Amendment 5, SOL-CI-15-00021
1. “Technical_Questions_and_Answers_SOL-CI-15-00021”, Q&A Tab 2, Row 9 provided clarification regarding conflicts between the Floor Plans, Elevations, and Door Schedule on Sheet A600 for Door #s A119A, A119F, and A120A regarding material type for doors and frames (aluminum or HM). Additional similar conflicts existing on Sheets A103, A200, and Door Schedule on A600 for Penthouse Doors P101A,P101B,P101C,P101D,P101E, P106A, P106B, P106C, P106D and P106E. Please confirm that the Door Schedule on A600 takes precedence on these as was the case for Doors A119A, A119F, and A120A.
Doors A119A, A119F, and A120A are aluminum as noted on the door schedule, remark 3 does not apply. Doors 101A, P101B, P101C, P101D, P101E, P106A, P106B, P106C, P106D and P106E are hollow metal per the door schedule, keynote 8.02 does not apply.