This document provides details for a federal solicitation to remodel specialty care and correct HVAC systems in Building 19 at the Martinez Veterans Affairs Medical Center. The contractor shall provide all labor, materials, tools, equipment, supervision and other resources necessary to complete the construction project in accordance with the attached specifications and drawings. The solicitation number is 36C77621B0021 and is seeking to award a contract to remodel areas for specialty care and repair HVAC systems in an existing medical center building. The work must be completed in coordination with the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Relevant details are provided regarding the scope of work and responsible federal agency to carry out this construction project at the Martinez VAMC.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Novus® Digital Multipurpose Portal
NV-DMP
NOTE: This information should not be used for final design.
Specifications are subject to change without notice.
West-Com Nurse Call Systems, Inc.
2200 Cordelia Road, Fairfield, CA 94534 westcomncs.com | 800.761.1180
NV-DMP | REV 3.2
Description The Novus Digital Multipurpose Portal is designed for multiple uses such as a standalone, complete call system for small units and senior living facilities utilizing the wired CliniCare solution. The NV-DMP can also serve as a standalone wireless call system, or as a Call Display Terminal to enhance visibility of calls to remote locations of a hospital.
The NV-DMP has an easy to read LCD display, RS- 422 specifically designed for wireless nurse call, RS- 232 connectivity for a direct connection to a paging transmitter, and RS-485 for West-Com Novus devices.
Compatibility
Systems and Devices
Novus CliniCare System, Novus Gen II System, West-Com Wireless
Ordering Information Model Name Description
NV-DMP Novus Digital Multipurpose Portal
Box Contents
NV-DMP (1)
Cable, RS-232 for NV-DMP (1) 6-32 x 1.75 flathead machine screws (4) Programming certificate and serial number RJ-45 connector 6-554720-2 (1) Panduit 8-pin CE100F24-8 (1) Panduit 3-pin CE156F22-3 (1) RS-232 Premade Cable (1)
† West-Com Patented Innovations This product is protected by one or more of the following U.S. Patents:
8,009,021, 7,994,900, D614,520
Specifications Characteristic Description
Operating Voltage 8-28VDC
Power Consumption <2.5W
Dimensions 4.75″H x 7.0″W (120.6mm x 177.8mm)
Faceplate Hospital grade Polylac PA765NAT with light grey opaque
Cable Requirements Ethernet CAT-5e 8-pin RS-485 device cable 24AWG 8-pin RS-422 cable 22AWG 2-pin RS-232 cable 22AWG 3-pin Power cable +28VDC 22AWG 3-pin
Termination RJ-45 connector (1), 6-554720-2 Panduit 8-pin CE100F24-8 (1) Panduit 3-pin CE156F22-2 (1)
Touch Screen 4.5″ (114.3mm), color
Speaker Built-in
Mounting 4-gang backbox with a 3-gang mud ring
RACO 822, 952
Compliance
Certifications UL-1069 US and Canada, E139082
Warranty Five years http://www.westcall.com/ MiguelLopez Highlight Novus® Digital Multipurpose Portal
NV-DMP
West-Com Nurse Call Systems, Inc.
2200 Cordelia Road, Fairfield, CA 94534
NV-DMP | REV 3.2
Wiring Information
Component Cable Compatibility Functionality
T1 CAT-5e, RJ-45 10BASE-T network connection
J3 22/4 Contact closure relay connections
J4 CAT-5e West-Com Straight Through RS-485, Data for Novus network
J7 22/2 RS-482, Rx+ & Rx- from wireless transmitter
J8 22/4 RS-232, Tx & Rx from paging transmitter
J12 18/2 Power and Ground
Novus® Dome Light
NV-DOME2
NV-DOME2 | REV 8.1 | 151222
West-Com Nurse Call Systems, Inc.
2200 Cordelia Road, Fairfield, CA 94534 westcall.com | 800.761.1180
System and Devices
Compatible with all Novus Systems
Compatible with Novus and Novus Visual devices
Software
FocusCare® Software 1.1.8.x
Ordering Information
Description Model Number
Novus dome with optical input, output relay, and buzzer.
NV-DOME2
Only uses CAT-5 cable; no audio support, for use with Visual Systems only.
NV-DOME2/V
Economy version. Provides same functionality as regular NV-DOME2, but uses simplified plastic housing to reduce cost.
NV-DOME2/E
Combines the /V and the /E options. NV-DOME2/VE
Box Contents
NV-DOME2 (1)
6-32 x 1.75 flathead machine screws (4)
Programming certification and serial number (1)
Options
None
Description
The NV-Dome2 gives clear visual notification to staff members of a room’s status. The customizable, four-segmented dome displays different color combinations to alert staff to a variety of alert types. A built-in buzzer can be activated for multiple alert types. The NV-Dome2 can automatically detect attached devices during the initial configuration and has the ability to report multiple connected devices as unique locations.
Characteristic Description
Operating Voltage 8-28VDC
Power Consumption <2.0W
Dimensions 5 ½” x 5 ½″W x 3 ¾″D (139.7mm x 139.7mm x 95.25mm)
Cable Requirements CAT-5, Special Orange, 22/2 pair shielded
Termination (3) RJ-45, (2) Panduit CE156F22-3, (1) Panduit CE100F22-5, (2) Panduit CE100F22-2
Faceplate Hospital grade ABS plastic back plate. PMS 427 light grey opaque.
Luminary Molded white polystyrene plastic, replaceable
Mounting 4.7” (119.4mm) square back-box with two-gauge plaster ring. Raco 257 with 818 or equivalent
Certifications UL-1069 for US and Canada, E139082
Warranty Five Year http://www.westcall.com/ mlopez Highlight
MiguelLopez Highlight
NV-DOME2
NV-DOME2 | REV 8.1 | 151222 2 of 2
West-Com Nurse Call Systems, Inc.
Connector Layouts
J1 Special Orange power input, 18 AWG, Panduit
J2 Special Orange power output, 18AWG, Panduit
J4 Special Orange input, RJ-45
J5 Special Orange output, RJ-45
J6 22/2 Pair Shielded, audio, Panduit
J7 CAT-5 to room (devices)
J9 Remote output (relay controlled), Panduit
J10 Isolated input, Panduit
Novus® Emergency Stations
NV-PBE2/X
NV-PBE2/X | REV 3
West-Com Nurse Call Systems, Inc.
The Novus Generation II emergency stations are designed for specific patient rooms and other areas where priority calls require immediate attention. These devices connect directly to a dome light or patient station. The emergency stations have a call assurance® LED indicator that confirms to the staff member that the alert has been placed.
Systems and Devices
Compatible with Novus Systems and Devices
Software
FocusCare® Software 1.1.8.x
Ordering Information Description Model Number
Emergency Station, HELP (red) NV-PBE2
Emergency Station, Staff Emergency (red) NV-PBE2/SE
Emergency (Red) NV-PBE2/E
Emergency Station, Code Blue (blue) NV-PBE2/CB
Emergency Station, Code (blue) NV-PBE2/C
Emergency Station, Code Pink (pink) NV-PBE2/CP
Emergency Station, Assist (yellow) NV-PBE2/A
Emergency Station, Code White (white) NV-PBE2/CW
Emergency Station, Staff Call (white) NV-PBE2/SC
Emergency Station, Staff Emergency (red) Code Blue (blue)
NV-PBE2/SE/CB
Emergency Station, Code White (white) Staff Emergency (red)
NV-PBE2/CW/SE
Emergency Station Clear Protector ESP-2000
Emergency Station Clear Protector (door) ESP-2000/D
Optional Accessories None
NV-PBE2 (1)
6-32 x 1.75 flathead machine screws (2) Programming certificate with serial number (1)
Specifications Characteristic Description
Operating Voltage 8-28VDC
Power Consumption 0.06W idle, 0.75W maximum
Dimensions 4 ½″H x 2 ¾″W x 1 ½″D (114.3mm x 69.8mm x 38.1mm)
Cable Requirements CAT-5e or better
Termination RJ-45 connectors (2), Panduit CE100F22-5, CE100F22-4, CE100F22-2
Mounting
4” (101.6mm) square back-box with one-gang plaster ring, Raco 190 with 768 one- gang adapter or equivalent. Minimum 2 1/8" (54mm) depth required.
Normal mounting is vertical. Remodel areas: use Raco 500 or 503 with 997 Grip-Lok or equivalent. Minimum 2 ½” depth is required.
Faceplate Hospital grade UL94V-0 ABS molded thermoplastic with inlaid membrane.
COLOR: PMS 427, Light Grey Opaque
Lamp-Life 500,000 hours minimum
Switch-Life 100,000 cycles minimum
Compliance
Certifications UL-1069 US and Canada, E139082
Warranty 5 Years david.kang Highlight david.kang Highlight
MiguelLopez Highlight Novus® Emergency Stations
NV-PBE2/X
NV-PBE2/X | REV 3
West-Com Nurse Call Systems, Inc.
Rear View
Wiring Information:
Connector Cable
J1A, J1B CAT-5e for connection to and from other Novus devices, RJ-45 (2)
J2 22/4 AWG for connection to NV-VDL or NV-LED4, LED output, Panduit CE100F22-4
J3 22/6 AWG for connection to remote input devices, Panduit CE100F22-5
J4 22/2 AWG for output relay (normally open, activates external devices for active alerts), Panduit CE100F22-2
Novus® Generation II Pull Cord Stations
NV-EPC2, NV-WPC2
Note: This information should not be used for final design.
NV-EPC2 | REV 0.B | 150610 1 of 2
West-Com Nurse Call Systems, Inc.
The NV-EPC2 is an emergency pull cord device for the Novus hardware system. Typically installed near the toilet in patient or hall restrooms, it may also be used in tub rooms or other applications where a pull cord may be needed. The standard configuration comes with an eight foot braided nylon cord that may be cut to the needed length. If installation near a damp location is required a SWPC-2000 may be connected to the NV-EPC2, or the NV-EPC2 may be replaced by a NV-WPC2.
(1) NV-EPC2
(2) 6-32 x 1.75” flat head machine screws
(1) Programming certificate with serial number
(1) Water resistant gasket (NV-WPC2 models only)
Cancel button, used to cancel alerts placed by the NV- EPC2 or connected SWPC-2000.
Active alert indicator LED. Flashes white when an alert is active.
Push for Assistance button (optional), used to place a bath assistance rather than a bath emergency alert.
Emergency pull cord, used to place a bath emergency alert.
Cord length may be shortened based on mounting and code requirements.
Performance
Operating voltage 12-28VDC
Power consumption 1VA maximum
Thermal 3.412 BTU maximum
Lamp life 500,000 hours MTBF
Switch life 100,000 cycles MTBF
Pull cord burst rating 30 lbs. +/- 3 lbs.
Mounting
New construction box RACO190
Plaster ring RACO 768
Remodel box RACO 500 or 503 with 977 Grip-Loc
Box depth 2.5” (63.5mm) minimum clear depth
Dimensions
Width 2.75” (70mm)
Height 4.5” (114.3mm)
Depth 1.5” (38mm)
Compliance
Certifications/Listings UL 1069 Pending
Warranty 5 years
Compatibility
Dome Lights
NV-DOME (all) NV-DOME2 (all) NV-LDL2
NV-SDL2 NV-VDL (w/ red PCB) NV-VDL2
In Room Devices
NV (all) NVV (all) SWPC-2000
NV-AER NV-SER
The NV-EPC2 may directly replace a NV-EPC or NVV-EPC.
Software and Displays
FocusCare® Patient Careboard NV-VIP mlopez
Note: This information should not be used for final design.
NV-EPC2 | REV 0.B | 150610 2 of 2
West-Com Nurse Call Systems, Inc.
J1A & J1B CAT5 RJ-45
Pin 1 White Blue Transmit (-)
Pin 2 Blue White Transmit (+)
Pin 3 White Orange Receive (-)
Pin 4 Orange White Receive (+)
Pin 5 White Green System Power (-)
Pin 6 Green White System Power (-)
Pin 7 White Brown System Power (+)
Pin 8 Brown White System Power (+)
J2 22/4 CE100F22-4
Pin 1 Green LED Power (+5V)
Pin 2 White Blue LED (-)
Pin 3 Red Red LED (-)
Pin 4 Black Green LED (-)
J3 22/6 CE100F22-5
Pin 1 White Remote Input 1
Pin 2 Black Ground
Pin 3 Red +5VDC Output
Pin 4 Green Remote LED
Pin 5 Blue Remote Input 2
J4 22/2 CE100F22-2
Pin 1 Red Relay Contact
Pin 2 Black Relay Contact
J2: LED output header, used for connecting to the NV-VDL2 or NV-VDL with red PCB. Capable of 16 unique colors.
J3: Remote device connection, used for connecting the SWPC-2000 or other remote input devices.
J1A & J1B: Novus device connections, used for connecting to and from other Novus devices.
J4: Output replay (normally open), used to activate external devices when alerts are active.
Cleaning Information The NV-EPC2 is designed to be cleaned using a cloth dampened with cleaning solution. Dousing or soaking of the device may result in water egress. Improper cleaning methods shall not be covered under warranty. For more information please see: West-Com Approved Cleaning Techniques and Supplies
Options
EPC Emergency pull cord, no options
WPC Emergency pull cord with water resistant membrane
/A Push for assistance button
/G Glow in the dark polyurethane cord
/P White polyurethane cord, red cord may be ordered by adding –RED to the part number.
Ordering Info Continued
Model Part No. Model Part No.
NV-EPC2 40139614 NV-WPC2 40139615
NV-EPC2/A 40139622 NV-WPC2/A 40139653
NV-EPC2/AG 41039652 NV-WPC2/AG 40139655
NV-EPC2/AP 40139651 NV-WPC2/AP 40139654
NV-EPC2/G 40139620 NV-WPC2/G 40139621
NV-EPC2/P 40139617 NV-WPC2/P 40139618
NV-EPC2/AP 4013965
Minimum mounting area required Voltage test points
16 dome lights per NV-HRM LED status indicators
Unlimited networking capabilities 63 devices per i-Dome®/Novus® Visual HR
Solid state circuitry Can be modified to support Novus® Visual and stand alone i-Dome® devices
Novus® Home Run Module
NV-HRM
Features
MiguelLopez Highlight Novus ® Home Run Module
NV-HRM
Versions and Model Numbers
STATION TYPE MODEL NO.
Home Run Module. Remote panel supports 16 Dome Lights. Includes required electronics, PS-28 and 12x12 Hoffman Box.
NV-HRM
i-Dome®/Novus® Home Run Module supports up to 63 devices. Includes required electronics, PS-28 and 12x12 Hoffman Box.
i-Dome HRM
For use with the WestCall® Novus® system
Operating Voltage 120 VAC and 28 VDC +/-10%
Power Consumption 3 Watts
Weight 15 lbs
Mounting Cabinet 12"H x 12"W x 6"D
Termination CE100F22-5 Panduit connector for field audio connection and CE156F22-3 for power connection. RJ-45 plugs for homerun data cable, CNTR-1 network connections.
Certifications UL-1069 for US and Canada, E139082
NOTE: This information should not be used for final design. Consult West-Com for total system requirements.
Specifications subject to change without notice.
West-Com Patented Innovations Components of the WestCall® Novus® system are protected by one or more of the following U.S. Patents: 8,009,021, 7,994,900, D614,520
Technical Specifications
Home Run Module. Remote panel supports 16 Dome Lights. Includes required electronics, PS-28 and 12x12 Hoffman Bo
MiguelLopez
NV-HRM
File details come from the government source that posted it. Updated .