S02 - 695-22-123 Drawings Part 4 of 4.pdf
PDF 15 MB Posted
- Solicitation number
- 36C25226B0023
About this file
These are electrical construction bid documents for the U.S. Department of Veterans Affairs' Clement J. Zablocki VAMC in Milwaukee, Wisconsin, specifically for the Upgrade North Campus Medium Voltage Feeder project (Project Number 695-22-123). The documents include comprehensive electrical site plans, electrical details, feeder schedules, equipment schedules, grounding plans, Kirk key interlock information, and a single-line diagram for the proposed electrical system upgrades. The work involves installation of new medium voltage (15kV) cable feeders, ductbank systems, electrical switches (HVP/HVS), transformers, panels, and associated infrastructure across five electrical zones covering the north campus area. The project includes replacement of aging equipment with new Cooper/Eaton switches and transformers, installation of cable vault details at Building 115, grounding and bonding systems, and Kirk key interlocked switches (HVS-SL1, HVS-2, HVS-3, HVS-12, HVS-20, HVS-24, HVS-27, and HVS-31) to prevent backfeeding throughout distribution loops. The drawings specify cable schedules with 250 kcmil conductors, equipment specifications including 15kV rated components, manhole details for underground construction, and detailed installation procedures for ductbank, cable carriers, and grounding configurations. The issue date is October 9, 2025, with drawings sealed by a New York-based licensed professional engineer.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T105
XF-97
XF-36
RED ARROW CIR
W
OR
KS
HO
P
RO
AD
BARRON CT
WOOD AVE
XF-108
MH-37
107/108-DS-A
MH-38
XF-39
MH-10
PNL-2V
MH-36B
HANK AARON TRAIL BRIDGE
E
E
E
E
E
E
E
T106
T107
MH-36A
MH-36
HVP-36A
HVP-11A PNL-39
HVP-11
MH-11
XF-20
HVP-36
1538 3589
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL - ZONE 3 BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES403
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ES501 FOR ELECTRICAL DETAILS
3. SEE ES601 FOR CABLE SCHEDULE
4. SEE ES602 & ES603 FOR EQUIPMENT SCHEDULES.
5. SEE ES605 FOR KIRK KEY INFORMATION
6. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.
7. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS
8. THIS DRAWING IS DIAGRAMMATIC IN NATURE ONLY. SEE CU101 FOR ACTUAL SITE
SURVEY AND TRUE LOCATIONS OF UTILITY LINES.
SCALE: 1" = 60'
ELECTRICAL - ZONE 31
N
ZONE 5 1/ES405
MATCHLINE
ZO
NE
1/E
S4
MA
TC
HL
IN
E
SITE PROPOSED LINETYPES
MATCHLINE
EXISTING DUCT BANK AND NEW CABLE
EXISTING LOW VOLTAGE DUCT BANK
NEW DUCT BANK / CABLE / EQUIPMENT
- POWER DISTRIBUTION SWITCH (HVP OR HVS)
- TRANSFORMER (XF)
- ELECTRICAL PANEL (PNL)
- UTILITY, ELECTRICAL MANHOLE (MH)
SITE PLAN SYMBOL LEGEND
E
BUILDING FED FROM WE ENERGIES
BUILDING FED FROM VA
- LIGHT POLE / STREET LIGHT
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
HVP-K
HVP-15
LINCOLN DR
HI
NE
S
BL
VD
FLOWER DR
HINES BLV
D
HVP-16
XF-102
BCL
XF-43
XF-119
MH-47A
MH-2B
MH-2A
MH
MH-15
PNL-K
MH-47
XF-1301
MH-21
Cemetery National Wood
Wheeler Lake
E
E
E
E
E
E
E
E
E
HVS-SL1
MH-3
GENERAL MITCHELL BLVD
HVP-2
E
HVS-3
HVS-A
XF-K
HVS-2
HVP-16A
MH-2
EMH-12E
MH-12D
265126552674
30493050
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL - ZONE 4 BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES404
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
SCALE: 1" = 60'
ELECTRICAL - ZONE 41
N
MA
TC
HL
IN
E
ZO
NE
1/E S4
MATCHLINE
ZONE 2 1/ES402
SITE PROPOSED LINETYPES
MATCHLINE
EXISTING DUCT BANK AND NEW CABLE
NEW DUCT BANK/CABLE/EQUIPMENT
EXISTING LOW VOLTAGE DUCT BANK
- POWER DISTRIBUTION SWITCH (HVP OR HVS)
- TRANSFORMER (XF)
- ELECTRICAL PANEL (PNL)
- UTILITY, ELECTRICAL MANHOLE (MH)
SITE PLAN SYMBOL LEGEND
E
BUILDING FED FROM WE ENERGIES
BUILDING FED FROM VA
- LIGHT POLE / STREET LIGHT
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ES501 FOR ELECTRICAL DETAILS
3. SEE ES601 FOR CABLE SCHEDULE
4. SEE ES602 & ES603 FOR EQUIPMENT SCHEDULES.
5. SEE ES605 FOR KIRK KEY INFORMATION
6. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.
7. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS
8. THIS DRAWING IS DIAGRAMMATIC IN NATURE ONLY. SEE CU101 FOR ACTUAL SITE
SURVEY AND TRUE LOCATIONS OF UTILITY LINES.
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GENERAL MITCHELL BLVD
BARRON CT
HVS-146
XF-146
CB-100-CLC
CB-600-146
HVS-147
XF-147
CB-600-147
CB-600-148
XF-148
HVS-148
MH-13 MH-13A
PNL-CLC
E
E
E
E
XF-SL1
PNL-SL1
E
MH-12
HVS-12
MH-12B
HVP-11
WAREHOUSE WAY
E MH-12A
E MH-12C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL - ZONE 5 BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES405
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
- POWER DISTRIBUTION SWITCH (HVP OR HVS)
- TRANSFORMER (XF)
- ELECTRICAL PANEL (PNL)
- MANHOLE (MH)
SITE PLAN SYMBOL LEGEND
SCALE: 1" = 60'
ELECTRICAL - ZONE 51
N
E
MATCH LINE
ZONE 3 1/ES403
MA
TC
H
LIN
E
ZO
NE
1/E S4
SITE PROPOSED LINETYPES
MATCHLINE
EXISTING DUCT BANK AND NEW CABLE
NEW DUCT BANK
EXISTING LOW VOLTAGE DUCT BANK
- STREETLIGHT / LIGHT POLE
- BUILDING POWERED BY WE ENERGIES
- BUILDING POWERED BY VA
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ES501 FOR ELECTRICAL DETAILS
3. SEE ES601 FOR CABLE SCHEDULE
4. SEE ES602 & ES603 FOR EQUIPMENT SCHEDULES.
5. SEE ES605 FOR KIRK KEY INFORMATION
6. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.
7. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS
8. THIS DRAWING IS DIAGRAMMATIC IN NATURE ONLY. SEE CU101 FOR ACTUAL SITE
SURVEY AND TRUE LOCATIONS OF UTILITY LINES.
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DETECTABLE WARNING
TAPE
CAST-IN-PLACE
CONCRETE ENCASEMENT
SECURE TOP SPACER
TO PREVENT CONDUITS FROM
FLOATING DURING CONCRETE POUR
4" DUCTBANK CONDUITS
TYP
PLASTIC CODUIT
SPACERS / SUPPORTS
CONCRETE PAVERS FOR
LEVELING
UNDISTURBED EARTH3" 3"
3 5 /16
3"
3"
6" MI
NI
MU
M
BE
LO
W G
RA
DE
INSTALL #4 REBAR
TYPICAL
FLOAT CONTACT AREA
(2 PLACES REQUIRED)
OPENING FOR OPTIONAL 1/2"
CABLE TO STABILIZE DUCT
BANK DURING INSTALLATION
(2 REQUIRED AS SHOWN)
2" DIAMETER
WHEEL ASSEMBLY
SECURE CONDUITS TO BORE SPACERS SLOT IS CHAMFERED .312" x 22.5° ON ONE
SIDE OF BORE SPACER TO AID IN THE
WITHDRAWAL OF GROUT INJECTION PIPE.
NOTES:
1. USE ONE BORE SPACER FOR EVERY 5 FEET OF DUCT BANK.
2. THE CASING ID MUST BE SMOOTH AND FREE FROM RIDGES, PROJECTIONS AND
SEAMS THAT MIGHT IMPEDE THE ROLLING OF WHEELS
3. INSTALL BORE SPACERS PERPENDICULAR TO CONDUITS TO REDUCE THE
TENDENCY OF DUCT BANK TO CORKSCREW.
4. A THROUGH OR FEEDER BRIDGE SHOULD BE CONSTRUCTED AT THE LEADING
EDGE OF THE CASING TO SUPPORT SECTIONS OF DUCT BANK AS THEY ARE
ASSEMBLED AND PULLED INTO THE CASING.
5. IT IS ESSENTIAL THAT THE BORE SPACERS ARE HELD IN PLACE RELATIVE TO
THE CONDUIT.
6. THE DUCT BANK MUST BE HELD IN POSITION AT BOTH ENDS TO ACCOMMODATE
POSSIBLE UNEVEN THRUST LOADS THAT MAY BE GENERATED DURING THE
GROUTING OPERATION.
7. WHEN FILLING THE AREA BETWEEN THE CONDUITS AND CASING WITH GROUT,
TAKE CARE NOT TO EXCEED THE HYDRAULIC COLLAPSE PRESSURE OF THE
CONDUITS.
8. DETAILS PERTAIN TO JACK AND BORE AREAS. SEE CS401 AND CS402 FOR
ADDITIONAL INFORMATION.
FIRE TAPED FEEDER
BUNDLE (TYP)
ADJUSTABLE HEAVY
DUTY 20" LONG
FIBERGLASS ARM
(TYP)
60" ADJUSTABLE HEAVY
DUTY FIBERGLASS
STANCHIONS - MOUNTED
TO WALL
WALL
CABLE VAULT FLOOR
CABLE VAULT CEILING
USE CABLE TIE TO
ATTACH FIRE TAPED
FEEDER BUNDLE TO ARM
(TYP)
NOTE:
1. PROVIDE FIBERGLASS VERTICAL STANCHIONS AND
ARM SUPPORTS AT MAXIMUM SPACING OF 5'-0". REFER
TO CABLE MANUFACTURE'S RECOMMENDED SUPPORT
REQUIREMENTS.
2. FASTEN TO WALL WITH STAINLESS STEEL HARDWARE.
FIBERGLASS CHANNEL
MOUNTED TO CEILING
(TYP)
NOTE:
1. PROVIDE FIBERGLASS CHANNEL AND PORCELAIN CLAMP SUPPORTS AT
MAXIMUM SPACING OF 5'-0". REFER TO CABLE MANUFACTURE'S
RECOMMENDED SUPPORT REQUIREMENTS.
2. FASTEN TO CEILING WITH STAINLESS STEEL HARDWARE.
PORCELAIN CABLE
CHANNEL CLAMP (TYP)
FIRE TAPED FEEDER
BUNDLE (TYP)
8"
SECTION "A-A"
SECTION "B-B"
VA
RI
ES
5'-0"
6'-4"
8"
" M
IN
8"
5'-0"
8"
7'- 4"
3"
8'- 0"
8"
9'- 4"
8"
BB
3'- 0"3'-0"
NOTES:
1. VAULT LOADING: H-20 BRIDGE SPECIFICATIONS, NO OVERBURDEN.
2. MINIMUM ROOF AND WALL THICKNESS IS 6" EXCEPT FOR KNOCKOUT
WINDOWS.
3. GROUND ROD HOLES: 1" DIAMETER, 1 REQUIRED
4. PROVIDE FOUR (4) PULLING IRONS MADE FROM 78" GALVANIZED STEEL
BAR
5. PROVIDE 6" SUB-BASE LAYER OF WELL-TAMPED 1" CRUSHED BLUE
STONE BENEATH EACH VAULT
6. VAULTS SHALL BE ON A 12" LEVEL BED OF 90% COMPACTED GRANULAR
FILL, WELL GRADED FROM THE 1" SIEVE TO THE NO. 4 SIEVE,
GRANULAR FILL SHALL BE COMPACTED WITH A MINIMUM OF FOUR )4)
PASSES WITH A PLATE COMPACTOR
7. VAULT LID SHALL BE EFFECTIVELY BONDED TO THE VAULT GROUND
SYSTEM PER NEC
8. INCLUDE ALUMINUM LADDER (NOT SHOWN FOR CLARITY)
TOP VIEW
POWER
3'-2"
6'-4"
3'-2"
5'- 6"
3'-
9'- 4"
AA
GROUND ROD PER
SECTION 26 05 26.
GRAVEL SUMP
1 CUBIC YARD 3/4"
SUMP 12"
SUMP FRAME
& COVER
PULLING
IRON
FINISHED
GRADE
GRADE RINGS AS REQ'D TO
MATCH CIVIL FINISHED
GRADE ELEVATION.
CABLE
STANCHION
GROUND ROD
SLEEVE
PULLING
IRON
SUMP
12"x12"
SLOPE
SLOPE
SL
OP
E
CABLE STANCHION PER
SECTION 26 05 41.
CAST-IN-PLACE
CONCRETE ENCASEMENT
SECURE TOP SPACER
TO PREVENT CONDUITS FROM
FLOATING DURING CONCRETE POUR
4" DUCTBANK CONDUITS
TYP
PLASTIC CODUIT
SPACERS / SUPPORTS
CONCRETE PAVERS FOR
LEVELING
3" 3"
3 5 /16
3"
TOP OF EXISTING CONCRETE CULVERT
INSTALL #4 REBAR
TYPICAL
NO
MI
NA
L 1
6" V
IF
6" THK CONCRETE SIDEWALK
SEE CS501, DETAIL 7
AB
NOTES:
1. MANUFACTURE CAP FROM 14" CARBON STEEL.
2. WELD LIFTING EYES AT 4 CORNERS OF CAP.
3. REFERENCE SPECIFICATION 05 50 00 METAL FABRICATIONS FOR ADDITIONAL INFORMATION.
4. PAINT INSIDE AND OUTSIDE WITH 2-PART EPOXY PAINT 2 MILS THICK.
5. SEE PAINT SPECIFICATION 09 91 00 PAINTING FOR ADDITIONAL INFORMATION.
FRONT SIDE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
SITE ELECTRICAL DETAILS BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES501
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
SCALE: NTS
SITE ELECTRICAL DUCT BANK DETAIL1 SCALE: NTS
BORE CARRIER DETAIL2 SCALE: NTS
WALL CABLE CARRIER DETAIL3 SCALE: NTS
CEILING CABLE CARRIER DETAIL4
SCALE: NTS
TYPICAL MANHOLE DETAIL5 SCALE: NTS
SITE ELECTRICAL DUCT BANK AT CULVERT CROSSING DETAIL6
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.
3. SEE EG101 FOR GROUNDING SITE PLAN.
4. SEE EP101 FOR BUILDING 115 FLOOR PLAN.
5. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.
6. SEE SPECIFICATION 26 05 41 FOR UNDERGROUND ELECTRICAL CONSTRUCTION.
SCALE: NTS
PEDESTAL / VAULT COVER DETAIL7
Exp.: 12/31/2028
AutoCAD SHX Text
CONC. ENVELOPE
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
T/FINISHED GRADE
OR FLOOR
APPROVED
BACKFILL
CAUTION-BUR
UTILITY WARNING
TAPE
RIGID METALLIC
CONDUIT RISER
RIGID METALLIC
COUPLING
CONCRETE
ENCASEMENT
RIGID METALLIC CONDUIT
ELBOW OR SWEEP
UNDISTURBED
SOIL
PVC-TO-RIGID
METALLIC COUPLING
UNLESS NOTED OTHERWISE,
SCHEDULE 40 PVC CONDUIT
RUN, ROUTE PER PLAN DRAWING
REFER TO ESD-318 FOR
ADDITIONAL CONCRETE ENCASED
DUCTBANK INFORMATION
T/CONCRETE
ENCASEMENT
SHALL BE RED
6" 4"
CT
CT
CT
BYZ CT
GROUND SHIELD WIRES
NOTES:
1. IF GROUND SENSOR CT IS USED, RETURN SHIELD WIRE VIA
CT AND THEN TO GROUND.
2. ALL STRESS CONES MUST BE AT THE SAME LEVEL IN ELEVATION
TO REDUCE DETERIORATION OF CABLE DUE TO CORONA.
NON-SHIELDED
FACTORY WIRING
CONDUIT
CABINET
STRESS CONE LOCATIONS
ALL AT SAME LEVEL
SHIELDED CABLES
AFTER ALL TESTING HAS BEEN
COMPLETED, INSULATE ALL FIELD
TERMINATIONS USING FILLER, HIGH
VOLTAGE & FINISHING TAPE
TYPICAL CRIMP LUG
CONCRETE MANHOLE OR
UNDERGROUND CABLE VAULT
FINAL 10' LENGTH OF
CONDUIT INTO MANHOLE
OR VAULT TO BE PVC
5'-0"
1'-6" 2"
PVC END BELL
(TYPICAL)
FILL REMAINING CONDUIT
WINDOW OPENING WITH
CONCRETE OR GROUT
DRILL 7/8"Ø HOLES IN EXTERIOR WALL.
EPOXY ANCHOR #6 REINFORCING
BARS INTO HOLES. OVERLAP WALL
BARS WITH DUCTBANK BARS, AND TIE.
SCHEDULE 40 PVC RUN
PVC-TO-PVC COUPLING
REINFORCED
CONCRETE WALL
TOP VIEW
2'-4"
4'-8"
2'-4"
2'- 4"
2'- 4"
4'- 8"
AA
SUMP 12"
GROUND ROD PER
SECTION 26 05 26.
GALVANIZED PULL/LIFT
IRON
(1 EACH CORNER)
2'-0" LG
GALVANIZED
"C" CHANNEL
4"
3'- 6"4'-
0"
6"
SPRING ASSISTED
GALVANIZED DIAMOND
PLATE DOOR
SECTION "A-A"
1'- 0"
6" 6"
CONCRETE PAVEMENT
SUB-BASE COURSE
STABILIZATION FABRIC
COMPACTED FILL OF PREPARED
SUB-GRADE (TO BE LEVEL)
1/4" SAW CUT
CONTRACTION JOINT
X X3"
6x6 W2.1xW2.1 WELDED
WIRE REINFORCEMENT
SECURE HVP TO VAULT
USING HILTI 1/2" CONCRETE
ANCHOR BOLTS
SECURE HVP TO VAULT
USING HILTI 1/2" CONCRETE
ANCHOR BOLTS
GALVANIZED
STEEL UNISTRUT
(TYP)
GALVANIZED
STEEL POST
(TYP)
PANEL
NEMA 3R
ENCLOSURE
ES502
4'- 0"
2"
1'-0"
TYPE "C" CONCRETE
FOOTING (TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
SITE ELECTRICAL DETAILS BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES502
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
SCALE: NTS
BELOW-GRADE DUCTBANK FOUNDATION
STUB-UP DETAIL1 SCALE: NTS
MV CONDUCTORS CABLE STRESS
CONE TERMINATION DETAIL2
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.
3. SEE EG101 FOR GROUNDING SITE PLAN.
4. SEE EP101 FOR BUILDING 115 FLOOR PLAN.
5. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.
6. SEE SPECIFICATION 26 05 41 FOR UNDERGROUND ELECTRICAL CONSTRUCTION.
SCALE: NTS
DUCTBANK TO MANHOLE DETAIL3
SCALE: NTS
SWITCH VAULT HVS/HVP4 SCALE: 1 1/2"=1'-0"
TYPICAL CONCRETE PAD SECTION5 SCALE: NTS
TYPICAL HVP MOUNTING DETAIL6 SCALE: NTS
TYPICAL PANEL MOUNTING DETAIL7 SCALE: NTS
TYPICAL CONCRETE FOOTING DETAIL8
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL FEEDER SCHEDULE -
NEW WORK
BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES601
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
MEDIUM VOLTAGE FEEDER SCHEDULE - NEW WORK
15KV CABLE CONNECTION INSTALL
FAULT
INDICATOR
(1 PER
PHASE)
NOTE
CABLE
NUMBER TAG SIZES
TOTAL
CONDUCTOR
LENGTH (FT)
3-PHASES
GROUND
LENGTH
(FT)
REEL
NUMBER FROM VIA TO
1 NC-CBL-15KV-001 3 - 250KCMIL, 4/0 GND 2685 895 BLD 115 -
NW-4A
HVS-A
HVP-K HVS-SL1 X CONTRACTOR TO SUPPLY CABLE
2 NC-CBL-15KV-002 3 - 250KCMIL, 4/0 GND 1809 603 18 HVS-SL1 HVP-K
HVP-2 HVS-2 X VA SUPPLIED CABLE
3 NC-CBL-15KV-003 3 - 250KCMIL, 4/0 GND 1071 357 1 HVS-2 HVP-2 HVS-3 X VA SUPPLIED CABLE 4 NC-CBL-15KV-004 3 - 250KCMIL, 4/0 GND 1056 352 1 HVS-3 HVP-15 X VA SUPPLIED CABLE 5 NC-CBL-15KV-005 3 - 250KCMIL, 4/0 GND 1125 375 16 HVP-15 HVP-20 HVS-20 X VA SUPPLIED CABLE
6 NC-CBL-15KV-006 3 - 250KCMIL, 4/0 GND 1425 475 19 HVS-20 HVP-23
HVS-23A HVS-24 X VA SUPPLIED CABLE
7 NC-CBL-15KV-007 3 - 250KCMIL, 4/0 GND 1950 650 6 HVS-24 HVS-27 X VA SUPPLIED CABLE 8 NC-CBL-15KV-008 3 - 250KCMIL, 4/0 GND 612 204 16 HVS- 27 HVP-29 X VA SUPPLIED CABLE 9 NC-CBL-15KV-009 3 - 250KCMIL, 4/0 GND 1161 387 12 HVP-29 HVS-31 X VA SUPPLIED CABLE
10 NC-CBL-15KV-010 3 - 250KCMIL, 4/0 GND 1089 363 2 HVS-31 HVP-34 X VA SUPPLIED CABLE 11 NC-CBL-15KV-011 3 - 250KCMIL, 4/0 GND 1512 504 7 HVP-34 HVP-36 X VA SUPPLIED CABLE 12 NC-CBL-15KV-012 3 - 250KCMIL, 4/0 GND 3039 1013 HVP-36 HVS-12 X CONTRACTOR TO SUPPLY CABLE
13 NC-CBL-15KV-013 3 - 250KCMIL, 4/0 GND 4050 1350 HVS-12 BLD 115
CB-SE-4B X CONTRACTOR TO SUPPLY CABLE
14 NC-CBL-15KV-014 3 - 250KCMIL, 4/0 GND 75 25 19 HVS-SL1 XF-K X VA SUPPLIED CABLE 15 NC-CBL-15KV-015 3 - 250KCMIL, 4/0 GND 3000 1000 HVS-SL1 XF-SL1 X CONTRACTOR TO SUPPLY CABLE 16 NC-CBL-15KV-016 3 - 250KCMIL, 4/0 GND 1050 350 2 HVS-3 HVP-4 X VA SUPPLIED CABLE 17 NC-CBL-15KV-017 3 - 250KCMIL, 4/0 GND 231 77 12 HVP-4 HVS-4 XF-43 X VA SUPPLIED CABLE 18 NC-CBL-15KV-018 3 - 250KCMIL, 4/0 GND 1440 480 13 HVP-4 XF39 X VA SUPPLIED CABLE
19 NC-CBL-15KV-019 3 - 250KCMIL, 4/0 GND 849 283 22 HVP-15 HVP-16
HVS-16 XF-119 X VA SUPPLIED CABLE
20 NC-CBL-15KV-020 3 - 250KCMIL, 4/0 GND 726 242 22 HVP-15 HVP-18 X VA SUPPLIED CABLE
21 NC-CBL-15KV-021 2 - 250KCMIL, 4/0 GND (C-A) 630 210 17 HVP-18 HVP-18
HVS-18 XF-112 X VA SUPPLIED CABLE
22 NC-CBL-15KV-022 3 - 250KCMIL, 4/0 GND 420 140 8 HVP-18 XF-49 X VA SUPPLIED CABLE
23 NC-CBL-15KV-023 3 - 250KCMIL, 4/0 GND 585 195 8 HVS-20
XF-2
BLDG-102 X VA SUPPLIED CABLE
24 NC-CBL-15KV-024 3 - 250KCMIL, 4/0 GND 1065 355 8 HVS-20 HVP-22A XF-CL1 X VA SUPPLIED CABLE 25 NC-CBL-15KV-025 3 - 250KCMIL, 4/0 GND 2205 735 10 HVS-24 HVP-40 X VA SUPPLIED CABLE 26 NC-CBL-15KV-026 3 - 250KCMIL, 4/0 GND 795 265 3 HVP-40 HVP-41 X VA SUPPLIED CABLE 27 NC-CBL-15KV-027 2 - 250KCMIL, 4/0 GND (A-B) 645 215 3 HVP-41 HVP-42 X VA SUPPLIED CABLE 29 NC-CBL-15KV-029 3 - 250KCMIL, 4/0 GND 350 117 5 HVP-41 HVS-41 X VA SUPPLIED CABLE 30 NC-CBL-15KV-030 2 - 250KCMIL, 4/0 GND (B-C) 567 189 5 HVP-42 XF-17 X VA SUPPLIED CABLE 31 NC-CBL-15KV-031 2 - 250KCMIL, 4/0 GND (A-B) 606 202 5 HVP-42 XF-19 PNL-19 X VA SUPPLIED CABLE 32 NC-CBL-15KV-032 3 - 250KCMIL, 4/0 GND 60 20 5 HVS-27 XF-27 X VA SUPPLIED CABLE 33 NC-CBL-15KV-033 3 - 250KCMIL, 4/0 GND 594 198 17 HVS-27 XF-6 X VA SUPPLIED CABLE 34 NC-CBL-15KV-034 3 - 250KCMIL, 4/0 GND 1089 363 20 HVP-29 HVP-30 X VA SUPPLIED CABLE 35 NC-CBL-15KV-035 3 - 250KCMIL, 4/0 GND 90 30 14 HVP-29 XF-5 X VA SUPPLIED CABLE 36 NC-CBL-15KV-036 3 - 250KCMIL, 4/0 GND 90 30 14 HVP-30 XF-11 X VA SUPPLIED CABLE 37 NC-CBL-15KV-037 3 - 250KCMIL, 4/0 GND 261 87 14 HVP-30 XF-7 X VA SUPPLIED CABLE 38 NC-CBL-15KV-038 3 - 250KCMIL, 4/0 GND 552 184 17 HVS-31 XF-3 X VA SUPPLIED CABLE 39 NC-CBL-15KV-039 3 - 250KCMIL, 4/0 GND 552 184 20 HVS-31 XF-4 X VA SUPPLIED CABLE 40 NC-CBL-15KV-040 3 - 250KCMIL, 4/0 GND 93 31 14 HVP-34 XF-1 X VA SUPPLIED CABLE 41 NC-CBL-15KV-041 3 - 250KCMIL, 4/0 GND 180 60 14 HVP-36 XF-36 X VA SUPPLIED CABLE 42 NC-CBL-15KV-042 3 - 250KCMIL, 4/0 GND 735 245 15 HVP-36 XF-97 X VA SUPPLIED CABLE 43 NC-CBL-15KV-043 3 - 250KCMIL, 4/0 GND 732 244 15 HVP-36 XF-108 X VA SUPPLIED CABLE 44 NC-CBL-15KV-044 3 - 250KCMIL, 4/0 GND 96 32 15 HVP-36 XF-20 X VA SUPPLIED CABLE 45 NC-CBL-15KV-045 3 - 250KCMIL, 4/0 GND 1650 550 11 HVS-12 HVS-146 X VA SUPPLIED CABLE 47 NC-CBL-15KV-047 3 - 250KCMIL, 4/0 GND 600 200 14 HVS-2 XF-1301 X VA SUPPLIED CABLE
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL SCHEDULES BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES602
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.
MEDIUM VOLTAGE TRANSFORMER SCHEDULE
EQUIPMENT
TAG BUILDING KVA SIZE VOLTAGE PHASE MANUF.
DATE AGE (YR) ACTION
NOTES
KEEP REPLACE REMOVE NEW
XF-001 1 75 13.2KV - 208/120 3 1/1/1988 37 X BUILDING IS ON WE ENERGIES
REPLACE WITH COOPER/EATON CA202003EN
XF-002 2 500 13.2KV - 208/120 3 1/1/1983 42 X BUILDING IS ON WE ENERGIES
XF-003 3&4 225 13.2KV - 208/120 3 1/1/2005 20 X REPLACE WITH COOPER/EATON CA202003EN XF-004 5 225 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN XF-005 5 300 13.2KV - 208/120 3 1/1/1992 33 X REPLACE WITH COOPER/EATON CA202003EN XF-006 6 1000 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN XF-007 7 500 13.2KV - 208/120 3 1/1/1993 32 X REPLACE WITH COOPER/EATON CA202003EN XF-011 11 50 13.2KV - 240/120 1 1/1/2021 4 X REPLACE WITH COOPER/EATON CA201002EN
XF-012 12 75 13.2KV - 208/120 3 1/1/1988 37 X
XF-014 14ST LIGHTS 37.5 13.2KV - 240/120 1 1/1/1988 37 X
XF-016 GARAGE 50 13.2KV - 208/120 3 1/1/1988 37 X
XF-017 17ST LIGHTS 75 13.2KV - 240/120 1 8/29/2015 10 X
XF-019 18&19ST LIGHTS 75 13.2KV - 240/120 1 1/1/1988 37 X
TRANSFORMER IS REPLACED AND MOVED TO A NEW
LOCATION
REPLACE WITH COOPER/EATON CA201002EN
XF-020 20 112.5 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN
XF-027 ST LIGHTS 75 13.2KV - 208/120 3 1/1/1997 28 X PAD SHOWS SIGNS OF SINKING
REPLACE WITH COOPER/EATON CA202003EN
XF-036 PNL 2V 75 13.2KV - 208/120 3 1/1/1997 28 X REPLACE WITH COOPER/EATON CA202003EN XF-039 ST LIGHTS 37.5 13.2KV - 240/120 1 1/1/2021 4 X REPLACE WITH COOPER/EATON CA201002EN
XF-041 (HVP-41) 16ST LIGHTS 75 13.2KV - 208/120 3 1/1/1997 28 X BUILDING IS ON WE ENERGIES
XF-041 (HVP-8) 41 (VACANT) 225 13.2KV - 208/120 3 1/1/1988 37 X
XF-043 43 750 13.2KV - 480/277 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN
XF-049 49 GARAGE 75 13.2KV - 240/120 1 1/1/1988 37 X BUILDING IS ON WE ENERGIES
REPLACE WITH COOPER/EATON CA201002EN
XF-062 62, 18 &19ST LIGHTS 75 13.2KV - 240/120 1 1/1/1988 37 X BUILDING IS ON WE ENERGIES XF-097 99,T105,T106, T1 75 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN
XF-102 102 750 13.2KV - 208/120 3 1/1/2008 17 X
XF-108 107/108 112.5 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN
XF-112 112 500/560 13.2KV - 480/277 3 1/1/2013 12 X
XF-119 119&150 225 13.2KV - 208/120 3 1/1/2014 11 X
XF-1301 1301 112.5 13.2KV - 208/120 3 1/1/1993 32 X REPLACE WITH COOPER/EATON CA202003EN
XF-146 146 225 13.2KV - 208/120 3 1/1/2013 12 X
XF-147 147 225 13.2KV - 208/120 3 1/1/2015 10 X
XF-148 148 225 13.2KV - 208/120 3 1/1/2015 10 X
XF-CL1 CRASH LAB 750 13.2KV - 480/277 3 1/1/1998 27 X REPLACE WITH COOPER/EATON CA202003EN XF-K ST LIGHTS, PUMPS 37.5 13.2KV - 240/120 1 1/1/2020 5 X REPLACE WITH COOPER/EATON CA201002EN
XF-MP-FDS 57 7.5 120/240 - 480/240 1 UNKNOWN UNKNOWN X CEMETERY GAZEBO AND LIGHTS XF-SL1 PARKING GARAGES 37.5 13.2KV - 120/240 1 UNKNOWN UNKNOWN X REPLACE WITH COOPER/EATON CA201002EN
MEDIUM VOLTAGE PEDESTAL SCHEDULE
EQUIPMENT TAG MANUF. DATE AGE (YR) PAD DIMENSIONS PAD CONDITION ACTION
NOTES
WIDTH DEPTH REPAIR REPLACE KEEP REPLACE REMOVE NEW
HVP-002 NA 62" 59" X USED AS A PASS-THROUGH
HVP-003 NA 62" 59" X REPLACED WITH AN HVS
HVP-004 NA 62" 59" X
HVP-008 NA 62" 59" X
HVP-011 NA 62" 59" X USED AS A PASS-THROUGH
HVP-015 NA 62" 59" X
HVP-016 NA 62" 59" X USED AS A PASS-THROUGH
HVP-018 NA 62" 59" X
HVP-020 NA 62" 59" X USED AS A PASS-THROUGH
HVP-022 NA 62" 59" X USED AS A PASS-THROUGH
HVP-023 NA 62" 59" X USED AS A PASS-THROUGH
HVP-024 NA 62" 59" X REPLACED WITH AN HVS
HVP-027 NA 62" 59" X REPLACED WITH AN HVS
HVP-029 NA 62" 59" X
HVP-030 NA 62" 59" X
HVP-031 NA 62" 59" X REPLACED WITH AN HVS
HVP-034 NA 62" 59" X
HVP-036 NA 62" 59" X
HVP-040 NA 62" 59" X
HVP-041 NA 62" 59" X
HVP-042 NA 62" 59" X
HVP-044 NA 62" 59" X
HVP-K NA 62" 59" X USED AS A PASS-THROUGH
LOW VOLTAGE PANEL SCHEDULE
EQUIPMENT
TAG MANUF. DATE AGE (YR)
PAD CONDITION ACTION
NOTES
KEEP REPAIR/
REPLACE KEEP REPLACE REMOVE NEW
107/108-DS-A NA X X DOES NOT EXIST, LOCAL
DISCONNECT LOCATED IN PLACE
PNL-001 12/1/1988 36 X X
PNL-002V 2/3/1998 27 X X
PNL-003 X X
PNL-011 NA X X
PNL-014 NA X X
PNL-016 7/1/1988 37 X X
PNL-017 NA X X
PNL-019 NA X X PANEL IS REPLACED AND MOVED TO
A NEW LOCATION
PNL-027 2/3/1998 27 X X PANEL AND TRANSFORMER PAD
SHOWS SIGNS OF SINKING
PNL-039 NA X X
PNL-041 2/3/1998 27 X X
PNL-049 NA X X
PNL-062 NA X X
PNL-CLC NA X X
PNL-K NA X X
PNL-SL1 NA X X
MEDIUM VOLTAGE SWITCH SCHEDULE
EQUIPMENT
TAG MANUF. DATE AGE (YR)
PAD
DIMENSIONS ACTION NOTES
WIDTH DEPTH REPAIR REPLACE KEEP REPLACE REMOVE NEW
HVS-001/HVS-A 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH
HVS-002(1301) 7/1/1993 32 62" 74" X REPLACE WITH EATON/COOPER POWER
MOST-6
HVS-004 5/1/2016 9 62" 74" X USED AS A PASS-THROUGH HVP-4A
HVS-011 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH HVP-11A
HVS-016 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH HVP-16A
HVS-018 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH HVP-18A
HVS-020 3/1/1988 37 62" 74" X REPLACE WITH EATON/COOPER POWER
MOST-6
HVS-022 9/1/1998 27 75" 69" X USED AS A PASS-THROUGH HVP-22A
HVS-023A 3/1/2017 8 72" 40" X USED AS A PASS-THROUGH HVP-23A
HVS-023B 3/1/2017 8 72" 40" X
HVS-036 11/1/1997 27 67" 60.5" X
HVS-041 11/1/1997 27 67" 60.5" X USED AS PASS-THROUGH HVS-41A
HVS-146 5/1/2013 12 - - X NEW SWITCH, NO NEED TO REPLACE
HVS-147 10/1/2015 9 - - X NEW SWITCH, NO NEED TO REPLACE
HVS-148 10/1/2015 9 - - X NEW SWITCH, NO NEED TO REPLACE
HVS-SL1 3/1/1996 29 58" 66" X REPLACE WITH EATON/COOPER POWER
MOST-9
HVS-003 62" 59" X EATON/COOPER POWER MOST-6
HVS-012 62" 74" X REPLACE WITH EATON/COOPER POWER
MOST-9. INSTALL VAULT FOR HVS.
HVS-024 62" 59" X REPLACE WITH EATON/COOPER POWER
MOST-6
HVS-027 62" 59" X REPLACE WITH EATON/COOPER POWER
MOST-9
HVS-031 62" 59" X REPLACE WITH EATON/COOPER POWER
MOST-9
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL SCHEDULES BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES603
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
GOVERNMENT FURNISHED EQUIPMENT SCHEDULE
ITEM DESCRIPTION QTY SUPPLIER MANUFACTURER CATALOG
NUMBER NOTES
COLD SHRINK TERMINATION KIT 4 WERNER ELECTRIC SUPPLY 3M 7693-S-4
250KCMIL LONG BARREL COPPER LUG 1/2IN STUD TWO-HOLE
COMPLETION TYPE 12 WERNER ELECTRIC SUPPLY PANDUIT LCC250-12-X
LOAD BREAK ELBOW WITH TEST POINT AND SHIELD ADAPTER 55 WERNER ELECTRIC SUPPLY CPS LE215CC09T-SA2
2-WAYDEADBREAK SPLICE WITH TEST POINT, COMPRESSION
CONNECTORS, CABLE ADAPTERS, AND SHIELD ADAPTER 26 WERNER ELECTRIC SUPPLY CPS SSPL625CC16A2T-SA2
3-WAY DEAD BREAK SPLICE WITH TEST POINT, COMPRESSION
CONNECTORS, CABLE ADAPTERS, AND SHIELD ADAPTER 48 WERNER ELECTRIC SUPPLY CPS SSPL625CC16A3T-SA2
4-WAY DEAD BREAK SPLICE WITH TEST POINT, COMPRESSION
CONNECTORS, CABLE ADAPTERS, AND SHIELD ADAPTER 21 WERNER ELECTRIC SUPPLY CPS SSPL625CC16A4T-SA2
DEAD BREAK DEAD-END KIT WITH TEST POINT AND SHIELD ADAPTER 33 WERNER ELECTRIC SUPPLY CPS BT625CC16A1T-SA2+DI P625A
CABLE CAPS FOR FIELD INSTALL AFTER PULLING BUT BEFORE
TERMINATING 300 WERNER ELECTRIC SUPPLY ALR 766749-000 VERIFY WITH COR THAT ITEMS ARE STORED ON SITE READY FOR USE ON
PROJECT
GREEN 4/0 XHHW GROUNDING WIRE 14225 WERNER ELECTRIC SUPPLY SOUTHWIRE SIMpull CH-XHHW VERIFY WITH COR THAT ITEMS ARE STORED ON SITE READY FOR USE ON
PROJECT
GOVERNMENT FURNISHED EQUIPMENT - MEDIUM VOLTAGE CABLE
REEL NO. QTY
(FT)
AVAILABLE
LENGTH
(FT)
SUPPLIER MANUFACTURER CATALOG
NO.
CONDUCT
OR SIZE
(KCMIL)
APPROXIMATE
O.D. (IN)
AMPACITY
UNDERGROUND
DUCT BANK
NOTES
1 2190 730 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
2 2190 730 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
3 1599 533 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
4 1599 533 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
5 1965 655 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
6 1965 655 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
7 1527 509 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
8 2097 699 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
9 2205 735 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
10 2217 739 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
11 1737 579 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
12 1557 519 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
13 1551 517 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
14 1632 544 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
15 1623 541 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
16 1803 601 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
17 1980 651 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
18 1860 620 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
19 1530 510 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
20 1683 561 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
21 1683 561 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
22 1662 554 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.
BRANCH PANEL: PNL-001
LOCATION: BUILDING 1 VOLTS: 208/120 A.I.C RATING: 10000
SUPPLY FROM: XF-1 PHASE: 3 MAINS TYPE: MCB
MOUNTING: CLOSE COUPLED WIRES: 4 MAINS RATING: 400A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 225A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
FOUNTAIN 20 A 2
1664.00 VA 1919.15 VA
3 20 A STEET LIGHTS
3 1664.00 VA 1919.15 VA 4
5 SPARE 20 A 1 0000.00 VA 1919.15 VA 6
7 PHOTOCELL/ COIL 20 A 1 1920.00 VA 0000.00 VA 1 20 A SPARE 8
9 UNKNOWN 20 A 1 1920.00 VA 0000.00 VA 1 20 A SPARE 10
SPARE 20 A 3
0000.00 VA 0000.00 VA
3 20 A SPARE
13 0000.00 VA 0000.00 VA 14
15 0000.00 VA 0000.00 VA 16
SPARE 20 A 2
0000.00 VA 0000.00 VA
2 20 A SPARE
19 0000.00 VA 0000.00 VA 20
21 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 22
23 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 24
25 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 26
27 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 28
29 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 30
TOTAL LOAD: 5503.15 VA 5503.15 VA 1919.15 VA
TOTAL AMPS: 0045.86 A 0045.86 A 0015.99 A
BRANCH PANEL: PNL-002V
LOCATION: BUILDING 20 VOLTS: 208/120 A.I.C RATING: 10000
SUPPLY FROM: XF-36 PHASE: 3 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 4 MAINS RATING: 250 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 250 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
1 COIL & PHOTOCELL 20 A 1 1920.00 VA 1919.15 VA
3 20 A STREET LIGHTS
POLES 68-73
STREET LIGHTS
POLES 74-81 20 A 3
1919.15 VA 1919.15 VA 4
5 1919.15 VA 1919.15 VA 6
7 1919.15 VA 0000.00 VA
3 20 A SPARE
SPARE 20 A 3
0000.00 VA 0000.00 VA 10
11 0000.00 VA 0000.00 VA 12
13 0000.00 VA 0000.00 VA
3 20 A SPARE
SPARE 20 A 3
0000.00 VA 0000.00 VA 16
17 0000.00 VA 0000.00 VA 18
19 0000.00 VA 0000.00 VA
2 20 A SPARE
SPARE 20 A 2
0000.00 VA 0000.00 VA 22
23 0000.00 VA 0000.00 VA
2 20 A SPARE
SPARE 20 A 2
0000.00 VA 0000.00 VA 26
27 0000.00 VA 0000.00 VA 1 20 A SPARE 28
29 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 30
31 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 32
33 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 34
35 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 36
37 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 38
39 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 40
41 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 42
TOTAL LOAD: 5758.30 VA 3838.30 VA 3838.30 VA
TOTAL AMPS: 0047.99 A 0031.99 A 0031.99 A
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.
3. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.
4. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.
5. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS.
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
ELECTRICAL SCHEDULES BID DOCUMENTS
UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES604
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
BRANCH PANEL: PNL-027
LOCATION: BLDG 6 / HANK ARRON TRAIL VOLTS: 208/120 A.I.C RATING: 10000
SUPPLY FROM: XF-27 PHASE: 3 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 4 MAINS RATING: 250 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 250 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
1 COIL & PHOTOCELL 20 A 1 1920.00 VA 0000.00 VA
3 20 A SPARE
3 STREET LIGHTING 20 A 1 1920.00 VA 0000.00 VA 4
5 STREET LIGHTING 20 A 1 1920.00 VA 0000.00 VA 6
7 STREET LIGHTING 20 A 1 1920.00 VA 0000.00 VA
3 20 A SPARE
9 SPARE 20 A 1 0000.00 VA 0000.00 VA 10
11 SPARE 20 A 1 0000.00 VA 0000.00 VA 12
13 SPARE 20 A 1 0000.00 VA 0000.00 VA
2 20 A SPARE
15 SPARE 20 A 1 0000.00 VA 0000.00 VA 16
17 SPARE 20 A 1 0000.00 VA 0000.00 VA
2 20 A SPARE
19 SPARE 20 A 1 0000.00 VA 0000.00 VA 20
21 SPARE 20 A 1 0000.00 VA 0000.00 VA
2 20 A SPARE
23 SPARE 20 A 1 0000.00 VA 0000.00 VA 24
25 SPARE 20 A 1 0000.00 VA 0000.00 VA
3 20 A SPARE
27 SPARE 20 A 1 0000.00 VA 0000.00 VA 28
29 SPARE 20 A 1 0000.00 VA 0000.00 VA 30
TOTAL LOAD: 3840.00 VA 1920.00 VA 1920.00 VA
TOTAL AMPS: 0032.00 A 0016.00 A 0016.00 A
BRANCH PANEL: PNL-039
LOCATION: BUILDING 39 VOLTS: 240/120 A.I.C. RATING: 10000
SUPPLY FROM: XF-39 PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 400 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 400 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
STREET LIGHTS 20 A 2
1920.00 VA 1920.00 VA
2 20 A STREET LIGHTS
3 1920.00 VA 1920.00 VA 4
STREET LIGHTS 20 A 2
1920.00 VA 2880.00 VA
2 30 A SHED / PHOTOCELL
7 1920.00 VA 2880.00 VA 8
SPARE 20 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 10
11 0000.00 VA 0000.00 VA 1 20 A SPARE 12
SPARE 20 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 14
15 0000.00 VA 0000.00 VA 1 20 A SPARE 16
SPARE 20 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 18
19 0000.00 VA 0000.00 VA 1 20 A SPARE 20
SPARE 20 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 22
23 0000.00 VA 0000.00 VA 1 20 A SPARE 24
TOTAL LOAD: 8640.00 VA 8640.00 VA
TOTAL AMPS: 0072.00 A 0072.00 A
BRANCH PANEL: PNL-CLC
LOCATION: CLC LOOP VOLTS: 208/120 A.I.C. RATING: 10000
SUPPLY FROM: XF-146 PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 100 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 100 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
1 NORTH POLE LIGHTS 20 A 1 1 20 A SPARE 2
3 SPARE 20 A 1 1 20 A WEST POLE LIGHTS 4
5 CIRCLE DR POLE LIGHTS 20 A 1 1 20 A POLE LIGHTS BY XMFR 6
7 SPARE 20 A 1 1 20 A SPARE 8
FLAG POLE LIGHTS 20 A 2
1 20 A PHOTOCELL 10
11 1 20 A RECEPTICAL 12
13 SPARE 20 A 1
2 20 A SPARE
15 SPARE 20 A 1 16
17 SPARE 20 A 1
2 20 A SPARE
19 SPARE 20 A 1 20
21 SPARE 20 A 1
2 20 A SPARE
23 SPARE 20 A 1 24
TOTAL LOAD: 0000.00 VA 0000.00 VA
TOTAL AMPS: 0000.00 A 0000.00 A
BRANCH PANEL: PNL-K
LOCATION: HVS-SL1 VOLTS: 240/120 A.I.C RATING: 10000
SUPPLY FROM: XF-K PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 200 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 200 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
STREET LIGHTS 30 A 2
2880.00 VA 2880.00 VA
2 30 A FISHER HOUSE
3 2880.00 VA 2880.00 VA 4
SOUTH SIDE OF 43 30 A 2
2880.00 VA 2880.00 VA
2 30 A FISHER HOUSE
7 2880.00 VA 2880.00 VA 8
9 STEAM MH REC. 20 A 1 1920.00 VA 1920.00 VA 1 20 A MH 1 REC 10
11 ISLAND REC. 20 A 1 1920.00 VA 1920.00 VA 1 20 A POND 12
13 POND 20 A 1 1920.00 VA 0000.00 VA 1 20 A SPARE 14
SPARE 30 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 16
17 0000.00 VA 0000.00 VA 1 20 A SPARE 18
SPARE 30 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 20
21 0000.00 VA 0000.00 VA 1 20 A SPARE 22
SPARE 30 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 24
25 0000.00 VA 0000.00 VA 1 20 A SPARE 26
SPARE 30 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 28
29 0000.00 VA 0000.00 VA 1 20 A SPARE 30
TOTAL LOAD: 17280.00 VA 15360.00 VA
TOTAL AMPS: 0144.00 A 0128.00 A
BRANCH PANEL: PNL-SL1
LOCATION: BUILDING 152 VOLTS: 240/120 A.I.C RATING: 10000
SUPPLY FROM: XF-SL1 PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 225 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 225 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
SPARE 30 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 2
3 0000.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #1
5 LOT 35 GATE 20 A 1 1920.00 VA 1920.00 VA 6
BUS SHELTER HEATER 20 A 2
1920.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #2
9 1920.00 VA 1920.00 VA 10
STREET LIGHT CIRCUIT #8 LOT 35 20 A 2
1920.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #3
13 1920.00 VA 1920.00 VA 14
15 SPARE 20 A 1 0000.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #4
17 SPARE 20 A 1 0000.00 VA 1920.00 VA 18
19 TALK-A-PHONES 20 A 1 1920.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #5
21 GATES/CTRLS DR. LOT 20 A 1 1920.00 VA 1920.00 VA 22
23 LIGHTING CONTACTOR 20 A 1 1920.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #6
25 SPARE 20 A 1 0000.00 VA 1920.00 VA 26
27 NORTH GATES 20 A 1 1920.00 VA 1920.00 VA
2 20 A STREET LIGHT CIRCUIT #7 LOT 35
29 SPARE 20 A 1 0000.00 VA 1920.00 VA 30
TOTAL LOAD: 21120.00 VA 23040.00 VA
TOTAL AMPS: 0176.00 A 0192.00 A
BRANCH PANEL: PNL-019
LOCATION: MH-43 VOLTS: 240/120 A.I.C. RATING: 10000
SUPPLY FROM: XF-19 PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 400 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 400 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
1 SPARE 40 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 2
3 SPARE 20 A 1 0000.00 VA 0000.00 VA
2 70 A SPARE
5 SPARE 20 A 1 0000.00 VA 0000.00 VA 6
7 COIL & PHOTOCELL 20 A 1 1920.00 VA 5760.00 VA
2 60 A PNL - OUTDOOR SERVICE NORTH LOT
9 STREET LIGHTING NORTH
12-14, 21, 21A, 22 20 A 2
1920.00 VA 5760.00 VA 10
11 1920.00 VA 0000.00 VA
2 200 A SPARE
13 STREET LIGHTING SOUTH
15-20, 23-28 20 A 2
1920.00 VA 0000.00 VA 14
15 1920.00 VA 0000.00 VA
2 200 A SPARE
17 SPARE 20 A 1 0000.00 VA 0000.00 VA 18
SPARE 60 A 2
0000.00 VA 0000.00 VA
2 60 A SPARE
21 0000.00 VA 0000.00 VA 22
23 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 24
TOTAL LOAD: 9600.00 VA 11520.00 VA
TOTAL AMPS: 0080.00 A 0096.00 A
BRANCH PANEL: PNL-011
LOCATION: BUILDING 11 VOLTS: 240/120 A.I.C RATING: 10000
SUPPLY FROM: XF-11 PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 400 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 400 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
EAST BUILDING 11 225 A 2
21600.00 VA 21600.00 VA
2 225 A WEST BUILDING 11
3 21600.00 VA 21600.00 VA 4
PARKING LOT LIGHTS 15 A 2
1440.00 VA 1920.00 VA 1 20 A PANEL GFCI 6
7 1440.00 VA 0000.00 VA 1 20 A SPARE 8
SPARE 20 A 2
0000.00 VA 0000.00 VA 1 15 A SPARE 10
11 0000.00 VA 0000.00 VA 1 15 A SPARE 12
SPARE 15 A 2
0000.00 VA 0000.00 VA 1 15 A SPARE 14
15 0000.00 VA 0000.00 VA 1 15 A SPARE 16
SPARE 15 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 18
19 0000.00 VA 0000.00 VA 1 20 A SPARE 20
SPARE 20 A 2
0000.00 VA 0000.00 VA 1 20 A SPARE 22
23 0000.00 VA 0000.00 VA 1 20 A SPARE 24
TOTAL LOAD: 46560.00 VA 44640.00 VA
TOTAL AMPS: 0388.00 A 0372.00 A
BRANCH PANEL: PNL-017
LOCATION: BUILDING 17 VOLTS: 240/120 A.I.C. RATING: 14000
SUPPLY FROM: XF-17 PHASE: 1 MAINS TYPE: MCB
MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 200 A
ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 200 A
NOTES:
CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT
1 SPARE 20 A 1 0000.00 VA 1920.00 VA 1 20 A COIL/ PHOTOCELL 2
SURGE PROTECTOR 30 A 2
2880.00 VA 1920.00 VA 1 20 A SIGNS AND GFI 4
5 2880.00 VA 3840.00 VA
2 40 A STREET LIGHTS
XF-MP-FDS 40 A 2
3840.00 VA 3840.00 VA 8
9 3840.00 VA 0000.00 VA
2 20 A SPARE
SPARE 30 A 2
0000.00 VA 0000.00 VA 12
13 0000.00 VA 0000.00 VA
2 30 A SPARE
SPARE 20 A 2
0000.00 VA 0000.00 VA 16
17 0000.00 VA 0000.00 VA 1 20 A SPARE 18
19 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 20
21 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 22
23 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 24
TOTAL LOAD: 12480.00 VA 12480.00 VA
TOTAL AMPS: 0104.00 A 0104.00 A
GENERAL NOTES
1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.
2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.
3. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.
4. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.
5. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS.
Exp.: 12/31/2028
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
K2 K2 OPEN
CLOSED
K1 K2
K2 K1
K2 K1
LOAD BREAK FUSES
LOOP LOAD BREAK SWITCHES
K2HVS-SL1 HVS-2 HVS-3 HVS-20 HVS-24 HVS-12HVS-31
TIE
SE-4B
WE H-69165
NW-4A
WE H-3257
13.2 KV 13.2 KV
N.C. N.C.
HVS-27
N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.O. N.C. N.C. N.C. N.C.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
23 MECHANIC STREET, SPRINGVILLE, NY 14141
KIRK KEY INFORMATION BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM
VOLTAGE FEEDER CLEMENT J.
ZABLOCKI VAMC
5000 W. NATIONAL AVE.
MILWAUKEE, WI 53295
2025/10/09
ES605
SITE
695-22-123
CJR DAK
REV 0 - BID DOCUMENTS 2025-10-09
"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".
CERTIFICATE OF AUTHORIZATION NUMBER: 0020000
GENERAL NOTES
1. DANGER - ELECTRICAL HAZARD. ENSURE THE SYSTEM IS ELECTRICALLY ISOLATED AND
THAT NO HAZARDOUS VOLTAGES ARE PRESENT BEFORE PERFORMING MAINTENANCE
WORK WITHIN ENCLOSURES.
2. FOR A COMPLETE LIST OF DANGERS AND HAZARDS PLEASE CONSULT THE APPROPRIATE
SUPPLIER'S EQUIPMENT MAINTENANCE, INSTALLATION, AND OPERATION MANUAL(S)
SUPPLIED WITH THE EQUIPMENT.
3. THERE ARE A TOTAL OF 8 KIRK KEYED SWITCHES BEING…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .