MANUFACTURED HOUSING UNIT
FEDERAL EMERGENCY MANAGEMENT AGENCY
NextGen Express Unit
(HVAC Wall Mounted Package System)
June 28, 2019
VERSION 1
COVER PAGE
TITLE:
Scale: NTS
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-1.1
. Jun 28, 2019
INDEX
Dwg. No. Title
8B-1.1 Cover Page
8B-1.2 Index
8B-1.3 General Notes
8B-2 Floor Plan
8B-3 Door and Window Schedule
8B-4.1 Furniture Plan
8B-4.2 Installed Furniture Layout
8B-5 UFAS Layout
8B-6 Electrical Plan
8B-7 Water Lines
8B-8 Drain Lines
8B-9 HVAC Design and Overhead Duct Layout
8B-10 Elevations
8B-11.1 Chassis
8B-11.2 Chassis Details
8B-12 Floor Framing Layout
8B-13 Floor Decking Layout
8B-14 Interior Wall/Back Panel Layout
8B-15 Reserved
8B-16.1-.15 Interior Walls
8B-17.1&.2 End Wall Framing and Interior Sheathing
8B-18.1 Front Shearwall Framing and Exterior Sheathing
8B-18.2 Rear Shearwall Framing and Exterior Sheathing
8B-19 Front Door Sidewall
8B-20 Back Door Sidewall
8B-21 Roof Framing Layout
8B-22 Roof Sheathing Layout
8B-23 Roof Overhang Detail
8B-24.1 Kitchen Elevations
8B-24.2 Bathroom Elevations
8B-24.3 Reserved
8B-25.1 Sprinkler System Layout
8B-25.2 Sprinkler System Details
8B-26 Ship Loose Layout
8B-27 Transit Protection Details
8B-28 Transportation Lighting
8B-29.1 Tie Down System
8B-29.2 Exterior Wall Tie Down Details
8B-30 Double Stack Pier Layout & Details
APPENDIX A
Dwg. No. Title
A-1 Cover Page
A-2 Miscellaneous Height Requirement Details
A-3 Miscellaneous Height Requirement Details
A-4 Kitchen Sink Access Panel Details
A-10 Door Details
A -11 Door Flashing Details
A-20 Window Details
A-21 Window Flashing Details
A-30 Miscellaneous Details
A-31 Miscellaneous Details
A-32 Miscellaneous Details
A-50 TPS Closet Plan and Notes (14' Wide)
A-51 TPS Closet Elevations (14' Wide)
A-52 TPS Closet Details (14' Wide)
A-60 Sprinkler Riser Plan and Detail (8' Wide)
INDEX
TITLE:
Scale: NTS
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-1.2
MANUFACTURED HOUSING UNIT
Federal Emergency Management Agency
GENERAL NOTES
CODES AND STANDARDS
Manufactured Home Construction and Safety Standards 24 CFR 3280
Manufactured Home Procedural and Enforcement Regulations 24 CFR 3282
Uniform Federal Accessibility Standards (UFAS)
Standard for the installation of Sprinkler Systems in Manufactured Homes (NFPA 13D)
Referenced 2005 National Electrical Code (NFPA 70) Articles as Incorporated in HUD 24 CFR 3280
STRUCTURAL LOADS
Floor Live Load 40 PSF
Floor Dead Load 10 PSF
Roof Live Load 40 PSF
Roof Dead Load 10 PSF
Comply with Wind Zone 3 Requirements of 24 CFR 3280
Wood Roof Diaphragm
Wall Height: 7'-6"
GENERAL NOTES
TITLE:
Scale: NTS
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-1.3
WD
REFER
9'-2"27'-1"7'-7"
9'-6"
48'-0"
22'-8
4"29'-2"
36'-10
2"
2'-1
2" 5'-0
2"12'-1"6'-11
2"
29'-7
2"
9'-6"
22'-3
4"
17'-3"
41'-5
2"
10'-6"
5'-11
2"
4"
4" 2'-4
2"
14'-10"
36'-10
2"
3'-2" 2'-10" 2'-6"
2'-10"
4"
39'-6
2"
4"
3060E
5"
2" 3"
RANGE HOOD
RANGE
FIXED PANE
4 SHLVS
HVAC
PACKAGE
SYSTEM
2"
9'-2"
SHEARWALLS - WIND ZONE 3
NO. LENGTH PLF
64"
96" 637
SIDEWALL HEIGHT = 90"
TRUSS VERTICAL PROJECTION = 9
LIGHT & VENT SCHEDULE
ROOM TITLE AREA REQ'D LIGHT REQ'D VENT
LIVING/DINING
AREA
150 S.F. 12.0 S.F. 6.0 S.F.
BEDROOM 70.1 S.F. 5.61 S.F. 2.81 S.F.
SHEAR WALLS WIND ZONE 3
DESIGNATES A 2X4 INTERIOR WALL
DESIGNATES A 2X6 INTERIOR WALL
70.1 SQ. FT.
150.0 SQ. FT.
W/H
BATH
KITCHEN
LIVING/DINING AREA
BEDROOM
UTILITY
14'-3
2"
PANTRY
34"
20'-1
4"
18"
31'-10"
4" 24"
8" 25
2"
2"
FLOOR PLAN
TITLE:
Scale: 3/16" = 1'-0"
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-2
D1
D2
D3
W1
W2
D3
W1
W1
Door Notes
1. Exterior doors shall meet 24 CFR 3280.405 requirements and shall comply with Wind Zone 3 requirements.
2. All exterior doors shall be insulated fiberglass or steel with a maximum U-Value of 0.33.
3. All doors shall have lever type handles in compliance with UFAS 4.13.9.
4. For additional information on exterior and interior doors see FEMA specifications and Appendix A.
5. Return air grills shall be installed above doors unless the grill will be blocked by the sprinkler system and then may be installed in the door or wall.
6. Door stops shall be installed at all interior and wardrobe doors. Door stops may be installed on the door or the floor baseboard. Door stop finish to match interior hardware finish.
7. All bathroom and bedroom doors shall have a privacy lock. The lock mechanism shall be the button type
(UFAS 4.13.9) and located on the inside of the bathroom or bedroom.
8. The water heater compartment side of the water heater access door shall be covered with minimum 5/16 inch thick gypsum board.
9. The closet door shall be equipped with a passage lockset.
MARK
W1
W2
WIDTH
2'-6"
2'-6"
HEIGHT
5'-0"
2'-3"
TYPE
Single Hung Window
Fixed Pane Window
WINDOW SCHEDULE
Window Notes
1. Windows shall meet 24 CFR 3280.403 and 3280.404 requirements and shall comply with Wind Zone 3 requirements.
2. Windows shall be double paned, low E with vinyl frame. Windows shall have a minimum SHGC of 0.30 and a maximum U-Value of 0.36.
3. Windows shall have a design pressure rating of 58.
4. Windows shall have screens.
TOTAL WINDOW AREA: 44.27 SQ. FT.
D1
D2
HVAC
PACKAGE
SYSTEM
W/H
BATH
KITCHEN
LIVING/DINING AREA
BEDROOM
UTILITY
PANTRY
MARK
D1
D2
D3
WIDTH
3'-0"
3'-0"
2'-0"
HEIGHT
6'-8"
6'-8"
6'-8"
THICKNESS
1-3/8"
1-3/8"
1-3/8"
TYPE
Outswing Door
Hallway Doors
Closet & W/H Doors *
DOOR SCHEDULE
TOTAL EXTERIOR DOOR AREA: 43.28 SQ. FT.
D4 1'-6" 6'-8" 1-3/8" Sprinkler Riser Access Door
D4
DOOR AND WINDOW SCHEDULE
TITLE:
Scale: 3/16" = 1'-0"
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-3
HVAC
PACKAGE
SYSTEM
BATH
KITCHEN
LIVING/DINING AREA
BEDROOM
UTILITY
PANTRY
W/H
DINING
TABLE
LOVE SEAT
C O
F F
E E
T A
B L
E
LIVING ROOM
ITEM SPECIFICATIONS
LOVE SEAT 44" W x 24" D
COFFEE TABLE 30" W x 18" D
DINING ROOM
ITEM SPECIFICATIONS
DINING TABLE 36" L x 24" W
DINING CHAIR 2 IDENTICAL CHAIRS
PANTRY 24" W x 12" D
BEDROOM
ITEM SPECIFICATIONS
FULL BED 75" L x 54" W
DRESSER
(4 DRAWER)
30" W x 18" D x 48" H
BATHROOM
ITEM SPECIFICATIONS
MEDICINE CABINET 15" W x 25" H x 3" D
SHOWER
36" W x 36" L, FIBERGLASS
WC SEE FEMA SPEC
WATER HEATER 40 GALLONS
KITCHEN
ITEM SPECIFICATIONS
REFRIGERATOR
30" W x32.5" D, 18 CU. FT.
RANGE *
30" W x 28" D (MAX)
MICROWAVE
19" D MIN., 1.2 CU. FT.
DEHUMIDIFIER PROVIDED BY FEMA
DRESSER
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY: VERSION:
FURNITURE PLAN
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-4.1
Furniture And Appliances Notes
1. All refrigerators shall be ENERGY STAR qualified and have the ENERGY STAR label affixed to the appliance when delivered with the MHU.
2. Range and oven controls shall be at the front of the appliance.
3. The range hood shall extend the width of the range and a minimum of 3" beyond the front face of the overhead cabinet.
4. The range hood vent opening at the cap shall be screened with a corrosion-resistant, non-combustible wire mesh with
1/4" openings or equivalent.
5. A shower rod and new, neutral-colored plastic shower curtain (71" L x 71" H) with full set of rings/hooks shall be provided for all shower/bath fixtures.
6. Two (2) metal, rust-resistant, wall-mounted towel bars with chrome finish shall be installed in each bathroom.
7. Metal, rust-resistant, toilet-paper holder with chrome finish shall be installed in each bathroom.
8. Mattresses shall be innerspring, non-latex (can be polyester, cotton, or blend ticking and wadding) new mattresses with medium firmness and 9" to 11" height.
9. The range hood vent shall be vented through the exterior wall.
* General Notes
1. Range depth (Back of range to front edge of oven handle depth cannot exceed 28").
FEMA SUPPLIED
DEHUMIDIFIER
SYSTEM
BATH
KITCHEN
LIVING/DINING AREA
BEDROOM
UTILITY
PANTRY
W/H
DINING
TABLE
LOVE SEAT
C O
F F
E E
T A
B L
E
DRESSER
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY: VERSION:
INSTALLED FURNITURE LAYOUT
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-4.2
General Notes
1. Vendor to tape a copy of this drawing to the outside of the water heater compartment door.
SYSTEM
BEDROOM LIVING/DINING AREA KITCHEN
UTILITY
BATH
6 5 2
4 3 9 10
W/H
DINING
TABLE
LOVE SEAT
C O
F F
E E
T A
B L
E
UFAS MANEUVERING CLEARANCES AT DOORS AND TURNING SPACE CONFIGURATION LAYOUT
24" 18"
24"24
4"
DRESSER
HVAC
PACKAGE
SYSTEM
BEDROOM LIVING/DINING AREA KITCHEN
UTILITY
BATH
W/H
DINING
TABLE
LOVE SEAT
C O
F F
E E
T A
B L
E
UFAS CLEAR FLOOR SPACE LAYOUT
SEE NOTE 4
SEE NOTE 4
SEE NOTE 4
DRESSER
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY: VERSION:
UFAS LAYOUT
Scale: 1/8" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-5
UFAS Maneuvering Clearances at Doors and Egress Chart
Location UFAS Section and/or Figure References
Exterior Doors
1. Front Door – Living Room/Kitchen to Front Door 4.13.6 – Figure b – Push side
2. Front Door – Living Room/Bedroom to Front Door 4.13.6 – Figure b – Push side
3. Rear Door – Hall to Rear Door 4.13.6 – Figure b – Push side
4. Rear Door – Kitchen to Rear Door 4.13.6 – Figure c – Push side
Bedroom
5. Hallway to Bedroom 4.13.6 – Figure a – Push side – See Note 1
6. Bedroom to Hallway 4.13.6 – Figure a – Pull side
7. Bedroom to Closet 4.13.6 – Figure c – Pull side
8. Turning Space Configuration 4.2.3 – Figure a – 60" Diameter Space
Location UFAS Section and/or Figure References
Bath 1
9 Hall to Bath 4.13.6 – Figure a – Pull side
10. Bath to Hallway 4.13.6 – Figure a – Push side – See Note 1
11. Turning Space Configuration 4.2.3 – Figure b – T-Shaped Space
12. Lavatory Clear Floor Space 4.19.3 – 30” x 48”
13. Shower Clear Floor Space 4.21.2 – Figure 35(a) - 36” x 48”
14. Toilet Clear Floor Space 4.16.2 - Figure 28 – 56” x 60”
Living Room
15. Turning Space Configuration 4.2.3 – Figure a – 60" Diameter Space
Kitchen
16. Turning Space Configuration 4.2.3 – Figure b – T-Shaped Space
17. Range Clear Floor Space 4.34.6.2 – 30” x 48”
18. Sink Clear Floor Space 4.34.6.5(7) – 30” x 48”
19. Counter Work Surface Clear Floor Space 4.34.6.2 – 30” x 48”
20. Refrigerator Clear Floor Space 4.34.6.2 – 30” x 48”
Notes
1. Door does not have closer.
2. The minimum clear width for a single wheelchair continuous path is 36” (UFAS 4.2.1).
3. All appliances shall be UFAS Compliant.
4. 50% of shelf space shall be below 54" reach range (UFAS 4.25.3).
5. The ADA compliant range cannot be deeper than 28” (From rear wall to the furthest extend of the range handle .
6. The Range electrical receptacle must be recessed.
NOAA
GFCI-WP
S
S
G F
C I
SSS
H.T. GFCI
RH 16
SS
REFR
7-GFCI
GFCI
S
G F
C I
G F
C I
G F
C I
TV
TV
J
HVAC
PACKAGE
SYSTEM
G F
C I
W/H
SA
SA
T
GFCI-WP
44" AFF 18" AFF TO RECEPTACLE SCREWS
FE
SS
GFCI-WP
WP
WP
SS
Service Entrance J-Box
SINGLE OUTLET RECEPTACLE
FOR REFRIGERATOR
WP
SEE
GENERAL
NOTE 2
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY:
Cir. Purpose Type Wire Size Amps Pole
Bedroom 1 14-2 15 1
2 NA - -
3 NA - -
4 Kitchen 20 1
5 Kitchen 1
6 Ext. Recep 1
7 Washer 1
8 Dryer 30 2
9 Electric Range
10 Water Heater
11 Package System
12 Smoke Detectors 15 1
13 Reserved
GFCI
12-2
10-3
Per MFR. Specs.
14-3
20GFCI 12-2
20GFCI 12-2
20GFCI 12-2
Per MFR. Specs.
Per MFR. Specs.
14 Living Room 15 114-2
16 Lights/Recep 15 114-2
17 Dining Room 20 114-2
18 Refrigerator 15 114-2
Per MFR. Specs.
19 Bath Receps / Heat Tape 20 114-2
GFCI
GFCI
J
WP
Sym. Description
110 volt duplex recep-wall mounted
110 volt duplex-GFCI protected recept
220 volt recept-wall mounted
Light Fixture - Ceiling Mounted
Light Fixture - Wall mounted
Exhaust fan - Light Combo
Distribution panel board - 200 Amp
Exterior light fixture - weather proof
Junction Box
TV
FE
S
S
NOAA
T
Telephone Recept
TV Outlet
Fire Extinguisher
Switch
Switch - Three Way
Outlet for NOAA Weather radio
Thermostat
SA
Sym. Description
ELECTRICAL PLAN
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-6
TPS System
Smoke Alarm with strobe light- wired in series
30 28-3
Electrical and Lighting Notes
1. The highest breaker in the panel box should be 48” high. Panel box bottom must be at least 24” from the floor.
2. The light bulbs shall be LED, equivalent to 60-watt incandescent bulbs, min. 800 lumens, white in color, between 2,700 K and 4,100 K.
3. No glass shall be used in any of the lighting globes.
4. The exterior lights shall be stored in the refrigerator during transport.
5. Interconnected smoke alarms shall utilize the home’s primary power source and shall have battery backup.
6. The centerline of the switches and the top of thermostat must be installed at no more than 48” above the finished floor.
7. Electrical outlets must be no lower than 18" above the floor to the center of the receptacle screw.
8. The junction box for the telephone and cable shall be located within 4’ of the road side rear of the MHU.
9. Electric wiring may be done either through the floor or the ceiling.
10. The exterior service entrance junction box shall be rated NEMA 3 and minimum of 12” x 12” x 4”.
11. Service entrance junction box shall be mounted to floor joist between the I-beam and sidewall.
12. Service entrance junction box to be located within 10’ on the curb side rear of MHU.
13. The wiring from the service entrance junction box to service panel to be in seal-tight conduit.
14. Bathroom exhaust fan with light to be 75 cfm with an integrated timer to allow fan to operate sixty minutes minimum prior to turning off.
15. Kitchen range hood exhaust fan with a white light shall be a minimum 100 cfm exhaust fan, with separate switches.
16. Bathroom and kitchen exhaust fans shall vent directly to the outside.
17. Ceiling lights shall have 2 LED bulbs.
18. The bathroom vanity light shall be wall mounted with 3 LED bulbs.
19. The circuit breaker(s) providing power to the TPS unit shall be equipped with a UL-listed locking device that can secure the breaker(s) in the ON position. Devices shall be installed set to the ON position and shall be equipped with an appropriate lock that fits inside the panel board.
20. Kitchen countertop receptacles and switches must be furred out to be 24" (max) from front edge of countertop and no more than 44" to the top of the switches or receptacles above finished floor.
General Notes
1. The range electrical receptacle must be flush mount.
2. Circuit #15 has an external TPS electrical connection with a female IEC 60 309-2 international pin and sleeve connection. The external TPS electrical connection shall be located 24" in from the road side of the MHU and 12" up from the bottom of the exterior siding.
LEGEND
CUT OFF VALVE LOCATION
3/4" LINE (HOT)
1/2" LINE (HOT)
3/4" LINE (COLD)
1/2" LINE (COLD)
ADJACENT PIPE SIZES.
FITTING SIZES TO CORRESPOND TO
ALL SIZING OF PIPE + OR -, MUST
MEET OR EXCEED ANY APPLICABLE
2)
CODES.
1)
NOTES:
SInk
W/H
Washer
Lav
Stool
Shower
Inlet
Master Shutoff
DRAIN
Hose Bib
LOW POINT DRAIN IN WATER
LINES WITH SHUT OFF VALVES
Federal Emergency Management Agency
COMPANY:
WATER LINES
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-7
Water Supply System Notes
1. The water supply lines shall be Cross-linked polyethylene (PEX) or chlorinated polyvinyl chlorine (CPVC) and comply with the requirements of 24 CFR 3280.
2. All water lines shall be 1/2” unless noted.
3. The water supply inlet shall be 3/4” and have a brass quarter turn ball valve.
4. The water supply inlet shall extend not more than 6” below the bottom board.
5. The water supply inlet shall be located within 12” of the curb side of the home.
6. The water supply inlet shall not be located under an exterior door.
7. Individual secondary shut off valves shall be located on each water line at each fixture, except at the tub/shower or shower.
8. All water line floor penetrations shall be caulked or foamed. Caulk or foam shall be acceptable to be in contact with the water line material.
9. Adequately sized access panels (12” x 12” min) shall be located in the walls at all points where concealed plumbing slip joints exist. The access panels shall match the wall color and finish. Access panels shall be unobstructed and accessible for inspection and repair.
10. The MHU shall be equipped with a frost-free hose bib located near the main water supply inlet. It shall not be located under an exterior door.
11. Low point drain in water lines with shut off valves shall be located above bottom board and insulation. Vendor to provide access panel, labeled, "Low Point Drain."
SANITARY TEE
LONG TURN TY
CLEAN OUT PLUG
CAP & CHAIN
22.5° ELL
45° ELL
REDUCER BUSHING
90° CLOSET ST. ELL
DWV FITTING LEGEND
MECHANICAL VENT
90° LONG TURN ELL
DOUBLE SANITARY TEE
90° LONG TURN ST. ELL
LK
P-TRAP
COUPLING
NM
T
R
S
Q
O P
45° Y
DOUBLE ELL
F
JI
H
B
D
E
G
A
C
To Sewer
H
K.Sink
K
A
B
Washer
M
F
Stool
D
A
M
F
Lav
K
A
Shower
M
(Stool Vent)
H
A
B
M
F
SEE NOTES 5 THRU 7
H
B
B
A
F
K
A
H
Notes
1. FITTING SIZES CORRESPOND TO ADJACENT PIPE SIZES.
2. SINGLE (THIN) LINES REPRESENT 1-1/2" PIPE;
DARK (THICK) LINES REPRESENT 2" PIPE;
DOUBLE LINES REPRESENT 3" PIPE.
3. P-TRAP DIRECTIONS MAY VARY.
Federal Emergency Management Agency
COMPANY:
Drain System General Notes
1. Drain lines shall be ABS or PVC and comply with the requirements of 24 CFR 3280.
2. All drain lines shall be 1 ½” diameter unless noted.
3. The drain line system shall be accessible without removing the axles and wheels.
4. All drain line floor penetrations, except at tub/shower and shower floor penetrations shall be caulked or foamed. Caulk or foam shall be acceptable to be in contact with the drain line material.
5. The drain line which shall run below the floor and above the bottom board to the place of drain outlet not less than two feet (2') but not more than three feet (3') in front of the axle group.
6. The drain line outlet shall protrude at least six inches (6”), but not more than eight inches (8”), below the bottom board.
7. The drain line outlet shall have a threaded end and will be capped with a removable plastic cap and chain or strap.
DRAIN LINES
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-8
SYSTEM
9'-2"27'-1"10'-6"4" 4"
9'-6"36'-10
2"
48'-0"
BATH
LIVING/DINING AREA
BEDROOM
14x30 GRILL W/ FILTER
90 CFM
90 CFM
90 CFM
110 CFM
110 CFM 90 CFM
8" FLEX
8" FLEX
8" FLEX
8" FLEX 8" FLEX
6" FLEX
8x8 ID14x8 ID
90 CFM
8" FLEX
4'-8"
16'-8"
24'-8"
31'-4"
32'-8"
43'-4"
44'-8"
14 1/2"x30 1/2"x10"
PLENUM
10" JUMPER DUCT
42'-0"
14x30 GRILL
14 1/2"x30 1/2"x10" PLENUM
27'-4"
W/H
HVAC DESIGN AND
TITLE:
Scale: 3/16" = 1'-0"
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-9OVERHEAD DUCT DESIGN
Heating/
Cooling
HVAC Wall Mounted Package System Specifications
(1.5 Ton Package System)
HVAC General Notes
1. See FEMA specifications for programable and configurable thermostat requirements.
2. Duct system shall be constructed of Class 0 or Class 1 circular insulated flex ductwork or equal. Circular flex duct shall be sized per duct design calculations. All ducts to be insulated with a minimum of
R-4 insulation.
3. Metal supply registers shall be 8” x 8” with damper, RectorSeal MV-4 or equivalent.
4. All supply ducts shall be in the roof attic space.
5. All supply duct seams and fasteners shall be sealed with UL-181A or UL-181B listed duct tape.
6. The manufacturer shall provide a duct pressure test report (See FEMA Spec for testing procedure) for each MHU duct system showing duct leakage of 5 percent or less prior to FEMA acceptance of the
MHU.
7. No construction debris or sawdust shall be left in the duct system.
8. Undercutting of interior doors is not permitted.
9. Return air grilles shall be sized per 24 CFR 3280.715(b)(4).
10. N/A
11. When the sprinkler system obstructs the return air grille, it may be located in the interior door or interior wall.
HVAC Wall Mounted Package System Notes
1. The MHU shall be equipped with a specifically engineered HVAC wall mounted package system based on the size and intended use of the MHU, in accordance with 24 CFR 3280.506, that is compatible with the HVAC wall mounted package system size and capable of maintaining an average temperature of seventy degrees Fahrenheit (70°F) in the MHU.
2. The HVAC wall mounted package system shall not cause vibration within the MHU. The HVAC wall mounted package system shall be mounted in such a way as to dampen the vibrations and any sound that accompany the packaged during operation cycles.
3. The HVAC wall mounted package system shall be able to maintain the temperature based on the coldest average temperature of the operating area of the MHU.
4. The HVAC wall mounted package system will require the manufacturer to have a current Alternative Construction letter from HUD.
5. The HVAC wall mounted package system shall be installed with a curb unit to minimize vibration and sound transmitted to the MHU.
6. A motorized room ventilator shall be installed in the HVAC wall mounted package system.
7. The thermostat shall be designed to work with the HVAC wall mounted package system.
8. The ceiling return air grill located in the bedroom shall accommodate a filter.
9. Duct penetrations thru ceiling shall be sealed.
HITCH END ELEVATION TAIL END ELEVATION
8'-0"
8'-0"
3" 3"
M
A X
T
O
T
P
F
R
I D
G E
V
N
T
8'-6" EAVE TO EAVE MAX.
EXTERIOR
RECEPT. (GFCI)
3" 3"
M
T
R
I D
N
T
8'-6" EAVE TO EAVE MAX.
12"
HUD LABEL: APPROX. 12" UP FROM
FLOOR AND 12" FROM ROADSIDE.
HVAC
WALL
MOUNTED
PACKAGE
SYSTEM
BACK DOOR SIDE ELEVATION
FRONT DOOR SIDE ELEVATION
BACK DOOR
ANGLE RAIN DIVERTER OVER DOOR
EXTERIOR
LIGHT
RIDGE VENT (TYP.)
INTERIOR FLOOR LINE
VINYL SIDING BELOW DOORS TO COVER 2X8 PERIMETER RAILS.
PEEP
HOLES
ANGLE RAIN DIVERTER OVER DOOR
RIDGE VENT (TYP.)
PEEP
HOLES
FRONT DOOR
EXTERIOR
LIGHT
INTERIOR FLOOR LINE
24"
DRYER VENT.
RANGE EXHAUST FAN
EXTERIOR RECEPTACLE (GFCI)
SERVICE ENTRANCE BOX
HOSE BIB
TRANSPONDER
FEMA Manufactured Housing Units
Federal Emergency Management Agency
TITLE: VERSION:
ELEVATIONS
Scale: 1/8" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-10
Exterior Finish Notes
1. Siding shall be light gray vinyl.
2. Siding shall be double 4” lap.
3. Siding shall be approved for HUD Wind Zone III requirements.
4. The manufacturer shall provide a transponder sled. See Appendix A.
5. The sled shall be painted with a powder coat paint to match the exterior color of the MHU or white.
6. The transponder sled shall be made out of sheet metal.
32'-0" CTR. OF AXLES (66.7% OF FRAME LENGTH)
48"48"
16'-0" CTR. OF AXLES
32" 32"
10"x9# I-BEAM HEADER
10"x9# MAIN I-BEAM
CROSSMEMBER
(TYP)
32"
42"
21"
48'-0"
10"
(MOVED JOIST)
2'-2"
(ADDED JOIST)
5'-4"
6'-8"
9'-4"
10'-8"
13'-4"
14'-8"
17'-4"
18'-8"
21'-4"
22'-8"
26'-8"
28'-0"
29'-4"
30'-8"
32'-0"
33'-4"
34'-8"
36'-0"
37'-4"
38'-8"
42'-8"
41'-4" 45'-4"
46'-8"
FRAME CLIPS IN AXLE AREA ARE LOCATED ON INSIDE OF I-BEAM AS SHOWN.
2'-8"
25'-4"
10"x9# I-BEAM HEADER
10"x9# MAIN I-BEAM
13'-4" INSTALL TIRE BLOW-OUT
PROTECTION IN THIS AREA (BOTH SIDES)
25'-4" START BLOW-OUT PROTECTION
SEE CHASSIS DETAILS,
DETAIL "A"
DETAIL "B"
26'-9
2"
26"
6"
26"
6"
26"
6"
26"
28'-11
2"
29'-5
2"
31'-7
2"
32'-1
2"
34'-3
2"
34'-9
2"
36'-11
2"
96" LONGITUDINAL BRACKET
4'-0"
9'-4"
12'-0"
16'-0" 20'-0"24'-0"
40'-0" 44'-0"
- SPRING HANGER
DRAWING NOTES
FRAME CLIP DETAIL (SAME ON BOTH MAIN I-BEAMS).
**DIMS ARE PULLED FROM END OF HEADER BEAM.
**BE SURE TO VERIFY FLOOR JOIST LAYOUT TO MATCH CLIPS TO JOISTS.
LONGITUDINAL
BRACKET
LONGITUDINAL
BRACKET
32"48" 32" 48"48"48"48"48"32"
48'-0" 4'-0"8'-0"12'-0"16'-0"20'-0"24'-0"44'-0" 40'-0" 37'-4" 34'-8" 32'-0" 26'-8"29'-4"
96" LONGITUDINAL BRACKET
SEE CHASSIS DETAILS, DETAIL "C"
8"
8"
10 HOLES AT 10-1/4" O.C.
4"
FRONT AND REAR HEADER SHEARWALL LAG BOLT SPACING
" TYP. HOLE SPACING
Chassis Frame Notes
1. All metal-to-metal contact with 1/8” fillet weld minimum.
2. Floor shall be lagged to frame with frame clip, Fastec 9mm x 76mm listed lags or lags equivalent in size and strength at each joist and outrigger tip.
3. Clips shall be welded to the I-beam.
4. All parts of the chassis including added/welded parts shall be completely coated with waterproof paint.
5. Tires shall be new, 14.5” rim diameter, 14 ply with “G” load range.
6. Wheels and tires shall meet or exceed the axle rating and be rated for continuous speeds of 65 mph or greater.
7. All axles shall be new.
8. All axles shall be brake axles.
9. A valve stem cover shall be present on every tire.
10. The serial number shall be permanently stamped to the front header to comply with 3280.6. In addition, the serial number shall be painted with rust resistance contrasting color paint, 2 inches (2”) tall on the front header.
11. Rims, bolts, nuts, or other related tire-mounting hardware shall be new.
12. Longitudinal brackets shall be installed at 96” maximum from each end of the home.
13. Spring hangers shall be multi-leaf.
14. All rims shall be the same color.
15. Maximum typical pier spacing along main I-beams at 8' O.C. Typical pier load = 4250 lbs.
16. Manufacturer to place permanent indicators (paint or label) on each I-beam at 2'-0" in from each end, 12'-0" O.C. max.
and at door jambs for locations of temporary piers for storage.
17. Longitudinal bracket slot to face closest end of home
Frame Specs:
Main I-beam: 10X9#.
Front/Rear headers: 10x9#.
Cross members: 13 ga. C or Z, 1
"x3"x1
"@4'-0" O.C. Typ.
Outriggers: N/A.
Frame clip: 1"x1
"x12 ga.
Hitch Specs:
See Chassis Details, Detail "A"
Welding Specs:
1. All welds to be a minimum 1/8" unless otherwise noted. Weld beads can be concave in application as long as the weld size is met.
2. Coupler and jack shall be welded per manufacture's installation instructions.
3. I-beam splice plate shall be 4" wide x height of I-beam minus 1 1/4"x13 GA. splice plate can be offset +/- 1/4". Weld shall be full width of splice plate. Splice plate only required on one side of I-beam.
4. All weld lengths stated or shown are minimum lengths and shall have a tolerance of minus 1/4" (except spring hangers). Weld lengths that are not noted shall be full length.
CHASSIS
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-11.1
VERSION:
DRAWBAR I-BEAM - 12" X 10.8#
DRAWBAR CROSSMEMBER I-BEAM - 12" X 10.8#
REINFORCEMENT UNDER FRONT HEADER AND
CENTERED BETWEEN FRONT HEADER AND TONGUE.
VENTURE 2-5/16" - 60 DEGREE, 10,000 LB. COUPLER OR EQUIVALENT
JACK - VENTURE TOP MOUNT,
10,000 LB. GALVANIZED OR EQUIVALENT.
7-3/8" X 4" NOSE PLATE
1"x1 1/2"x12 GA. FRAME CLIP.
1/8" x 1-1/2" FILLET WELD TO TOP
FLANGE OF I-BEAM.
CROSSMEMBER -
C OR Z 1.5"x3"x1.5"
13 GA. AT 48" OC.
1-1/2" x 1-1/2" x 13 GA. ANGLE GUSSET
" x 1"L FILLET WELD TO I-BEAM AND
CROSSMEMBER
I-BEAM - 10" X 9# AT 68
"SPACING
FRONT AND REAR I-BEAM
HEADERS - 10" X 9#.
A
A
° BOTTOM OF
FRAME I-BEAM
1/8" x2" LONG
FILLET WELD
2"
SEE SLOT
DETAIL
" Ø HOLE
3"
4" 1
2"
4"
" Ø HOLES
SEE SLOT
DETAIL
" Ø HOLE
4" 1
2"
4"
2"1
2"
SLOT DETAIL
8"
16"
DETAIL "A-A"
" Ø
HOLE
SEE SLOT
DETAIL
F
U
L
L
M
A
X
M
A
X
N
O
W
E
L
D
1/4" FILLET WELD
EACH SIDE
Notes
1. Thickness is 4 gauge.
2. Vendor to assure all spring hangers are installed 90° to I-beam.
3. Shoulder bolts to be torqued per axle manufacturer requirements (Approximately
30 to 50 ft. lbs). Leaf spring to move freely in spring hanger.
I-BEAM FLANGE
LOOKING UP AT SPRING HANGER
SPRING HANGER
SPRING
HANGER
LEAF
SPRING
EQUALIZER
AXLE
U-BOLTS
LEAF
SPRING
SHACKLE LINK
WITH BOLTS
CENTER SPRING
HANGER
FRAME I-BEAM
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY:
CHASSIS DETAILS
TITLE:
Scale: NTS
Date: 6/28/2019
DRAWING NO.
8B-11.2
VERSION:
Express MHU (Package System)
DETAIL C: LONGITUDINAL TIE-DOWN BRACKET
DETAIL B: SPRING HANGER WELDING
DETAIL A: HITCH ASSEMBLY
DETAIL D: EQUALIZER & SHACKLE LINK FASTENING
DETAIL C: LONGITUDINAL TIE-DOWN BRACKET
DETAIL B: SPRING HANGER WELDING
DETAIL A: HITCH ASSEMBLY
LONGITUDINAL TIE-DOWN BRACKET (12 GA. MIN.) SHALL
HAVE 3150 LB. WORKING LOAD CAPACITY.
DETAIL D: EQUALIZER & SHACKLE LINK FASTENING
Notes
1. Shoulder bolts are to be used at all equalizer and shackle link locations.
2. Shoulder bolts shall be torqued per axle manufacturer requirements.
(Approximately 30 to 50 ft. lbs.)
3. Equalizer and shackle links are to move freely after shoulder bolts have been torqued.
4. Axle U-bolts shall be torqued per axle manufacturer requirements
(Approximately 70 to 95 ft. lbs.)
48'-0"
S
H E
A R
W A
L
J
I S
S
W
Z
S
H E
A R
W A
J
I S
W
A D
D E
D
J O
I S
T
M O
V E
D
J O
I S
T
F
R O
M
J O
I S
T
O
C
U
N L
E S
S
N
O T
E D
28"
2 - 2x6x18" treated lumber backers for mounting service entrance junction box. Fasten thru bottom board into joists above with 2 - #8x3" stainless steel screws or hot dipped galvanized (G185) screws each end.
Floor Framing Notes
1. The floor joists shall be 2 x 8 #2 SPF 16” o.c.
2. Edge rails shall be 2 x 8 #2 SPF.
3. Edge rail splice 4 x 5 x 20 GA metal connector plate on each side or 2 x 8 x min. 6" each side of joint block centered +/- 1”, to be fastened with 7/16 x 2 ½ x 15 GA staples or .131 x 3” PD nails (8) each side of edge rail with PVA 80% coverage.
Floor Insulation Notes
1. The insulation shall have a flame spread of 25 or less and a smoke development of 450 or less.
2. The floor insulation shall be a minimum of R-26 fiberglass blanket insulation. One full batt, one additional full width batt between the I-beams, and one additional 16” wide batt between joist outside of I-beams.
Bottom Board Notes
1. All penetrations sealed per bottom board manufacturer’s installation instructions.
2. Bottom board shall be a minimum of twenty (20) mil thickness.
3. Multiple layers of acceptable bottom board material per 3280.305(g)(6) may be used.
4. Fasten bottom board to perimeter framing per manufacturer’s installation instructions.
FLOOR FRAMING LAYOUT
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY: VERSION:
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-12
Floor joists to rim joist
Multiple joists (to each other)
(80% PVA glue coverage)
7/16 x 2-1/2 x 15Ga staple
OR 0.131 x 3" Nail
7/16 x 2-1/2 x 15Ga staple
OR 0.131 x 3" Nail
7 each
5 each
12" o.c.
12" o.c.
DESCRIPTION FASTENER QTY
FASTENING SCHEDULE - FLOOR FRAMING
Cut joist (header) to transv.
joist (straight or toenailed)
7/16 x 2-1/2 x 15Ga staple
OR 0.131 x 3" Nail
5 each
3 each
TOILET
4'-0"8'-0"8'-0"8'-0"8'-0"8'-0"4'-0"
8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0"
W/H
23'-8" KIT SINK
38'-3
4"
11'-1
2" WASHER
11'-9" WASH DRAIN
4'-4" LAV
2'-6"
5'-1" LAV
AUTOVENT
6" TOILET SUPPLY
1'-5"
P.BOX
23'-0" KIT DRAIN
123456
7 6 5 4 3 2 1
A
B
PHONE
WIRE
TV WIRE
44'-4"
45'-0"
DRAIN
6"
W/H
HOT &
COLD
PHONE
WIRE
TV WIRE
33'-0"
32'-4"
DEHUMIDIFIER
22'-4"
SHOWER
P-TRAP
10"
7'-6"
6'-1
4"
S H
O W
R
R
S
H O
W E
R
9'-7
4"
S
P R
I N
K L E
R
D R
A I N
39'-9
8"
S P
R I N
K L E
R
R I S
E R
Ø
Ø
Floor Decking Notes
1. The floor decking shall be 23/32” tongue-and-groove (T&G) OSB or APA-rated 24/0 index plywood laid out as shown in decking plan.
2. Decking shall be Exposure 1 rated.
3. Long edges of the panel shall be T&G installed perpendicular to the floor joist.
4. PVA (polyvinyl acetate) or equal shall be used as adhesive with 80% coverage.
5. Vinyl flooring shall be installed on all interior floors of the home installed per manufacturer’s installation instructions.
Federal Emergency Management Agency
COMPANY: VERSION:
FLOOR DECKING LAYOUT
Scale: 3/16" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-13
Decking to Joists 7/16 x 1-3/4 x 16Ga staple
OR 0.092 x 2" Nail
4" edges / 6" field w/ glue
6" edges / 10" field w/ glue
DESCRIPTION FASTENER APPLICATION
FASTENING SCHEDULE - FLOOR DECKING
P3
P1
P4
P6
P5
P9
P10
P12
P11
S2
E2
S1
HVAC
PACKAGE
SYSTEM
2"
2"x8
2" x
4"
21"x8
4"
2" x
2"
2"
3"
P13
P14
W/H
P15
P7
P8
P2
E1
BATH
KITCHEN
LIVING/DINING AREA
BEDROOM
UTILITY
PANTRY
General Notes
1. Gypsum to be jointed above all doors in line with jambs.
2. Horizontal and vertical gypsum layouts for interior walls are the same.
TOP PLATE SPLICE
BOTTOM PLATE SPLICE
2" X 4" X 20 GA.
Metal connector plate, one each side
Min 2" X 4" X 10" block centered over splice +/- 1" and fastened with
6-7/16" X 2 1/2" X 15 GA staples each side of splice
Min 2" X 4" X 10" block centered over splice +/- 1" and fastened with 6-7/16"
X 2 1/2" X 15 GA staples each side of splice
2" X 4" X 20 GA.
Metal connector plate, one each side
INTERIOR WALL/BACK PANEL PLAN
TITLE:
Scale: 3/16" = 1'-0"
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
Express MHU (Package System)
8B-14
Stud to top/bottom plate
Door header to stud or 0.131 x 3" nail
3 each
2 each
DESCRIPTION FASTENER APPLICATION
FASTENING SCHEDULE - INTERIOR WALLS
15 ga x 7/16"x 2-1/2" staple
Bottom plate to floor
12" o.c.
Gypsum to studs, 80% PVA glue
Alternative Gypsum to studs, 100% one part urathane glue
Gypsum to studs (shearwall)
Per product manufacturer's instructions
Stud to stud
Layflat to top/bottom plate
Top plate to ceiling or 0.131 x 3" nail
15 ga x 7/16"x 2-1/2" staple or 0.131 x 3" nail
15 ga x 7/16"x 2-1/2" staple
0.131 x 3" nail
15 ga x 7/16"x 2-1/2" staple
#8 x 3" screw
19 ga x 3/16"x 1-1/4" staple or drywall screw
Into layflat into trusses
19 ga x 3/16"x 1-1/4" staple or drywall screw
0.131 x 3" nail or #8 x 3" screw or
15 ga x 7/16"x 2-1/2" staple
2 each
3 each
2 each
12" o.c.
12" o.c.
12" o.c.
6" o.c. at edges and
12" o.c. in field
6" edges
12" o.c.
Interior wall to sidewall (non-shearwall)
Interior wall to interior wall
#8 screw (min. 1" penetration at 16" O.C.)
0.131 nail (min. 1" penetration at 16" O.C.)
#8 x 3" screw 6" o.c.
15 ga x 7/16"x 2-1/2" staple or 0.131 x 3" nail
Backers to stud
6 Each
15 ga X
" X 2
" staple or 0.131 X 3" nail
3 Each
(end grain only)
(end grain or toed)
RESERVED
FEMA Manufactured Housing Units
Federal Emergency Management Agency
COMPANY: VERSION:
Scale: NTS
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-15
P1
Gypsum Layout
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.1
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
25 1/2
P2
4 1/2 25 1/2 3
Gypsum Layout
4"
NOTCH FOR SPRINKLER SYSTEM PIPE
2x3x2
1x3x2
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.2
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P3 x x
B
A C
K E
R
D
N
BCKR
DOWN
2X6
T
O W
E L
B
A R
Gypsum Layout
2x4 studs
2x4 top plate
1x4 bottom plate
V T
R
L O
C A
T I O
N
BCKR
DOWN
2X6
COMPANY:
INTERIOR WALL
Scale: 1/2" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.3
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
37 1/2
P4 x x
B
A C
K E
R
U
P
Gypsum Layout
47 1/2 37 1/2x8 3/4 3
NOTCH FOR SPRINKLER
SYSTEM PIPE
NOTCH FOR SPRINKLER
SYSTEM PIPE
2x3x2
1x3x2
4"
14"x14" access panel (Oatley 34056 or equivalent). Panel cut gypsum access panels are not acceptable.
19 3/4 14
4 1/4
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.4
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P5
BCKR
UP
2X6
BCKR
UP
2X6
Gypsum Layout
28 1/2
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.5
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
37 1/2
P6 x
B
A C
K E
R
U
P
Gypsum Layout
43 1/2 37 1/2x8 3/4 7
RAG
2-1/4"
1x FILLER
2x BLOCK 18" MIN.
M
I N
NOTCH FOR SPRINKLER SYSTEM PIPE
-SEE APPENDIX A-30 DETAIL "B"
NOTCH FOR SPRINKLER
SYSTEM PIPE
54 7/8 14 3/4
RAG
2x6 SPRINKLER HEAD BACKER UP. SPRINKLER HEAD BACKER
LOCATION MAY VARY BASED ON SPRINKLER DESIGN.
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.6
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
25 1/2
P7
Gypsum Layout
1 1/2 25 1/2
1 1/2
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.7
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P8
Gypsum Layout
19 1/2
2x6 studs
2x6 top plate
1x6 bottom plate
NOTCH FOR
SPRINKLER
SYSTEM PIPE
2-1/4"
1x
FILLER
SEE APPENDIX A-30 DETAIL "B"
19 1/2
41 1/2
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.8
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P9
P A
N E
L
B
O X
Gypsum Layout
26 1/2
2x4 studs
2x4 top plate
1x4 bottom plate
E L
E C
T R
I C
A L
P A
N E
L
B
O X
E L
E C
T R
I C
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.9
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P10
Gypsum Layout
25 1/2
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.10
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P11
Gypsum Layout
5 1/4 21x8 1/2
5 1/4
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.11
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P12
Gypsum Layout
25 1/2
BCKR UP
2X6
BCKR UP
2X6
BCKR UP
2X6
BCKR UP
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.12
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P13
Horizontal Back Panel Gypsum Layout
60 1/2
2x3 studs
2x3 top plate
1x3 bottom plate
Dryer vent hole to exterior
WASHER/DRYER
12 1/2
Optional Back Panel Vertical Gypsum Layout
Nail on washer box size will vary. Manufacturer to verify size from the washer box vendor that will be used.
m a x
Gypsum is shown from the back side.
*Jig Side is NOT to have Gypsum
6 3/8
13 1/4
15 1/214
This wall not to be paneled on framing jig.
6"x9" louvered access panel (Oatley 34247 or equivalent) for recessed autovent
14"x14" washer p-trap access panel
(Oatley 34056 or equivalent)
To be paneled after floor plumbing is installed.
Standpipe cannot be more than 30" above the p-trap weir.
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.13
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
P14
Gypsum Layout
2x3 studs laid flat
2x3 top plate laid flat
2x3 bottom plate laid flat
2 1/2
COMPANY:
INTERIOR WALL
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.14
Scale: 1/2" = 1'-0"
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
V
A T
O R
Y
T
O
C
L
M
E D
I C
I N
E
C
A B
I N
C
K E
R
P15
BCKR
DOWN
2X6
2x4 studs
2x4 top plate
1x4 bottom plate
BCKR
DOWN
2X6
BCKR
DOWN
2X6
DOUBLE
6"x9" LOUVERED
ABS ACCESS
PANEL (OATEY
34247 OR
EQUIVALENT)
FOR RECESSED
AUTOVENT.
BCKR
DOWN
2X6
Back Panel Gypsum Layout
Gypsum is shown from the back side.
*Jig Side is NOT to have Gypsum
6 3/8
20 1/2
7 1/8
COMPANY:
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud. 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
9. Horizontal and vertical gypsum layouts are the same.
INTERIOR WALL
Scale: 1/2" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-16.15
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
E1
BATHROOM
A C
K E
R
U
P
OPTIONAL VERTICAL WALL BOARD PANEL BREAKS
H
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
I
P
L I C
A B
L E
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E x x
B A
C K
U
2x6 sprinkler head backer up.
Sprinkler head backer location may vary based on sprinkler design.
TOP PLATE SPLICE
NTS
BOTTOM PLATE SPLICE
NTS
3" X 5" X 20 GA.
Metal connector plate, one each side
Min 2" X 4" X 10" block centered over splice +/- 1" and fastened with full coverage approved adhesive and
6-7/16" X 2 1/2" X 15 GA staples or
4-.131x3" nails each side of splice
Min 2" X 4" X 10" block centered over splice +/- 1" and fastened with full coverage approved adhesive and
6-7/16" X 2 1/2" X 15 GA staples or
4-.131x3" nails each side of splice
3" X 5" X 20 GA.
Metal connector plate, one each side
Federal Emergency Management Agency
COMPANY:
END WALL FRAMING AND
Scale: 3/8" = 1'-0"
Date: 6/28/2019
DRAWING NO.
Express MHU (Package System)
8B-17.1
INTERIOR…