This package includes construction drawings and details for telecommunications and electrical system upgrades at the Camp Butler National Cemetery. The drawings call for installing new telecom rooms in the Administration Building basement, first, and second floors, as well as in the Maintenance Building. Equipment to be provided and installed includes wall-mounted equipment racks, fiber optic and copper cable infrastructure, patch panels, switches, UPS backup power systems, and related hardware. Grounding and bonding details are shown. Electrical work includes upgrading panelboards in the Administration and Maintenance Buildings to support the new telecom loads. Conduit and wiring routes are provided for connecting the new equipment to the upgraded power sources.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
ADMIN
ET102
AB
A
TE102
AB-4,6,8 AB-2
24 5
1 +74"
2 2
M
2 1
+84"
+36"
ET102
M-38M-4025 21 23
4 22
C
TE102
9 11
ADMIN
AB
ADMINISTRATION BUILDING
EXISTING
NEW
PROVIDE (4) #4AWG CU, #8 AWG CU
GROUND IN 1-1/2" CONDUIT.
SPD
4 23
IN
T
E
GR I TY FEDE
R
A L
S ERV I C E S
INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
NCA DESIGN
AND
CONSTRUCTION
SERVICE
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FULLY SPRINKLERED
Above Group, Inc.
(321) 345-9026
CAMP BUTLER NATIONAL CEMETERY
BID DOCUMENTS SUBMISSION
A u to d e s k D o c s /0
C a m p
B u tl e r
IT
U p g ra d e s /0
C a m p
B u tl e r
IT
U g ra d e s
R
T
.r v t
/2
/2
:4
:1
P
M
ET102
TELECOM FLOOR PLANS - NEW REPAIR ROADS, PARKING LOTS, CURB &
GUTTER;
CORRECT IT DEFICIENCIES
SANGAMON COUNTY, ILLINOIS
806CM3029
JUNE 28, 2023 BMS CVM
BID DOCUMENTS
CODED NOTES:
DRAWING NOTES:
1. LABELING STANDARDS SHALL BE FOLLOWED FOR TR NUMBER, RACK NUMBER, PATCH PANEL (A-Z), AND PORT NUMBER. EXAMPLE: TR1-1A-01.
2. 8P8C CONNECTION PORTS IN TCO WALL PLATES SHALL BE COLOR CODED BASED ON TYPE. REFER
TO SHEET T-001 FOR CABLE COLOR CHART. TCO WALL PLATE PORT AND CABLE COLOR SHALL
MATCH ASSOCIATED PATCH PANEL COLOR.
3. LABEL ALL CABLES AND PORTS ON BOTH ENDS WITH COMPUTER GENERATED, SELF-LAMINATING, ADHESIVE, WRAPAROUND LABELS WITH THE TCO ROOM NUMBER (101, 102...), AND PORT SEQUENCE
NUMBER (001, 002...).
INSTALL NEW PANEL BOARD ON AVAILABLE WALL SPACE ADJACENT TO EXITING PANEL. COORDINATE
EXACT LOCATION IN FIELD WITH EXISTING CONDITIONS.
RELOCATE INDICATED LOADS TO NEW PANEL "AB". INSTALL NEW 75A, 3-POLE BREAKER INTO SPACE MADE AVAILABLE BY RELOCATED LOADS. NEW BREAKER TO MATCH EXISTING BREAKERS IN MAKE, MODEL AND AIC VALUE.
PROVIDE CONDUIT AND CABLING AS REQUIRED FOR RELOCATION OF INDICATED EXISTING LOADS TO
NEW PANEL.
INSTALL NEW 30A, 1-POLE BREAKER INTO AVAILABLE SPACE 38. NEW BREAKER TO MATCH EXISTING
BREAKERS IN MAKE, MODEL AND AIC VALUE.
PROVIDE (3) #10AWG CU, #10 AWG CU GROUND IN 1" CONDUIT TO 30A OUTLET INDICATED.
CONNECT TO NEW 20A, 1-POLE BREAKER IN PANELBOARD "M" AT POSITION 40. PROVIDE (2) #10AWG CU, #
10AWG CU GROUND IN 3/4" CONDUIT.
COORDINATE EXACT LOCATION OF NETWORK EQUIPMENT AND BACK BOARD WITH NCA IT PERSONNEL
PRIOR TO CONSTRUCTION.
PROVIDE TIA APPROVED, FIRE RATED, AC GRADE PLYWOOD BACKBOARD 4'x4'x1/2", OR APPROVED FIRE PLYWOOD. PAINT ON ALL SIDES AND WITHIN CUTOUT AREAS WITH AT LEAST (2) COATS OF FIRE RETARDANT, LIGHT COLORED PAINT. LOCATE BACKBOARD 12" COUNTER, INSTALL SO 'A' SIDE OF
PLYWOOD IS EXPOSED.
PROVIDE 48"H X 24"W X 30"D WALL MOUNTED CABINET WITH SWING-OUT REAR ACCESS, AND LOCKABLE FRONT DOOR. BASIS OF DESIGN IS CHATSWORTH CUBE-IT WALL-MOUNT CABINET, GEN 3, 26U, #12-24
TAPPED RAILS, TEMPERED GLASS DOOR, GLACIER WHITE - 12419-E48 CUBE-IT OR EQUAL.
TELECOM MAIN GROUND BUSBAR. ALL VERTICAL AND HORIZONTAL RACKS AND CABLE TRAYS SHALL BE BONDED TO BUSBAR. REFER TO GROUND BUS BAR DETAIL ON THIS SHEET FOR MORE INFORMATION.
VERTICAL WIRE MANAGERS IN CABINET. BASIS OF DESIGN IS CHATSWORTH 40970-711.
1U FIBER OPTIC SHELF WITH (2) 12 FIBER LC CONNECTOR CASSETTES FOR TERMINATION OF INCOMING
FIBER OPTIC CABLES. REFER TO SHEET T-100 FOR ADDITIONAL INFORMATION.
1U NETWORK ROUTER. PROVIDED AND INSTALLED BY OWNER.
1U, (48) PORT POE+ SWITCH FOR NCA NETWORK. SWITCH PROVIDED AND INSTALLED BY NCA. BASIS OF
DESIGN IS CISCO 9300.
2U HORIZONTAL CABLE MANAGEMENT. BASIS OF DESIGN CHATSWORTH 35431-X02-E.
2U, (48) PORT ANGLED PATCH PANEL.
2U SHELF FOR OWNER SUPPLIED AND INSTALLED NON-RACK MOUNTED EQUIPMENT.
PROVIDE (1) RACK MOUNTED PDU FOR CONNECTION OF RACK MOUNTED EQUIPMENT. PDU SHALL HAVE A MINIMUM OF (6) NEMA 5-20R OUTLETS AND BE RATED FOR 1.9KW MINIMUM. PDU BASIS OF DESIGN IS
CHATSWORTH 12820-707 20A. CONNECT EACH PDU TO 5-20R UPS OUTPUT.
(1) 5KVA RACK MOUNTED UPS FOR PDU POWER. BASIS OF DESIGN IS APC SURTD5000RMXLP3U.
(1) 2.2KVA RACK MOUNTED UPS FOR PDU POWER. BASIS OF DESIGN IS APC SMX2200RMLV2U WITH
EXTENDED RUNTIME BATTERY SMX120RMBP2U.
30A, 120V NEMA L5-30, RECEPTACLE MOUNTED BEHIND WALL MOUNTED CABINET FOR CONNECTION OF RACK MOUNTED UPS. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH RACK AND RACK
MOUNTED EQUIPMENT PRIOR TO CONSTRUCTION. CONNECT TO NEW 30A, 1-POLE BREAKER.
INSTALL (1) NEW 20A, 1-POLE BREAKER INTO EXISTING SPACE 40. NEW BREAKER TO MATCH EXISTING
BREAKERS IN MAKE, MODEL, AND AIC RATING.
PROVIDE (2) #6AWG CU, #6 AWG CU GROUND IN 1" CONDUIT TO 30A OUTLET INDICATED.
30A, 208V NEMA L14-30, RECEPTACLE MOUNTED BEHIND WALL MOUNTED CABINET FOR CONNECTION OF RACK MOUNTED UPS. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH RACK AND RACK
MOUNTED EQUIPMENT PRIOR TO CONSTRUCTION.
DOUBLE DUPLEX OUTLET LOCATED BEHIND WALL MOUNTED RACK FOR EQUIPMENT POWER
CONNECTIONS.
NN
0 4' 8' 16' 24'
1/8" = 1'-0"1/8" = 1'-0"1
ADMIN BLDG - BASEMENT PLAN - TELECOM - NEW WORK
1/8" = 1'-0"2
ADMIN BLDG - FIRST FLOOR PLAN - TELECOM - NEW WORK
1/8" = 1'-0"3
ADMIN BLDG - SECOND FLOOR PLAN - TELECOM - NEW WORK
1/8" = 1'-0"5
MAINTENANCE BLDG - FIRST FLOOR PLAN - TELECOM - NEW WORK
1" = 1'-0"
ADMINISTRATION BLDG RACK ELEVATION
1" = 1'-0"
MAINTENANCE BLDG RACK ELEVATION
N.T.S
PARTIAL ELECTRICAL ONE-LINE DIAGRAM
N.T.S.
ADMINISTRATION BLDG PANEL
A
N.T.S.
ADMINISTRATION BLDG PANEL ADMIN
B
4. CONTRACTOR SHALL PROVIDE CABLE PULL SCHEDULE FOR EACH SWITCH IN ALL RACKS AS PART OF
SHOP DRAWING SUBMITTAL.
5. PROVIDE SERVICE LOOP, (15') LOOPED IN FIGURE-8 PATTERN ABOVE CEILING OVER DATA CABINET, FOR ALL STRUCTURED CABLING PRIOR TO TERMINATION ON PATCH PANEL.
6. PATCH PANELS ARE TO BE COLOR CODED WITH THE DATA OUTLET PORT THAT IT IS ASSOCIATED WITH. REFER TO WALL MOUNTED OUTLET DETAIL ON THIS SHEET FOR ADDITIONAL INFORMATION.
138-001
PORT SEQUENCE
ROOM NUMBER
N.T.S.
MAINTENANCE BLDG PANEL M CKT 38/40
C
0 1' 2' 3'
1" = 1'-0"
LOAD CALCULATIONS PANEL 'M'
100A, 120V/240V, 1-PHASE, 3-WIRE
TOTAL REVISED LOAD:
(EXISTING LOAD + NEW LOAD)
NEW LOAD ADDED
(LIGHTS, RECP, MECH, ETC)
KVA
19.20
NO NET LOAD CHANGE ON EXISTING 100A, 120V/240V, 1-PHASE PANEL
'M'. NO NEW LOAD IS BEING ADDED UNDER THIS PROJECT. EXISTING
LOADS BEING MOVED TO DEDICATED CIRCUITS.
EXISTING LOAD ON PANEL 'M'
(BASED ON 80% OF BREAKER RATING)
19.20
Revisions Date
0.312Ø (54)
0.437Ø (8) CHATSWORTH "UL"
GROUND BAR LABEL
UL
1' 1/8" TYPICAL
PART NO. 40153-020
1"
1 1/2"
PROVIDE GROUNDING CONDUCTOR TO BUILDINGS STEEL PER TIA-607-D.
PROVIDE GROUNDING CONDUCTOR TO MAIN
SERVICE GROUND POINT PER TIA-607-D.
(APPROXIMATELY 125 FEET)
INSULATOR MOUNTING
BRACKET (TYP.) CPI 10622-000
INSULATOR (TYP)
GENERAL NOTES:
ALL HARDWARE (BOLTS, NUTS, WASHERS,ETC.) SHALL BE SOLID
COPPER OR BRONZE. COPPER PLATING SHALL NOT BE
ACCEPTABLE.
BUSBAR SHALL BE 1/4" THICK (MINIMUM).
1.
INCREASE LENGTH OF BUSBAR, FOR NUMBER OF
CONNECTIONS, AS REQUIRED TO MAINTAIN CORRECT
SPACING BETWEEN LUGS.
2.
3.
CPI 10622-012 OR EQUALPROVIDE # 6 COPPER CABLE 2-HOLE LUG
CLAMP FOR CABLE CONNECTION. (TYP)
2-HOLE LUG (TYP)
INSTALLATION NOTES:
SELECT BOLT LENGTH TO PROVIDE A MINIMUM OF TWO EXPOSED THREADS.A.
BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT.B.
APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN EXCESS COMPOUND.C.
USE SOLID COPPER WIRE AND MECHANICAL 2-HOLE LUG FOR ALL EXTERIOR GROUNDING.D.
#6 OR #2 GND TO GROUND BAR OF FLAT SURFACE.
#6 IS USED PRIMARILY AS CABINET TO BUS LINK.
#6 GRN OR #2 GRN 2 HOLE LUG
1/4-20 HEX BOLT
1/4" FLAT WASHER
1/4-20 HEX NUT
1/4" EXT. TOOTH LOCKWASHER
PRIMARY GROUND BAR/
METAL ENCLOSURE
MODULAR JACK WIRING (FRONT VIEW)
W-O O W-G BL W-BL G W-BR BR
PAIR3
PAIR2 PAIR1 PAIR4
JACK POSITIONS
TIA/EIA T568B
1 2 3 4 5 6 7 8
VERIFY CAMPUS STANDARD WITH CAMPUS IT REPRESENTATIVE PRIOR TO CONSTRUCTION.
FLOOR SLAB
1-1/2" CONDUIT TO ABOVE
CEILING
ACCESSIBLE CEILING
(ROUTE CABLE IN CONDUIT ABOVE HARD
CEILINGS.)
J-HOOKS
1-1/2" CONCEALED CONDUIT EMT
WALL
FACEPLATE
DEEP 4" SQUARE BOX WITH
SINGLE GANG STEEL PLASTER RING.
3'-5' MAX
CAT6A DATA CABLE
FLOOR
1-1/2" CONDUIT TO ABOVE
CEILING
ACCESSIBLE CEILING
(ROUTE CABLE IN CONDUIT ABOVE HARD
CEILINGS.)
J-HOOKS
1-1/2" SURFACE MOUNTED CONDUIT EMT. PAINTED TO MATCH WALL
WALL
FACEPLATE
DEEP 4" SQUARE BOX.
3'-5' MAX
CAT6A DATA CABLE
STUD TO STUD TELESCOPING BOX SUPPORT, B-LINE BB2 SERIES OR
EQUAL.
CONDUITS
RECEPTACLE
EQUIPMENT
GROUND
CONDUCTOR
GROUND SCREW
ON WIRING DEVICE.
PLASTER RINGNEUTRAL CONDUCTOR
HOT CONDUCTOR
METAL STUD
DRYWALL
PLASTER RING
RECEPTACLE
CONDUIT
4 SQUARE OUTLET BOX
OUTLET BOX SECURED TO BOX SUPPORT
WIRE NUT (TYP.)
GROUND SCREW IN OUTLET BOX.
PHASE A
PHASE B
PHASE C
NEUTRAL
GROUND
BLACK
RED
BLUE
WHITE
GREEN
VOLTAGE
208Y/120V
IDENTIFICATION OF GROUNDED CONUCTORS SHALL
BE PERFORMED BASED ON NEC ARTICLE 200.
NOTES:
1. #3/0 TO PRIMARY PROTECTOR.
2. #3/0 TO ELECTRICAL PANEL.
3. #3/0 TO EQUIPMENT RACKS/CABLE TRAY.
4. TWO-HOLE LUG, IRRIVERSABLE.
PBB: PRIMARY BONDING BUSBAR
SBB: SECONDARY BONDING BUSBAR
MSB: MAIN SWITCH BOARD
BBC: BACKBONE BONDING CONDUCTOR
GENERAL NOTES:
1. BONDING CONDUCTOR SHALL BE NO SMALLER THAN #2 CU.
2. ALL WORK SHALL COMPLY WITH NEC ARTICLE 250, UL 467, ANSI/TIA TIA-607-C, NECA/BICSI 607-2011.
3. PREPARE BUSBAR SURFACE AS DESCRIBED BELOW:
a. USE AN ABRASIVE PAD, REMOVE ANY DIRT, GREASE, OIL OR OXIDATION THAT IS PRESENT AT
THE SURFACE.
b. APPLY THIN COAT OF AN ANTIOXIDANT TO THE CONNECTION POINT ON THE BUSBAR.
c. USE STAINLESS STEEL OR SILICON BRONZE HARDWARE, TIGHTEN AND TORQUE TO THE
REQUIREMENTS OF THE HARDWARE MATERIAL, SIZE AND GRADE.
4. CONDUCTORS SHALL BE COPPER.
5. LUGS SHALL BE 2-HOLE TYPE WITH INSPECTION WINDOW, LONG BARREL, IRREVERSIBLE
(COMPRESSION OR EXOTHERMIC WELDING) AND MECHANICAL.
6. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL GROUNDING INFORMATION.
BBC LENGTH (FT)
BBC CONDUCTOR TABLE
<13
14-20
21-26
BBC SIZE (AWG)
27-33
34-41
42-52
1/0
53-66
67-84
85-105
2/0
3/0
4/0
106-125
126-150
151-175
250 KCMIL
300 KCMIL
350 KCMIL
176-250
251-300
>301
500 KCMIL
600 KCMIL
750 KCMIL
X
ELECTRICAL ROOM
GROUND BUS
MDP
BBC CONDUCTOR PER TABLE
DATA ROOM
PBB3
24120V (BASED ON 1500W LOAD) MIN. CONDUCTOR SIZE
CIRCUIT LENGTH INCREASE FOR VOLTAGE DROP
0 FT - 70 FT
71 FT - 115 FT
116 FT - 180 FT
#12 AWG
#10 AWG
#8 AWG
181 FEET AND LONGER: SUBMIT WIRE SIZE TO
ENGINEER OF RECORD FOR WRITTEN APPROVAL.
277V (BASED ON 4155W LOAD) MIN. CONDUCTOR SIZE
CIRCUIT LENGTH INCREASE FOR VOLTAGE DROP
0 FT - 70 FT
71 FT - 115 FT
116 FT - 180 FT
#12 AWG
#10 AWG
#8 AWG
CONDUCTORS:
1. ALL WIRE SHALL BE SIZED AS SHOWN ON THE DRAWINGS.
IF NO SIZE IS SHOWN, THEN WIRE SHALL BE #12 AWG,
EXCEPT AS MODIFIED FOR VOLTAGE DROP BY THE TABLE
BELOW. REFER TO BRANCH CIRCUIT VOLTAGE DROP
TABLES BELOW. BRANCH CIRCUIT WIRING SHALL BE SIZED
TO LIMIT THE VOLTAGE DROP TO 3% OF NOMINAL VOLTAGE
OR LESS.
IN
T
E
GR I TY FEDE
R
A L
S ERV I C E S
INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
NCA DESIGN
AND
CONSTRUCTION
SERVICE
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FULLY SPRINKLERED
Above Group, Inc.
(321) 345-9026
CAMP BUTLER NATIONAL CEMETERY
BID DOCUMENTS SUBMISSION
A u to d e s k D o c s /0
C a m p
B u tl e r
IT
U p g ra d e s /0
C a m p
B u tl e r
IT
U g ra d e s
R
T
.r v t
/2
/2
:4
:2
P
M
ET501
ELECTRICAL/TELECOM DETAILS REPAIR ROADS, PARKING LOTS, CURB &
GUTTER;
CORRECT IT DEFICIENCIES
SANGAMON COUNTY, ILLINOIS
806CM3029
JUNE 28, 2023 BMS CVM
BID DOCUMENTS
N.T.S.1
GROUND BUS BAR
N.T.S.2
GROUND BAR 2-HOLE LUG TERMINATION
N.T.S.
MODULAR JACK WIRING DETAIL
N.T.S.4
TYPICAL FLUSH OUTLET MOUNTING
N.T.S.
TYPICAL SURFACE OUTLET MOUNTING
N.T.S.
TYPICAL RECEPTACLE MOUNTING DETAIL
6N.T.S.
WIRE COLOR TABLE
BRANCH CIRCUIT NOTES:
TOTAL EST. DEMAND... 15 A
TOTAL CONNECTED... 15 A
TOTAL EST. DEMAND: 5360 VA
TOTAL CONNECTED LOAD: 5360 VA
Receptacle 5360 VA 100.00% 5360 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
LEGEND:
TOTAL... 17 A 14 A 14 A
TOTAL... 2027 VA 1667 VA 1667 VA
41 EXIST SMOKE DETECTORS 20 A 1 0 VA 0 VA 42
39 Spare 20 A 1 0 VA 0 VA
2 30 A EXIST INTERMENT SHELTER
37 EXIST LOADS (SPLIT 20A BREAKERS) 20 A 1 0 VA 0 VA 1 20 A EXIST LOAD 38
35 0 VA 0 VA 36
EXIST MINI SPLIT 40 A 2
0 VA 0 VA
2 40 A EXIST BASMENT AH
31 EXIST LOAD 20 A 1 0 VA 0 VA 32
29 EXIST LOAD 20 A 1 0 VA 0 VA
2 20 A EXIST LOAD
27 EXIST SP 20 A 1 0 VA 0 VA 28
25 EXIST OFFICE RECPT 20 A 1 0 VA 0 VA
2 20 A EXIST ROOF A/C
23 EXISTSTOVE 20 A 1 0 VA 0 VA 24
21 EXIST STOVE 20 A 1 0 VA 0 VA
2 20 A EXIST FLAG POLE
19 EXIST DISPOSAL/KITCHEN RECPT 20 A 1 0 VA 0 VA 1 20 A EXIST OFFICE FLR RECPT 20
17 EXIST OFFICE HEAT/AC RECPT 20 A 1 0 VA 0 VA 1 20 A EXIST COMP RM LTS 18
15 EXIST OFFICE HEAT/AC RECPT 20 A 1 0 VA 0 VA 1 20 A EXIST LTS 16
13 EXIST SP 20 A 1 0 VA 0 VA 1 20 A EXIST LTS 14
11 EXIST KITCHEN/RESTROOM RECPTS 20 A 1 0 VA 0 VA 1 20 A EXIST AC 12
9 EXIST BOILER 20 A 1 0 VA 0 VA 1 20 A EXIST AC 10
7 EXIST OFFICE RECPTS 20 A 1 0 VA 0 VA 1 20 A EXIST REFRIG/KITCHEN RECPTS 8
5 1667... 0 VA 1 20 A EXIST 2ND FLR 6
3 1667... 0 VA 1 20 A EXIST 2ND FLR 4
NEW PANEL B 75 A 3
2027... 0 VA 1 20 A EXIST LTS 2
CKT CIRCUIT DESCRIPTION
NOTE
S TRIP POLES A B C POLES TRIP
NOTE
S CIRCUIT DESCRIPTION CKT
EXISTING SQUARE-D NQOD PANEL
GENERAL NOTES:
ENCLOSURE: Type 1 SERVICE ENTRANCE: YES
MOUNTING: Surface WIRES: 4 MAINS RATING: 200 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: MCB
LOCATION: BASEMENT VOLTS: 120/208 Wye A.I.C. RATING: 10,000
BRANCH PANEL: ADMIN
BRANCH CIRCUIT NOTES:
TOTAL EST. DEMAND... 15 A
TOTAL CONNECTED... 15 A
TOTAL EST. DEMAND: 5360 VA
TOTAL CONNECTED LOAD: 5360 VA
Receptacle 5360 VA 100.00% 5360 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
LEGEND:
TOTAL... 17 A 14 A 14 A
TOTAL... 2027 VA 1667 VA 1667 VA
29 SPARE 20 A 1 0 VA 0 VA 30
27 SPARE 20 A 1 0 VA 0 VA 28
25 SPARE 20 A 1 0 VA 0 VA
3 30 A SPD
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPACE -- 1 -- -- 1 -- SPACE 12
9 SPACE -- 1 -- -- 1 -- SPACE 10
7 SPACE -- 1 -- 1667... 8
5 SPACE -- 1 -- 1667... 6
3 RELOCATED PHONE 20 A 1 0 VA 1667...
3 30 A NEW NEMA L14-30 RECEPT AT RACK
1 RELOCATED LTS 20 A 1 0 VA 360 VA 1 20 A NEW QUAD RECPT AT RACK 2
CKT CIRCUIT DESCRIPTION
NOTE
S TRIP POLES A B C POLES TRIP
NOTE
S CIRCUIT DESCRIPTION CKT
NEW PANEL
GENERAL NOTES:
ENCLOSURE: Type 1 SERVICE ENTRANCE: NO
MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: ADMIN PHASES: 3 MAINS TYPE: MLO
LOCATION: BASEMENT VOLTS: 120/208 Wye A.I.C. RATING: 10,000
BRANCH PANEL: AB
N.T.S.
TELECOM GROUNDING RISER DIAGRAM
LOAD CALCULATIONS PANEL 'ADMIN'
200A, 208Y/120V, 3-PHASE, 4-WIRE
TOTAL REVISED LOAD:
(EXISTING LOAD + NEW LOAD)
NEW LOAD ADDED
(LIGHTS, RECP, MECH, ETC)
KVA
24.02
NO NET LOAD CHANGE ON EXISTING 200A, 208Y/120V, 3-PHASE PANEL
'ADMIN'. NO NEW LOAD IS BEING ADDED UNDER THIS PROJECT.
EXISTING LOAD BEING MOVED TO DEDICATED CIRCUITS.
EXISTING LOAD ON PANEL 'ADMIN'
(BASED ON 80% OF BREAKER RATING)
24.02
N.T.S.
CONDUCTORS DETAIL
Revisions Date
| Camp Butler IT Ugrades - ET - Stamped |
| Sheets |
| ET102 - TELECOM FLOOR PLANS - NEW |
| ET501 - ELECTRICAL/TELECOM DETAILS |
File details come from the government source that posted it. Updated .