DRAFT Salient Characteristics Heating Boiler B575.pdf
PDF 106 KB Posted
- Attached to
- REPLACE HEATING BOILER - JBSA Randolph, TX
- Solicitation number
- F2M3CB5152A001
About this file
This document details the minimum salient characteristics for a replacement boiler system at Joint Base San Antonio (JBSA) Randolph, TX. The specifications include a gas-fired, non-condensing boiler with a preferred Fulton brand or equivalent, requiring 300,000 BTU/hour input and 270,000 BTU/hour output. Technical requirements specify a design pressure of 100 PSI, a relief valve capacity of at least 270,000 BTU/hour, manifold gas pressure of 2.8 inches water column, and electrical requirements of 120 Volts, 60 Hz. These detailed specifications are part of a pre-solicitation market research effort by the Department of the Air Force Air Education and Training Command to identify potential contractors for replacing the existing boiler system in Building 575.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI - JBSA RAN Replace Boiler.docx | DOCX document | |
| DRAFT SOW - TYMX B575 RAN BOILER.docx | DOCX document | |
| DRAFT SOW - TYMX B575 RAN BOILER.pdf | ||
| B575-RAN_Record Drawings _2015 1.pdf | ||
| Record drawing - 1953 (3) 575 1.pdf | ||
| Salient Characteristics Heating Boiler B575.docx | DOCX document | |
| boiler 575 2.JPG | JPG image | |
| boiler 575 4.JPG | JPG image | |
| boiler 575 1.JPG | JPG image | |
| boiler 575 3.JPG | JPG image |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Minimum Salient Characteristics for a Replacement Boiler System:
• Fuel Type: Gas-fired
• Boiler Type: Non-Condensing (or equivalent)
• Brand: Fulton (preferred) or equal
• BTU Input: 300,000 BTU/hour (300 MBH)
• BTU Output: 270,000 BTU/hour (270 MBH)
• Design Pressure: 100 PSI
• Relief Valve Capacity: Minimum 270,000 BTU/hour
• Manifold Gas Pressure: 2.8 inches Water Column (W.C.)
• Electrical Requirements: 120 Volts, 60 Hz