S02 drawings Plumbing Final .pdf
PDF 5 MB Posted
- Solicitation number
- 36C24522B0006
About this file
This document package includes plumbing drawings and specifications for a federal construction project to correct safety and facility condition assessment issues at a Department of Veterans Affairs medical center. The drawings show demolition, new work, and connection details for plumbing systems in the basement, temporary trailer, mechanical rooms, and endoscopy suite. Plumbing fixtures, piping materials, and medical gas connections are specified. Backflow preventers, floor drains, and thermostatic mixing valves are detailed for installation. The related solicitation is for a construction contractor to perform the plumbing work shown on the drawings and specified in the technical requirements. The solicitation number is 36C24522B0006 and was issued by the VA Veterans Health Administration VISN 5 for the project located at VA Beckley in West Virginia.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI Responses amendment 0006.pdf | ||
| 36C24522B0006 0006.docx | DOCX document | |
| 36C24522B0006 0005.docx | DOCX document | |
| 36C24522B0006 0004.docx | DOCX document | |
| S06 Revised Response to RFIs -Revised (002).pdf | ||
| 36C24522B0006 0003.docx | DOCX document | |
| 36C24522B0006 0002.docx | DOCX document | |
| S06 Response to RFIs 36C245220006.pdf | ||
| 36C24522B0006 0001.docx | DOCX document | |
| S04 Pre Bid Attendance list.pdf | ||
| S04 Pre Bid Agenda Correct Safety FCA Issues.pdf | ||
| 36C24522B0006.docx | DOCX document | |
| S02 drawings Structural-Final .pdf | ||
| S02 drawings Mechanical Final .pdf | ||
| S02 Final Combined Specs V1 .pdf | ||
| S02 Drawings Architectural Final .pdf | ||
| S02 wage determination SPS .pdf | ||
| S02 Drawings Fire Protection Final-Bond .pdf | ||
| S02 Final Combined Specs V2 .pdf | ||
| S02 Drawings Electrical Final-Bond .pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEGEND
PLUMBING FIXTURE SCHEDULE
MARK FIXTURE DFU
DCWS
WSFU
DHWS
WSFU
TOTAL
WSFU
CONNECTION PIPE SIZE
REMARKS
WASTE VENT DCWS DHWS
P-401
LAVATORY,
PRIVATE
1.00 0.50 0.50 0.70 1.50 1.50 0.375 0.375 1 AND 7
K1416 SCULLERY SINK 4.00 3.00 3.00 4.00 4.00 1.50 0.75 0.75 2 AND 7
K1421 PREP SINK 4.00 3.00 3.00 4.00 4.00 1.50 0.75 0.75 3 AND 7
P-502 SERVICE SINK 2.00 3.00 3.00 4.00 3.00 1.50 0.50 0.50 4
P-707
EMERGENCY
SHOWER, EYE &
FACE WASH COMBO
- - - - - - 1.25 1.25 5 AND 7
P-708
EMERGENCY EYE &
FACE WASH
- - - - - - 0.50 0.50 6 AND 7
1. DESIGN BASIS: MANUFACTURER: POWERS, MODEL: LFG480-025-11 OR APPROVED EQUAL.
2. DESIGN BASIS: MANUFACTURER: POWERS, MODEL: LFe480-050-01 OR APPROVED EQUAL.
3. DESIGN BASIS: MANUFACTURER: POWERS, MODEL: ES-150-11 OR APPROVED EQUAL.
4. DESIGN BASIS: MANUFACTURER: POWERS, MODEL: EVT200-13 OR APPROVED EQUAL.
5. ASSE1070 LISTED.
6. ASSE 1071 LISTED
7. EXPOSED, ROUGH BRONZE CHROME PLATED FINISH, SIDE INLET, TOP OUTLET CONNECTIONS.
8. EXPOSED, ROUGH BRONZE BOTTOM INLET, TOP OUTLET CONNECTIONS WITH TEMPERATURE GAUGE.
9. EXISTING BUILDING HOT WATER TEMPERATURE.
10. DESIGN BASIS: MANUFACTURER WATTS, MODEL LFL1170
DOMESTIC WATER CALCULATIONS
SIZE
GPM
FLUSH VALVE
WSFU
FLUSH TANK
WSFU
FLUSH
VALVE
FLUSH
TANK
3/8" 2 2 - 0.25
1/2" 3 3 - 1
3/4" 6 6 - 3
1. FIXTURE UNIT VALUES BASED ON THE INTERNATIONAL PLUMBING CODE SIZING CHARTS.
2. MAX VELOCITY FOR HOT WATER - 5 FT/SECOND, FOR COLD WATER 6 FT/SECOND.
THERMOSTATIC TYPE PRESSURE BALANCE MIXING VALVE SCHEDULE
MARK
PIPING INCHES
PRESSURE
DROP
PSI
DESIGN
FLOW
CAPACITY
GPM
TEMPERATURE
REMARKS
INLET
INCH
OUTLET
INCH
COLD HOT TEMPERED
MV-1
3/8 3/8
5 0.35 50°F NOTE 9 110°F
1, 5, AND 7
MV-2
1/2 1/2
5 0.5 50°F NOTE 9 110°F
2, 5, AND 7
MV-3
1/2 1/2
5 3.6 50°F NOTE 9 85°F
3, 6, AND 8
MV-4
1 1/4 1 1/4
10 19 50°F NOTE 9 85°F
4, 6, AND 8
MV-5
1/2 1/2
5 2.6 50°F NOTE 9 95°F 9 AND 10
1. WALL HUNG, VITREOUS CHINA. PROVIDE SINGLE SPOUT, DECK MOUNTED, P-708 FAUCET, EYE/FACE
WASH, ELBOW CONTROL FAUCET WITH VACUUM BREAKER. PROVIDE ASSE 1070 CERTIFIED POINT
OF USE THERMOSTATIC MIXING VALVE (MV-1) UNDER SINK FOR FAUCET.
2. EXISTING SCULLERY SINK RELOCATED. PROVIDE NEW SWING SPOUT FAUCET MOUNTED ON BACK
SPLASH. PROVIDE ASSE 1070 CERTIFIED POINT OF USE THERMOSTATIC MIXING VALVE (MV-2) UNDER
SINK FOR FAUCET.
3. FREE STANDING STAINLESS STEEL THREE COMPARTMENT SINK. PROVIDE TWO SWING SPOUT
FAUCET AND SPRY RINSE ASSEMBLY. PROVIDE ASSE 1070 CERTIFIED POINT OF USE THERMOSTATIC
MIXING VALVE UNDER SINK FOR FAUCETS.
4. FLOOR MOUNTED, CORNER, TERRAZZO SERVICE SINK, 24" X 24" X 12".
5. FREE STANDING COMBINATION EMERGENCY DRENCH SHOWER AND EYE/FACE WASH UNIT. PROVIDE
FLOW TYPE ALARM SYSTEM. PROVIDE ASSE 1071 THERMOSTATIC MIXING VALVE ON WALL.
6. WALL HUNG EYE/FACE WASH. PROVIDE ASSE 1071 THERMOSTATIC MIXING VALVE ON WALL BELOW
FIXTURE.
7. BARRIER-FREE HEALTHCARE INITIATIVE REQUIREMENTS.
SHOCK ABSORBER SCHEDULE
ABSORBOTRON TYPE NO. 5005 5010 5020 5030 5040 5050
P.D.I. SYMBOL A B C D E F
FIXTURE UNIT RATING 1-11 12-32 33-60 61-113 114-154 155-330
1. J.R. SMITH MANUFACTURING COMPANY NUMBER SHOWN. JOSAM, ZURN, OR APPROVED EQUAL IS
ACCEPTABLE.
NOTES
NOTES
NOTES
NOTES
PLUMBING FIXTURE UNIT CALCULATION
MARK FIXTURE QTY
DRAINAGE FU DOMESTIC WATER FU
EACH TOTAL
COLD
WATER
EACH
COLD
WATER
TOTAL
HOT
WATER
EACH
HOT
WATER
TOTAL
WATER
SUPPLY
EACH
WATER
SUPPLY
TOTAL
P-401
LAVATORY,
PRIVATE
2 1.00 2.00 0.50 1.00 0.50 1.00 0.70 1.40
K1416 SCULLERY SINK 1 4.00 4.00 3.00 3.00 3.00 3.00 4.00 4.00
K1421 PREP SINK 1 4.00 4.00 3.00 3.00 3.00 3.00 4.00 4.00
P-502 SERVICE SINK 1 2.00 2.00 3.00 3.00 3.00 3.00 4.00 4.00
P-707
EMERGENCY
SHOWER EYE &
FACE WASH COMBO
1 - - - - - - - -
P-708
EMERGENCY
EYE & FACE WASH
1 - - - - - - - -
12.00 10.00 10.00 13.40
DOMESTIC WATER SUPPLY 13.40 WSFU = 27.00 GPM
DOMESTIC COLD WATER SUPPLY 10.00 WSFU = 19.80 GPM
DOMESTIC HOT WATER SUPPLY 10.00 WSFU = 11.80 GPM
PIPE SIZE: 2" DRAINAGE 3/4" DCWS ~ 3/4" DHWS
PLUMBING PIPING SYMBOLS
DOMESTIC COLD WATER SUPPLY
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
CONDENSATE DRAIN
VENT, SANITARY
SANITARY SEWER
CD
SS
PLUMBING VALVE SYMBOLS
CHECK VALVE
BALL VALVE
TEST PLUG
BALANCING VALVE
VALVE ON RISER
GENERAL PLUMBING SYMBOLS
PIPE REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
WATER HAMMER ARRESTOR
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
HOSE BIBB
NON-FREEZE WALL HYDRANT
FLOOR DRAIN
HUB DRAIN
PLUGGED TEE
WALL CLEANOUT
NEW WORK CONNECTION
LIMIT OF DEMOLITION
PLUMBING SPECIALITIES SYMBOLS
THERMOMETER
FLOW METER
PRESSURE SENSOR
TEMPERATURE SENSOR
CD
SS
PETE'S PLUG
STORM DRAINAGE
SDSD
A. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE NOT TO BE
SCALED. FIELD VERIFY ALL DIMENSIONS, PIPE SIZES, AND INVERTS.
REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS AND
LOCATIONS OF ALL PLUMBING FIXTURES AND EQUIPMENT.
B. COORDINATE PIPE ROUTING WITH DUCT ROUTING, EQUIPMENT
LOCATIONS, ELECTRICAL INSTALLATIONS, AND BUILDING STRUCTURAL
MEMBERS. OFFSET PIPING WHERE REQUIRED TO AVOID CONFLICTS.
AVOID PENETRATING ANY MAIN STRUCTURAL BEAM. NOTIFY COR OF ANY
CONFLICTS.
C. CONTRACTOR SHALL REMOVE AND REPAIR/RESTORE ALL
PENETRATIONS, HOLES, VOIDS, HOLLOWS, DEPRESSIONS, DIPS, DENTS,
INDENTS, CAVITIES, CONCAVITIES, PITS, TROUGHS, DIMPLES, CLEFTS,
NICKS, NOTCHES, GROOVES, IMPRESSIONS, IMPRINTS, MARKS,
RECESSES, BAYS, INLETS, AND ANY COVES IN FLOORS, CEILINGS, AND
WALLS AND/OR SLABS AFFECTED BY PLUMBING MODIFICATIONS OR
WHICH ARE DISCOVERED DURING DEMOLITION BACK TO THE ORIGINAL
BASE MATERIAL OR BETTER COMPLYING WITH WATER TIGHT OR FIRE
RETARDANT CONDITIONS.REPAIR SURFACES TO MATCH EXISTING
UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
D. WHERE CHASES ARE NOT PRESENT, CONNECT VENT PIPING TOGETHER
IN CEILING SPACE IF POSSIBLE TO AVOID CUTTING THROUGH STUDS.
E. PRIOR TO PERFORMING ANY PLUMBING WORK OR PURCHASING ANY
MATERIALS VERIFY EXACT LOCATION, ROUTING, AND PIPE SIZES, ETC.
OF ALL EXISTING WASTE, DRAIN, VENT, DOMESTIC WATER SUPPLY AND
RETURN PIPING.
F. PROVIDE CLEANOUT(S) AS REQUIRED BY INTERNATIONAL PLUMBING
CODE, LOCAL CODE, BOTTOM OF STACKS, AND WHERE HORIZONTAL
SANITARY SEWER PIPING CHANGES DIRECTION OVER 45°.
G. NEW 2" SANITARY SEWER PIPING SHALL BE SLOPED A MINIMUM OF TWO
PERCENT, ONE-QUARTER INCH PER FOOT. NEW 3" AND 4" SANITARY
SEWER PIPING SHALL BE SLOPED A MINIMUM OF ONE PERCENT,
ONE-EIGHTH INCH PER FOOT.
H. ALL DOMESTIC COLD WATER SUPPLY, DOMESTIC HOT WATER SUPPLY,
AND DOMESTIC HOT WATER RETURN PIPING SHALL BE INSULATED.
PLUMBING ABBREVIATIONS
CONTRACTOR GENERAL NOTES
AC
AFF
AFG
ASHRAE
ASME
ASPE
ASR
BF
CFM
COTG
DCWS
DFU
DHWR
DHWS
DN
EL
DWG
ET
EWH
FCO
F
FD
FDC
FS
FU
A/E
AG
GAL
GCO
GPH
GPM
GT
H&CW
HB
HD
HP
HYD
INV.EL
INV
IPC
IRW
KW
KWH
AP
BG
MA
MBH
MED
MV
NC
NTS
OX
OSCO
PG
PSI
PSIA
PSIG
RP
SS
SCFM
TYP
V
VP
VE
VS
VTR
W
WCO
WH
WH
WHA
WSFU
YCO
DS
RL
BF
BG
BFP
NO
CENT
ENT
EWT
LWT
ARWP
ARVP
CD
FIP
P.D.I.
QTY
SD
SAN
ABOVE CEILING
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
AMERICAN SOCIETY OF
HEATING,
REFRIGERATION,
AIR CONDITIONING
ENGINEERS
AMERICAN SOCIETY
OF MECHANICAL
ENGINEERS
AMERICAN SOCIETY
OF
PLUMBING ENGINEERS
AUTOMATIC
RISER
BELOW FLOOR
CUBIC FEET PER
CLEANOUT TO GRADE
DOMESTIC COLD
DRAINAGE FIXTURE
WATER SUPPLY
UNITS
DOMESTIC HOT
WATER RETURN
DOMESTIC HOT
WATER SUPPLY
DOWN
ELEVATION
DRAWING
EXPANSION TANK
ELECTRIC WATER
HEATER
FLOOR CLEANOUT
FAHRENHEIT
FLOOR DRAIN
(HOSE) CONNECTION
FIRE DEPARTMENT
FLOW SWITCH
FIXTURE UNITS
ARCHITECT / ENGINEER
AIR GAP
GALLON
GRADE CLEANOUTS
GALLONS PER HOUR
GALLONS PER MINUTE
GREASE TRAP
HOT AND COLD
WATER
HOSE BIBB
HUB DRAIN
HORSEPOWER
HYDRANT
INVERT ELEVATION
INVERT
INTERNATIONAL PLUMBING
CODE
IRRIGATION WATER
KILOWATT
KILOWATT-HOUR
ACCESS PANEL
SPRINKLER
BELOW GRADE
MEDICAL AIR
1000 BTUH
MEDICAL
MEDICAL VACUUM
NORMALLY CLOSED
NOT TO SCALE
OXYGEN
OUTSIDE CLEANOUT
PRESSURE GAGE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH
ATMOSPHERE
POUNDS PER SQUARE INCH
GAGE
RECIRULATION PUMP
SANITARY SEWER
STANDARD CUBIC
FOOT/MINUTE
TYPICAL
VENT
VACUUM PUMP
VENT EXHAUST
VENT STACK
VENT THROUGH ROOF
WASTE
WALL CLEANOUT
WALL HYDRANT
WATER HEATER
WATER HAMMER ARRESTER
WATER SUPPLY FIXTURE
UNITS
YARD CLEANOUT
DOWNSPOUT
RAIN WATER LEADER
BELOW FLOOR
BELOW GRADE
BACKFLOW PREVENTER
NORMALLY OPEN
CENTRIFUGAL
ENTERING
ENTERING WATER
TEMPERATURE
LEAVING WATER
TEMPERATURE
ACID RESISTANT WASTE PIPE
ACID RESISTANT VENT PIPE
CONDENSATE DRAIN
FEMALE IRON PIPE
PLUMBING AND DRAINAGE
QUANTITY
STORM DRAINAGE
SANITARY SEWER
INSTITUTE
1. DESIGN BASIS; MANUFACTURER: ZURN WILKINS, MODEL: 975XL2 OR APPROVED EQUAL.
2. REFER TO MANUFACTURER LITERATURE FOR INSTALLATION OF BACKFLOW PREVENTER AND
SPECIFICATIONS FOR MANUFACTURER.
3. PROVIDE AIR GAP FITTING AND DISCHARGE TO FLOOR DRAIN.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER SCHEDULE
MARK
PIPING
PRESSURE
DROP
PSI
CAPACITY
GPM
SYSTEM LOCATION NOTES
INLET
INCHES
OUTLET
INCHES
BFP-1 3/4 3/4 10 12 DCWS
REFER TO
PLANS FOR
LOCATION
1, 2, AND 3
BFP-2 1 1 10 12 DCWS
REFER TO
PLANS FOR
LOCATIONS
1, 2, AND 3
NOTES
LEGEND: TYPE:
S = SANITARY C = FINISHED AREA
D = LATEX MASTIC/THIN SET TILE
E = HEAVY BODY WITH NON-TILTING NICKEL BRONZE
OR DUCTILE IRON GRATE, REMOVABLE SEDIMENT
BUCKET, MIN. 300 MM [12 IN.] SQUARE. EXTRA
HEAVY DUTY GRATE FOR TRAFFIC USE.
R = BODY COATED WITH ACID RESISTANT ENAMEL
FINISH WITH SECONDARY DOME STRAINER AND
WITHOUT GRATE, 200 MM [8 IN.] SQUARE.
S = FLOOR SINK, 304 STAINLESS STEEL BODY WITH
POLISHED INTERIOR WITH INTERNAL DOME
STRAINER, NON-TILTING LOOSE GRATE, 300 MM
[12 IN.] SQUARE.
FLOOR DRAIN SCHEDULE
LOCATION
DRAIN
TYPE
SIZE
INCHES
SEWER REMARKS
CLEAN ROOM C/D 2 S 1
MECHANICAL ROOM E 4 S 1
EQUIPMENT ROOM R 3 S 1
SPS/ENDO S 4 S 1
1. REFER TO DRAWINGS FOR LOCATION OF FLOOR DRAIN.
NOTES:
DOMESTIC WATER BRANCH LENGTH SCHEDULE
SIZE
INCH
TEMPERATURE
VOLUME
FLUSH VALVE
WSFU
MAXIMUM
PIPE LENGTH
FEET
LITERS OUNCES GALLONS
3/8 HOT 0.35 12 0.0938
PUBLIC LAVATORY
LOW FLOW LAVATORY
16.38
3/8 HOT 0.35 12 0.0938
PRIVATE LAVATORY
PATIENT AND EXAM ROOMS
9.38
1/2 HOT 0.70 24 0.1875
SINKS AND SHOWER
18.75
3/8 COLD 0.35 12 0.0938
PUBLIC LAVATORY
LOW FLOW LAVATORY
16.38
3/8 COLD 0.35 12 0.0938
PRIVATE LAVATORY
PATIENT AND EXAM ROOMS
9.38
3/8 COLD 0.70 12 0.0938
ICE MACHINE
9.38
1/2 COLD 0.70 24 0.1875
SINKS AND SHOWER
18.75
3/4 COLD 1.90 64 0.5000
URINALS
21.74
1 COLD 4.85 164 1.2800
TOILETS
31.22
1. MAXIMUM DEAD END LENGTH IS TWO (2) PIPE DIAMETER OFF THE MAIN.
NOTES:
I. CONTRACTOR SHALL CONNECT ALL SANITARY AND VENT PIPING FROM
NEAREST EXISTING SANITARY AND VENT PIPING TO FLOOR DRAIN PER IPC.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
I P
R O
J E
C T
S T
M
V
A
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
N D
F
C
I S
S U
E S
T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
S
H E
E T
S P
P
D
W G
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
440 Martin Luther King Jr. Blvd
Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
FULLY SPRINKLERED
CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
517-19-301
Bldg. 1
FINAL SUBMITTAL
06-04-2021
LEGENDS, GENERAL NOTES,
SCHEDULES, AND DETAILS
P-001
GTK DLB
AutoCAD SHX Text F
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text 17817
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text
TO ENDOSCOPY UNIT
AutoCAD SHX Text
MV-5
AutoCAD SHX Text
TEMPERATURE AND PRESSURE GAUGE (TYP)
AutoCAD SHX Text
PRESSURE GAUGE (TYP)
AutoCAD SHX Text
PRESSURE REGULATOR (TYP)
AutoCAD SHX Text
ISOLATION VALVE (TYP)
AutoCAD SHX Text
DCW
AutoCAD SHX Text
DHW
AutoCAD SHX Text
TO FLOOR DRAIN
AutoCAD SHX Text
TO MEDICAL AIR
AutoCAD SHX Text
TO MIXING VALVE
AutoCAD SHX Text
ENDOSCOPY REPROCESSING UNIT (NIC)
AutoCAD SHX Text
6" MAX
AutoCAD SHX Text
ENDOSCOPY MIXING VALVE AND CONNECTION DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
NTS
UP
UP
OPEN TO OUTSIDE
DN
FEMALE
LOCKER
BC-108D
MALE LOCKER
BA-102
STORAGE
BA-101A
MECH
BC-108H
CORRIDOR
ELECTRICAL
DETERGENT
BC-108H
DUMB
WAITER
BC-108C
HSK
BC-108A
RM
BA-101
CORRIDOR
STAIR
BA-101B
HSK
BA-108C
BC-108I
DECONTAMINATION
BA-103
SPS STORAGE
BC-108
OFFICE
BC-108B
OFFICE
BC-108E
BREAK
OUT
RM
BC-109
SPD SUPV
BC-110
PREP & PACK
ETO
ABATOR
RM
BA-103A
STERILIZATION
BC-108K
A
A
A
A
RO RO
RO RO
R O
R O
RETAIL STORAGE
BA-105
HC WOMENS
TOILET
BA-104
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
I P
R O
J E
C T
S T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
S
H E
E T
S P
P
D D
W G
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
440 Martin Luther King Jr. Blvd
Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
FULLY SPRINKLERED
CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
517-19-301
Bldg. 1
FINAL SUBMITTAL
06-04-2021
SCALE:
PARTIAL BASEMENT SPS
PLUMBING FLOOR PLAN - DEMOLITION
1. EXISTING TWO -COMPARTMENT SCULLERY SINK TO BE
REMOVED, CLEANED AND STORED IN A SECURE SPACE FOR
REUSE IN NEW WORK. EXISTING UTILITIES SHALL BE CUT
AND CAPPED IN WALL. REFER TO PL101 FOR LOCATION AND
CONNECTION TO UTILITIES.
2. REMOVE AND DISCARD EXISTING THREE-COMPARTMENT
SINK. EXISTING UTILITIES SHALL REMAIN AND BE REUSED IN
NEW WORK.
3. REMOVE AND DISCARD EXISTING FLOOR DRAIN. FLOOR
DRAIN SHALL BE REMOVED AND PIPING PLUGGED BELOW
FLOOR. REPAIR FLOOR TO MATCH EXISTING.
4. REMOVE AND DISCARD EXISTING HUB DRAIN BACK TO THE
SANITARY SEWER STACK. EXISTING SANITARY SEWER
SHALL BE PLUGGED BELOW FLOOR. REPAIR FLOOR TO
MATCH EXISTING.
5. REMOVE AND DISCARD EXISTING PIPING BACK TO LIMITS OF
DEMOLITION.
6. REMOVE AND DISCARD ALL EXISTING PIPING FITTINGS,
VALVES, SUPPORTS, AND HANGERS BACK TO THE LIMITS OF
DEMOLITION.
7. REMOVE AND DISCARD EXISTING PIPING. PIPING SHALL BE
PLUGGED BELOW FLOOR.
8. REMOVE AND DISCARD ALL EXISTING WATER PIPING,
FITTINGS, VALVES, SUPPORTS, AND FILTERS BACK TO THE
LIMITS OF DEMOLITION
9. CUT, REMOVE, AND DISCARD EXISTING PIPING IN BACK TO
THE LIMITS OF DEMOLITION. WASTE AND VENT STACK IN
WALL SHALL REMAIN FOR NEW WORK CONNECTION.
10. CUT, REMOVE, AND DISCARD EXISTING COMPRESSED AIR
PIPING ON WALL BACK TO LIMITS OF DEMOLITION.
11. LIMITS OF DEMOLITION.
KEY PLAN
PARTIAL BASEMENT SPS PLUMBING
FLOOR PLAN - DEMOLITION
PD101
GTK DLB
A. EXISTING PLUMBING FIXTURES TO REMAIN UNLESS NOTED
OTHERWISE.
B. PRIOR TO PERFORMING ANY WORK OR PURCHASING ANY
MATERIAL, THE CONTRACTOR SHALL VERIFY LOCATION OF
EXISTING PLUMBING PIPING.
C. REMOVE ALL EXISTING PLUMBING FIXTURES, TRIM, AND ALL
ASSOCIATED PIPING BACK TO LIMITS OF DEMOLITION.
D. DEMOLITION SHALL INCLUDE PIPING, VALVES, FITTINGS,
PIPE SUPPORTS, AND HANGERS OF PIPING BEING REMOVED.
E. ABANDONED OR UNUSED PIPING, FITTINGS, SUPPORTS, AND
HANGERS ABOVE CEILING SHALL BE REMOVED.
F. CONTRACTOR SHALL RESTORE ALL PENETRATIONS, HOLES,
VOIDS, HOLLOWS, DEPRESSIONS, DIPS, DENTS, INDENTS,
CAVITIES, CONCAVITIES, PITS, TROUGHS, DIMPLES, CLEFTS,
NICKS, NOTCHES, GROOVES, IMPRESSIONS, IMPRINTS,
MARKS, RECESSES, BAYS, INLETS, AND ANY COVES IN
FLOORS AND CEILINGS WHICH ARE DISCOVERED DURING
DEMOLITION BACK TO THE ORIGINAL BASE MATERIAL OR
BETTER COMPLYING WITH WATER TIGHT AND/OR FI
CONDITIONS. REFER TO ARCHITECTURAL DRAWINGS FOR
ADDITIONAL INFORMATION ON THE FLOOR AND CEILING
REPAIR.
G. REFER TO PHASING SCHEDULE BY ARCHITECTURE.
12'
3/16" = 1'-0"
4'0 8'
GENERAL NOTES
DEMOLITION KEY NOTES
PLAN
NORTH
TRUE
NORTH
SPS DEPARTMENT
AutoCAD SHX Text 17817
AutoCAD SHX Text
STATE OF
CART
WASH
PASS
THRU
STERILIZERSTERILIZERWASHWASH
UP
UP
ACCESS
BC-108J
P-401
P-401
P-707
K-1421
K-1416
TS
TS
2 23
4 9
A
A
A
A
RO RO
RO RO
R O
R O
DETERGENT
BC-108H
DUMB
WAITER
BC-108C
BA-101B
RM
BA-101
STORAGE
BA-101A
DECONTAMINATION
BA-103
MALE
LOCKER
BA-102
R.O.
BA-103B
ANTEROOM
BA-103A
HC
WOMENS
TOILET
BA-104
RETAIL
STORAGE
BA-105
ELECTRICAL
STAIR
MECH
BC-108H
CORRIDOR
SPS
STORAGE
BC-108
C O
R R
I D
O R
HSK
BC-108A
FEMALE
LOCKER
BC-108D
OFFICE
BC-108B
OFFICE
BC-108E
SPD
SUPV
BC-110
BREAK
OUT
RM
BC-109
PREP &
PACK
BC-108I
HSK
BA-108C
4"CO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
I P
R O
J E
C T
S T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
S
H E
E T
S P
P
L D
W G
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
440 Martin Luther King Jr. Blvd
Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
FULLY SPRINKLERED
CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
517-19-301
Bldg. 1
FINAL SUBMITTAL
06-04-2021
SCALE:
PARTIAL BASEMENT SPS
PLUMBING FLOOR PLAN - NEW WORK
1. CONNECT TO EXISTING UTILITIES AT APPROXIMATE
LOCATION INDICATED.
2. CONNECT TO EXISTING DOMESTIC WATER PIPING ABOVE
CEILING.
3. PROVIDE AND INSTALL EMERGENCY SHOWER EYE/FACE
WASH AND ASSE 1071 APPROVED TEMPERING VALVE (MV-3).
4. PROVIDE AND INSTALL ASSE 1070 APPROVED POINT OF USE
TEMPERING VALVE (MV-2).
5. PROVIDE AND INSTALL 2" HUB DRAIN AT APPROXIMATE
LOCATION INDICATED. TOP OF HUB DRAIN 18" MAXIMUM
ABOVE FINISHED FLOOR.
6. PROVIDE AND INSTALL 3" FLOOR SINK AT APPROXIMATE
LOCATION INDICATED.
7. 2"SS-DN.
8. PROVIDE AND INSTALL REDUCE PRESSURE BACKFLOW
PREVENTER (BFP-2).
9. 3" SS-DN.
10. CONNECT NEW SANITARY SEWER PIPING TO EXISTING
SANITARY SEWER PIPING BELOW FLOOR AT THE
APPROXIMATE LOCATION INDICATED.
11. CONNECT NEW VENT PIPING TO EXISTING VENT PIPING
ABOVE CEILING AT APPROXIMATE LOCATION INDICATED.
KEY PLAN
PARTIAL BASEMENT SPS PLUMBING
FLOOR PLAN - NEW WORK
PL101
GTK DLB
A. COORDINATE PIPE ROUTING WITH DUCT ROUTING,
EQUIPMENT LOCATIONS, ELECTRICAL INSTALLATIONS, AND
BUILDING STRUCTURAL MEMBERS. OFFSET PIPING WHERE
REQUIRED TO AVOID CONFLICTS. AVOID PENETRATING ANY
MAIN STRUCTURAL BEAM. NOTIFY COR AND ARCHITECT OF
ANY CONFLICTS.
B. CONTRACTOR SHALL INSPECT AND ROD OUT EXISTING
SANITARY WASTE AND/OR SEWER PIPING BEFORE MAKING
ANY NEW CONNECTIONS. CONTRACTOR SHALL NOTIFY
OWNER AND COR OF ALL SANITARY SEWER WHICH IS NOT
SERVICEABLE AND REQUIRE REPLACEMENT.
C. PRIOR TO PERFORMING ANY PLUMBING WORK OR
PURCHASING ANY MATERIALS VERIFY EXACT LOCATION,
ROUTING, AND PIPE SIZES, ETC. OF ALL EXISTING SANITARY
SEWER, VENT, AND STORM DRAINAGE PIPING.
D. SEE ARCHITECTURAL PLANS FOR WALL RATINGS.
PLAN
NORTH
TRUE
NORTH
SPS DEPARTMENT
GENERAL NOTES
KEY NOTES
12'
3/16" = 1'-0"
4'0 8'
AutoCAD SHX Text 17817
AutoCAD SHX Text
STATE OF
RAMP DN
DN
FOAM
Ø
W
S
HSK
FEMALE
LOCKER
BC-108D
MOBILE POWER
DISTRIBUTION
UNIT
MOBILE STEAM
GENERATOR
UNIT
MOBILE WATER
SOLUTIONS
UNIT
MOBILE WATER
SOLUTIONS
UNIT
DECONTAMINATION
STERILIZATION
2"Ø DCWS
EXISTING
4" COTG
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
I P
R O
J E
C T
S T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
S
H E
E T
S P
P
L D
W G
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
440 Martin Luther King Jr. Blvd
Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
FULLY SPRINKLERED
CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
517-19-301
Bldg. 1
FINAL SUBMITTAL
06-04-2021
1. ROUTE DOMESTIC WATER BELOW GRADE. PROVIDE A
PROTECTION SLEEVE FOR DOMESTIC WATER PIPING. SEE
DETAIL THIS SHEET.
2. CONNECT NEW 4" DOMESTIC WATER PIPING TO EXISTING
DOMESTIC WATER PIPING BELOW GRADE AT APPROXIMATE
LOCATION INDICATED.
3. 2"DCWS-DN. CONNECT DOMESTIC WATER TO MOBILE WATER
SOLUTION UNIT AT APPROXIMATED LOCATION INDICATED.
4. CONTRACTOR SHALL EXTEND THE FIRE PROTECTION TO THE
FIRE PROTECTION CONNECTION AT THE TEMPORARY SPS
TRAILER.
5. CONTRACTOR SHALL EXTEND SANITARY SEWER PIPING TO
SANITARY SEWER PIPING CONNECTION FOR THE
TEMPORARY SPS TRAILER.
6. CONTRACTOR SHALL ROUTE SANITARY SEWER PIPING ON
GRADE AND TURN DOWN AND SPILL INTO EXISTING CLEAN
OUT TO GRADE. RELOCATE CLEAN OUT OUTSIDE OF
TEMPERATURE RAMP AS NEEDED.
KEY PLAN
PARTIAL TEMPORARY SPS TRAILER
PLUMBING FLOOR PLAN - NEW WORK
PL102
GTK DLB
A. COORDINATE PIPE ROUTING WITH DUCT ROUTING,
EQUIPMENT LOCATIONS, ELECTRICAL INSTALLATIONS, AND
BUILDING STRUCTURAL MEMBERS. OFFSET PIPING WHERE
REQUIRED TO AVOID CONFLICTS. AVOID PENETRATING ANY
MAIN STRUCTURAL BEAM. NOTIFY COR AND ARCHITECT OF
ANY CONFLICTS.
B. CONTRACTOR SHALL INSPECT AND ROD OUT EXISTING
SANITARY WASTE AND/OR SEWER PIPING BEFORE MAKING
ANY NEW CONNECTIONS. CONTRACTOR SHALL NOTIFY
OWNER AND COR OF ALL SANITARY SEWER WHICH IS NOT
SERVICEABLE AND REQUIRE REPLACEMENT.
C. PRIOR TO PERFORMING ANY PLUMBING WORK OR
PURCHASING ANY MATERIALS VERIFY EXACT LOCATION,
ROUTING, AND PIPE SIZES, ETC. OF ALL EXISTING SANITARY
SEWER, VENT, AND STORM DRAINAGE PIPING.
D. SEE ARCHITECTURAL PLANS FOR WALL RATINGS.
PLAN
NORTH
TRUE
NORTH
SPS DEPARTMENT
GENERAL NOTES
KEY NOTES
SCALE:
PARTIAL TEMPORARY SPS TRAILER
PLUMBING FLOOR PLAN - NEW WORK
12'
3/16" = 1'-0"
4'0 8'
ALL PIPE EXTENSIONS AND CONNECTIONS ARE THE
RESPONSIBLY OF THE CONTRACTOR AND THE VENDER.
REFER TO ARCHITECTURAL SCHEMATIC PIPING DRAWING
FOR PIPE ROUTING.
NOTE
AutoCAD SHX Text 17817
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text
AutoCAD SHX Text
%%UDOMESTIC WATER PIPING BELOW CONCRETE AND ASPHALT SURFACES DETAIL
AutoCAD SHX Text
EXISTING PAVEMENT
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
2" THICK ASPHALT PATCH
AutoCAD SHX Text 12"
AutoCAD SHX Text 12"
AutoCAD SHX Text
BEDDING OF FINE GRAVEL OR
AutoCAD SHX Text
COARSE SAND
AutoCAD SHX Text
1/8 DIAMETER OF PIPE
AutoCAD SHX Text
OR 4" MINIMUM
AutoCAD SHX Text
APPROVED BACKFILL COMPACTED
AutoCAD SHX Text
IN 6" THICK LAYERS TO 95%
AutoCAD SHX Text
8"-3000 PSI CONCRETE UNDER EXISTING ASPHALT,
AutoCAD SHX Text
UNDISTURBED SOIL
AutoCAD SHX Text
MAX. DENSITY
AutoCAD SHX Text
SHALL MATCH EXISTING SIDEWALK
AutoCAD SHX Text
WHERE EXISTING SIDEWALKS ARE CUT THICKNESS
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
WHERE SIDEWALKS ARE CUT
OMIT ASPHALT PATCH.
PATIENT BATH
RM 3A-131
SOILED
UTILITY
3A-142
STERILE
SUPPLY 1A-105
EXAM RM / C AND
P PSYCHOLOGY
CLINIC
1A-108
HOUSE
KEEPING
1A-107
COPPER
CLINIC
NURSE
EXAM RM
1AB-131
EXAM RM /
C AND P
MD CLINIC
1A-109
MECH
1A-113
DH-1
3 4
BF
3"CO
3"Ø SAN
N
OPERATORY
EXAM RM
2A-151
DENTAL
SUPPLY
2A-152
OPERATORY
EXAM RM
2A-154
SUPPLY RM
2A-153
DH-1
3 4 5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
I P
R O
J E
C T
S T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
T
B
E C
K L E
Y
C
O R
R
S
A F
E T
Y
A
S U
E S
S
H E
E T
S P
P
L D
W G
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
440 Martin Luther King Jr. Blvd
Macon, GA 31201
478.743.8415 Fax: 478.743.8239
www.clarknexsen.com
FULLY SPRINKLERED
CORRECT SAFETY AND
FCA ISSUES FOR SPS
BECKLEY, WEST VIRGINIA
517-19-301
Bldg. 1
FINAL SUBMITTAL
06-04-2021
2ND & 3RD FLOOR MECHANICAL ROOM
PLUMBING - NEW WORK
PL103
GTK DLB
1. CONNECT NEW 3/4" DOMESTIC WATER SUPPLY PIPING TO
EXISTING DOMESTIC WATER SUPPLY PIPING ABOVE CEILING.
2. PROVIDE AND INSTALL NEW 3/4" REDUCED PRESSURE
BACKFLOW PREVENTER ASSEMBLY (BFP-1). CONTRACTOR
SHALL PROVIDE AIR GAP DRAIN AND ROUTE TO NEW FLOOR
DRAIN.
3. PROVIDE AND INSTALL NEW 2” FLOOR DRAIN, TYPE C/D WITH
TRAP PRIMER CONNECTION AND PROVIDE A CHEMICALLY
RESISTANT ELASTOMER TRAP SEAL DEVICE.
4. PROVIDE AND INSTALL NEW AUTOMATIC TRAP PRIMER.
5. UNCOVER EXISTING FLOOR DRAIN AND CONNECT TO
EXISTING PIPING.
6. CONNECT TO EXISTING SANITARY FOR JANITOR'S SINK.
A. COORDINATE PIPE ROUTING WITH DUCT ROUTING,
EQUIPMENT LOCATIONS, ELECTRICAL INSTALLATIONS, AND
BUILDING STRUCTURAL MEMBERS. OFFSET PIPING WHERE
REQUIRED TO AVOID CONFLICTS. AVOID PENETRATING ANY
MAIN STRUCTURAL BEAM. NOTIFY COR AND ARCHITECT OF
ANY CONFLICTS.
B. CONTRACTOR SHALL REMOVE AND REPAIR PORTIONS OF
FLOORS, CEILINGS AND/OR SLABS AFFECTED BY PLUMBING
MODIFICATIONS. REPAIR SURFACES TO MATCH EXISTING
UNLESS NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS.
C. CONTRACTOR SHALL INSPECT AND ROD OUT EXISTING
SANITARY WASTE AND/OR SEWER PIPING BEFORE MAKING
ANY NEW CONNECTIONS. CONTRACTOR SHALL NOTIFY
OWNER AND COR OF ALL SANITARY SEWER WHICH IS NOT
SERVICEABLE AND REQUIRE REPLACEMENT.
D. PRIOR TO PERFORMING ANY PLUMBING WORK OR
PURCHASING ANY MATERIALS VERIFY EXACT LOCATION,
ROUTING, AND PIPE SIZES, ETC. OF ALL EXISTING SANITARY
SEWER, VENT, AND STORM DRAINAGE PIPING.
E. PROVIDE CLEANOUT(S) AS REQUIRED BY INTERNATIONAL
PLUMBING CODE, LOCAL CODE, AND/OR WHERE HORIZONTAL
SANITARY SEWER PIPING CHANGES DIRECTION OVER 45°.
F. NEW 2" SANITARY SEWER PIPING SHALL BE SLOPED A
MINIMUM TWO PERCENT, ONE-QUARTER INCH PER FOOT.
NEW 3" AND 4" SANITARY SEWER PIPING SHALL BE SLOPED A
MINIMUM ONE PERCENT, ONE-EIGHTH INCH PER FOOT.
G. SEE ARCHITECTURAL PLANS FOR WALL RATINGS.
PLAN
NORTH
TRUE
NORTH
SCALE:
12'
3/16" = 1'-0"
4'0 8'
SECOND FLOOR KEY PLAN
ROOF
UP
RAMP DN
RAMP DN
ROLLING SHUTTER
ROLLING SHUTTER
5'6" PASS THRU
FIRST FLOOR KEY PLAN
GENERAL NOTES
KEY NOTES
SCALE:
12'
3/16" = 1'-0"
4'0 8'
1A-105
2A-152
AutoCAD SHX Text 17817
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text
1A-105 STERILE SUPPLY MECHANICAL PLAN - NEW WORK
AutoCAD SHX Text
AutoCAD SHX Text
2A-152 DENTAL SUPPLY MECHANICAL PLAN - NEW WORK
| Sheets and Views |
| P-001 LEGENDS, GENERAL NOTES, SCHEDULES, AND DETAILS |
| PD101 PARTIAL BASEMENT SPS PLUMBING FLOOR PLAN - DEMOLITION |
| PL101 PARTIAL BASEMENT SPS PLUMBING FLOOR PLAN - NEW WORK |
| PL102 PARTIAL TEMPORARY SPS TRAILER PLUMBING FLOOR PLAN - NEW WORK |
| PL103 2ND & 3RD FLOOR MECHANICAL ROOM PLUMBING - NEW WORK |
| PL104 5TH FLOOR OR SUITE PLUMBING PLANS - NEW WORK |
| PL105 PARTIAL 5TH FLOOR ENDOSCOPY PLUMBING PLANS - NEW WORK |
File details come from the government source that posted it. Updated .