S05 - Att 02 - Nurse Call Cut-Sheets Request.pdf

PDF 2 MB Posted

Attached to
Y1DA--Remodel Specialty Care & Correct HVAC in Bldg. 19 - Martinez VAMC
Solicitation number
36C77621B0021
Issued by

About this file

This document provides details for a federal solicitation to remodel specialty care and correct HVAC systems in Building 19 at the Martinez Veterans Affairs Medical Center. The contractor shall provide all labor, materials, tools, equipment, supervision and other resources necessary to complete the construction project in accordance with the attached specifications and drawings. The solicitation number is 36C77621B0021 and is seeking to award a contract to remodel areas for specialty care and repair HVAC systems in an existing medical center building. The work must be completed in coordination with the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Relevant details are provided regarding the scope of work and responsible federal agency to carry out this construction project at the Martinez VAMC.

View the file

Other files

File Type Posted
S05 - Att 08e - Existing Equipment (5).jpg JPG image
S05 - Att 08b - Existing Equipment (2).jpg JPG image
S05 - Att 04 - 19_Martinez Floor Plan.pdf PDF
S05 - Att 03 - ICRA_ICCP -- Final.pdf PDF
S05 - Att 08g - Existing Equipment (7).jpg JPG image
S05 - Att 07g - CAD Files - Plumbing (7).zip ZIP file
S05 - Att 07b - CAD Files - Architectural (2).zip ZIP file
S05 - Att 08h - Existing Equipment (8).jpg JPG image
S05 - Att 07f - CAD Files - Mechanical (6).zip ZIP file
S05 - Att 07d - CAD Files - Electrical (4).zip ZIP file
S05 - Att 06 - VAV Pipe Detail.zip ZIP file
36C77621B0021 0003.pdf PDF
S05 - Att 08d - Existing Equipment (4).jpg JPG image
S05 - Att 07c - CAD Files - Structural (3).zip ZIP file
S05 - Att 07a - CAD Files - Architectural (1).zip ZIP file
S05 - Att 07b - CAD Files - Structual.zip ZIP file
S05 - Att 07e - CAD Files - Fire Protection (5).zip ZIP file
S05 - Att 05 - Martinez B19_RxR_220908.xlsx XLSX spreadsheet
S05 - Att 08a - Existing Equipment (1).jpg JPG image
S05 - Att 08i - Existing Equipment (9).jpg JPG image
S05 - Att 08c - Existing Equipment (3).jpg JPG image
S05 - Att 01 - Technical Questions and Answers 9.9.2022.pdf PDF
S05 - Att 08f - Existing Equipment (6).jpg JPG image
S05 - Att 09 - CAD Files - Chaparral Layouts.zip ZIP file
36C77621B0021 0002.pdf PDF
S04 - Site Visit - Sign-in Sheet.pdf PDF
S06 - SF30 - 36C77621B0021 - Amendment 0001.pdf PDF
S02 - ATTACHMENT 2 - Specifications Vol. 2 of 2.pdf PDF
S02 - ATTACHMENT 9 - Construction Wage Rates.pdf PDF
36C77621B0021.pdf PDF
S02 - ATTACHMENT 10 - Contractor Safety - Environmental Form.docx DOCX document
S02 - ATTACHMENT 5 - Drawings Vol. 3 of 3.pdf PDF
S02 - ATTACHMENT 8 - Limitations on Subcontracting - Construction.docx DOCX document
S02 - ATTACHMENT 4 - Drawings Vol. 2 of 3.pdf PDF
S02 - ATTACHMENT 6 - Contractor Core Work Hours.pdf PDF
S02 - ATTACHMENT 7 - COVID-19 Safety Protocols 12-14-21.pdf PDF
S02 - ATTACHMENT 3 - Drawings Vol. 1 of 3.pdf PDF
S02 - ATTACHMENT 1 - Specifications Vol. 1 of 2.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Novus® Digital Multipurpose Portal

NV-DMP

NOTE: This information should not be used for final design.

Specifications are subject to change without notice.

West-Com Nurse Call Systems, Inc.

2200 Cordelia Road, Fairfield, CA 94534 westcomncs.com | 800.761.1180

NV-DMP | REV 3.2

Description The Novus Digital Multipurpose Portal is designed for multiple uses such as a standalone, complete call system for small units and senior living facilities utilizing the wired CliniCare solution. The NV-DMP can also serve as a standalone wireless call system, or as a Call Display Terminal to enhance visibility of calls to remote locations of a hospital.

The NV-DMP has an easy to read LCD display, RS- 422 specifically designed for wireless nurse call, RS- 232 connectivity for a direct connection to a paging transmitter, and RS-485 for West-Com Novus devices.

Compatibility

Systems and Devices

Novus CliniCare System, Novus Gen II System, West-Com Wireless

Ordering Information Model Name Description

NV-DMP Novus Digital Multipurpose Portal

Box Contents

NV-DMP (1)

Cable, RS-232 for NV-DMP (1) 6-32 x 1.75 flathead machine screws (4) Programming certificate and serial number RJ-45 connector 6-554720-2 (1) Panduit 8-pin CE100F24-8 (1) Panduit 3-pin CE156F22-3 (1) RS-232 Premade Cable (1)

† West-Com Patented Innovations This product is protected by one or more of the following U.S. Patents:

8,009,021, 7,994,900, D614,520

Specifications Characteristic Description

Operating Voltage 8-28VDC

Power Consumption <2.5W

Dimensions 4.75″H x 7.0″W (120.6mm x 177.8mm)

Faceplate Hospital grade Polylac PA765NAT with light grey opaque

Cable Requirements Ethernet CAT-5e 8-pin RS-485 device cable 24AWG 8-pin RS-422 cable 22AWG 2-pin RS-232 cable 22AWG 3-pin Power cable +28VDC 22AWG 3-pin

Termination RJ-45 connector (1), 6-554720-2 Panduit 8-pin CE100F24-8 (1) Panduit 3-pin CE156F22-2 (1)

Touch Screen 4.5″ (114.3mm), color

Speaker Built-in

Mounting 4-gang backbox with a 3-gang mud ring

RACO 822, 952

Compliance

Certifications UL-1069 US and Canada, E139082

Warranty Five years http://www.westcall.com/ MiguelLopez Highlight Novus® Digital Multipurpose Portal

NV-DMP

West-Com Nurse Call Systems, Inc.

2200 Cordelia Road, Fairfield, CA 94534

NV-DMP | REV 3.2

Wiring Information

Component Cable Compatibility Functionality

T1 CAT-5e, RJ-45 10BASE-T network connection

J3 22/4 Contact closure relay connections

J4 CAT-5e West-Com Straight Through RS-485, Data for Novus network

J7 22/2 RS-482, Rx+ & Rx- from wireless transmitter

J8 22/4 RS-232, Tx & Rx from paging transmitter

J12 18/2 Power and Ground

Novus® Dome Light

NV-DOME2

NV-DOME2 | REV 8.1 | 151222

West-Com Nurse Call Systems, Inc.

2200 Cordelia Road, Fairfield, CA 94534 westcall.com | 800.761.1180

System and Devices

Compatible with all Novus Systems

Compatible with Novus and Novus Visual devices

Software

FocusCare® Software 1.1.8.x

Ordering Information

Description Model Number

Novus dome with optical input, output relay, and buzzer.

NV-DOME2

Only uses CAT-5 cable; no audio support, for use with Visual Systems only.

NV-DOME2/V

Economy version. Provides same functionality as regular NV-DOME2, but uses simplified plastic housing to reduce cost.

NV-DOME2/E

Combines the /V and the /E options. NV-DOME2/VE

Box Contents

NV-DOME2 (1)

6-32 x 1.75 flathead machine screws (4)

Programming certification and serial number (1)

Options

None

Description

The NV-Dome2 gives clear visual notification to staff members of a room’s status. The customizable, four-segmented dome displays different color combinations to alert staff to a variety of alert types. A built-in buzzer can be activated for multiple alert types. The NV-Dome2 can automatically detect attached devices during the initial configuration and has the ability to report multiple connected devices as unique locations.

Characteristic Description

Operating Voltage 8-28VDC

Power Consumption <2.0W

Dimensions 5 ½” x 5 ½″W x 3 ¾″D (139.7mm x 139.7mm x 95.25mm)

Cable Requirements CAT-5, Special Orange, 22/2 pair shielded

Termination (3) RJ-45, (2) Panduit CE156F22-3, (1) Panduit CE100F22-5, (2) Panduit CE100F22-2

Faceplate Hospital grade ABS plastic back plate. PMS 427 light grey opaque.

Luminary Molded white polystyrene plastic, replaceable

Mounting 4.7” (119.4mm) square back-box with two-gauge plaster ring. Raco 257 with 818 or equivalent

Certifications UL-1069 for US and Canada, E139082

Warranty Five Year http://www.westcall.com/ mlopez Highlight

MiguelLopez Highlight

NV-DOME2

NV-DOME2 | REV 8.1 | 151222 2 of 2

West-Com Nurse Call Systems, Inc.

Connector Layouts

J1 Special Orange power input, 18 AWG, Panduit

J2 Special Orange power output, 18AWG, Panduit

J4 Special Orange input, RJ-45

J5 Special Orange output, RJ-45

J6 22/2 Pair Shielded, audio, Panduit

J7 CAT-5 to room (devices)

J9 Remote output (relay controlled), Panduit

J10 Isolated input, Panduit

Novus® Emergency Stations

NV-PBE2/X

NV-PBE2/X | REV 3

West-Com Nurse Call Systems, Inc.

The Novus Generation II emergency stations are designed for specific patient rooms and other areas where priority calls require immediate attention. These devices connect directly to a dome light or patient station. The emergency stations have a call assurance® LED indicator that confirms to the staff member that the alert has been placed.

Systems and Devices

Compatible with Novus Systems and Devices

Software

FocusCare® Software 1.1.8.x

Ordering Information Description Model Number

Emergency Station, HELP (red) NV-PBE2

Emergency Station, Staff Emergency (red) NV-PBE2/SE

Emergency (Red) NV-PBE2/E

Emergency Station, Code Blue (blue) NV-PBE2/CB

Emergency Station, Code (blue) NV-PBE2/C

Emergency Station, Code Pink (pink) NV-PBE2/CP

Emergency Station, Assist (yellow) NV-PBE2/A

Emergency Station, Code White (white) NV-PBE2/CW

Emergency Station, Staff Call (white) NV-PBE2/SC

Emergency Station, Staff Emergency (red) Code Blue (blue)

NV-PBE2/SE/CB

Emergency Station, Code White (white) Staff Emergency (red)

NV-PBE2/CW/SE

Emergency Station Clear Protector ESP-2000

Emergency Station Clear Protector (door) ESP-2000/D

Optional Accessories None

NV-PBE2 (1)

6-32 x 1.75 flathead machine screws (2) Programming certificate with serial number (1)

Specifications Characteristic Description

Operating Voltage 8-28VDC

Power Consumption 0.06W idle, 0.75W maximum

Dimensions 4 ½″H x 2 ¾″W x 1 ½″D (114.3mm x 69.8mm x 38.1mm)

Cable Requirements CAT-5e or better

Termination RJ-45 connectors (2), Panduit CE100F22-5, CE100F22-4, CE100F22-2

Mounting

4” (101.6mm) square back-box with one-gang plaster ring, Raco 190 with 768 one- gang adapter or equivalent. Minimum 2 1/8" (54mm) depth required.

Normal mounting is vertical. Remodel areas: use Raco 500 or 503 with 997 Grip-Lok or equivalent. Minimum 2 ½” depth is required.

Faceplate Hospital grade UL94V-0 ABS molded thermoplastic with inlaid membrane.

COLOR: PMS 427, Light Grey Opaque

Lamp-Life 500,000 hours minimum

Switch-Life 100,000 cycles minimum

Compliance

Certifications UL-1069 US and Canada, E139082

Warranty 5 Years david.kang Highlight david.kang Highlight

MiguelLopez Highlight Novus® Emergency Stations

NV-PBE2/X

NV-PBE2/X | REV 3

West-Com Nurse Call Systems, Inc.

Rear View

Wiring Information:

Connector Cable

J1A, J1B CAT-5e for connection to and from other Novus devices, RJ-45 (2)

J2 22/4 AWG for connection to NV-VDL or NV-LED4, LED output, Panduit CE100F22-4

J3 22/6 AWG for connection to remote input devices, Panduit CE100F22-5

J4 22/2 AWG for output relay (normally open, activates external devices for active alerts), Panduit CE100F22-2

Novus® Generation II Pull Cord Stations

NV-EPC2, NV-WPC2

Note: This information should not be used for final design.

NV-EPC2 | REV 0.B | 150610 1 of 2

West-Com Nurse Call Systems, Inc.

The NV-EPC2 is an emergency pull cord device for the Novus hardware system. Typically installed near the toilet in patient or hall restrooms, it may also be used in tub rooms or other applications where a pull cord may be needed. The standard configuration comes with an eight foot braided nylon cord that may be cut to the needed length. If installation near a damp location is required a SWPC-2000 may be connected to the NV-EPC2, or the NV-EPC2 may be replaced by a NV-WPC2.

(1) NV-EPC2

(2) 6-32 x 1.75” flat head machine screws

(1) Programming certificate with serial number

(1) Water resistant gasket (NV-WPC2 models only)

Cancel button, used to cancel alerts placed by the NV- EPC2 or connected SWPC-2000.

Active alert indicator LED. Flashes white when an alert is active.

Push for Assistance button (optional), used to place a bath assistance rather than a bath emergency alert.

Emergency pull cord, used to place a bath emergency alert.

Cord length may be shortened based on mounting and code requirements.

Performance

Operating voltage 12-28VDC

Power consumption 1VA maximum

Thermal 3.412 BTU maximum

Lamp life 500,000 hours MTBF

Switch life 100,000 cycles MTBF

Pull cord burst rating 30 lbs. +/- 3 lbs.

Mounting

New construction box RACO190

Plaster ring RACO 768

Remodel box RACO 500 or 503 with 977 Grip-Loc

Box depth 2.5” (63.5mm) minimum clear depth

Dimensions

Width 2.75” (70mm)

Height 4.5” (114.3mm)

Depth 1.5” (38mm)

Compliance

Certifications/Listings UL 1069 Pending

Warranty 5 years

Compatibility

Dome Lights

NV-DOME (all) NV-DOME2 (all) NV-LDL2

NV-SDL2 NV-VDL (w/ red PCB) NV-VDL2

In Room Devices

NV (all) NVV (all) SWPC-2000

NV-AER NV-SER

The NV-EPC2 may directly replace a NV-EPC or NVV-EPC.

Software and Displays

FocusCare® Patient Careboard NV-VIP mlopez

Note: This information should not be used for final design.

NV-EPC2 | REV 0.B | 150610 2 of 2

West-Com Nurse Call Systems, Inc.

J1A & J1B CAT5 RJ-45

Pin 1 White Blue Transmit (-)

Pin 2 Blue White Transmit (+)

Pin 3 White Orange Receive (-)

Pin 4 Orange White Receive (+)

Pin 5 White Green System Power (-)

Pin 6 Green White System Power (-)

Pin 7 White Brown System Power (+)

Pin 8 Brown White System Power (+)

J2 22/4 CE100F22-4

Pin 1 Green LED Power (+5V)

Pin 2 White Blue LED (-)

Pin 3 Red Red LED (-)

Pin 4 Black Green LED (-)

J3 22/6 CE100F22-5

Pin 1 White Remote Input 1

Pin 2 Black Ground

Pin 3 Red +5VDC Output

Pin 4 Green Remote LED

Pin 5 Blue Remote Input 2

J4 22/2 CE100F22-2

Pin 1 Red Relay Contact

Pin 2 Black Relay Contact

J2: LED output header, used for connecting to the NV-VDL2 or NV-VDL with red PCB. Capable of 16 unique colors.

J3: Remote device connection, used for connecting the SWPC-2000 or other remote input devices.

J1A & J1B: Novus device connections, used for connecting to and from other Novus devices.

J4: Output replay (normally open), used to activate external devices when alerts are active.

Cleaning Information The NV-EPC2 is designed to be cleaned using a cloth dampened with cleaning solution. Dousing or soaking of the device may result in water egress. Improper cleaning methods shall not be covered under warranty. For more information please see: West-Com Approved Cleaning Techniques and Supplies

Options

EPC Emergency pull cord, no options

WPC Emergency pull cord with water resistant membrane

/A Push for assistance button

/G Glow in the dark polyurethane cord

/P White polyurethane cord, red cord may be ordered by adding –RED to the part number.

Ordering Info Continued

Model Part No. Model Part No.

NV-EPC2 40139614 NV-WPC2 40139615

NV-EPC2/A 40139622 NV-WPC2/A 40139653

NV-EPC2/AG 41039652 NV-WPC2/AG 40139655

NV-EPC2/AP 40139651 NV-WPC2/AP 40139654

NV-EPC2/G 40139620 NV-WPC2/G 40139621

NV-EPC2/P 40139617 NV-WPC2/P 40139618

NV-EPC2/AP 4013965

Minimum mounting area required Voltage test points

16 dome lights per NV-HRM LED status indicators

Unlimited networking capabilities 63 devices per i-Dome®/Novus® Visual HR

Solid state circuitry Can be modified to support Novus® Visual and stand alone i-Dome® devices

Novus® Home Run Module

NV-HRM

Features

MiguelLopez Highlight Novus ® Home Run Module

NV-HRM

Versions and Model Numbers

STATION TYPE MODEL NO.

Home Run Module. Remote panel supports 16 Dome Lights. Includes required electronics, PS-28 and 12x12 Hoffman Box.

NV-HRM

i-Dome®/Novus® Home Run Module supports up to 63 devices. Includes required electronics, PS-28 and 12x12 Hoffman Box.

i-Dome HRM

For use with the WestCall® Novus® system

Operating Voltage 120 VAC and 28 VDC +/-10%

Power Consumption 3 Watts

Weight 15 lbs

Mounting Cabinet 12"H x 12"W x 6"D

Termination CE100F22-5 Panduit connector for field audio connection and CE156F22-3 for power connection. RJ-45 plugs for homerun data cable, CNTR-1 network connections.

Certifications UL-1069 for US and Canada, E139082

NOTE: This information should not be used for final design. Consult West-Com for total system requirements.

Specifications subject to change without notice.

West-Com Patented Innovations Components of the WestCall® Novus® system are protected by one or more of the following U.S. Patents: 8,009,021, 7,994,900, D614,520

Technical Specifications

Home Run Module. Remote panel supports 16 Dome Lights. Includes required electronics, PS-28 and 12x12 Hoffman Bo

MiguelLopez

NV-HRM

File details come from the government source that posted it. Updated .