Questions and ResponsesAHU 6-23-10.doc

DOC document 27 KB Posted

Attached to
BASE NOTICE: RECOVERY- REPAIR, REPLACEMENT OF HEATING VENTILLATION AND AIR CONDITIONING UNITS AT NIST GAITHERSBURG, MD
Solicitation number
SB1341-10-RP-0047
Issued by

About this file

Remaining Questions and Responses

View the file

Other files

File Type Posted
Q R 6-15-10.doc DOC document
AHUQA18June2010pm.doc DOC document
Amendment 7 to SB1341-10-RP-0047.doc DOC document
Attachment A- NIST Bldg 245 ACU 1A Hot Water Coil Schedule.pdf PDF
AHU questions and answers 6-17-10.doc DOC document
Amendment 0005 6-11-10.doc DOC document
AHU q a 6-10-10.doc DOC document
EHXBIT ACU Casing Sizes Per building —
Amendment 0004 6-9-10.doc DOC document
Amendment 0003 6-1-10.doc DOC document
Questions and Responses to SB1341.doc DOC document
Amendment 0002 SB1341-10-RP-0047.doc DOC document
visitor's log.pdf PDF
revised Section K.doc DOC document
2-Table of Contents.doc DOC document
15725 Modular Indoor Central-Station Air-Handling Units.doc DOC document
Bldg 225.zip ZIP file
Bldg 231.zip ZIP file
Fraud Prevention Presentation.pptx PPTX presentation
Bldg 220 Part 2.zip ZIP file
Bldg 245 Part 2.zip ZIP file
Bldg 221 Part 1.zip ZIP file
Bldg 236.zip ZIP file
Bldg 220 Part 1.zip ZIP file
Solicitation Air Handlers 5-3-10.doc DOC document
Specs HVAC 4-26-10.zip ZIP file
Bldg 230.zip ZIP file
Bldg 221 Part 2.zip ZIP file
Bldg 202.zip ZIP file
Bldg 245 Part 1.zip ZIP file
Bldg 224.zip ZIP file
Bldg 223.zip ZIP file
Bldg 235.zip ZIP file
Bldg 226.zip ZIP file
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(AHU Project Questions & Answers) 6/22/2010

Q: 55 - The Type A 1 high x 2 wide in the response contradicts the response provided in Amendment #4 response to question 12 listed above. Please confirm that Type A is 1 coil, (ie 1 high x 1 wide).

There is no schedule for a Hot Water coil in ACU-1A on drawing 245-497.

A: 55- The Type A coil is, 1 high x 1 wide per response to #12 in Amendment # 4.

See attachment A for Hot Water Coil schedule for ACU-1A.

Q: 56- Response #to question 51 ACU-1A: states Cooling coil should be Type C, 1 high x 2 wide, steam coil should be Type A, 1 high x 2 wide and hot water coil should be 2 high x 1 wide.

A: 56- Response to Amendment #6 question #51 should read:

“Cooling coil should be Type C, 1 high x 2 wide, steam coil should be Type C, 1 high x 2 wide and hot water coil should be Type A, 1 high x 1 wide.”

Q: 57- On drawings 104 of 164, 106 of 164 and 107 of 164, the ACU elevation detail views on the above drawings, state that we are to follow notes 4 and 9. Note 9 does not appear on these pages, what is note 9? Also these same pages state in note 1 we are to remove the entire ACU and discard the unit. There is not a note 4 given in any of the details on this page telling us to reinstall a new unit. Are reinstalling a new ACU?

A: 57- Plan view and elevation view should reference notes 1 through 8. Delete reference to note 9. Note 1 does not remove the entire unit. Removes fan and cooling coil section.

Note 4 states: “ Provide new modular type horizontal draw-thru ACU unit with fan and cooling coil with all…..”. There is no note about “reinstalling”.