Salient Characteristics Heating Boiler B575.docx

DOCX document 15 KB Posted

Attached to
REPLACE HEATING BOILER - JBSA Randolph, TX
Solicitation number
F2M3CB5152A001
Issued by

About this file

The document is a Salient Characteristics file specifying detailed technical specifications for a heating boiler. The boiler requires specific performance parameters including 300k BTU input per hour, 270k BTU output per hour, a design pressure of 100 PSI, a minimum relief valve capacity of 270k BTU/HR, manifold gas pressure of 2.8 inches W.C., and electrical requirements of 120 Volts at 60HZ.

This specification is related to a pre-solicitation opportunity (Solicitation Number: F2M3CB5152A001) for the Department of the Air Force Air Education and Training Command, specifically for replacing a boiler at JBSA Randolph. The government is currently conducting market research to identify contractors capable of providing the required items and associated costs in accordance with a draft Statement of Work (SOW). The opportunity is in the pre-solicitation phase, indicating that detailed solicitation documents have not yet been released.

View the file

Other files

File Type Posted
DRAFT Salient Characteristics Heating Boiler B575.pdf PDF
RFI - JBSA RAN Replace Boiler.docx DOCX document
DRAFT SOW - TYMX B575 RAN BOILER.docx DOCX document
DRAFT SOW - TYMX B575 RAN BOILER.pdf PDF
boiler 575 2.JPG JPG image
B575-RAN_Record Drawings _2015 1.pdf PDF
Record drawing - 1953 (3) 575 1.pdf PDF
boiler 575 1.JPG JPG image
boiler 575 3.JPG JPG image
boiler 575 4.JPG JPG image

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics: Characteristics must match the following heating Boiler.

Product must meet the following characteristics of The heating boiler

Product must meet the following specifications:

· BTU input/HR 300k

· BTU Output/HR 270k

· Design pressure 100 PSI

· Minimum relief valve capacity 270k BTU/HR

· Manifold gas pressure 2.8 inches W.C.

· 120 Volts -60HZ