MANUFACTURED HOUSING UNIT
FEDERAL EMERGENCY MANAGEMENT AGENCY
NEXT GEN 3 BEDROOM UNIT
(HVAC WALL MOUNTED PACKAGED SYSTEM)
JUNE 28, 2019
VERSION 1
TITLE:
1/8" = 1'-0"
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
14' WIDE MHU
DATE:
SCALE:
COMPANY: VERSION:
14B3-1.1
COVER PAGE
(PACKAGED SYSTEM)
. Jun 28, 2019
DWG. NO.
TITLE
14F3-1.1
14F3-1.2
14F3-1.3
GENERAL NOTES
14F3-2
FLOOR PLAN
14F3-3
14F3-4.1
14F3-5
DOOR AND WINDOW SCHEDULE
14F3-6
14F3-7
DRAIN LINES
14F3-8
HVAC DESIGN AND OVERHEAD DUCT LAYOUT
14F3-9
INTERIOR WALL AND BACKPANELING LAYOUT (HORIZONTAL)
14F3-10
INTERIOR WALLS
14F3-11.1
FRONT SHEARWALL FRAMING AND EXTERIOR SHEATHING
14F3-12
ROOF FRAMING LAYOUT
14F3-13
ROOF SHEATHING LAYOUT
14F3-14
14F3-15
14F3-16.1-16.20
14F3-17.1-17.2
14F3-18.1
14F3-19
14F3-20
ROOF OVERHANG DETAIL
14F3-21
14F3-22
SPRINKLER SYSTEM LAYOUT
14F3-23
TRANSIT PROTECTION DETAILS
RESERVED
14F3-25.1
14F3-26
14F3-27
14F3-28
COVER PAGE
INDEX
UFAS LAYOUT
ELECTRICAL PLAN
WATER LINES
FURNITURE PLAN
FLOOR DECKING LAYOUT
INTERIOR WALL AND BACKPANELING LAYOUT (VERTICAL) - OPTIONAL
ELEVATIONS
CHASSIS
FLOOR FRAMING LAYOUT
ENDWALL FRAMING AND INTERIOR SHEATHING
SHIP LOOSE LAYOUT
FRONT DOOR SIDEWALL
BACK DOOR SIDEWALL
TIE DOWN SYSTEM
14F3-29.1
EXTERIOR WALL TIEDOWN DETAILS
14F3-29.2
KITCHEN ELEVATIONS
14F3-24.1
BATHROOM #1 ELEVATIONS
14F3-24.2
BATHROOM #2 ELEVATIONS
14F3-24.3
14F3-30
DOUBLE STACK PIER LAYOUT AND DETAILS
DWG. NO.
TITLE
A-1
A-2
A-3
COVER PAGE
MISCELLANEOUS HEIGHT REQUIREMENT DETAILS
APPENDIX A
MISCELLANEOUS HEIGHT REQUIREMENT DETAILS
A-4
KITCHEN SINK ACCESS PANEL DETAILS
A-10
DOOR DETAILS
A-11
DOOR FLASHING DETAILS
A-20
WINDOW DETAILS
A-21
WINDOW FLASHING DETAILS
A-30
MISCELLANEOUS DETAILS
A-40
CHASSIS AC MOUNT DETAILS
A-50
TPS CLOSET PLAN AND NOTES (14' WIDE)
A-51
TPS CLOSET ELEVATIONS (14' WIDE)
A-52
TPS CLOSET DETAILS (14' WIDE)
INDEX
14F3-11.2
CHASSIS DETAILS
14F3-18.2
RESERVED
14F3-25.2
REAR SHEARWALL FRAMING AND EXTERIOR SHEATHING
14F3-4.2
INSTALLED FURNITURE LAYOUT
A-31
A-32
MISCELLANEOUS DETAILS
MISCELLANEOUS DETAILS
A-60
SPRINKLER RISER PLAN AND DETAIL (8' WIDE EXPRESS)
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DRAWING NO.
DATE:
SCALE:
COMPANY: VERSION:
14B3-1.2
INDEX
14' WIDE MHU
MANUFACTURED HOUSING UNIT
FEDERAL EMERGENCY MANAGMENT AGENCY
GENERAL NOTES
CODES AND STANDARDS
Manufactured Home Construction and Safety Standards 24 CFR 3280
Manufactured Home Procedural and Enforcement Regulations 24 CFR 3282
Uniform Federal Accessibility Standards (UFAS)
Standard for the Installation of Sprinkler Systems in Manufactured Homes (NFPA 13D)
Referenced 2005 National Electrical Code (NFPA 70) Articles as Incorporated in HUD 24 CFR 3280
STRUCTURAL LOADS
Floor Live Load 40 PSF
Floor Dead Load 10 PSF
Roof Live Load 40 PSF
Roof Dead Load 10 PSF
Comply with Wind Zone 3 Requirements of 24 CFR 3280
Wood Roof Diaphragm
Wall Height: 7'-6"
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-1.3
DRAWING NO.
GENERAL NOTES
14' WIDE MHU
R E
F E
R
3060-E-SG
SEAT
W/H
30603060
B A
T H
BEDROOM #1
TPS
CLOSET
D R
Y E
R W
A S
H E
R
3060-E
3060-E-SG
S E
A T
BATH #2
PANTRY
KITCHEN
BEDROOM #3
BEDROOM #2
P.BOX
2381037
5'-3
2"
2"
38'-8"
2"
4'-9"
2"
8'-0"
2"
7'-3
2"
7'-10
2"
2"
5'-1"
2"
2'-2"
2"
9'-7"
2"
34'-3
2"
2"
5'-2
2"
2"
1'-10
2"
54'-6
2" 52'-1" 42'-3
2" 7'-9
2"
61'-4
4" 37'-0
2" 31'-4
4" 26'-8
4" 16'-10
4"
47'-3" 36'-4
4" 18'-8
4" 4'-0
4"
2'-4
2"
2"
R A
G
14x4 R.A.G.
x
A
G
84.00 SF
83.00 SF
85.00 SF
68'-0"
59'-11"
16'-0"21'-0
2"59'-11"65'-5"
DESIGNATES A 2X4 WALL
SHEARWALLS - WIND ZONE 3
PLFLENGTHNO.
130"1
SIDEWALL HEIGHT = 90"
162" 543
BEDROOM #3
TRUSS HEEL HEIGHT = 9-15/16"
LIGHT AND VENT SCHEDULE
REQUIRED VENTREQUIRED LIGHTROOM TITLE AREA
6.40 S.F.12.80 S.F.LIVING / DINING ROOM 160.00 S.F
3.36 S.F.6.72 S.F.BEDROOM #1 84.00 S.F.
3.40 S.F.6.80 S.F.BEDROOM #2 85.00 S.F.
3.32 S.F.6.64 S.F.83.00 S.F.
160.00 SF
6"
6"
18'-6"
SHEAR WALLS FOR WIND ZONE 3
(FIXED)
4 SHELVES
LIVING & DINING
ROOM
HVAC
PACKAGE
SYSTEM
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-2
DRAWING NO.
FLOOR PLAN
14' WIDE MHU
F E
R
3060-E-SG
SEAT
W/H
30603060
B A
BEDROOM #1
TPS
CLOSET
D R
Y E
R W
A S
H E
R
3060-E
3060-E-SG
S E
A T
BATH #2
PANTRY
KITCHEN
BEDROOM #3
BEDROOM #2
P.BOX
D1
D3
D1
D1
D2
D2 D2
D2
D2
D3
D3
D3
MARK
D1
D2
D3
WIDTH
3'-0"
3'-0"
2'-0"
HEIGHT
6'-8"
6'-8"
6'-8"
THICKNESS
1-3/8"
1-3/8"
1-3/8"
TYPE
Outswing Door
Hallway Doors
Closet & W/H Doors *
DOOR SCHEDULE
MARK
W1
W2
WIDTH
2'-6"
2'-6"
HEIGHT
5'-0"
2'-3"
TYPE
Single Hung Window
Fixed Pane Window
WINDOW SCHEDULE
W2W1 W1
W1 W1W1
TOTAL EXTERIOR DOOR AREA: 62.67 SQ. FT.
TOTAL WINDOW AREA: 69.87 SQ. FT.
(FIXED)
Door Notes
1. Exterior doors shall meet 24 CFR 3280.405 requirements and shall comply with Wind Zone 3 requirements.
2. All exterior doors shall be insulated fiberglass or steel with a maximum
U-Value of 0.33.
3. All doors shall have lever type handles in compliance with UFAS
4.13.9.
4. For additional information on exterior and interior doors see FEMA specifications and Appendix A.
5. Return air grills shall be installed above doors unless the grill will be blocked by the sprinkler system and then may be installed in the door or wall.
6. Door stops shall be installed at all interior and wardrobe doors. Door stops may be installed on the door or the floor baseboard. Door stop finish to match interior hardware finish.
7. All bathroom and bedroom doors shall have a privacy lock. The lock mechanism shall be the button type (UFAS 4.13.9) and located on the inside of the bathroom or bedroom.
8. The water heater compartment side of the water heater access door shall be covered with minimum 5/16 inch thick gypsum board.
9. The closet doors shall be equipped with passage locks.
Window Notes
1. Windows shall meet 24 CFR 3280.403 and 3280.404 requirements and shall comply with Wind Zone 3 requirements.
2. Windows shall be double paned, low E with vinyl frame. Windows shall have a maximum SHGC of 0.30 and a maximum U-Value of 0.36.
3. Windows shall have a design pressure rating of 58.
4. Windows shall have screens.
4 SHELVES
LIVING & DINING
ROOM
HVAC
PACKAGE
SYSTEM
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-3
DRAWING NO.
DOOR AND WINDOW SCHEDULE
14' WIDE MHU
R E
F E
R
SEAT
W/H
B A
BEDROOM #1
TPS
CLOSET
D R
Y E
R W
A S
H E
R
S E
A T
BATH #2
NIGHT-
STAND
N I G
H T
S T
A N
D
B U
N K
B
D
S
C O
F F
A B
L E
TABLE
END-
PANTRY
NIGHT-
STAND
KITCHEN
BEDROOM #3
BEDROOM #2
P.BOX
68'-0"
ITEM
SOFA
ARM-CHAIR
COFFEE TABLE
SPECIFICATIONS
72" W x 36" D
36" W x 32" D
30" W x 18" D
LIVING ROOM
END TABLE 12" W x 12" D
ITEM
DINING TABLE
DINING CHAIR
PANTRY
SPECIFICATIONS
72" L x 36" W
6 Identical Chairs
36" W x 12" D
DINING ROOM
ITEM
FULL BED
BUNK BED
DRESSER (4 DRAWER)
SPECIFICATIONS
75" L x 54" W
75" L x 39" W
48" W x 18" D
BEDROOMS
NIGHTSTAND 12" W x 12" D
ITEM
MEDICINE CABINET
BATH TUB
WC
SPECIFICATIONS
15" W x 25" H X 3" D
30" W x 60" L, FIBERGLASS
SEE FEMA SPEC
BATHROOM
WATER HEATER 40 GALLONS
ITEM
REFRIGERATOR
RANGE
MICROWAVE
SPECIFICATIONS
30" W x 32.5" D, 18 CU. FT.
30" W, 4 BURNERS
19" D MIN., 1.2 CU. FT.
KITCHEN
D R
E S
S E
R
D R
E S
S E
R
D R
E S
S E
R
(FIXED)
4 SHELVES
DEHUMIDIFIER PER FEMA
LIVING & DINING
ROOM
FEMA SUPPLIED DEHUMIDIFIER
HVAC
PACKAGE
SYSTEM
TITLE:
1/8" = 1'-0"
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-4.1
DRAWING NO.
FURNITURE PLAN
14' WIDE MHU
(PACKAGED SYSTEM)
Furniture and Appliance Notes
1. All refrigerators shall be ENERGY STAR qualified and have the ENERGY STAR label affixed to the appliance when delivered with the MHU.
2. Range and oven controls shall be at the front of the appliance.
3. The range hood shall extend the width of the range and a minimum of 3" beyond the front face of the overhead cabinet.
4. The range hood vent opening at the cap shall be screened with a corrosion-resistant, non-combustible wire mesh with
1/4" openings or equivalent.
5. A shower rod and new, neutral-colored plastic shower curtain (71" L x 71" H) with full set of rings/hooks shall be provided for all shower/bath fixtures.
6. Two (2) metal, rust-resistant, wall-mounted towel bars with chrome finish shall be installed in each bathroom.
7. Metal, rust-resistant, toilet-paper holder with chrome finish shall be installed in each bathroom.
8. Mattresses shall be innerspring, non-latex (can be polyester, cotton, or blend ticking and wadding) new mattresses with medium firmness and 9" to 11" height.
9. The range hood vent shall be vented through the exterior wall. . Jun 28, 2019
R E
F E
R
SEAT
W/H
B A
BEDROOM #1
TPS
CLOSET
D R
Y E
R W
A S
H E
R
S E
A T
BATH #2
NIGHT-
STAND
N I G
H T
S T
A N
D
B U
D
S
C O
F F
B
L E
TABLE
END-
PANTRY
NIGHT-
STAND
KITCHEN
BEDROOM #3
BEDROOM #2
P.BOX
68'-0"
D R
E S
S E
R
D R
E S
S E
R
D R
E S
S E
R
(FIXED)
4 SHELVES
LIVING & DINING
ROOM
FEMA SUPPLIED DEHUMIDIFIER
HVAC
PACKAGE
SYSTEM
TITLE:
1/8" = 1'-0"
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-4.2
DRAWING NO.
INSTALLED FURNITURE LAYOUT
14' WIDE MHU
(PACKAGED SYSTEM)
General Notes
1. Vendor to tape a copy of this drawing to the outside of the water heater compartment door.
F E
R
3060-E-SG
SEAT
W/H
30603060
B A
BEDROOM #1
TPS
CLOSET
D R
Y E
R W
A S
H E
R
3060-E
3060-E-SG
S E
A T
BATH #2
NIGHT-
STAND
N I G
H T
S T
A N
D
B U
D
S
C O
F F
B
L E
TABLE
END-
PANTRY
NIGHT-
STAND
KITCHEN
BEDROOM #3
BEDROOM #2
P.BOX
S
I D
E
A
10 9
5 6 7
UFAS MANEUVERING CLEARANCES AT DOORS AND TURNING SPACE CONFIGURATION LAYOUT
D R
E S
S E
R
D R
E S
S E
R
D R
E S
S E
R
(FIXED)
4 SHELVES
LIVING & DINING
ROOM
FEMA SUPPLIED DEHUMIDIFIER
HVAC
PACKAGE
SYSTEM
R E
F E
R
3060-E-SG
SEAT
W/H
30603060
B A
BEDROOM #1
TPS
CLOSET
D R
Y E
R W
A S
H E
R
3060-E
3060-E-SG
S E
A T
BATH #2
NIGHT-
STAND
N I G
H T
S T
A N
D
B U
D
S
C O
F F
B
L E
TABLE
END-
PANTRY
NIGHT-
STAND
KITCHEN
BEDROOM #3
BEDROOM #2
P.BOX
S
I D
E
A
36" PATH
36" PATH
36" PATH
KITCHEN
UFAS CLEAR FLOOR SPACE LAYOUT
D R
E S
S E
R
D R
E S
S E
R
D R
E S
S E
R
(FIXED)
SEE NOTE 4.
4 SHELVES
LIVING & DINING
ROOM
FEMA SUPPLIED DEHUMIDIFIER
HVAC
PACKAGE
SEE NOTE 4
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-5
DRAWING NO.
UFAS LAYOUT
Location UFAS Section and/or Figure References Exterior Doors
1. Front Door - Hall to Front Door 4.13.6 - Figure b - Push side
2. Front Door - Living Room to Front Door 4.13.6 - Figure c - Push side
3. Rear Door - Hall to Rear Door 4.13.6 - Figure c - Push side
4. Rear Door - Kitchen to Rear Door 4.13.6 - Figure b - Push side
Bedroom 1
5. Hallway to Bedroom 1 4.13.6 - Figure a - Push side - See Note 1.
6. Bedroom 1 to Hallway 4.13.6 - Figure a - Pull side
7. Bedroom 1 to Closet 4.13.6 - Figure a - Pull side
8. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space
Bath 1
9. Bedroom/Hallway to Bath 1 4.13.6 - Figure c - Push side
10. Kitchen/Hallway to Bath 1 4.13.6 - Figure b - Push side
11. Bath 1 to Hallway 4.13.6 - Figure a - Pull side
12. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space
13. Lavatory Clear Floor Space 4.19.3 - 30” x 48”
14. Tub/Shower Clear Floor Space 4.20.2 - Figure 33(a) - 30” x 60”
15. Toilet Clear Floor Space 4.16.2 - Figure 28 - 56” x 60”
Living Room
16. Turning Space Configuration 4.2.3 - Figure b - T-Shaped Space
Location UFAS Section and/or Figure References Kitchen
17. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space
18. Range Clear Floor Space 4.34.6.2 - 30” x 48”
19. Sink Clear Floor Space 4.34.6.5(7) - 30” x 48”
20. Counter Work Surface Clear Floor Space 4.34.6.2 - 30” x 48”
21. Refrigerator Clear Floor Space 4.34.6.2 - 30” x 48” Bedroom 2
22. Hallway to Bedroom 2 4.13.6 - Figure a - Push side - See Note 1.
23. Bedroom 2 to Hallway 4.13.6 - Figure a - Pull side
24. Bedroom 2 to Closet 4.13.6 - Figure a - Pull side
25. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space Bath 2
26. Kitchen/Hallway to Bath 2 4.13.6 - Figure b - Push side
27. Bedroom/Hallway to Bath 2 4.13.6 - Figure c - Push side
28. Bath 2 to Hallway 4.13.6 - Figure a - Pull side
29. Turning Space Configuration 4.2.3 - Figure b - T-Shaped Space
30. Lavatory Clear Floor Space 4.19.3 - 30” x 48”
31. Tub/Shower Clear Floor Space 4.20.2 - Figure 33(a) - 48” x 60”
32. Toilet Clear Floor Space 4.16.2 - Figure 28 - 48”x56” Bedroom 3
33. Kitchen/Hallway to Bedroom 3 4.13.6 - Figure b - Push side - See Note 1.
34. Bath 2/Hallway to Bedroom 3 4.13.6 - Figure c - Push side
35. Bedroom 3 to Hallway 4.13.6 - Figure a - Pull side
36. Bedroom 3 to Closet 4.13.6 - Figure a - Pull side
37. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space
UFAS Maneuvering Clearances at Doors and Egress Chart - 3 Bedroom
14' WIDE MHU
(PACKAGED SYSTEM)
Notes
1. Door does not have closer.
2. The minimum clear width for a single wheelchair continuous path is 36” (UFAS 4.2.1).
3. All appliances shall be UFAS Compliant.
4. 50% of shelf space shall be below 54" reach range (UFAS 4.25.3)
5. Location of tub/shower seat shall be within UFAS forward reach range of tub/shower controls (UFAS 4.20.3 and Fig. 5(a)).)
F E
R
SEAT
W/H
D R
Y E
R W
A S
H E
R
S E
A T
PANTRY
P.BOX
S
I D
E
A
SS
S
S
GFCI-WP
NOAA
S
TV
WP-16
SS
19-GFCI
SA
7-GFCI
SSS
Back box for exterior alarm.
S
S
GFCI-WP
141717
GFCI-WP 6
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
RH-16
TPS Annunciator Panel
SA
SSS
WP-16
S
S
TV
3 NOAA
S
SA
S
S
SSS
19-GFCI
TV
NOAA
SA
FE
T
H.T.
S
J
Service entrance J-Box
GFCI-WP
GFCI
TV
(FIXED)
4 SHELVES
HVAC
PACKAGE
Single outlet recept for refrigerator
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
Cir. Purpose Type Wire Size Amps Pole
Bedroom 1 14-2 15 1
2 Bedroom 2 15 1
3 Bedroom 3 15 1
4 Kitchen 20 1
5 Kitchen 1
6 Ext. Recep 1
7 Washer 1
8 Dryer 30 2
9 Electric Range
10 Water Heater
11 Package System
12 Smoke Detectors 15 1
13 Reserved
GFCI
14-2
14-2
12-2
10-3
Per MFR. Specs.
14-3
20GFCI 12-2
20GFCI 12-2
20GFCI 12-2
Per MFR. Specs.
Per MFR. Specs.
14 Living Room 15 114-2
15 TPS System
16 Lights/Recep 15 114-2
17 Dining Room 20 114-2
18 Refrigerator 15 114-2
Per MFR. Specs.
Per MFR. Specs.
19 Bath Receps / Heat Tape 20 114-2
GFCI
GFCI
J
WP
Sym. Description
110 volt duplex recep-wall mounted
110 volt duplex-GFCI protected recept
220 volt recept-wall mounted
Light Fixture - Ceiling Mounted
Light Fixture - Wall mounted
Exhaust fan - Light Combo
Distribution panel board - 200 amp
Exterior light fixture - weather proof
Junction Box
TV
FE
S
S
NOAA
T
Smoke Alarm w/ Strobe Light - wired in series
Telephone Recept
TV Outlet
Fire Extinguisher
Switch
Switch - Three Way
Outlet for NOAA Weather radio
Thermostat
SA
Sym. Description
14B3-6
DRAWING NO.
ELECTRICAL PLAN
14' WIDE MHU
(PACKAGED SYSTEM)
Electrical And Lighting Notes
1. The highest breaker in the panel box should be 48" high. Panel box bottom must be at least 24" from the floor.
2. The light bulbs shall be LED, equivalent to 60-watt incandescent bulbs, minimum 800 lumens, white in color, between 2,700 K and 4,100 K.
3. No glass shall be used in any of the lighting globes.
4. The exterior lights shall be stored in the refrigerator during transport.
5. Interconnected smoke alarms shall utilize the home's primary power source and shall have battery backup.
6. The center line of the switches and the top of the thermostat must be installed at no more than 48” above the finished floor.
7. Electrical outlets must be no lower than 18" above the floor to the center of the receptacle screw.
8. The junction box for the telephone and cable shall be located within 4' of the road side rear of the MHU.
9. Electric wiring may be done either through the floor or the ceiling.
10. The exterior service entrance junction box shall be rated NEMA 3 and minimum of 12” x 12” x 4”.
11. Service entrance junction shall be mounted to floor joist between the I-beam and sidewall.
12. Service entrance junction box to be located within 10' on the curb side rear of MHU.
13. The wiring from the service entrance junction box to service panel to be in seal-tight conduit.
14. Bathroom exhaust fan with light to be 75 cfm with an integrated timer to allow fan to operate sixty minutes minimum prior to turning off.
15. Kitchen range hood exhaust fan with a white light shall be a minimum 100 cfm exhaust fan, with separate switches.
16. Bathroom and kitchen exhaust fans shall vent directly to the outside.
17. Ceiling lights shall have 2 LED bulbs.
18. The bathroom vanity light shall be wall mounted with 3 LED bulbs.
19. The circuit breaker(s) providing power to the TPS unit shall be equipped with a UL-listed locking device that can secure the breaker(s) in the ON position. Devices shall be installed set to the ON position and shall be equipped with an appropriate lock that fits inside the panel board.
20. Kitchen countertop receptacles and switches must be furred out to be 24" (max) from front edge of countertop, and no more than 44" to the top of the switches or receptacles above finished floor.
21. See TPS closet and TPS closet elevations for electrical locations in Appendix A.
LEGEND
CUT OFF VALVE LOCATION
3/4" LINE (HOT)
1/2" LINE (HOT)
3/4" LINE (COLD)
1/2" LINE (COLD)
ADJACENT PIPE SIZES.
FITTING SIZES TO CORRESPOND TO
ALL SIZING OF PIPE + OR -, MUST
MEET OR EXCEED ANY APPLICABLE
2)
CODES.
1)
Notes
W/H
Washer
Lav
Stool
Tub
K.Sink
Inlet
Master Shutoff
Stool
Tub
Hose Bib
Lav
Low point drain in water lines with shut-off valves
NTS
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-7
DRAWING NO.
WATER LINES
14' WIDE MHU
(PACKAGED SYSTEM)
Water Supply System Notes
1. The water supply lines shall be Cross-linked polyethylene (PEX) or chlorinated polyvinyl chlorine (CPVC) and comply with the requirements of 24 CFR 3280.
2. All water lines shall be 1/2” unless noted.
3. The water supply inlet shall be 3/4” and have a brass quarter turn ball valve.
4. The water supply inlet shall extend not more than 6” below the bottom board.
5. The water supply inlet shall be located within 12” of the curb side of the home.
6. The water supply inlet shall not be located under an exterior door.
7. Individual shut off valves shall be located on each water line at each fixture, except at the tub/shower or shower.
8. All water line floor penetrations shall be caulked or foamed. Caulk or foam shall be acceptable to be in contact with the water line material.
9. Adequately sized access panels (12” x 12” min) shall be located in the walls at all points where concealed plumbing slip joints exist. The access panels shall match the wall color and finish. Access panels shall be unobstructed and accessible for inspection and repair.
10. The MHU shall be equipped with a frost-free hose bib located near the main water supply inlet. It shall not be located under an exterior door.
11. Low point drain in water lines with shut-off valves shall be located above bottom board and insulation. Vendor to provide access panel, labeled "Low Point Drain".
Stool
D
SANITARY TEE
LONG TURN TY
CLEAN OUT PLUG
CAP & CHAIN
22.5° ELL
45° ELL
REDUCER BUSHING
90° CLOSET ST. ELL
FITTING SIZES CORRESPOND TO ADJACENT PIPE SIZES.
DOUBLE LINES REPRESENT 3" PIPE.
DARK (THICK) LINES REPRESENT 2" PIPE;
SINGLE (THIN) LINES REPRESENT 1-1/2" PIPE;
DWV FITTING LEGEND
P-TRAP DIRECTIONS MAY VARY.3)
2)
1)
MECHANICAL VENT
90° LONG TURN ELL
DOUBLE SANITARY TEE
90° LONG TURN ST. ELL
LK
P-TRAP
COUPLING
NM
T
R
S
Q
O P
45° Y
DOUBLE ELL
F
JI
H
B
D
E
G
A
C
To Sewer
A
B
Tub
A
F
M
(Stool Vent)
H
B
H
F
M
L
F
Lav
K
A
H
F
M
L
F
K.Sink
K
A
B
C
H
Washer
L
M
F
F
K
Stool
D
H
B
Tub
A
F
M
(Stool Vent)
H
F
M
L
F
Lav
A
K
SEE NOTES 5 THRU 7
Notes
NTS
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-8
DRAWING NO.
DRAIN LINES
14' WIDE MHU
(PACKAGED SYSTEM)
Drain System General Notes
1. Drain lines shall be ABS or PVC and comply with the requirements of 24 CFR 3280.
2. All drain lines shall be 1 ½” diameter unless noted.
3. The drain line system shall be accessible without removing the axles and wheels.
4. All drain line floor penetrations, except at tub/shower and shower floor penetrations shall be caulked or foamed. Caulk or foam shall be acceptable to be in contact with the drain line material.
5. The drain line which shall run below the floor and above the bottom board to the place of drain outlet not less than two feet (2') but not more than three feet (3') in front of the axle group.
6. The drain line outlet shall protrude at least six inches (6”), but not more than eight inches (8”), below the bottom board.
7. The drain line outlet shall have a threaded end and will be capped with a removable plastic cap and chain or strap.
ANGLE RAIN DIVERTER OVER DOOR
EXTERIOR LIGHT
FRONT DOOR
TPS DOOR BACK DOOR
PEEP HOLES
PEEP HOLES
ANGLE RAIN DIVERTER OVER DOOR
EXTERIOR LIGHT
EXTERIOR ALARM DEVICE BOX w/ COVER PLATE
RIDGE VENT (TYP.)
M
X
O
T
P
F
R
I D
G
V
N
T
14'-0" EAVE TO EAVE
13'-6"
INTERIOR FLOOR LINE
INTERIOR FLOOR LINE
M
T
R
I D
N
T
14'-0" EAVE TO EAVE
13'-6"
VINYL SIDING BELOW DOORS TO COVER 2X8 PERIMETER RAILS.
FRONT DOOR SIDE ELEVATION
HITCH END ELEVATION TAIL END ELEVATION
BACK DOOR SIDE ELEVATION
3"3"3"3"
HUD LABEL: APPROX. 12" UP
FROM FLOOR AND 12" FROM
ROADSIDE.
EXTERIOR RECEPTACLE (GFCI)
RIDGE VENT (TYP.)
EXTERIOR RECEPTACLE (GFCI)
RANGE VENT
EXTERIOR RECEPTCLE (GCFI)
(6" ABOVE FINISHED FLOOR)
SERVICE ENTRANCE
JUNCTION BOX
PROTECTIVE COVER
PER FEMA SPEC.
HOSE BIB
TRANSPONDER
OSB WIND DIVERTERS
TITLE:
Scale: 1/8" = 1'-0"
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency 14B3-10
DRAWING NO.
ELEVATIONS
14' WIDE MHU
(PACKAGED SYSTEM)
Exterior Finishes Notes
1. Siding shall be light gray vinyl.
2. Siding shall be double 4" lap.
3. Siding shall be approved for HUD Wind Zone 3 requirements.
4. The manufacturer shall provide a transponder sled. See Appendix A.
5. The sled shall be painted with a powder coat paint to match the exterior color of the MHU or White.
6. The transponder sled shall be made out of sheet metal.
37'-0
4"
48 48
4'-0"8'-0"68'-0" 24'-0"32'-0"
68'-0"
48 4848 4848 48
20'-0" 16'-0" 12'-0"28'-0"
36'-0"
39'-10"
3737373746484848
20'-0" INSTALL TIRE BLOW-OUT
PROTECTION IN THIS AREA (BOTH SIDES)
20'-0" LENGTH OF SISTER BEAM (TYP.)
42'-11"46'-0"49'-1"52'-2"56'-0"60'-0"64'-0"
261126112611261126
39'-2
4"
40'-1
4"
42'-3
4"
43'-2
4"
45'-4
4"
46'-3
4"
48'-5
4"
49'-4
4"
51'-6
4"
- SPRING HANGER
- SISTER BEAM
36'-0" START SISTER BEAM AND BLOW-OUT PROTECTION
S
I D
E
A
Drawing Notes
FRAME CLIP DETAIL
(SAME ON BOTH MAIN I-BEAMS)
**DIMS ARE PULLED FROM END OF HEADER BEAM.
**BE SURE TO VERIFY FLOOR JOIST LAYOUT TO MATCH CLIPS TO JOISTS.
68'-0"
FRAME CLIPS IN AXLE AREA ARE LOCATED ON INSIDE OF SISTER BEAM AS SHOWN.
1'-4"
2'-8"
5'-4"
6'-8"
9'-4"
10'-8"
13'-4"
14'-11"
(MOVED JOIST)
17'-5
4"
18'-9
4"
21'-4"25'-4"
26'-8"
29'-4"
22'-8"30'-8"
33'-4"
34'-8"
37'-4"
38'-8"
40'-0"
41'-4"
42'-8"
44'-0"
45'-4"
46'-8"
48'-0"
49'-4"
50'-8"
52'-0"
53'-7"
54'-8"
57'-4"61'-4"
62'-8"
65'-4"
66'-8"
LONGITUDINAL
BRACKET
LONGITUDINAL
BRACKET
58'-5"
(MOVED JOIST)
4 TYP. HOLE SPACING
FRONT AND REAR HEADER SHEARWALL LAG BOLT SPACING
A-FRAME
RE-INFORCEMENT
CENTERED AND
UNDER FRONT
HEADER
DETAIL "B"
DETAIL "C", SEE CHASSIS DETAILS
52'-5
4"
54'-7
4"
SEE CHASSIS DETAILS, DETAIL "A"
3'-6"
12" X 10.8# I-BEAM HEADER12" X 10.8# I-BEAM HEADER
LONGITUDINAL BRACKETS LONGITUDINAL BRACKETS
22'-0" CENTER OF AXLES
46'-0" CENTER OF AXLES (67.6% OF FRAME LENGTH)
17'-2
4"
18'-6
4"
TITLE:
Scale: 1/8" = 1'-0"
Date: 6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency 14B3-11.1
DRAWING NO.
CHASSIS
14' WIDE MHU
(PACKAGED SYSTEM)
Chassis Frame Notes
1. All metal-to-metal contact with 1/8” fillet weld minimum.
2. Floor shall be lagged to frame with frame clip, Fastec 9mm x 76mm listed lags or lags equivalent in size and strength at each joist and outrigger tip.
Alternate lags must be reviewed and approved by FEMA or their designee.
3. Clips shall be welded to the I-beam.
4. All parts of the chassis including added/welded parts shall be completely coated with waterproof paint.
5. Tires shall be new, 14.5” rim diameter, 14 ply with “G” load range.
6. Wheels and tires shall meet or exceed the axle rating and be rated for continuous speeds of 65 mph or greater.
7. All axles shall be new.
8. All axles shall be brake axles.
9. A valve stem cover shall be present on every tire.
10. The serial number shall be permanently stamped to the front header to comply with 3280.6. In addition, the serial number shall be painted with rust resistance contrasting color paint, 2 inches (2”) tall on the front header.
11. Rims, bolts, nuts, or other related tire-mounting hardware shall be new.
12. Longitudinal brackets shall be installed at 8'-0” and 16'-0" maximum from each end of the home.
13. Spring hangers shall be multi-leaf.
14. All rims shall be the same color.
15. Maximum typical pier spacing along main I-beams @ 8'-0” o.c. Typical pier load = 6,400 lbs.
16. Manufacturer to place permanent indicators (paint or label) on each I-Beam @ 2'-0" from each end, 12'-0" on center max, and at door jambs for location temporary piers for storage.
17. Longitudinal bracket slot to face towards closest end of home.
Frame Specs
· Main I-Beam: 12" x 10.8#
· Front and Rear Headers: 12" x 10.8#
· Crossmember: 13 Ga. C or Z, 1-1/2" x 3" x 1-1/2"x13 Ga.
· Outriggers: 9" Min Depth at I-Beam tapered to 1" , 13 Ga min., C or Z type, with 1-1/2" flange top and bottom.
· Frame Clips: 1" x 1-1/2" x 12 Ga.
Hitch Specs
· See Chassis Details, Details "A"
Welding Specs
1. All welds to be a minimum 1/8" unless otherwise noted. Weld beads can be concave in application as long as the weld size is met.
2. Coupler and Jack shall be welded per manufacturer's installation instructions.
3. I-Beam splice plate shall be 4" wide x height of I-Beam minus 1-1/4" x 13 GA.
Splice plate can be offset +/- 1/4". Weld shall be full width of splice plate.
Splice plate only required on one side of I-Beam.
4. Sister I-Beam shall be welded with 1/8" butt welds 2" long at 24" o.c. top and bottom of I-beam
5. All weld lengths stated or shown are minimum lengths and shall have a tolerance of minus 1/4" (except spring hangers). Weld lengths that are not noted shall be full length.
I-BEAM 12" X 10.8#
DRAWBAR CROSSMEMBER I-BEAM 12" X 10.8# REINFORCEMENT
UNDER FRONT HEADER AND CENTERED BETWEEN FRONT HEADER AND TONGUE
VENTURE 2-5/16" - 60 DEGREE, 10,000LB COUPLER OR EQUIVALENT
JACK - VENTURE TOP MOUNT,
10,000LB GALVANIZED OR EQUIVALENT.
7-3/8" X 4" NOSE PLATE
1" x 1-1/2" X 12GA FRAME CLIP
1/8" x 1-1/2" FILLET WELD TO TOP
FLANGE OF I-BEAM.
9" x 1.5" x 1.5" x 13 Ga
FULL LENGTH OUTRIGGER
CROSSMEMBER
C OR Z 1-1/2" x 3" x 1-1/2"
13 GA. @ 48" O.C.
1-1/2" x 1-1/2" x 13"L x 13 GA. ANGLE
1/8" x 1"L FILLET WELD TO I-BEAM
AND CROSSMEMBER
FRONT AND REAR I-BEAM HEADERS - 12" X 10.8#
1 1/21 1/2
BOTTOM OF FRAME I-BEAM
1/8" X 2" LONG FILLET WELD
3/4 1 1/2 3/4
DIA. 9/16" HOLE
DETAIL - SEE SLOT
A
A
1 1/21 1/2
1 1/2 3/43/4
DETAIL "A-A"
SLOT DETAIL
1 5/8
13/16
DIA. 9/16" HOLE
DIA. 9/16" HOLE
DIA. 9/16" HOLE
F
U
L
L
M
A
X
M
A
X
N
O
W
E
L
D
1/4" FILLET WELD
EACH SIDE
Notes
1. Thickness is 4 gauge.
2. Vendor to assure all spring hangers are 90° to I-Beam.
3. Shoulder bolts to be torqued per axle manufacturer requirements
(Approximately 30 to 50 ft. lbs).
Leaf Spring to move freely in hanger.
I-BEAM FLANGE
LOOKING UP AT SPRING HANGER
SPRING HANGER
SPRING
HANGER
LEAF
SPRING
EQUALIZER
AXLE
U-BOLTS
LEAF
SPRING
SHACKLE LINK
WITH BOLTS
CENTER SPRING
HANGER
FRAME I-BEAM
TITLE:
FEMA Manufactured Housing Units
Federal Emergency Management Agency
1/8" = 1'-0"
6/28/2019
VERSION:DATE:
SCALE:
COMPANY:
14B3-11.2
DRAWING NO.
CHASSIS DETAILS
14' WIDE MHU
(PACKAGED SYSTEM)
DETAIL C: LONGITUDINAL TIE-DOWN BRACKET
DETAIL B: AXLE HANGER
DETAIL A: HITCH ASSEMBLY
DETAIL D: EQUALIZER & SHACKLE LINK FASTENING
Notes
1. Shoulder bolts are to be used at all equalizer and shackle link locations.
2. Shoulder bolts shall be torqued per axle manufacturer requirements.
(Approximately 30 to 50 ft. lbs.)
3. Equalizer and shackle links are to move freely after shoulder bolts have been torqued.
4. Axle U-bolts shall be torqued per axle manufacturer requirements
(Approximately 70 to 95 ft. lbs.)
LONGITUDINAL TIE-DOWN BRACKET (12Ga. MIN.) SHALL HAVE
3150 LB WORKING LOAD CAPACITY.
S
I D
E
A
68'-0"
S
H E
A R
W A
L L
J O
I S
T S
S
H E
A R
W A
L L
J O
I S
T S
D
O U
B L
E
J O
I S
T
D
O U
B L
E
J O
I S
T
D
O U
B L
E
J O
I S
T
M
O V
D
J
I S
T
M
O V
J
I S
T
D
R Y
N
T
L
O C
A T
I O
N
2 - 2"x6"x18" TREATED LUMBER BACKERS FOR MOUNTING SERVICE ENTRANCE JUNCTION BOX.
FASTEN THRU BOTTOM BOARD INTO JOISTS ABOVE WITH 2-#8x3" STAINLESS STEEL OR HOT DIPPED GALVANIZED(GI85) SCREWS EACH END.
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
14B3-12
DRAWING NO.
FLOOR FRAMING LAYOUT
14' WIDE MHU
(PACKAGED SYSTEM)
Floor Framing Notes
1. The floor joists shall be 2 x 8 #2 SPF 16” o.c.
2. Edge rails shall be 2 x 8 #2 SPF.
3. Edge rail splice 4 x 5 x 20 GA metal connector plate on each side, or 2 x 8 x minimum 6" each side of joint centered +/- 1”, to be fastened with 7/16 x 2 ½ x 15 GA staples or .131 x 3” PD nails (8) each side of edge rail, with minimum 80% PVA coverage.
Floor Insulation Notes
1. The insulation shall have a flame spread of 25 or less and a smoke develop of 450 or less.
2. The floor insulation shall be a minimum of R-26 fiberglass blanket insulation. One full batt, one additional full width batt between the I-beams, and one additional 16” wide batt between joist outside of I-beams.
Bottom Board Notes
1. All penetrations sealed per bottom board manufacturer's installation instructions.
2. Bottom board shall be a minimum of twenty (20) mil thickness.
3. Multiple layers of acceptable material per 3280.305(g)(6) may be used.
4. Fasten bottom board to perimeter framing per manufacturer's installation instructions.
Floor joists to rim joist
Multiple joists (to each other)
7/16 x 2-1/2 x 15Ga staple
OR 0.131 x 3" Nail
7/16 x 2-1/2 x 15Ga staple
OR 0.131 x 3" Nail
7 each
5 each
12" o.c.
12" o.c.
DESCRIPTION FASTENER QTY
FASTENING SCHEDULE - FLOOR FRAMING
(80% PVA glue coverage)
S
I D
E
A
TOILET
W/H DRAIN
LAV
A
B
C
D
123456789
123456789
3456789
123456789
55'-1
4" TUB/SHOWER P-TRAP
54'-11
4" TUB/SHOWER
52'-2
4" LAV
58'-4
2" TOILET DRAIN
37'-11" KIT. SINK
37'-7
2" KIT. SINK
21'-8
2" TV WIRE
24'-10" P.BOX
20'-7" W/H
18'-7
4" WASHER
8'-2
2" LAV
18'-3" DRYER DUCT
18'-7
4" DRYER WIRE
20'-9" TPS CLOSET DRAIN Ø1"
15'-5
4" TOILET SUPPLY
14'-11" TOILET DRAIN
8'-10" TUB P-TRAP
9'-5" TUB SUPPLY
8'-3
2" TUB DRAIN
7'-10
4" PHONE & TV WIRE
P
H O
N E
T
V
24'-8" P.BOX
24'-6" P.BOX
57'-11" TOILET SUPPLY
37'-11" K. SINK
37'-7
2" K. SINK
30'-9" RANGE WIRE
W/H SUPPLY
33'-4" DEHUMIDIFIER DRAIN Ø2"
21'-5
2" TV WIRE
51'-1" PHONE WIRE
60'-1" PHONE & TV WIRE
51'-1" TV WIRE
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
Decking to Joists 7/16 x 1-3/4 x 16Ga staple
OR 0.092 x 2" Nail
4" edges / 6" field w/ glue
6" edges / 10" field w/ glue
DESCRIPTION FASTENER APPLICATION
FASTENING SCHEDULE - FLOOR DECKING
14B3-13
DRAWING NO.
FLOOR DECKING LAYOUT
14' WIDE MHU
(PACKAGED SYSTEM)
Floor Decking Notes
1. The floor decking shall be 23/32" Tongue and Grove (T&G) OSB or
APA-rated plywood 24/0 index, laid out as shown on decking plan.
2. Decking shall be Exposure 1 rated.
3. Long edges of the panel shall be T&G installed perpendicular to the floor joists.
4. PVA (polyvinyl acetate) or equal shall be used as adhesive with 80% coverage.
5. Vinyl flooring shall be installed on all interior floors of the home installed per manufacturer's instructions.
P1 x x
B
A C
K E
R
U
P
2X6 UP
S
H E
L F
S
H E
L F
2X6 UP
BED#1 CLO.
VERTICAL WALL BOARD PANEL BREAKS
6/28/2019FEMA Manufactured Housing Units
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.1
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
8. Paint shall be any latex paint. See FEMA spec.
25 1/2
P2
3 1/2
25 1/2
3 1/2
25 1/2
BED#1 CLO.
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.2
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
37 1/2
P3 x x
B
A C
K E
R
U
P x x
B
A C
K E
R
U
P
BACKER
DOWN
2X6
37 1/2
109 1/2
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
I
P
L I C
A B
L E
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
14 3/4
R.A.G. R.A.G.
14 3/8
1x
FILLER
2x BLOCK 18" MIN.
M
I N
NOTCH FOR SPRINKLER SYSTEM PIPE
-SEE APPENDIX A-30 DETAIL "B"
NOTCH FOR SPRINKLER
SYSTEM PIPE
2X6 SPRINKLER HEAD BACKER, SPRINKLER
HEAD BACKER LOCATION MAY VARY BASED
ON SPRINKLER DESIGN.
VERTICAL WALL BOARD PANEL BREAKS
48 48 13 1/2
37 1/2 3
BATHROOM #1
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/4" = 1'-0"
14B3-16.3
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P4 x x
B
A C
K E
R
U
P
32 1/2
LEAVE THIS BAY OPEN FOR TUB VTR CHASE
14" x 14" ACCESS PANEL
(OATLEY 34056 OR EQUIVALENT)
CUT GYPSUM ACCESS PANELS ARE
NOT ACCEPTABLE.
32 1/2
BATH #1
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.4
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P5
2X6 UP2X6 UP
2X6 UP2X6 UP
2X6 UP2X6 UP
S
I N
K
M
E D
I C
I N
E
C
A B
I N
E T
1x
FILLER
2x BLOCK 18" MIN.
M
I N
NOTCH FOR SPRINKLER SYSTEM PIPE
-SEE APPENDIX A-30 DETAIL "B"
Note
This wall not to be paneled on framing jig. To be paneled after floor plumbing installed.
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.5
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
This wall not to be paneled on framing jig. To
37 1/2
P6 x x
B
A C
K E
R
U
P x x
B
A C
K E
R
U
P
51 1/2 42
37 1/2 21
3 1/2
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
2X6 SPRINKLER HEAD BACKER, SPRINKLER
HEAD BACKER LOCATION MAY VARY BASED
ON SPRINKLER DESIGN.
BACKER
UP & DOWN
2X6
4237 1/2
3 1/2
48 21
3 1/2
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/4" = 1'-0"
14B3-16.6
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P7
BCKR
DOWN
2X6
BCKR
DOWN
2X6
DN
G R
R
1x
FILLER
2x BLOCK 18" MIN.
M
I N
NOTCH FOR SPRINKLER SYSTEM PIPE
-SEE APPENDIX A-30 DETAIL "B"
NOTCH FOR SPRINKLER
SYSTEM PIPE
TPS CLOSET
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.7
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P8 x x
B
A C
K E
R
U
P
BCKR
BOTH
2X6
BCKR
DWN
2X6
BCKR
DWN
2X6
H
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
59 1/2
H
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
2X6 SPRINKLER HEAD BACKER, SPRINKLER
HEAD BACKER LOCATION MAY VARY BASED
ON SPRINKLER DESIGN.
BATH #1
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.8
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
ALL 2X6 BACKERS DOWN
P9
60 1/2
H
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
H
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
Nail on washer box size will vary. Manufacturer to verify size from the washer box vendor that will be used.
14"x14" washer p-trap access panel
(Oatley 34056 or equivalent) for p-trap.
6"x9" louvered access panel (Oatley 34247 or equivalent) for recessed autovent
M
A X
BATH #1
28 1/2
VERTICAL WALL BOARD PANEL BREAKS
Standpipe cannot be more than 30" above the p-trap weir.
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.9
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
25 1/2
A C
K E
R
U
P
BCKR
UP
2X6
BCKR
UP
2X6
A C
K E
R
U
P
BCKR
UP
2X6
P10
25 1/2
1x
FILLER
2x BLOCK 18" MIN.
M
I N
NOTCH FOR SPRINKLER SYSTEM PIPE
-SEE APPENDIX A-30 DETAIL "B"
NOTCH FOR SPRINKLER
SYSTEM PIPE
BCKR
UP
2X6
BCKR
UP
2X6
25 1/2 4834
W/H - FURNACE
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
3/8" = 1'-0"
14B3-16.10
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P11
4 107 1/2
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
A C
K E
R
D
O W
N
A C
K E
R
D
O W
N
E
C
B
I N
E T
S
E
A D
C A
B I N
E T
S
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
KITCHEN
48 11 1/2
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
3/8" = 1'-0"
14B3-16.11
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
37 1/2
P12
37 1/2
40 1/2
BACKER
UP
2X6
14 3/414 3/4
R.A.G.
50 3/850 3/8
R.A.G.
37 1/2 40 1/238
BED #3
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
3/8" = 1'-0"
14B3-16.12
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
37 1/2
P13
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
BCKR
UP
2X6
W
L
R
G R
R
P
H O
L D
E R
37 1/2
BACKER
UP
2X6
2X6 SPRINKLER HEAD BACKER, SPRINKLER
HEAD BACKER LOCATION MAY VARY BASED
ON SPRINKLER DESIGN.
37 1/245 7
BATH #2
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
3/8" = 1'-0"
14B3-16.13
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
25 1/2
P14
A C
K E
R
U
P
2X6 UP
2X6 UP
UP
UP
2X6 UPUP
M
D
I C
I N
E
C
A B
I N
E T
S
N
K
25 1/2
H
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
1x
FILLER
2x BLOCK 18" MIN.
M
I N
NOTCH FOR SPRINKLER SYSTEM PIPE
-SEE APPENDIX A-30 DETAIL "B"
NOTCH FOR SPRINKLER
SYSTEM PIPE
25 1/235 1/2
BATH #2
40 1/2
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.14
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P15
2X6 UP
S
H E
L F
25 1/2
T
O W
E L
B
A R
2X6 DN
DN
2X6
S
H E
L F
2X6 UP
25 1/2
BED #3
CLOSET
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.15
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P16 x x
B
A C
K E
R
D
O W
N
LEAVE THIS BAY OPEN FOR TUB VTR CHASE
14" x 14" ACCESS PANEL
(OATLEY 34056 OR EQUIVALENT)
CUT GYPSUM ACCESS PANELS ARE
NOT ACCEPTABLE.
BATH #2
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.16
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
40 1/2
P17 x x
B
A C
K E
R
U
P x x
B
A C
K E
R
U
P
BACKER
UP
2X6
W
R
BACKER
UP
2X6
BACKER
DOWN
2X6
109 1/2
37 1/2
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
O R
I Z
O N
T A
L
P A
N E
L
S
I Z
E
P
L I C
A B
L E
BACKER
UP
2X6
BACKER
UP
2X6
G R
R
BACKER
UP
2X6
P
14 3/4
R.A.G. R.A.G.
14 3/8
NOTCH FOR SPRINKLER
SYSTEM PIPE
(SEE APPENDIX A-30 - DETAIL "B"
2x3x2
1x3x2
NOTCH FOR SPRINKLER
SYSTEM PIPE
2X6 SPRINKLER HEAD BACKER, SPRINKLER
HEAD BACKER LOCATION MAY VARY BASED
ON SPRINKLER DESIGN.
48 48 13 1/2
37 1/2 3
BATH #2
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/4" = 1'-0"
14B3-16.17
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
25 1/2
P18
3 1/2
25 1/2
3 1/2
25 1/2
BED#2 CLO.
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.18
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall Framing Notes
1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.
2. Top plates to be 2 x 3 (unless noted) #2 SPF.
3. Bottom plates to be 1 x 3 (unless noted) #2 SPF.
4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.
6. Wall panel trim (1/2” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.
7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)
P19
A C
K E
R
U
P
2X6 UP
S
H E
L F
2X6 UP
S
H E
L F
BED#2 CLO.
Federal Emergency Management Agency
DATE:
SCALE:
COMPANY: VERSION:
1/2" = 1'-0"
14B3-16.19
DRAWING NO.
INTERIOR WALLS
14' WIDE MHU
(PACKAGED SYSTEM)
Interior Wall…