Salient Characteristics Heating Boiler B575.docx
DOCX document 15 KB Posted
- Attached to
- REPLACE HEATING BOILER - JBSA Randolph, TX
- Solicitation number
- F2M3CB5152A001
About this file
The document is a Salient Characteristics file specifying detailed technical specifications for a heating boiler. The boiler requires specific performance parameters including 300k BTU input per hour, 270k BTU output per hour, a design pressure of 100 PSI, a minimum relief valve capacity of 270k BTU/HR, manifold gas pressure of 2.8 inches W.C., and electrical requirements of 120 Volts at 60HZ.
This specification is related to a pre-solicitation opportunity (Solicitation Number: F2M3CB5152A001) for the Department of the Air Force Air Education and Training Command, specifically for replacing a boiler at JBSA Randolph. The government is currently conducting market research to identify contractors capable of providing the required items and associated costs in accordance with a draft Statement of Work (SOW). The opportunity is in the pre-solicitation phase, indicating that detailed solicitation documents have not yet been released.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DRAFT Salient Characteristics Heating Boiler B575.pdf | ||
| RFI - JBSA RAN Replace Boiler.docx | DOCX document | |
| DRAFT SOW - TYMX B575 RAN BOILER.docx | DOCX document | |
| DRAFT SOW - TYMX B575 RAN BOILER.pdf | ||
| B575-RAN_Record Drawings _2015 1.pdf | ||
| Record drawing - 1953 (3) 575 1.pdf | ||
| boiler 575 2.JPG | JPG image | |
| boiler 575 4.JPG | JPG image | |
| boiler 575 1.JPG | JPG image | |
| boiler 575 3.JPG | JPG image |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics: Characteristics must match the following heating Boiler.
Product must meet the following characteristics of The heating boiler
Product must meet the following specifications:
· BTU input/HR 300k
· BTU Output/HR 270k
· Design pressure 100 PSI
· Minimum relief valve capacity 270k BTU/HR
· Manifold gas pressure 2.8 inches W.C.
· 120 Volts -60HZ