conformance with the design concept and the information given in the Construction Documents. Approvals are based upon the opinion, knowledge, information, and belief of design team at time of issuance of this Addendum and reliance upon data submitted. Approvals are therefore interim in nature and subject to reconsideration as additional data, materials, workmanship, and coordination with other work are observed and reviewed. In proposing items allowed by this Addendum, Bidder assumes all risks, costs, and responsibilities for items final acceptance, integration into Work, and performance.
| Item (with EPA Contracting Officer label) |
| Spec Section |
| Proposed Manufacturer |
| Manufacturer Representative Name |
| Approved or Disapproved |
Permeable Interlocking Concrete Pavers
| Pavestone (Willamette Graystone Division) |
| Gale Schroeder |
Willamette Graystone (Division of Pavestone)
2405 NE 244th Ave
Wood Village OR 97060 ph 971-241-0312 gale@willamettegraystone.com Approved.
| Metal Wall Panels |
| 074213 |
| Metal Sales |
| Stacey Henderson |
Metal Sales Manufacturing
2727 E. Trent
Spokane, WA 99202
P: (509) 828-4757 Approved.
Chemical Fume Hood
| 115300 |
| BMC Metal-ARC |
| Brian Johnston |
Laboratory Design & Construction
PO Box 728
Wauna, WA 98395
P: (253) 858-7835 brian@laboratorydesign.net
Disapproved. Fume hood performance does not match the basis of design.
| Chemical Fume Hood |
| 115300 |
| Labconco |
| Brian Johnston |
Laboratory Design & Construction
PO Box 728
Wauna, WA 98395
Disapproved. Specification Section 11 53 00 requires:
Approved substitute in accordance with Section 01 60 00.
2.00.D. The selected manufacturer for the Chemical Fume Hood will also be selected for the Laboratory Casework (Section 12 33 60) to assure compatibility of the products.
The selected manufacturer for the Chemical Fume Hood will also be selected for the Laboratory Casework (Section 12 33 60) to assure compatibility of the product The selected manufacturer must warrant for a period of one-year starting (date of acceptance
| Laboratory Casework |
| 123360 |
| BMC Metal-ARC |
| Brian Johnston |
Laboratory Design & Construction
PO Box 728
Wauna, WA 98395
Disapproved. Does not meet EPA AE Guidelines.
Temp Controls
(EPA #4)
| 230900 |
| Distech Controls |
| Scott Conley or Becky Moon |
Office Manager
Essential Building Technologies, LLC
600 SE Maritime Avenue, Ste. 240
Vancouver, WA 98661
P: (360) 573-3200 x101
F: (360) 573-3201 beckym@essentialbuildings.com
Approved
Temp Controls
(EPA #3)
| 230900 |
| Reliable Controls |
| Scott Conley or Becky Moon |
Office Manager
Essential Building Technologies, LLC
600 SE Maritime Avenue, Ste. 240
Vancouver, WA 98661
P: (360) 573-3200 x101
F: (360) 573-3201 beckym@essentialbuildings.com
Approved
| Balancing Valves (EPA #12) |
| 232113 |
| NuTech AB/MB |
| Greg Oberle |
Oregon Air Reps
Ph 503-620-4300 grego@oregonairreps.com Approved
| Duct Silencers (EPA # 11) |
| 233300 |
| Price model RH |
| Johnson Air Products |
2220 SE Ninth Ave
Portland, OR 97214
Eric Danielson Engineering Sales Manager 971-244-5236 Direct edanielson@johnsonair.com Approved
| Air Duct Accessories |
| 233300 |
| Pottorff |
| Cory Hayes |
Norman S. Wright - Northwest
OFFICE: 503.563.6033
FAX: 503.563.6031
MOBILE: 503.475.2000
Approved for duct silencers and dampers.
| Exhaust Fans for lab exhaust |
| 233423 |
| Twin City Fans |
| Greg Oberle |
Oregon Air Reps
Ph 503-620-4300 grego@oregonairreps.com Approved for lab exhaust fans. Approved for inline fans.
| Single Duct Air Terminal Units |
| 233600 |
| Krueger LMHS |
| Cory Hayes |
Norman S. Wright - Northwest
OFFICE: 503.563.6033
FAX: 503.563.6031
MOBILE: 503.475.2000
Approved
| Venturi Valves and Lab Controls (EPA #14) |
| 233605 |
| Price Critical Controls |
| Johnson Air Products |
2220 SE Ninth Ave
Portland, OR 97214
Eric Danielson Engineering Sales Manager 971-244-5236 Direct edanielson@johnsonair.com Approved.
No major differences. Engineer has no experience with this product.
Air Handling Units
(EPA #10)
| 237313 |
| TEAM Air Conditioning Equipment |
| Dave Havelick |
TraneOregon
7257 SW Kable Lane
Portland, OR 97224 Approved.
Air Handling Units
(EPA #9)
| 237313 |
| Haakon Industries |
| Dave Havelick |
TraneOregon
7257 SW Kable Lane
Portland, OR 97224 Approved.
| Air Handling Units |
| 237313 |
| BASX |
| Cory Hayes |
Norman S. Wright - Northwest
OFFICE: 503.563.6033
FAX: 503.563.6031
MOBILE: 503.475.2000
Disapproved. Too little data available on products from BASX.
| Air Handling Units |
| 237313 |
| Unitech WhisperAir |
| Greg Oberle |
Oregon Air Reps
Ph 503-620-4300 grego@oregonairreps.com Approved.
Appears acceptable. Engineer has no prior experience with this manufacturer.
| Air Handling Units (EPA #1) |
| 237313 |
| Engineered Air |
| Nathan Ralphe |
Engineered Air
3443 S Galena St, Suite 102
Denver, CO 80231 Approved.
Appears acceptable. Engineer has minimal prior experience with this manufacturer.
| Water Source Heat Pumps |
| 238143 |
| Enertech Global |
| Cory Hayes |
Norman S. Wright - Northwest
OFFICE: 503.563.6033
FAX: 503.563.6031
MOBILE: 503.475.2000
Disapproved.
Not enough demonstrated service.
| Water Source Heat Pumps |
| 238146 |
| Daikin |
| Greg Oberle |
Oregon Air Reps
Ph 503-620-4300 grego@oregonairreps.com Disapproved.
Heat pump data is insufficient to determine capacity. No data for units of comparable size.
| Hot Water Convector |
| 238233 |
| Sterling FSG-A |
| Greg Oberle |
Oregon Air Reps
Ph 503-620-4300 grego@oregonairreps.com Approved.
| Propeller Unit Heaters (EPA #13) |
| 238239 |
| Modine model HC |
| Johnson Air Products |
2220 SE Ninth Ave
Portland, OR 97214
Eric Danielson Engineering Sales Manager 971-244-5236 Direct edanielson@johnsonair.com Approved.
| Engine Generators |
| 263213 |
| MTU Onsite Energy |
| Jake Austin |
Power Generation Sales
7215 South 228th St.
Kent, WA 98032 Approved.
Appears to be acceptable. Engineer does not have experience with this brand. Subject to space limitations and requirements of specifications and drawings.