S02_Attachment 6_866CM3030 NNC Burial-Expansion Drawings-3.pdf
PDF 9 MB Posted
- Attached to
- Y1PZ--CONS Natchez NC Expansion/Demo Mx Fac/Roads (866CN3029/866CM3030) (VA-23-00072411)
- Solicitation number
- 36C78624B0041
About this file
This document appears to be a set of drawings and specifications for the Burial Expansion Project at the Natchez National Cemetery, which is part of Federal Contract Opportunity 307de05017b84e149af582cea364e822 (Solicitation Number 36C78624B0041).
The key details include:
- The project involves construction and expansion of the burial area, including new concrete sidewalks, roads, flower vasing stations, irrigation system, and a committal shelter.
- The drawings cover site plans, irrigation details, structural plans for the committal shelter, and electrical plans and panel schedules.
- The federal agency involved is the Department of Veterans Affairs National Cemetery Administration.
- The project ID numbers are 866CM3029 and 866CM3030.
- This appears to be bid documentation, with a bid documents submission date of March 7, 2023.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL DESCRIPTION
GENERAL NOTES
FLAG NOTES
LEGEND
Q
IR
IR
R
R
A
Q
S
F
G
M
F
IRRIGATION NOTES
IRRIGATION DEMOLITION FLAG NOTES
A
B
C
D
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
P-
NA
CH
EZ
-E
XP
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
N
3/7/23 33
SECTION
SSECTION
T
SECTION
V
SECTION
U
IR
IR
IR
IR
IR
IR
IR
IR
IRIR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR IR IR IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
Q
Q
QIR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IRIR
IR
IR
IR
IR
Q
Q
IR
IR
IR
IRIR
IR
IR
IR
IR
IR
Q
AB
D
D
Q
Q
Q
IR
IRIR
IR
IR
IR
IR
Q
R
R
S
S
S
S
R
R
R
R
R
R
R R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R R
R
R
CONCRETE
BUILDING
C O
M M
ITTAL
SH
ELTER
A
A
A
B
B
B
C
C
C
D
D
D
CUT AND CAP
MAINLINE
CONNECTION TO
FLOWER WATER
STATION UNIT AND
REMOVE UNIT
IRRIGATION DEMOLITION PLAN
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
P-
NA
CH
EZ
-E
XP
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
N
3/7/23
1" =
20' 0' 10' 20' 40'
20'
KEY MAP
NATCHEZ
NATIONAL
CEMETERY
(WEST)
MARBLESTONE ROAD
CE
M
ET
ER
Y
RO
AD
NATCHEZ
NATIONAL
CEMETERY
(EAST)
LEGEND
Q
IR
IR
R
R
A
Q
S
F
G
M
F
Q
Q
R
R
S
S
S
S
R
R
R
R
R
R
R
R
R
R
R
5 6
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IRIR
IR
IR
IR
IR
EX
IS
TI
N
G B
U R
IA
L
SE
C
TI
O
N (P
H
AS
E I)
G
EN
ER
AL
W O
R K
PL
AN
EXISTING PROPERTY LINE/R.O.W.
EXISTING PROPERTY LINE/R.O.W.
EXISTING PROPERTY LINE/R.O.W.
N
EW
L
AR
G E
M
AS
O N
R Y
C O
LU
M
N
EX
IS
TI
N
G
FL
AG
P
O
LE
H O
LD
ER
N
EW
M
AN
H O
LE
C
O M
M
IT
TA
L
SH
EL
TE
R
P
AR
KI
N
G
N
EW
" S
AN
IT
AR
Y
SE
W
ER
L
IN
E
C O
M M
IT
TA
L
SH
EL
TE
R P
AR
KI
N G
N
EW
F
LO
W
ER
V
AS
E/ W
AT
ER
IN
G
S
TA
TI
O
N
EXISTING PROPERTY LINE/R.O.W.
PR
IM
AR
Y
RO
AD
VI
SI
TO
R
/E M
PL
O
YE
E
PA
R
KI
N
G A
R
EA
PIC/RR
EX
IS
TI
NG
P
RO
PE
RT
Y
LI
NE
/R
.O .W
PRIMARY ROAD
EXISTING 6" SS
N
EW
S M
AL
L
M
AS
O N
R Y
C O
LU
M
N S
N
EW
L
AR
G E
M
AS
O N
R Y
C O
LU
M
N S
N
EW
-F
O O
T O
R N
AM
EN
TA
L
FE
N
C E
FO
O T
C O
N C
R
ET
E
SI
D
EW
AL
K
EX
IS
TI
N
G R
O
LL
C U
R B
G
U
TT
ER
EN
D
O F
EX
IS
TI
N
G
FL
AG
P
O
LE
H O
LD
ER
S
EN
D
O F
EX
IS
TI
N
G R
O
LL
C U
R B
G
U
TT
ER
EX
IS
TI
N
G 1"
D O
M
ES
TI
C
W
AT
ER
L
IN
E
C O
M M
IT
TA
L
SH
EL
TE
R
SL
AB
EL
. 2
.0
NEW 6 FOOT CONCRETE SIDEWALK
VISITOR PARKING
MAINTENANCE
BUILDING
SLAB EL. 253.0
N
EW
P O
W
FL
AG
P
O
LE
N
EW
SA
N
IT
AR
Y C
LE
AN
O U
T
NE
W
" S
AN
IT
AR
Y
SE
W
ER
L
IN
E
N
EW
A
LU
M
IN
U M
H
AN
D R
AI
L
N
EW
F
LO
W
ER
V
AS
E/ W
AT
ER
IN
G
S
TA
TI
O
N
BE
G
IN
N
EW
FL
AG
PO
LE
H
O
LD
ER
S
EX
IS
TI
N
G
" M
AI
N
IR
R
IG
AT
IO
N L
IN
E
CO
NC
RE
TE
EN
TR
AN
CE
AR
EA
N
EW
-F
O O
T C
H
AI
N L
IN
K
FE
N
C E
230'+/-
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -P
C
R -F
C
R -F
C
R -F
C
R -F
C
R -F
C
R-
PC
R-
FC
R-
FC
R-
FC
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
2" MI
2" MI
I
R -F
C
2" MI
R -P
C
R -P
C
R -F
C
I
I
I
R -F
C
I
R -F
C
I
R -F
C
R -F
C
I
2" M
I
2" M
I
2" M
I R
-P C
R-PC
I
I
R -P
C
R-PC
I
I
R -P
C R
-P C
R -P
C
I
I
I
R -P
C
R -P
C
R -P
C
S- F
S- F
S- F
S- F
8%
8%
7.5%
8%
2%
8%
7.3%
250.74
251.00
LP250.25
(252.00) 251.85
LP250.55
251.00
LP250.10
LP249.90
250.14
251.20
8%
250.50
(250.70)
(250.90)
(251.03)
(250.87)
(250.80)
(251.12)
250.35
250.40
251.32 250.60
(251.18)
(251.60)
(251.90)
(251.13)
250.34
251.75
(251.90)
251.75
251.60 250.73
251.44
(252.05) 251.90
252.02
(251.90)
251.04
(251.95)
HP250.75
HP250.50
250.66
250.87 250.54
HP250.30
250.46
250.88
251.84
HP251.70
251.75
251.50
V.I.F.
V.I.F.
V.I.F.
WALK: 252.38
PVMT: 251.88
WALK: 252.50
PVMT: 252.00WALK: 252.13
PVMT: 252.13
WALK: 252.13
PVMT: 252.13
2%
MIN.
2%
MIN.
251.95251.95
252.02
252.02
(248.00)
247.75
(247.45) 247.20
(246.82) 246.57
(246.57) 246.32
(246.32) 246.07
(246.07) 245.82
(245.82) 245.57
(245.57) 245.32
(245.57)
245.32
A
Q
Q
R
R
S
S
S
S
R
R
R
R
R
R
R
R
R
R
R
5 6
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IR
IRIR
IR
IR
IR
IR
250252
A
1.5"
1.5"
- 1.5"
1.5"
- 1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
EXISTING
SPRAY
1.5"
1.5"
- 1.5"
1.5"
- 1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
EXISTING
SPRAY
2"
2"
1.5"
1.25"
1"
2"
2"
1"
1.5"
1.25"
1"
2"
1"
1"
2" 1.25"
1"
1.25"
1"
1"
1"
1.5" 1.25"
1"
2"
2"2"
1.5"
1.5"
1.25"
1"
2"
2"
1"
1"
1.5"
1.25"
1.25"
1"
1"
1"
2"
1.5"
1.25"
1"
1.5"
1"
1"
1"
2"
1.25"
1.5"
1.5"
1.25"
1" 1"
1" 1"
2"
1"
1.5"
1.5"
1.25"
1"
2"
1"
1.5"
1.25"
1"
2"
2"
1"
1.5"
1" 1.25"
2"
1"
1"
2"
1"
1"
1.25"
1"
2"
2"
1.5"
1.25"
1"
2"
2"
1"
1.5"
1.25"
1"
2"
1"
1"
2" 1.25"
1"
1.25"
1"
1"
1"
1.5" 1.25"
1"
2"
2"2"
1.5"
1.5"
1.25"
1"
2"
2"
1"
1"
1.5"
1.25"
1.25"
1"
1"
1"
2"
1.5"
1.25"
1"
1.5"
1"
1"
1"
2"
1.25"
1.5"
1.5"
1.25"
1" 1"
1" 1"
2"
1"
1.5"
1.5"
1.25"
1"
2"
1"
1.5"
1.25"
1"
2"
2"
1"
1.5"
1" 1.25"
2"
1"
1"
2"
1"
1"
1.25"
1"
Q
Q
F
F
G
G
G
G
MF
Q
Q
Q
Q
Q
Q
Q
Q
Q
F
F
G
G
G
G
MF
Q
Q
Q
Q
Q
Q
Q
REMOVE EXISTING PRESSURE VACUUM
BREAKER AND REPLACE WITH REDUCED
PRESSURE ZONE DEVICE.
IRRIGATION DISTRIBUTION PLAN
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
JUNE 7, 2024 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
SU
BM
IT
TA
LS
\20
-0
3-
\35 -L
I10 2.D
W G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
N
3/7/23
1" =
20' 0' 10' 20' 40'
20'
KEY MAP
NATCHEZ
NATIONAL
CEMETERY
(WEST)
MARBLESTONE ROAD
CE
M
ET
ER
Y
RO
AD
NATCHEZ
NATIONAL
CEMETERY
(EAST)
LEGEND
Q
IR
IR
R
R
A
Q
S
F
G
M
F
JStilan Text Box
MARCH 7, 2023
JStilan Text Box Scope Revision & Clarification
JStilan Text Box 6/7/2024
1 ISOLATION GATE VALVE
ASSEMBLY N.T.S. 2 QUICK COUPLER VALVE ASSEMBLY
ASSEMBLY N.T.S. 3 DECODER CABLE FUSE
ASSEMBLY N.T.S.
4 REMOTE CONTROL VALVE
ASSEMBLY N.T.S.
IRRIGATION DETAILS 1
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
P-
NA
CH
EZ
-E
XP
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
3/7/23 36
1 POP-UP ROTOR
ASSEMBLY N.T.S. 2 ROTOR DOUBLE SWING JOINT
ASSEMBLY N.T.S. 3 POP-UP SPRAY
ASSEMBLY N.T.S.
4 SPRINKLER PLACEMENT
DETAIL N.T.S.
54" MIN.
4'-9"
2'-9"
54" MIN.
3'
IRRIGATION DETAILS 2
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
P-
NA
CH
EZ
-E
XP
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
3/7/23 37
1 FLOWER WATER STATION
ASSEMBLY N.T.S.
IRRIGATION DETAILS 3
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
P-
NA
CH
EZ
-E
XP
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
N
3/7/23 38
EQUIPMENT LIST
COPPER PIPE (REFER TO MEP PLANS). MAKE NECESSARY CONNECTION
TO BOOSTER PUMP.
CONCRETE FLOOR - SECURE BOOSTER PUMP TO CONCRETE FLOOR PER
BOOSTER PUMP MANUFACTURER'S GUIDELINES
PREFABRICATED BOOSTER PUMP. ITEMS INCLUDE BUT NOT LIMITED TO:
· CONTROL PANEL (SHIPPED LOOSE): REMOTE MOUNTED, SERVICE
DISCONNECT, FORCE AIR COOLED VARIABLE FREQUENCY DRIVE,
SWITCH GEAR
· 2 HP PUMP AND MOTOR
· CHECK VALVES
· PRESSURE TRANSDUCER
· BY PASS VALVE
· FLOW SENSOR
· TEMPERATURE SENSOR
· PRESSURE GAUGE
· PAINTED STEEL SKID
· THREAD-O-LET AT INLET AND OUTLET
· DRAIN PLUGS
NOTES:
1. PROVIDE SHOP DRAWING OF BOOSTER PUMP FOR APPROVAL PRIOR TO
CONSTRUCTION.
2. BOOSTER PUMP TO BE TESTED IN FACTORY PRIOR TO SHIPMENT TO SITE.
MANUFACTURER TO PROVIDE TESTING RESULTS TO OWNER'S
REPRESENTATIVE.
3. PUMP MANUFACTURER'S REPRESENTATIVE MUST BE PRESENT DURING
INSTALLATION AND START UP.
4. CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL FIELD CONDITIONS
PRIOR TO ORDERING BOOSTER PUMP.
5. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
6. BOOSTER PUMP TO MAINTAIN DISCHARGE PRESSURE (PRESSURE START,
FLOW STOP).
7. REFER TO ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.
PLAN VIEW
ITEMS WITHIN DASHED
LINE ARE INCLUDED WITH
PREFABRICATED BOOSTER
PUMP (ALSO INCLUDES REMOTE
MOUNTED DISCONNECT AND CONTROL PANEL)
A
WATERTRONICS
psi
PSI
WATERTRONICS
42" MIN.
SEE LOCAL
NEC CODE
REMOTE MOUNTED
HIGH VOLTAGE DISCONNECT
AND CONTROL PANEL BOARD
±3'
±3'
±1'-2"
PANEL TO BE MOUNTED WITHIN 25' LINE OF SIGHT OF PUMP
2'-11"
BASE
4'-4"
BASE
2"+/- 111
2"+/-
+/-2'-2"
+/-9"
FLOW
FLOW
ITEMS WITHIN DASHED
LINE ARE INCLUDED WITH
PREFABRICATED BOOSTER
PUMP (ALSO INCLUDES REMOTE
MOUNTED DISCONNECT AND CONTROL PANEL)
CONCRETE ANCHOR
TYPICAL (4) LOCATIONS
SECTION VIEW
A
A
A A
B
B
B
C
C
C
DISCONNECT
CONTROL PANEL
DISCONNECT
CONTROL PANEL
NOTES:
1. FURNISH FITTINGS AND PIPING SIZED IDENTICALLY WITH NOMINAL BACKFLOW
PREVENTION DEVICE.
2. SUBMIT SHOP DRAWINGS SPECIFYING ENCLOSURE SIZE AND SHOWING
RELATIVE LAYOUT OF EQUIPMENT.
A
B
C
D
E F
G
H I J
K
A. BACKFLOW PREVENTER ENCLOSURE (SIZE
AS NECESSARY)
B. BACKFLOW PREVENTION DEVICE
C. C x M COPPER ADAPTER (1 OF 2)
D. TYPE K COPPER PIPE (TYPICAL) (LENGTH AS
REQUIRED)
E. CL200 PVC PIPE SLEEVE (1 OF 2)
F. 4" THICK CONCRETE PAD 6" LARGER IN ALL
DIMENSIONS THAN ENCLOSURE
G. FINISH GRADE/TOP OF MULCH
H. COPPER FEMALE ADAPTER
I. SCH 40 PVC MALE ADAPTER
J. PVC MAINLINE
K. TYPE K COPPER PIPE
2 BACKFLOW PREVENTION DEVICE
ASSEMBLY N.T.S. 3 BOOSTER PUMP
ASSEMBLY N.T.S.
1 MASTER VALVE
ASSEMBLY N.T.S. 2 FLOW SENSOR
ASSEMBLY N.T.S.
IRRIGATION DETAILS 4
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 JDL CCT Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : O
:\IF
S\
NA
TC
HE
Z-
EX
P\
P-
NA
CH
EZ
-E
XP
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
Ce rt i f ie d Irrigat ion Designer
46102
JO
HN D. LEONARD
I RR
I G A T I O N A S S OC I AT I O
N
3/7/23 39
A
B C
D
E
F G
H
I
JK
A. TRACING WIRE
B. 12" VALVE BOX WITH COVER
C. FINISH GRADE/TOP OF MULCH
D. SENSOR DECODER
E. WIRE SPLICE, TYPICAL
F. FLOW SENSOR
G. TWO WIRE CABLE
H. FILTER FABRIC
I. PVC PIPE
J. BRICK (1 OF 4)
K. 3" MINIMUM DEPTH OF 3/4"
WASHED GRAVEL
L. INSTALL SENSOR ROTATED
BETWEEN 60° AND 90° FOR
BEST PERFORMANCE
NOTES:
1. ALLOW 10 PIPE DIAMETERS UPSTREAM AND 5 PIPE DIAMETERS DOWNSTREAM OF
STRAIGHT RUN OF PIPE TO ACHIEVE PROPER FLOW REGIME.
2. INSTALL FILTER FABRIC AROUND EXTERIOR OF VALVE BOX. USE DUCT TAPE TO
SECURE FABRIC TO PIPE AND VALVE BOX.
3. DO NOT CUT OUT ENDS OF VALVE BOX UNNECESSARILY.
4. INSTALL SO THAT GRAVEL IS ONLY IN CONTACT WITH BOTTOM OF SENSOR ASSEMBLY.
L
FLOW
A
B
C
D
E
F
G
H I
J
K L
MN
A. VALVE BOX WITH COVER ( SIZE TO ALLOW FOR A
MINIMUM OF 6" OF SPACE ON ALL SIDES )
B. FINISH GRADE
C. WIRE SPLICE
D. SOLENOID WIRES
E. DECODER
F. TRACING WIRE
G. MASTER VALVE
H. VAN STONE STYLE PVC FLANGE (1 OF 2)
I. FILTER FABRIC
J. PVC MAINLINE
K. TWO-WIRE CABLE
L. 3" MINIMUM DEPTH OF 3/4" WASHED GRAVEL
M. BRICK (1 OF 4)
N. CONCRETE SUPPORT BLOCK
NOTES:
1. INSTALL DECODER PER MANUFACTURER'S GUIDELINES.
2. USE VALVE BOX EXTENSION AS NECESSARY TO ACHIEVE A MINIMUM CLEARANCE OF 6" ABOVE ASSEMBLY.
3. NOMINAL SIZE OF ALL COMPONENTS ARE TO BE THE SAME NOMINAL SIZE AS THE MASTER VALVE.
4. INSTALL FILTER FABRIC AROUND EXTERIOR OF VALVE BOX. USE DUCT TAPE TO SECURE FABRIC TO PIPE AND VALVE BOX.
5. DO NOT CUT OUT ENDS OF VALVE BOX UNNECESSARILY.
6. POSITION VALVE BOX OVER MASTER VALVE TO ALLOW ACCESS TO SOLENOID.
7. INSTALL SO THAT GRAVEL IS ONLY IN CONTACT WITH BOTTOM OF VALVE ASSEMBLY.
JStilan
MARCH 7, 2023
SE501
A B
6'-6"
'-0
4'-6"
1'-0" 1'-0"
1' -0
9"
'-6
9"
1' -0
20'-0"
SE501
SCALE:1
SPREAD FOOTING
FOUNDATION PLAN
1/4" = 1'-0"
SE501
'-0
28'-0"
1' -2
'-7
2' -3
4'-0" 24'-0"
A B
1'-6"
1' -6
SE501
SCALE:2 SLAB PLAN
1/4" = 1'-0"
7/ 8"
2' -7
/8
6'
-1
/8
2' -7
/8
1' -1
/8
1" 5'-1 1/4"
A B
SCALE:3 SHED ROOF FRAMING PLAN
1/4" = 1'-0"
STRUCTURAL NOTES AND PLANS
SHELTER
SE101
42 47
RIDALK
SHEET NOTES:
1. VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS BOTH
ON PLANS AND IN THE FIELD PRIOR TO COMMENCEMENT OF
CONSTRUCTION.
2. IDENTIFYING ANY CONFLICT AND/OR DISCREPANCY,
REPORTING SUCH CONFLICT AND DISCREPANCY TO THE COR
PRIOR TO AND DURING CONSTRUCTION.
3. USE PLAN DIMENSIONS. DO NOT SCALE FROM DRAWINGS.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : P
:\G
OR
D1 -2
1 I
FS
N
AT
CH
EZ
B
UR
IA
L E
XP
AN
SI
ON
\D
RA
W
IN
GS
\S
HE
ET
S\
SE
1 S
TR
UC
TU
RA
L P
LA
NS
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GRITY FEDERA
L
SERV I CES
KEY NOTES:
1. 24" WIDE x 24" DEEP CONTINUOUS FOOTING
2. 12" WIDE x 24" DEEP CONTINUOUS FOOTING
3. 24" DIAMETER x 24" DEEP AUGERED FOOTING
4. 5" CONCRETE SLAB WITH (1) #4 AT 18" ON CENTER EACH WAY.
CENTERED IN SLAB
5. SLAB EDGE
6. 5" WIDE x 4" HIGH CURB.
7. CMU WALL AND COLUMNS, DESIGN BY SHELTER SUPPLIER
8. COLD FORMED STEEL TRACK FASTENED TO CMU WALL
9. COLD FORMED ROOF JOISTS AT 24" ON CENTER, MAXIMUM 6"
DEEP
10. COLD FORM STEEL STUD WALL
N
0'
SCALE: 1/4" = 1'-0"
8'4'2'
DESIGN CRITERIA
APPLICABLE CODES & STANDARDS:
1. INTERNATIONAL BUILDING CODE - 2018 EDITION.
2. ASCE 7-16 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR
BUILDINGS AND OTHER STRUCTURES.
3. AISC STEEL CONSTRUCTION MANUAL- 15TH EDITION.
4. ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE.
5. ACI 301-16 SPECIFICATIONS FOR STRUCTURAL CONCRETE.
6. TMS 402/602 BUILDING CODE REQUIREMENTS AND SPECIFICATIONS
FOR MASONRY CONSTRUCTION
DESIGN LOADS
1. DEAD LOADS:
ROOF 20 PSF
FLOOR 125 PSF
2. LIVE LOADS:
FLOOR 115 PSF
3. SNOW LOADS:
GROUND SNOW LOAD, Pg 30 PSF
TERRAIN CATEGORY D
EXPOSURE FACTOR, Ce 0.80 THERMAL FACTOR, Ct 1.10 IMPORTANCE FACTOR, Is 1.10 FLAT ROOF SNOW LOAD, Pf 13.6 PSF SLOPE FACTOR, Cs 1.00 SLOPED ROOF SNOW LOAD, Ps 13.6 PSF MINIMUM SNOW LOAD, Pm 22.0 PSF
4. WIND LOADS:
BASIC WIND SPEED (3 SECOND GUST) 120 MPH
RISK CATEGORY III
WIND DIRECTIONALITY FACTOR, Kd 0.85
EXPOSURE CATEGORY C
TOPOGRAPHICAL FACTOR, Kzt 0.85
GUST EFFECT FACTOR 0.85
ENCLOSURE CLASSIFICATION ENCLOSED
INTERNAL PRESSURE COEFFICIENT, GCpi +/-0.18 VELOCITY PRESSURE COEFFICIENT. Kh/Kz 0.85 (EXP. C)
5. SEISMIC LOADS:
SHORT PERIOD ACCELERATION, SS 19.9%
ONE SECOND ACCELERATION, S1 6.3%
SITE CLASS D
RISK CATEGORY III
IMPORTANCE FACTOR, IE 1.25
SEISMIC DESIGN CATEGORY B
GENERAL NOTES
1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH OTHER
DRAWINGS. COORDINATE THE WORK OF OTHER DISCIPLINES,
INCLUDING BUT NOT LIMITED TO: THE REQUIREMENTS FOR SLEEVE
INSERTS, HOLES, HANGERS AND ANCHORS.
2. ALL BUILDING ELEVATIONS ARE GIVEN AS REFERENCE ELEVATIONS TO
THE FINISHED FIRST FLOOR ELEVATION.
3. VERIFY ALL DIMENSIONS AND CONDITIONS AFFECTING THE JOB SITE.
4. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DRAWINGS TO THE
CONTRACTING OFFICER'S REPRESENTATIVE (COR) PRIOR TO
BEGINNING WORK IN AREAS THAT WILL BE AFFECTED.
5. ALL STRUCTURAL WORK AND MATERIALS SHALL CONFORM TO THE
REQUIREMENTS OF THE PROJECT SPECIFICATIONS.
6. DO NOT SCALE DRAWINGS.
7. FOR ADDITIONAL INFORMATION, REFER TO INDIVIDUAL SHEETS FOR
EACH FLOOR, STRUCTURE OR FACILITY.
8. THE CONTRACTOR IS TO ACCEPT FULL RESPONSIBILITY FOR THE
STABILITY AND STRUCTURAL INTEGRITY OF THE EXISTING
STRUCTURES WITHIN AND ADJACENT TO THE WORKS.
9. WHERE CERTAIN FEATURES ARE NOT FULLY SHOWN OR DETAILED ON
THE CONTRACT DOCUMENTS, THEIR CONSTRUCTION IS OF THE SAME
CHARACTER AS FOR SIMILAR CONDITIONS THAT ARE FULLY SHOWN OR
DETAILED.
10. DETAILS NOTED AS 'TYPICAL' APPLY NOT ONLY WHERE SPECIFICALLY
INDICATED OR REFERENCED, BUT ALSO IN ALL OTHER CASES WHERE
THE NATURE OF THE CONSTRUCTION REQUIRE THEIR USE. DETERMINE
APPLICABILITY OF TYPICAL DETAILS FROM THE SIMILARITY OF A
CONSTRUCTION.
11. THE STRUCTURAL DRAWINGS CONTAINED HEREIN REPRESENT THE
FINISHED STRUCTURE. PROVIDE ALL TEMPORARY GUYING AND
BRACING REQUIRED TO HOLD THE STRUCTURE IN PROPER ALIGNMENT
UNTIL ALL STRUCTURAL WORK, INCLUDING CONNECTIONS, IS
COMPLETE. THE ANALYSIS, DESIGN, SAFETY, ADEQUACY, AND
INSPECTION OF ERECTION BRACING, SHORING, FORMWORK, AND
OTHER TEMPORARY SUPPORTS ARE THE SOLE RESPONSIBILITY OF
THE CONTRACTOR.
12. CONSTRUCTION MEANS, METHODS, TECHNIQUE, SEQUENCES AND
SUPERVISION OF THE WORK ARE THE SOLE RESPONSIBILITY OF THE
CONTRACTOR.
13. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS
SHOP DRAWINGS UNDER ANY CIRCUMSTANCES.
14. ALL DIMENSIONS ARE OUT TO OUT OF STRUCTURAL ELEMENTS AND DO
NOT INCLUDE THE ARCHITECTURAL TREATMENTS SUCH AS PLASTER,
CONCRETE AND MASONRY AND OPENINGS THAT ARE INDICATED ON
THE FACILITY DRAWINGS MAY VARY WITH THE EQUIPMENT PROVIDED.
15. THE CONTRACTOR SHALL COORDINATE OPENING REQUIREMENTS WITH
ALL DISCIPLINES.
16. MANUFACTURERS AND MODEL NUMBERS ARE LISTED TO ESTABLISH
REQUIRED QUALITY CHARACTERISTICS AND MATERIALS FOR ITEMS TO
BE PROVIDED. THEY ARE NOT INTENDED TO LIMIT COMPETITION. AN
APPROVED EQUAL PRODUCT MAY BE CONSIDERED AS APPLICABLE.
ABBREVIATIONS
BP BASE PLATE
BR BRACING
BCF BEAM- COLUMN- FLANGE
BCW BEAM - COLUMN- WEB
A. BLOCK
BOT. BOTTOM
BOW BOTTOM OF WALL
C CENTERLINE
CBB COLUMN - BEAM - BRACE
CL CLEARANCE
CMU CONCRETE MASONRY UNIT
CONN. CONNECTION
CONT. CONTINUOUS
DIA. DIAMETER
DN. DOWN
EA. EACH
ELEV. ELEVATION
FDN FOUNDATION
FF FINISHED FLOOR ELEVATION
FG FINISHED GRADE ELEVATION
GA GAUGE
GFT GROUND FIXED TILT
GP GUSSET PLATE
I MOMENT OF INERTIA (IN^4)
MAX MAXIMUM
MFA. MANUFACTURER
MIN MINIMUM
MPH MILES PER HOUR
O.C. ON CENTER
PROJ. PROJECTION
PL PLATE
PSF POUNDS PER SQUARE FOOT
TOC TOP OF CONCRETE ELEVATION
TOS TOP OF STEEL ELEVATION
TOW TOP OF WALL
T&B TOP AND BOTTOM
TH. THICK
TYP. TYPICAL
SDI STEEL DECK INSTITUTE
S SECTION MODULUS (IN^3)
WWF WELDED WIRE FABRIC
7 MARCH 23
rday RID CO Seal
5" CONCRETE SLAB
NON SHRINK GROUT
12" WIDE x 24" DEEP
CONTINUOUS FOOTING
24" WIDE x 24" DEEP
CONTINUOUS FOOTING
24" Ø x 24" DEEP
AUGERED FOOTING
CL CL
(1) #3 TIE AT 12"
ON CENTER.
(6) #5 CONTINUOUS
(1) #3 TIE AT 12"
ON CENTER.
(4) #5 CONTINUOUS
(1) #3 CONTINUOUS
IN CURB
PLACE CURB
MONOLITHICALLY
WITH SLAB
1/2" EXPANSION JOINT
MATERIAL
#4 CLOSED TIES @ 10"
ON CENTER
(6) #5 VERTICAL
COMPACTION & BACKFILL
PER GEOTECHNICAL
RECOMMENDATIONS.
STEEL POST BY SHELTER
SUPPLIER
NON SHRINK GROUT
1/2" EXPANSION JOINT
MATERIAL
STEEL POST BY SHELTER
SUPPLIER
SCALE:1 FOUNDATION SECTION
1/2" = 1'-0"
100'-0"
TOP OF SLAB
SCALE:3 ANCHORAGE DETAIL
1/2" = 1'-0"
CL
CL
10"
1" 4"
4" 1"
1" 4" 4" 1"
PL 10"x10"x1/2"
BY SHELTER SUPPLIER
5x5 HOLLOW
STRUCTURAL SECTION
BY SHELTER SUPPLIER
CONCRETE SLAB
HEAVY HEX NUT
WITH 14" PLATE WASHER
(4) 3/4" Ø F1554 GRADE 36
ANCHOR BOLT
1' -0
1/ 2"
NON SHRINK GROUT
NOTE: BASE PLATE IS AN EXEMPLAR.
ACTUAL PLATE MAY VARY.
5" CONCRETE SLAB
12" WIDE x 24" DEEP
CONTINUOUS FOOTING
(1) #3 TIE AT 12"
ON CENTER.
(4) #5 CONTINUOUS
SCALE:2 FOUNDATION SECTION
1/2" = 1'-0"
12" WIDE x 24" DEEP
CONTINUOUS FOOTING
(1) #3 TIE AT 12"
ON CENTER.
(4) #5 CONTINUOUS
(1) #3 CONTINUOUS
IN CURB
PLACE CURB
MONOLITHICALLY
WITH SLAB
(1) #3 CONTINUOUS
IN CURB
PLACE CURB
MONOLITHICALLY
WITH SLAB
CL CL
COMPACTION & BACKFILL
PER GEOTECHNICAL
RECOMMENDATIONS.
NON SHRINK GROUT
(1) #5 BAR TO MATCH
VERTICAL WALL
REINFORCING. BENT AS
SHOWN
SCALE:4 CMU WALL PLAN AND ELEVATION
1/2" = 1'-0"
#5 DOWELS SPACED TO
MATCH CMU REINFORCING
PROVIDE HORIZONTAL JOINT LADDER
REINFORCING AT 16" OC.
USE PREFABRICATED CORNERS
AT WALL CORNERS.
CL CL
(1) #5 VERTICAL AT 32" ON CENTER
6' -8
(1) #5 VERTICAL AT 32" ON CENTER
(1) #5 HORIZONTAL AT
BOND BEAM
8"
48"
" M
IN
STRUCTURAL DETAILS - SHELTER
SE501
43 47
RIDALK
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : P
:\G
OR
D1 -2
1 I
FS
N
AT
CH
EZ
B
UR
IA
L E
XP
AN
SI
ON
\D
RA
W
IN
GS
\S
HE
ET
S\
SE
1 S
TR
UC
TU
RA
L D
ET
AI
LS
.D
W G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GRITY FEDERA
L
SERV I CES
0'
SCALE: 1/2" = 1'-0"
4'2'1'
7 MARCH 23
rday RID CO Seal
GENERAL NOTES
PC
#4
EX OR CX
ST-4
SL
UF
4P
K
(2#12+#12 GRD)1/2"C
P1-1
WP
GFI
15A
A
FUTNG-1
A1,3
KWH
M
M
350 AT
400 AF
30A 2P
ELECTRICAL POWER LEGEND
J
X
PRIMARY DISTRIBUTION LEGEND SECONDARY DISTRIBUTION LEGEND
EXTERIOR ELECTRICAL LEGEND
UNDERGROUND ELECTRICAL FEEDER - QUANTITY,
SIZE, AND VOLTAGE RATING OF PHASE AND NEUTRAL
CONDUCTORS AS INDICATED
ELECTRICAL ABBREVIATIONS
DUPLEX RECEPTACLE - 2P,3W GROUNDING TYPE RECEPTACLE, 125V, NUMERAL
ADJACENT IDENTIFIES CURRENT RATING IN AMPS (NO DESIGNATION INDICATES
20A) GFI INDICATES DEVICE WITH INTEGRAL GROUND FAULT PROTECTION, WP
INDICATES WEATHERPROOF, UPS INDICATES SURGE PROTECTIVE (TVSS)
RECEPTACLE SOURCE BACKED BY UPS.
BRANCH CIRCUIT AND FEEDER WIRING. ARROWS AND LETTER/NUMERALS
IDENTIFY ABV. GRADE HOME-RUN CIRCUITS. ALL CONDUIT SHALL CONTAIN A
GREEN INSULATED GROUND WIRE SIZED IN ACCORDANCE WITH 2005 NEC TABLE
250.122, UNLESS OTHERWISE NOTED.
2P, 3W GROUNDING TYPE RECEPTACLE - 125V, CONVENTIONAL DUPLEX, NEMA 5-20R.
RECEPTACLE COVERPLATE SHALL BE PROVIDED WITH LABEL STATING "COMPUTER".
X: "EM"-CONNECTED TO EMERGENCY CIRCUIT, "NR"-CONNECTED TO NORMAL CIRCUIT.
GENERAL LEGEND
CONTROL INTERFACE OR OPERATING RELATIONSHIP BETWEEN
2 OR MORE DEVICES (KEY INTERLOCK BETWEEN SWITCHES)
DASHED LINES UNDERGROUND (UNLESS OTHERWISE NOTED)
NEW
AREA DEMOLITION (GENERAL)
OVERHEAD ELECTRIC DEMOLITION
UNDERGROUND ELECTRIC DEMOLITION
KEY NOTES
MOLDED CASE CIRCUIT BREAKER, FIXED TRIP. THREE POLE
UNLESS DESIGNATED '1P' OR '2P'
MOLDED CASE CB OF A GIVEN FRAME SIZE WITH
ADJUSTABLE TRIP SETTINGS
MOTOR - EQUIPMENT SCHEDULE IDENTIFICATION AS
SHOWN.
DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED IN
SCHEDULE.
MOTOR STARTER, TYPE AND SIZE AS INDICATED IN
SCHEDULE.
COMBINATION STARTER W/ EXTERNALLY OPERATED
DISCONNECT.
UNDERGROUND DUCT LINE, CONCRETE ENCASED NUMERAL INDICATES QUANTITY
OF DUCTS (4" MIN. IF NOT IDENTIFIED, FOR COMM. TYP, 5" FOR ELEC. TYP.) LETTER
"P" INDICATES ELECTRICAL POWER LINE, "C" A COMMUNICATIONS TYPE LINE.
MANHOLE OR HANDHOLE - NUMBER DESIGNATION AS
INDICATED: E - ELECTRICAL, C - COMMUNICATION
GROUNDING SYSTEM - ELECTRODE AND CONDUCTOR
(BARE COPPER) - SIZE AS INDICATED
STREET LIGHTING FIXTURE, FIXTURE TYPE AS NOTED FUT - INDICATES FUTURE
LIGHTING FIXTURE LOCATION "NG-1" - POWER SOURCE (PANEL AND CIRCUIT NO.)
STREET LIGHTING FIXTURE, FIXTURE TYPE AS NOTED 1,3 - INDICATES CIRCUIT
NUMBER
KILOWATT HOUR METER
NEW WORK
EXISTING
VARIABLE FREQUENCY DRIVE
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
NORMALLY CLOSED MOMENTARY PUSHBUTTON
NORMALLY OPEN MOMENTARY PUSHBUTTON
POWER DISTRIBUTION PANEL WITH MAIN CIRCUIT BREAKER
CONDUIT RUN - SCHEMATIC DIAGRAM
CONDUIT SIZE
QUANTITY OF GROUND WIRES
QUANTITY OF PHASE AND NEUTRAL WIRES
CONTACTOR
LIGHTING CONTROL CABINET
CONDUIT TURNING TOWARD VIEWER
CONDUIT TURNING AWAY FROM VIEWER
CEILING MOUNTED DUPLEX RECEPTACLE OUTLET
FLOOR DUPLEX RECEPTACLE OUTLET
FLOOR DOUBLE DUPLEX RECEPTACLE OUTLET
JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISE
SECONDARY UNDERGROUND FEEDER, DIRECT BURIAL DUCT LINE
STREET LIGHTING, DIRECT BURIAL DUCT LINE
ELECTRICAL EQUIPMENT IN PAD MOUNTED CABINET OR EQUIP.
ASSEMBLY - TYPE AND NUMBER DESIGNATION AS INDICATED:
ST-4, - SWITCH STATION NUMBER 4
SEC, - SECONDARY RACK MOUNTED EQUIPMENT
CONDUIT STUB-OUT
PHOTOELECTRIC CONTROL RELAY
ELECTRICAL POWER DISTRIBUTION POLE
POLE NUMBER
GUY WIRE
EXISTING PAD MOUNTED TRANSFORMER
ELECTRIC METER
CONCRETE PAD MOUNTED TRANSFORMER INSTALLATION
ANSI (C84.1) VOLTAGE CONFIGURATION AS INDICATED.
A-AMP AMPERE
ABV ABBREVIATION
AL ALUMINUM
AIC AMPS INTERRUPTING CAPACITY (SYM RMS)
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AS AMMETER SWITCH
AWG AMERICAN WIRE GAGE
AUX AUXILIARY
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CL CENTER LINE
CONC CONCENTRIC
CONT CONTINUOUS
COR CONTRACTING OFFICER'S REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CU COPPER
DET DETAIL
DIM DIMENSION
DISC DISCONNECT
DWG DRAWING
E EAST
ELEC ELECTRICAL OR ELECTRIC
ENCL ENCLOSURE
ENT ENTRANCE
EQUIP EQUIPMENT
EXC EXCAVATE
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FDN FOUNDATION
FIG FIGURE
FIN FINISH
FLEX FLEXIBLE
FUT FUTURE
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND OR GRD GROUND
G.O. GANG OPERATED
GOVT GOVERNMENT
GRC GALVANIZED RIGID STEEL CONDUIT
HID HIGH INTENSITY DISCHARGE
HMI HUMAN-MACHINE INTERFACE
J-BOX JUNCTION BOX
K KEY
KCMIL KILO CIRCULAR MIL
KV KILOVOLTS
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOURS
KVAR KILOVOLT AMPERES REACTIVE
LTG LIGHTING
MGB MAIN GROUNDING BUSBAR
MH MANHOLE
MSS MAIN SWITCH STATION
MTD MOUNTED
N NORTH
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELEC MANUFACTURES ASSOC,
NIC NOT IN CONTRACT
NIPRNET NONCLASSIFIED INTERNET PROTOCOL
ROUTER
NO NORMALLY OPEN, NUMBER
OD OUTSIDE DIAMETER
O.C.A. ON CENTER
PART PARTIAL
PNL PANEL
PF POWER FACTOR
PFCS POWER FACTOR CORRECTION STATION
PH PHASE
PSS PRIMARY SWITCH STATION
PVC POLYVINYL CHLORIDE
RCPT RECEPTACLE
REF REFERENCE
REQD REQUIRED
S SOUTH
SEC SECONDARY
SIPRNET SECRET INTERNET PROTOCOL ROUTER
NETWORK
SPEC SPECIFICATIONS
ST SWITCH STATION
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TGB / TGBB TELECOM GROUNDING BUSBAR
TR TELECOMMUNICATION ROOM
TYP TYPICAL
UG UNDERGROUND
UPS UNINTERRUPTIBLE POWER SUPPLY
URD UNDERGROUND RESIDENTIAL DISTRIBUTION
V VOLT
VA VOLT AMPERE
W WEST
W/ WITH
WP WEATHERPROOF
WPF WATERPROOF
XMFR TRANSFORMER
LIGHTING AND APPLIANCE TYPE PANELBOARD. - SURFACE MOUNTED
SPECIAL RECEPTACLE, PROVIDE RECEPTACLE CONFIGURATION NOTEDVFD
3# 2/0,15KV + #2/0,600V N
(NOT ALL ABBREVIATIONS REQUIRED FOR THIS PROJECT)
EXISTING
UPS
A A
A A
AA
A
A
A A
LIGHTING SYMBOLS
SUSPENDED MTD. CAN LIGHTS. UPPER CASE LETTER
IDENTIFIES FIXTURE TYPE. DARKENED AREA INDICATES
EMERGENCY POWERED.
WALL MOUNTED COMPACT FLUORECENT, LED OR H.I.D.
LUMINAIRE, UPPER CASE LETTER IDENTIFIES FIXTURE
TYPE. DARKENED AREA INDICATES EMERGENCY
POWERED.
RECESS MOUNTED LED FIXTURE. UPPER CASE LETTER
DESIGNATES THE FIXTURE TYPE. DARKENED AREA
INDICATES EMERGENCY POWERED.
SURFACE MOUNTED LED FIXTURE W/ UPPER CASE LETTER
DESIGNATES THE FIXTURE TYPE. DARKENED AREA
INDICATES EMERGENCY POWERED.
WALL(SURFACE) MOUNTED LED FIXTURE W/ LENS. UPPER
CASE LETTER DESIGNATES THE FIXTURE TYPE. DARKENED
AREA INDICATES EMERGENCY POWERED.
2'X4' RECESS MOUNTED LED FIXTURE. UPPER CASE
LETTER DESIGNATES THE FIXTURE TYPE. DARKENED AREA
INDICATES EMERGENCY POWERED.
STRIP LIGHT LED FIXTURE W/ UPPER CASE LETTER
DESIGNATES THE FIXTURE TYPE. DARKENED AREA
INDICATES EMERGENCY POWERED.
SINGLE POLE SWITCH, 48" AFF
PHOTOSENSOR FOR DAYLIGHTING CONTROL
A
A
A A
PS
1. ALL PANELS SHOWN IN BOLD ARE BEING MODIFIED OR
REPLACED. PANELS SHOWN IN LIGHT COLOR ARE FOR
REFERENCE BUT ARE NOT A PART OF THIS PROJECT.
2. CONTRACTOR TO CLEAN ALL AREAS OF WORK UPON
COMPLETION, INCLUDING BUT NOT LIMITED TO: ALL EXISTING
EQUIPMENT, FIXTURES, LIGHTS, WINDOWS, BLINDS, AND
REGISTERS.
3. CONTRACTOR ENCOURAGED TO VISIT ALL AREAS OF WORK,
INCLUDING WALKING THE SITE, MEASURING EXISTING
DIMENSIONS AND OBSERVING EXISTING CONDITIONS BEFORE
BIDDING WORK, ORDERING MATERIALS, AND/OR STARTING
ANY CONSTRUCTION WORK.
4. UNLESS NOTED OTHERWISE, ALL MATERIALS TO BE REMOVED
SHALL BE THE PROPERTY OF THE CONTRACTOR. DISPOSE OF
ALL WASTE MATERIAL IN APPROVED MANNER AND LOCATION,
COORDINATE MATERIALS FOR SALVAGE AND RECYCLING
WITH COR. THE CONTRACTOR SHALL USE ONLY DESIGNATED
PATHWAYS AS ESTABLISHED BY THE VA OR NCA TO REMOVE
ITEMS AND MATERIALS FROM THE PROJECT BUILDING AND
SITE.
5. CONTRACTOR TO COMPLETE WORK DURING BUSINESS
HOURS WHENEVER POSSIBLE. COORDINATE WITH COR FOR
ACCEPTABLE WORK HOURS. THE WORK IS TO NOT
INTERFERE WITH FACILITY OPERATIONS. THOSE AREAS THAT
NEED TO BE COMPLETED AFTER HOURS TO BE COORDINATED
WITH COR.
6. CONTRACTOR TO USE ONLY APPROVED STAGING AREA FOR
STORAGE OF CONSTRUCTION MATERIALS.
7. THE EXTENT OF DEMOLITION AND RENOVATION WORK AS
INDICATED IN THESE DRAWINGS SHALL BE REVIEWED AND
COORDINATED WITH THE VA COR PRIOR TO THE
COMMENCEMENT OF WORK IN ORDER TO DETERMINE THE
FULL EXTENT OF WORK TO BE PERFORMED BY THE
CONTRACTOR.
8. PROCEED WITH CARE AND CAUTION DURING DEMOLITION TO
AVOID AND MINIMIZE DAMAGE TO EXISTING CONSTRUCTION,
MATERIALS, SYSTEMS AND FINISHES TO REMAIN.
9. THE NCA'S INTERNAL REVIEW POLICY SHALL BE VERIFIED AND
IMPLEMENTED THROUGHOUT CONSTRUCTION.
10. CONTRACTOR SHALL COMPLY WITH ALL CURRENT
APPLICABLE CODES AND STANDARDS.
11. CONTRACTOR SHALL PROTECT AND MAINTAIN ALL EXISTING
BUILDING SYSTEMS INCLUDING ALL SYSTEMS PASSING
THROUGH AND ADJACENT TO AREAS REQUIRED; INCLUDING,
BUT NOT LIMITED TO, WIRING, CONDUITS, PIPING, DUCTWORK,
AND OTHER UTILITIES TO SERVE OCCUPIED AREAS.
12. COORDINATE WITH COR AND COMPLY WITH THEIR
REGULATIONS FOR UTILITY SHUT DOWN, NOISE AND
VIBRATION.
13. PROVIDE SEALANT AROUND ALL ELECTRICAL OUTLETS,
PLUMBING FIXTURES, PIPING, AND EQUIPMENT ABUTTING OR
PENETRATING A WALL OR PARTITION INCLUDING
FIRESTOPPING AT FIRE RATED ASSEMBLES.
14. CONDUIT SHALL BE CONTINUOUS AND COMPLETE BETWEEN
PANELS, JUNCTION, OUTLET, PULL AND FIXTURE BOXES. IT
SHALL BE KEPT CLEAN AND UNOBSTRUCTED INSIDE WITH
ENDS FREE OF BURRS AND OTHER PROJECTIONS WHICH
WOULD DAMAGE OR IMPEDE PULLING OF WIRE. ALL CONDUIT
SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO THE
BUILDING LINES. ALL CONDUIT SHALL BE ROUTED
CONCEALED IN FINISHED AREAS EXCEPT WHERE OTHERWISE
NOTED.
15. UNLESS OTHERWISE NOTED, ALL WIRES AND CABLES SHALL
BE CONTINUOUS WITHOUT SPLICES OR TAPS IN CONDUIT
RUNS. ALL WIRING SHALL BE IN CONDUIT OR AS NOTED. ALL
SPLICES SHALL BE MADE AT OUTLET BOXES, PULL BOXES OR
JUNCTION BOXES. AT ALL JOINTS, CONDUCTORS SHALL BE
SPLICED OR JOINED AS TO BE MECHANICALLY AND
ELECTRICALLY SECURE.
16. WIRE SHALL NOT BE DRAWN INTO CONDUIT UNTIL ALL WORK
WHICH COULD CAUSE INJURY TO THE CONDUCTORS IS
COMPLETE.
17. ALL MATERIAL SHALL CONFORM TO NEMA, ANSI AND U.S.
STANDARDS, WHICHEVER APPLIES AND SHALL BEAR THE
INSPECTION LABEL OF UNDERWRITER LABORATORIES, INC.
18. ALL BOXES AND ENCLOSURES SHALL BE SET PLUMB, SQUARE
AND SECURELY FASTENED. BOXES IN FINISHED WALLS SHALL
BE FLUSH WITH FINISH SURFACE.
19. TEMPORARY SHUTDOWNS SHALL BE SCHEDULED WITH
CONTRACTING OFFICER THREE (3) WEEKS IN ADVANCE SO AS
NOT TO INTERFERE WITH NORMAL DAYTIME OPERATIONS
AND AT NO ADDITIONAL COST.
20. PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR ALL PANELS
INSTALLED OR MODIFIED UNDER THIS CONTRACT.
21. ALL ELECTRICAL WORK SHALL BE IN STRICT COMPLIANCE
WITH THE CURRENT EDITION OF THE NEC AS ADOPTED BY
THE LOCAL JURISDICTION INCLUDING ANY LOCAL
AMENDMENTS, ORDINANCES, AND INTERPRETATIONS.
ELECTRICAL WORK SHALL ALSO COMPLY WITH ANY
APPLICABLE FEDERAL AND STATE REGULATIONS.
22. COORDINATE INSTALLATION OF CONDUIT WITH OTHER
TRADES AND EQUIPMENT SUPPLIERS AS REQUIRED PRIOR TO
ROUGH-IN.
23. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
CUTTING AND CORE DRILLING ALL PENETRATIONS THROUGH
FLOORS,WALLS, ETC.
24. IT IS NOT INTENDED THAT THE PLANS INDICATE ALL CONDUIT
ROUTES, PULL BOXES, ETC. ELECTRICAL CONTRACTOR SHALL
BE RESPONSIBLE FOR DETERMINING ACTUAL CONDUIT
ROUTING, QUANTITY, AND LOCATION OF PULL BOXES WITHIN
ACCESSIBLE LOCATIONS. PROVIDE SCREW-COVER PULL
BOXES IN CONDUIT RUNS AS REQUIRED TO LIMIT NUMBER OF
BEND TO NO MORE THAN THREE (3) OR 270 DEGREES TOTAL.
SIZE PULL BOXES IN ACCORDANCE WITH NEC. DOCUMENT ON
RECORD DRAWINGS THE SIZE AND LOCATION OF PULL BOXES
USED IN FEEDER CONDUIT RUNS.
25. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
ABOUT QUALITY AND GENERAL INSTALLATION
REQUIREMENTS OF ELECTRICAL CONSTRUCTION MATERIALS,
ITEMS, AND DEVICES.
26. CONDUIT RUNS ARE SHOWN FOR REFERENCE AND BIDDING
PURPOSES ONLY. CONTRACTOR SHALL VERIFY EXISTING
FIELD CONDITIONS AND DETERMINE SHORTEST AND LEAST
DISRUPTIVE ROUTE FOR CONDUIT RUNS. COORDINATE WITH
OTHER TRADES AND CONFIRM ROUTE SELECTION WITH
OWNER PRIOR TO BID. ANY DEVIATIONS FROM DRAWINGS
SHALL BE SHOWN IN DETAIL ON AS-BUILT DRAWINGS BY
CONTRACTOR.
27. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. SIZE AND
LOCATION OF EQUIPMENT AND WIRING ARE SHOWN TO SCALE
WHERE POSSIBLE, BUT MAY BE DISTORTED FOR CLARITY ON
THE DRAWINGS. FINAL LOCATIONS OF OUTLETS AND
EQUIPMENT SHALL BE AS SHOWN IN ENLARGED DETAILS OR
AS APPROVED BY THE ARCHITECT.
28. THE PLANS DO NOT INDICATE ALL THE NECESSARY BENDS,
OFFSETS, PULL BOXES AND OBSTRUCTIONS. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK
TO CONFORM TO THE STRUCTURE, MAINTAIN HEADROOM
AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
29. GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY
MEANS OF AN INSULATED GROUNDING CONDUCTOR
INSTALLED WITH FEEDER CONDUCTORS IN ALL CONDUITS
WHETHER OR NOT INDICATED ON DRAWINGS. PROVIDE
GROUNDING CONDUCTOR IN ALL TELEPHONE AND CATV
SERVICE CONDUITS.
30. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR THE
PROPER INSTALLATION OF THE NEW ELECTRICAL WORK. ALL
PATCHING SHALL BE OF THE SAME MATERIALS,
WORKMANSHIP, AND FINISH AND SHALL ACCURATELY MATCH
ALL ADJACENT WORK.
31. PLAN INSTALLATION OF NEW WORK AND CONNECTIONS TO
EXISTING WORK TO ENSURE MINIMUM INTERFERENCE WITH
REGULAR OPERATION OF EXISTING FACILITIES. ALL SYSTEM
SHUTDOWNS AFFECTING OTHER AREAS SHALL BE
COORDINATED WITH VA COR. ALARM, EMERGENCY AND LIFE
SAFETY SYSTEMS SHALL NOT BE INTERRUPTED OR
COMPROMISED.
32. CLEAN UP RESULTANT DEBRIS FROM THIS WORK AND
REMOVE FROM THE SITE. DISCONNECT AND REMOVE ALL
TEMPORARY POWER INCLUDING BUT, NOT LIMITED TO
PANELS, FIXTURES, BOXES AND WIRING.
33. TEST FOR GROUNDS AND SHORTS, TO ENSURE PROPER
OPERATION OF ELECTRICAL EQUIPMENT. REPAIR OR
REPLACE FAULTY EQUIPMENT AT NO ADDITIONAL COST TO
THE VA.
34. CONDUCTOR SIZES CALCULATED USING COPPER
CONDUCTOR. ALUMINUM CONDUCTORS ARE NOT
ACCEPTABLE..
ELECTRICAL GENERAL NOTES
EI001
N/A
WBRMMM
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : P
:\G
OR
D1 -2
1 I
FS
N
AT
CH
EZ
B
UR
IA
L E
XP
AN
SI
ON
\D
RA
W
IN
GS
\S
HE
ET
S\
EI
1 E
LE
CT
RI
CA
L G
EN
ER
AL
N
OT
ES
.D W
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
jlandrith CO - No Date jlandrith Typewriter
7 MAR 2023
W W
W
W
W
W
W
E/U E/U E/U
E/U
EU
EU
WP
GFCI
WP
GFCI
B
A
A
P1-5
P1-1
PS B
VAC
A
P1-3
PANEL: P1 AES GROUP, INC. STATUS: NEW
208Y/120V BUS: 125A COPPER LOCATION: COMMITTAL SHELTER
3Ø,4W+GND MAINS TYPE: MCB 100A SUPPLY FROM:
10kAIC MOUNTING: SURFACE
ENCLOSURE: NEMA 3R
DESCRIPTION P BKR CKT A B C CKT BKR P DESCRIPTION
SERVICE RECEPTACLE 1 20 1 1000 2 SPACE
TAPS PLAYER (GEN REC) 1 20 3 540 4 SPACE
LIGHTING 1 20 5 100 6 SPACE
SPARE 1 20 7 0 8 SPACE
SPARE 1 20 9 0 10 SPACE
SPACE 11 12 SPACE
SURGE SURPRESSOR 3 / 13 0 14 SPACE
- - - / / 15 0 16 SPACE
- - - / / 17 0 18 SPACE
1000 0 540 0 100 0
ANY DOWNSTREAM LOADS ARE INCLUDED IN TOTALS BELOW:
CONNECTED LOAD: CATEGORY CONNECTED LOAD FACTOR DEMAND LOAD AMPS AT 208Y/120 VOLTS
PHASE VA LIGHTING 100 125% 125 0
A PHASE 1,000 RCPTS (1ST 10kVA) 1,540 100% 1,540 4
B PHASE 540 RCPTS (>10kVA) 0 50% 0 0
C PHASE 100 MOTOR 0 100% 0 0
LARGEST MOTOR 0 25% 0 0
TOTAL 1,640 MISC 0 125% 0 0
TOTAL 1,640 1,665 5
LUMINAIRE SCHEDULE
TYPE LAMPS DESCRIPTION
VOLTAGE
WATTS
COLOR
TEMPERATURE
COLOR RENDERING
INDEX LUMENS BULB TYPE
A LED
AIRCRAFT CABLE OR HOOK AND CORD
SUSPENDED, LOW BAY, LED DOWNLIGHT*
120-277V
27W
4000K 70≤ 3500 LED
B LED 4' LED WALL MOUNTED STRIPLIGHT
120-277V
30W
3500K 70≤ 3000 LED
*NOTE
DEPENDING ON THE ATTACHMENT METHOD AND LIGHT FIXTURE CONSTRUCTION, PROVIDE ALL THE REQUIRED SUPPORTS, BOXES, RECEPTACLES, AND ANCILLARIES FOR THE COMPLETE ON/OFF OPERATION OF THE LIGHTING FIXTURE.
CONCRETE
FOUNDATION IN
DIRECT CONTACT
WITH EARTH
25' OF BARE FULL SIZE GROUNDING
ELECTRODE CONDUCTOR
EMBEDDED IN CONCRETE
FOUNDATION EXOTHERMICALLY
WELD TO FOUNDATION STEEL,
1/2-INCH DIAMETER OR LARGER, AT
TWO (2) LOCATIONS.
DRIVEN GROUND ROD ON
BUILDING EXTERIOR IN
AN AREA EXPOSED TO
MOISTURE.
EXOTHERMICALLY
WELDED
BARE FULL SIZE GROUNDING
ELECTRODE CONDUCTOR.
GROUNDING ELECTRODE
CONDUCTOR IN CONDUIT,
SIZED PER NEC 250.66
REBAR
EXOTHERMICALLY
WELDED (TYP)
BUILDING STEEL WHERE
EFFECTIVELY GROUNDED
TO EMBEDDED
FOUNDATION STEEL.
GROUND CLAMP SIZE
AS REQUIRED WITH
CONDUIT HUB AND
CABLE CLAMP.
GROUND CLAMP SIZE
AS REQUIRED WITH
CONDUIT HUB.
GROUNDING
JUMPER AROUND
INSULATING JOINTS.
METALLIC COLD WATER
SERVICE ENTRANCE
METALLIC FIRE RISER
SERVICE ENTRANCE
GROUND CLAMP
SIZE AS REQUIRED
WITH CONDUIT HUB.
GROUNDING JUMPER
AROUND INSULATING
JOINTS.
#4 AWG
MGB (MAIN GROUND
BAR)
NOTE: NOT ALL ITEMS
MAY BE PRESENT TO
BOND AT SPECIFIC
SITE.
EP101
N/A
WBRMMM
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : P
:\G
OR
D1 -2
1 I
FS
N
AT
CH
EZ
B
UR
IA
L E
XP
AN
SI
ON
\D
RA
W
IN
GS
\S
HE
ET
S\
EP
1 E
LE
CT
RI
CA
L P
OW
ER
P
LA
N.
DW
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
SHEET NOTES:
1. COORDINATE INSTALLATION WITH ALL TRADES PRIOR
TO COMMENCEMENT OF WORK.
2. UNDERGROUND UTILITIES SHOWN ON PLAN HAVE BEEN
INTERPRETED FROM PDF AS-BUILTS PROVIDED BY THE
VA. FIELD VERIFY EXACT LOCATIONS AND TIE IN POINTS.
KEY NOTES:
1. EXISTING UNDERGROUND ELECTRICAL FEED AND
STUB UP LOCATED BENEATH PANEL 'P1'.
2. PROVIDE NEW WALL MOUNTED PANEL 'P1'. LOCATE
PANEL ABOVE AND UTILIZE STUB UP AND
CONDUCTOR (PROVIDED BY PROJECT ROAD
EXPANSION 866CM3029). PROVIDE SERVICE
RECEPTACLE AND WEATHERPROOF WHILE-IN-USE
COVER UNDERNEATH THE PANEL. DRIVE A NEW
GROUND ROD UNDERNEATH THE PANEL FOR
GROUNDING CONNECTION. REFER TO DETAIL 2 THIS
SHEET FOR THE MINIMUM PANEL SCHEDULE
REQUREMENTS.
3. PROVIDE HORIZONTALLY MOUNTED CONVENIENCE
RECEPTACLE MOUNTED AT 48"AFF. PROVIDE
HORIZONTAL WEATHERPROOF WHILE IN USE COVER.
4. PROVIDE LISTED BEAM CLAMP TO MOUNT LIGHTING.
REFER TO ARCHITECTURAL DRAWINGS FOR
PLACEMENT. CONCEAL CONDUIT AND ROUTE
CONDUIT AS NEAR AND PARALLEL TO THE
STRUCTURE AS POSSIBLE. PAINT EXPOSED CONDUIT
TO MATCH SURROUNDING STRUCTURE OR FINISH.
5. PROVIDE EXTERIOR, SEPARATELY MOUNTED,
PHOTOSENSOR CONTROL OF COMMITTAL SHELTER
(TYPE A) LIGHTING. PROVIDE MANUAL ON/OFF
OVERRIDE OF AUTOMATIC PHOTOSENSOR CONTROL
LOCATED WITHIN STORAGE CLOSET.
6. PROVIDE INTEGRAL VACANCY (VAC) SENSOR SWITCH
TO CONTROL FIXTURE 'B'. SENSOR SHOULD BE
CAPABLE OF PRESS ON, AUTOMATIC OFF
FUNCTIONALITY.
7. PROVIDE EXTERIOR, WALL MOUNTED, 15W MINIMUM,
PASSIVE SPEAKER FOR TAPS SYSTEM. PROVIDE
COMPATIBLE INTERIOR MOUNTED, CLASS-D
AMPLIFIER AND MANUFACTURER RECOMMENDED
TRANSFORMER. ROUTE SPEAKER WIRE CONCEALED
ALONG THE STRUCTURE. FINAL SPEAKER SELECTION
SUBJECT TO VA APPROVAL. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS.
8. PROVIDE INTERIOR, WALL MOUNTED, CORD AND PLUG
CONNECTED, AUDIO RECORDER/PLAYBACK SYSTEM
(TAPS SYSTEM) WITH EXTERIOR, WALL MOUNTED,
PLAY BUTTON. COORDINATE LOCATION OF PLAY
BUTTON WITH THE COR IN THE FIELD. PLAYER SHALL
BE LOW POWER AMPLIFICATION AND CAPABLE OF
AUXILIARY AND BLUETOOTH CONNECTION TO AUDIO
INPUT DEVICES. FINAL DEVICE SELECTION SUBJECT
TO VA APPROVAL. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
N 0' 5' 10'
SCALE: 1" = 5'
SCALE:1 ENLARGED ELECTRICAL SITE PLAN
1" = 5'
ELECTRICAL POWER PLAN
- EAST
SCALE:2 PANEL SCHEDULE
NONE
SCALE:3 LIGHTING SCHEDULE
NONE
SCALE:4 GROUNDING DETAIL
NONE
jlandrith Typewriter
7 MAR 2023
jlandrith CO - No Date
EU
EU
EU
M
BOND 5TH JAW TO NEUTRAL AS
INDICATED BY THE
MANUFACTURER IF A 5TH JAW
S REQUESTED BY THE UTILITY
LOAD
PH 1 PH 2
PROVIDE UL LISTED, 100A, NEMA 3R,
SELF CONTAINED METER SOCKET.
COORDINATE THE NEED FOR A
MECHANICAL GANG-OPERATED
BYPASS SWITCH WITH THE UTILITY
COMPANY. COMBINATION METER
PANELS SHALL BE ALLOWED WITH
PRIOR CONSENT OF THE UTILITY
COMPANY.
NEUTRAL
SOURCE
POLE-MOUNTED SERVICE
XFMR PROVIDED AND
INSTALLED BY UTILITY
UTILITY INSTALLED CUSTOMER
SUPPLIED RISER ON THE POLE.
COORDINATE WITH UTILITY
FOR THE REQUIREMENTS OF
PULLING CONDUIT. ASSUME
PULLING THE ENTIRE LENGTH
OF THE CONDUIT RUN UP THE
POLE WHEN PRICING.
7" FROM BASE OF POLE
PROVIDE 2.5" GRAY SCHEDULE 80PVC
CONDUIT FOR EACH CONDUCTOR SET
36" RADIUS 90 DEGREE SCHEDULE 80 PVC
ELBOW OR EQUIVALENT
FLOOR
BOND
STRUCTURE TO
LIGHTNING
PROTECTION
SYSTEM IN
ACCORDANCE
WITH NFPA 780
CHANNEL
CROSS MEMBER
" M
AX
" M
IN
PANEL 1
LOCKABLE
ENCLOSURE
2.5"
CONDUIT
TO DOWNSTREAM LOADS
METER
TO POLE MOUNTED
UTILITY TRANSFORMER
WEATHERPROOF
WHILE IN USE
RECEPTACLE
SIZE AS REQUIRED
AND DESCRIBED IN
THESE DRAWINGS
PROVIDE GROUND ROD
OR GROUNDING PLATE
PROVIDE GROUND ROD
OR GROUNDING PLATE
SPACE GROUND RODS 6' APPART
EP102
N/A
MMMJL
SHEET NOTES:
1. DETAILS ARE BASED ON THE MOST CURRENT
ELECTRICAL SERVICE DETAILS PROVIDED BY THE
LOCAL UTILITY. FINAL INSTALLATION REQUIREMENTS
SHALL BE COORDINATED AND DETERMINED BY THE
UTILITY PROVIDER IN THE FIELD. RECEIVE WRITTEN
APPROVAL FROM THE UTILITY PROVIDER PRIOR TO
PURCHASE OF EQUIPMENT AND COMMENCEMENT OF
ANY WORK.
2. EXACT LOCATION OF UTILITY POLES, ROADWAYS,
FENCES, ETC. SHALL BE VERIFIED IN THE FIELD PRIOR
TO COMMENCEMENT OF ANY WORK.
N 0' 400'200'
SCALE: 1" = 200'
ELECTRICAL POWER PLAN
SCALE:1 ELECTRICAL POWER PLAN
1" = 200'
KEY NOTES:
1. PROPOSED LOCATION OF NEW CONNECTION POINT
TO EXISTING UTILITY POLE. COORDINATE WITH LOCAL
UTILITY FOR NEW ELECTRICAL CONNECTION TO
EXISTING OVERHEAD LINES. SEE DETAIL 2 ON THIS
SHEET FOR ADDITIONAL INFORMATION.
2. TRENCH ELECTRICAL SERVICE UNDERGROUND IN
MINIMUM 2.5" CONDUIT TO NEW PEDESTAL MOUNT.
PROVIDE 3-WIRE #4 COPPER WIRE AND INSTALL IN
ACCORDANCE WITH UTILITY PROVIDER'S
REQUIREMENTS.
3. PROVIDE STRUT RACK FOR USE AS A SERVICE
PEDESTAL IN MOUNTING UTILITY METER AND SERVICE
PANEL. SEE DETAIL 4 ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE FINAL LOCATION OF
RACK IN THE FIELD WITH THE VA AND THE UTILITY
PROVIDER.
4. PROVIDE NEMA-3R, 100A, SERVICE RATED PANEL
CONFIGURED AS INDICATED IN THE PANEL
SCHEDULES.
5. PROVIDE 3-WIRE, #12, SINGLE PHASE CONNECTION TO
NEW BOOSTER IRRIGATION PUMP. ROUTE CONDUIT
UNDERGROUND AND COORDINATE WITH MECHANICAL
TRADE IN THE FIELD FOR FINAL LOCATION OF
BOOSTER PUMP.
6. PROVIDE NEUTRAL TO GROUND BOND AND
GROUNDING ELECTRODE CONDUCTOR IN
ACCORDANCE WITH ARTICLE 250.25. CONNECTION
CAN BE MADE WITHIN THE METER OR SERVICE PANEL.
COORDINATE WITH THE UTILITY COMPANY FOR
INSTALLATION WITHIN THE METER HOUSING.
7. COORDINATE INSTALLATION REQUIREMENTS WITH
THE UTILITY PROVIDER FOR INSTALLATION OF
ADDITIONAL GROUNDING ELECTRODE FROM THE
POLE MOUNTED TRANSFORMER.
1/EP102
SCALE:3
TYPICAL 3-WIRE SINGLE PHASE
120/240V METER CONNECTION DETAIL
NTS
SCALE:4
SERVICE PEDESTAL
INSTALLATION DETAILS
NTS
SCALE:2
UTILITY POLE SERVICE DROP
INSTALLATION DETAIL
NTS
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : P
:\G
OR
D1 -2
1 I
FS
N
AT
CH
EZ
B
UR
IA
L E
XP
AN
SI
ON
\D
RA
W
IN
GS
\S
HE
ET
S\
EP
2 E
LE
CT
RI
CA
L P
OW
ER
P
LA
N.
DW
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
jlandrith CO - No Date jlandrith Typewriter
7 MAR 2023
2880 0 1800 0
ANY DOWNSTREAM LOADS ARE INCLUDED IN TOTALS BELOW:
CONNECTED LOAD: CATEGORY CONNECTED LOAD FACTOR DEMAND LOAD AMPS AT 240VOLTS
PHASE VA LIGHTING 0 100% 0 0
A 2,880 RECEPTACLE 1,800 100% 1,800 8
B 1,800
MOTOR 2,880 100% 2,880 12
TOTAL 4,680 LARGEST MOTOR 2,880 25% 720 3
MISC 0 100% 0 0
TOTAL 4,680 5,400 23
PANEL: PANEL 1 AES GROUP, INC. STATUS: NEW
120/240V BUS: 100A COPPER LOCATION: ENTRANCE
1Ø,3W+GND MAINS TYPE: MCB 100A 18 CIRCUIT SPACES SUPPLY FROM: UTILITY
kAIC SUITABLE FOR SERVICE ENTRY MOUNTING: SURFACE
ENCLOSURE: NEMA 3R
DESCRIPTION P BKR CKT A B CKT BKR P DESCRIPTION
PUMP 1 40 1 2880 0 2 20 1 SPARE FOR FUTURE LIGHTING
20A SERVICE RECEPTACLE 1 20 3 1800 0 4 30 2 SPARE FOR FUTURE GATE
SPARE 1 15 5 0 0 6 / / - - -
SPARE 1 15 7 0 0 8 20 1 SPARE
SPACE 9 0 10 20 1 SPARE
SPACE 11 12 SPACE
SPACE 13 14 SPACE
SURGE SURPRESSOR 2 / 15 0 16 SPACE
- - - / / 17 0 18 SPACE
EP501
N/A
MMMJL
SHEET NOTES:
1. LABEL ALL SPARE BREAKERS AS "SPARE" AND
PLACE THE BREAKER IN THE OFF POSITION.
ELECTRICAL PANEL
SCHEDULE
SCALE:1 PANEL SCHEDULE: PANEL 1
NONE
KEY NOTES:
1. PROVIDE SURGE PROTECTIVE DEVICE (SPD)
INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IF
BREAKER IS TO BE PROVIDED, SIZE BREAKER PER
MANUFACTURER'S INSTRUCTIONS AND INSTALL
SURGE PROTECTIVE DEVICE AS NEAR TO THE
PRIMARY LUGS AS POSSIBLE. MINIMIZE THE LENGTH
OF THE SPD LEADS.
2. PROVIDE PANEL MOUNTED, 20A, WEATHERPROOF
WHILE IN USE, GFCI, SERVICE RECEPTACLE. REFER
TO 4/EP102 FOR ADDITIONAL INFORMATION.
3. COORDINATE THE MINIMUM PANEL kAIC RATING WITH
THE UTILITY COMPANY PUBLISHED TRANSFORMER
DATA.
1/EP1021
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
ADAMS COUNTY, MISSISSIPPI
866CM3030
MARCH 7, 2023 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
NATCHEZ NATIONAL CEMETERY
BURIAL EXPANSION PROJECT
Fil e P ath : P
:\G
OR
D1 -2
1 I
FS
N
AT
CH
EZ
B
UR
IA
L E
XP
AN
SI
ON
\D
RA
W
IN
GS
\S
HE
ET
S\
EP
1 E
LE
CT
RI
CA
L P
AN
EL
S
CH
ED
UL
E.
DW
G
The LA Group
(518) 587-8100
AQUA ENGINEERING
(970) 229-9668
AES Group
(303) 841-3922
CB DESIGN GROUP
(888) 585-2234 INTEGRITY
FEDERAL SERVICES
CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
Phone: 304-725-8456 www.ifs-ae.com
IN
TE
GR I TY FEDERA
L
S ERV I C E S
jlandrith Typewriter
7 MAR 2023