250205-2203001-Saginaw Correctional Facility - HVAC Renovations - Addendum 2 - 1.pdf
PDF 14 MB Posted
- Attached to
- 472/22064. CTS; Saginaw CF - HVAC Renovations
- Solicitation number
- RFQ-171-250000000200-3
- Issued by
- Saginaw County, Flint City, Michigan
About this file
This is Construction Bid Addendum No. 2 issued by the Michigan Department of Technology, Management and Budget's State Facilities Administration Design and Construction Division for HVAC renovations at the Saginaw Correctional Facility (File No. 472/22064.CTS). The addendum extends the bid due date to February 19, 2025 at 2:00pm, with questions due to Matrix Consulting Engineers by February 12, 2025. The project involves miscellaneous HVAC renovations in several buildings, including installation of new 24-volt combination fire/smoke DDC damper actuators, controls, and associated accessories. A mandatory pre-bid meeting was held on January 31, 2025. The contract period is 100 calendar days from notice to proceed to substantial completion (June 18, 2025), with final completion 30 days after.
The project requires a bid security equal to 5% of the base bid and includes a $40,000 allowance for provisionary/contingency scope. Bids must be submitted electronically through SIGMA VSS. The contractor must provide performance and payment bonds, proof of insurance including builder's risk, and is responsible for obtaining all required permits and inspections. Special working conditions apply due to the correctional facility setting, including required security clearance, site-specific training, escort requirements, and restricted work hours (6:00 AM - 6:00 PM Monday-Friday). The contractor must be on site 100% of the time and use Michigan products when possible where price, quality and performance are equal or superior.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DTMB-0414 (Rev 12/17)
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
State Facilities Administration Design and Construction Division
CONSTRUCTION BID ADDENDUM NO. 2
This form identifies an Addendum to Bidding Documents, and incorporates interpretations or clarifications, modifications, acceptance of proposed “or equal” materials, and other information into the Bidding Documents. Addenda will be numbered by the Professional and distributed through www.michigan.gov/SIGMAVSS as an attachment.
TO:
ALL BIDDERS
DATE ISSUED
2/5/2025
PROJECT NAME
Saginaw Correctional Facility – HVAC Renovations
FILE NUMBER
472/22064.CTS
PROFESSIONAL
Matrix Consulting Engineers, Inc.
PROJECT DIRECTOR
Chris Schanbeck
BID OPENING DATE:
2/19/2025
ADDENDUM ITEMS: (attach additional sheets and drawings if required)
1. 1/31/2025 Prebid meeting sign-in sheet (attached).
2. 1/31/2025 Prebid meeting agenda (attached).
3. Project Clarification: Questions are due to Matrix (dpung@matrixceinc.com), Friday, February 12, 2025 at 2:00 pm.
4. Project Clarification: Bid due date is extended to Wednesday, February 19, 2025 at
2:00pm.
5. Clarification: Sheet M-000, M-100, M-301, M-302, M-303, M-304, M-305, M-306, M-307, M-308, M-309, M-310, and M-311 reissued (attached). Added notes for Add Alternate #1 and added notes for the relocation/installation of sensors.
6. Clarification: M-401, M-402, M-403, M-404, M-405, M-406, M-407, M-408, M-409, M-410, and M-411 reissued (attached). Added notes for Add Alternate #1 and added notes for the relocation/installation of sensors.
7. Clarification: M-303.1 and M-403.1 issued (attached). Added notes for the relocation/installation of sensors and schedules for Add Alternate #1.
8. Clarification: Specification Section 230993 – Sequence of Operations for HVAC Controls reissued (attached).
9. Clarification: Bid Summary Form reissued (attached). Updated to include Add Alternate #1 and extend bid due date.
10. Clarification: A lap-top workstation does not need to be included as part of the project.
11. Clarification: Prime contractor is to determine the scope of work cover by each discipline and ensure that all project scope is included in bid.
ACKNOWLEDGMENT: This Addendum must be acknowledged by the Bidder in the space provided in the Bid Summary and Bid Form. Failing to acknowledge Addenda may be cause for the Bid to be rejected. Addenda will become part of the Contract Documents.
PROFESSIONAL: Devon Pung, Matrix Consulting Engineers DATE: 2/5/2025
APPROVED BY: Chris Schanbeck PROJECT DIRECTOR: Chris Schanbeck DATE: 2/5/2025 http://www.michigan.gov/SIGMAVSS
MANDATORY PRE-BID MEETING
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
State Facilities Administration Design and Construction Division
Project: Saginaw Correctional Facility, HVAC Renovations
File Number: 472/22064.CTS
Date & Time: Friday, January 31, 2025, at 10:00am
A. Introductions and Sign-in Sheet
All attendees are to sign-in. Individuals can represent only one firm that may submit a bid.
B. Project Scope: Miscellaneous HVAC Renovations in several buildings as specified in the contract documents.
C. Addendum will be issued to document any questions, issues or changes to the contract documents that arise during bidding. All questions or issues shall be submitted via email including any items discussed in this meeting that are not documented in an addendum. The sign-in sheet will be issued in an addendum.
D. Bid Submissions
1. Execute and include all required forms and documents. Refer to Bidder’s Checklist.
a. Note the allowance, $40,000, to be included in the bid for provisionary or contingency scope as directed in writing from the PSC and Project Director.
b. Bid Security equal to five percent (5%) of the base bid is required.
2. Bids shall be submitted electronically in Adobe PDF format to SIGMA VSS.
a. Maximum file size for uploading attachments is 25 MB.
b. Do not wait until the last minute. Submit early.
c. If you experience issues or have questions regarding your electronic submission, you must work through the SIGMA Help Center for assistance and if necessary, receive a ticket number prior to contacting the DCD.
E. Items to be provided by Contractor after notification of award including but not limited to:
1. Performance and Payment Bonds,
2. Proof of Insurance including Builder’s Risk and
3. Additional documentation requested.
F. Schedule
1. February 5, 2025, 2:00pm, any questions must be submitted to dpung@matrixceinc.com.
2. February 12, 2025, 2:00pm, Bids are due on SIGMA VSS.
3. March 10, 2025, Anticipated Pre-construction Kickoff Meeting and Notice to Proceed to be confirmed after contract is executed.
4. Contract Time specified as 100 calendar days from notice to proceed to substantial completion, June 18, 2025. Final completion anticipated 30 calendar days after substantial completion.
5. Liquidated damages specified at $500 per day after substantial completion.
G. Use Michigan products and recycled and/or environmentally friendly products whenever possible where price, quality and performance are equal to, or superior to non-Michigan products.
H. Permits - The contractor is responsible for obtaining and paying for all permits required by LARA, or any other agency as required. The Contractor is responsible for scheduling all inspections.
RFP 472/22064.CTS PRE-BID MEETING 1/31/2025
I. The Contractor is responsible for managing and supervising the work and must be on site 100% of time.
J. Special Working Conditions – Department of Corrections. Refer to Appendix II for additional information.
1. Security Clearance Request – LEIN Clearance and site-specific training. All employees will be required to attend orientation prior to any onsite activity.
2. Working hours will be confirm but generally understood to be daylight hours between 6:00
AM and 6:00 PM during normal business days (Monday through Friday). Additional weekday hours or work on weekends or State Holidays is NOT allowed unless specific written permission is granted.
3. Facility Escort will be required for each work crew at all times inside the secure perimeter. A single escort will be provided for this work. Scheduling of the work shall be coordinated in advance with escort availability.
4. Additional security requirements: in/out of perimeter, onsite items, sally port access, etc.
5. Site controls & staging
K. PSC to review technical and any additional scope information.
L. Comments – Questions – Walk Through
9625 PIERCE ROAD,
FREELAND, MI 48623
FILE NUMBER: 472/22064.CTS
MATRIX PROJECT NUMBER: 22030.01MECHANICAL/ELECTRICAL ENGINEER
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FOR DEPARTMENT OF CORRECTIONS
SAGINAW CORRECTIONAL FACILITY (SRF) - HVAC RENOVATIONS
N SITE MAP
MECHANICAL DRAWING INDEX
M-000
TITLE SHEET
DBP
CAT
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
472SRFMAINTPROJ
1/22/2025 CD SET
2/5/2025 ADDENDUM 2
GENERAL HVAC NOTES
1. LOCATE EXHAUST OUTLETS OF VENTILATION SYSTEMS, AT
LEAST 10 FEET FROM OUTDOOR AIR INTAKES.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION
THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
4. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.
5. FIRE DAMPERS & COMBINATION FIRE/SMOKE DAMPERS SHALL
MATCH RATING OF WALL. UNLESS NOTED OTHERWISE.
6. INTERLOCK FIRE/SMOKE DAMPERS BY ELECTRICAL TRADES.
PROVE OPEN BEFORE AIR HANDLING UNITS FAN(S) START.
7. COORDINATE LOUVER SIZES PRIOR TO CONSTRUCTION AND
ORDERING NEW DAMPERS.
8. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
9. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT
MAY AFFECT THE WORK.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
11. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.
12. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
13. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT
FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED
OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED
SHEET METAL, MIN. 26 GA.
14. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
15. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
16. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE
STATUTES, ORDINANCES, CODES OR REGULATIONS OF
FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING
JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
17. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY
OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,
ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION
BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE
FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING
AND SPECIFICATIONS.
18. DRAWING LAYOUT IS SCHEMATIC. EXACT LOCATION OF
EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, AND ALL OTHER TRADES
PRIOR TO INSTALLATION. ANY CONTRACTOR INSTALLING
WORK WITHOUT PRIOR COORDINATION SHALL RELOCATE HIS
WORK AT HIS EXPENSE TO ALLOW PROPER INSTALLATION OF
ANY AND ALL TRADES WORK.
19. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS
REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.
CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY
LOCAL CODES. POWER SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR.
20. CONTRACTOR TO REPAIR CEILING/WALL/ROOF TO MATCH
EXISTING AS REQUIRED WHERE NEW/DEMOLITION WORK
OCCURRED.
21. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST
CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER
TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.
22. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO
OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED
THROUGHOUT THE PROJECT.
23. CONTRACTOR WILL HAVE 1 ESCORT TO WORK WITH THROUGH
AT THE PROJECT.
24. CONTRACTOR TO PATCH AND PAINT EXISTING WALLS AS
NEEDED TO MATCH EXISTING WHERE DEMOLITION AND/OR
NEW WORK IS COMPLETED.
25. FIELD VERIFY EXISTING SIZE OF ALL EQUIPMENT PRIOR TO
ORDERING NEW EQUIPMENT.
26. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN
ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO
DISABLE THE FIRE ALARM.
27. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL
USE TAMPERPROOF SCREWS.
28. ALL ROOF PENETRATIONS SHALL BE SEALED WATER TIGHT
AND SHALL MAINTAIN ALL EXISTING WARRANTIES.
29. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
INSTALLATION OF ALL 24 VOLT CONTROL WIRING AS REQUIRED
TO CONTROL ALL HVAC EQUIPMENT PER THE SEQUENCE OF
OPERATIONS. REFER TO MECHANICAL SPECIFICATIONS AND
COORDINATE WITH MECHANICAL CONTRACTOR. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR INSTALLING WIRING AND
RACEWAY PER ELECTRICAL SPECIFICATIONS.
30. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING
AND INSTALLING ALL MECHANICAL EQUIPMENT.
31. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL OTHER
HARDWARE REQUIRED FOR WIRING THE HVAC EQUIPMENT
PER THE SEQUENCE OF OPERATIONS.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLS
HVAC PIPING
HVAC DUCTWORK
F/S
F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL
OTHER TRADES PRIOR TO DEMOLITION.
2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,
STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE
STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE
DRAWING AND SPECIFICATIONS.
4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.
5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY
KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.
6. PATCH AND REPAIR ALL ROOF AND WALL SURFACES LEFT DAMAGED OR
INCOMPLETE FROM REMOVAL OF EXISTING FIXED ACCESSORIES AND
EQUIPMENT WITH MATERIALS TO MATCH EXISTING, AS ACCEPTABLE TO THE
ARCHITECT.
7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL
ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE
DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE
REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR
RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE
NEW WORK AS SHOWN.
8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE
REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO
FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF
THIS WORK.
9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO
COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND
APPROVAL OF THE LOCAL CODE JURISDICTIONS.
10. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN
APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.
11. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED
IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE
CONTRACTOR.
12. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING
REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE
DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.
GENERAL DEMOLITION NOTES
1. CONTRACTOR TO INSTALL NEW 24-VOLT COMBINATION FIRE/SMOKE DDC DAMPER ACTUATORS (BASED ON BELIMO
FSNF24), CONTROLS, CONTROL WIRING, AND ALL ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. NEW DDC DAMPER ACTUATORS TO BE INSTALLED ON EXISTING FIRE/SMOKE DAMPERS. NEW DDC DAMPER ACTUATORS ARE TO MEET ALL UL REQUIREMENTS FOR THIS APPLICATION AND FAIL CLOSED. NEW DDC COMBINATION FIRE/SMOKE DAMPER ACTUATORS ARE TO BE TIED TO EACH BUILDING'S EXISTING FIRE ALARM SYSTEM AND EXISTING CONTROL SEQUENCE TO REMAIN (FIRE/SMOKE DAMPER ACTUATORS SHALL CLOSE TO THEIR NORMAL POSITION WHEN SIGNALED BY THE FIRE ALARM SYSTEM AFTER ANY FIRE/SMOKE DETECTION OR ALARM DEVICE IS ACTIVATED). CONTRACTOR TO PROVIDE ALL ASSOCIATED ACCESSORIES REQUIRED TO CONNECT TO THE EXISTING FIRE ALARM CONTROL PANEL LOCATED IN EACH CORRESPONDING BUILDING'S MECHANICAL ROOM. NEW 24-VOLT STEPDOWN TRANSFORMERS ARE TO BE INSTALLED NEAR FIRE ALARM CONTROL PANELS IN EACH BUILDING MECHANICAL ROOM TO SERVE NEW CORRESPONDING 24-VOLT COMBINATION FIRE/SMOKE DDC DAMPER ACTUATORS. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL ELECTRICAL CIRCUITS REQUIRED TO POWER ALL NEW 24-VOLT STEPDOWN
TRANSFORMERS.
1.1. CONTRACTOR TO PROVIDE (5) ADDITIONAL DDC SMOKE DAMPER ACTUATORS AS ATTIC STOCK.
2. CONTRACTOR TO PERFORM ALL REQUIRED CALCULATIONS FOR THE PROPER OPERATION AND CONNECTION TO THE EXISTING FIRE ALARM CONTROL PANEL. THE FIRE ALARM SHALL BE A DELEGATED DESIGN SYSTEM AND WILL BE
REVIEWED AND SUBMITTED IN ACCORDANCE WITH OTHER SYSTEMS ON THIS PROJECT.
3. COMPLY WITH NFPA 72, NFPA 101, AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION FOR INSTALLATION AND TESTING OF FIRE-ALARM EQUIPMENT. INSTALL ALL ELECTRICAL WIRING TO COMPLY WITH REQUIREMENTS IN NFPA 70
INCLUDING, BUT NOT LIMITED TO, ARTICLE 760, "FIRE ALARM SYSTEMS."
4. NEW 24-VOLT FIRE ALARM WIRING SERVING NEW COMBINATION FIRE/SMOKE DAMPER ACTUATORS IS TO BE SUPPORTED
AND ROUTED SEPARATE FROM OTHER LOW VOLTAGE WIRING.
5. ALL NEW FIRE ALARM COMPONENTS ARE TO MATCH/BE FULLY COMPATIBLE WITH EXISTING FIRE ALARM CONTROL PANEL
MANUFACTURER.
6. EXISTING FIRE ALARM SYSTEM IS A SILENT KNIGHT SYSTEM MANUFACTURED BY HONEYWELL. THE FIRE ALARM SYSTEM IS
TO BE RE-CERTIFIED AFTER THE COMPLETION OF NEW WORK.
COMBINATION FIRE/SMOKE DAMPER ACTUATORSGENERAL ELECTRICAL NOTES
1. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS ARE TO BE
SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL RATING.
2. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE MATERIAL TO MAINTAIN
ORIGINAL RATING.
3. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
4. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO
DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE
BIDDING THE PROJECT.
5. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT
WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
7. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN
CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED
NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH
SURFACE AND THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.
8. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO
MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING
SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
12. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. REFER TO SPECIFICATION 260533 -
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.
13. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
13.1. STRAP DISTANCE: 5 FEET.
13.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
13.3. FITTINGS: COMPRESSION.
13.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
14. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
14.1. STRAP DISTANCE: 3 FEET.
14.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
14.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
14.4. FITTINGS: COMPRESSION.
14.5. BELL BOXES: FS TYPE.
14.6. NO KNOCKOUTS.
14.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
15. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE
CEILINGS IS ACCEPTABLE.
16. CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR
PERPENDICULAR TO THE BUILDING LINES.
17. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.
18. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED
CONDUIT FOLLOWING NOTES 11 AND 12 ABOVE.
19. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.
20. ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2 HOURS. FOR OUTAGES OVER 2
HOURS PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY ELECTRICAL
SERVICE EXCEEDING THAT DURATION.
21. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,
RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.
22. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.
23. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTOR SHALL VERIFY THAT THE
LIGHTS AND CAMERAS AREA WORKING PROPERLY PRIOR TO LEAVING THE SITE.
24. All LOW VOLTAGE WIRING TO BE ROUTED IN ABOVE CEILING SPACE, IN
MECHANICAL/ELECTRICAL SPACES, OR IN EXISTING SOFFITS/CHASE SPACES.
2 2
M-100
DBP
CAT
MECHANICAL/ELECTRICAL
SYMBOLS, NOTES,
ABBREVIATIONS, AND
SCHEDULES
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
472SRFMAINTPROJ
X-RF-1
X-SF-1
M
X-UH-2
X-P-2
X-P-5
X-P-1
X-CHEMICAL POT FEEDER
X-DWH-1
X-7" VTR
X-UH-1
X-IH-1
(LOCATED
ON ROOF)
M
M
X-EH-2
(LOCATED
ON ROOF)M
X-EF-3
X-30x48 RA
X-240x72
LOUVER
X-32x108 EA UP
TO X-EH-1
X-36"
PLENUM
X-36x30
SA DN
X-40x40
SA DN
X-42x42 SA
X-36x50 SA
X-36x18 SA
M
X-44x24RA
X-48x24
RA DN
X-48x48 RA X-44x24 RA
X-AHU-1
UP
X-COND
X-CONCRETE
PAD
X-CONCRETE
PAD
X-P-3
M
M
M
T
T
X-SF-1
X-UH-2
T
X-UH-1
B-100-2
B-100-1
CU-100-1
6'' CA VTR
8'' VTR
CC-100-1
X-AHU-1 & X-RF-1 DDC
CONTROL PANEL
MISC. EQUIPMENT
DDC CONTROL PANEL
6'' CA VTR
8'' VTR
EPO SWITCH
EPO SWITCH
RA DAMPER ACTUATOR
(BELOW)
M
UP
UP
X-EF-4
M-301
T
M
X-LOUVER
(ABOVE CEILING)
DEMOLITION NOTESDEMOLITION NOTES
1 EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
EXISTING SUPPLY FAN AND LOUVER TO REMAIN.
DISCONNECT, REMOVE, AND DEMO DAMPER AND
ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRETY. DISCONNECT, REMOVE, AND SALVAGE
EXISTING DAMPER ACTUATOR, DDC CONTROLS,
CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES TO BE RE-USED ON NEW DAMPER.
EXISTING LOUVER TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
ADD ALTERNATE DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY FAN, DAMPER, FILTER RACK, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING SUPPLY FAN CONTROL WIRING AND
CONTROLS TO REMAIN AND BE RE-USED. SALVAGE EXISTING DAMPER ACTUATOR, CONTROLS,
CONTROL WIRING AND ALL ASSOCIATED CONTROL ACCESSORIES. MODIFY EXISTING OUTDOOR
AIR PLENUM AS REQUIRED FOR DEMOLITION AND NEW INSTALL. EXISTING CONDUIT, WIRE, AND ALL ELECTRICAL ACCESSORIES TO REMAIN. MODIFY EXISTING CONDUIT AND WIRE AS REQUIRED
FOR DEMOLITION AND NEW INSTALL.
M-301
BUILDING 100 SECOND
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 100 SECOND FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
0 1 5 10 20
1 BUILDING 100 MECHANICAL ROOM - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
UP
X-EF-3
X-EF-1
X-EF-14
X-EF-5
X-EF-4
X-EF-6
X-EF-2
X-EF-15
X-EF-8
X-EF-13
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-CUH-14
X-CUH-3
X-CUH-2
X-CUH-18
X-CUH-8
X-CUH-7 X-CUH-4
X-CUH-1
X-CUH-13
X-CUH-11
X-CUH-12
X-UH-6
X-UH-5
X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTR X-FTRX-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTRX-FTRX-FTRX-FTRX-FTRX-FTRX-FTRX-FTRX-FTRX-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTRX-FTR
X-FTR X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-FTR
X-10x6 SA
X-14x6 SA
X-12x8 SA
X-16x6 SAX-10x6 SA
X-18x10 SA
X-10x6 SA
X-20x10 SA
X-16x6 SA
X-16x10 SA
X-12x6 SA
X-20x10 SA X-12x6 SA
X-16x10 SA
X-12x6 SA
X-18x10 SA
X-12x12 SA
X-12x6 SAX-8x6 SA X-16x10 SA
X-8x6 SA
X-14x6 SA
X-12x8 SA
X-8x6 SA
X-8x6 SA
X-10x8 SA
X-10x6 SA X-8x6 SA
X-8x6 SA
X-8x6 SAX-16x10 SA
X-14x10 SA X-8x6 SA
X-8x6 SA
X-12x8 SA X-8x6 SA X-8x6 SA
X-8x8 SA
X-12x6 SA
X-12x6 SA
X-12x6 SA X-8x6 SA
X-8x6 SA
X-18x16 SA
X-18x10 SA
X-10x6 SA
X-18x22 SA
X-18x10 SA
X-18x10 SA
X-26x22 SA
X-18x10 SA
X-45x22 SA
X-34x16 SA
X-18x10 SA
X-18x10 SA
X-30x16
SA
X-22x16 SA X-24x16 SA
X-22x12 SA
X-10x6 SA
X-10x6 SA
X-18x10 SA
X-18x10 SA
X-22x6 SA
X-28x12 SA
X-24x12 SA
X-14x8 SA
X-14x6 SA
X-12x6 SA
X-10x6 SA X-8x6
SA
X-20x6 SA
X-20x12 SA X-16x10 SA
X-8x6 SA
X-16x10 SA
X-12x10 SA
X-10x6 SA
X-14x8 SA
X-14x6 SA
X-8x6 SA
X-10x6 SA X-8x6 SA
X-16x6 SA
X-18x8 SA
X-14x6 SA
X-14x10 SA X-12x10 SA X-12x10 SA
X-34x12 SA
X-18x10 SAX-16x6 SA
X-20x12 SA X-18x12 SA X-16x12 SA X-16x10 SA X-16x8 SA X-16x6 SA
X-16x6 SA X-16x6 SA
X-16x6 SAX-16x6 SAX-16x6 SA
X-8x6
SA (TYP.)
X-8x6 EA
(TYP.)
X-10x10 SA X-8x8 SA X-8x6 SAX-10x8 SA X-8x6 SA
X-10x6 SA X-10x8 SA
X-8x6 EA X-8x8 EA X-10x8 EA X-12x8 EA X-12x10 EA X-12x8 EA
X-10x8 EA X-8x8 EA X-8x6 EA
X-16x12 RA
X-32x12 OPEN
END RA
X-20x18 RA
& SA UP
X-22x12 OPEN
END RA
X-22x6 RA
18x6 OPEN
END RA
X-12x6 RA
X-12x8 RA
X-12x12
OPEN
END RA
X-22x12 OPEN
END RA
X-30x12 OPEN
END RA
X-12X8 OPEN
END RA
X-12X6 OPEN
END RA
X-18X10
OPEN END RA X-34X12 OPEN
END RA
X-12X12
OPEN END RA
X-20x12 RA
X-28x18 RA
X-10x12 RA
X-34x18 RA
X-8x6 RA
X-8x6 RA
X-48X12 OPEN
END RA
X-22x6 RA (TYP)
X-10X10 UP
TO X-EF-7
X-8x6 EA
X-8x6 EA X-14x6 EA
X-12x6 EA
X-8x8 EA
X-8x6 EA
X-8x8
EA
X-8x6 EA
X-6x6 EA
X-8x6 EA
X-8x8 EA
X-SD 360
14" TYP. 2
X-SD 200
8" TYP. 2
X-SD 200
8" ---
X-SD 240
8" ---
X-SD320
14"---
X-SD 240
10" ---
X-SD 80
6" TYP. 2
X-SD 85
6" TYP. 2
X-SD 75
6" ---
X-SD 150
7" ---
X-SD 85
6" TYP. 3
X-SD 100
6" TYP. 2
X-SD 80
6" TYP. 2
X-SD 105
6" ---
X-SD 85
6" ---
X-SD 200
8" TYP. 2
X-SD 330
12" ---
X-SD 215
10" ---
X-SD 165
8" --- X-SD 165
8" ---
X-SD 130
6" ---
X-SD 320
12" ---
X-SD 75
6" TYP. 4 X-SD 75
6" ---
X-SD 170
8" ---
X-SD 65
6" ---
X-SD 115
6" TYP. 3
X-SD 145
10" ---
X-SD 310
10" ---
X-SD 245
10" ---
X-SD 50
6" ---
X-SD 50
6" ---
X-SD 140
6" ---
X-SD 230
10" ---
X-SD 285
--- TYP. 4 X-SD 260
--- TYP. 3
X-SD 50
--- TYP. 18
X-EG 50
--- TYP. 18
X-EG 50
--- TYP. 4
X-EG 75
--- TYP. 2X-EG 235
X-EG 75
X-EG 120
--- TYP. 2
X-EG 75
--- TYP. 2X-EG 75
--- TYP. 2
X-EG 75
X-EG 500
X-12X8 UP
TO EF-10
X-SD 200
8" ---
X-SD 180
8" ---
X-45x22
SA UP
X-SD 840
15" TYP. 4
X-SD 840
15" TYP. 6
X-EG 220
X-EG 220
X-EG 410
X-RG 180
--- ---X-RG 215
X-RG 290
X-RG 180
--- TYP. 2
X-RG 215
X-RG 220
X-EG 75
X-RG 130
X-RG 235
X-RG 150
--- TYP. 2
X-RG 85
X-RG 85
--- TYP. 2
X-RG 260
X-RG 90
X-RG 145
X-RG 180
X-RG 200
24X24 UP
TO X-EF-9
X-RG 290
--- --- X-RG 150
X-RG 115
X-RG 650
X-RG 205
X-RG 120
X-RG 290
X-RG 65
--- TYP. 2
X-RG 190
X-RG 1140
X-RG 780
X-8x6 SA
X-EG 50
--- TYP. 2 X-EG 50
--- TYP. 2
X-SD 50
--- TYP. 2
X-SD 50
--- TYP. 2
X-26x26
RA UP
X-FTRX-EF-8
X-CUH-5X-CUH-6
X-EF-16
F/S F/S
F/S
F/S F/S F/S
F/S
F/S
F/S F/SF/SF/SF/S
F/S
F/S
F/S F/S
T
T
T
T
T
T
X-AHU-2
X-AHU-4
AC-200-2
T
AC-200-1
T
AC-200-3
T
S
S
S
S
X-AHU-3
S
X-AHU-1
(ZONE 1)
S
X-AHU-1
(ZONE 2)
X-AHU-1
(ZONE 3)
X-AHU-1
(ZONE 5)
X-AHU-1 (ZONE 7)
S
S
SS
X-AHU-1
(ZONE 4)
S
S
S
S
S
S
S
S S
S
X-AHU-1
(ZONE 6)
X-AHU-1
(ZONE 8)
S
S
S
S
S
S
S
S
MANUAL SMOKE PURGE
KEYED SWITCH
DP11
1 1 1
DEMOLITION NOTES
1 DISCONNECT, REMOVE, AND DEMO EXISTING
PNEUMATIC ACTUATOR, PNEUMATIC TUBING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES
IN THE LOCATIONS SHOWN. EXISTING
COMBINATION FIRE AND SMOKE DAMPER TO
REMAIN.
EXISTING FIN TUBE, CONTROL VALVE, AND ALL
ASSOCIATED ACCESSORIES TO REMAIN.
DISCONNECT, REMOVE, AND DEMO EXISTING
CONTROL WIRING TO THE EXTENTS SHOWN.
CONNECT FIN TUBE AND CONTROL VALVE TO
NEW SENSOR SHOWN ON NEW DRAWING.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
THERMOSTAT, CONTROL WIRING, CONTROLS,
AND ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRELY. RE-INSTALL SALVAGED THERMOSTAT
IN THE LOCATION SHOW ON THE NEW DRAWINGS.
CONTRACTOR TO PATCH, PRIME, AND PAINT
WALL LOCATION AS REQUIRED TO MATCH
EXISTING WHERE THERMOSTAT IS REMOVED.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-302
BUILDING 200 FIRST FLOOR
PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 200 FIRST FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
0 1 5 10 20
X-SF-5
X-EF-12X-12x8 EA X-12x8
EA DN
X-UH-1
X-UH-4
X-EF-7
M
X-EH-5
(LOCATED
ON ROOF)
X-SF-411 X-SF-3 X-SF-2 X-SF-1X-XT-1
X-P-1
X-P-2
X-P-3
X-P-4
X-EF-11
X-16x8 EA
X-16x8
EA DN
X-UH-3
X-UH-2
X-8" VTRX-8" VTR
X-DWH-2 X-DWH-1
X-12x8 EA X-12x8
EA DN
X-EF-10
X-EF-9
M
X-EH-4
(LOCATED
ON ROOF)
X-DAC-1
M
X-708x152 OA
X-56" PLENUM
X-AHU-4
X-RF-3
EA UP
TO X-EH-3
X-20x18
RA DN
X-20x18
SA DN
X-20x18 RA
X-20x18 SA
X-AHU-3
X-30x30
SA DN
X-30x30 SA
M
X-AHU-2
EA UP
TO X-EH-2
X-46x34 RA
X-RF-2
X-50x38 RA
X-32x50
RA
X-32x50 RA
X-46x34
SA DN
X-30x16 SA
X-30x16 SAX-30x16 SA X-30x16 SAX-30x14 SA
X-46x34 SA
X-42x34 SA
X-46x34 SA
X-24x20
SA DN
X-24x20
SA DN
X-42x24 SAX-40x20 SA
X-24x20
SA DN
X-24x20
SA DN
X-20x20 SA
X-20x20
SA DN
X-RF-1
X-26x26 RA X-26x26 RA
X-26x26 RA
X-AHU-1
M
EA UP
TO X-EH-1
X-180x152 OA
X-56" PLENUM
X-26x26 RA X-14x22
SA DN,
ZONE 8
X-6x22 SA DN, ZONE 7
X-16x18
SA DN,
ZONE 1
X-8x18 SA DN, ZONE 5
X-8x22 SA DN, ZONE 2
X-8x22 SA DN, ZONE 4
X-6x22 SA DN, ZONE 3
X-8x22 SA DN, ZONE 6
X-680x56 LOUVER
X-LOUVER X-LOUVER
M
M
X-WATER
SOFTENER
X-8" VTRX-8" VTR
X-DWH-4 X-DWH-3
X-IT RACK
X-CONCRETE PAD
X-CONCRETE PAD
X-COND
X-CONDENSER RAIL
X-CONDENSER RAIL
M
M
M
X-P-6
X-P-6
X-LOUVER
M
M
M
1 1
MMM
B-200-1
M
M
M
M
M
M
T
X-SF-5 X-UH-4
T
T
X-UH-3
T X-SF-4
T
X-UH-2
T
X-SF-3
T
X-UH-1
CU-200-1
CU-200-1 CU-200-2
6" VTR
(TYP. 4)
4" CA VTR
(TYP. 4)
X-AHU-1 & X-RF-1
DDC CONTROL
PANEL
X-AHU-2 & X-RF-2
DDC CONTROL
PANEL
X-AHU-3 DDC
CONTROL PANEL
X-AHU-4 & X-RF-3 DDC
CONTROL PANEL
CC-200-1
M
EPO SWITCH
EPO SWITCH
M
M
M
MULTIZONE DAMPER
ACTUATOR(S), 8 ACTUATORS
M
M
MISC. EQUIPMENT
DDC CONTROL
PANEL
CU-200-3
4" CONCRETE
PAD (TYP.)
B-200-2
B-200-3 B-200-4
M 1 1
M
1 1 1 1
M
M
1 1
1 1
DEMOLITION NOTES
EXISTING SUPPLY FAN AND LOUVER TO REMAIN.
DISCONNECT, REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING DAMPER
ACTUATOR, DDC CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO BE RE-USED ON NEW
DAMPER.
EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL ASSOCIATED
ACCESSORIES IN THEIR ENTIRETY. DISCONNECT,
REMOVE, AND SALVAGE EXISTING DAMPER ACTUATOR,
DDC CONTROLS, CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES TO BE RE-USED ON NEW DAMPER.
DISCONNECT, REMOVE, AND SALVAGE EXISTING FIN TUBE
LOOP WATER TEMPERATURE SENSOR, CONTROLS,
CONTROL WIRING, AND ALL ASSOCIATED ACCESSORIES
TO BE RELOCATED IN LOCATION SHOWN ON NEW
DRAWING. MODIFY EXISTING PIPING AS REQUIRED TO
SALVAGE AND RELOCATE SENSOR.
ADD ALTERNATE DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY FAN, DAMPER, FILTER RACK, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING SUPPLY FAN CONTROL WIRING AND
CONTROLS TO REMAIN AND BE RE-USED. SALVAGE EXISTING DAMPER ACTUATOR, CONTROLS,
CONTROL WIRING AND ALL ASSOCIATED CONTROL ACCESSORIES. MODIFY EXISTING OUTDOOR
AIR PLENUM AS REQUIRED FOR DEMOLITION AND NEW INSTALL. EXISTING CONDUIT, WIRE, AND
ALL ELECTRICAL ACCESSORIES TO REMAIN. MODIFY EXISTING CONDUIT AND WIRE AS
REQUIRED FOR DEMOLITION AND NEW INSTALL.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-303
BUILDING 200 SECOND
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 200 SECOND FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
X-12x6
SA
X-SD 350
12"ø ---
X-22x18 SA X-24x18 SA
X-14x6
SA
X-RG ---
X-28x18 RA
X-FTR
X-RG 4600
X-VAV-301-29
T
DEMOLITION NOTES
1 EXISTING FIN TUBE, CONTROL VALVE, AND ALL
ASSOCIATED ACCESSORIES TO REMAIN.
DISCONNECT, REMOVE, AND DEMO EXISTING
CONTROL WIRING TO THE EXTENTS SHOWN.
CONNECT FIN TUBE AND CONTROL VALVE TO
NEW SENSOR SHOWN ON NEW DRAWING.
M-303.1
BUILDING 300 FIRST FLOOR
PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 300 FIRST FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
X-48x48 LOUVERX-UH-1
X-SF-2
X-30x48 LOUVER X-72x48 LOUVER
X-SF-1
M
X-IH-6
(LOCATED
ON ROOF)
X-EH-2
(LOCATED
ON ROOF)
M
M
M
X-RF-4
X-24x24 RA
X-33" RA
X-33"
RA
X-24x24 RA
X-26" RA
X-24x24 SA
X-AHU-4
X-24x24 SA
X-30x20 SA
X-26" SA
X-AHU-3
M
M X-96x40
RA
X-42x24 SA UP
TO X-IH-4
X-96x54 SA UP
TO X-IH-3
M
X-44x36
RA
M
X-44x40 EA
X-194x48 LOUVER
X-44x40
RA
X-RF-3
X-42x42 RA DN
X-42" RA
X-44x30
RA DN
M
X-EH-1
(LOCATED
ON ROOF)
X-AHU-5X-AHU-2
M
X-36x20 SA UP
TO X-IH-5
X-22x18
SA DN
X-22x18
RA DN
X-36x20 SA UP
TO X-IH-2
M
M
X-RF-2
X-22x18
SA DN
X-22x18 SA
X-22x18 RA
X-22x18
RA
X-30x48 LOUVER
M
X-22x18
SA DN
X-22x18
SA
X-22x18 EA
X-P-11X-P-10
X-7" VTR
X-DWH-2
X-7" VTR
X-DWH-1
X-UH-2
X-AHU-1
X-30x20 RA
X-26" SA
X-26" RA
X-24X24 RA
X-RF-1
X-30x48 LOUVER
X-33" RA
X-36x30 SA UP
TO X-IH-1
M
M
X-CHEMICAL
POT FEEDER
X-IT RACK X-CONCRETE
PAD
X-CONDENSOR RAIL X-CONDENSOR RAIL
M
X-P-1 X-P-2
M
M
M
M
M
M
M M
X-IH-6
(LOCATED
ON ROOF)
CU-300-1
T
X-SF-2
T
X-UH-2
T
X-SF-1
T
X-UH-1
T
X-SF-2
T
X-UH-2
T
X-SF-1
T
X-UH-1
X-SF-2
X-UH-2 X-SF-1
X-UH-1
6" VTR
(TYP. 4)
4" CA VTR
(TYP. 4)
X-AHU-1 & X-RF-1
CONTROL PANEL
X-AHU-2 & X-RF-2
CONTROL PANEL
X-AHU-5
CONTROL PANEL
X-AHU-3 & X-RF-3
CONTROL PANEL
MISC. EQUIPMENT
CONTROL PANEL
X-AHU-4 & X-RF-4
CONTROL PANEL
CC-300-1
CONCRETE
PAD
EPO SWITCH
EPO SWITCH
M
B-300-1
B-300-2
B-300-3
B-300-4
1 1
DEMOLITION NOTES
1 EXISTING SUPPLY FAN AND LOUVER TO REMAIN.
DISCONNECT, REMOVE, AND DEMO DAMPER AND
ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRETY. DISCONNECT, REMOVE, AND SALVAGE
EXISTING DAMPER ACTUATOR, DDC CONTROLS,
CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES TO BE RE-USED ON NEW DAMPER.
EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
FIN TUBE LOOP WATER TEMPERATURE SENSOR,
CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO BE RELOCATED IN
LOCATION SHOWN ON NEW DRAWING. MODIFY
EXISTING PIPING AS REQUIRED TO SALVAGE AND
RELOCATE SENSOR.
ADD ALTERNATE DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY FAN, DAMPER, FILTER RACK, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING SUPPLY FAN CONTROL WIRING AND
CONTROLS TO REMAIN AND BE RE-USED. SALVAGE EXISTING DAMPER ACTUATOR, CONTROLS,
CONTROL WIRING AND ALL ASSOCIATED CONTROL ACCESSORIES. MODIFY EXISTING
OUTDOOR AIR PLENUM AS REQUIRED FOR DEMOLITION AND NEW INSTALL. EXISTING CONDUIT,
WIRE, AND ALL ELECTRICAL ACCESSORIES TO REMAIN. MODIFY EXISTING CONDUIT AND WIRE
AS REQUIRED FOR DEMOLITION AND NEW INSTALL.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-304
BUILDING 300 SECOND
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 300 SECOND FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
UP
UP
M-305
X-LOUVER
X-UH-1 X-EH-1
X-SF-1
T T
M
X-IT RACK
M
X-40x16 3
F/S
X-24x24 LOUVER
X-SF-2
X-8" VTR
X-DWH-1
X-8" VTR
X-DWH-2
X-UH-2
X-P-1X-P-2
X-52x32 LOUVER X-78x48 LOUVER
X-AHU-1
M
X-66x14 EA
UP TO X-EH-3
M
X-EH-2
X-RF-1
X-28x14 RA
M
X-24x24 SA, ZONE 2
X-11x10 SA, ZONE 1
X-12x8 SA, ZONE 3
X-12x6 SA, ZONE 4 X-18x12 SA, ZONE 5
X-20x12 SA, ZONE 8
X-12x10 SA, ZONE 7
X-16x8 SA, ZONE 6
X-CONCRETE PAD
M
M
X-P-4 X-P-9
M
T
T
X-UH-2
T
X-UH-2
X-SF-2 & X-EH-2
B-400-1
B-400-2
4'' CA VTR
(TYP.)
6'' VTR
(TYP.)
MISC. EQUIPMENT DDC
CONTROL PANEL
AHU-1 DDC CONTROL
PANEL
EPO SWITCH MULTIZONE DAMPER
ACTUATOR (8), 8
ACTUATORS
RELIEF & RA DAMPER
ACTUATOR (BELOW)
2 DEMOLITION NOTESDEMOLITION NOTES
1 EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
EXISTING SUPPLY FAN AND LOUVER TO REMAIN.
DISCONNECT, REMOVE, AND DEMO DAMPER AND
ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRETY. DISCONNECT, REMOVE, AND SALVAGE
EXISTING DAMPER ACTUATOR, DDC CONTROLS,
CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES TO BE RE-USED ON NEW DAMPER.
DISCONNECT, REMOVE, AND DEMO EXISTING
PNEUMATIC ACTUATOR, PNEUMATIC TUBING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES
IN THE LOCATIONS SHOWN. EXISTING
COMBINATION FIRE AND SMOKE DAMPER TO
REMAIN.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
FIN TUBE LOOP WATER TEMPERATURE SENSOR,
CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO BE RELOCATED IN
LOCATION SHOWN ON NEW DRAWING. MODIFY
EXISTING PIPING AS REQUIRED TO SALVAGE AND
RELOCATE SENSOR.
ADD ALTERNATE DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY FAN, DAMPER, FILTER RACK, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING SUPPLY FAN CONTROL WIRING AND
CONTROLS TO REMAIN AND BE RE-USED. SALVAGE EXISTING DAMPER ACTUATOR, CONTROLS,
CONTROL WIRING AND ALL ASSOCIATED CONTROL ACCESSORIES. MODIFY EXISTING OUTDOOR
AIR PLENUM AS REQUIRED FOR DEMOLITION AND NEW INSTALL. EXISTING CONDUIT, WIRE, AND ALL ELECTRICAL ACCESSORIES TO REMAIN. MODIFY EXISTING CONDUIT AND WIRE AS REQUIRED
FOR DEMOLITION AND NEW INSTALL.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-305
BUILDING 400 UPPER LEVEL
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 400 UPPER LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
0 1 5 10 20
1 BUILDING 400 MECHANICAL ROOM - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
UP
UPUP
UP
M-306
M
X-LOUVER
X-SF-1
X-UH-1
X-EH-1
M
X-IT RACK
T T
X-TG 550
--- TYP. 2
X-TG 440
--- TYP. 2
X-TG 350
--- TYP. 2
X-22x10 SA X-22x8 SA X-18x10 SAX-22x10 SA3 3 3 F/S F/S F/S F/S
X-UH-2
X-DWH-1
X-8" VTR
X-DWH-2
X-8" VTR
X-78x48
LOUVER
M
X-24x24
LOUVER
X-SF-2
X-AHU-1
M X-42x18 SA
UPX-EH-2
X-P-1 X-P-2
M
X-18x10 SA, ZONE 1
X-10x8 SA, ZONE 2
X-10x10 SA, ZONE 4
X-CONCRETE
PAD
M
X-10x8 SA, ZONE 3
X-P-4
TX-UH-1
T
X-SF-2 & X-EH-2
B-500-2 B-500-1
MISC. EQUIPMENT DDC
CONTROL PANEL
X-AHU-1 DDC CONTROL
PANEL
4'' CA VTR
(TYP.)
6'' VTR (TYP.)
EPO SWITCH
MULTIZONE DAMPER
ACTUATOR(S), 4 ACTUATORS
1 1
DEMOLITION NOTESDEMOLITION NOTES
1 EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
EXISTING SUPPLY FAN AND LOUVER TO REMAIN.
DISCONNECT, REMOVE, AND DEMO DAMPER AND
ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRETY. DISCONNECT, REMOVE, AND SALVAGE
EXISTING DAMPER ACTUATOR, DDC CONTROLS,
CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES TO BE RE-USED ON NEW DAMPER.
DISCONNECT, REMOVE, AND DEMO EXISTING
PNEUMATIC ACTUATOR, PNEUMATIC TUBING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES
IN THE LOCATIONS SHOWN. EXISTING
COMBINATION FIRE AND SMOKE DAMPER TO
REMAIN.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
FIN TUBE LOOP WATER TEMPERATURE SENSOR,
CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO BE RELOCATED IN
LOCATION SHOWN ON NEW DRAWING. MODIFY
EXISTING PIPING AS REQUIRED TO SALVAGE AND
RELOCATE SENSOR.
ADD ALTERNATE DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY FAN, DAMPER, FILTER RACK, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING SUPPLY FAN CONTROL WIRING AND
CONTROLS TO REMAIN AND BE RE-USED. SALVAGE EXISTING DAMPER ACTUATOR, CONTROLS,
CONTROL WIRING AND ALL ASSOCIATED CONTROL ACCESSORIES. MODIFY EXISTING OUTDOOR
AIR PLENUM AS REQUIRED FOR DEMOLITION AND NEW INSTALL. EXISTING CONDUIT, WIRE, AND ALL ELECTRICAL ACCESSORIES TO REMAIN. MODIFY EXISTING CONDUIT AND WIRE AS REQUIRED
FOR DEMOLITION AND NEW INSTALL.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-306
BUILDING 500 UPPER LEVEL
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 500 UPPER LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
0 1 5 10 201 BUILDING 500 MECHANICAL ROOM - MECHANICAL DEMOLITION
UP UP
M-307
X-10x18 SA
X-10x18 SA
X-24x18 SA
X-30x18
RA
X-26x20
RA
X-10x16 SA
X-10x24 SA
X-26x20 RA
X-24x18 SA
X-30x18 RA
F/S
F/S
F/S
F/S
F/S
F/S
F/S
X-SD 300
X-SD 50
4"ø ---
X-12x6 SA
X-6x4 SA2 F/S
X-12" VTR
X-DWH-1
X-DWH-2
X-12" VTR
X-24x24 LOUVER
X-EF-1
X-UH-2
X-24x24 LOUVER
X-EF-2
X-30"x18 SA
UP TO X-IH-7
M
X-48x48 LOUVER
X-48x48 LOUVER
X-48x48 LOUVER
X-UH-1
X-RF-1
X-26x20 RA
M
X-30x24 RA
X-RF-2
X-30x18 RA
M
X-30x24 RA
X-RF-3
X-26x20 RA MX-30x24 RA
X-20" VTR
X-30x24 SA
X-AHU-1
M
M X-48x48 SA UP
TO X-IH-1
X-30x24 SA
X-AHU-2
M
M X-48x48 SA UP
TO X-IH-2
X-24x18 SA
X-24x18 SA
X-30x18 DUCT
UP (CAPPED)
TO X-IH-4
M
X-30x24 RAX-AHU-3
M
X-36x48 SA UP
TO X-IH-3
X-10x16 SA, ZONE 5
X-10x24 SA, ZONE 4
X-10x24 SA, ZONE 1
X-10x14 SA, ZONE 2X-10x18 SA, ZONE 3
X-20x12 SA
M
X-24x30 SA UP
TO X-IH-5
M
X-12x30 CA DN
X-P-1
X-P-2 X-CONCRETE
PAD
X-IT RACK
M
X-24x18 SA
X-24x18 SA
X-HC-4
X-HC-3
X-HC-2
X-HC-1
X-P-9
MISC. EQUIPMENT DDC
CONTROL PANEL
X-AHU-2 DDC CONTROL
PANEL
T T
X-UH-2 X-EF-1
B-600-1
B-600-2
4'' CA VTR (TYP.)
6'' VTR (TYP.)
X-AHU-3 DDC CONTROL PANEL
X-AHU-1 DDC CONTROL
PANEL
T
T
MULTIZONE DAMPER
ACTUATOR(S), 5 ACTUATORS
EPO SWITCH
DEMOLITION NOTESDEMOLITION NOTES
1 EXISTING INTAKE HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
DISCONNECT, REMOVE, AND DEMO EXISTING
DAMPER ACTUATOR, CONTROL WIRING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES IN
THE LOCATIONS SHOWN. EXISTING COMBINATION
FIRE AND SMOKE DAMPER TO REMAIN.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
FIN TUBE LOOP WATER TEMPERATURE SENSOR,
CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO BE RELOCATED IN
LOCATION SHOWN ON NEW DRAWING. MODIFY
EXISTING PIPING AS REQUIRED TO SALVAGE AND
RELOCATE SENSOR.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-307
BUILDING 600 UPPER LEVEL
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 600 UPPER LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
0 1 5 10 20
1 BUILDING 600 MECHANICAL ROOM - MECHANICAL DEMOLITION
UPUP
UP
UP
UP
M-308
X-EH-1
X-UH-1 M
X-LOUVER
X-SF-1
X-IT RACK
M
T T
X-TG 800
--- TYP. 2
X-TG 500
--- TYP. 2
X-22x12 RA X-22x12 RA X-22x8 RA
X-TG 800
--- TYP. 2
3 3 3 3
F/S F/S F/S F/S
X-16x12 SA
2 2
X-CONCRETE
PAD
X-20x48
LOUVERM
X-20x24 SA
DN TO 6" AFF
M
X-AHU-1
X-EH-2
X-42x42
LOUVER
M X-12x42
LOUVER
X-14x18 SA, ZONE 4
X-12x8 SA, ZONE 2
X-16x12 SA, ZONE 1
X-UH-2
X-DWH-1
X-DWH-2
X-8" VTR
X-24x24
LOUVER
X-SF-2
X-P-2 X-P-1
M
X-8" VTR
X-14x18 SA, ZONE 3
X-P-4
1T
X-UH-2
T
X-SF-2 & X-EH-2
B-700-1 B-700-2
6'' VTR
4'' CA VTR 6'' VTR
4'' CA VTR
MISC. EQUIPMENT DDC
CONTROL PANEL
X-AHU-1 DDC CONTROL
PANEL
MULTIZONE DAMPER
ACTUATOR(S), 4 ACTUATORS
EPO SWITCH
M2
2 1
DEMOLITION NOTESDEMOLITION NOTES
1 EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
DAMPER ACTUATOR, DDC CONTROLS, CONTROL
WIRING, AND ALL ASSOCIATED ACCESSORIES TO
BE RE-USED ON NEW DAMPER.
EXISTING SUPPLY FAN AND LOUVER TO REMAIN.
DISCONNECT, REMOVE, AND DEMO DAMPER AND
ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRETY. DISCONNECT, REMOVE, AND SALVAGE
EXISTING DAMPER ACTUATOR, DDC CONTROLS,
CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES TO BE RE-USED ON NEW DAMPER.
DISCONNECT, REMOVE, AND DEMO EXISTING
PNEUMATIC ACTUATOR, PNEUMATIC TUBING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES
IN THE LOCATIONS SHOWN. EXISTING
COMBINATION FIRE AND SMOKE DAMPER TO
REMAIN.
DISCONNECT, REMOVE, AND SALVAGE EXISTING
FIN TUBE LOOP WATER TEMPERATURE SENSOR,
CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO BE RELOCATED IN
LOCATION SHOWN ON NEW DRAWING. MODIFY
EXISTING PIPING AS REQUIRED TO SALVAGE AND
RELOCATE SENSOR.
ADD ALTERNATE DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY FAN, DAMPER, FILTER RACK, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING SUPPLY FAN CONTROL WIRING AND
CONTROLS TO REMAIN AND BE RE-USED. SALVAGE EXISTING DAMPER ACTUATOR, CONTROLS,
CONTROL WIRING AND ALL ASSOCIATED CONTROL ACCESSORIES. MODIFY EXISTING OUTDOOR
AIR PLENUM AS REQUIRED FOR DEMOLITION AND NEW INSTALL. EXISTING CONDUIT, WIRE, AND ALL ELECTRICAL ACCESSORIES TO REMAIN. MODIFY EXISTING CONDUIT AND WIRE AS REQUIRED
FOR DEMOLITION AND NEW INSTALL.
22030.01
472/22064.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P
L A
C H
R
A
D
IR
E C
T O
R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
KEY PLAN
SCALE: NTS
N
472SRFMAINTPROJ
1/22/2025 CD SET
M-308
BUILDING 700 UPPER LEVEL
FLOOR PLAN - MECHANICAL
DEMOLITION
DBP
CAT
N BUILDING 700 UPPER LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/8" = 1'-0"
0 1 5 10 20
1 BUILDING 700 MECHANICAL ROOM - MECHANICAL DEMOLITION
UP
UP
UP
M-309
X-EH-1
X-UH-1 M
X-LOUVER
X-SF-1
X-IT RACK
M
T T
X-TG 800
--- TYP. 2
X-TG 500
--- TYP. 2
X-22x12 RA X-22x12 RA X-22x8 RA
X-TG 800
--- TYP. 2
3 3 3 3
F/S F/S F/S F/S
X-16x12 SA
2 2
X-CONCRETE
PAD
X-20x48
LOUVERM
X-20x24 SA
DN TO 6" AFF
M
X-AHU-1
X-EH-2
X-42x42
LOUVER
M X-12x42
LOUVER
X-14x18 SA, ZONE 4
X-12x8 SA, ZONE 2
X-16x12 SA, ZONE 1
X-UH-2
X-DWH-1
X-DWH-2
X-8" VTR
X-24x24
LOUVER
X-SF-2
X-P-2 X-P-1
M
X-8" VTR
X-14x18 SA, ZONE 3
X-P-4
1T
X-UH-2
T
X-SF-2 & X-EH-2
B-700-1 B-700-2
6'' VTR
4'' CA VTR 6'' VTR
4'' CA VTR
MISC. EQUIPMENT DDC
CONTROL PANEL
X-AHU-1 DDC CONTROL
PANEL
MULTIZONE DAMPER
ACTUATOR(S), 4 ACTUATORS
EPO SWITCH
M2
DEMOLITION NOTESDEMOLITION NOTES
1 EXISTING RELIEF HOOD TO REMAIN. DISCONNECT,
REMOVE, AND DEMO DAMPER AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
DISCONNECT, REMOVE, AND SALVAGE…