S02_Attachment - CBNC-806CM3029-BD-PLANS_Part3.pdf

PDF 6 MB Posted

Attached to
PN: 806CM3029 Camp Butler Road Repairs and Correct IT Deficiencies
Solicitation number
36C78623B0036
Issued by

About this file

This package includes construction drawings and details for telecommunications and electrical system upgrades at the Camp Butler National Cemetery. The drawings call for installing new telecom rooms in the Administration Building basement, first, and second floors, as well as in the Maintenance Building. Equipment to be provided and installed includes wall-mounted equipment racks, fiber optic and copper cable infrastructure, patch panels, switches, UPS backup power systems, and related hardware. Grounding and bonding details are shown. Electrical work includes upgrading panelboards in the Administration and Maintenance Buildings to support the new telecom loads. Conduit and wiring routes are provided for connecting the new equipment to the upgraded power sources.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

ADMIN

ET102

AB

A

TE102

AB-4,6,8 AB-2

24 5

1 +74"

2 2

M

2 1

+84"

+36"

ET102

M-38M-4025 21 23

4 22

C

TE102

9 11

ADMIN

AB

ADMINISTRATION BUILDING

EXISTING

NEW

PROVIDE (4) #4AWG CU, #8 AWG CU

GROUND IN 1-1/2" CONDUIT.

SPD

4 23

IN

T

E

GR I TY FEDE

R

A L

S ERV I C E S

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

NCA DESIGN

AND

CONSTRUCTION

SERVICE

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FULLY SPRINKLERED

Above Group, Inc.

(321) 345-9026

CAMP BUTLER NATIONAL CEMETERY

BID DOCUMENTS SUBMISSION

A u to d e s k D o c s /0

C a m p

B u tl e r

IT

U p g ra d e s /0

C a m p

B u tl e r

IT

U g ra d e s

R

T

.r v t

/2

/2

:4

:1

P

M

ET102

TELECOM FLOOR PLANS - NEW REPAIR ROADS, PARKING LOTS, CURB &

GUTTER;

CORRECT IT DEFICIENCIES

SANGAMON COUNTY, ILLINOIS

806CM3029

JUNE 28, 2023 BMS CVM

BID DOCUMENTS

CODED NOTES:

DRAWING NOTES:

1. LABELING STANDARDS SHALL BE FOLLOWED FOR TR NUMBER, RACK NUMBER, PATCH PANEL (A-Z), AND PORT NUMBER. EXAMPLE: TR1-1A-01.

2. 8P8C CONNECTION PORTS IN TCO WALL PLATES SHALL BE COLOR CODED BASED ON TYPE. REFER

TO SHEET T-001 FOR CABLE COLOR CHART. TCO WALL PLATE PORT AND CABLE COLOR SHALL

MATCH ASSOCIATED PATCH PANEL COLOR.

3. LABEL ALL CABLES AND PORTS ON BOTH ENDS WITH COMPUTER GENERATED, SELF-LAMINATING, ADHESIVE, WRAPAROUND LABELS WITH THE TCO ROOM NUMBER (101, 102...), AND PORT SEQUENCE

NUMBER (001, 002...).

INSTALL NEW PANEL BOARD ON AVAILABLE WALL SPACE ADJACENT TO EXITING PANEL. COORDINATE

EXACT LOCATION IN FIELD WITH EXISTING CONDITIONS.

RELOCATE INDICATED LOADS TO NEW PANEL "AB". INSTALL NEW 75A, 3-POLE BREAKER INTO SPACE MADE AVAILABLE BY RELOCATED LOADS. NEW BREAKER TO MATCH EXISTING BREAKERS IN MAKE, MODEL AND AIC VALUE.

PROVIDE CONDUIT AND CABLING AS REQUIRED FOR RELOCATION OF INDICATED EXISTING LOADS TO

NEW PANEL.

INSTALL NEW 30A, 1-POLE BREAKER INTO AVAILABLE SPACE 38. NEW BREAKER TO MATCH EXISTING

BREAKERS IN MAKE, MODEL AND AIC VALUE.

PROVIDE (3) #10AWG CU, #10 AWG CU GROUND IN 1" CONDUIT TO 30A OUTLET INDICATED.

CONNECT TO NEW 20A, 1-POLE BREAKER IN PANELBOARD "M" AT POSITION 40. PROVIDE (2) #10AWG CU, #

10AWG CU GROUND IN 3/4" CONDUIT.

COORDINATE EXACT LOCATION OF NETWORK EQUIPMENT AND BACK BOARD WITH NCA IT PERSONNEL

PRIOR TO CONSTRUCTION.

PROVIDE TIA APPROVED, FIRE RATED, AC GRADE PLYWOOD BACKBOARD 4'x4'x1/2", OR APPROVED FIRE PLYWOOD. PAINT ON ALL SIDES AND WITHIN CUTOUT AREAS WITH AT LEAST (2) COATS OF FIRE RETARDANT, LIGHT COLORED PAINT. LOCATE BACKBOARD 12" COUNTER, INSTALL SO 'A' SIDE OF

PLYWOOD IS EXPOSED.

PROVIDE 48"H X 24"W X 30"D WALL MOUNTED CABINET WITH SWING-OUT REAR ACCESS, AND LOCKABLE FRONT DOOR. BASIS OF DESIGN IS CHATSWORTH CUBE-IT WALL-MOUNT CABINET, GEN 3, 26U, #12-24

TAPPED RAILS, TEMPERED GLASS DOOR, GLACIER WHITE - 12419-E48 CUBE-IT OR EQUAL.

TELECOM MAIN GROUND BUSBAR. ALL VERTICAL AND HORIZONTAL RACKS AND CABLE TRAYS SHALL BE BONDED TO BUSBAR. REFER TO GROUND BUS BAR DETAIL ON THIS SHEET FOR MORE INFORMATION.

VERTICAL WIRE MANAGERS IN CABINET. BASIS OF DESIGN IS CHATSWORTH 40970-711.

1U FIBER OPTIC SHELF WITH (2) 12 FIBER LC CONNECTOR CASSETTES FOR TERMINATION OF INCOMING

FIBER OPTIC CABLES. REFER TO SHEET T-100 FOR ADDITIONAL INFORMATION.

1U NETWORK ROUTER. PROVIDED AND INSTALLED BY OWNER.

1U, (48) PORT POE+ SWITCH FOR NCA NETWORK. SWITCH PROVIDED AND INSTALLED BY NCA. BASIS OF

DESIGN IS CISCO 9300.

2U HORIZONTAL CABLE MANAGEMENT. BASIS OF DESIGN CHATSWORTH 35431-X02-E.

2U, (48) PORT ANGLED PATCH PANEL.

2U SHELF FOR OWNER SUPPLIED AND INSTALLED NON-RACK MOUNTED EQUIPMENT.

PROVIDE (1) RACK MOUNTED PDU FOR CONNECTION OF RACK MOUNTED EQUIPMENT. PDU SHALL HAVE A MINIMUM OF (6) NEMA 5-20R OUTLETS AND BE RATED FOR 1.9KW MINIMUM. PDU BASIS OF DESIGN IS

CHATSWORTH 12820-707 20A. CONNECT EACH PDU TO 5-20R UPS OUTPUT.

(1) 5KVA RACK MOUNTED UPS FOR PDU POWER. BASIS OF DESIGN IS APC SURTD5000RMXLP3U.

(1) 2.2KVA RACK MOUNTED UPS FOR PDU POWER. BASIS OF DESIGN IS APC SMX2200RMLV2U WITH

EXTENDED RUNTIME BATTERY SMX120RMBP2U.

30A, 120V NEMA L5-30, RECEPTACLE MOUNTED BEHIND WALL MOUNTED CABINET FOR CONNECTION OF RACK MOUNTED UPS. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH RACK AND RACK

MOUNTED EQUIPMENT PRIOR TO CONSTRUCTION. CONNECT TO NEW 30A, 1-POLE BREAKER.

INSTALL (1) NEW 20A, 1-POLE BREAKER INTO EXISTING SPACE 40. NEW BREAKER TO MATCH EXISTING

BREAKERS IN MAKE, MODEL, AND AIC RATING.

PROVIDE (2) #6AWG CU, #6 AWG CU GROUND IN 1" CONDUIT TO 30A OUTLET INDICATED.

30A, 208V NEMA L14-30, RECEPTACLE MOUNTED BEHIND WALL MOUNTED CABINET FOR CONNECTION OF RACK MOUNTED UPS. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH RACK AND RACK

MOUNTED EQUIPMENT PRIOR TO CONSTRUCTION.

DOUBLE DUPLEX OUTLET LOCATED BEHIND WALL MOUNTED RACK FOR EQUIPMENT POWER

CONNECTIONS.

NN

0 4' 8' 16' 24'

1/8" = 1'-0"1/8" = 1'-0"1

ADMIN BLDG - BASEMENT PLAN - TELECOM - NEW WORK

1/8" = 1'-0"2

ADMIN BLDG - FIRST FLOOR PLAN - TELECOM - NEW WORK

1/8" = 1'-0"3

ADMIN BLDG - SECOND FLOOR PLAN - TELECOM - NEW WORK

1/8" = 1'-0"5

MAINTENANCE BLDG - FIRST FLOOR PLAN - TELECOM - NEW WORK

1" = 1'-0"

ADMINISTRATION BLDG RACK ELEVATION

1" = 1'-0"

MAINTENANCE BLDG RACK ELEVATION

N.T.S

PARTIAL ELECTRICAL ONE-LINE DIAGRAM

N.T.S.

ADMINISTRATION BLDG PANEL

A

N.T.S.

ADMINISTRATION BLDG PANEL ADMIN

B

4. CONTRACTOR SHALL PROVIDE CABLE PULL SCHEDULE FOR EACH SWITCH IN ALL RACKS AS PART OF

SHOP DRAWING SUBMITTAL.

5. PROVIDE SERVICE LOOP, (15') LOOPED IN FIGURE-8 PATTERN ABOVE CEILING OVER DATA CABINET, FOR ALL STRUCTURED CABLING PRIOR TO TERMINATION ON PATCH PANEL.

6. PATCH PANELS ARE TO BE COLOR CODED WITH THE DATA OUTLET PORT THAT IT IS ASSOCIATED WITH. REFER TO WALL MOUNTED OUTLET DETAIL ON THIS SHEET FOR ADDITIONAL INFORMATION.

138-001

PORT SEQUENCE

ROOM NUMBER

N.T.S.

MAINTENANCE BLDG PANEL M CKT 38/40

C

0 1' 2' 3'

1" = 1'-0"

LOAD CALCULATIONS PANEL 'M'

100A, 120V/240V, 1-PHASE, 3-WIRE

TOTAL REVISED LOAD:

(EXISTING LOAD + NEW LOAD)

NEW LOAD ADDED

(LIGHTS, RECP, MECH, ETC)

KVA

19.20

NO NET LOAD CHANGE ON EXISTING 100A, 120V/240V, 1-PHASE PANEL

'M'. NO NEW LOAD IS BEING ADDED UNDER THIS PROJECT. EXISTING

LOADS BEING MOVED TO DEDICATED CIRCUITS.

EXISTING LOAD ON PANEL 'M'

(BASED ON 80% OF BREAKER RATING)

19.20

Revisions Date

0.312Ø (54)

0.437Ø (8) CHATSWORTH "UL"

GROUND BAR LABEL

UL

1' 1/8" TYPICAL

PART NO. 40153-020

1"

1 1/2"

PROVIDE GROUNDING CONDUCTOR TO BUILDINGS STEEL PER TIA-607-D.

PROVIDE GROUNDING CONDUCTOR TO MAIN

SERVICE GROUND POINT PER TIA-607-D.

(APPROXIMATELY 125 FEET)

INSULATOR MOUNTING

BRACKET (TYP.) CPI 10622-000

INSULATOR (TYP)

GENERAL NOTES:

ALL HARDWARE (BOLTS, NUTS, WASHERS,ETC.) SHALL BE SOLID

COPPER OR BRONZE. COPPER PLATING SHALL NOT BE

ACCEPTABLE.

BUSBAR SHALL BE 1/4" THICK (MINIMUM).

1.

INCREASE LENGTH OF BUSBAR, FOR NUMBER OF

CONNECTIONS, AS REQUIRED TO MAINTAIN CORRECT

SPACING BETWEEN LUGS.

2.

3.

CPI 10622-012 OR EQUALPROVIDE # 6 COPPER CABLE 2-HOLE LUG

CLAMP FOR CABLE CONNECTION. (TYP)

2-HOLE LUG (TYP)

INSTALLATION NOTES:

SELECT BOLT LENGTH TO PROVIDE A MINIMUM OF TWO EXPOSED THREADS.A.

BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT.B.

APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN EXCESS COMPOUND.C.

USE SOLID COPPER WIRE AND MECHANICAL 2-HOLE LUG FOR ALL EXTERIOR GROUNDING.D.

#6 OR #2 GND TO GROUND BAR OF FLAT SURFACE.

#6 IS USED PRIMARILY AS CABINET TO BUS LINK.

#6 GRN OR #2 GRN 2 HOLE LUG

1/4-20 HEX BOLT

1/4" FLAT WASHER

1/4-20 HEX NUT

1/4" EXT. TOOTH LOCKWASHER

PRIMARY GROUND BAR/

METAL ENCLOSURE

MODULAR JACK WIRING (FRONT VIEW)

W-O O W-G BL W-BL G W-BR BR

PAIR3

PAIR2 PAIR1 PAIR4

JACK POSITIONS

TIA/EIA T568B

1 2 3 4 5 6 7 8

VERIFY CAMPUS STANDARD WITH CAMPUS IT REPRESENTATIVE PRIOR TO CONSTRUCTION.

FLOOR SLAB

1-1/2" CONDUIT TO ABOVE

CEILING

ACCESSIBLE CEILING

(ROUTE CABLE IN CONDUIT ABOVE HARD

CEILINGS.)

J-HOOKS

1-1/2" CONCEALED CONDUIT EMT

WALL

FACEPLATE

DEEP 4" SQUARE BOX WITH

SINGLE GANG STEEL PLASTER RING.

3'-5' MAX

CAT6A DATA CABLE

FLOOR

1-1/2" CONDUIT TO ABOVE

CEILING

ACCESSIBLE CEILING

(ROUTE CABLE IN CONDUIT ABOVE HARD

CEILINGS.)

J-HOOKS

1-1/2" SURFACE MOUNTED CONDUIT EMT. PAINTED TO MATCH WALL

WALL

FACEPLATE

DEEP 4" SQUARE BOX.

3'-5' MAX

CAT6A DATA CABLE

STUD TO STUD TELESCOPING BOX SUPPORT, B-LINE BB2 SERIES OR

EQUAL.

CONDUITS

RECEPTACLE

EQUIPMENT

GROUND

CONDUCTOR

GROUND SCREW

ON WIRING DEVICE.

PLASTER RINGNEUTRAL CONDUCTOR

HOT CONDUCTOR

METAL STUD

DRYWALL

PLASTER RING

RECEPTACLE

CONDUIT

4 SQUARE OUTLET BOX

OUTLET BOX SECURED TO BOX SUPPORT

WIRE NUT (TYP.)

GROUND SCREW IN OUTLET BOX.

PHASE A

PHASE B

PHASE C

NEUTRAL

GROUND

BLACK

RED

BLUE

WHITE

GREEN

VOLTAGE

208Y/120V

IDENTIFICATION OF GROUNDED CONUCTORS SHALL

BE PERFORMED BASED ON NEC ARTICLE 200.

NOTES:

1. #3/0 TO PRIMARY PROTECTOR.

2. #3/0 TO ELECTRICAL PANEL.

3. #3/0 TO EQUIPMENT RACKS/CABLE TRAY.

4. TWO-HOLE LUG, IRRIVERSABLE.

PBB: PRIMARY BONDING BUSBAR

SBB: SECONDARY BONDING BUSBAR

MSB: MAIN SWITCH BOARD

BBC: BACKBONE BONDING CONDUCTOR

GENERAL NOTES:

1. BONDING CONDUCTOR SHALL BE NO SMALLER THAN #2 CU.

2. ALL WORK SHALL COMPLY WITH NEC ARTICLE 250, UL 467, ANSI/TIA TIA-607-C, NECA/BICSI 607-2011.

3. PREPARE BUSBAR SURFACE AS DESCRIBED BELOW:

a. USE AN ABRASIVE PAD, REMOVE ANY DIRT, GREASE, OIL OR OXIDATION THAT IS PRESENT AT

THE SURFACE.

b. APPLY THIN COAT OF AN ANTIOXIDANT TO THE CONNECTION POINT ON THE BUSBAR.

c. USE STAINLESS STEEL OR SILICON BRONZE HARDWARE, TIGHTEN AND TORQUE TO THE

REQUIREMENTS OF THE HARDWARE MATERIAL, SIZE AND GRADE.

4. CONDUCTORS SHALL BE COPPER.

5. LUGS SHALL BE 2-HOLE TYPE WITH INSPECTION WINDOW, LONG BARREL, IRREVERSIBLE

(COMPRESSION OR EXOTHERMIC WELDING) AND MECHANICAL.

6. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL GROUNDING INFORMATION.

BBC LENGTH (FT)

BBC CONDUCTOR TABLE

<13

14-20

21-26

BBC SIZE (AWG)

27-33

34-41

42-52

1/0

53-66

67-84

85-105

2/0

3/0

4/0

106-125

126-150

151-175

250 KCMIL

300 KCMIL

350 KCMIL

176-250

251-300

>301

500 KCMIL

600 KCMIL

750 KCMIL

X

ELECTRICAL ROOM

GROUND BUS

MDP

BBC CONDUCTOR PER TABLE

DATA ROOM

PBB3

24120V (BASED ON 1500W LOAD) MIN. CONDUCTOR SIZE

CIRCUIT LENGTH INCREASE FOR VOLTAGE DROP

0 FT - 70 FT

71 FT - 115 FT

116 FT - 180 FT

#12 AWG

#10 AWG

#8 AWG

181 FEET AND LONGER: SUBMIT WIRE SIZE TO

ENGINEER OF RECORD FOR WRITTEN APPROVAL.

277V (BASED ON 4155W LOAD) MIN. CONDUCTOR SIZE

CIRCUIT LENGTH INCREASE FOR VOLTAGE DROP

0 FT - 70 FT

71 FT - 115 FT

116 FT - 180 FT

#12 AWG

#10 AWG

#8 AWG

CONDUCTORS:

1. ALL WIRE SHALL BE SIZED AS SHOWN ON THE DRAWINGS.

IF NO SIZE IS SHOWN, THEN WIRE SHALL BE #12 AWG,

EXCEPT AS MODIFIED FOR VOLTAGE DROP BY THE TABLE

BELOW. REFER TO BRANCH CIRCUIT VOLTAGE DROP

TABLES BELOW. BRANCH CIRCUIT WIRING SHALL BE SIZED

TO LIMIT THE VOLTAGE DROP TO 3% OF NOMINAL VOLTAGE

OR LESS.

IN

T

E

GR I TY FEDE

R

A L

S ERV I C E S

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

NCA DESIGN

AND

CONSTRUCTION

SERVICE

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FULLY SPRINKLERED

Above Group, Inc.

(321) 345-9026

CAMP BUTLER NATIONAL CEMETERY

BID DOCUMENTS SUBMISSION

A u to d e s k D o c s /0

C a m p

B u tl e r

IT

U p g ra d e s /0

C a m p

B u tl e r

IT

U g ra d e s

R

T

.r v t

/2

/2

:4

:2

P

M

ET501

ELECTRICAL/TELECOM DETAILS REPAIR ROADS, PARKING LOTS, CURB &

GUTTER;

CORRECT IT DEFICIENCIES

SANGAMON COUNTY, ILLINOIS

806CM3029

JUNE 28, 2023 BMS CVM

BID DOCUMENTS

N.T.S.1

GROUND BUS BAR

N.T.S.2

GROUND BAR 2-HOLE LUG TERMINATION

N.T.S.

MODULAR JACK WIRING DETAIL

N.T.S.4

TYPICAL FLUSH OUTLET MOUNTING

N.T.S.

TYPICAL SURFACE OUTLET MOUNTING

N.T.S.

TYPICAL RECEPTACLE MOUNTING DETAIL

6N.T.S.

WIRE COLOR TABLE

BRANCH CIRCUIT NOTES:

TOTAL EST. DEMAND... 15 A

TOTAL CONNECTED... 15 A

TOTAL EST. DEMAND: 5360 VA

TOTAL CONNECTED LOAD: 5360 VA

Receptacle 5360 VA 100.00% 5360 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

LEGEND:

TOTAL... 17 A 14 A 14 A

TOTAL... 2027 VA 1667 VA 1667 VA

41 EXIST SMOKE DETECTORS 20 A 1 0 VA 0 VA 42

39 Spare 20 A 1 0 VA 0 VA

2 30 A EXIST INTERMENT SHELTER

37 EXIST LOADS (SPLIT 20A BREAKERS) 20 A 1 0 VA 0 VA 1 20 A EXIST LOAD 38

35 0 VA 0 VA 36

EXIST MINI SPLIT 40 A 2

0 VA 0 VA

2 40 A EXIST BASMENT AH

31 EXIST LOAD 20 A 1 0 VA 0 VA 32

29 EXIST LOAD 20 A 1 0 VA 0 VA

2 20 A EXIST LOAD

27 EXIST SP 20 A 1 0 VA 0 VA 28

25 EXIST OFFICE RECPT 20 A 1 0 VA 0 VA

2 20 A EXIST ROOF A/C

23 EXISTSTOVE 20 A 1 0 VA 0 VA 24

21 EXIST STOVE 20 A 1 0 VA 0 VA

2 20 A EXIST FLAG POLE

19 EXIST DISPOSAL/KITCHEN RECPT 20 A 1 0 VA 0 VA 1 20 A EXIST OFFICE FLR RECPT 20

17 EXIST OFFICE HEAT/AC RECPT 20 A 1 0 VA 0 VA 1 20 A EXIST COMP RM LTS 18

15 EXIST OFFICE HEAT/AC RECPT 20 A 1 0 VA 0 VA 1 20 A EXIST LTS 16

13 EXIST SP 20 A 1 0 VA 0 VA 1 20 A EXIST LTS 14

11 EXIST KITCHEN/RESTROOM RECPTS 20 A 1 0 VA 0 VA 1 20 A EXIST AC 12

9 EXIST BOILER 20 A 1 0 VA 0 VA 1 20 A EXIST AC 10

7 EXIST OFFICE RECPTS 20 A 1 0 VA 0 VA 1 20 A EXIST REFRIG/KITCHEN RECPTS 8

5 1667... 0 VA 1 20 A EXIST 2ND FLR 6

3 1667... 0 VA 1 20 A EXIST 2ND FLR 4

NEW PANEL B 75 A 3

2027... 0 VA 1 20 A EXIST LTS 2

CKT CIRCUIT DESCRIPTION

NOTE

S TRIP POLES A B C POLES TRIP

NOTE

S CIRCUIT DESCRIPTION CKT

EXISTING SQUARE-D NQOD PANEL

GENERAL NOTES:

ENCLOSURE: Type 1 SERVICE ENTRANCE: YES

MOUNTING: Surface WIRES: 4 MAINS RATING: 200 A

SUPPLY FROM: PHASES: 3 MAINS TYPE: MCB

LOCATION: BASEMENT VOLTS: 120/208 Wye A.I.C. RATING: 10,000

BRANCH PANEL: ADMIN

BRANCH CIRCUIT NOTES:

TOTAL EST. DEMAND... 15 A

TOTAL CONNECTED... 15 A

TOTAL EST. DEMAND: 5360 VA

TOTAL CONNECTED LOAD: 5360 VA

Receptacle 5360 VA 100.00% 5360 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

LEGEND:

TOTAL... 17 A 14 A 14 A

TOTAL... 2027 VA 1667 VA 1667 VA

29 SPARE 20 A 1 0 VA 0 VA 30

27 SPARE 20 A 1 0 VA 0 VA 28

25 SPARE 20 A 1 0 VA 0 VA

3 30 A SPD

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPACE -- 1 -- -- 1 -- SPACE 18

15 SPACE -- 1 -- -- 1 -- SPACE 16

13 SPACE -- 1 -- -- 1 -- SPACE 14

11 SPACE -- 1 -- -- 1 -- SPACE 12

9 SPACE -- 1 -- -- 1 -- SPACE 10

7 SPACE -- 1 -- 1667... 8

5 SPACE -- 1 -- 1667... 6

3 RELOCATED PHONE 20 A 1 0 VA 1667...

3 30 A NEW NEMA L14-30 RECEPT AT RACK

1 RELOCATED LTS 20 A 1 0 VA 360 VA 1 20 A NEW QUAD RECPT AT RACK 2

CKT CIRCUIT DESCRIPTION

NOTE

S TRIP POLES A B C POLES TRIP

NOTE

S CIRCUIT DESCRIPTION CKT

NEW PANEL

GENERAL NOTES:

ENCLOSURE: Type 1 SERVICE ENTRANCE: NO

MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: ADMIN PHASES: 3 MAINS TYPE: MLO

LOCATION: BASEMENT VOLTS: 120/208 Wye A.I.C. RATING: 10,000

BRANCH PANEL: AB

N.T.S.

TELECOM GROUNDING RISER DIAGRAM

LOAD CALCULATIONS PANEL 'ADMIN'

200A, 208Y/120V, 3-PHASE, 4-WIRE

TOTAL REVISED LOAD:

(EXISTING LOAD + NEW LOAD)

NEW LOAD ADDED

(LIGHTS, RECP, MECH, ETC)

KVA

24.02

NO NET LOAD CHANGE ON EXISTING 200A, 208Y/120V, 3-PHASE PANEL

'ADMIN'. NO NEW LOAD IS BEING ADDED UNDER THIS PROJECT.

EXISTING LOAD BEING MOVED TO DEDICATED CIRCUITS.

EXISTING LOAD ON PANEL 'ADMIN'

(BASED ON 80% OF BREAKER RATING)

24.02

N.T.S.