S02 drawings Structural-Final .pdf
PDF 4 MB Posted
- Solicitation number
- 36C24522B0006
About this file
This document package includes structural drawings and details for repair and reinforcement work at a Veterans Affairs medical center. The drawings show proposed modifications to the first, fifth and sixth floor framing plans, including adding new steel beams and columns. Details include base plate, beam to column, and wall opening connections. Related specifications call for work such as installing new steel prior to deck penetrations, locating existing rebar, and matching control joints in new slabs. The associated federal contract opportunity is a solicitation for corrective safety and facility condition assessment issues at the same medical center, issued by the VA Veterans Health Administration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI Responses amendment 0006.pdf | ||
| 36C24522B0006 0006.docx | DOCX document | |
| 36C24522B0006 0005.docx | DOCX document | |
| 36C24522B0006 0004.docx | DOCX document | |
| S06 Revised Response to RFIs -Revised (002).pdf | ||
| 36C24522B0006 0003.docx | DOCX document | |
| 36C24522B0006 0002.docx | DOCX document | |
| S06 Response to RFIs 36C245220006.pdf | ||
| 36C24522B0006 0001.docx | DOCX document | |
| S04 Pre Bid Attendance list.pdf | ||
| S04 Pre Bid Agenda Correct Safety FCA Issues.pdf | ||
| S02 drawings Plumbing Final .pdf | ||
| 36C24522B0006.docx | DOCX document | |
| S02 drawings Mechanical Final .pdf | ||
| S02 Final Combined Specs V1 .pdf | ||
| S02 Drawings Architectural Final .pdf | ||
| S02 wage determination SPS .pdf | ||
| S02 Drawings Fire Protection Final-Bond .pdf | ||
| S02 Final Combined Specs V2 .pdf | ||
| S02 Drawings Electrical Final-Bond .pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
Drawn
Revisions:
Bldg.1
STRUCTURAL NOTES CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
S001
517-19-301
06-04-2021
FINAL SUBMITTAL
BCGSLW
A401
1NEW A IR HANDL I NG UNI T
SEE MECHANI CAL DWGS .
UP
RAMP DN
RAMP DN
ROLLING SHUTTER
ROLLING SHUTTER
5'6" PASS THRU
REMOVE EAS T
LOUVER &
PORT ION OF
WALL BELOW
TO ALLOW FULL
10 '-8" OPENING
SUPPLY
1A-105
STERI LE
LOUVER TO BE INS TALLED
NOTE: SEE SHEET A4 01
FOR LOUVER DETAI LS
24 24.1
H.5
K
L
M
M.5
24.5 27
R E
F
9'
R E
F
R E
F
R E
F
EXISTING
CONCRETE
COLUMN, TYP.
EXISTING
CONCRETE
BEAM, TYP.
EXISTING 7"
REINFORCED
CONCRETE SLAB
B E
A M
, S E
E N
O
TE
/4
F R
O M
F A
C E
O F
S E
E N
O T
E
3'
SEE NOTE 2
8' - 4"
SEE NOTE 2
9' - 0"
B E
A M
, S E
E N
O
TE
/4
F R
O M
F A
C E
O F
S502
TYP.
S502
TY
P.
S502
S E
E N
O T
E
3'
2' - 6" 2' - 6"
REF
9' - 0"
REF
26' - 4"
REF
1' - 9"
REF
7' - 3"
H S
S
X 4X
1/
H S
S
X 4X
1/
HSS10X4X1/4
HSS10X4X1/4
H S
S
X 4X
1/
H S
S
X 4X
1/
HSS10X4X1/4
HSS10X4X1/4
NEW FLOOR DRAIN, SEE
PLUMBING DRAWINGS
AND NOTE 7
1. REF DENOTES FOR REFERENCE ONLY. FIELD VERIFY
2. COORDINATE LOCATION OF ROOF PENETRATIONS WITH
MECHANICAL DRAWINGS AND ACTUAL EQUIPMENT
PURCHASED
3. DO NOT OVERCUT OPENINGS
4. NEW STEEL SHALL BE INSTALLED PRIOR TO INSTALLATION OF
NEW DECK PENETRATIONS
5. PROVIDE NON-SHRINK GROUT BETWEEN NEW STEEL AND
EXISTING SLAB TO PROVIDE POSITIVE BEARING WHERE
REPAIRED
6. ALL HSS 10x4 SHALL BE LSV
7. LOCATE EXISTING SLAB REINFORCING (TOP AND BOTTOM) OF
SLAB THROUGH NON-DESTRUCTIVE MEANS PRIOR TO
INSTALLING NEW PENETRATIONS. DO NOT CUT EXISTING
REINFORCING DURING INSTALLATION.
8. E-XXXX INDICATES EXISTING BEAM.
EXISTING BEAM/COLUMNS
NEW BEAM
DENOTES AREA OF SLAB DEMO FOR NEW DUCT
PENETRATION
PLAN
NORTH
TRUE
NORTH
24 24.1
H.5
K
L
M
M.5
24.5 27
E-B520 E-B521 E
-S B
E -S
B
E
-S B
E -B
E-B524 E-B525
E-B528 E-B529
E-B524 E-B525
E-B532 E-B533
E -S
B
E -B
E -B
E -B
E -B
REF
1' - 9"
REF
7' - 3"
REF
9' - 0"
REF
26' - 4"
R E
F
9'
R E
F
R E
F
R E
F
E -S
B
E
-S B
E -S
B
M A
X 1'
M A
X
2'
M A
X
3'
M A
X 1'
EXISTING 7"
REINFORCED
CONCRETE SLAB
PIPE INSTALLATION
AS REQUIRED FOR
M
ID
D E
P T
H
CLEAN AND ROUGHEN
EXISTING SURFACE APPLY
EPOXY BONDING AGENT PRIOR
TO PLACEMENT OF FRESH
CONCRETE IN ACCORDANCE
WITH MANUFACTURERS
RECOMMENDATIONS
DRILL HOLE INTO EXISTING SLAB 12
BAR DIAMETERS DEEP BY ONE BAR
DIAMETER + 1/4" MAX IN DIAMETER
INTO SLAB IN ACCORDANCE WITH
MANUFACTURERS
RECOMMENDATIONS CLASS B
SPLICE TYP
#4@14" E.W.
NEW SLAB TO MATCH EXISTING
SLAB THICKNESS, ALIGN
CONTROL JOINTS WITH
EXISTING JOINTS
EXISTING SLAB
MINIMUM 4" GRANULAR BASE.
COMPACTED TO 98% OF ITS
STANDARD PROCTOR MAXIMUM
DRY DENSITY IN ACCORDANCE
WITH ASTM D698.
LAP AND TAPE 10 MIL VAPOR
BARRIER
NEW PIPE. REFER TO PLUMBING
FOR PIPE SIZE, DEPTH AND
BEDDING REQUIREMENTS.
NOTES:
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO
COMMENCING WORK. DO NOT INTERRUPT OR UNDERPIN
EXISTING FOOTINGS OR SLAB DURING PIPE DEMOLITION OR
INSTALLATION
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
Drawn
Revisions:
Bldg.1
FIRST FLOOR FRAMING
PLAN
CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
S101
517-19-301
06-04-2021
FINAL SUBMITTAL
BCGSLW
1/4" = 1'-0"S101
1 FIRST FLOOR ROOF FRAMING PLAN
Scale: 1/4"=1'-0"
1' 4' 8' 12'
FIRST FLOOR FRAMING PLAN NOTES
FRAMING PLAN LEGEND
KEY PLAN
1/4" = 1'-0"S101
2 FIRST FLOOR FRAMING PLAN
Scale: 1/4"=1'-0"
1' 4' 8' 12'
3/4" = 1'-0"S101
TYPICAL SLAB ON GROUND
REPAIR DETAIL AT BASEMENT PIPING
NOTE:
RE-USE EXISTING EQUIPMENT SUPPORTS AT AHU-
SPS. COORDINATE WITH ACTUAL EQUIPMENT
PROVIDED PRIOR TO SUBMISSION FOR REVIEW.
H
F
D
25 2624
E
C
H.1
26.5 28.1 28.5
B.95
24.1
REF
17' - 7 1/2"
REF
16' - 4 1/2"
REF
16' - 3 3/4"
REF
2' - 0"
REF
7 3/4"
REF
11' - 10 1/4"
REF
10' - 0"
R E
F
1/
2" R
E F
R E
F
3'
R E
F
9'
R E
F
/2
R E
F
1'
1/ 2"
REF
1' - 9"
S E
E N
O T
E
HSS10X8X1/2
HSS10X4X1/4
H S
S
X 4X
1/
H S
S
X 4X
1/
S E
E N
O T
E
5'
HSS4X4X1/4
S501
S501
TYP
8' - 9 1/4"4' - 1"
18' - 1"
S501
9TYP
S501
S501 9 11
S501
EXISTING CONCRETE
BEAM TYP
EXISTING CONCRETE
COLUMN TYP
EXISTING CONCRETE
BEAM TYP
EXISTING CONCRETE
COLUMN TYP
EXISTING CONCRETE
JOIST TYP
EXISTING HSS 4x4
COLUMN
W8X18
W8X18
W14X22
W8X18
W8X18
W8X18
W8X18 W8X18
W8X18
W8X18
W8X18
W8X18
W8X18
W8X18E-
E-
E-
E-
E-
E-
E-
E-
E-
E-
E-
E-
E-
E-
W14X22 W14X22
W
X
W
X
W 8X
W
X
W 8X
E- E-
E
E
E
E
E
- E -W
X
24.5 27
HSS4X4X1/4
HSS4X4X1/4
T/STL = +48'-5 1/2"
FFE EXIST.
+45'- 6"
FFE EXIST.
+47'- 6"
T/STL = +48'-5 1/2"
T /S
T L
+4
8' -5
/2
T /S
T L
+4
8' -5
/2
HSS6X2X1/4
HSS6X2X1/4
S502
NEW FLOOR DRAIN, SEE
PLUMBING DRAWINGS
AND NOTE 4
NEW FLOOR DRAIN, SEE
PLUMBING DRAWINGS
AND NOTE 4
PROVIDE BRICK LINTEL
AS SHOWN ON 4/S502
S501
TYP.
S502
SEE NOTE 6
7' - 6 1/2"
SEE NOTE 6
10' - 6 1/2"
AHU-1
1' - 3"
HSS4X4X1/4
SEE ARCH
TYP
PLAN
NORTH
TRUE
NORTH
EXIST CONCRETE BEAM
NEW STEEL BEAM
EXISTING STEEL BEAM
EDGE OF DECK
DENOTES DECK SPAN DIRECTION
INDICATES FINISHED FLOOR ELEVATION
E-WXxXX
WXxXX
FFE
1. CONTRACTOR FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS
PRIOR TO SUBMISSION OF SHOP DRAWINGS FOR REVIEW.
2. REF DENOTES FOR REFERENCE ONLY. FIELD VERIFY
3. COORDINATE STEEL LOCATION WITH ACTUAL EQUIPMENT PROVIDED
PRIOR TO SUBMISSION OF SHOP DRAWINGS.
4. LOCATE EXISTING SLAB REINFORCING (TOP AND BOTTOM) OF SLAB
THROUGH NON-DESTRUCTIVE MEANS PRIOR TO INSTALLING NEW
PENETRATIONS. DO NOT CUT EXISTING REINFORCING DURING
INSTALLATION.
5. DO NOT DAMAGE EXISTING REINFORCING DURING ANCHOR
INSTALLATION.
6. COORDINATE WITH ACTUAL EQUIPMENT PURCHASED
HC MALE /
FEMALE STAFF
TOILET5B-120
CLOSET
5AB-106A
CART
LIFT
MALE /
FEMALE
STAFF
TOILET5AB-111
HC MALE /
FEMALE
TOILET5B-121
MALE /
FEMALE
PATIENTS
TOILET5B-112A
HOUSE
KEEPING5B-109
HAC
MECH
RM5A-123
FIRE PROTECTION
FIRE PROTECTION
FIRE PROTECTION
STORAGE
5AB-112
NURSES STATION
5B-112
CORRIDORHALLWAY
ELEVATOR
P-1 ELEVATOR
S-3
ELEVATOR
P-2
ST-3
ELECTRICAL RM
5A-117
CORRIDOR
STORAGE
5A-116
ST-5
ELEVATOR
PS-1
ELEVATOR
PS-2
ST-6
WOMENS LOCKER
5AB-101
RECEPTION
/ OFFICE5AB-104
LOCKER
5AB-103MENS
TOILET5AB-102
WAITING AREA
5B-101
RECEPTION
5B-102
PROCEDURE
RM5B-103
ENDOSCOPY
PROCEDURE RM5B-107
MECHANICAL
5B-108
OFFICE
5B-110
HC MALE /
FEMALE
PATIENT
TOILET5B-111
PATIENT RECOVERY
5B-113
SOILED
LINEN5B-115
MECH RM
5B-114
SUPPLY RM
5B-116
EXAM RM
5B-117
PRF-
ANESTHESIA5B-118
LOUNGE
5B-119
CORRIDOR
TELEPHONE RM
5AB-110
BIO-MEDICAL ENGG
5AB-106
STORAGE
5A-108
BMET
SHOP5AB-109
BMET
SHOP5A-107
STAIR
TOILET
TOILET
STAIR
STAIR
STAIR
UTILITY SHAFT
UTILITY SHAFT
UTILITY SHAFT
5A-106
WHTR
5B-104
RA D I A N T P A N E L
FA N C O I L
FA N C O I L
NEW
STORAG
E
SYSTEM
NEW
STORAG
E
SYSTEM
NEW ON-
DEMAND
WATER HEATER
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
Drawn
Revisions:
Bldg.1
5TH FLOOR FRAMING PLAN CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
S102
517-19-301
06-04-2021
FINAL SUBMITTAL
BCGSLW
1/4" = 1'-0"S102
1 5TH FLOOR FRAMING PLAN
Scale: 1/4"=1'-0"
1' 4' 8' 12'
5TH FLOOR FRAMING PLAN LEGEND
5TH FLOOR FRAMING PLAN NOTES
KEY PLAN
PLAN
NORTH
TRUE
NORTH
1. CONTRACTOR FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO SUBMISSION OF SHOP DRAWINGS FOR REVIEW.
2. REF DENOTES FOR REFERENCE ONLY. FIELD VERIFY
3. T/STEEL = +9'-10 5/8" ABOVE EXISTING FINISHED FLOOR. MATCH TOP OF
STEEL OF ADJACENT EXISTING STEEL.
4. LOCATE EXISTING SLAB REINFORCING (TOP AND BOTTOM) OF SLAB THROUGH
NON-DESTRUCTIVE MEANS PRIOR TO INSTALLING NEW PENETRATIONS. DO
NOT CUT EXISTING REINFORCING DURING INSTALLATION.
5. DO NOT DAMAGE EXISTING REINFORCING DURING ANCHOR INSTALLATION.
EXIST CONCRETE BEAM
NEW STEEL BEAM
EXISTING STEEL BEAM
EDGE OF DECK
DENOTES DECK SPAN DIRECTION
E-WXxXX
WXxXX
H
F
D
25 2624
E
C
H.1
26.5 28.1 28.5
B.95
E- W8X18 E- W8X18
E- W8X18
E
W
X
E- W8X18
E- W8X18 E- W8X18
E- W8X18E- W8X18
E- W8X18 E- W8X18
E- W8X18E- W8X18
E- W8X18 E- W8X18
E- W8X18E- W8X18
E- W8X18 E- W8X18
E
W
X
E
W 8X
E
W
8X
E
W 8X
E
W 8X
REF
17' - 7 1/2"
REF
16' - 4 1/2"
REF
16' - 3 3/4"
REF
2' - 0"
REF
7 3/4"
REF
11' - 10 1/4"
REF
10' - 0"
R E
F
1/
2" R
E F
R E
F
3'
R E
F
9'
R E
F
/2
R E
F
1'
1/ 2"
24.1
W8X18
W8X18
W8X18
W 8X
W8X18
W8X18
W8X18
W 8X
W 8X
HSS4X4X1/4
HSS4X4X1/4HSS4X4X1/4
1' - 9"
3" E
O D
EOD
7 1/2"
EOD
9"
1.5B16 STEEL
ROOF DECK
S501
S501
1/
2" E
.O .D
W8X18 W8X18
S501
TYP
TYP
TYP
E Q
E Q
E Q
E Q
EXISTING CONCRETE
BEAM TYP
EXISTING CONCRETE
COLUMN TYP
EXISTING CONCRETE
BEAM TYP
EXISTING CONCRETE
COLUMN TYP
EXISTING CONCRETE
JOIST TYP
EXISTING HSS 4x4
COLUMN
EXISTING HSS 4x4
COLUMN
S501
S501
S501
S501
W 8X
W 8X
W
8X
W 8X
NEW OPENING IN
EXISTING WALL,
SEE ARCH.
S103
24.5 27
HSS6X2X1/4
HSS6X2X1/4
S501
S501
S502
W8X18W8X18
BEARING TYP.
4" MIN.
NEW LINTEL,
SEE SECTION
S501
NOTES:
1. CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL SHORING DESIGN REQUIRED
TO INSTALL NEW WORK.
COORD W/ ARCH
3' - 0"
C O
O R
D W
/ A R
C H
4'
EXISTING CMU,
FIELD VERIFY
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
Drawn
Revisions:
Bldg.1
6TH FLOOR FRAMING PLAN CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
S103
517-19-301
06-04-2021
FINAL SUBMITTAL
BCGSLW
6TH FLOOR FRAMING PLAN NOTES
6TH FLOOR FRAMING PLAN LEGEND
1/4" = 1'-0"S103
1 6TH FLOOR FRAMING PLAN
Scale: 1/4"=1'-0"
1' 4' 8' 12'
3/4" = 1'-0"S103
2 ELEVATION AT INTERIOR WALL OPENING
Scale: 3/4"=1'-0"
1' 2' 4' 8'
KEY PLAN
1 1/2"
/2
3"
STEEL COLUMN,
SEE PLAN
5/16
13/16'' DIA. HOLE FOR 1/2"
POST INSTALLED ANCHOR
BOLTS
3/4" THICK BASE PLATE, U.N.O.
CL
CL
NOTE:
USE (4) 1/2"x2 3/4" EMBED HILTI
HY200 ANCHORS WITH STD HAS
RODS, TYP. U.N.O.
1/4'' CAP PLATE AT TOP
OF COLUMN
NOTE:
1. QTY. OF FASTENERS, PLATE SIZE,
AND WELD AS REQUIRED FOR BEAM
SHEAR, SEE GENERAL NOTES
HSS COLUMN
3/8" PL. MIN.
3/4''Ø ASTM A-325 BOLTS
1/8''
1/2"
T/ STL
SEE PLAN
CL
3/16
MIN.
/2
/2
W8
W10
W12
BEAM SIZE # OF BOLTS
2L4x3x1/4 LLO
3/4''Ø A325 BOLTS
BEAM,
SEE PLAN
WIDE FLANGE,
SEE PLAN
T/ STL
SEE PLAN
BEAM, SEE PLAN
1/2"
2L4x3x1/4 LLO
/2
/2
3/16
+1/2" RTN T&B TYP.
COPE BEAM AS
REQUIRED
NOTES:
1. QTY. OF FASTENERS, PLATE SIZE, AND
WELD AS REQUIRED FOR BEAM SHEAR -
SEE GENERAL NOTES
EXIST. HSS
COLUMN, SEE PLAN
3/8" PLATE.
3/4''Ø ASTM
A-325 BOLTS
1/2"
T/ STL
SEE PLAN
CL
BEAM,
SEE PLAN EXIST.BEAM,
SEE PLAN
3/16
TYP.
W8
W10
W12
BEAM SIZE # OF BOLTS
EXISTING
BRICK
1' - 4"
1/2"DECK SEE PLAN
BEAM SEE PLAN
EXISTING BRICK
L3x3x1/4xCONT
3/16 2@12
F
3"
9"
1/2"
BEAM SEE PLAN
DECK SEE PLAN
1/4"x4"x0'-8 1/2"xCONT BENT
PLATE. LONG LEG
HORIZONTAL
3/16 2@12
EXISTING BRICK
3/16 2@12
8"
1/2"
BEAM SEE PLAN
DECK SEE PLAN
1/4"x4"x0'-7 1/2"xCONT BENT
PLATE. LONG LEG
HORIZONTAL
EXISTING BRICK
BEAM SEE PLAN
DECK SEE PLAN
600S200-97 STUDS
AT 12" O.C.
7"
9 1/8"
METAL PANEL -
SEE ARCH
L3x3x1/4xCONT
3/16 2@12
400S200-68 LAPPED
TO 6" STUD
1'
VERTICLIP SLS600-12
WITH (3)#12 SCREWS
TO STUD AND (3) .141"
DIA PDF'S TO STEEL
BEAM
VERTICLIP SLB600 W/
(3)#12 SCREWS TO
STUD AND (3).141" DIA
PDF'S TO STEEL BEAM
CL600-68 STIFF CLIP W/(4)#12
SCREWS TO STUD ANCHORED
TO CONCRETE BEAM WITH
1/2"x2 3/4" EMBED HILTIKWIK
BOLT TZ
(3)#12 SDS
2" 2"
1/2"x4"x0'-10" PLATE AT HSS 10x4 1/2"x4"x1'-2" PLATE AT HSS 10x8
PROVIDE 1" GROUT UNDER BASE
PLATE AS REQUIRED FOR
POSITIVE UNIFORM BEARING
AREA ON EXISTING BEAM
1 1/2" 1 1/2"
BEAM SEE PLAN!/2" DIAx2 3/4" EMBED HITLI HY200
ANCHORS WITH STD HAS RODS
1/4
1/4" CAP PLATE
1/8
BEAM SEE
PLAN
L4x4x1/4x0'-6"
LONG TYP3/16
TYP
1/4'' CAP PLATE AT TOP
OF COLUMN
HSS COLUMN
SEE PLAN
3/8" PLATE
1/8''
T/ STL
SEE PLAN
CL
1/4
MIN.
1/4
TOP AND
BOTT
4"HSS BEAMN
SEE PLAN
S501
EXISTING BEAM
TOP OF BEAM
45'- 6"
3/4''Ø A325 BOLTS
EXIST. WIDE
FLANGE, SEE PLAN
T/ STL
SEE PLAN
BEAM,
SEE PLAN
1/2"
2L4x3x1/4 LLO
COPE BEAM AS
REQUIRED
1/
2"
3" 3"
1/
2"
3/16
+1/2" RTN T&B TYP.
FIELD VERIFY
1' - 2" REF
EXISTING
BRICK
EXISTING
BLOCK
L8x6x1/2 LSV
3/16 2@12
4" AT EA.
END
1/2"x1'-2"xCONT.
PLATE
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
Drawn
Revisions:
Bldg.1
STEEL DETAILS CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
S501
517-19-301
06-04-2021
FINAL SUBMITTAL
BCGSLW
1 1/2" = 1'-0"S501
1 TYPICAL BASE PLATE
1 1/2" = 1'-0"S501
TYPICAL WIDE FLANGE BEAM
TO NEW HSS COLUMN CONNECTION
1 1/2" = 1'-0"S501
3 TYPICAL WF TO WF CONNECTION
1 1/2" = 1'-0"S501
TYPICAL WIDE FLANGE BEAM
TO EXISTING HSS COLUMN CONNECTION
1" = 1'-0"S501
5 SECTION AT EXISTING EAST WALL
1" = 1'-0"S501
6 SECTION AT EXISTING SOUTH WALL
1" = 1'-0"S501
7 SECTION AT EXISTING NORTH WALL
1" = 1'-0"S501
8 SECTION AT WEST WALL
1" = 1'-0"S501
PLAN DETAIL AT TUBE TO EXISTING FLOOR
CONNECTION
1" = 1'-0"S501
10 TYPICAL TUBE TO TUBE CONNECTION
1 1/2" = 1'-0"S501
TYPICAL WIDE FLANGE BEAM
TO NEW HSS COLUMN CONNECTION
1 1/2" = 1'-0"S501
12 TYPICAL WF TO EXISTING WF CONNECTION
1 1/2" = 1'-0"S501
13 SECTION AT LINTEL
1/2"x2 3/4" EMBED. HILTI
HY20 AT 1'-0" O.C.
EXISTING SLAB,
SEE PLAN
L4x4x1/4x CONT.
BEAM, SEE PLAN
3/16 2@12
BEAM, SEE PLAN
L4x4x1/4x0'-6"
LONG
3/16
1/2" RTN TOP & BOTT
EXISTING SLAB 1
1/
2"
1/ 2"
5"
2"
L4x4x1/4x0'-8" LONG
BEAM SEE
PLAN EXISTING BEAM,
SEE PLAN
3/16
(4) 1/2" x 2 3/4" EMBED
HILTI HY200 ANCHORS
EXISTING SLAB,
SEE PLAN
M
IN6"
6"6"
S501
COLUMN, SEE PLAN
BEAM, SEE PLAN
BEARING
4" MIN.
BEARING
4" MIN.
1 1/2"
MIN
2"
MIN
2"
1 1/2"
FIELD VERIFY
2' - 0" MAX
EXISTING SLAB
MATCH
EXISTING SLAB
(2)#4
1/4" HILTI KWIK-CON II SCREW
ANCHOR AT 6" O.C. AND AT
EACH CORNER OF PLATE
1/4"STEEL PLATE
4,000 PSI
CONCRETE INFILL
CLEAN AND ROUGHEN EXISTING SURFACE
AND APPLY EPOXY BONDING AGENT PRIOR
TO PLACEMENT OF FRESH CONCRETE IN
ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS
3" 3"
EXIST BEAM
HSS, SEE
PLAN
1/2"x6"x1'- 4" PLATE W/
(4)1/2" DIA. HILT KWIK
BOLT 3 ANCHORS
7"
L4x4x1/4"x0'-4" LONG
HSS6x2x1/4
(LSH)
L4x4x1/4"x0'-4" LONG
L3x3x1/4"
3/8" GUSSET PLATE
3/16
L3x3x1/4"x0'-9" LONG
BOTH SIDES OF HSS
BEAM, SEE
PLAN
+8'-0" MIN
COORDINATE WITH
ACTUAL DOOR
PROVIDED
3/16
3/16
EXIST SLAB
BEAM, SEE
PLAN
DECK, SEE PLAN
L3x3x1/4xCONT
3/16 2@12
1 1/2" 4" 1 1/2" 1 1/2"
4" 1 1/2"
3" 3"
1' - 4"
6"
3/16
3/16
A A
A - A
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
Drawn
Revisions:
Bldg.1
STEEL DETAILS CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
S502
517-19-301
06-04-2021
FINAL SUBMITTAL
BCGSLW
1 1/2" = 1'-0"S502
1 BEAM TO EXISTING SLAB DETAIL
1 1/2" = 1'-0"S502
2 HSS TO HSS CONNECTION DETAIL
1 1/2" = 1'-0"S502
CONNECTION TO EXISTING
CONCRETE BEAM DETAIL
1 1/2" = 1'-0"S502
4 ELEVATION AT BEAM PENETRATION
1 1/2" = 1'-0"S502
5 TYPICAL PENTRATION INFILL DETAIL
1" = 1'-0"S502
6 SECTION AT DOOR SUPPORT
| Sheets |
| S001 - STRUCTURAL NOTES |
| S101 - FIRST FLOOR FRAMING PLAN |
| S102 - 5TH FLOOR FRAMING PLAN |
| S103 - 6TH FLOOR FRAMING PLAN |
| S501 - STEEL DETAILS |
| S502 - STEEL DETAILS |
File details come from the government source that posted it. Updated .