S02-ATTACHMENT B- Cleaver Brooks Datasheet.pdf

PDF 1 MB Posted

Attached to
J045--Maintenance, Inspection and Calibration of Boiler system for the Edward Hines JR VAMC located in Chicago IL
Solicitation number
36C25226Q0400
Issued by

About this file

This file is a transmittal of pre-testing certificates and data for boiler plant demonstrations and tests, submitted as part of the Hines VA Hospital New Boiler Plant federal construction contract (W912QR-16-C-0020) with the U.S. Army Corps of Engineers Chicago Project Office. The transmittal was submitted on July 8, 2019, by Walsh Federal JV (mechanical contractor Mechanical, Inc.) to document pre-commissioning testing of four boiler units at the facility.

The documentation includes comprehensive boiler/burner performance data sheets dated November 2018 for four SP-NB-200D-55 boiler units equipped with NATCOM P-42-LOG-17-0812 burners, tested under natural gas and fuel oil conditions across multiple firing rates (0%, 50%, and 100%). Data captured includes steam flow rates, pressure readings, combustion efficiency metrics (oxygen levels, carbon monoxide, NOx emissions), flue gas outlet temperatures, economizer outlet temperatures, flame characteristics, and air flow measurements. Supporting documentation includes checklists for deaerator tank safety systems (high water alarm, low water alarm, overflow drain system, and safety valve testing), all verified during October-November 2018 commissioning with setpoints adjusted to comply with Safety Device Test Manual Version 3 specifications. The contractor noted in their response to initial comments that actual boiler outlet temperatures exceeded predicted theoretical temperatures at 100% fire rate due to accurate temperature sensing, and that economizer thermal exchange performance was proportionate to inlet temperature and exceeded minimum requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL SAMPLES, OR

MANUFACTURER'S CERTIFICATES OF COMPLIANCE

For use of this form, see ER 415-1-10; the proponent agency is CECW-CE.

SECTION I - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)

DATE TRANSMITTAL NO.

TO: FROM: CONTRACT NO. CHECK ONE:

THIS IS A NEW TRANSMITTAL

THIS IS A RESUBMITTAL OF

TRANSMITTAL ___________

SPECIFICATION SEC. NO. (Cover only one section with each transmittal) PROJECT TITLE AND LOCATION 01-Main Register THIS TRANSMITTAL IS FOR: (Check one)

FIO GA DA CR DA/CR DA/GA

ITEM

NO.

(See Note 3) a.

DESCRIPTION OF SUBMITTAL ITEM

(Type size, model number/etc.)

b.

SUBMITTAL

TYPE CODE

(See Note 8) c.

NO.

OF

COPIES

d.

CONTRACT REFERENCE

DOCUMENT

SPEC.

PARA. NO.

e.

DRAWING

SHEET NO.

f.

CONTRACTOR

REVIEW

CODE

g.

VARIATION

Enter "Y" if requesting a variation

(See Note 6) h.

USACE

ACTION

CODE

(Note 9) i.

REMARKS I certify that the above submitted items have been reviewed in detail and are correct and in the strict conformance with the contract drawings and specifications except as otherwise stated.

NAME AND SIGNATURE OF CONTRACTOR

SECTION II - APPROVAL ACTION

ENCLOSURES RETURNED (List by item No.) NAME, TITLE AND SIGNATURE OF APPROVING AUTHORITY DATE

ENG FORM 4025-R, MAR 2012 REPLACES EDITION OF MAR 95, WHICH IS OBSOLETE.

7/8/2019 23 08 11-4.1

23 08 11 DMONSTRATIONS AND TESTS FOR BOILER PLANT

W912QR-16-C-0020 NA

Chicago Project Office

Northern Area Office

2417 Paul Jones Street, Bldg 837

Great Lakes, IL 60088

Walsh Federal JV

929 West Adams Street

Chicago, IL 60607

Hines VA Boiler Plant Hines VA Hospital

X 23 08 11-4

X

Actual boiler outlet temperatures exceed predicted (theoretical) temperatures at 100% fire rate. Temperature sensors are accurate and this is a true value. Regarding the economizer performance, the thermal exchange temperature delta is proportionate to inlet temperature and is actually performing better than required."

2 Pre-Testing Certificates & Data SD-07 2 1.5.c A meadrianar

LETTER OF TRANSMITTAL

Mechanical, Inc.

2175. - Hines VA Hospital - New Boiler Plant

DATE: 07/08/2019

TRANSMITTAL#: 119

To: Matt Dexheimer From: Scott Truitt

Walsh Construction Mechanical, Inc.

929 West Adams Street Chicago, IL 60607

Phone: ( ) Phone: (630)-891-3400 Fax: Fax: (630)-891-3401

Email: mdexheimer@walshgroup.com Email: struitt@mechinc.com

CC:

Attached and/or enclosed are the following documents.

DOCUMENT COPIES STATUS REMARKS

SUB

Boiler Pretesting Data per Spec Section 230811-1.5-C – Rev. 1

Additional Notes:

In response to the Revision 0 Comments, actual boiler outlet temperatures exceed predicted (theoretical) temperatures at 100% fire rate. Temperature sensors are accurate and this is a true measured value. Regarding the economizer performance, the thermal exchange temperature delta is proportionate to inlet temperature and is actually performing better than required.

Scott Truitt

ENGINEERED BOILER SYSTEMS

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #1

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Natural gas

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/16/18

Dry Bulb Temperature: 37 deg F

Wet Bulb Temperature: 33.3 deg F

Barometric Pressure: 30.3" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Gas Flow CV % 18.2 32.3 47.5 32.6 17.2

Steam Flow (Compensated) KPPH 4.5 19.6 37.5 19.8 4.3

Steam Pressure Header PSIG 125.0 126.0 125.0 127.0 125.0

Gas Supply Press CCS PSIG 18.6 18.50 18.20 18.50 18.6

Burner Pressure PSIG 0.2 3.50 10.40 3.80 0.4

Gas Flow Total Kscfh 4.9 22.9 41.1 24.0 5.9

Feed water pressure PSIG 187.0 185.0 180.0 185.0 188.0

FW Ent. Econ. Deg.F. 227.0 227.0 227.0 227.0 227.0

FW Out. Econ. Deg.F. 252.0 253.0 261.0 257.0 251.0

Boiler Flue Gas Outlet Temprature Deg.F. 354.0 454.0 545.0 452.0 352.0

Economiser Outlet Temprature Deg.F. 265.0 312.0 363.0 311.0 266.0

O2. (Insitu) % 6.30 3.4 3.0 3.4 6.00

O2. (Portable) % 6.5 3.5 3 3.1 5.7

Windbox O2 (Portable) % 19.20 18.60 19.10 18.80 19.00

CO. (Portable) PPM 30.1 0 0 0 6

NOx Corrected at 3% O2 PPM 26.0 25 28 25 28.0

Air Flow Raw Percent % 8.80 42.7 78.0 43.3 9.00

Air Flow CV % 3.9 37.3 87.5 37.2 3.9

Inlet Damper FB % 4.9 39.5 91.0 39.0 5.0

Wind Box Pressure "WC 0.8 4.0 10.0 4.5 1.0

Furnace Pressure "WC 0.1 0.8 2.5 0.8 0.0

Stack Pressure PV "WC -0.1 0.0 0.7 0.0 -0.1

Stack Pressure CV % 51.0 100.0 100.0 100.0 39.0

FGR Raw Flow Signal % 22.6 62.5 73.9 62.7 13.7

FGR CV % 30.4 60.5 96.8 60.8 28.1

Technician: Thad Jonas Signature:

(print)

Flame Shape

F la m e sh ap e, s ta b il it y a n d g en er al o p er at in g c o n d it io n

O ra n g e co re w it h b lu e fi n g er s

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n g e sp c k le s

H o ll o w c o re

B lu e H a ll o w a n d B lu e f in g e rs

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

O ra n g e co re w it h b lu e fi n g er s

BOILER/BURNER DATA SHEET

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #2

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Natural gas

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/29/18

Dry Bulb Temperature: 36 deg F

Wet Bulb Temperature: 32.4 deg F

Barometric Pressure: 32.4" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Gas Flow CV % 16.9 33.9 48.9 34.5 16.9

Steam Flow (Compensated) KPPH 3.3 23.4 37.5 22 3.3

Steam Pressure Header PSIG 127 125 126.0 125 127

Gas Supply Press CCS PSIG 17.9 17.8 17.70 17.8 17.9

Burner Pressure PSIG .5 4 10.50 4.5 .5

Gas Flow Total Kscfh 3.9 22.3 37.5 23.8 3.9

Feed water pressure PSIG 185 186 179.0 186 185

FW Ent. Econ. Deg.F. 227 227 227.0 227 227

FW Out. Econ. Deg.F. 259 276 266.0 266 259

Boiler Flue Gas Outlet Temprature Deg.F. 354 470 542.0 475 354

Economiser Outlet Temprature Deg.F. 263 313 360.0 320 263

O2. (Insitu) % 5.9 3.9 2.8 .3 5.9

O2. (Portable) % 6.5 4.1 2.9 3.0 6.5

Windbox O2 (Portable) % 19.3 18.8 19.30 18.8 19.3

CO. (Portable) PPM 4.0 0 0 0 4.0

NOx Corrected at 3% O2 PPM 31 25 28 27 31

Air Flow Raw Percent % 9.7 46.2 76.8 46 9.7

Air Flow CV % 2.6 47.5 89.9 47 2.6

Inlet Damper FB % 2.9 48.2 91.1 48 2.9

Wind Box Pressure "WC .1 2.5 7.0 2.5 .1

Furnace Pressure "WC 0 0.75 2.3 1 0

Stack Pressure PV "WC .1 .3 0.6 .3 .1

Stack Pressure CV % 100 100 100.0 100 100

FGR Raw Flow Signal % 9.8 58.7 69.4 58.5 9.8

FGR CV % 11.1 52.8 70.6 52.8 11.1

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

Flame Shape

F la m e sh ap e, s ta b il it y a n d g en er al o p er at in g c o n d it io n

O ra n g e co re w it h b lu e fi n g er s

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

H o ll o w c o re

B lu e H a ll d B lu e f in g e rs

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

O ra n g e co re w it h b lu e fi n g er s

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #3

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Natural gas

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/21/18

Dry Bulb Temperature: 36 deg F

Wet Bulb Temperature: 30.4 deg F

Barometric Pressure: 30" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Gas Flow CV % 16.2 31.3 46.0 31.9 16.2

Steam Flow (Compensated) KPPH 3.6 19.0 35.4 19.8 3.8

Steam Pressure Header PSIG 125.0 127.0 126.0 125.0 126.0

Gas Supply Press CCS PSIG 18.0 18.00 17.70 18.00 18.0

Burner Pressure PSIG 0.5 3.00 10.40 3.50 0.5

Gas Flow Total Kscfh 4.2 21.4 42.5 23.4 4.2

Feed water pressure PSIG 188.0 186.0 180.0 186.0 188.0

FW Ent. Econ. Deg.F. 227.0 277.0 227.0 277.0 227.0

FW Out. Econ. Deg.F. 257.0 267.0 266.0 265.0 257.0

Boiler Flue Gas Outlet Temprature Deg.F. 353.0 449.0 529.0 447.0 352.0

Economiser Outlet Temprature Deg.F. 264.0 310.0 361.0 313.0 266.0

O2. (Insitu) % 6.00 4.3 3.0 3.4 6.00

O2. (Portable) % 6.0 4.4 2.9 3.1 6.0

Windbox O2 (Portable) % 19.70 19.00 19.00 19.00 19.70

CO. (Portable) PPM 20 0 0 0 20

NOx Corrected at 3% O2 PPM 34.0 28 28 28 34.0

Air Flow Raw Percent % 10.50 38.6 76.2 39.9 10.50

Air Flow CV % 4.9 35.1 88.0 34.7 4.9

Inlet Damper FB % 4.9 35.1 88.3 35.0 4.9

Wind Box Pressure "WC 0.5 3.5 10.0 3.5 0.5

Furnace Pressure "WC 0.0 0.5 2.3 0.8 0.0

Stack Pressure PV "WC -0.1 0.1 0.7 0.1 -0.1

Stack Pressure CV % 91.0 100.0 100.0 100.0 91.0

FGR Raw Flow Signal % 7.9 46.0 65.4 46.3 7.9

FGR CV % 25.0 58.3 84.7 58.0 25.0

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

Flame Shape

F la m e sh ap e, s ta b il it y a n d g en er al o p er at in g c o n d it io n

O ra n g e co re w it h b lu e fi n g er s

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

H o ll o w c o re

B lu e H a ll d B lu e f in g e rs

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

O ra n g e co re w it h b lu e fi n g er

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #4

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Natural gas

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/20/18

Dry Bulb Temperature: 50 deg F

Wet Bulb Temperature: 42.1 deg F

Barometric Pressure: 29.8" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Gas Flow CV % 16.9 33.9 48.9 34.5 16.9

Steam Flow (Compensated) KPPH 3.3 23.4 36.3 22.0 3.3

Steam Pressure Header PSIG 127.0 125.0 126.0 125.0 127.0

Gas Supply Press CCS PSIG 17.9 17.80 17.70 17.80 17.9

Burner Pressure PSIG 0.5 4.00 10.50 4.50 0.5

Gas Flow Total Kscfh 3.9 22.3 37.5 23.8 3.9

Feed water pressure PSIG 185.0 186.0 179.0 186.0 185.0

FW Ent. Econ. Deg.F. 227.0 227.0 227.0 227.0 227.0

FW Out. Econ. Deg.F. 259.0 276.0 266.0 256.0 259.0

Boiler Flue Gas Outlet Temprature Deg.F. 354.0 470.0 542.0 475.0 354.0

Economiser Outlet Temprature Deg.F. 263.0 313.0 360.0 320.0 263.0

O2. (Insitu) % 5.90 3.9 2.8 3.0 5.90

O2. (Portable) % 6.5 4.1 2.9 3 6.5

Windbox O2 (Portable) % 19.30 18.80 19.30 18.80 19.30

CO. (Portable) PPM 40 0 0 0 40

NOx Corrected at 3% O2 PPM 31.0 25 28 27 31.0

Air Flow Raw Percent % 9.70 46.2 76.8 46.0 9.70

Air Flow CV % 2.6 47.5 89.9 47.0 2.6

Inlet Damper FB % 2.9 48.2 91.1 48.0 2.9

Wind Box Pressure "WC 0.1 2.5 7.0 2.5 0.1

Furnace Pressure "WC 0.0 0.8 2.3 1.0 0.0

Stack Pressure PV "WC 0.1 0.3 0.6 0.3 0.1

Stack Pressure CV % 100.0 100.0 100.0 100.0 100.0

FGR Raw Flow Signal % 9.8 58.7 69.4 58.5 9.8

FGR CV % 11.1 52.8 70.6 52.8 11.1

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

Flame Shape

F la m e sh ap e, s ta b il it y a n d g en er al o p er at in g c o n d it io n

O ra n g e co re w it h b lu e fi n g er s

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

H o ll o w c o re

B lu e H a ll d B lu e f in g e rs

O ra n g e t in te d c o re w it h b lu e f in g e rs a n d o ra n c k le s

O ra n g e co re w it h b lu e fi n g er

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #1

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Fuel Oil

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/19/18

Dry Bulb Temperature: 35 deg F

Wet Bulb Temperature: 29.6 deg F

Barometric Pressure: 30.1" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Oil Valve Output % 19.0 46.90 67.00 46.90 18.9

Steam Flow (Compensated) KPPH 4.0 18.3 34.2 18.3 3.8

Steam Pressure Header PSIG 125.0 125.0 126.0 125.0 126.0

Atomizing supply PSIG 125.0 124.0 121.0 123.0 124.0

Oil Supply up or regulator PSIG 126.0 125.00 123.00 129.00 130.0

Oil Supply PSIG 106.0 105.00 102.00 105.00 107.0

Atomizing Burner Press PSIG 16.0 64.0 98.0 64.0 16.0

Oil Burner Press PSIG 10.0 53.0 86.0 53.0 10.0

Atomizing DP PSIG 5.0 12.0 12.0 12.0 5.0

Oil Flow GPH 37.4 149.40 250.80 149.40 36.6

Feed Water Press PSIG 188.0 185.0 180.0 185.0 188.0

FW Ent. Econ. Deg.F. 227.0 227.0 227.0 227.0 227.0

FW Out. Econ. Deg.F. 255.0 264.0 266.0 264.0 256.0

Boiler Flue Gas Outlet Temprature Deg.F. 348.0 440.0 521.0 442.0 350.0

Economiser Outlet Temprature Deg.F. 255.0 302.0 348.0 304.0 256.0

O2. (Insitu) % 8.20 6.0 3.3 6.0 7.90

O2. (Portable) % 8.4 6.3 3.1 6.3 8.4

Windbox O2 (Portable) % 20.50 20.30 20.00 20.30 20.50

CO. (Portable) PPM 50 0 0 0 50

NOx Corrected at 3% O2 PPM 20.3 20.3 20.1 20.3 20.3

Air Flow Percent % 11.70 44.8 68.5 44.8 11.70

Air Flow CV % 7.1 40.8 72.1 40.8 7.1

Inlet Damper FB % 8.1 43.1 74.6 43.1 8.1

Wind Box Pressure "WC 1.5 4.5 7.4 4.5 1.5

Furnace Pressure "WC 0.0 0.0 0.3 0.0 0.0

Stack Pressure PV "WC -0.1 0.0 0.3 0.0 -0.1

Stack Pressure CV % 55.0 100.0 100.0 100.0 55.0

FGR Raw Flow Signal % 6.1 17.9 37.1 17.9 6.1

FGR CV % 10.3 35.0 58.9 35.0 10.3

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

F la m e sh ap e, s ta b il it y a n d g en er al o p er at in co d it io n

O ra n g e fi n g er t ip s w it h b lu e b as e

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er t ip s w e b as e

Flame Shape

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #2

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Fuel Oil

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/30/18

Dry Bulb Temperature: 39 deg F

Wet Bulb Temperature: 35.4 deg F

Barometric Pressure: 30.1" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Oil Valve Output % 22.6 42.9 62.9 42.7 22.5

Steam Flow (Compensated) KPPH 4.9 18.2 35.2 16.6 5.2

Steam Pressure Header PSIG 125 125 126 125 125

Atomizing supply PSIG 124 124 120 121 124

Oil Supply up or regulator PSIG 128 124 123 130 131

Oil Supply PSIG 104 103 101 103 104

Atomizing Burner Press PSIG 17 61 96 60 16

Oil Burner Press PSIG 12 50 84 58 12

Atomizing DP PSIG 5 12 12 12 5

Oil Flow GPH 41.8 144 285 135.3 42.5

Feed Water Press PSIG 185 186 179.0 186 185

FW Ent. Econ. Deg.F. 227 227 227.0 227 227

FW Out. Econ. Deg.F. 261 267 266 262 263

Boiler Flue Gas Outlet Temprature Deg.F. 362 448 524 448 366

Economiser Outlet Temprature Deg.F. 267 300 348 307 274

O2. (Insitu) % 8.8 6.8 3.4 7 9.2

O2. (Portable) % 9.4 7 3.5 7.5 9.6

Windbox O2 (Portable) % 20.4 20.3 20.4 20.5 20.5

CO. (Portable) PPM 45 0 0 0 35

NOx Corrected at 3% O2 PPM 55 60 53 62 61

Air Flow Percent % 15.2 43.2 72.6 43.4 15.2

Air Flow CV % 12.9 39.5 63.1 29.4 12.9

Inlet Damper FB % 13.3 40 63.8 39.8 13.3

Wind Box Pressure "WC 0.5 1.5 5.5 1.75 0.5

Furnace Pressure "WC 0 .6 2 .75 0

Stack Pressure PV "WC -0.1 .1 .5 .1 -.1

Stack Pressure CV % 70.6 100 100 100 87

FGR Raw Flow Signal % 6.5 17 25.5 16.9 6.3

FGR CV % 0 19.8 30.1 20.2 1

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

F la m e sh ap e, s ta b il it y a n d g en er al o p er at d it io n

O ra n g e fi n g er t ip s w e b as e

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er t ip s w e b as e

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #3

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Fuel Oil

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/27/18

Dry Bulb Temperature: 54 deg F

Wet Bulb Temperature: 45.5 deg F

Barometric Pressure: 29.9" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Oil Valve Output % 17.5 38.00 51.90 37.90 17.5

Steam Flow (Compensated) KPPH 4.8 19.4 35.0 19.0 4.7

Steam Pressure Header PSIG 125.0 125.0 126.0 125.0 125.0

Atomizing supply PSIG 125.0 123.0 120.0 124.0 124.0

Oil Supply up or regulator PSIG 127.0 126.00 124.00 130.00 131.0

Oil Supply PSIG 105.0 103.00 102.00 104.00 106.0

Atomizing Burner Press PSIG 16.0 62.0 80.0 62.00 15.0

Oil Burner Press PSIG 10.0 51.0 92.0 51.0 10.0

Atomizing DP PSIG 5.0 12.0 12.0 12.0 5.0

Oil Flow GPH 41.7 158.10 285.00 156.00 42.0

Feed Water Press PSIG 188.0 186.0 180.0 186.0 188.0

FW Ent. Econ. Deg.F. 227.0 277.0 227.0 277.0 227.0

FW Out. Econ. Deg.F. 256.0 263.0 265.0 264.0 259.0

Boiler Flue Gas Outlet Temprature Deg.F. 345.0 439.0 520.0 438.0 347.0

Economiser Outlet Temprature Deg.F. 256.0 302.0 349.0 306.0 258.0

O2. (Insitu) % 8.70 5.7 3.0 6.0 9.20

O2. (Portable) % 9.3 5.7 3.2 6.2 9.2

Windbox O2 (Portable) % 20.90 20.50 19.90 20.50 20.60

CO. (Portable) PPM 46 0 0 0 40

NOx Corrected at 3% O2 PPM 57.0 55 50 56 56.0

Air Flow Percent % 15.10 43.8 70.1 45.0 15.70

Air Flow CV % 13.7 47.1 78.0 46.9 13.9

Inlet Damper FB % 13.8 47.2 78.3 47.0 14.0

Wind Box Pressure "WC 1.0 3.3 7.0 3.0 0.5

Furnace Pressure "WC 0.0 0.5 1.8 0.5 0.0

Stack Pressure PV "WC 0.0 0.2 0.6 0.1 -0.1

Stack Pressure CV % 100.0 100.0 100.0 100.0 80.0

FGR Raw Flow Signal % 0.0 10.4 27.0 10.4 0.0

FGR CV % 0.0 35.0 59.8 35.3 0.0

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

F la m e sh ap e, s ta b il it y a n d g en er al o p er at d it io n

O ra n g e fi n g er t ip s w e b as e

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er t ip s w e b as e

Customer : Mechanical INC/ VA Burner Manufacturer: NATCOM Boiler #: #4

Location : Hines, IL Burner Model: P-42-LOG-17-0812 Fuel : Fuel Oil

Observer : Thad Jonas Boiler Model: SP-NB-200D-55 Date: 11/28/18

Dry Bulb Temperature: 59 deg F

Wet Bulb Temperature: 48.7 deg F

Barometric Pressure: 29.9" Hg

Firing rate 0.0% 50.0% 100% 50% 0%

Oil Valve Output % 22.6 42.90 62.90 42.7 22.5

Steam Flow (Compensated) KPPH 4.9 18.2 35.2 16.6 5.2

Steam Pressure Header PSIG 125.0 125.0 126.0 125.0 125.0

Atomizing supply PSIG 124.0 124.0 120.00 121.0 124.0

Oil Supply up or regulator PSIG 128.0 124.00 123.00 130.0 131.0

Oil Supply PSIG 104.0 103.00 101.00 103.0 104.0

Atomizing Burner Press PSIG 17.0 61.0 96.0 60.0 16.0

Oil Burner Press PSIG 12.0 50.0 4.0 58.0 12.0

Atomizing DP PSIG 5.0 12.0 12.0 12.0 5.0

Oil Flow GPH 41.8 144.00 285.00 135.3 42.5

Feed Water Press PSIG 185.0 186.0 179.0 186.0 185.0

FW Ent. Econ. Deg.F. 227.0 227.0 227.0 227.0 227.0

FW Out. Econ. Deg.F. 261.0 267.0 266.0 262.0 263.0

Boiler Flue Gas Outlet Temprature Deg.F. 362.0 448.0 524.0 448.0 366.0

Economiser Outlet Temprature Deg.F. 267.0 300.0 348.0 307.0 274.0

O2. (Insitu) % 8.80 6.7 3.4 7.0 9.2

O2. (Portable) % 9.2 7 3.5 7.5 9.6

Windbox O2 (Portable) % 20.40 20.30 20.40 20.5 20.5

CO. (Portable) PPM 45 0 0 0.0 35.0

NOx Corrected at 3% O2 PPM 55.0 60 53 62.0 61.0

Air Flow Percent % 15.20 45.2 72.6 43.4 15.2

Air Flow CV % 12.9 39.5 63.1 29.4 12.9

Inlet Damper FB % 13.3 40.0 63.8 39.8 13.3

Wind Box Pressure "WC 0.5 1.5 5.5 1.8 0.5

Furnace Pressure "WC 0.0 0.6 2.0 0.8 0.0

Stack Pressure PV "WC -0.1 0.1 0.5 0.1 -0.1

Stack Pressure CV % 71.0 100.0 100.0 100.0 87.0

FGR Raw Flow Signal % 6.5 17.0 25.5 16.9 6.3

FGR CV % 0.0 19.0 30.1 20.2 1.0

Technician: Thad Jonas Signature:

(print)

BOILER/BURNER DATA SHEET

F la m e sh ap e, s ta b il it y a n d g en er al o p er at d it io n

O ra n g e fi n g er t ip s w e b as e

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er a n d o ra n g e ce n te r

O ra n g e fi n g er t ip s w e b as e

September 2008 48

Checklist for High Water Alarm on Deaerator Tank (HWADT) Item Make Float /

Probe

Alarm

Setpoint

Correct Device

Type Y / N

Correct

Location Y / N

HWADT

*Alarm setpoint should be below 2/3rds of tank height & at least 4” below the overflow.

*Alarm type should be a probe sensor.

Vent

PRV

Steam

Bypass Valve

Makeup / Condensate

SVFPRV

MV

DASV

10 Psig

500-1000 lb/hr

Vac Breaker

OVERFLOW PROBE

HWA (PROBE)

DA TANK

LWA

Overflow

SOLENOID ACTUATED

BUTTERFLY VALVE

To Boiler

Drain sight glass (Drain 0079, 0080, 0081, 0083, 0083) without draining alarm column and quickly close drain valve. Water level should quickly rise in sight glass indicating good communication with tank.

Use bypass valve (RO-011) to add water to the deaerator at a rate not to exceed 1 inch per minute. Use water level sight glass to observe point that alarm sounds.

DO NOT ALLOW WATER LEVEL TO LEAVE SIGHT GLASS.

Result Y/N Water Level

Did the alarm work correctly?

What was the water level in sight glass at alarm point?

Can the switch be isolated with manual valves

Comment:

Probe

See following

P&ID

Foxboro

Y Y70"

Y

Y 70"

Deaerator Tank was pretested during October/November 2018 Commissioning.

HWADT, LWADT & DAODS were adjusted to conform with Safety Device Test Manual Version 3 regarding 1/3-2/3 setpoints. Setpoints verified by Commissioning Agent on

11/13/18 and with BEI on 1/24/19. Updated SDTM V3 Test Results shown below:

W912QR16R0030-0000

September 2008 50

Checklist for Low Water Alarm on Deaerator Tank (LWADT)

Probe

Alarm

Setpoint

Correct Device

Type Y / N

Correct

Location Y / N

LWADT

*Alarm set point should be above 1/3rd of tank height.

PRV

Bypass Valve

MV

indicating good communication with tank.

Drain the water (Drain 033) from the deaerator at a rate not to exceed 1 inch per minute. Use water level sight glass to observe alarm point DO NOT ALLOW

WATER LEVEL TO LEAVE SIGHT GLASS.

Did the alarm work correctly?

What was the water level in sight glass at alarm point?

Can the switch be isolated with manual valves

P&ID

Foxboro 47.5"

Y Y36"

Y

Y 36"

September 2008 52

Checklist for Deaerator Overflow Drain System (DAODS)

Probe

Overflow

Setpoint

Correct Device

Type Y / N

Correct

Location Y / N

DAODS

*Overflow type should be a conductivity probe connected to electronic valve.

*Setpoint should be at least 4” below top of tank.

indicating good communication with tank.

Open manual bypass valve (RO-011) to supply feedwater at maximum rate.

Use sight glass in drain system to determine that dump valve has opened. Use water level sight glass to observe whether dump valve maintains water level visible in sight glass. DO NOT ALLOW WATER LEVEL TO LEAVE SIGHT GLASS.

Did the overflow valve work correctly?

Was the water level maintained in sight glass.

View port in place to view overflow?

P&ID

Foxboro 87"

Y Y74"

Y Y Y

74"

September 2008 54

Checklist for Deaerator Safety Valve (DASV) Item Make Capacity

(lb/hr)

Range DASV Setpoint

DA PRES

(psig)

Correct

Installation

DASV

Pressure Gage

*Setpoint should be about 5 PSIG higher than DA pressure

*Capacity should be approximately (1000 lb/hr)

Item Make Type MAWP NDT (date)

Deaerator

Abort testing if NDT is not current within six years.

Pour water into drip pan ell drain and confirm that it is open.

Slowly open bypass valve (HPS-201) to raise pressure until safety lifts. DO

NOT RAISE PRESSURE MORE THAN 2 PSIG ABOVE SET POINT

PRESSURE.

Re-seat pressure should be about 6% less than lift pressure.

After lifting valve, close bypass valve (HPS-201) and allow safety to reseat.

Result Y/N Pressure

Did the safety valve work correctly?

What was the safety valve relief pressure?

What is the re-seat pressure?

Is vacuum breaker present (VA requirement)?

Makeup / Condensate DASV

Vent

SVFPRV

Steam Vac Breaker

OVERFLOW PROBE

DA TANK

HWA (PROBE)

See following

P&ID

Cleaver Brooks Traymaster

Kunkle 5800 15 psig

1400,000

7.5 Ashcroft 0-60

(SV-22A & 22B)

(SV-22A & 22B)

Installed on Tank

Body.

Two Safety Relief Valves installed on DA tank See Following P&ID

SV22A SV22B

50 psig

Y Y

Y

Y

15 psig 15 psig

14.5 psig 14.5 psig

HPS-201