This is a pre-solicitation notice for an invitation for bid to renovate a maintenance building at Fort Smith National Cemetery. The project has an estimated value between $500,000 and $1,000,000, and is set aside for service-disabled veteran-owned small businesses. Interested firms must be verified as SDVOSBs and registered in the Vendor Information Pages database. The solicitation is expected to be issued on August 10, 2021 via SAM.gov. Bids are due on the date specified in the IFB. The work includes renovations to a maintenance building, including electrical, lighting and security system upgrades. The National Cemetery Administration of the Department of Veterans Affairs will award the firm-fixed price construction contract.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
DS
S
S
S
S
M
VFD
CB
J
T
S
S
DH
S CR FAA
S
S
UE
OE
UT
S
M
M
M
KEYED NOTES:
LIGHTING CONTROLS
ELECTRICAL ONE LINE
ELECTRICAL EQUIPMENT
EQUIPMENT CONTROLLERS
SYMBOL NOTATIONS USED
RECEPTACLES
NAMEPLATE REQUIREMENTS
BID NOTESELECTRICAL EQUIPMENT CLEARANCE REQUIREMENTS
SPECIAL SYSTEMS
LIGHTING
ABBREVIATIONS
SITE ELECTRICAL
TS
M
M
H
TELECOM OUTLETS & DEVICES
DATA OUTLET
COMINATION DATA AND VOICE OUTLET
VOICE OUTLET
WIRELESS ACCESS POINT
FLOOR MOUNTED DATA OUTLET
A/V OUTLET BOX
FIRE ALARM AND (VOICE/ MASS) NOTIFICATION DEVICES
COMBINATION HORN/STROBE
VISUAL ONLY, CEILING MOUNTED, CLEAR LENS, cd=CANDELA RATING/SETTING
MANUAL PULL STATION
COMBINATION SPEAKER/VISUALS, CEILING MOUNTED, AMBER AND CLEAR LENS,
cd=CANDELA RATING/SETTING, W=WATTAGE
AREA SMOKE DETECTOR
AREA HEAT DETECTOR
DUCT MOUNTED SMOKE DETECTOR
HOOD FIRE SUPPRESSION SYSTEM RELAY
VALVE SUPERVISORY SWITCH
WATER FLOW SWITCH
FIRE DETECTION & ALARM CONTROL PNL
NOTIFICATION CIRCUIT EXPANSION PNL
FACP REMOTE ANNUNCIATOR PANEL
KITCHEN HOOD FIRE SUPPRESSION PNL
MOTORIZED SMOKE FIRE DAMPER
ACCESS CONTROL (ACS) & INTRUSTION DETECTION SYSTEMS
CARD READER FOR CAC SMART CARD
DOOR SENSOR, SECURITY SYSTEM
KEY PAD
OVERHEAD DOOR SENSOR, SECURITY SYSTEM
CARBON MONOXIDE DETECTOR
AREA SMOKE DETECTOR WITH SOUNDER BASE
COMBINATION SPEAKER/STROBE
TV
COMBINATION SPEAKER/VISUALS, WALL MOUNTED, AMBER AND CLEAR
LENS, cd=CANDELA RATING/SETTING, W=WATTAGE
COMBINATION SPEAKER/VISUALS, WALL MOUNTED, WEATHERPROOF, AMBER
AND CLEAR LENS, cd=CANDELA RATING/SETTING, W=WATTAGE
TV/CATV OUTLET
LOCAL OPERATOR CONSOLE
VISUAL ONLY, WALL MOUNTED, CLEAR LENS, cd=CANDELA RATING/SETTING
SB
MASS NOTIFICATION SYSTEM
cd cd cd cd
MNS, CEILING MOUNTED, AMBER LENS, cd=CANDELA RATING/SETTING
MNS, WALL MOUNTED, AMBER LENS, cd=CANDELA RATING/SETTING cd C cd cd
WP
W
W
W
LOW TEMPERATURE SWITCH
ADDRESSABLE OUTPUT CONTROL MODULE
FIRE ALARM SYSTEM CONTROLS
REQUEST TO EXIT
AUDIO VIDEO INPUT JACK BOX
HORN
MONITOR MODULE
DOOR OPEN PUSHBUTTON
ELECTRIFIED EXIT PUSH BAR
FIRE DETECTION DEVICES FA SPECIFICATION AND INSTALLATION REQUIREMENTS
SPEAKER, WALL MOUNT C - CEILING MOUNT WP - WEATHERPROOF
MOTION SENSOR, WALL MOUNTED
WS
WINDOW SENSOR
FIRE ALARM
PULL DOWN
SIMPLEX
FIRE
FB1
EPO
HOA
DP F EPO
KPOS
D
HOA
AVB
FACP
F
TV
AOM
M
M
S
S
S
DP
E1
P2
P1
KP
CR
REX
MM
LT
WF
VS
H
HFS
LOC
FAA
NAC
MNS
AVB
WAP
LCP
LCS
WDP
GEN
SPD
DOOR FRAME SWITCH
X
SINGLE POLE, SINGLE THROW SWITCH 1. 20A, 120V/277V RATED
2. SCREW TYPE TERMINALS, W/ GND TERM.
3. NYLON COVER PLATE
4. FINISHED AREAS: COMMERCIAL GRADE, ROCKER TYPE
SWITCH
5. UNFINISHED AREAS: HEAVY DUTY TOGGLE SWITCH
6. DEVICE AND COVER PLATE COLOR PER ARCHITECT
TWO POLE, SINGLE THROW
SINGLE POLE, DOUBLE THROW 3-WAY
TWO POLE, DOUBLE THROW 4-WAY
SLIDE DIMMER, COMMERCIAL GRADE
WALL MOUNTED W/ PUSHBUTTON
AIMABLE WALL MOUNTED
360° CEILING MOUNTED, CNTR IN RM
PHOTOCELL
TIMECLOCK
OS
OS 1. COMBINATION INFRARED AND ULTRASONIC
2. ADJUSTABLE OFF DELAY, SET AT 15 MIN.
3. DAYLIGHT SENSING, ADJUSTABLE SENSITIVITY
4. WALL MNT: PUSH ON, AUTO OFF "VACANCY TYPE"
5. CLNG MNT: 360°, 1,000 SQ FT COVERAGE
6. AIMABLE WALL MNT SHALL BE ON ADJUSTABLE MOUNTING
ASSEMBLY AT 18" BELOW CEILING AIMED AWAY FROM
TRAFFIC PASSING THE SPACE.
OS
1. SCREW CLAMP, CONCEALED TERMINALS
2. TIME CLOCKS: 24 HR, 7 DAY, ASTRONOMICAL & HOLIDAY
PROGRAMMING, BATTERY BACK UP.
3. LCP: PROGRAMMABLE, MULTI-CIRCUIT DIMMER PANEL
WITH SINGLE INPUT AND MULTIPLE 20A OUTPUT CIRCUITS
WITH INDIVIDUAL OCPDs; AND DIMMER MODULES OR
ON/OFF CONTACTS AS REQUIRED.
4. LCS: WALL MOUNTED CONTROL STATION WITH ON/OFF,
SCENE SELECTION, & LV CABLE TO CENTRAL LCP OR
ADDRESSIBLE POWER PACKS. LCS SHALL BE ABLE TO
COMMUNICATE DISCRETE COMMANDS TO MULTIPLE
POWER PACKS OR "SWITCHLEGS" TO SET THEM AT
DIFFERENT DIMMING LEVELS
5. WDP: WALL MNT LOCAL DIMMER PANEL WITH SINGLE 20A
INPUT AND 4 OR MORE DIMMABLE OUTPUTS, AND
MULTIPLE PROGRAMMED SETTING OPTIONS.
6. PROVIDE START UP AND PROGRAMMING FOR ALL
LIGHTING CONTROL SYSTEMS AND DEVICES.
AUTOMATED CONTROLS
MOLDED/INSULATED CASE BREAKER
DRAWOUT CIRCUIT BREAKER, AIR TYPE
THERMAL OVERLOAD
FUSED DISCONNECT SWITCH
FUSE, HOLDER & PULLER
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
1. CIRCUIT BREAKERS SHALL BE BOLT ON TYPE, WITH
OVERLOAD AND INSTANTANEOUS TRIP COMPONENTS.
2. DISTRIBUTION BREAKERS SHALL HAVE DIGITAL TRIP UNITS
WITH ADJUSTABLE LSIG TRIP SETTINGS.
3. CONTROL POWER TRANSFORMERS SHALL BE
ENCLOSED/ENCAPSUALTED, MIN .5% ACCURACY
4. CURRENT TRANSFORMERS SHALL BE TORROIDAL OR
RECTANGLE WINDOW, SINGLE RATIO, W/ POLARITY
MARKS .
5. PROVIDE UTILITY METER HOUSING PER UTILITY
SPECIFICATIONS FOR SERVICES UP TO 225A
6. PROVIDE CT ENCLOSURE FOR SERVICES OVER 225A.
PROVIDE MIN 36"W x 36"H X 16"D UTILITY PROVIDER
APPROVED ENCLOSURE. NOTE THAT LARGER SIZE MAY B
REQUIRED FOR SERVICES OVER 800As.
7. ATSs SHALL BE 4 POLE, NEUTRAL SWITCHING TYPE, UNO.
UTILITY METER
CT ENCLOSURE
SURGE PROTECTION DEVICE
ELECTRICAL BRANCH PANEL
TRANSFORMER
JUNCTION BOX
1. PANELS: COPPER PH, N, G BUSSING, HINGED DOOR,
REMOVABLE FRONT COVER
2. TRANSFORMERS: COPPER, 2 WINDING, 3-PHASE DELTA TO
WYE ON CONCRETE PAD WITH ISOLATORS, UNLESS
NOTED TO BE SUSPENDED.
3. ALL FLOOR-BOXES SHALL BE PROVIDED WITH
RECEPTACLES, AND WHERE APPLICABLE, DATA MOUNTING
PLATES.
4. ALL TRANSFORMERS SHALL MEET U.S. DEPARTMENT OF
ENERGY 2016 MANDATED MINIMUM EFFICIENCY.
GENERATOR REMOTE ANNUNCIATION PNL
ENCLOSED CIRCUIT BREAKER
DISCONNECT SWITCH
MAGNETIC STARTER - FVNR U.N.O.
COMBINATION STARTER & DISCONNECT
MAGNETIC CONTACTOR (LTG CONTACTOR)
VARIABLE FREQUENCY DRIVE
1. STARTERS: N.O. & N.C. AUXILLARY CONTACTS, FUSED CPT,
ADJUSTABLE OVERLOAD, SIZED PER MOTOR HP, REMOTE
START INPUT, HOA SWITCH
2. LIGHTING CONTACTORS: 20A MIN PER POLE, 120/277V
RATED, HOA SWITCH, HINGED METAL ENCLOSURE, SCREW
TERMINALS, QTY OF POLES AS NOTED.
3. PROVIDE INTEGRAL DISCONNECT FOR STARTERS, VFDs, ETC, LOCKABLE ON OR OFF.
4. EMERGENCY POWER OFF PUSHBUTTON SHALL BE A RED
MUSHROOM HEAD, LATCHING CONTACT, ENGRAVED.
MOTOR, "X" INDICATING HORSE POWER
HORSE POWER RATED TOGGLE SWITCH
MANUAL MOTOR STARTER W/ OVERLOADS
DAYLIGHT SENSORDS
PANEL NAME & CIRCUIT NUMBER
LUMINAIRE TAG, REFER TO SCHEDULE
LOWER CASE LETTER INDICATES
SWITCHLEG (WHERE APPLICABLE)
MOUNTING REQUIREMENTS:
PANEL NAME & CIRCUIT NUMBER
48"
AC
C
SPECIFICATION NOTES:
= DOUBLE POLE
= THREE WAY
= FOUR WAY
= DIMMER
= EXPLOSION PROOF
= HORSEPOWER RATED
= KEY OPERATED
= LOW VOLTAGE
= MANUAL MOTOR STARTER
= PILOT LIGHT
= TIMER
D
EP
H K
LV
M P T
SWITCHING INSTRUCTIONS:
LOWER CASE LETTER DESIGNATES A
SWITCHLEG, LETTER WILL BE SHOWN
NEXT TO EACH FIXTURE
CONTROLLED BY SWITCH
= MOUNT AT 48 INCHES ABOVE FINISHED FLOOR
= MOUNT ABOVE COUNTER 4" ABOVE BACK-SPLASH
= CEILING MOUNT
SPECIFICATION NOTES:
= INTEGRAL GROUND FAULT TRIP MODULE
= ISOLATED GROUND
= MARINE GRADE
= TWIST-LOCK
= WEATHER RESISTANT RECEPTACLE WITH
METAL WEATHERPROOF WHILE IN USE COVER
GFI
IG
MG
TL
WP
SWITCHLEG TO LIGHTS
(OMITTED WHERE THE LTG
SERVED IS OBVIOUS)
LIGHTING CONTROL PANEL
WALL MOUNTED DIMMER PANNEL
LIGHTING CONTROL STATION
LIGHTING CONTACTOR
SIMPLEX RECEPTACLE 1. 20A, 120V RATED, SCREW TYPE TERMINALS, W/ GND TERM.
2. NYLON COVER PLATE
3. FINISHED AREAS: COMMERCIAL GRADE
4. LABS, HALLS, MECHANICAL ROOMS, ETC: HEAVY DUTY
5. PATIENT CARE AREAS: HOSPITAL GRADE.
6. DAMP LOCATIONS: GFCI TYPE
7. WET LOCATIONS: GFCI TYPE, METAL WEATHERPROOF
WHILE IN USE COVER.
8. OCC. SENSOR CONTROLLED: PROVIDE WITH SYMBOL:
9. DEVICE AND COVER PLATE COLOR PER ARCHITECT
10. USB TYPE: TAMPER RESISTANT DUPLEX WITH 5A, 5V USB
OUTPUT. USB PORTS RATED FOR 10,000 CYCLES MIN.
DUPLEX RECEPTACLE
QUADRAPLEX RECEPTACLE
FLOOR MOUNTED RECEPTACLE
CEILING MOUNTED RECEPTACLE
1. HEAVY DUTY
2. ALL ENCLOSED CBs, SWITCHES, AND DISCONNECTS SHALL
HAVE INTEGRAL LOCK OUT DEVICES.
3. ENCLOSED CIRCUIT BREAKERS: OVERLOAD AND
INSTANTANEOUS TRIP COMPONENTS, LOCK OUT
PROVISIONS, AND INTEGRAL SHUNT TRIP MODULES
4. DISCONNECTS: QUICK-MAKE/BREAK LOAD INTERRUPTER
KNIFE SWITCH, HINGED METAL ENCLOSURE, EXTERNAL
OPERABLE HANDLE, LOCKABLE ON OR OFF.
E S
48"
3"
RECEPTACLES J-BOXES
PANEL L1
208/120V, 3PH, 4W
225A, FED FROM H1
VIA XFMR T-L1
PNL # CKT
6" 6"
XFMR
6' 30"
3' (0-150V TO GND),
3.5' (151V-600V TO GND), 4'
(OVER 150V WITH EXPOSED
LIVE PARTS ON OTHER SIDE).
DEDICATED EQUIPMENT
SPACE SHALL BE KEPT
CLEAR TO 6FT ABOVE
EQUIPMENT OR TO
STRUCTURE OF ALL BUT
CONDUIT SERVING
EQUIPMENT.
MIN OFF SET SHALL BE
DEPTH OF EQUIPMENT ON
PERPENDICULAR WALL
18"
80"
6"
MIN HT TO
BOTTOM
OF
NOTIFICATION
APPLIANCES
MINIMUM
CLEARANCE
TO CEILING.
6"
DOOR
WIDTH
MINUS 3".
TO LTG/PANEL
TO DOOR OPERATOR
TO PLENUM, EXCEPT TO IT CLOSET
WHERE CEILING IS EXPOSED TO
DECK OR INACCESSIBLE
TO FACP
/2
/2
/2
/2
ELECTRIC
AL
EQUIP
MENT
ELECTRICAL
EQUIPMENT
W
ORKING SPACE
TO PANEL
TO PLENUM. TO IT CLOSET
WHERE CEILING IS EXPOSED
TO DECK OR INACCESSIBLE.
/4
/4
-2
-1
TO PLENUM, EXCEPT TO AV
EQUIP. WHERE CEILING IS
EXPOSED TO DECK OR
INACCESSIBLE.
1. REFER TO RCP FOR CEILING TYPES IN
ALL AREAS.
2. PRIORITY FOR PROXIMITY TO DOOR
SHALL BE AS SHOWN.
SPECIAL PURPOSE RECEPTACLE
E INDICATES BACK UP POWERED
NL INDICATES NIGHT LIGHT
AUTOMATIC TRANSFER SWITCH
TO FLOORBOX
FLOORBOX
/4
TO PANEL
TO PLENUM EXCEPT TO AV
EQUIP WHERE CEILING IS
EXPOSED TO DECK OR
INACCESSIBLE.
60"VERIFY TV HT
BEFORE
INSTALL AND
CENTER
OUTLETS
BEHIND TV
WALL MNT TV
TVTV
6"
CLEARANCE
TO CEILING
SHALL HAVE
PRIORITY
OVER 80"
ABOVE
FINISHED
FLOOR
EMERGENCY POWER OFF PUSHBUTTON
TO CONTACTOR
BACKSPLASH
4"
ACAC
"HAND-OFF-AUTO" CONTROL SELECTOR
1. NAMEPLATE: 1/16" PHENOLIC PLASTIC LAMINATE, TWO FLAT HEAD SCREWS
2. FINISHED AREA WIRING DEVICES: ADHESIVE LABELS, CLEAR W/ BLACK TEXT
3. J-BOXES: USE PERMANENT INK MARKER AND PAINT AS NOTED
4. OUTDOOR AND HARSH ENVIRO WIRING DEVICES: MARKER ON INSIDE OF
COVER
5. IN PUBLIC AREAS SUCH AS LOBBIES, CONF. ROOMS, ETC, LABEL INSIDE OF
RECEPTACLE COVERS AND EXPOSED JBOX COVERS USING MARKER.
PLACE A DOT OF PAINT ON OUTSIDE OF SPECIAL SYSTEMS BOXES.
L1#1 120V
COM FA
NAC
ORANGE
COVER
RED
COVER
NO
PAINT
CWP-VFD
208/120V, 3PH, 4W
5HP, FED FROM L1
SPECIFICATIONS
EXIT
6" 8"
MINIMUM
CLEARANCE
TO CEILING.
OS
12' MAX
SHUNT TRIP (K=KIRK KEY INTERLOCK, RT=REMOT TRIP)
PWR IT FIRE
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SCOPE OF WORK UNLESS EXPLICITLY NOTED
OTHERWISE. WHERE WORK IS NOTED TO BE BY SPECIALIST CONTRACTOR SUCH AS FIRE ALARM
CONTRACTOR, THIS WORK SHALL BE PART OF THE CONTRACT UNLESS EXPLICITLY NOTED OTHERWISE.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE COMPLETE CONTRACT DOCUMENTS AS SOME
SCOPE REQUIRING ELECTRICAL WORK SUCH AS HVAC CONTROL POWER, CONTROL POWER TRANSFORMERS, DAMPERS, FLUSH VALVES, LIFT STATIONS, ETC MAY BE SHOWN ON OTHER DISCIPLINES' PLANS.
3. PRIOR TO BID, THE GENERAL CONTRACTOR (GC), ELECTRICAL, AND SPECIAL SYSTEMS CONTRACTORS SHALL
COORDINATE THE PROJECT SCOPE TO VERIFY THAT ALL WORK AND EQUIPMENT NECESSARY FOR THE
OPERATION OF THE IT, FIRE ALARM, SECURITY, A/V, AND OTHER SPECIAL SYSTEMS ARE INCLUDED IN THE BID.
4. THE GC SHALL COORDINATE WITH THE MECHANICAL, CONTROLS, PROCESS, PLUMBING, AND ELECTRICAL
CONTRACTOR TO CONFIRM THAT ALL ELECTRICAL WORK AND EQUIPMENT NECESSARY FOR THE HVAC
CONTROLS SYSTEM, AUTOMATIC FLUSH VALVES, ETC IS INCLUDED IN THE BID.
5. WHERE THE CONTRACT DOCUMENTS ARE UNCLEAR OR DO NOT SPECIFY WHO IS RESPONSIBLE FOR THE
SCOPE, THE GC SHALL BE RESPONSIBLE FOR DELEGATION OF THE PROJECT SCOPE AND VERIFICATION THAT
ALL SUB CONTRACTORS ARE AWARE OF WHICH COMPONENTS OF THE SCOPE ARE IN THEIR CONTRACT.
6. THE SPECIFICATION REQUIREMENTS SHOWN ON THIS PAGE ARE PROVIDED TO GIVE A GENERAL CONCEPT OF
THE PROJECT REQUIREMENTS. MORE DETAILED REQUIREMENTS ARE SHOWN ON THE PLANS AND IN THE
WRITTEN SPECIFICATIONS.
MIN
CL
CL
CL
CL
DRAWOUT CIRCUIT BREAKER, VAC TYPE
SWITCHED RECEPTACLE
TIME SWITCH, 60 MIN. OVERRIDE U.N.O.
SURFACE RACEWAY
DISCONNECT MOUNTED ON UNISTRUT
KIRK-KEY
1. REQUIREMENTS SHOWN HERE ARE MINIMUM BASIC
REQUIREMENTS, ADDITIONAL REQUIREMENTS
ELSEWHERE.
2. FA DEVICES SHALL BE ADDRESSABLE.
3. STROBES: XENON TYPE, BUILDING WIDE FLASH
SYNCHRONIZED, WITH FIELD ADJUSTABLE
INTENSITY.
4. HORN INTENSITY SHALL BE 15DB ABOVE AMBIENT.
5. PULL STATIONS: SINGLE ACTION, ADA COMPLIANT
6. SMOKE DETECTORS: ADJUSTABLE SENSITIVITY,
STATUS LEDs
7. HEAT DETECTORS: RATE OF RISE, FIXED TEMP,
SPOT TYPE AS REQUIRED, WITH STATUS LEDs
8. DUCT DETECTORS: FULL DUCT WIDTH SAMPLING
TUBE, RELAY CONTACT, LOCATE 3FT FROM FAN,
BEFORE BRANCHES, LED STATUS INDICATORS, FA
MODULE.
9. FACP: MODULAR, ADDRESSABLE, AUTOMATIC FA
SYSTEM, REMOTE MONITORING, BATTERY BACKUP
SUFFICIENT FOR 24 HOURS OF MONITORING PLUS 5
MIN. OF ALARM,
10. MONITOR AND CONTROL MODULES:ADDRESSABLE,
MOUNTED IN 4" DEEP J-BOXES WITH A CUSTOM
COVER PLATE WITH APPROPRIATE LABELING AND
VIEW PORTS FOR ANY LED INDICATORS.
11. PROVIDE CONDUIT BETWEEN DUCT DETECTORS,
FSDs, FLOW SWITCHES, ETC AND MONITOR AND
CONTROL MODULES, FMC MAY BE USED FOR
SHORT RUNS TO EQUIPMENT OR PIPING, 3FT MAX.
12. PROVIDE 120V POWER AND CPT (WHERE
REQUIRED) TO ALL MOTORIZED DAMPERS AND
OTHER ANCILLARY EQUIPMENT NOT POWERED
FROM THE FIRE ALARM PANEL
GENERAL SPECIAL SYSTEMS INSTALLATION REQUIREMENTS
1. PROVIDE 4" SQUARE DEEP J-BOX FOR ALL DATA OUTLETS, FIRE ALARM COMPONENTS, SECURITY, A/V AND OTHER
SPECIAL SYSTEMS EQUIPMENT AND DEVICES, UNO.
2. THE GENERAL, ELECTRICAL, AND SPECIAL SYSTEMS CONTRACTORS SHALL COORDINATE SCOPE BEFORE BID AND
ALL DEVICE AND EQUIPMENT LOCATIONS BEFORE ROUGH IN.
3. PROVIDE SINGLE GANG REDUCER FOR FLUSH MOUNT DEVICES THAT HAVE SINGLE GANG COVER PLATES.
4. PROVIDE RACEWAY SYSTEM FROM ALL SPECIAL SYSTEMS EQUIPMENT, DEVICES, ETC TO THEIR RESPECTIVE
SOURCE EQUIPMENT, RACK, ETC.
5. WHERE SPECIAL SYSTEMS CABLING IS PERMITTED TO BE ROUTED IN AIR THROUGH ACCESSIBLE ABOVE CEILING
SPACE, USE J-HOOKS AND CABLE TIES TO GROUP, SECURE AND NEATLY ROUTE CABLE TO SOURCE. ROUTE
PARALLEL/PERPENDICULAR TO STRUCTURAL ELEMENTS. PROVIDE SLEEVES THROUGH INACCESSIBLE SECTIONS
OF HOME-RUNS.
EQUIP MOUNTED ON CHANNEL RACK
EXIT SIGN - SINGLE FACE
EXIT SIGN - DUAL FACE
DUAL HEAD EMERGENCY LT
WITH INTEGRAL BATTERY PACK
1. EDGE LIT, LED EXIT SIGNS.
2. INTEGRAL 90 MIN BATTERY PACK
3. SELF DIAGNOSTIC
4. INTEGRAL TEST SWITCH
EMERGENCY/EGRESS LIGTHING
SHOWN HATCHED AND/OR
TAGGED WITH "E" (AS IN "AE" )
UNSWITCHED WHERE NOTED NL
1. EMERGENCY/EGRESS LIGHTING
SHALL USE SELF CONTAINED
BATTERY PACKS, UNO.
2. INTEGRAL 90 MIN BATTERY PACK
3. SELF DIAGNOSTIC
4. INTEGRAL TEST SWITCH
GENERAL SPECIAL SYSTEMS INSTALLATION REQUIREMENTS
1. ROUTE UNSWITCHED CIRCUIT LET TO ALL EMERGENCY/EGRESS LIGHTING
AND EXIT SIGNS FOR BATTERY CHARGING AND TRANSFER CONTROL.
2. EMERGENCY LIGHTING TO BE SWITCHED WITH ADJACENT AREA LIGHTING,
UNLESS NOTED "NL" FOR NIGHT LIGHT.
A.
AC
AFF
AIC
A/V
ATS
BLDG
C
CKT
CM
CONN
CT
DIM
EA
EC
EF
ELEC
EMER
EPO
EWC
FACP
FLA
FS
FSD
GC
GFI
GND
HOA
HP
HPS
HTR
J-BOX
KCM
AMPERE
ABOVE COUNTER
ABOVE FINISHED FLOOR
AMP INTERRUPTING CAPACITY
AUDIO VISUAL
AUTOMATIC TRANSFER SWITCH
BUILDING
CONDUIT
CIRCUIT
CONTROL MODULE
CONNECT OR CONNECTION
CURRENT TRANSFORMER
DIMENSION
EACH
ELECTRICAL CONTRACTOR
EXHAUST FAN
ELECTRIC,ELECTRICAL
EMERGENCY
EMERGENCY POWER OFF
ELECTRIC WATER COOLER
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FLOW SWITCH
FIRE SMOKE DAMPER
GENERAL CONTRACTOR
GROUND FAULT INTERRUPTER
GROUND
HAND-OFF-AUTO
HORSEPOWER
HIGH PRESSURE SODIUM
HEATER
JUNCTION BOX
THOUSAND CIRCULAR MILLS
LOTO
LTG
MCB
MCC
MCP
MIN
MH
MLO
MNS
MRS
MSB
MTD
MTS
MV
N.I.C.
NL
NTS
OL
OE
PS
RECPT
RGS
SPD
TS
TYP.
UG
UNO
V
WH
WP
WR
XFMR
LOCK OUT TAG OUT
LIGHT OR LIGHTING
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MINIMUM
METAL HALIDE
MAIN LUGS ONLY
MASS NOTIFICATION SYSTEM
MOTOR RATED SWITCH
MAIN SWITCH BOARD
MOUNTED
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
NOT IN CONTRACT
NIGHT LIGHT (UNSWITCHED)
NOT TO SCALE
PHASE
OVERLOAD
OVER HEAD ELECTRIC
PULL STRING
RECEPTACLE
RIGID GALVANIZED STEEL
SURGE PROTECTION DEVICE
TAMPER SWITCH
TYPICAL
UNDERGROUND
UNLESS NOTED OTHERWISE
VOLTAGE
WATER HEATER
WEATHER PROOF
WEATHER RATED
TRANSFORMER
LIGHTING SYMBOLOGY GENERAL NOTES
1. USING THE LUMINAIRE TAG FOR REFERENCE, REFER TO THE LUMINAIRE
(FIXTURE) SCHEDULE FOR THE DESCRIPTION OF EACH FIXTURE TYPE.
2. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR
ADDITIONAL INFORMATION ABOUT LUMINAIRES, THE CEILING, MOUNTING
HEIGHTS, ETC.
LUMINAIRE TAG, REFER TO SCHEDULE
LOWER CASE LETTER INDICATES
SWITCHLEG (WHERE APPLICABLE)
SPECIFICATIONS
WALL SWITCHES
OCCUPANCY SENSORS
ONE LINE
DISCONNECTS AND OCPD
RECEPTACLES
MOTOR AND EQUIPMENT CONTROLS
ELECTRICAL PANELS
DISTRIBUTION EQUIPMENT
EXIT LIGHTING SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
EQUIPMENT CONTROLS
IN GRADE 600V PULL BOXPB
CIRCUIT WIRING
UNDERGROUND CIRCUIT WIRING
UNDERGROUND HV/MV UTILITY LINE
OVERHEAD HV/MV UTILITY LINE
ELECTRICAL MANHOLE
COMMUNICATIONS MANHOLECM
EM
IN GRADE COMMUNICATIONS PULL BOXCP
TRANSFORMER PAD EQUIPMENT MOUNTING RACK
STUB UP / TURN DOWN
UTILITY POLE
POLE MOUNTED TRANSFORMERT MV PAD MOUNT SWITCH
V W
M S
COMMUNICATIONS SERVICE ENCLOSUREC
UNDERGROUND UTILITY PULL BOXMV
PB
UNDERGROUND TELECOM SERVICE
SITE WIRING
EXTERIOR IN GRADE EQUIPMENT
EXTERIOR ABOVE GRADE EQUIPMENT
SPECIFICATIONS
1. ELECTRICAL BURIAL DEPTH:
1.1. 24" AT VEHICLE ACCESSED AREAS.
1.2. 18" AT AREAS INACCESSIBLE TO VEHICLES.
2. COMMUNICATIONS BURIAL DEPTH: 18"
3. PROVIDE 12" SEPARATION FROM UTILITIES.
4. ALL SITE UNDERGROUND RACEWAYS SHALL BE BEDDED
IN SAND OR SELECT FILL, LARGE ROCKS SHALL BE
REMOVED FROM BACKFILL, UNLESS NOTED TO BE
CONCRETE ENCASED.
5. MANHOLES SHALL BE CONCRETE, RE-ENFORCED AS
REQUIRED, GROUTED AND SEALED, EARTH GROUNDED.
LIDS: ENGRAVED, BOLT DOWN COVERS, CONCRETE OR
CAST IRON (SEE DETAILS)
6. PULL BOXES FOR 600V BRANCH CIRCUITS AND
COMMUNICATIONS SHALL BE 24"L x 12"W x 18"D, POLYMER CONCRETE, UNO (SEE DETAILS)
7. EQUIPMENT PADS SHALL BE 10" THICK, 3000 PSI
CONCRETE, WITH #3 REBAR GRID AT 9" ON CENTER, UNO
(SEE DETAILS).
8. ENCLOSURES SHALL BE OUTDOOR RATED
9. EQUIPMENT MOUNTING RACKS SHALL BE GALVANIZED
STEEL TUBE AND GALVANIZED SLOTTED U-CHANNEL,
CONCRETE EMBEDDED OR SET ON PADS (SEE DETAILS)
EXISTING UNDERGROUND
MULT-CONDUIT UNDERGROUND
(CONCRETE ENCASED WHERE NOTED)
L1#1
L1#1
E/NL
A a
A a
E/NL
a AC GFI
USB RECEPTACLE
D
LC
PC
TC
ST
K
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:2
A
M
E-001
ELECTRICAL SYMBOLS RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
William Klock, P.E. - AR
2021.05.27 12:46:22-05'00'
WH
OS
3 3
J
EXISTING
LIGHTING
CIRCUIT
J
EXISTING
LIGHTING
CIRCUIT
PNL P
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR SHOULD COORDINATE WITH THE ENGINEER OR OWNER
FOR THE DISPOSITION OF ANY EQUIPMENT NOT MENTIONED ON
THESE PLANS THAT IS FOUND IN THE FIELD THAT WILL BE AFFECTED
BY OR SHOULD BE DEMOLISHED ALONG WITH THE OTHER
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
2. ALL CONDUIT EMBEDDED IN CONCRETE OR BURIED SHALL BE
ABANDON IN PLACE. THE ABANDON CONDUIT SHALL BE CUT OFF
FLUSH WITH SURFACE AND CAPPED.
3. THE OWNER SHALL HAVE FIRST RIGHT OF SALVAGE FOR ALL
DEMOLISHED EQUIPMENT. DISPOSAL OF ALL DEMOLISHED
EQUIPMENT NOT REQUESTED BY THE OWNER SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL RECYCLABLE MATERIALS
SHALL BE SORTED AND DELIVERED TO THE FT. HOOD RECYCLING
CENTER.
4. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR THE
DISPOSAL OF HAZARDOUS MATERIALS SUCH AS PCBs AND MERCURY
CONTAINING FLUORESCENT LAMPS FOLLOWING ALL LOCAL, STATE,
AND FEDERAL GUIDELINES AND PROVIDE DOCUMENTATION OF
DISPOSAL TO THE OWNER.
5. ALL ELECTRICAL EQUIPMENT SUCH AS CONDUIT, CONDUCTORS,
DISCONNECTS, SUPPORTS, ETC. THAT IS ASSOCIATED WITH OTHER
EQUIPMENT SUCH AS RECEPTACLES, LIGHTING, HVAC EQUIPMENT,
ETC THAT IS SHOWN ON THESE PLANS TO BE REMOVED SHALL ALSO
BE REMOVED FROM THE ELECTRICAL PANEL TO THE LOAD SERVED
UNLESS NOTED TO BE USED FOR NEW EQUIPMENT OR ALSO SERVING
EXISTING TO REMAIN LOADS.
6. PATCH AND FIRE SEAL AS REQUIRED ALL PENETRATIONS IN
STRUCTURES MADE BY ELECTRICAL EQUIPMENT SUCH AS CONDUIT
AND CABLE TRAY THAT IS BEING REMOVED.
7. ALL MATERIALS SALVAGED TO OWNER SHALL BE STORED BY
CONTRACTOR FOR REUSE UNTIL END OF PROJECT THEN RETURNED
TO THE OWNER.
8. REFER TO MECHANICAL AND PLUMBING DEMOLITION PLANS FOR
EQUIPMENT THAT REQUIRES ELECTRICAL SERVICE TO BE REMOVED
FROM LOAD TO SOURCE.
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:2
A
M
ELD-101
MAINTENANCE BLDG. LIGHTING
DEMO PLAN
RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
1/4" = 1'-0"1 LIGHTING DEMO - LEVEL 1 - MAINTENANCE BLDG.
1. ELECTRICAL CONTRACTOR TO REMOVE THE EXISTING INTERIOR
LIGHTING AND CONTROLS BACK TO THE LIGHTING CIRCUIT STARTING
JUNCTION BOX TO REMAIN. ELECTRICAL CONTRACTOR TO FIELD
VERIFY THE LOCATION OF THE JUNCTION BOX PRIOR TO BID.
2. ELECTRICAL CONTRACTOR SHALL REMOVE THE EXISTING
EMERGENCY EGRESS LIGHTING AND EXIT SIGNS BACK TO THE
NEAREST JUNCTION BOX TO REMAIN. ELECTRICAL CONTRACTOR TO
FIELD VERIFY THE LOCATION OF THE JUNCTION BOX PRIOR TO BID.
3. ELECTRICAL CONTRACTOR SHALL REMOVE THE EXISTING EXTERIOR
WALL PACKS. ELECTRICAL CONTRACTOR SHALL MAINTAIN THE
EXISTING CONDUIT, CONDUCTORS, AND BACK BOX FOR THE NEW
EXTERIOR WALL PACKS.
4. ELECTRICAL CONTRACTOR SHALL REMOVE THE EXISTING LIGHT
FIXTURES AND WALL SWITCH IN THE EXISTING RESTROOM.
ELECTRICAL CONTRACTOR TO MAINTAIN THE EXISTING CONDUIT,
CONDUCTORS, AND BACKBOXES FOR THE NEW LIGHT FIXTURES AND
CONTROLS IN THE AREA.
5. ELECTRICAL CONTRACTOR SHALL REMOVE THE EXISTING LIGHT
FIXTURES AND WALL SWITCH IN THE EXISTING SHOWER AREA.
ELECTRICAL CONTRACTOR TO MAINTAIN THE EXISTING CONDUIT,
CONDUCTORS, AND BACKBOXES FOR THE NEW LIGHT FIXTURES AND
CONTROLS IN THE AREA.
ELECTRICAL KEYED NOTES:
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:47:10-05'00'
KP
PNL P
GFI
S
S
P
P1
AC
GFI
AC
GFI
AC
GFI
P1
S
S
S
P1
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR SHOULD COORDINATE WITH THE ENGINEER OR OWNER
FOR THE DISPOSITION OF ANY EQUIPMENT NOT MENTIONED ON
THESE PLANS THAT IS FOUND IN THE FIELD THAT WILL BE AFFECTED
BY OR SHOULD BE DEMOLISHED ALONG WITH THE OTHER
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
2. ALL CONDUIT EMBEDDED IN CONCRETE OR BURIED SHALL BE
ABANDON IN PLACE. THE ABANDON CONDUIT SHALL BE CUT OFF
FLUSH WITH SURFACE AND CAPPED.
3. THE OWNER SHALL HAVE FIRST RIGHT OF SALVAGE FOR ALL
DEMOLISHED EQUIPMENT. DISPOSAL OF ALL DEMOLISHED
EQUIPMENT NOT REQUESTED BY THE OWNER SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL RECYCLABLE MATERIALS
SHALL BE SORTED AND DELIVERED TO THE FT. HOOD RECYCLING
CENTER.
4. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR THE
DISPOSAL OF HAZARDOUS MATERIALS SUCH AS PCBs AND MERCURY
CONTAINING FLUORESCENT LAMPS FOLLOWING ALL LOCAL, STATE,
AND FEDERAL GUIDELINES AND PROVIDE DOCUMENTATION OF
DISPOSAL TO THE OWNER.
5. ALL ELECTRICAL EQUIPMENT SUCH AS CONDUIT, CONDUCTORS,
DISCONNECTS, SUPPORTS, ETC. THAT IS ASSOCIATED WITH OTHER
EQUIPMENT SUCH AS RECEPTACLES, LIGHTING, HVAC EQUIPMENT,
ETC THAT IS SHOWN ON THESE PLANS TO BE REMOVED SHALL ALSO
BE REMOVED FROM THE ELECTRICAL PANEL TO THE LOAD SERVED
UNLESS NOTED TO BE USED FOR NEW EQUIPMENT OR ALSO SERVING
EXISTING TO REMAIN LOADS.
6. PATCH AND FIRE SEAL AS REQUIRED ALL PENETRATIONS IN
STRUCTURES MADE BY ELECTRICAL EQUIPMENT SUCH AS CONDUIT
AND CABLE TRAY THAT IS BEING REMOVED.
7. ALL MATERIALS SALVAGED TO OWNER SHALL BE STORED BY
CONTRACTOR FOR REUSE UNTIL END OF PROJECT THEN RETURNED
TO THE OWNER.
8. REFER TO MECHANICAL AND PLUMBING DEMOLITION PLANS FOR
EQUIPMENT THAT REQUIRES ELECTRICAL SERVICE TO BE REMOVED
FROM LOAD TO SOURCE.
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:4
A
M
EPD-101
MAINTENANCE BLDG. POWER
DEMO PLAN
RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
1/4" = 1'-0"1 POWER DEMO - LEVEL 1 - MAINTENANCE BLDG.
1. EXISTING GAS UNIT HEATERS ARE TO BE REMOVED.
ELECTRICAL CONTRACTOR TO REMOVE THE EXISTING
DISCONNECT, CONDUIT, AND CONDUCTORS BACK TO THE
NEAREST JUNCTION BOX TO REMAIN. EXISTING ELECTRICAL
CIRCUIT TO BE RE-USED IN NEW WORK.
2. EXISTING COIL DOOR OPENER TO BE REMOVED BACK TO THE
NEAREST JUNCTION BOX TO REMAIN. NEW COIL DOOR
OPENER TO BE INSTALLED IN NEW WORK. EXISTING DOOR
OPENER CIRCUIT TO BE REUSED.
3. EXISTING SECURITY SYSTEM DEVICES TO BE REMOVED BACK
TO THE CONTROL PANEL IN THE LODGE BASEMENT.
4. EXISTING FIRE ALARM DEVICES TO BE REMOVED.
KEYED NOTES: X
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:37:53-05'00'
EX-RTU-1 1
EX-EF-1 EX-EF-2
2 2
EX-EF-3
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR SHOULD COORDINATE WITH THE ENGINEER OR OWNER
FOR THE DISPOSITION OF ANY EQUIPMENT NOT MENTIONED ON
THESE PLANS THAT IS FOUND IN THE FIELD THAT WILL BE AFFECTED
BY OR SHOULD BE DEMOLISHED ALONG WITH THE OTHER
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
2. ALL CONDUIT EMBEDDED IN CONCRETE OR BURIED SHALL BE
ABANDON IN PLACE. THE ABANDON CONDUIT SHALL BE CUT OFF
FLUSH WITH SURFACE AND CAPPED.
3. THE OWNER SHALL HAVE FIRST RIGHT OF SALVAGE FOR ALL
DEMOLISHED EQUIPMENT. DISPOSAL OF ALL DEMOLISHED
EQUIPMENT NOT REQUESTED BY THE OWNER SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL RECYCLABLE MATERIALS
SHALL BE SORTED AND DELIVERED TO THE FT. HOOD RECYCLING
CENTER.
4. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR THE
DISPOSAL OF HAZARDOUS MATERIALS SUCH AS PCBs AND MERCURY
CONTAINING FLUORESCENT LAMPS FOLLOWING ALL LOCAL, STATE,
AND FEDERAL GUIDELINES AND PROVIDE DOCUMENTATION OF
DISPOSAL TO THE OWNER.
5. ALL ELECTRICAL EQUIPMENT SUCH AS CONDUIT, CONDUCTORS,
DISCONNECTS, SUPPORTS, ETC. THAT IS ASSOCIATED WITH OTHER
EQUIPMENT SUCH AS RECEPTACLES, LIGHTING, HVAC EQUIPMENT,
ETC THAT IS SHOWN ON THESE PLANS TO BE REMOVED SHALL ALSO
BE REMOVED FROM THE ELECTRICAL PANEL TO THE LOAD SERVED
UNLESS NOTED TO BE USED FOR NEW EQUIPMENT OR ALSO SERVING
EXISTING TO REMAIN LOADS.
6. PATCH AND FIRE SEAL AS REQUIRED ALL PENETRATIONS IN
STRUCTURES MADE BY ELECTRICAL EQUIPMENT SUCH AS CONDUIT
AND CABLE TRAY THAT IS BEING REMOVED.
7. ALL MATERIALS SALVAGED TO OWNER SHALL BE STORED BY
CONTRACTOR FOR REUSE UNTIL END OF PROJECT THEN RETURNED
TO THE OWNER.
8. REFER TO MECHANICAL AND PLUMBING DEMOLITION PLANS FOR
EQUIPMENT THAT REQUIRES ELECTRICAL SERVICE TO BE REMOVED
FROM LOAD TO SOURCE.
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:5
A
M
EPD-102
MAINTENANCE BLDG. POWER
DEMO ROOF PLAN
RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
1/4" = 1'-0"1 02 - POWER DEMO - ROOF LEVEL - MAINTENANCE BLDG.
1. EXISTING ROOF TOP UNIT TO BE REMOVED. ELECTRICAL
CONTRACTOR TO REMOVE THE EXISTING DISCONNECT,
CONDUIT, AND CONDUCTORS BACK TO THE PANEL.
2. EXISTING ROOF TOP EXHAUST FANS TO REMAIN. NOT PART OF
THIS SCOPE.
3. EXISTING ROOF TOP EXHAUST FAN TO BE REMOVED.
ELECTRICAL CONTACTOR TO REMOVE THE EXISTING
DISCONNECT. CONDUIT, AND CONDUCTORS BACK TO THE
PANEL.
KEYED NOTES: X
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:46:36-05'00'
F
F
PNL A
PNL M
P1
FACP
FAA
AC
GFI
AC
GFI
AC
GFI
AC
GFI
P1
S
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR SHOULD COORDINATE WITH THE ENGINEER OR OWNER
FOR THE DISPOSITION OF ANY EQUIPMENT NOT MENTIONED ON
THESE PLANS THAT IS FOUND IN THE FIELD THAT WILL BE AFFECTED
BY OR SHOULD BE DEMOLISHED ALONG WITH THE OTHER
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
2. ALL CONDUIT EMBEDDED IN CONCRETE OR BURIED SHALL BE
ABANDON IN PLACE. THE ABANDON CONDUIT SHALL BE CUT OFF
FLUSH WITH SURFACE AND CAPPED.
3. THE OWNER SHALL HAVE FIRST RIGHT OF SALVAGE FOR ALL
DEMOLISHED EQUIPMENT. DISPOSAL OF ALL DEMOLISHED
EQUIPMENT NOT REQUESTED BY THE OWNER SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL RECYCLABLE MATERIALS
SHALL BE SORTED AND DELIVERED TO THE FT. HOOD RECYCLING
CENTER.
4. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR THE
DISPOSAL OF HAZARDOUS MATERIALS SUCH AS PCBs AND MERCURY
CONTAINING FLUORESCENT LAMPS FOLLOWING ALL LOCAL, STATE,
AND FEDERAL GUIDELINES AND PROVIDE DOCUMENTATION OF
DISPOSAL TO THE OWNER.
5. ALL ELECTRICAL EQUIPMENT SUCH AS CONDUIT, CONDUCTORS,
DISCONNECTS, SUPPORTS, ETC. THAT IS ASSOCIATED WITH OTHER
EQUIPMENT SUCH AS RECEPTACLES, LIGHTING, HVAC EQUIPMENT,
ETC THAT IS SHOWN ON THESE PLANS TO BE REMOVED SHALL ALSO
BE REMOVED FROM THE ELECTRICAL PANEL TO THE LOAD SERVED
UNLESS NOTED TO BE USED FOR NEW EQUIPMENT OR ALSO SERVING
EXISTING TO REMAIN LOADS.
6. PATCH AND FIRE SEAL AS REQUIRED ALL PENETRATIONS IN
STRUCTURES MADE BY ELECTRICAL EQUIPMENT SUCH AS CONDUIT
AND CABLE TRAY THAT IS BEING REMOVED.
7. ALL MATERIALS SALVAGED TO OWNER SHALL BE STORED BY
CONTRACTOR FOR REUSE UNTIL END OF PROJECT THEN RETURNED
TO THE OWNER.
8. REFER TO MECHANICAL AND PLUMBING DEMOLITION PLANS FOR
EQUIPMENT THAT REQUIRES ELECTRICAL SERVICE TO BE REMOVED
FROM LOAD TO SOURCE.
EXISTING
SECURITY
SYSTEM
PANEL
TC
+42"
+42"
P1
AC
GFI
S
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:5
A
M
EPD-111
LODGE BLDG. POWER DEMO
PLAN
RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
1/4" = 1'-0"1 POWER PLAN DEMO - LEVEL 1 - LODGE BLDG.
1. REMOVE THE EXISTING SECURITY SYSTEM PANEL AND ACCESSORIES.
2. REMOVE THE EXISTING SECURITY SYSTEM DEVICES IN THE BUILDING.
REMOVE THE WINDOW, DOOR, AND MOTION SENSORS. REMOVE THE
DEVICES AND THE WIRING AND CONDUITS BACK TO THE SOURCE.
ELECTRICAL CONTRACTOR SHALL FIELD VERIFY THE EXACT NUMBER
AND LOCATIONS OF ALL SECURITY DEVICES PRIOR TO BID.
3. REMOVE THE EXISTING BATHROOM RECEPTACLE. MAINTAIN THE
EXISTING BACK BOX, CONDUIT, AND CONDUCTORS FOR THE NEW
WORK.
4. REMOVE THE EXISTING FIRE ALARM CONTROL PANEL AND ANN. PANEL.
5. REMOVE THE EXISTING FIRE ALARM DEVICES BACK TO THE FIRE ALARM
PANEL.
6. REMOVE THE LANDSCAPING SHRUB INFRONT OF THE PANEL 'M'
LOCATED ON THE EXTERIOR WALL. PROVIDE THE REQUIRED NEC
CLEARANCES FOR THE ELECTRICAL EQUIPMENT.
KEYED NOTES: X
1/4" = 1'-0"3 POWER PLAN DEMO - BASEMENT - LODGE BLDG.
1/4" = 1'-0"2 POWER PLAN DEMO - LEVEL 2 - LODGE BLDG.
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:47:28-05'00'
2 2
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR SHOULD COORDINATE WITH THE ENGINEER OR OWNER
FOR THE DISPOSITION OF ANY EQUIPMENT NOT MENTIONED ON
THESE PLANS THAT IS FOUND IN THE FIELD THAT WILL BE AFFECTED
BY OR SHOULD BE DEMOLISHED ALONG WITH THE OTHER
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
2. ALL CONDUIT EMBEDDED IN CONCRETE OR BURIED SHALL BE
ABANDON IN PLACE. THE ABANDON CONDUIT SHALL BE CUT OFF
FLUSH WITH SURFACE AND CAPPED.
3. THE OWNER SHALL HAVE FIRST RIGHT OF SALVAGE FOR ALL
DEMOLISHED EQUIPMENT. DISPOSAL OF ALL DEMOLISHED
EQUIPMENT NOT REQUESTED BY THE OWNER SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL RECYCLABLE MATERIALS
SHALL BE SORTED AND DELIVERED TO THE FT. HOOD RECYCLING
CENTER.
4. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR THE
DISPOSAL OF HAZARDOUS MATERIALS SUCH AS PCBs AND MERCURY
CONTAINING FLUORESCENT LAMPS FOLLOWING ALL LOCAL, STATE,
AND FEDERAL GUIDELINES AND PROVIDE DOCUMENTATION OF
DISPOSAL TO THE OWNER.
5. ALL ELECTRICAL EQUIPMENT SUCH AS CONDUIT, CONDUCTORS,
DISCONNECTS, SUPPORTS, ETC. THAT IS ASSOCIATED WITH OTHER
EQUIPMENT SUCH AS RECEPTACLES, LIGHTING, HVAC EQUIPMENT,
ETC THAT IS SHOWN ON THESE PLANS TO BE REMOVED SHALL ALSO
BE REMOVED FROM THE ELECTRICAL PANEL TO THE LOAD SERVED
UNLESS NOTED TO BE USED FOR NEW EQUIPMENT OR ALSO SERVING
EXISTING TO REMAIN LOADS.
6. PATCH AND FIRE SEAL AS REQUIRED ALL PENETRATIONS IN
STRUCTURES MADE BY ELECTRICAL EQUIPMENT SUCH AS CONDUIT
AND CABLE TRAY THAT IS BEING REMOVED.
7. ALL MATERIALS SALVAGED TO OWNER SHALL BE STORED BY
CONTRACTOR FOR REUSE UNTIL END OF PROJECT THEN RETURNED
TO THE OWNER.
8. REFER TO MECHANICAL AND PLUMBING DEMOLITION PLANS FOR
EQUIPMENT THAT REQUIRES ELECTRICAL SERVICE TO BE REMOVED
FROM LOAD TO SOURCE.
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:3
A
M
ELD-111
LODGE BLDG. LIGHTING DEMO
PLAN
RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
1/4" = 1'-0"1 LIGHTING DEMO - LEVEL 1 - LODGE BLDG.
1. ELECTRICAL CONTRACTOR SHALL REMOVE THE EXISTING
EMERGENCY EGRESS LIGHTING AND EXIT SIGNS BACK TO THE
NEAREST JUNCTION BOX TO REMAIN.
2. REMOVE THE EXISTING LIGHT SWITCHES IN THE AREA. MAINTAIN THE
EXISTING CONDUIT, CONDUCTORS AND BACKBOXES FOR ADDING
WALL MOUNTED SENSOR SWITCHES IN THE NEW WORK.
3. REMOVE THE EXISTING SURFACE MOUNTED LIGHT AND SWITCH IN
THE RESTROOM. MAINTAIN THE EXISTING CONDUIT, CONDUCTORS
AND BACK BOXES TO BE USED IN THE NEW WORK.
ELECTRICAL KEYED NOTES:
1/4" = 1'-0"2 LIGHTING PLAN - LEVEL 2 - LODGE BLDG.
1/4" = 1'-0"3 LIGHTING PLAN - BASEMENT - LODGE BLDG.
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:47:37-05'00'
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
ADMIN
BLDG.
MAINTENANCE
BLDG.
GARLAND AVE.
ENTRANCE
GATE
FUEL STORAGE
TANKS
J
ELECTRICAL GENERAL NOTES:
1. CONTRACTOR SHOULD COORDINATE WITH THE ENGINEER OR OWNER
FOR THE DISPOSITION OF ANY EQUIPMENT NOT MENTIONED ON
THESE PLANS THAT IS FOUND IN THE FIELD THAT WILL BE AFFECTED
BY OR SHOULD BE DEMOLISHED ALONG WITH THE OTHER
DEMOLITION WORK REQUIRED FOR THIS PROJECT.
2. ALL CONDUIT EMBEDDED IN CONCRETE OR BURIED SHALL BE
ABANDON IN PLACE. THE ABANDON CONDUIT SHALL BE CUT OFF
FLUSH WITH SURFACE AND CAPPED.
3. THE OWNER SHALL HAVE FIRST RIGHT OF SALVAGE FOR ALL
DEMOLISHED EQUIPMENT. DISPOSAL OF ALL DEMOLISHED
EQUIPMENT NOT REQUESTED BY THE OWNER SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL RECYCLABLE MATERIALS
SHALL BE SORTED AND DELIVERED TO THE FT. HOOD RECYCLING
CENTER.
4. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR THE
DISPOSAL OF HAZARDOUS MATERIALS SUCH AS PCBs AND MERCURY
CONTAINING FLUORESCENT LAMPS FOLLOWING ALL LOCAL, STATE,
AND FEDERAL GUIDELINES AND PROVIDE DOCUMENTATION OF
DISPOSAL TO THE OWNER.
5. ALL ELECTRICAL EQUIPMENT SUCH AS CONDUIT, CONDUCTORS,
DISCONNECTS, SUPPORTS, ETC. THAT IS ASSOCIATED WITH OTHER
EQUIPMENT SUCH AS RECEPTACLES, LIGHTING, HVAC EQUIPMENT,
ETC THAT IS SHOWN ON THESE PLANS TO BE REMOVED SHALL ALSO
BE REMOVED FROM THE ELECTRICAL PANEL TO THE LOAD SERVED
UNLESS NOTED TO BE USED FOR NEW EQUIPMENT OR ALSO SERVING
EXISTING TO REMAIN LOADS.
6. PATCH AND FIRE SEAL AS REQUIRED ALL PENETRATIONS IN
STRUCTURES MADE BY ELECTRICAL EQUIPMENT SUCH AS CONDUIT
AND CABLE TRAY THAT IS BEING REMOVED.
7. ALL MATERIALS SALVAGED TO OWNER SHALL BE STORED BY
CONTRACTOR FOR REUSE UNTIL END OF PROJECT THEN RETURNED
TO THE OWNER.
8. REFER TO MECHANICAL AND PLUMBING DEMOLITION PLANS FOR
EQUIPMENT THAT REQUIRES ELECTRICAL SERVICE TO BE REMOVED
FROM LOAD TO SOURCE.
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:2
A
M
E-100
ELECTRICAL SITE DEMO PLAN RENOVATE MAINTENANCE
FACILITY
05/31/21 JM TT
847CM3020
1" = 20'-0"1 ELECTRICAL DEMO SITE PLAN - NORTH
1. ELECTRICAL CONTRACTOR TO REMOVE THE EXISTING FUEL
TANK PUMP CIRCUIT BACK TO THE PANEL. THE EXISTING FUEL
TANKS SHALL BE REMOVED BY OTHERS. ELECTRICAL
CONTRACTOR SHALL REMOVE THE CONDUCTORS BACK TO
THE SOURCE AND THEN CAP THE UNDERGROUND CONDUIT
BELOW GRADE.
KEYED NOTES:
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:46:17-05'00'
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
ELECTRICAL GENERAL NOTES:
1. REFER TO SPECIFICATIONS, SCHEDULES, DETAILS AND GENERAL
NOTES SHEET FOR ADDITIONAL ELECTRICAL EQUIPMENT AND
SYSTEM INSTALLATION REQUIREMENTS.
2. SPECIAL REQUIREMENTS SUCH AS MOUNTING ABOVE COUNTER
(AC), GROUND FAULT CIRCUIT INTERRUPTERS (GFI), AND
WEATHERPROOF ENCLOSURES (WP) ARE NOTED ADJACENT TO
RECEPTACLES.
3. REFER TO EQUIPMENT CONNECTION SCHEDULE FOR
DISCONNECT, CONDUIT, CONDUCTOR, AND CONTROLS
REQUIREMENTS.
4. CONTRACTOR SHALL PROVIDE POWER TO ALL ITEMS SHOWN
FROM THE PANEL AND CIRCUIT NUMBERS THAT ARE SHOWN
ADJACENT TO THE LOAD (RECEPTACLE, DISCONNECT, JBOX,
EQUIPMENT CONNECTION POINT, ETC). SIZE CIRCUIT PER PANEL
SCHEDULE. PROVIDE NEUTRAL AND GROUND, U.N.O.
5. ALL JUNCTION BOXES SHALL BE LABELED WITH THE BRANCH
CIRCUIT NUMBERS AND THEIR PANEL ORIGINATIONS.
6. ALL OUTLETS, INCLUDING RECEPTACLES AND SWITCHES SHALL BE
LABELED WITH THE BRANCH CIRCUIT NUMBERS AND THEIR PANEL
ORIGINATIONS FOR CRITICAL CARE FACILITIES AND FACILITIES
THAT MAINTAIN OR STORE HAZARDOUS MATERIALS.
7. IN OFFICE AREAS, 50% OF ALL RECEPTACLES WITHIN A SPACE
SHALL BE CONTROLLED WITH THE LIGHTING. PROVIDE RELAY THAT
PROVIDES POWER TO RECEPTACLE ONLY WHEN LIGHTING
CONTROLS ARE IN 'OCCUPIED' MODE.
8. ALL SINGLE POLE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL
CONDUCTOR ROUTED TO THE SOURCE PANEL.
ADMIN
BLDG.
MAINTENANCE
BLDG.
GARLAND AVE.
ENTRANCE
GATE1
J
2 J
NEW FUEL
STORAGE
TANKS
MAINTENENCE
AREA
PNL "PP"
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:1
A
M
E-101
ELECTRICAL SITE PLAN RENOVATE MAINTENANCE
FACILITY
05/31/21 Checker Author
847CM3020
1. ELECTRICAL CONTRACTOR TO PROVIDE A NEW CIRCUIT FOR
THE NEW HAZMAT LOCKER. PROVIDE (1) SET OF (3) #8, (1) #
10G, IN A 1" CONDUIT FROM THE NEW ELECTRICAL PANEL TO
THE NEW HAZMAT LOCKER LOCATION.
2. ELECTRICAL CONTRACTOR TO PROVIDE A NEW CIRCUIT FOR
THE NEW FUEL PUMPS. PROVIDE AN EMERGENCY PUSH
BUTTON SHUT OFF SWITCH THAT WILL TRIP THE SHUNT TRIP
BREAKER FOR THE FUEL PUMPS. PROVIDE (2) SETS OF (2) #8,
(1) #10G, IN A 1-1/2" CONDUIT FROM THE EXISTING PANEL PP TO
THE NEW PUMP LOCATIONS. REFER TO DETAILS 4 & 5 ON
SHEET E-501.
KEYED NOTES:
1" = 20'-0"1 ELECTRICAL SITE PLAN - NORTH
1" = 20'-0"2 ELECTRICAL SITE PLAN - SOUTH
Revisions: Date:
William Klock, P.E. - AR
2021.05.27 12:47:24-05'00'
2 J
NEW FUEL
STORAGE
TANKS
KEYED NOTES:
120V
1. NEW 20A/1P CIRCUIT BREAKER TO BE INSTALLED IN EXISTING PANEL PP.
CIRCUIT BREAKER SHALL BE PROVIDED WITH A SHUNT TRIP MODUEL.
2. SHUNT TRIP COIL.
3. NEW EXTERIOR RED EMERGENCY POWER OFF PUSH BUTTON,
MUSHROOM HEAD, WITH CLEAR BUBBLE LID, LABELED FOR
EMERGENCY POWER OFF. STI - #SS2079PS-EN OR APPROVED EQUAL.
FUEL TANK ESTOP
PUSH BUTTON
INPUT
POWER
PANEL PP
SHUNT TRIP
CIRCUIT
BREAKER
FUEL PUMP
MOTOR
KEYED NOTES:
GENERAL NOTES:
WIDEN TRENCH AS NECESSARY TO KEEP CONDUITS EQUALLY SPREAD AS THE NUMBER OF
CONDUITS INCREASES.
24"
GRADE
12"
2" MIN
1. SAWCUT EXISTING PARKING LOTS AND STREETS. REPLACE ASPHALT TO MATCH EXISTING. IN
GRASSY AREAS REPLACE GRASS TO MATCH.
2. BACKFILL WITH EXISTING (EXCAVATED) SOIL IN 6" LIFTS AND COMPACT TO 95%. REMOVE
ROCKS LARGER THAN 3" DIAMETER.
3. CONTINUOUS 6" WIDE RED METALLIC DETECTION MARKER TAPE.
4. BED CONDUIT USING STABLIZED SAND. WET AND COMPACT.
1.
KEYED NOTES:
1. J-BOX WITH CIRCUIT NUMBER AND VOLTAGE LABEL MOUNTED IN ACCESSIBLE CEILING SPACE.
2. UL LISTED CONDUIT SUPPORT.
3. PROVIDE 4X4" J-BOXES WITH SINGLE GANG EXTENSION COVER.
4. ATTACH TO STUD WITH SCREW ON TYPE BRACKET. USE BRACKETS SEDURED TO TWO STUDS FOR
DOUBLE GANG AND LARGER BOXES.
5. STUB RACEWAY TO NEAREST ACCESSIBLE CEILING OR IT CLOSET. REFER TO ARCHITECTURAL
RCPs FOR LOCATIONS WHERE UN-ACCESSIBLE OR EXPOSED CEILINGS REQUIRE HORIZONTAL
RUNS OF SPECIAL SYSTEMS RACEWAYS TO REACH AN ACCESS POINT.
CEILING TILE
E M
T
STUD
STUD
10' MAX
3' MAX
18" MAX
POWER COMMUNICATIONS
3" MIN
PULL STRING
TO PANEL1
ACCESSIBLE
E M
T
KEYED NOTES:
1. UNISTRUT IN CAST-IN-PLACE CONCRETE STRUCTURE.
2. SPRINGLESS NUT.
3. FLAT WASHER AND HEX NUT.
4. 1/4" THREADED ROD.
5. FLAT WASHER AND HEX NUT.
6. SPRINGLESS NUT.
7. CONTINUOUS UNISTRUT, FULL LENGTH OF LIGHT FIXTURES.
8. SELF-TAPPING SCREW. ATTACH LIGHT FIXTURES TO UNISTRUT WITH 3 SCREWS PER 48"
FIXTURE. ALL SCREWS SHALL BE ACCESSIBLE FROM TOP OF UNISTRUT FOR REMOVAL OF
FIXTURE WITHOUT REMOVING HANGER RODS.
KEYED NOTES:
GENERAL NOTES:
SECURE FLEX CONDUIT WITH UL APPROVED ATTACHEMENTS PER NEC. NO CABLE TIES.
1. J-BOX WITH CIRCUIT NUMBER AND VOLTAGE LABEL GALVANIZED STEEL 4-11/16" BOX WITH
COVER ON BOX AS REQUIRED.
2. WHERE REQUIRED BY LOCAL CODE PROVIDE ADDITIONAL HANGER WIRES TO CONNECT THE
STRUCTURE DIRECTLY TO THE LIGHT FIXTURE AT TWO POINTS INDEPENDENT OF THE T-BAR.
3. HANGER WIRE REQUIRED AT ALL FOUR CORNERS.
4. FLEX CONDUIT. MAXIMUM 6'-0".
5. T-BAR LOCK CLIP (2 REQUIRED PER FIXTURE), SECURE FIXTURE TO T-BAR AT OPPOSITE
CORNERS.
6. WIRING ADAPTER PLATE.
7. STRAIGHT CONNECTOR FOR UA FLEX.
1.
CONDUIT
T-BAR
CEILING TILE
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:5
A
M
E-501
ELECTRICAL DETAILS RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
NTS4 FUEL TANK EPO SWITCH
NTS5 TYPICAL TRENCH DETAIL
NTS1 POWER & IT OUTLET INSTALLATION DETAIL
NTS2 LIGHT FIXTURE HANGER AND SUPPORT DETAIL
NTS3 TYPICAL LUMINAIRE INSTALLATION DETAIL
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:47:55-05'00'
LIGHTNING & GROUNDING
155 / 156 - STYLE VERTICAL AIR TERMINAL BASE
NTS
120 - STYLE AIR TERMINAL
ADAPTER
COPPER OR ALUMINUM,
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
CCC / ACC - SERIES
CABLE FASTENER
155 / 156 - STYLE
UNIVERSAL CONCEALED
AIR TERMINAL BASE
MOUNTED VERTICALLY
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
LIGHTNING & GROUNDING
160 - STYLE AIR TERMINAL BASE EXTENSION
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
160 - STYLE RIDGE
SADDLE AIR
TERMINAL BASE
CCC / ACC - SERIES
CABLE FASTENER
COPPER OR ALUMINUM,
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
NTS
LIGHTNING & GROUNDING
155 / 156 - STYLE HORIZONTAL AIR TERMINAL BASE
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
155 / 156 - STYLE
UNIVERSAL CONCEALED
AIR TERMINAL BASE
MOUNTED HORIZONTALLY
CCC / ACC - SERIES
CABLE FASTENER
COPPER OR ALUMINUM,
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
120 - STYLE AIR
TERMINAL ADAPTER
NTS
LIGHTNING & GROUNDING
225 - STYLE THRU-ROOF CONNECTOR
225 - STYLE THRU-ROOF
CONNECTOR
COPPER OR ALUMINUM,
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
COPPER OR ALUMINUM,
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
NTS
LIGHTNING & GROUNDING
300 - STYLE GROUND ROD DETAIL
NO. 302U, UNIVERSAL
GROUND ROD CLAMP
COPPER, COPPER CLAD OR
STAINLESS STEEL GROUND
ROD
COPPER LIGHTNING
PROTECTION OR
GROUNDING CONDUCTOR
NTS
LIGHTNING & GROUNDING
305 - STYLE GROUND ROD DETAIL
NO. 305 - GROUND
ROD CLAMP
COPPER, COPPER CLAD OR
STAINLESS STEEL GROUND
ROD
COPPER LIGHTNING
PROTECTION OR
GROUNDING CONDUCTOR
NTS
LIGHTNING & GROUNDING
305 - GAW910 - GROUND ROD DETAIL
NTS
GAW910 - TEST
WELL
COPPER LIGHTNING
PROTECTION OR
GROUNDING
CONDUCTOR
COPPER, COPPER CLAD OR
STAINLESS STEEL GROUND
ROD
NO. 305 - GROUND
ROD CLAMP
LIGHTNING & GROUNDING
No. 217, Style Bonding Plate No. 222, Style Heavy Duty Bonding Lug
No. 213, Style Bonding Plate No. 216, Style Bonding Lug
No. 223, Style Flange Bonding Plate
TYPICAL BONDING LUGS & PLATES
NTS
50H2
HLP
U L
LIGHTNING & GROUNDING
THRU-ROOF CONNECTOR.12
LIGHTNING DOWN CONDUCTOR.
VERTICALLY MOUNTED AIR TERMINAL ON PARAPET SPACE 20 FEET
MAXIMUM. SEE AIR TERMINAL DETAIL.
AIR TERMINAL MOUNTED ON EXHAUST FAN (`DEAD-END' METHOD).
AIR TERMINALS MOUNTED ON MECHANICAL EQUIPMENT ENCLOSURE.
HORIZONTALLY MOUNTED AIR TERMINAL ON ROOF SPACE 20 FEET
MAXIMUM. SEE AIR TERMINAL DETAIL.
BONDING DETAILS AND AIR TERMINAL LOCATIONS
SHOWN ARE TYPICAL, GENERAL EXAMPLES ONLY.
FINAL EXTENT OF BONDING AND SPECIFIC FITTING
APPLICATIONS TO BE DETERMINED IN FIELD BASED
ON ACTUAL SITE CONDITIONS.
BOND WINDOW, DOOR FRAMES, V.T.R.'S, LADDERS, AND ANTENNAS, OR
ANY METALLIC OBJECTS WITH BONDING LUGS AND SECONDARY
CONDUCTOR.
MAIN LIGHTNING CONDUCTOR.
CABLE CONNECTOR.
CABLE CLIP WITH STAINLESS STEEL SCREWS EVERY 3 FEET MAXIMUM
SPACING.
ADEHSIVE CABLE HOLDER EVERY 3 FEET MAXIMUM SPACING.
5 AIR TERMINAL ON SKYLIGHT WITH SADDLE TYPE AIR TERMINAL BASE.
AIR TERMINAL MOUNTED ON GUARDRAIL WITH PIPE RAILING BASE. 13
TYPICAL ROOF LIGHTNING PROTECTION LAYOUT
NTS
6615 Vaught Ranch Road, Suite 100
Austin, Texas 78730-2314 USA
512.744.4400 main - 512.744.4444 fax www.eeace.com
State of registration AR
Firm Registration No. 1032
EEA Project No.
CONSULTING
ENGINEERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PROJECT ARCHITECTCONSULTANT
321 4 5 6 7 8 9 10
N/A
FORT SMITH, AR
INTERIORSARCHITECTURE
COX DESIGN ASSOCIATES
PLANNING
Austin
5121 Bee Caves Road, Suite 203
Austin, Texas 78746
T: 512-327-4149
F: 512-327-7679e info@coxdesignassociates.com
20200211
C U s e rs \A a ro n B u lla
\D o c u m e n ts
\2
F S
N C
M
E P
C E
N T
R A
L
A a ro n
B u lla .r v t
/2
/2
:2
:0
A
M
E-502
LIGHTNING PROTECTION
DETAILS
RENOVATE MAINTENANCE
FACILITY
05/31/21 SB AB
847CM3020
Revisions: Date:
CONSTRUCTION DOCUMENTS 05/31/21
2021.05.27 12:46:31-05'00'
LARGEST MOTOR LOAD TOTAL PANEL
DEMAND AMPERAGE
15 SPARE 20/1 B - " " 16 3600
17 SPACE - A 20/1 A/C #3 FURNACE 18 1000
19 SPACE - B 20/1 SPARE 20
21 SPACE - A - SPACE 22
23 SPACE - B - SPACE 24
25 SPACE - A SPACE 26
27 SPD FOR LP SYSTEM N 30/2 B - SPACE 28
29 " " - A - SPACE 30
EEA PROJECT NAME: Fort Smith National Cemetery
PANEL M (EXISTING)EEA PROJECT NUMBER: 20200211 5/25/2021 20:52
PANEL OPTIONS: BUS RATING: 400A AIC RATING: EXISTING CB OPT: ST - SHUNT TRIP
MAIN: 400A MCB BUSSING: COPPER SS - SOLID STATE
VOLTAGE: 240/120V1PH,3W MOUNTING: SURFACE GF - GROUND FAULT CIRCUIT INTERRUPTER
LOCATION: REFER TO PLAN NEMA ENCLOSURE: NEMA 3R FR - FULLY RATED
FED FROM: UTILITY METER L - LOCKABLE
FEEDER SIZE: REFER TO ONE LINE N - NEW CB, MATCH EXIST MFR. & AIC RATING
LOAD (VA) CB CB LOAD (VA)
PHASE LOADING CONNECTED
AMPS PER
PHASE
PANEL TOTALS
LIGHT RECPT CONT MISC MOTOR KITCH TOTAL LIGHT RECPT CONT MISC MOTOR KITCH
1850 3600 0 500 14300 3250 23500 PHASE A 196 A 120 CONNECTED KVA TOTALS 4.23 7.20…