Saginaw Correctional Facility - HVAC Renovations CD Drawings-1.pdf
PDF 5 MB Posted
- Attached to
- 472/22064. CTS; Saginaw CF - HVAC Renovations
- Solicitation number
- RFQ-171-250000000200-3
- Issued by
- Saginaw County, Flint City, Michigan
About this file
This document contains mechanical/electrical engineering drawings for HVAC renovations at the Saginaw Correctional Facility (SRF) in Freeland, MI, issued by the State of Michigan Department of Technology, Management and Budget for the Department of Corrections. The project (File Number 472/22064.CTS, Matrix Project Number 22030.01) involves HVAC system upgrades including the installation of new 24-volt combination fire/smoke DDC damper actuators, controls, control wiring, and associated accessories. The drawings are part of the Construction Document set dated 1/22/2025 and include detailed site maps, mechanical drawing indexes, symbols, notes, and specifications.
The drawings outline extensive technical requirements including HVAC piping symbols, temperature control symbols, general HVAC notes, electrical specifications, and demolition guidelines. Key components include connecting new damper actuators to the existing Silent Knight fire alarm system manufactured by Honeywell, installing new 24-volt stepdown transformers, and providing 5 additional DDC smoke damper actuators as attic stock. The contractor is responsible for all calculations, electrical circuits, and maintaining compliance with NFPA standards. The work must be performed while maintaining normal facility operations, with electrical outages limited to 2 hours unless temporary power is provided.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
9625 PIERCE ROAD,
FREELAND, MI 48623
FILE NUMBER: 472/22064.CTS
MATRIX PROJECT NUMBER: 22030.01MECHANICAL/ELECTRICAL ENGINEER
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FOR DEPARTMENT OF CORRECTIONS
SAGINAW CORRECTIONAL FACILITY (SRF) - HVAC RENOVATIONS
N SITE MAP
MECHANICAL DRAWING INDEX
M-000
TITLE SHEET
DBP
CAT
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
472SRFMAINTPROJ
1/22/2025 CD SET
GENERAL HVAC NOTES
1. LOCATE EXHAUST OUTLETS OF VENTILATION SYSTEMS, AT
LEAST 10 FEET FROM OUTDOOR AIR INTAKES.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION
THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
4. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.
5. FIRE DAMPERS & COMBINATION FIRE/SMOKE DAMPERS SHALL
MATCH RATING OF WALL. UNLESS NOTED OTHERWISE.
6. INTERLOCK FIRE/SMOKE DAMPERS BY ELECTRICAL TRADES.
PROVE OPEN BEFORE AIR HANDLING UNITS FAN(S) START.
7. COORDINATE LOUVER SIZES PRIOR TO CONSTRUCTION AND
ORDERING NEW DAMPERS.
8. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
9. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT
MAY AFFECT THE WORK.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
11. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.
12. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
13. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT
FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED
OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED
SHEET METAL, MIN. 26 GA.
14. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
15. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
16. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE
STATUTES, ORDINANCES, CODES OR REGULATIONS OF
FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING
JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
17. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY
OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,
ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION
BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE
FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING
AND SPECIFICATIONS.
18. DRAWING LAYOUT IS SCHEMATIC. EXACT LOCATION OF
EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, AND ALL OTHER TRADES
PRIOR TO INSTALLATION. ANY CONTRACTOR INSTALLING
WORK WITHOUT PRIOR COORDINATION SHALL RELOCATE HIS
WORK AT HIS EXPENSE TO ALLOW PROPER INSTALLATION OF
ANY AND ALL TRADES WORK.
19. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS
REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.
CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY
LOCAL CODES. POWER SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR.
20. CONTRACTOR TO REPAIR CEILING/WALL/ROOF TO MATCH
EXISTING AS REQUIRED WHERE NEW/DEMOLITION WORK
OCCURRED.
21. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST
CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER
TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.
22. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO
OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED
THROUGHOUT THE PROJECT.
23. CONTRACTOR WILL HAVE 1 ESCORT TO WORK WITH THROUGH
AT THE PROJECT.
24. CONTRACTOR TO PATCH AND PAINT EXISTING WALLS AS
NEEDED TO MATCH EXISTING WHERE DEMOLITION AND/OR
NEW WORK IS COMPLETED.
25. FIELD VERIFY EXISTING SIZE OF ALL EQUIPMENT PRIOR TO
ORDERING NEW EQUIPMENT.
26. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN
ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO
DISABLE THE FIRE ALARM.
27. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL
USE TAMPERPROOF SCREWS.
28. ALL ROOF PENETRATIONS SHALL BE SEALED WATER TIGHT
AND SHALL MAINTAIN ALL EXISTING WARRANTIES.
29. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
INSTALLATION OF ALL 24 VOLT CONTROL WIRING AS REQUIRED
TO CONTROL ALL HVAC EQUIPMENT PER THE SEQUENCE OF
OPERATIONS. REFER TO MECHANICAL SPECIFICATIONS AND
COORDINATE WITH MECHANICAL CONTRACTOR. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR INSTALLING WIRING AND
RACEWAY PER ELECTRICAL SPECIFICATIONS.
30. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING
AND INSTALLING ALL MECHANICAL EQUIPMENT.
31. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL OTHER
HARDWARE REQUIRED FOR WIRING THE HVAC EQUIPMENT
PER THE SEQUENCE OF OPERATIONS.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLS
HVAC PIPING
HVAC DUCTWORK
F/S F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL
OTHER TRADES PRIOR TO DEMOLITION.
2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,
STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE
STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE
DRAWING AND SPECIFICATIONS.
4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.
5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY
KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.
6. PATCH AND REPAIR ALL ROOF AND WALL SURFACES LEFT DAMAGED OR
INCOMPLETE FROM REMOVAL OF EXISTING FIXED ACCESSORIES AND
EQUIPMENT WITH MATERIALS TO MATCH EXISTING, AS ACCEPTABLE TO THE
ARCHITECT.
7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL
ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE
DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE
REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR
RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE
NEW WORK AS SHOWN.
8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE
REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO
FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF
THIS WORK.
9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO
COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND
APPROVAL OF THE LOCAL CODE JURISDICTIONS.
10. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN
APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.
11. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED
IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE
CONTRACTOR.
12. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING
REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE
DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.
GENERAL DEMOLITION NOTES
1. CONTRACTOR TO INSTALL NEW 24-VOLT COMBINATION FIRE/SMOKE DDC DAMPER ACTUATORS (BASED ON BELIMO
FSNF24), CONTROLS, CONTROL WIRING, AND ALL ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. NEW DDC DAMPER ACTUATORS TO BE INSTALLED ON EXISTING FIRE/SMOKE DAMPERS. NEW DDC DAMPER ACTUATORS ARE TO MEET ALL UL REQUIREMENTS FOR THIS APPLICATION AND FAIL CLOSED. NEW DDC COMBINATION FIRE/SMOKE DAMPER ACTUATORS ARE TO BE TIED TO EACH BUILDING'S EXISTING FIRE ALARM SYSTEM AND EXISTING CONTROL SEQUENCE TO REMAIN (FIRE/SMOKE DAMPER ACTUATORS SHALL CLOSE TO THEIR NORMAL POSITION WHEN SIGNALED BY THE FIRE ALARM SYSTEM AFTER ANY FIRE/SMOKE DETECTION OR ALARM DEVICE IS ACTIVATED). CONTRACTOR TO PROVIDE ALL ASSOCIATED ACCESSORIES REQUIRED TO CONNECT TO THE EXISTING FIRE ALARM CONTROL PANEL LOCATED IN EACH CORRESPONDING BUILDING'S MECHANICAL ROOM. NEW 24-VOLT STEPDOWN TRANSFORMERS ARE TO BE INSTALLED NEAR FIRE ALARM CONTROL PANELS IN EACH BUILDING MECHANICAL ROOM TO SERVE NEW CORRESPONDING 24-VOLT COMBINATION FIRE/SMOKE DDC DAMPER ACTUATORS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL ELECTRICAL CIRCUITS REQUIRED TO POWER ALL NEW 24-VOLT STEPDOWN
TRANSFORMERS.
1.1. CONTRACTOR TO PROVIDE (5) ADDITIONAL DDC SMOKE DAMPER ACTUATORS AS ATTIC STOCK.
2. CONTRACTOR TO PERFORM ALL REQUIRED CALCULATIONS FOR THE PROPER OPERATION AND CONNECTION TO THE EXISTING FIRE ALARM CONTROL PANEL. THE FIRE ALARM SHALL BE A DELEGATED DESIGN SYSTEM AND WILL BE
REVIEWED AND SUBMITTED IN ACCORDANCE WITH OTHER SYSTEMS ON THIS PROJECT.
3. COMPLY WITH NFPA 72, NFPA 101, AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION FOR INSTALLATION AND TESTING OF FIRE-ALARM EQUIPMENT. INSTALL ALL ELECTRICAL WIRING TO COMPLY WITH REQUIREMENTS IN NFPA 70
INCLUDING, BUT NOT LIMITED TO, ARTICLE 760, "FIRE ALARM SYSTEMS."
4. NEW 24-VOLT FIRE ALARM WIRING SERVING NEW COMBINATION FIRE/SMOKE DAMPER ACTUATORS IS TO BE SUPPORTED
AND ROUTED SEPARATE FROM OTHER LOW VOLTAGE WIRING.
5. ALL NEW FIRE ALARM COMPONENTS ARE TO MATCH/BE FULLY COMPATIBLE WITH EXISTING FIRE ALARM CONTROL PANEL
MANUFACTURER.
6. EXISTING FIRE ALARM SYSTEM IS A SILENT KNIGHT SYSTEM MANUFACTURED BY HONEYWELL. THE FIRE ALARM SYSTEM IS
TO BE RE-CERTIFIED AFTER THE COMPLETION OF NEW WORK.
COMBINATION FIRE/SMOKE DAMPER ACTUATORSGENERAL ELECTRICAL NOTES
1. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS ARE TO BE
SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL RATING.
2. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE MATERIAL TO MAINTAIN
ORIGINAL RATING.
3. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
4. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO
DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE
BIDDING THE PROJECT.
5. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT
WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
7. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN
CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED
NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH
SURFACE AND THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.
8. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO
MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING
SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
12. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. REFER TO SPECIFICATION 260533 -
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.
13. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
13.1. STRAP DISTANCE: 5 FEET.
13.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
13.3. FITTINGS: COMPRESSION.
13.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
14. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
14.1. STRAP DISTANCE: 3 FEET.
14.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
14.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
14.4. FITTINGS: COMPRESSION.
14.5. BELL BOXES: FS TYPE.
14.6. NO KNOCKOUTS.
14.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
15. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE
CEILINGS IS ACCEPTABLE.
16. CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR
PERPENDICULAR TO THE BUILDING LINES.
17. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.
18. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED
CONDUIT FOLLOWING NOTES 11 AND 12 ABOVE.
19. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.
20. ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2 HOURS. FOR OUTAGES OVER 2
HOURS PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY ELECTRICAL
SERVICE EXCEEDING THAT DURATION.
21. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,
RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.
22. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.
23. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTOR SHALL VERIFY THAT THE
LIGHTS AND CAMERAS AREA WORKING PROPERLY PRIOR TO LEAVING THE SITE.
M-100
DBP
CAT
MECHANICAL/ELECTRICAL
SYMBOLS, NOTES,
ABBREVIATIONS, AND
SCHEDULES
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
472SRFMAINTPROJ
1/22/2025 CD SET
| Sheets and Views |
| M000-2203000-M-000 |
| M100-2203000-M-100 |
| M300-2203000-M-300 |
File details come from the government source that posted it. Updated .