S02 - ATTACHMENT 4 - Drawings Vol. 2 of 3.pdf

PDF 14 MB Posted

Attached to
Y1DA--Remodel Specialty Care & Correct HVAC in Bldg. 19 - Martinez VAMC
Solicitation number
36C77621B0021
Issued by

About this file

This document provides details for a federal contract solicitation to remodel specialty care and correct HVAC systems in Building 19 at the Martinez VA Medical Center in California. The contractor will be responsible for providing all labor, materials, equipment, supervision and other resources necessary to complete the construction project according to the specifications and drawings in the attachments. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Contractors must have experience with remodeling and HVAC system work and will be expected to start work promptly upon award. The response deadline and anticipated award date are not specified in this document.

View the file

Other files

File Type Posted
S05 - Att 08e - Existing Equipment (5).jpg JPG image
S05 - Att 08b - Existing Equipment (2).jpg JPG image
S05 - Att 04 - 19_Martinez Floor Plan.pdf PDF
S05 - Att 03 - ICRA_ICCP -- Final.pdf PDF
S05 - Att 08g - Existing Equipment (7).jpg JPG image
S05 - Att 07g - CAD Files - Plumbing (7).zip ZIP file
S05 - Att 07b - CAD Files - Architectural (2).zip ZIP file
S05 - Att 08h - Existing Equipment (8).jpg JPG image
S05 - Att 07f - CAD Files - Mechanical (6).zip ZIP file
S05 - Att 07d - CAD Files - Electrical (4).zip ZIP file
S05 - Att 06 - VAV Pipe Detail.zip ZIP file
S05 - Att 02 - Nurse Call Cut-Sheets Request.pdf PDF
36C77621B0021 0003.pdf PDF
S05 - Att 08d - Existing Equipment (4).jpg JPG image
S05 - Att 07c - CAD Files - Structural (3).zip ZIP file
S05 - Att 07a - CAD Files - Architectural (1).zip ZIP file
S05 - Att 07b - CAD Files - Structual.zip ZIP file
S05 - Att 07e - CAD Files - Fire Protection (5).zip ZIP file
S05 - Att 05 - Martinez B19_RxR_220908.xlsx XLSX spreadsheet
S05 - Att 08a - Existing Equipment (1).jpg JPG image
S05 - Att 08i - Existing Equipment (9).jpg JPG image
S05 - Att 08c - Existing Equipment (3).jpg JPG image
S05 - Att 01 - Technical Questions and Answers 9.9.2022.pdf PDF
S05 - Att 08f - Existing Equipment (6).jpg JPG image
S05 - Att 09 - CAD Files - Chaparral Layouts.zip ZIP file
36C77621B0021 0002.pdf PDF
S04 - Site Visit - Sign-in Sheet.pdf PDF
S06 - SF30 - 36C77621B0021 - Amendment 0001.pdf PDF
S02 - ATTACHMENT 2 - Specifications Vol. 2 of 2.pdf PDF
S02 - ATTACHMENT 9 - Construction Wage Rates.pdf PDF
36C77621B0021.pdf PDF
S02 - ATTACHMENT 10 - Contractor Safety - Environmental Form.docx DOCX document
S02 - ATTACHMENT 5 - Drawings Vol. 3 of 3.pdf PDF
S02 - ATTACHMENT 8 - Limitations on Subcontracting - Construction.docx DOCX document
S02 - ATTACHMENT 6 - Contractor Core Work Hours.pdf PDF
S02 - ATTACHMENT 7 - COVID-19 Safety Protocols 12-14-21.pdf PDF
S02 - ATTACHMENT 3 - Drawings Vol. 1 of 3.pdf PDF
S02 - ATTACHMENT 1 - Specifications Vol. 1 of 2.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5 6 7

N

P

Q

R

S

T

U

V

1A

/A 350 SF

B130

BLOOD DRAW

LBVP1

/A 64 SF

B131

LAB/PC TOILET

TLTU1

/A 83 SF

B175

WS CONSULT

OFDC2

/A 116 SF

B143A

PC EXAM

EXPA1

/A 112 SF

B144A

PC Exam

EXPA1

/A 113 SF

B132

PC EXAM

EXPA1

/A 126 SF

B146

PC EXAM

EXPA1

/A 123 SF

B145

PC EXAM

EXPA1

/A 230 SF

B145B

TEAM ROOM

WRTM1

/A 117 SF

B144

PC EXAM

EXPA1

/A 121 SF

B143

PC EXAM

EXPA1

/A 56 SF

B174

WS TOILET

TLTU1

/A 225 SF

B171

WS

PROCEDURE

TRPR1

/A 117 SF

B173

WS EXAM

EXPA1

/A 47 SF

B180

HAC

JANC1

/A 82 SF

B170

WS WAITING

WRC01

/A 57 SF

B170A

RECEPTION/GREETER

RECP1

IN-04.03

IN-04.03

IN-04.03

IN-04.03IN-04.03

IN-04.03

IN-09.03

IN-07.01

IN-04.03

IN-04.03

IN-04.03

IN-04.03IN-14.07

IN-14.07

IN-14.07

IN-01.29

IN-04.03

IN-01.29

IN-09.03

IN-09.02

IN-04.03

/A 47 SF

B171A

WS TOILET

TLTB1/A 41 SF

B172

SOILED

UTILITY

USCL1

IN-04.03

/A 116 SF

B133

PC EXAM

EXPA1

IN-04.03

IN-01.31

IN-01.31

IN.01.02

IN.01.02

/A 118 SF

1074A

CORRIDOR

/A 100 SF

CORRIDOR

/A 99 SF

CORRIDOR

IN-04.03

R.2

IN-04.03

IN-13.01

IN-13.01

/A 255 SF

CORRIDOR

/A 252 SF

CORRIDOR

/A 102 SF

B145A

BREAKROOM

EX. CORRIDOR

(NO WORK)

IN-14.07

IN-04.03

IN-01.29

MAINT ID

MAINT ID

MAINT ID

MAINT ID

MAINT ID

MAINT ID

MAINT ID

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :4

P

M

AW101

ENLARGED PHASE 2 FIRST FLOOR

WAYFINDING PLAN - EAST

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

100% - BID SET

KEY PLAN

Floor 1

1. PARTIALLY-CONSTRUCTED WALLS HAVE BEEN FRAMED (FRAMING SIZE TO BE V.I.F.) AND BEEN TAGGED WITH PARTITION TYPE TAGS FOR REFERENCE ONLY. GC IS TO COORDINATE FINISHES BASED ON REFERENCED PARTITION TYPE. IT IS THE RESPONSIBILITY OF THE GC TO EVALUATE PARTIALLY-CONSTRUCTED PARTITIONS AND REPLACE

WALL COMPONENTS AS NEEDED.

2. CONTRACTOR SHALL FIELD VERIFY EXTENT OF ALL EXISTING PARTIALLY-CONSTRUCTED PARTITIONS PRIOR TO BEGINNING WORK. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSPECT SUCH PARTITIONS AND REPLACE

COMPONENTS AS NEEDED TO MATCH ILLUSTRATED PARTITION TYPES.

3. WHERE EXISTING GYP. BD. FINISH IS REMOVED FOR NEW CONSTRUCTION, PROVIDE NEW 5/8" GYP. BD. AS REQUIRED TO PATCH EXISTING PARTITIONS. INSTALL NEW GYP. BD. ON EXISTING STEEL STUDS, PROVIDE ADDITIONAL 16 GAUGE WIDTH TO MATCH EXISTING STUD WIDTH STEEL STUDS AS REQUIRED TO ACHIEVE STUD SPACING AT 16" O.C.

MAXIMUM. PATCH EXISTING INSULATION AS REQUIRED. PATCH WORK SHALL MATCH EXISTING ADJACENT AREA IN

CONSTRUCTION, MATERIAL, TYPE, AND FIRE RESISTIVE RATINGS.

4. ADJUST FURRING SPACE AS NECESSARY TO CLEAR ANY PIPES OR CONDUITS WITHIN THE FURRING SPACE. PROVIDE 1/2-INCH CLEAR MINIMUM CLEARANCE BETWEEN PIPES, CONDUITS AND THE BACK OF GYPSUM BOARD, UNLESS

OTHERWISE NOTED.

5. AT SOUND RATED PARTITION, PROVIDE 3 1/2" THICK ACOUSTICAL INSULATION, EXTEND SOUND INSULATION TO UNDERSIDE OF STRUCTURE, SOUND INSULATION SHALL BE CONTINUOUS BEHIND PANELS, FIXTURES AND OTHER WALL PENETRATIONS. AT NON-FIRE RATED PARTITION, EXTEND BOTH SIDES OF GYPSUM BOARD TO UNDERSIDE OF

STRUCTURE AND SEAL AIR TIGHT, TYPICAL, UNLESS OTHERWISE NOTED.

6. WHERE FLOOR FINISHES CHANGE BETWEEN ROOMS, TRANSITION SHALL OCCUR AT CENTER OF DOOR.

7. PROVIDE AND COORDINATE BACKING PLATES FOR ALL ACCESSORIES, CASEWORK, EQUIPMENT, ETC., SEE SHEET

AS502 FOR BACKING PLATE TYPES AND INTERIOR ELEVATIONS FOR LOCATIONS.

8. PATCH TO MATCH EXISTING PARTITIONS, CEILING AND FLOORING DAMAGED BY NEW CONSTRUCTION WORK WITHIN

OR OUTSIDE THE PROJECT AREA. PATCH WORK SHALL MATCH EXISTING ADJACENT AREA IN CONSTRUCTION, MATERIALS, COLORS, FIRE-RESISTIVE RATINGS AND FINISHES.

9. PROVIDE SUPPORTS AND BRACINGS AS REQUIRED FOR EXISTING UTILITIES, PIPES, CONDUITS, DUCTS, ETC., WHERE EXISTING SUPPORTS WERE REMOVED DUE TO WORK UNDER THIS CONTRACT. NEW SUPPORTS SHALL MEET

CURRENT CODE REQUIREMENTS.

10. IN ALL CONSTRUCTION AREAS, SEAL ALL EXISTING AND NEW PENETRATIONS SUCH AS DUCTS, CONDUITS, PIPES, ETC. THAT PENETRATE EXISTING, NEW FIRE-RATED AND ACOUSTIC PARTITIONS AND FLOOR/CEILING ASSEMBLIES, WHETHER SHOWN OR NOT. USE APPROPRIATE SEALANT TYPE AND FIRESTOPPING TO MAINTAIN PROPER FIRE RATING OF THE PENETRATED ASSEMBLIES. PENETRATIONS SHALL BE IN COMPLIANCE WITH IBC CHAPTER 7.

11. BEADBLAST EXISTING FLOORING TO REMOVE ALL GREASE, GLUE, ETC., FILL ALL EXISTING CRACKS, DEPRESSIONS, AND INSTALL LEVELING COMPOUND TO PROVIDE A CLEAN AND SMOOTH SUB-FLOOR FOR FINISHED FLOORING.

12. EXISTING COLUMN SPACINGS SHOWN ARE APPROXIMATE AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL

OBTAIN THESE DIMENSIONS BY FIELD MEASUREMENT.

13. FOR CABINET AND COUNTERTOP TYPE, SEE CASEWORK SECTIONS AND DETAILS ON SHEET AS503.

14. PATCH AND REPAIR EXISTING CONCRETE SLAB REMOVED OR DAMAGED BY NEW CONSTRUCTION WORK WITHIN OR

OUTSIDE THE PROJECT AREA. PATCH WORK SHALL MATCH EXISTING ADJACENT IN CONSTRUCTION, MATERIALS, BELOW SLAB VAPOR BARRIER, AGGREGATE BASE, SUB-BASE, COLORS, AND FINISHES.

GENERAL SIGNAGE AND WAYFINDING NOTES

N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

1/4" = 1'-0"

ENLARGED PHASE 2 FIRST FLOOR WAYFINDING PLAN - EAST

Revisions: Date:

E

F

G

/A 164 SF

C201

CHARTING

IN-04.03

EX. HALLWAY

(NO WORK)

3 5

N

P

Q

R

S

T

U

V

/A 151 SF

B202

PRE-SCREENING/

EXAM 2

EYOT2

/A 165 SF

B203

PRE-SCREENING/

EXAM 3

EYOT2

/A 120 SF

B204

WAITING

WTG03

/A 159 SF

B224

(E) EXAM 3

/A 162 SF

B225

(E) EXAM 4

/A 167 SF

B226

PROCEDURE/

EXAM

/A 70 SF

B392

(E) HUDDLE

/A 125 SF

B227

RN/ PA OFFICE

/A 204 SF

B213

CATARACT

SURGERY

TESTING

/A 111 SF

B212

VISUAL FIELD

EYVF1

/A 132 SF

B209

EXAM/

TREATMENT 9

EYOT2

/A 132 SF

B210

EXAM/

TREATMENT 8

EYOT2

/A 141 SF

B223

(E) OFFICE /

EXAM

/A 113 SF

B205

(E) EXAM/

TREATMENT 5

/A 210 SF

B206

MD TECH

WKSTN

WRTM1/A 120 SF

B207

EXAM/

TREATMENT 7

EYOT2

/A 133 SF

B208

BREAK ROOM

SL001

/A 281 SF

CORRIDOR

/A 417 SF

B349

WAITING

/A 139 SF

B216A

RECEPTION -

EYE CLINIC

RCP1

M5016

4' - 8 5/8"

/8

IN-04.03 IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-14.07

/A 19 SF

B200

SOILED

/A 92 SF

B201

PRE-SCREENING/

EXAM 1

EYVS1

IN-01.29

IN-04.03

PHASE 1 CONSTRUCTION PHASE 2 CONSTRUCTION

IN.01.02

IN-01.31

IN-01.31

/A 334 SF

CORRIDOR

/A 334 SF

CORRIDOR

/A 387 SF

CORRIDOR

IN.01.02

/A 157 SF

B214B

EXAM

EXPA1

/A 155 SF

B214E

EXAM

EXPA1

/A 107 SF

B214C

OFFICE

OFA07

/A 105 SF

B214D

OFFICE

OFA07

/A 155 SF

B214G

EXAM

EXPA1

/A 107 SF

B214F

CLEAN UTILITY

/ OMNI

/A 207 SF

B214K

ENT EXAM

EXPA1

/A 237 SF

B214J

TEAM ROOM

WRTM1

/A 155 SF

B214I

EXAM

EXPA1

/A 58 SF

B214H

TOILET

TLTU1

/A 44 SF

B214L

SOILED

UTILITY

USCL1

/A 387 SF

CORRIDOR

/A 274 SF

B214A

PROCEDURE

TRPR1

/A 190 SF

B211

OCT

IMAGING/FUNDUS

PHOTO

EYVS1

IN-04.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03 IN-04.03

IN-04.03

IN-09.03

IN-04.03

IN-04.03

IN-04.03

IN-04.03

R.2

IN-04.03

IN-04.03

IN-13.01

IN-04.03IN-04.03

EX. CORRIDOR

(NO WORK)

IN-01.29MAINT ID

MAINT ID MAINT ID

MAINT ID

MAINT ID

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :5

P

M

AW102

ENLARGED PHASE 1 & 2 SECOND

FLOOR WAYFINDING PLANS

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

100% - BID SET

KEY PLAN

Floor 2

N

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

1/4" = 1'-0"

ENLARGED PHASE 1 SECOND FLOOR WAYFINDING PLAN - NORTH

1/4" = 1'-0"

ENLARGED PHASE 1 & 2 SECOND FLOOR WAYFINDING PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :5

P

M

AW103

SIGNAGE SCHEDULE & SIGNAGE

FINISHES

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

100% - BID SET

Signage Schedule

Sign ID Room #

Room: Name Sign Message Mounting

Height (Top) Sign

Height Sign Width Sign Type Sign Mounting Comments

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214E CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214F CORRIDOR CLEAN UTILITY 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214G CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-09.03 - RESTROOM IDENTIFICATION B214H CORRIDOR RESTROOM 5' - 0" 1' - 0" 0' - 9" Interior Signs TAPE MOUNT With Graphic

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214I CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214J CORRIDOR TEAM ROOM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214K CORRIDOR ENT EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214L CORRIDOR SOILED 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B216A EX. CORRIDOR

(NO WORK)

RECEPTION-EYE CLINIC 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B349 WAITING MULTI-SPECIALTY 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B349 WAITING EYE CLINIC 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B349 WAITING WAITING 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT C201 EX. HALLWAY (NO

WORK)

CHARTING 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

Signage Schedule

Sign ID Room #

Room: Name Sign Message Mounting

Height (Top) Sign

Height Sign Width Sign Type Sign Mounting Comments

IN-14.07 - WALL DIRECTIONAL SIGN 1050 CORRIDOR (Symbol Arrow Left) PC Exam (Symbol Arrow Right) PC Exam

6' - 0" 2' - 6" 1' - 8" Interior Signs TAPE MOUNT

IN-01.02 - FIRE EQUIPMENT IDENTIFICATION 1050 CORRIDOR FIRE EQUIPMENT 6' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT With Graphic

IN-01.29 - EXIT SIGN 3"x9" - VANCHCS 1074 CORRIDOR EXIT 6' - 8" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT With Graphic

IN-01.31 - FIRE EQUIPMENT IDENTIFICATION (FLAG) 1074A CORRIDOR FIRE EQUIPMENT 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG With Graphic

IN-13.1 - PERPENDICULAR (FLAG) MOUNT 2 1074A CORRIDOR RESTROOM 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG With Graphic

IN-14.07 - WALL DIRECTIONAL SIGN 1074A-1 CORRIDOR (Symbol Arrow Left) Blood Draw (Symbol Arrow Right) Lab/PC Toilet, PC Exam

6' - 0" 2' - 6" 1' - 8" Interior Signs TAPE MOUNT

IN-01.29 - EXIT SIGN 3"x9" - VANCHCS 1075 CORRIDOR EXIT 6' - 8" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT Vinyl Glass Backer

IN-14.07 - WALL DIRECTIONAL SIGN 1076 EX. CORRIDOR

(NO WORK)

Primary Care and Women Services

6' - 0" 2' - 6" 1' - 8" Interior Signs TAPE MOUNT

IN-14.07 - WALL DIRECTIONAL SIGN 1076 CORRIDOR (Symbol Arrow Right) WS Exam, WS Procedure, Reception/Greeter, WS Waiting (Symbol Arrow Left) WS Consult, WS Toilet, PC Exam

6' - 0" 2' - 6" 1' - 8" Interior Signs TAPE MOUNT

IN-01.29 - EXIT SIGN 3"x9" - VANCHCS 1076 CORRIDOR WS WAITING 6' - 8" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT

IN-01.31 - FIRE EQUIPMENT IDENTIFICATION (FLAG) 1076 CORRIDOR FIRE EQUIPMENT 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG With Graphic

IN-01.02 - FIRE EQUIPMENT IDENTIFICATION 1076 CORRIDOR FIRE EQUIPMENT 6' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT With Graphic

IN-13.1 - PERPENDICULAR (FLAG) MOUNT 2 1076 CORRIDOR RESTROOM 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG With Graphic

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B130 EX. CORRIDOR

(NO WORK)

BLOOD DRAW 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-09.03 - RESTROOM IDENTIFICATION B131 CORRIDOR RESTROOM 5' - 0" 1' - 0" 0' - 9" Interior Signs TAPE MOUNT With Graphic

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B132 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B133 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B143 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B143A CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B144 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B144A CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B145 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B145A CORRIDOR STAFF LOUNGE 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B145B CORRIDOR TEAM ROOM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B146 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B170 WS WAITING WS WAITING 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B170A RECEPTION/GREE

TER

RECEPTION 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B171 CORRIDOR PROCEDURE 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-09.02 - RESTROOM IDENTIFICATION B171A WS PROCEDURE RESTROOM 5' - 0" 1' - 0" 0' - 9" Interior Signs TAPE MOUNT With Graphic

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B172 CORRIDOR SOILED 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B173 CORRIDOR WS EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-09.03 - RESTROOM IDENTIFICATION B174 CORRIDOR RESTROOM 5' - 0" 1' - 0" 0' - 9" Interior Signs TAPE MOUNT With Graphic

IN-07.01 - CONFERENCE / CONSULT ROOM

IDENTIFICATION -VANCHCS

B175 CORRIDOR WS CONSULT 5' - 0" 1' - 0 1/4" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B180 EX. CORRIDOR

(NO WORK)

HAC 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-01.29 - EXIT SIGN 3"x9" - VANCHCS 2019 CORRIDOR WAITING 6' - 8" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT

IN-01.31 - FIRE EQUIPMENT IDENTIFICATION (FLAG) 2019 CORRIDOR FIRE EQUIPMENT 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG With Graphic

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT 2019 CORRIDOR PROCEDURE 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-13.1 - PERPENDICULAR (FLAG) MOUNT 2 2019 CORRIDOR RESTROOM 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG With Graphic

IN-01.29 - EXIT SIGN 3"x9" - VANCHCS 2026 CORRIDOR EXIT 6' - 8" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT

IN-01.31 - FIRE EQUIPMENT IDENTIFICATION (FLAG) 2026-2 CORRIDOR THIS WAY OUT 7' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

FLAG

IN-01.02 - FIRE EQUIPMENT IDENTIFICATION 2026-3 CORRIDOR FIRE EQUIPMENT 6' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT With Graphic

IN-14.07 - WALL DIRECTIONAL SIGN 2027 CORRIDOR (Symbol Arrow Right) Exam Treatment 7, Exam Treatment 8, Exam Treatment 9, Toilet, ENT Exam

6' - 0" 2' - 6" 1' - 8" Interior Signs TAPE MOUNT

IN-01.02 - FIRE EQUIPMENT IDENTIFICATION 2027 CORRIDOR FIRE EQUIPMENT 6' - 0" 0' - 9" 0' - 9" Code and Life Safety Signs

TAPE MOUNT With Graphic

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B200 CORRIDOR SOILED 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B201 CORRIDOR PRE-SCREENING/EXAM 1 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B202 CORRIDOR PRE-SCREENING/EXAM 2 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B203 CORRIDOR PRE-SCREENING/EXAM 3 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B204 WAITING WAITING 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B206 CORRIDOR MD TECH 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B207 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B208 CORRIDOR STAFF LOUNGE 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B209 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B210 CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B211 CORRIDOR OCT IMAGING 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B212 CORRIDOR VISUAL FIELD 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B213 CORRIDOR CATARACT SURGERY

TESTING

5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214B CORRIDOR EXAM 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214C CORRIDOR OFFICE 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

IN-04.03 - PRIMARY ROOM IDENTIFCATION WITH INSERT B214D CORRIDOR OFFICE 5' - 0" 0' - 9" 0' - 9" Interior Signs TAPE MOUNT

NOTE:

Utilize VANCHCS signage standards package for signage requirements. Sign types not included in the VANCHCS signage standard, shall follow the TIL standard with VANCHCS shape and finishes.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :5

P

M

AW104

SIGN TYPE DETAILS

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

100% - BID SET

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :5

P

M

AW105

SIGN TYPE DETAILS

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :0

P

M

AW106

SIGN TYPE DETAILS

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

B

IM

/M a rt in e z B

/6

-1

-3

A

.r v t

/3

/2

:5 :0

P

M

AW107

SIGN TYPE DETAILS

CONCOURSE FEDERAL GROUP

213 SOUTH ROYAL STREET

ALEXANDRIA, VA 22314

GENE KLOW

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/2021

SYSTEM #W-L-1001 FOR UNINSULATED PIPE. SYSTEM

#W-L-5001 FOR INSULATED PIPE.

3M/CP 25W/B CAULK OR

3M/CP 25N/S CAULK ON

BOTH SIDES OF THE WALL.

DETAIL NOTES

PIPE INSULATION

(WHERE APPLICABLE)

FIRE RATED WALL

DAMMING MAT.

1. THE MAXIMUM ANNULAR SPACE TO BE FILLED IS 2". THE MINIMUM

ANNULAR SPACE IS 3/4". THE MAXIMUM PIPE SIZE IS A NOMINAL 4".

2. FOR SOLID CONCRETE WALLS, 3M/CP 25 CAULK MAY BE CENTERED

IN THE WALL WITH DAMMING MATERIAL ON BOTH SIDES OF CAULK.

3. USE CP 25S/L (SELF LEVELING) CAULK ON HORIZONTAL SURFACES

WHEN SEALING OPENING FROM ABOVE THE PENETRATION. USE

CP25N (NO SAG) CAULK ON VERTICAL SURFACES AND ON

HORIZONTAL SURFACES WHEN SEALING OPENINGS FROM BELOW.

USE CP 25WB CAULK ON EITHER APPLICATION.

4. SHRINKAGE OF CP CAULKS IS ACCEPTABLE AFTER INITIAL WET

DEPTH INSTALLATION.

5. THE DEPTH OF THE CP 25 CAULKS DEPENDS ON THE INSULATION

THICKNESS.

CAULK DEPTH (MIN.) INSULATION

1" 1" THICK

2" 2" - 3" THICK

6. IF WATER PIPE IS INSULATED, CAULK PIPE OUTSIDE OF PIPE

INSULATION.

SYSTEM #C-AJ-5017 FOR CONCRETE WALL/ FLOOR PENETRATIONS

DROP

SPRINKLER HEAD B OBSTRUCTION

A

DISTANCE FROM MAX. ALLOWANCE DISTANCE

SPRINKLERS TO SIDE OF

OBSTRUCTION

(A)

LESS THAN 1 FT.

1'-0" TO LESS THAN 1'-6"

1'-6" TO LESS THAN 2'-0"

2'-0" TO LESS THAN 2'-6"

2'-6" TO LESS THAN 3'-0"

3'-0" TO LESS THAN 3'-6"

3'-6" TO LESS THAN 4'-0"

4'-0" TO LESS THAN 4'-6"

4'-6" TO LESS THAN 5'-0"

5'-0" TO LESS THAN 5'-6"

5'-6" TO LESS THAN 6'-0"

6'-0" TO LESS THAN 6'-6"

6'-6" TO LESS THAN 7'-0"

7'-0" TO LESS THAN 7'-6"

OF DEFLECTOR ABOVE BOTTOM

OF OBSTRUCTION (IN.)

(B)

2-1/2

3-1/2

5-1/2

7-1/2

9-1/2

16-1/2

CONCRETE FILLED

HILTI "KWIK BOLT TZ"

CONCRETE EXPANSION

ANCHOR. 3/8"∅ W/ 2"

EMBEDMENT (ICC

ESR-1917)

3/8" ROD COUPLING

3/8" ALL THREADED ROD

TOLCO FIG. 100

"KWIK-BOLT TZ" ANCHOR, ROD, COUPLING AND RING

PIPE SIZE MAXIMUM SPACING

EXISTING

STRUCTURAL STEEL

NOTE:

A.

1" MIN.

3/8" ALL THREADED ROD

RESTRAINING STRAP (TYP.)

TOLCO FIG. 200

TOLCO FIG. 100

TOLCO FIG. 69/69R

PIPE RING HANGER

SPRINKLER PIPE PER PLAN

BEAM CLAMP, ROD, COUPLING AND RING

MAXIMUM SPACINGPIPE SIZE

1" & 1 1/4"

1 1/2" - 3" 15'-0"

12'-0"

PIPE HANGER TO STEEL

FOR STEEL PIPE, THE UNSUPPORTED HORIZONTAL LENGTH BETWEEN THE END

SPRINKLER AND THE LAST HANGER ON THE LINE SHALL BE AS FOLLOWS;

PIPE SIZE

1"

1 1/2" & LARGER

1 1/4"

HORIZONTAL LENGTH

NOT GREATER THAN 48"

NOT GREATER THAN 36"

NOT GREATER THAN 60" (NFPA 13, SEC. 17.4.3.4.1, 2019 EDITION)

SYMBOL

REVERSIBLE BEAM CLAMP

(TYPICAL) TOLCO FIG. 65

1" MIN.

1" & 1 1/4"

4" & LARGER

1 1/2" - 3" 15'-0"

12'-0"

10'-0"

PIPE HANGER TO CONCRETE

PIPE RING HANGER

TOLCO FIG. 200

SPRINKLER PIPE PER PLAN

TO

L

C O

T O L

C O

T O L

C O

METAL DECK

(2) #8 x 1/2" SELF-TAPPING

SCREWS

BARE METAL DECK

4 TIGHT TURNS

3" WIDE x 4" LONG, 12 GA. STEEL STRAP

SPLAYED SEISMIC BRACING WIRE

PER NFPA 13 2019, FIG. A.18.6.1(b)

SURGE RESTRAINER

TOLCO FIG. 25

5/16" DRILL-IN EXPANSION

ANCHOR

END OF BRANCH LINE SEISMIC RESTRAINT

(NFPA 13 2019, SECTION A.18.6.1)

CONCRETE

1" WIDE x 2" LONG, 12 GA. STEEL STRAP

4 TIGHT TURNS

SPLAYED SEISMIC BRACING WIRE

PER NFPA 13 2019, FIG. A18.6.1(a) NOTES:

1. THE END SPRINKLER ON A BRANCH LINE SHALL BE RESTRAINED

AGAINST EXCESSIVE VERTICAL OR LATERAL MOVEMENT

(NFPA 13, 18.6.3, 2019 EDITION.)

2.

3/8"∅ ALL-THREAD ROD

W/ RING HANGER AND

SURGE RESTRAINER

TOLCO FIG. 25

SURGE RESTRAINER

ALTERNATE END OF BRANCH LINE SEISMIC RESTRAINT

(NFPA 13 2019 SECTION A.18.6.1)

THE ABOVE DETAIL CAN ALSO BE USED WHERE THE UPWARD

OR LATERAL MOVEMENT OF THE SYSTEM PIPING WOULD RESULT

IN DAMAGE TO THE SPRINKLER THROUGH THE IMPACT AGAINST

THE BUILDING STRUCTURE, EQUIPMENT OR FINISH MATERIALS.

(NFPA 13, TABLE 18.6.4(a), 2019 EDITION.)

PIPE SIZE

1"

1 1/2"

1 1/4"

2"

MAXIMUM SPACING

27' INTERVALS

26' INTERVALS

29' INTERVALS

31' INTERVALS

DENOTES LINE RESTRAINT WITH SPLAY WIRE, SURGE

RESTRAINER, RING HANGER, HANGER ROD AND BEAM

CLAMP ASSEMBLY FIELD VERIFY WITH INSPECTOR FOR

ADDITION OR DELETION OF LINE RESTRAINTS AS REQUIRED

BY UNFORESEEN FIELD CONDITIONS.

No. 12, WIRE INSTALLED AT LEAST 45

DEGREES FROM THE VERTICAL PLANE

AND ANCHORED ON BOTH SIDES OF PIPE.

(209 LB. MAXIMUM LOAD)

1. BRANCH LINE PIPING

2. 1" SCH. 40

3. 1" 90 ELBOW

4. 1" x 1/2" REDUCING COUPLING

5. CEILING

6. 1/2" PENDANT SPRINKLER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:0

P

M

FP001

FIRE PROTECTION SYMBOLS,

NOTES AND ABBREVIATIONS

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

FIRE PROTECTION NOTES

1 A LICENSED (C-16) CONTRACTOR SHALL ROUTE AND SUPPORT AUTOMATIC SPRINKLER SYSTEM PER REQUIREMENTS OF NFPA 13

(2019), IBC CHAPTER 9 (2018), NFPA 25 (2019) AND ANY OTHER APPLICABLE CODE PER AHJ.

2 EXISTING WORK DAMAGED OR CUT INTO DURING CONSTRUCTION SHALL BE PATCHED OR REPAIRED, PAINTED AND FINISHED TO

MATCH EXISTING FINISHES.

3 NO HOLES SHALL BE DRILLED OR CUT IN OR THROUGH ANY STRUCTURAL ELEMENT.

4 SEE SPECIFICATION SECTION 21 13 13 FOR ADDITIONAL REQUIREMENTS.

5 ALL DEVICES AND COMPONENTS TO BE EITHER LISTED BY A NATIONALY RECOGNIZED TESTING LABORATORY FOR FIRE

PROTECTION SERVICE OR APPROVED BY THE VISN SAFETY ENGINEER.

6 THE FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED LISTED CENTRAL MONITORING STATION.

7 A SPARE SPINKLER CABINET SHALL BE INSTALLED NEAR THE RISER WITH THE QUANTITY OF SPARE SPRINKLERS REQUIRED PER

NFPA 13 SECTION 6.2.9.

8 PIPE SIZES SHOWN ON DRAWINGS ARE NOMINAL (NPS). LENGTHS OF PIPE ARE CENTER TO CENTER DIMENSIONS.

9 ITEMS SHOWN ON PLANS DESCRIBE GENERAL LAYOUT REQUIREMENTS, AND ARE NOT INTENDED TO SHOW A COMPLETE LAYOUT OF REQUIRED FIRE PROTECTION SYSTEM PIPING AND COMPONENTS. REFER TO ARCHITECTURAL, MECHANICAL AND PLUMBING SHEETS, FIRE PROTECTION SPECIFICATIONS, AS WELL AS OTHER PORTIONS OF THE CONTRACT DOCUMENTS FOR ADDITIONAL

COORDINATION REQUIREMENTS.

10 THE LAYOUT REQUIREMENTS DESCRIBED IN THESE PLANS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE BUT SHALL NOT SUPERSEDE CODE CONSTRAINTS AND/OR REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION (AHJ'S). WHERE CODE OR AHJ REQUIREMENTS SUPERSEDE ITEMS SHOWN ON THIS PLAN, CONTRACTOR SHALL INCLUDE ALL ASSOCIATED PROVISIONS IN THE BID, AND SHALL MAKE THEM AT NO ADDITIONAL COST TO THE OWNER. PROPOSED DEVIATIONS FROM THIS PLAN SHALL BE

SUBJECT TO ENGINEER OF RECORD REVIEW AND APPROVAL PRIOR TO IMPLEMENTATION.

11 ALL AREAS OF THE BUILDING NOT COVERED BY NOTES HEREIN SHALL BE FULLY SPRINKLED IN ACCORDANCE WITH

SPECIFICATIONS AND NFPA 13

12 WHERE PLAN INDICATES EXPOSED FIRE SPRINKLER PIPING DIRECTION OF LAYOUT, ASSOCIATED CONNECTED FIRE SPRINKLER PIPING RUNNING IN PERPENDICULAR DIRECTIONS SHALL BE INSTALLED ONLY IN CONCEALED LOCATIONS UNLESS INDICATED

OTHERWISE.

13 INSTALLING CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND IS RESPONSIBLE FOR PREPARING A DESIGN TO

ACCOMODATE ALL EXISTING CONDITIONS.

14 EXPOSED FIRE SPRINKLER SYSTEM PIPING SHALL BE RUN STRAIGHT AND TIGHT TO UNDERSIDE OF STRUCTURAL MEMEBERS.

15 IF AT THE CONTRACTOR'S OPTION, PIPING IS NOT INSTALLED IN CONFORMANCE WITH THESE CONDITIONS, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS (1/4" = 1'-0") OF SEISMIC BRACING SYSTEM IN ACCORDANCE WITH SEISMIC RESTRAINTS

GUIDELINES FOR SUSPEND

16 THE STRUCTURAL ENGINEER OF RECORD SHALL BE RESPONSIBLE TO VERIFY THE ADEQUANCY OF THE STRUCTURE TO SUPPORT

THE HANGER AND BRACING LOADS.

17 THE CONTRACTOR SHALL SURVEY EXISTING FIELD CONDITIONS PRIOR TO BIDDING. IF AWARDED THE CONTRACT, THE CONTRACTOR SHALL SURVEY EXISTING FIELD CONDITIONS IN DETAIL AND COORDINATE THE WORK WITH EXISTING BUILDING

SYSTEMS.

18 ANY DAMAGE TO NEW BUILDING ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS THAT OCCURS DURING THE WORK SHALL BE RESTORED TO THE ORIGINAL CONDITION AT THE CONTRACTOR'S EXPENSE. IF LANDSCAPED AREAS INCLUDING NATURAL SPACES MUST BE USED FOR BUILDING ACCESS, THE LANDSCAPING SHALL BE RETURNED TO ITS ORIGINAL CONDITION. THE CONTRACTOR SHALL INCLUDE COSTS IN THE BID FOR THIS WORK IF THIS APPROACH IS USED. THE OWNER WILL NOT PAY ANY ADDITIONAL COSTS TO COVER DAMAGE TO THE BUILDING SYSTEMS, LANDSCAPING OR DRIVE AREAS.

19 COORDINATE THE FOLLOWING WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL SRAWINGS AND

ELEMENTS AS INSTALLED, INCLUDING EXISTING BUILDING SYSTEMS:

A. EXACT LOCATION OF ALL EQUIPMENT.

B. ALL PENETRATIONS THRU ROOF, WALLS AND FLOORS.

C. EXACT SIZE AND ROUTING OF PIPING.

20 DRAWINGS INDICATE DIAGRAMMATICALLY THE ARRANGEMENT OF PRINCIPAL APPARATUS, PIPING, AND OTHER MATERIAL. FOLLOW DRAWING AS CLOSELY AS POSSIBLE, INORDER TO ACHIEVE A NEAT ARRANGEMENT OF PIPING AND EQUIPMENT WHILE STILL

OVERCOMING OBSTRUCTIONS.

21 THE LAYOUT REQUIREMENTS DESCRIBED IN THESE PLANS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE BUT SHALL NOT SUPERSEDE CODE CONSTRAINTS AND/OR REQUIREMENTS OF THE VISN SAFETY ENGINEER. WHERE CODE OR VISN SAFETY

ENGINEER REQUIREMENTS SUPERSEDE ITEMS SHOWN ON TH

22 ALL EXISTING FIRE PROTECTION SYSTEMS SHALL REMAIN IN OPERATION DURING PHASES OF CONTRUCTION. NO SYSTEMS ARE TO

BE SHUTDOWN WITHOUT AUTHORIZATION FROM THE VISN SAFETY ENGINEER.

23 THE LOCATION OF FIRE SPRINKLER HEADS SHALL BE COORDINATED WITH THE NEW CEILING LAYOUTS AND ALL OTHER TRADES FOR COMPLETE FIRE PROTECTION COVERAGE OF ALL AREAS. PROVIDE DETAILED PLANS FOR APPROVAL PRIOR TO INSTALLATION.

24 HEADS SHALL BE SYMMETRICALLY LOCATED IN CENTER OF CEILING PANELS. COORDINATE LAYOUT WITH CEILING OR SOFFIT LIGHT FIXTURES, AND HVAC DIFFUSERS,RETURNS, ETC. PROVIDE PENDENT AND/OR UPRIGHT TYPE SPRINKLER HEAD WHERE REQUIRED.

25 WORKMANSHIP:

ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER ACCORDING TO THE BEST TRADE PRACTICE BY THOSE SKILLED IN THE PARTICULAR TRADE. PIPES, EQUIPMENT, ETC., TO BE INSTALLED LEVEL, SQUARE OR CENTERED, ETC., TO GIVE A NEAT AND PLEASING APPEARANCE. ALL EQUIPMENT IS TO BE INSTALLED STRICTLY PER MANUFACTURER'S RECOMMENDATIONS. COORDINATE

ALL WORK WITH OTHER TRADES.

26 THE ANNULAR SPACE BETWEEN PIPE SLEEVESAND THE PIPE THEOUGH ALL RATED WALLS AND FLOORS SHALL BE FIRESTOPPED.

FIRESTOPPING OF ALL PIPE PENETRATIONS OF ALL PIPE PENETRATIONS SHALL COMPLY WITH U.L. REQUIREMENTS.

MANUFACTURER PREAPPROVED UL PENETRATION FOR PIPE MATERIAL AND SURFACE PENETRATED SHALL BE USED.

PENETRATIONS SHALL BE 3M, PROSET, OR APPROVED EQUAL. SUBMIT SHOP DRAWINGS.

27 BY OTHERS:

A. ELECTRICAL CONTRACTOR: ALL POWER AND ALARM WIRING, CONDUITS, DISCONNECTS, AND FINAL CONNECTIONS. NO FIELD SUPPLIED ELECTRICAL DEVICE SHALL BE MOUNTED ON PIPING AND NO RIGID ELECTRICAL CONNECTIONS SHALL BE MADE.

B. GENERAL CONTRACTOR: CUTTING, FRAMING, PATCHING, FURRING, AND PAINTING.

28 ALL MATERIALS AND EQUIPMENT INSTALLED UNDER THIS CONTRACT SHALL BE GUARANTEED FREE FROM ALL FIRE PROTECTION, ELECTRICAL AND WORKMANSHIP DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. THE CONTRACTOR SHALL BE RESPOSIBLE FOR ALL DAMAGES TO THE PREMISES CAUSED BY LEAKS AND/OR BREAKS IN PIPES AND FIXTURES

INSTALLED UNDER THIS CONTRACT.

29 IT IS THE INTENTION OF THE PLANS AND SPECIFICATIONS TO COVER ALL THINGS REQUIRED TO PROVIDE COMPLETE AND OPERATIVE SYSTEMS. THE CONTRACTOR IS TO FURNISH ALL LABOR, MATERIALS, TRANSPORTATION, EQUIPMENT, MISCELLANEOUS SERVICES, ETC., REQUIRED TO NECESSARY PART OF THE INSTALLATION IS TO BEINCLUDED, WHETHER SPECIFICALLY SHOWN OR MENTIONED. THE ENGINEER WILL GIVE ANY INTERPRETATIONS NECESSARY FOR THE CONTRACTOR TO PROPERLY ESTIMATE THE

JOB.

30 IT IS THE CONTRACTORS' RESPONSIBILITY TO PROVIDE FABRICATION OR SHOP DRAWINGS. CAD FILES WILL NOT BE PROVIDED.

ABBREVIATIONS

(E) EXISTING

(N) NEW

ABBR ABBREVIATION

AFF ABOVE FINISHED FLOOR

AFSR AUTOMATIC FIRE SPRINKLER RISER

BFV BUTTERFLY VALVE

DCDA DOUBLE CHECK DETECTOR ASSEMBLY

DI DUCTILE IRON

DN DOWN

FACP FIRE ALARM CONTROL PANEL

FDC FIRE DEPARTMENT CONNECTION

FH FIRE HYDRANT

PIV POST INDICATOR VALVE

POC POINT OF CONNECTION

PVC POLYVINYL CHLORIDE

RN RISER NIPPLE

SSP STANDARD SPRAY PENDANT

SSU STANDARD SPRAY UPRIGHT

UG UNDERGROUND

BUILDING DATA

PROJECT OWNER: VETERANS ASSOCIATION

VA MARTINEZ HEALTHCARE SYSTEM

CONTACT: HENRY LAPIRA

PROJECT MANAGER | PROJECT DEVELOPMENT SECTION

OFFICE OF FACILITY PLANNING & DEVELOPMENT

PROJECT DESCRIPTION: RELOCATE SPRINKLER HEADS IN BLDG 19

1ST AND 2ND FLOOR RENOVATION AREAS

OCCUPANCY GROUP: GROUP B

CONSTRUCTION TYPE: TYPE II (000) FULLY SPRINKLED

STRUCTURAL FRAME: 2 HOURS

INTERIOR NON-BEARING PARTITION 0 HOURS

FLOORS 2 HOURS

ROOFS 1 HOURS

GROSS FLOOR AREAS: EXISTING

2 FLOORS

SPRINKLER DESIGN CRITERIA:

CLASSIFICATION OF OCCUPANCY: GROUP B

DESIGN DENSITY: 0.10 GPM/ SQ.FT.

DESIGN AREA MIN.: 1,500 SQ.FT.

AREA OF COVERAGE/ SP HEAD: 225 SQ.FT. MAX/ HEAD

SPRINKLER DESIGN CRITERIA: MECHANICAL, ELECTRICAL, TELECOM, CUSTODIAL,

STORAGE ROOMS

CLASSIFICATION OF OCCUPANCY: ORDINARY HAZARD I

DESIGN DENSITY: 0.20 GPM/ SQ.FT.

DESIGN AREA MIN.: 1,500 SQ.FT.

AREA OF COVERAGE/ SP HEAD: 130 SQ.FT. MAX/ HEAD

GOVERNING CODES:

2018 INTERNATIONAL BUILDING CODE

2018 INTERNATIONAL FIRE CODE

2019 NFPA 13 AUTOMATIC SPRINKLER SYSTEMS

2019 NFPA 14 STANDPIPE SYSTEMS

2019 NFPA 72 NATIONAL FIRE ALARM CODE

2019 NFPA 80 FIRE DOORS AND OTHER OPENING PROTECTIVES

2015 VA FIRE PROTECTION DESIGN MANUAL

FIRE PROTECTION SHEET INDEX

FP001 FIRE PROTECTION SYMBOLS, NOTES AND ABBREVIATIONS

FP101 ENLARGED PHASE 2 FIRST FLOOR FIRE PROTECTION NEW PLAN EAST

FP201 ENLARGED PHASE 1 SECOND FLOOR FIRE PROTECTION NEW WORK PLAN

FP202 ENLARGED PHASE 2 SECOND FLOOR FIRE PROTECTION NEW WORK PLAN

FPD101 ENLARGED PHASE 2 FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN EAST

FPD201 ENLARGED PHASE 1 SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN

FPD202 ENLARGED PHASE 2 SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN

SCALE: NONEFP001

1 PIPE THROUGH RATED WALL PENETRATION

SCALE: NONEFP001

2 OBSTRUCTION TABLE

SCALE: NONEFP001

3 PIPE HANGER DETAIL

SCALE: NONEFP001

4 BRANCH LINE RESTRAINT

SCALE:FP001 NONE

5 ARM OVER DETAIL

EXP 6/30/22

P

Q

R

S

T

U

V

AA

BB

CC

CC.1

CC.2

DD

DD.1

EE

EE.1

6.4

R.2

(E)

RECEPTION

151 SF

(E) EXAM

114 SF

(E) OFFICE

115 SF

(E) EXAM

97 SF

(E) EXAM

1062A

111 SF

(E) OFFICE

1062B

89 SF

(E) EXAM

137 SF

(E) EXAM

1---

120 SF

(E)

CORRIDOR

164 SF

TEAM

ROOM

B145B

230 SF

WS

WAITING

B170

82 SF

PC EXAM

B132

113 SF

PC EXAM

B133

116 SF

LAB/PC

TOILET

B131

64 SF

PC EXAM

B146

127 SF

PC EXAM

B145

124 SF

BLOOD

DRAW

B130

350 SF

PC Exam B144A

112 SF

PC EXAM

B143A

116 SF

WS

CONSULT

B175

83 SF

PC EXAM

B143

121 SF

PC EXAM

B144

117 SF

(E) ANTE

ROOM

VESTIBULE

B143E

87 SF

(E) AIRLOCK

B143G

51 SF

(E) CHEMO

HOOD

ROOM

B143H

62 SF

(E) IV

BUFFER

B143I

50 SF

(E) ANTE

ROOM

B143F

105 SF

RECEPTION/GREETER

B170A

57 SF

HAC

B180

47 SF

SOILED

UTILITY

B172

41 SF

WS

PROCEDURE

B171

225 SF

WS TOILET

B171A

47 SF

WS EXAM

B173

117 SF

WS TOILET

B174

56 SF

(E

1/

2" F

(E

1/

2" F

(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

1/

2" F

(E) 1 1/4" F

(E

1/

2" F

(E) 1 1/4" F

(E) 1 1/4" F

(E

1/

2" F

(E) 1 1/4" F 1 1/4" F

(E

1/

2" F

1/

2" F

(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F

1/

2" F

PHASE BOUNDARY

1" 6' -3

1" 1' -6

1" 1' -6

1" 1'-6"

1" 2' -4

1" 2' -0

" 1" 3'-0"

1" 1' -3

1" 3' -9

1" 3' -3

1" 2' -7

1" 6' -7

1" 3'-5"

1" 2' -6

1" 3' -1

1" 1' -8

1" 2'

-1

1" 3'-3"

1" 2' -2

1" 1' -2

1" 5"

1" 3' -4

1" 8"

1" 1'-8"

1"8"

1" 2' -9

1" 1'-2"

1" 4' -9

1" 4' -1

"1" 5' -4

1" 2' -5

1" 4'

-1

1" 1'-2"

1" 8' -1

"1" 7'

-1

1" 7" 1" 7" 1" 7" 1" 7"

1" 1' -5

1" 1' -5

1" 4"

1" 1' -5

1" 1'-4"

1" 1' -5

1" 7"

1" 3"

(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F

BREAKROOM

B145A

102 SF

(E) 1 1/4" F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:1

P

M

FP101

ENLARGED PHASE 2 FIRST FLOOR

FIRE PROTECTION NEW PLAN

EAST

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

SCALE:FP101 1/4" = 1'-0"

1 ENLARGED PHASE 2 FIRST FLOOR FP NEW PLAN EAST

KEY PLAN: FIRST FLOOR EAST

SHEET NOTES:

1. PENDANT FIRE SPRINKLERS ARE TO BE LOCATED IN THE

CENTERLINE OF THE CEILING TILE IN THE 2'-0" DIMENSION AND AT

12" INCREMENTS IN THE 4'-0" DIMENSION (TYP).

2. PROVIDE END OF LINE RESTAINTS AS REQUIRED PER

NFPA 13 2019 SEC. A.18.6.1

3. UNSUPPORTED ARM OVER LENGTHS SHALL BE LESS THAN 24" MAX.

4. IN LIGHT HAZARD OCCUPANCY ROOMS UNDER 800 SF HEADS MAY

BE SPACED PER NFPA 13 2019, TABLE 18.6.4(a)

5. ALL NEW LINES ARE TO BE 1" U.N.O.

6. EXISTING SPRINKLER LAYOUT IS A GRID TYPE SYSTEM.

7. PERFORM CROSS TRADE COORDINATION BETWEEN CONTRACTORS

TO PREVENT CLASHES.

8. CONCELAED SPACES OF NONCOMBUSTIBLE AND LIMITED

COMBUSTIBLE CONSTRUCTION WITH MINIMAL COMBUSTIBLE

LOADING HAVING NO ACCESS SHALL NOT REQUIRE SPRINKLER

PROTECTION PER NFPA 13 SEC. 9.2.1.1

9. ALL EXISITNG HANGERS & BRACING ON EXISTING LINES TO REMAIN.

10. ROOM B-172 IS ORDINARY HAZARD GROUP 2 (0.2 GPM/SF DENSITY)

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

PHASE BOUNDARY

EXAM

B214E

EXAM

B214B

SOILED

UTILITY

B214L

1" 1' -2

1" 1' -2

1" 1' -2

1" 1' -2

1" 1'

-1

1" 1'

-1

1" 5'

-1

1" 10

1" 1' -7

1" 5"

1" 1' -9

1" 4' -5

1" 2' -0

1" 4' -3

1" 2' -8

1" 2' -8

"1" 1' -6

1" 6"

1" 4' -0

1" 4' -0

1" 6' -0

"1" 2' -1

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F(E) 1 1/4" F (E) 1 1/4" F

(E

1/

2" F

(E) 2 1/2" F

(E

1/

2" F

(E) 2 1/2" F

(E

1/

2" F

(E) 1 1/4" F

(E

1/

2" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F

(E

1/

2" F

(E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F(E) 1 1/4" F

(E

1/

2" F

(E

1/

2" F

(E) 1 1/4" F (E) 1 1/4" F(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F

ENT

PROCEDURE

B214A

274 SF

CORRIDOR

387 SF

OFFICE

B214C

107 SF

OFFICE

B214D

105 SF

EXAM

B214G

155 SF

CLEAN

UTILITY /

OMNI

B214F

110 SF

TOILET

B214H

58 SF

EXAM

B214I

155 SF

TEAM

ROOM

B214J

237 SF

ENT EXAM

B214K

207 SF

1" 2' -5

1" 2' -1

1" 1' -1

1" 1' -5

CHARTING

C201

(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:1

P

M

FP201

ENLARGED PHASE 1 SECOND

FLOOR FIRE PROTECTION NEW

WORK PLAN

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

SCALE:FP201 1/4" = 1'-0"

1 ENLARGED PHASE 1 SECOND FLOOR FP NEW PLAN

KEY PLAN: SECOND FLOOR

SHEET NOTES:

SCALE:FP201 1/4" = 1'-0"

2 ENLARGED PHASE 1 SECOND FLOOR FP NEW PLAN

1. PENDANT FIRE SPRINKLERS ARE TO BE LOCATED IN THE

CENTERLINE OF THE CEILING TILE IN THE 2'-0" DIMENSION AND AT

12" INCREMENTS IN THE 4'-0" DIMENSION (TYP).

2. PROVIDE END OF LINE RESTAINTS AS REQUIRED PER

NFPA 13 2019 SEC. A.18.6.1

3. UNSUPPORTED ARM OVER LENGTHS SHALL BE LESS THAN 24" MAX.

4. IN LIGHT HAZARD OCCUPANCY ROOMS UNDER 800 SF HEADS MAY

BE SPACED PER NFPA 13 2019, TABLE 18.6.4(a)

5. ALL NEW LINES ARE TO BE 1" U.N.O.

6. EXISTING SPRINKLER LAYOUT IS A GRID TYPE SYSTEM.

7. PERFORM CROSS TRADE COORDINATION BETWEEN CONTRACTORS

TO PREVENT CLASHES.

8. CONCELAED SPACES OF NONCOMBUSTIBLE AND LIMITED

COMBUSTIBLE CONSTRUCTION WITH MINIMAL COMBUSTIBLE

LOADING HAVING NO ACCESS SHALL NOT REQUIRE SPRINKLER

PROTECTION PER NFPA 13 SEC. 9.2.1.1

9. ALL EXISITNG HANGERS & BRACING ON EXISTING LINES TO REMAIN.

10 ROOM B-214 & B-214l ARE ORDINARY HAZARD GROUP 2 (0.2 GPM/SF

DENSITY)

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

3 4 5

P

Q

R

S

T

U

V

R.2

PHASE BOUNDARY

BREAK

ROOM

B208

133 SF

MD TECH

WKSTN

B206

210 SF

EXAM/

TREATMENT

B207

120 SF

CORRIDOR

281 SF

(E)

RECEPTION

B216

226 SF

RN/ PA

OFFICE

B227

125 SF

PROCEDURE/

EXAM

B226

167 SF

(E) EXAM 4

B225

162 SF

(E) EXAM 3

B224

159 SF

(E) EXAM/

TREATMENT

B205

113 SF

(E) OFFICE /

EXAM

B223

141 SF

(E)

CIRCULATION

386 SF

PRE-SCREENING/

EXAM 2

B202

151 SF

CATARACT

SURGERY

TESTING

B213

204 SF

EXAM/

TREATMENT

B209

132 SF

EXAM/

TREATMENT

B210

132 SF

VISUAL

FIELD

B212

111 SF

PRE-SCREENING/

EXAM 3

B203

165 SF

WAITING

B349

417 SF

RECEPTION

- EYE

CLINIC

B216A

139 SF

(E)

CIRCULATION

B391

67 SF

(E) HUDDLE

B392

70 SF

CORRIDOR

334 SF

WAITING

B204

120 SF

SOILED

B200

19 SF

PRE-SCREENING/

EXAM 1

B201

92 SF

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F

1" 7" 1" 7" 1" 7" 1" 7"

1" 1'

-1

1" 1'

-1

1" 1'

-1

1" 1'

-1

1" 1'

-1

1" 11

1" 11

1" 1"1" 1"

1" 3' -3

1" 3' -3

1" 2' -5

1" 3' -6

1" 3' -6

1" 3' -1

1" 7' -7

1" 1' -9

1" 1' -6

1" 1' -6

"1" 3' -0

1" 3' -0

1" 3' -9

1" 3' -9

1" 1'

-1

1" 1' -9

1 " 2 '

-1

1" 2'

-1

1" 1'-7"

1" 4' -0

1" 2' -1

(E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:1

P

M

FP202

ENLARGED PHASE 2 SECOND

FLOOR FIRE PROTECTION NEW

WORK PLAN

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

SCALE:FP202 1/4" = 1'-0"

1 ENLARGED PHASE 2 SECOND FLOOR FP NEW PLAN

KEY PLAN: SECOND FLOOR

SHEET NOTES:

1. PENDANT FIRE SPRINKLERS ARE TO BE LOCATED IN THE

CENTERLINE OF THE CEILING TILE IN THE 2'-0" DIMENSION AND AT

12" INCREMENTS IN THE 4'-0" DIMENSION (TYP).

2. PROVIDE END OF LINE RESTAINTS AS REQUIRED PER

NFPA 13 2019 SEC. A.18.6.1

3. UNSUPPORTED ARM OVER LENGTHS SHALL BE LESS THAN 24" MAX.

4. IN LIGHT HAZARD OCCUPANCY ROOMS UNDER 800 SF HEADS MAY

BE SPACED PER NFPA 13 2019, TABLE 18.6.4(a)

5. ALL NEW LINES ARE TO BE 1" U.N.O.

6. EXISTING SPRINKLER LAYOUT IS A GRID TYPE SYSTEM.

7. PERFORM CROSS TRADE COORDINATION BETWEEN CONTRACTORS

TO PREVENT CLASHES.

8. CONCELAED SPACES OF NONCOMBUSTIBLE AND LIMITED

COMBUSTIBLE CONSTRUCTION WITH MINIMAL COMBUSTIBLE

LOADING HAVING NO ACCESS SHALL NOT REQUIRE SPRINKLER

PROTECTION PER NFPA 13 SEC. 9.2.1.1

9. ALL EXISITNG HANGERS & BRACING ON EXISTING LINES TO REMAIN.

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

P

Q

R

S

T

U

V

AA

BB

CC

CC.1

CC.2

DD

DD.1

EE

EE.1

6.4

R.2

PHASE BOUNDARY

HAC

B144

LAB

B130

EXAM ROOM

B132

EXAM ROOM

B133

EXAM ROOM

B146

EXAM ROOM

B145

OFFICE

B143B

STAFF

BREAKROOM

B143A

VACANT

HALLWAY

B143F

VACANT

OFFICE

B143E

(E) RECEPTION

B143D

TOILET

B193

(E) ANTE ROOM

VESTIBULE

B287

(E) AIRLOCK

B387

(E) CHEMO HOOD

ROOM

B388

(E) IV BUFFER

B389

(E) ANTE ROOM

B390

(E) RECEPTION

EXAM

OFFICE

EXAM

EXAM

EXAM

B147

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:2

P

M

FPD101

ENLARGED PHASE 2 FIRST FLOOR

FIRE PROTECTION DEMOLITION

PLAN EAST

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

SCALE:FPD101 1/4" = 1'-0"

1 ENLARGED PHASE 2 FIRST FLOOR FP DEMOLITION PLAN EAST

GENERAL NOTES:

1. EXISTING SPRINKLER PIPING SHOWN FOR REFERENCE ONLY.

2. ROUTING OF EXISTING PIPING AND SIZES SHALL BE CONFIRMED BY

SPRINKLER CONTRACTOR IN THE FIELD.

3. TEMPORARILY RELOCATE OR ADD SPRINKLER HEADS AS NEEDED

TO PROVIDE COVERAGE DURING CONSTRUCTION WHEN THE

CEILING IS REMOVED.

4. NO CHANGES TO EXISTING SPRINKLER MAINS HANGERS AND/OR

SEISMIC BRACING.

5. COMPLY WITH FIRE SAFETY DURING CONSTRUCTION AND

DEMOLITION PER CHAPTER 33, 2018 IFC.

6. ALL SPRINKLER HEADS IN SCOPE OF WORK TO BE DEMOLISHED.

KEY PLAN: FIRST FLOOR

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

1-1/4"1-1/4"

1-1/4"1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4" 1-1/4"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2-1/2"

2 3

P

Q

R

S

T

U

V

R.2

CONF

B209

SUPPLY LAB

B208

OFFICE

B214A

PHASE BOUNDARY

(E

1/

2" F

(E

1/

2" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F

(E

1/

2" F

(E

1/

2" F

(E

1/

2" F

(E

1/

2" F

(E

1/

2" F

(E

1/

2" F

(E) 2 1/2" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

E

F

G

(E) 1 1/4" F(E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F

1 1/4" F 1 1/4" F

1 1/4" F 1 1/4" F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:2

P

M

FPD201

ENLARGED PHASE 1 SECOND

FLOOR FIRE PROTECTION

DEMOLITION PLAN

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

KEY PLAN: SECOND FLOOR

SCALE:FPD201 1/4" = 1'-0"

1 ENLARGED PHASE 1SECOND FLOOR FP DEMOLITION PLAN WEST

GENERAL NOTES:

1. EXISTING SPRINKLER PIPING SHOWN FOR REFERENCE ONLY.

2. ROUTING OF EXISTING PIPING AND SIZES SHALL BE CONFIRMED BY

SPRINKLER CONTRACTOR IN THE FIELD.

3. TEMPORARILY RELOCATE OR ADD SPRINKLER HEADS AS NEEDED

TO PROVIDE COVERAGE DURING CONSTRUCTION WHEN THE

CEILING IS REMOVED.

4. NO CHANGES TO EXISTING SPRINKLER MAINS HANGERS AND/OR

SEISMIC BRACING.

5. COMPLY WITH FIRE SAFETY DURING CONSTRUCTION AND

DEMOLITION PER CHAPTER 33, 2018 IFC.

6. ALL SPRINKLER HEADS IN SCOPE OF WORK TO BE DEMOLISHED.

SCALE:FPD201 1/4" = 1'-0"

2 ENLARGED PHASE 1SECOND FLOOR FP DEMOLITION PLAN WEST

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

1-1/4"

4 5

P

Q

R

S

T

U

V

R.2

PHASE BOUNDARY

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F(E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F(E) 1 1/4" F (E) 1 1/4" F

(E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F (E) 1 1/4" F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

ARCHITECT OF RECORD

Gene Klow, AIA

(855) 521-1110

Alexandria, Virginia 22314

123 S Royal Street

Concourse Federal GroupCapital Consulting Engineers

Bryan Johnson, PE

(916) 851-3500

Rancho Cordova, California 95670

11020 Sun Center Drive, Suite 100

JS DG

L R e v it L o c a l F ile s \2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

\2

.0

V

A M a rt in e z S p e c ia lt y C a re

M

P

D G re e r.

rv t

/3

/2

:0

:2

P

M

FPD202

ENLARGED PHASE 2 SECOND

FLOOR FIRE PROTECTION

DEMOLITION PLAN

REMODEL SPECIALTY

CARE - BUILDING 19

VA MARTINEZ

612-18-329

03/26/21

100% - BID SET

SCALE:FPD202 1/4" = 1'-0"

1 ENLARGED PHASE 2 SECOND FLOOR FP DEMOLITION PLAN WEST

GENERAL NOTES:

1. EXISTING SPRINKLER PIPING SHOWN FOR REFERENCE ONLY.

2. ROUTING OF EXISTING PIPING AND SIZES SHALL BE CONFIRMED BY

SPRINKLER CONTRACTOR IN THE FIELD.

3. TEMPORARILY RELOCATE OR ADD SPRINKLER HEADS AS NEEDED

TO PROVIDE COVERAGE DURING CONSTRUCTION WHEN THE

CEILING IS REMOVED.

4. NO CHANGES TO EXISTING SPRINKLER MAINS HANGERS AND/OR

SEISMIC BRACING.

5. COMPLY WITH FIRE SAFETY DURING CONSTRUCTION AND

DEMOLITION PER CHAPTER 33, 2018 IFC.

6. ALL SPRINKLER HEADS IN SCOPE OF WORK TO BE DEMOLISHED.

KEY PLAN: SECOND FLOOR

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

PLUMBING PIPE SYMBOLS LEGEND

SINGLE LINE DOUBLE LINE

ABBREVIATION DESCRIPTION

PLAN VIEW 3D VIEW PLAN VIEW

CIRCUIT SETTER VALVE

BALL VALVE

CHECK VALVE

GATE VALVE

BALANCING VALVE

DRAWING SYMBOLS

PLUMBING SYMBOLS LEGEND

ABBREVIATION DESCRIPTIONSYMBOL

--- ANCHOR

BFP, BP, DCW BACKFLOW PREVENTER, REDUCE PRESSURE, DOUBLE CHECKVALVE

--- BALANCING VALVE

--- BALL VALVE

--- BOTTOM CONNECTION

CBV CALIBRATED BALANCE VALVE

RD & OF ROOF AND OVERFLOW DRAIN

--- CHECK VALVE

--- CIRCUIT SETTER VALVE

CO CLEANOUT

FD FLOOR DRAIN

FS FLOOR SINK

--- FLOW ARROW

PLUMBING SYSTEMS LEGEND

ABBREVIATION DESCRIPTIONSYMBOL

TRAP PRIMER WATERTW

STORM DRAINSD

EQUIPMENT COMPRESSED AIRCA

DRAIND

TEMPERED DOMESTIC WATERTW

HOT DOMESTIC WATERHW

COLD DOMESTIC WATERCW

CONDENSATE DRAINCD

TW

SD

CA

D

TW

CD

(E) EXISTING---

FA, FB FROM ABOVE, FROM BELOW---

A.F.F. ABOVE FINISHED FLOOR---

PLUMBING GENERAL NOTES

1. CLOSELY COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO TRENCHING OR INSTALLING…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .