MANUFACTURED HOUSING UNIT
FEDERAL EMERGENCY MANAGEMENT AGENCY
Appendix A
Typical NextGen MHU Details
June 28, 2019
VERSION 1
COVER PAGE
TITLE:
Scale: NTS
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
TYPICAL MHU DETAILS
A-1
. Jun 28, 2019
44" MIN.
48" MAX.
18"TO THE SCREW
SWITCHES MUST BE NO HIGHER THAN 48" TO CENTER.
ELECTRICAL OUTLETS
MUST BE NO LOWER THAN
18" ABOVE THE FLOOR TO
THE CENTER OF THE
RECEPTACLE SCREW.
SWITCH & RECEPT DETAIL
48" MAX.
THE HIGHEST BREAKER IN
THE PANEL BOX MUST BE
NO HIGHER THAN 48"
ABOVE THE FLOOR.
MISC. HEIGHT REQUIREMENTS
- ELECTRICAL PANEL
- THERMOSTAT
- FIRE EXTINGUISHER
32"
48" MAX.
26" MAX.
TO THE BOTTOM
FIRE EXTINGUISHER MOUNTED ON THE WALL
MUST NOT PROTRUDE MORE THAN
4" FROM THE WALL SURFACE, IF THE
BOTTOM IS MORE THAN 27" ABOVE
THE FLOOR.
THERMOSTAT
CONTROL FOR
HVAC MUST BE
MOUNTED NO MORE
THAN 48" ABOVE
THE FLOOR.
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY:
MISC. HEIGHT REQUIREMENT DETAILS
Scale: 3/8" = 1'-0"
Date: 6/28/2019
DRAWING NO.
A-2
APPENDIX A
REV. 1
Notes
1. UL listed fire extinguisher with minimum rating of 1A:10:B:C
46"
48" MAX.
RECOMMENDED
PLACEMENT OF
SHELVING
TO BE UNDER
HORIZONTAL
WAINSCOT TRIM.
AT FEMA'S
DESCRETION
SHELF MAY BE
RELOCATED
FOR UFAS
COMPLIANCE.
CLOSET SHELVING
46"
48" MAX.
48" MAX.
MUST HAVE LEVER DOOR HANDLES.
THE OPERABLE PARTS OF THE
HARDWARE, UNCLUDING DEAD
BOLTS, MUST BE MOUNTED AT A
HEIGHT BETWEEN 34" MIN. AND 48"
MAX. ABOVE FLOOR.
34" MIN.
DOOR HARDWARE DETAILS
72"
34"
77"
MEDICINE CABINET & LAV DETAIL
15" MIN.
M
A X
TOP OF SHELF
MEDICINE CABINET 3"
DEEP MIN. 450 SQ. IN. MIN.
M
I N
General Notes
1. All interior and exterior doors shall have 3 hinges.
PLANT TO
INSTALL SHELF
AT THIS HEIGHT
72"
Federal Emergency Management Agency
COMPANY:
MISC. HEIGHT REQUIREMENT DETAILS
Scale: 3/8" = 1'-0"
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-3REV. 1
END STUD-
2x3 #2 SPF AT EACH SIDE OF SINK
/WORK SPACE OPENING,
FASTENED INTO CABINET OR
BACKER IN WALL W/ #8 SCREWS
AT 16" O.C. (MIN. 1" PENETRATION).
BLACK LAMINATED SLAB
COUNTERTOP MATERIAL
FASTENED TO 2X3s TOP AND
BOTTOM W/ #8 SCREWS W/
GROMMETS BOTH ENDS OF
ACCESS PANEL.
A
A
8' WIDE EXPRESS MHU SINK ACCESS PANEL ELEVATION
14' WIDE MHU SINK ACCESS PANEL ELEVATION
A
A
SECTION A-A
END STUD DETAIL
END STUD
END STUD
END STUD
END STUD
6" CABINET STILE
6"
8"
2x4x52" #2 SPF
LAV GUARD 2 INTERNAL RIBBED
VINYL OR EQUIVALENT DRAIN LINE
PROTECTOR.
Federal Emergency Management Agency
COMPANY:
ACCESS PANEL DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.
A-4
KITCHEN SINK
APPENDIX A
REV. 1
VINYL SIDING
WEATHER RESISTIVE BARRIER
7/16" OSB SHEATHING
1/2" GYPSUM WITH PAINT FINISH
FIBERGLASS BATT INSULATION
TRIM
DOOR
(2) - 2x4 HEADER
INTERIOREXTERIOR
VINYL SIDING
WEATHER RESISTIVE BARRIER
7/16" OSB SHEATHING
1/2" GYPSUM WITH PAINT FINISH
FIBERGLASS BATT INSULATION
TRIM
DOOR
(2) - 2x4 STUDS
INTERIOR
EXTERIOR
VINYL SIDING J-CHANNEL
ALL AROUND DOOR FRAME
VINYL SIDING J-CHANNEL
ALL AROUND DOOR FRAME
HEADER DETAIL
JAMB DETAIL
INTERIOREXTERIOR
PERIMETER
RAIL
FLOOR
DECKING
FLOOR JOIST
SILL DETAIL
UFAS COMPLIANT SILL TO
BE SET IN TWO
CONTINUOUS BEADS OF
SILICONE CAULK LOCATED
AS SHOWN. SILL TO BE
FASTENED DOWN WITH
FASTENERS PROVIDED BY
DUNBARTON OR
EQUIVALENT. FASTENERS
SHALL NOT BE OVERDRIVEN
THAT WILL WARP THE SILL.
Federal Emergency Management Agency
COMPANY:
DOOR DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-10REV. 1
Door Detail Notes
1. All exterior doors shall be insulated fiberglass Dunbarton Rediflex steel frame outswing fiberglass door and ADA sill or equivalent.
2. Door assemblies shall contain an integral J-channel above the door assembly.
3. All exterior doors, shall be outswing with primary and secondary seals, whose primary seam surrounds the perimeter of the door.
4. Doors shall meet HUD CFR 3280.405 requirements and shall be compliant with Wind Zone III (3280.305).
5. Fasten doors with #8 x 1 ½” screws spaced per manufacturer’s test report.
STANDARD CUT
INSTALL THE DOOR PLUMB
LEVEL AND SQUARE
AS PER MANUFACTURER'S
INSTRUCTIONS
INSTALL 6" WIDE SELF-ADHERING
FLASHING COVER OVER
NAILING FLANGE AT JAMBS
INSTALL METAL DRIP CAP
HEAD FLASHING
FOLD HOUSE WRAP BACK DOWN
AND TAPE ACROSS THE HEAD OF
WINDOW AND THEN TAPE
DIAGONAL CUTS.
EXTEND FLASHING MIN 2"
BEYOND JAMB FLASHING
INSTALL 6" SELF-ADHERING
FLASHING OVER DRIP CAP
NAILING FLANGE
INTERIOR VIEW
NTS
SEAL ENTIRE DOOR FRAME TO INSIDE
OF THE ROUGH OPENING TO FORM
A CONTINUOUS AIR SEAL.
STEP 5 STEP 6 STEP 8STEP 7
EXTERIOR DOOR
UP TO A 1/2" RISE IN THRESHOLD
1/2" HIGH, UP TO 1:2 SLOPE,
SAFE-PATH RUBBER BUTTED
TO THE EXTERIOR DOOR
THRESHOLD
EXTERIOR DOOR THRESHOLD
NTS
FOLD HOUSE WRAP
IN AT JAMBS
CUT HOUSE WRAP
HOUSE WRAP OVER
WALL SHEATHING
LINE OF DOOR OPENING
TEMPORARILY FOLD UP AND
SECURE HOUSE WRAP
TEMPORARILY FOLD UP AND
SECURE HOUSE WRAP
APPLY A SELF-ADHERING
FLASHING MEMBRANE
(SILL + 4" ABOVE FLOOR)
INSTALL SILL PAN FLASHING
SEALED TO WOOD FLOOR
APPLY 3/8" NOM. CONTINUOUS
BEAD OF SEALANT TO THE BACK
OF THE DOOR FLANGE IN
LINE WITH PRE-PUNCHED
HOLES / SLOTS.
STEP 1 STEP 2 STEP 4STEP 3
Federal Emergency Management Agency
COMPANY:
DOOR FLASHING DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-11REV. 1
Door Flashing Detail Notes
1. Install self-adhering flexible flashing at perimeters of door frame and seal door frame to the weather resistant barrier as shown in the details.
2. Flashing shall be pliable and adhesive waterproofing membrane with a removable release liner.
3. Cut flashing in lengths required for application as indicated on the details.
4. Seal over all fastening screw heads at doors before installing flashing around the door frame.
5. Door installation shall be per manufacturer’s installation instructions.
6. Self adhering flashing shall be rolled after placement.
VINYL SIDING
WEATHER RESISTIVE BARRIER
7/16" OSB SHEATHING
1/2" GYPSUM WITH
PAINT FINISH
FIBERGLASS BATT
INSULATION
TRIM
WINDOW
INTEGRAL J-CHANNEL
WINDOW FRAME
(2) - 2x4 HEADERS
VINYL SIDING
WEATHER RESISTIVE BARRIER
7/16" OSB SHEATHING
1/2" GYPSUM WITH PAINT FINISH
FIBERGLASS BATT INSULATION
TRIM
WINDOW FRAME
(1) - 2x4 SILL
SILL TRIM
VINYL SIDING
WEATHER RESISTIVE BARRIER
7/16" OSB SHEATHING
1/2" GYPSUM WITH
PAINT FINISH
FIBERGLASS BATT
INSULATION
TRIM
WINDOW
(2) - 2x4 STUDS
INTERIOR
EXTERIOR
INTEGRAL J-CHANNEL
WINDOW FRAME
HEADER DETAIL
SILL DETAIL
JAMB DETAIL
INTEGRAL J-CHANNEL
WINDOW FRAME
WINDOW FRAME
JAMB TRIM
WINDOW FRAME
HEADER TRIM
WINDOW
Federal Emergency Management Agency
COMPANY:
WINDOW DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-20REV. 1
Window Detail Notes
1. Windows shall be low-e with vinyl frame. For U-value & SHGC see FEMA spec's.
2. Windows shall meet HUD CFR 3280.403 and 3280.404 requirements.
3. Fasten windows with #8 x 1 1/2" screws @ 4" o.c. all along the opening.
CUT DRAINAGE WRAP @ A 45° ANGLE
LINE OF WINDOW OPENING
STANDARD OR MODIFIED I-CUT
HOUSE WRAP OVER WALL SHEATHING
TEMPORARILY FOLD UP AND
SECURE HOUSE WRAP
FOLD HOUSE WRAP IN
AT JAMBS AND SILL
SLOPE SILL ROUGH
OPENING TO EXTERIOR
TEMPORARILY FOLD UP AND
SECURE HOUSE WRAP
MECHANICALLY FASTEN
FANNED EDGES
(CAP NAILS, STAPLES)
INSTALL 9" WIDE SELF
ADHERING FLEXIBLE FLASHING
AT SILL.
EXTEND FLASHING UP
JAMBS 6" MIN.
ALIGN FLASHING WITH INTERIOR
EDGE OF SILL ROUGH OPENING
APPLY 3/8" NOM. CONTINUOUS
BEAD OF SEALANT TO THE BACK
OF THE WINDOW FLANGE IN
LINE WITH PRE-PUNCHED
HOLES / SLOTS.
INSTALL WINDOW PLUMB
LEVEL AND SQUARE
AS PER MANUFACTURER'S
INSTRUCTIONS
INSTALL 6" WIDE SELF-ADHERING
FLASHING COVER OVER
NAILING FLANGE AT JAMBS
INSTALL METAL DRIP CAP
HEAD FLASHING
EXTEND FLASHING MIN. 1"
BELOW SILL FLEXIBLE FLASHING
EXTEND FLASHING MIN 2"
BEYOND JAMB FLASHING
INSTALL 6" SELF-ADHERING
FLASHING OVER DRIP CAP
NAILING FLANGE
FOLD HOUSE WRAP BACK DOWN
AND TAPE ACROSS THE HEAD OF
WINDOW AND THEN TAPE
DIAGONAL CUTS.
SEAL WINDOW FRAME TO INSIDE OF R.O.
W/ SEALANT AT SILL AND A MIN. 12" UP
BOTH JAMBS. SEAL BALANCE OF FRAME
WITH SEALANT OR NON-EXPANDING
FOAM. (PROVIDE BACKER ROD WHERE
REQUIRED)
SELF ADHERING FLEXIBLE FLASHING
FLUSH WITH INTERIOR SIDE OF SILL.
INTERIOR VIEW
NTS
STEP 1 STEP 2 STEP 4STEP 3
STEP 5 STEP 6 STEP 8STEP 7
MODIFIED CUT
Federal Emergency Management Agency
COMPANY:
WINDOW FLASHING DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-21REV. 1
Window Flashing Detail Notes
1. Install self-adhering flexible flashing at perimeters of window frame and seal window frame to the weather resistant barrier as shown in the details.
2. Flashing shall be pliable and adhesive waterproofing membrane with a removable release liner.
3. Cut flashing in lengths required for application as indicated on the details.
4. Seal over all fastening screw heads at windows before installing flashing around the window frame.
5. Window installation shall be per manufacturer’s installation instructions.
6. Window installation and flashing details are to be consistent with ASTM 2112, Method A-1, except self-adhering flashings shall be used.
7. It is the manufacturer’s responsibility to verify the compatibility of all products. This is includes, but not limited to: House wrap, sealants and self-adhering flashing materials used during production. WARNING:
Sealants and flashing materials may react adversely if not compatible.
8. Install all flashing materials per manufacture’s written installation instructions.
9. Self adhering flashing shall be rolled after placement.
W/H
1" WIDE NYLON STRAP, WRAPPED TIGHTLY
AROUND WATER HEATER AND SECURED
TO WALL FRAMING MEMBER WITH 2-#8
SCREWS (MIN. 1" PENETRATION).
(8) 7/16"x2-1/2"x15 GA. STAPLES WITH 2 ROWS OF STAPLES EQUALLY
SPACED (CUT STUD TO FILLER & BLOCK TO FILLER). NO GLUE REQUIRED.
2-1/4"
1x
FILLER
2x BLOCK 18" MIN.
M
I N
EXTERIOR WALL
4" SEMI-RIGID
ALUMINUM DUCT
FLOOR CAVITY
VENT CAP
THE FLOOR PERIMETER RAIL IS CUT TO
ACCOMMODATE AN IN FLOOR DRYER EXHAUST
DUCT AND A SINGLE BLOCK PERIMETER PIER
SUPPORT MUST BE INSTALLED ON SITE. SUPPORT
LOCATION MUST BE MARKED WITH A PIER LABEL.
FLOOR DECKING W/
VINYL FLOORING
CONTINUOUS UNDER
FLOOR DRAIN.
FLOOR JOIST
BOTTOM BOARD
PIPE HANGER
FLOOR DRAIN SHALL TERMINATE AT
SKIRT LINE WITH A PVC VENT
SCREEN MODEL SVC-IS15 PVC VENT
CAP WITH STAINLESS STEEL INSECT
SCREEN OR EQUIVALENT ON 1"
THREADED PIPE FITTING. VENT CAP
MAY BE PERMANENTLY CEMENTED
TO THIS PIPE.
SKIRTING (INSTALLED ON SITE)
PITCH PIPE TO
EXTERIOR
1" SCHEDULE 40 PVC PIPE
SEAL FLOOR PENETRATION
" DIAMETER DRAIN FLANGE
W/ SOLID COVER
2"x6"x48" GA. GALVANIZED RAIN
DIVERTER W/ TURN UNDER EDGE
Federal Emergency Management Agency
COMPANY:
MISC DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-30REV. 1
TYPICAL INTERIOR WALL NOTCH DETAIL
(FOR SPRINKLER PIPING)
A
D
B C
E
DRYER EXHAUST VENT DETAIL
(14' WIDE MHU'S ONLY)
DEHUMIDIFIER FLOOR DRAIN
Notes
1. Drain is for future dehumidifier that FEMA will provide.
Notes
1. Rain diverter shall be centered over all exterior doors. TPS compartment door is excluded.
2. Diverter shall be slipped up under the 3rd course of shingles from the eave.
3. Diverter shall be fastened with typical roofing staple or nail at 8" o.c. sloped
1/2" toward hinge side of door.
4. All fastener heads shall be covered with roofing cement.
RAIN DIVERTER DETAIL
WATER HEATER STRAPPING DETAIL
Notes
1. Water heater shall be strapped within the upper one-third and lower one-third of the water heater's vertical dimension. At the lower strapping point, a minimum of four inches shall be maintained above the water heater controls.
2. Strapping must be located so as to allow access to water controls and connections without interference when servicing water heater.
EDGE
END LAP
EDGE
TOP LAP
EDGE
EDGE
TYPICAL
3" 3"
UNDERLAYMENT
CEMENT
SHEATHING
DETAIL AT TOP LAP
TYPICAL
6" 6"
UNDERLAYMENT
CEMENT
SHEATHING
DETAIL AT EDGES
AND END LAPS
TYPICAL
30°
MAX.
36"
2"
10"
1" 1"
10"
1" 1"
10" 1
2"
SEALANT STRIP
SEE NOTE 5
SEE NOTE 4
SEE NOTE 3
SEE NOTE 1
Federal Emergency Management Agency
COMPANY:
MISC DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-31REV. 1
UNDERLAYMENT, CEMENTING DETAIL
THIS DETAIL DOES NOT INCLUDE CEMENTING
REQUIREMENTS FOR REQUIRED ICE
DAMMING PROVISIONS.
F
G
Notes
1. FASTENERS SHOULD BE PLACED 1" IN FROM EACH END OF THE SHINGLE WITH A PLUS OR MINUS 1/2"
TOLERANCE. DISTANCE OF A STAPLE FROM THE END OF THE SHINGLE SHOULD BE MEASURED FROM
THE STAPLE LEG CLOSEST TO THE SHINGLE END.
2. THE FASTENERS ABOVE THE CUT-OUTS SHOULD BE PLACED IN SUCH A WAY THAT THE MIDDLE OF THE
CROWN OF THE STAPLE OR THE CENTER OF THE NAIL HEAD IS PLUS OR MINUS 1" TO EITHER SIDE OF
THE CENTER OF THE CUT-OUT.
3. DEVIATION FROM THE HORIZONTAL UP TO AN ANGLE OF 30 DEGREES IS ACCEPTABLE.
4. FASTENERS IN THE SEALANT WILL BE ACCEPTABLE WHEN THE LOCATION OF THE SEALANT STRIP IS
SUCH THAT THE FASTENERS CANNOT BE PLACED ACCORDING TO THE DIRECTIONS PRINTED ON EACH
BUNDLE WRAPPER. FASTENERS SHOULD ONLY BE PLACE ABOVE THE SEALANT LINE IF THE LOCATION
OF THE SEALANT STRIP IS LESS THAN 3/4" FROM TOP OF CUT-OUT. IF FASTENERS CAN NOT BE PLACED
AS DESCRIBED, THEY MAY BE LOCATED NO MORE THAN 1/2" ABOVE THE TOP EDGE OF THE SEALANT
LINE AND MUST BE DRIVEN FLUSH TO THE SURFACE OF THE SHINGLE.
5. ALTERNATE FASTENER LOCATION IS PERMITTED ONLY WHEN BOTTOM EDGE OF SEALANT STRIP IS
LESS THAN 3/4" FROM TOP OF CUT-OUT.
6. ALT. FASTENER LOCATION AT SHINGLE ENDS IS 3" MAX. FROM THE EDGE RAIL SO THAT FASTENERS
SEAT FIRMLY IN THE DECKING MATERIAL. STRICTEST REQUIREMENTS SHALL BE USED.
7. REFER TO MANUFACTURER'S INSTRUCTIONS IN THE EVENT OF CONFLICT WITH THE INSTRUCTIONS
PROVIDED WITHIN THIS DETAIL.
8. FOR SHINGLE INSTALLATION AT EAVES, RAKES AND RIDGE SEE APPENDIX B - FEMA RECOVERY
ADVISOR NO. 2.
10 STAINLESS STEEL POP
RIVETS. LOCATE AS
SHOWN
8"x12"x26 GA. METAL POP
RIVETED TO JUMBO
MOUNTING BLOCK
8"x12"x VINYL SIDING
JUMBO MOUNTING BLOCK
(MID-AMERICA OR
EQUIVALENT)
4"8"
10"
Federal Emergency Management Agency
COMPANY:
MISC DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-32REV. 1
H
Transponder Sled Detail
Notes
1. See FEMA Specs for color of metal & mounting block.
2. See FEMA drawing package elevations for location.
3. The transponder mounting (transponder sled) location shall (X) not impact the functionality and performance of the transponder, damage the MH and/or the transponder under any circumstance.
4. The transponder location shall (X) be accessible.
5. The transponder location shall (X) allow removing the transponder without any special tool without damaging the MHU, the surface or the transponder.
6. There shall (X) not be any object obstructing the signal that is emitted and/or received from the satellites.
FEMA Supplied Transponder
8"" MAX.
8" x 6.5# I-BEAM
FLOOR
I-BEAM
E N
D W
A L
L
12" MIN.
1/8" FILLET WELD TOP, BOTTOM,
AND ONE SIDE OF I-BEAM TO THE WEB
OF I-BEAM HEADER
EXTERIOR ELECTRICAL JUNCTION BOX
ELECTRICAL CONDUCTORS INSTALLED
BETWEEN JUNCTION BOX AND A/C UNIT TO BE
RATED FOR EXTERIOR USE AND INSTALLED
WITHIN AN APPROVED EXTERIOR RATED
LISTED METAL RACEWAY OR LISTED RIGID
NON-METALLIC CONDUIT
AIR CONDITIONER COMPRESSOR UNIT W/
PROTECTIVE COVER. SEE FEMA SPEC.
HOLD DOWN CLIPS EACH CORNER.
USE 1/4" DIA. MIN. CORROSION RESISTANT "TEK"
SELF TAPPING SCREWS TO FASTEN HOLD DOWN
CLIPS TO SUPPORTS.
2x2 MIN. RUBBER VIBRATION DAMPING PAD
REQUIRED UNDER EACH HOLD DOWN.
SIDE VIEW
CROSSMEMBER
CORNER TO HAVE 2" RADIUS MINIMUM.
AC MOUNT DETAILS
13"
3" x 9" PLATE
1/8" MIN THICKNESS
SHARP EDGES
ROUNDED AT LEAST
1" RADIUS
NOTE:
PLATE LOCATION DIMENSIONS ARE APPROXIMATE
AND MAY VARY PER MANUFACTURER INSTALLATION
INSTRUCTIONS.
BOTH SIDES
OF SPLICE
PLATE
1/8"
1/8"
EQ.
I-BEAM SPACING VARIES
EQ.
2"
1/8" FILLET WELD
TOP, BOTTOM, AND ONE SIDE
OF I-BEAM TO THE WEB
OF I-BEAM HEADER
3" ROUND (±1/2") HOLE IN WEBBING FOR A/C LINE
HOOK UP w/ PRETECTIVE SLEEVE
(LOCATED TO THE RIGHT OF ADDED SUPPORT BEAM)
3" DIA. PVC PIPE AT LEAST 6" LONG
FRICTION FIT IN HOLE.
PLAN VIEW
END VIEW
PERIMETER OF A/C UNIT
13 GA. "C" CROSSMEMBER 1-1/2"x3"x1-1/2"x2'
(SPLIT FURNACE/AC MHU's ONLY) 1/8"
FILLET WELD TO HEADER & MAIN I-BEAM
(2-1/2" MIN LENGTH WELD)
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY:
CHASSIS AC MOUNT DETAILS
TITLE:
Scale: NTS
Date: 6/28/2019
VERSION:
SCALE: 1/4" = 1'-0" SCALE: 3/8" = 1'-0"
DRAWING NO.APPENDIX A
A-40REV. 1
TPS TANK
"D" RINGS FOR TPS
SECUREMENT
WITH RATCHET
STRAP (TYPICAL 4
PLACES) SEE A-51,
ELEVATION 3&4.
2" RATCHET STRAPS
WITH DOUBLE "J"
HOOK ENDS. STRAPS
TO ENCIRCLE TPS
SYSTEM.
TPS
5"
20"
SPRINKLER ALARM W/ 3/4"
THRU WALL CONDUIT.
SEE A-52, DETAIL 3.
A-51
A
31"5"
"D" RINGS FOR TPS
SECUREMENT WITH
RATCHET STRAP
(TYPICAL 4 LOCATIONS)
OUTLINE OF ALTERNATE
TPS SYSTEM
30 AMP,240V NEMA,
DRYER RECEPTACLE.
SEE ELEVATION 2.
SPRINKLER RISER -
SEE A-51, ELEV 2
T
O
NOTE:
OVERHEAD LIGHT, SPRINKLER
STORAGE BOX, 110 RECEPTACLE,
ANNUNCIATOR CONDUIT AND
WALL BACKERS NOT SHOWN FOR
CLARITY.
3" MAX.
M
A X
56"
FLOOR DRAIN (4 1/4" DIA.) SHALL
BE 3" MAX. FROM EITHER WALL
AND DISCHARGE TO EXTERIOR
OF HOME THRU SKIRTING. SEE
A-52, DETAIL 4
ANNUNCIATOR PANEL
W/ DOUBLE GANG BACK
BOX W/ COVER PLATE -
SEE A-52, DETAIL 2
A
Federal Emergency Management Agency
COMPANY:
TPS CLOSET - PLANS & NOTES
Scale: 1/2"=1'
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-50REV. 1
TPS CLOSET - PLAN SECTION A-A - TPS STRAPPING
TPS Closet Notes
1. The TPS system is provided by FEMA and shall be installed and secured with ratchet straps by the manufacturer at the plant.
2. The 36” nominal locking door for the TPS closet (Ref FEMA Spec. 10.1) shall be provided with a deadbolt lock. The deadbolt lock shall be Schlage 6 pin Everest cylinder, C123 keyway with the 6 pin combination of 746105 or equivalent.
3. The TPS closet door shall not be keyed the same as the entry doors to the MHU.
4. The sprinkler alarm shall be mounted in a single gang back box at the same height as the exterior lights on the exterior of the MHU in the location as shown on the drawings. The ¾” rigid PVC conduit shall extend one inch (1”) maximum into the TPS compartment.
5. The TPS annunciator panel shall be mounted on a double gang box in the location and height as shown on the drawings. The flexible PVC conduit shall be from the double gang box with a pull string to the single gang box with cover plate located by the 110 volt receptacle in the TPS closet as shown on the drawings. The flexible PVC conduit shall extend one inch maximum into the gang boxes.
6. The Pex sprinkler riser shall permit the rotation of the point of connection around the vertical axis of the sprinkler riser. A brass elbow shall be used to permit this rotation. If CPVC pipe is used, a solvent welded spears short repair coupling shall be installed to permit this rotation.
7. The water connector to the sprinkler riser shall be a 1 ½” cam locking fitting with dust cap that complies with FEMA Spec.
8. The drain and vent manifold shall be provided with drain connections for the TPS tank, the sprinkler riser, the TPS tank overflow and the TPS vent line.
(14' WIDE)
T
O P
F
A
L A
R M
B
X
10"
8"
4 10
2"
R
E F
F
E M
A
S
P E
C
16" TO 20"
10" TO 14"
12" TO 16"
T
O
SEE DETAIL 1,
A-52
Federal Emergency Management Agency
COMPANY:
TPS CLOSET - ELEVATIONS
Scale: 3/8"=1"
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-51REV. 1
ELEVATION 1 ELEVATION 2 ELEVATION 3 ELEVATION 4
TPS Notes
1. MHU Document Bin (ref. FEMA Spec. 7.73)
2. 3/4" PVC conduit for exterior TPS alarm (1" max. projection beyond interior wall finish). See A-52, Detail 3.
3. Red sprinkler system document storage case shall be a Justrite No. 23304, or equivalent.
4. TPS sprinkler head. See A-52, Detail 5.
5. Sprinkler piping
6. Reliable red sprinker storage cabinet, model A4 (large) or equivalent. (Ref. FEMA
Spec 25.108)
7. Wall switch to wall light. See note 9.
8. Single gang box with 1" PVC conduit for Annunciator Panel w/ pull string to #15 double gang box. Conduit run down wall, in floor and up to double gang box #15.
See Detail 2, A-52.
9. Wall light w/ clear shatter resistant plastic globe
10. Sprinkler pipe support bracket at 16" o.c. max. See A-52, Detail 6.
11. 240 electric dryer receptacle w/ round hole at top & "L" at the bottom.
12. 110 GFCI protected receptacle
13. 1" male cam-locking fitting. Fitting rotated around the brass elbow fitting so that the fitting is flush against the wall for TPS installation into the closet. Locking dust cap required.
14. D-ring tie down secured to wall backer with 2-#8 screws each "D"-ring
(minimum 1" penetration).
15. 1" PVC conduit into double gang box for Annunciator Panel with pull string from #8.
16. Floor drain extend to 1" min. beyond vinyl siding w/ PVC drain and model
SVC-IS15 with stainless steel insert screen or equivalent.
17. Connection port for water tank overflow and tank vent. Angle out 45° from exterior wall.
18. Connection port for water tank drain. Angle out 45° from exterior wall.
19. Sprinkler riser (see Detail 1, A-52). Drain w/ PVC vent screen model
SVC-IS15 or equivalent.
CPVC SINGLE FASTENER
STRAP TYPE HANGER.
" MIN.
PENETRATION
INTO STUD
2xWALL STUD W/
" GYP. BRD.
T
O
ATTACH HANGERS TO
STUD WITH MIN. 2" LONG
#10 WOOD SCREW (16"
O.C. MAX.)
RIGID PIPE SUPPORT
ATTACHED TO WALL STUD
NOTE: ALARM WILL BE INSTALLED ON SITE.
CONNECTION PORT FOR
SPRINKLER SYSTEM DRAIN &
FILLING TPS TANK.
MANIFOLD CONNECTION
PORT FOR WATER TANK
OVERFLOW AND TANK VENT
MAINFOLD
CONNECTION
PORT FOR WATER
TANK DRAIN
FLOOR DECKING
FLOOR JOIST
BOTTOM BOARD
E X
T E
R I O
R
W A
L L
SEAL FLOOR
PENETRATION
PIPE HANGER
VENT SCREEN
MODEL SVC-IS15
OR EQUIVALENT
ON 1" THREADED
PIPE FITTING.
PITCH PIPE TO DRAIN
1 IN. PVC CONDUIT
WITH PULL STRING
TO TPS CLOSET
DOUBLE-GANG
BACK BOX WITH
COVER PLATE FOR
INSTALLATION OF
ANNUNCIATOR
PANEL
SINGLE-GANG WEATHERPROOF
OUTLET BOX FOR INSTALLATION
ON VINYL SIDING
SOLID FLAT COVER PLATE.
WEATHERPROOF FOR EXTERIOR WALL.
3/4" PVC RIDGID CONDUIT TO TPS
CLOSET MAXIMUM PROTRUSION FROM
INTERIOR WALL SURFACE SHALL BE 1".
3" MAX.
1" MAX
MANIFOLD CONNECTION
PORTS SHALL BE 1" FEMALE
NPT THREADS, AND SHALL BE
ALIGNED PARALLEL TO SIDE
WALL OF THE CLOSET.
1" SCHEDULE 40 PVC PIPE
SKIRTING (INSTALLED ON SITE)
T
O
F
L O
O R
CEILING LINE
SPRINKLER
SOFFISTEEL
SPRINKLER
HOUSING OR
EQUIVALENT
UPONOR PEX PIPE
OR EQUIVALENT
UPONOR PEX
PIPE OR
EQUIVALENT
SPRINKLER
COVER PLATE
THROUGH-WALL MOUNTSURFACE MOUNT
COVER PLATE
CEILING LINE
Federal Emergency Management Agency
COMPANY:
TPS CLOSET & SPRINKLER DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-52REV. 1
DETAIL 1 - SPRINKLER RISER DRAIN
DETAIL 2 - ANNUNCIATOR PANEL DETAIL 3 - EXTERIOR ALARM
DETAIL 6 - PIPE HANGER
(FOR USE WITH SOFFI-STEEL SHIELD OR EQUIVALENT)
DETAIL 5 - SPRINKLER PIPE/HEADS INSTALLATION
2" 25
2" 1
2"
2"
SPRINKLER
RISER W/
INSULATION
SPRINKLER
DRAIN
MAIN I-BEAM
FLOOR JOIST
MHU Sprinkler
Riser Options
A
B
C
Location A is preferred for sprinkler drain line. At installer's option, locations labeled B and C are acceptable.
No minimum dimensions apply for locations B or C.
Drain and riser must be located inside the wall.
Rigid metal hanger secured to structural member to prevent rotation.
Ceiling
Transition to
PEX pipe
Drain line may be any pipe material or size allowed by NFPA 13D
Seal opening around pipe. (Typical)
" Schedule
40 steel pipe.
Galvanized required below the floor. Black iron or galvanized acceptable above the floor.
(1" pipe permitted only above the floor where approved hydraulic calculations show 1".)
Riser clamp
Seal opening in bottom board around pipe with approved tape. (Typical)
1" male NPT thread with cap
" male cam-locking fitting. Locking dust cap required. but not shown here.
Floor
Bottom Board
1" thick pipe insulation
11" or greater
Federal Emergency Management Agency
COMPANY:
SPRINKLER RISER PLANS & DETAILS
Scale: NTS
Date: 6/28/2019
DRAWING NO.APPENDIX A
A-60REV. 1
SPRINKLER RISER PLAN
(8' WIDE EXPRESS)
External TPS Notes
1. The external TPS system is provided by FEMA.
2. The 18” nominal locking door for the riser access shall be provided with a deadbolt lock. The deadbolt lock shall be Schlage 6 pin Everest cylinder, C123 keyway with the 6 pin combination of 746105 or equivalent.
3. The TPS riser access door dead bolt lock shall not be keyed the same as the entry doors to the MHU.
SECTION A-A - SPRINKLER RISER
| Sheets and Views |
| Fema 8x48 Express MHU (AC&Furnace)-A-1 COVER |
| Fema 8x48 Express MHU (AC&Furnace)-A-2 MISC HT REQ |
| Fema 8x48 Express MHU (AC&Furnace)-A-3 MISC HT REQ |
| Fema 8x48 Express MHU (AC&Furnace)-A-4 SINK PANEL |
| Fema 8x48 Express MHU (AC&Furnace)-A-10-DOOR DETAILS |
| Fema 8x48 Express MHU (AC&Furnace)-A-11-DOOR FLASHING |
| Fema 8x48 Express MHU (AC&Furnace)-A-20-WINDOW DETAILS |
| Fema 8x48 Express MHU (AC&Furnace)-A-21-WINDOW FLASHING |
| Fema 8x48 Express MHU (AC&Furnace)-A-30 MISC |
| Fema 8x48 Express MHU (AC&Furnace)-A-31 MISC |
| Fema 8x48 Express MHU (AC&Furnace)-A-32 MISC |
| Fema 8x48 Express MHU (AC&Furnace)-A-40 CHASSIS AC |
| Fema 8x48 Express MHU (AC&Furnace)-A-50 TPS |
| Fema 8x48 Express MHU (AC&Furnace)-A-51 TPS |
| Fema 8x48 Express MHU (AC&Furnace)-A-52 TPS |
| Fema 8x48 Express MHU (AC&Furnace)-A-60 |