S02 - 695-22-123 Drawings Part 4 of 4.pdf

PDF 15 MB Posted

Attached to
Z1DZ--695-22-123 Upgrade N Campus Medium Voltage Feeders
Solicitation number
36C25226B0023
Issued by

About this file

These are electrical construction bid documents for the U.S. Department of Veterans Affairs' Clement J. Zablocki VAMC in Milwaukee, Wisconsin, specifically for the Upgrade North Campus Medium Voltage Feeder project (Project Number 695-22-123). The documents include comprehensive electrical site plans, electrical details, feeder schedules, equipment schedules, grounding plans, Kirk key interlock information, and a single-line diagram for the proposed electrical system upgrades. The work involves installation of new medium voltage (15kV) cable feeders, ductbank systems, electrical switches (HVP/HVS), transformers, panels, and associated infrastructure across five electrical zones covering the north campus area. The project includes replacement of aging equipment with new Cooper/Eaton switches and transformers, installation of cable vault details at Building 115, grounding and bonding systems, and Kirk key interlocked switches (HVS-SL1, HVS-2, HVS-3, HVS-12, HVS-20, HVS-24, HVS-27, and HVS-31) to prevent backfeeding throughout distribution loops. The drawings specify cable schedules with 250 kcmil conductors, equipment specifications including 15kV rated components, manhole details for underground construction, and detailed installation procedures for ductbank, cable carriers, and grounding configurations. The issue date is October 9, 2025, with drawings sealed by a New York-based licensed professional engineer.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T105

XF-97

XF-36

RED ARROW CIR

W

OR

KS

HO

P

RO

AD

BARRON CT

WOOD AVE

XF-108

MH-37

107/108-DS-A

MH-38

XF-39

MH-10

PNL-2V

MH-36B

HANK AARON TRAIL BRIDGE

E

E

E

E

E

E

E

T106

T107

MH-36A

MH-36

HVP-36A

HVP-11A PNL-39

HVP-11

MH-11

XF-20

HVP-36

1538 3589

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL - ZONE 3 BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES403

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ES501 FOR ELECTRICAL DETAILS

3. SEE ES601 FOR CABLE SCHEDULE

4. SEE ES602 & ES603 FOR EQUIPMENT SCHEDULES.

5. SEE ES605 FOR KIRK KEY INFORMATION

6. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.

7. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS

8. THIS DRAWING IS DIAGRAMMATIC IN NATURE ONLY. SEE CU101 FOR ACTUAL SITE

SURVEY AND TRUE LOCATIONS OF UTILITY LINES.

SCALE: 1" = 60'

ELECTRICAL - ZONE 31

N

ZONE 5 1/ES405

MATCHLINE

ZO

NE

1/E

S4

MA

TC

HL

IN

E

SITE PROPOSED LINETYPES

MATCHLINE

EXISTING DUCT BANK AND NEW CABLE

EXISTING LOW VOLTAGE DUCT BANK

NEW DUCT BANK / CABLE / EQUIPMENT

- POWER DISTRIBUTION SWITCH (HVP OR HVS)

- TRANSFORMER (XF)

- ELECTRICAL PANEL (PNL)

- UTILITY, ELECTRICAL MANHOLE (MH)

SITE PLAN SYMBOL LEGEND

E

BUILDING FED FROM WE ENERGIES

BUILDING FED FROM VA

- LIGHT POLE / STREET LIGHT

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

HVP-K

HVP-15

LINCOLN DR

HI

NE

S

BL

VD

FLOWER DR

HINES BLV

D

HVP-16

XF-102

BCL

XF-43

XF-119

MH-47A

MH-2B

MH-2A

MH

MH-15

PNL-K

MH-47

XF-1301

MH-21

Cemetery National Wood

Wheeler Lake

E

E

E

E

E

E

E

E

E

HVS-SL1

MH-3

GENERAL MITCHELL BLVD

HVP-2

E

HVS-3

HVS-A

XF-K

HVS-2

HVP-16A

MH-2

EMH-12E

MH-12D

265126552674

30493050

E

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL - ZONE 4 BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES404

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

SCALE: 1" = 60'

ELECTRICAL - ZONE 41

N

MA

TC

HL

IN

E

ZO

NE

1/E S4

MATCHLINE

ZONE 2 1/ES402

SITE PROPOSED LINETYPES

MATCHLINE

EXISTING DUCT BANK AND NEW CABLE

NEW DUCT BANK/CABLE/EQUIPMENT

EXISTING LOW VOLTAGE DUCT BANK

- POWER DISTRIBUTION SWITCH (HVP OR HVS)

- TRANSFORMER (XF)

- ELECTRICAL PANEL (PNL)

- UTILITY, ELECTRICAL MANHOLE (MH)

SITE PLAN SYMBOL LEGEND

E

BUILDING FED FROM WE ENERGIES

BUILDING FED FROM VA

- LIGHT POLE / STREET LIGHT

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ES501 FOR ELECTRICAL DETAILS

3. SEE ES601 FOR CABLE SCHEDULE

4. SEE ES602 & ES603 FOR EQUIPMENT SCHEDULES.

5. SEE ES605 FOR KIRK KEY INFORMATION

6. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.

7. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS

8. THIS DRAWING IS DIAGRAMMATIC IN NATURE ONLY. SEE CU101 FOR ACTUAL SITE

SURVEY AND TRUE LOCATIONS OF UTILITY LINES.

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

GENERAL MITCHELL BLVD

BARRON CT

HVS-146

XF-146

CB-100-CLC

CB-600-146

HVS-147

XF-147

CB-600-147

CB-600-148

XF-148

HVS-148

MH-13 MH-13A

PNL-CLC

E

E

E

E

XF-SL1

PNL-SL1

E

MH-12

HVS-12

MH-12B

HVP-11

WAREHOUSE WAY

E MH-12A

E MH-12C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL - ZONE 5 BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES405

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

- POWER DISTRIBUTION SWITCH (HVP OR HVS)

- TRANSFORMER (XF)

- ELECTRICAL PANEL (PNL)

- MANHOLE (MH)

SITE PLAN SYMBOL LEGEND

SCALE: 1" = 60'

ELECTRICAL - ZONE 51

N

E

MATCH LINE

ZONE 3 1/ES403

MA

TC

H

LIN

E

ZO

NE

1/E S4

SITE PROPOSED LINETYPES

MATCHLINE

EXISTING DUCT BANK AND NEW CABLE

NEW DUCT BANK

EXISTING LOW VOLTAGE DUCT BANK

- STREETLIGHT / LIGHT POLE

- BUILDING POWERED BY WE ENERGIES

- BUILDING POWERED BY VA

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ES501 FOR ELECTRICAL DETAILS

3. SEE ES601 FOR CABLE SCHEDULE

4. SEE ES602 & ES603 FOR EQUIPMENT SCHEDULES.

5. SEE ES605 FOR KIRK KEY INFORMATION

6. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.

7. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS

8. THIS DRAWING IS DIAGRAMMATIC IN NATURE ONLY. SEE CU101 FOR ACTUAL SITE

SURVEY AND TRUE LOCATIONS OF UTILITY LINES.

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DETECTABLE WARNING

TAPE

CAST-IN-PLACE

CONCRETE ENCASEMENT

SECURE TOP SPACER

TO PREVENT CONDUITS FROM

FLOATING DURING CONCRETE POUR

4" DUCTBANK CONDUITS

TYP

PLASTIC CODUIT

SPACERS / SUPPORTS

CONCRETE PAVERS FOR

LEVELING

UNDISTURBED EARTH3" 3"

3 5 /16

3"

3"

6" MI

NI

MU

M

BE

LO

W G

RA

DE

INSTALL #4 REBAR

TYPICAL

FLOAT CONTACT AREA

(2 PLACES REQUIRED)

OPENING FOR OPTIONAL 1/2"

CABLE TO STABILIZE DUCT

BANK DURING INSTALLATION

(2 REQUIRED AS SHOWN)

2" DIAMETER

WHEEL ASSEMBLY

SECURE CONDUITS TO BORE SPACERS SLOT IS CHAMFERED .312" x 22.5° ON ONE

SIDE OF BORE SPACER TO AID IN THE

WITHDRAWAL OF GROUT INJECTION PIPE.

NOTES:

1. USE ONE BORE SPACER FOR EVERY 5 FEET OF DUCT BANK.

2. THE CASING ID MUST BE SMOOTH AND FREE FROM RIDGES, PROJECTIONS AND

SEAMS THAT MIGHT IMPEDE THE ROLLING OF WHEELS

3. INSTALL BORE SPACERS PERPENDICULAR TO CONDUITS TO REDUCE THE

TENDENCY OF DUCT BANK TO CORKSCREW.

4. A THROUGH OR FEEDER BRIDGE SHOULD BE CONSTRUCTED AT THE LEADING

EDGE OF THE CASING TO SUPPORT SECTIONS OF DUCT BANK AS THEY ARE

ASSEMBLED AND PULLED INTO THE CASING.

5. IT IS ESSENTIAL THAT THE BORE SPACERS ARE HELD IN PLACE RELATIVE TO

THE CONDUIT.

6. THE DUCT BANK MUST BE HELD IN POSITION AT BOTH ENDS TO ACCOMMODATE

POSSIBLE UNEVEN THRUST LOADS THAT MAY BE GENERATED DURING THE

GROUTING OPERATION.

7. WHEN FILLING THE AREA BETWEEN THE CONDUITS AND CASING WITH GROUT,

TAKE CARE NOT TO EXCEED THE HYDRAULIC COLLAPSE PRESSURE OF THE

CONDUITS.

8. DETAILS PERTAIN TO JACK AND BORE AREAS. SEE CS401 AND CS402 FOR

ADDITIONAL INFORMATION.

FIRE TAPED FEEDER

BUNDLE (TYP)

ADJUSTABLE HEAVY

DUTY 20" LONG

FIBERGLASS ARM

(TYP)

60" ADJUSTABLE HEAVY

DUTY FIBERGLASS

STANCHIONS - MOUNTED

TO WALL

WALL

CABLE VAULT FLOOR

CABLE VAULT CEILING

USE CABLE TIE TO

ATTACH FIRE TAPED

FEEDER BUNDLE TO ARM

(TYP)

NOTE:

1. PROVIDE FIBERGLASS VERTICAL STANCHIONS AND

ARM SUPPORTS AT MAXIMUM SPACING OF 5'-0". REFER

TO CABLE MANUFACTURE'S RECOMMENDED SUPPORT

REQUIREMENTS.

2. FASTEN TO WALL WITH STAINLESS STEEL HARDWARE.

FIBERGLASS CHANNEL

MOUNTED TO CEILING

(TYP)

NOTE:

1. PROVIDE FIBERGLASS CHANNEL AND PORCELAIN CLAMP SUPPORTS AT

MAXIMUM SPACING OF 5'-0". REFER TO CABLE MANUFACTURE'S

RECOMMENDED SUPPORT REQUIREMENTS.

2. FASTEN TO CEILING WITH STAINLESS STEEL HARDWARE.

PORCELAIN CABLE

CHANNEL CLAMP (TYP)

FIRE TAPED FEEDER

BUNDLE (TYP)

8"

SECTION "A-A"

SECTION "B-B"

VA

RI

ES

5'-0"

6'-4"

8"

" M

IN

8"

5'-0"

8"

7'- 4"

3"

8'- 0"

8"

9'- 4"

8"

BB

3'- 0"3'-0"

NOTES:

1. VAULT LOADING: H-20 BRIDGE SPECIFICATIONS, NO OVERBURDEN.

2. MINIMUM ROOF AND WALL THICKNESS IS 6" EXCEPT FOR KNOCKOUT

WINDOWS.

3. GROUND ROD HOLES: 1" DIAMETER, 1 REQUIRED

4. PROVIDE FOUR (4) PULLING IRONS MADE FROM 78" GALVANIZED STEEL

BAR

5. PROVIDE 6" SUB-BASE LAYER OF WELL-TAMPED 1" CRUSHED BLUE

STONE BENEATH EACH VAULT

6. VAULTS SHALL BE ON A 12" LEVEL BED OF 90% COMPACTED GRANULAR

FILL, WELL GRADED FROM THE 1" SIEVE TO THE NO. 4 SIEVE,

GRANULAR FILL SHALL BE COMPACTED WITH A MINIMUM OF FOUR )4)

PASSES WITH A PLATE COMPACTOR

7. VAULT LID SHALL BE EFFECTIVELY BONDED TO THE VAULT GROUND

SYSTEM PER NEC

8. INCLUDE ALUMINUM LADDER (NOT SHOWN FOR CLARITY)

TOP VIEW

POWER

3'-2"

6'-4"

3'-2"

5'- 6"

3'-

9'- 4"

AA

GROUND ROD PER

SECTION 26 05 26.

GRAVEL SUMP

1 CUBIC YARD 3/4"

SUMP 12"

SUMP FRAME

& COVER

PULLING

IRON

FINISHED

GRADE

GRADE RINGS AS REQ'D TO

MATCH CIVIL FINISHED

GRADE ELEVATION.

CABLE

STANCHION

GROUND ROD

SLEEVE

PULLING

IRON

SUMP

12"x12"

SLOPE

SLOPE

SL

OP

E

CABLE STANCHION PER

SECTION 26 05 41.

CAST-IN-PLACE

CONCRETE ENCASEMENT

SECURE TOP SPACER

TO PREVENT CONDUITS FROM

FLOATING DURING CONCRETE POUR

4" DUCTBANK CONDUITS

TYP

PLASTIC CODUIT

SPACERS / SUPPORTS

CONCRETE PAVERS FOR

LEVELING

3" 3"

3 5 /16

3"

TOP OF EXISTING CONCRETE CULVERT

INSTALL #4 REBAR

TYPICAL

NO

MI

NA

L 1

6" V

IF

6" THK CONCRETE SIDEWALK

SEE CS501, DETAIL 7

AB

NOTES:

1. MANUFACTURE CAP FROM 14" CARBON STEEL.

2. WELD LIFTING EYES AT 4 CORNERS OF CAP.

3. REFERENCE SPECIFICATION 05 50 00 METAL FABRICATIONS FOR ADDITIONAL INFORMATION.

4. PAINT INSIDE AND OUTSIDE WITH 2-PART EPOXY PAINT 2 MILS THICK.

5. SEE PAINT SPECIFICATION 09 91 00 PAINTING FOR ADDITIONAL INFORMATION.

FRONT SIDE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

SITE ELECTRICAL DETAILS BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES501

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

SCALE: NTS

SITE ELECTRICAL DUCT BANK DETAIL1 SCALE: NTS

BORE CARRIER DETAIL2 SCALE: NTS

WALL CABLE CARRIER DETAIL3 SCALE: NTS

CEILING CABLE CARRIER DETAIL4

SCALE: NTS

TYPICAL MANHOLE DETAIL5 SCALE: NTS

SITE ELECTRICAL DUCT BANK AT CULVERT CROSSING DETAIL6

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.

3. SEE EG101 FOR GROUNDING SITE PLAN.

4. SEE EP101 FOR BUILDING 115 FLOOR PLAN.

5. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.

6. SEE SPECIFICATION 26 05 41 FOR UNDERGROUND ELECTRICAL CONSTRUCTION.

SCALE: NTS

PEDESTAL / VAULT COVER DETAIL7

Exp.: 12/31/2028

AutoCAD SHX Text

CONC. ENVELOPE

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T/FINISHED GRADE

OR FLOOR

APPROVED

BACKFILL

CAUTION-BUR

UTILITY WARNING

TAPE

RIGID METALLIC

CONDUIT RISER

RIGID METALLIC

COUPLING

CONCRETE

ENCASEMENT

RIGID METALLIC CONDUIT

ELBOW OR SWEEP

UNDISTURBED

SOIL

PVC-TO-RIGID

METALLIC COUPLING

UNLESS NOTED OTHERWISE,

SCHEDULE 40 PVC CONDUIT

RUN, ROUTE PER PLAN DRAWING

REFER TO ESD-318 FOR

ADDITIONAL CONCRETE ENCASED

DUCTBANK INFORMATION

T/CONCRETE

ENCASEMENT

SHALL BE RED

6" 4"

CT

CT

CT

BYZ CT

GROUND SHIELD WIRES

NOTES:

1. IF GROUND SENSOR CT IS USED, RETURN SHIELD WIRE VIA

CT AND THEN TO GROUND.

2. ALL STRESS CONES MUST BE AT THE SAME LEVEL IN ELEVATION

TO REDUCE DETERIORATION OF CABLE DUE TO CORONA.

NON-SHIELDED

FACTORY WIRING

CONDUIT

CABINET

STRESS CONE LOCATIONS

ALL AT SAME LEVEL

SHIELDED CABLES

AFTER ALL TESTING HAS BEEN

COMPLETED, INSULATE ALL FIELD

TERMINATIONS USING FILLER, HIGH

VOLTAGE & FINISHING TAPE

TYPICAL CRIMP LUG

CONCRETE MANHOLE OR

UNDERGROUND CABLE VAULT

FINAL 10' LENGTH OF

CONDUIT INTO MANHOLE

OR VAULT TO BE PVC

5'-0"

1'-6" 2"

PVC END BELL

(TYPICAL)

FILL REMAINING CONDUIT

WINDOW OPENING WITH

CONCRETE OR GROUT

DRILL 7/8"Ø HOLES IN EXTERIOR WALL.

EPOXY ANCHOR #6 REINFORCING

BARS INTO HOLES. OVERLAP WALL

BARS WITH DUCTBANK BARS, AND TIE.

SCHEDULE 40 PVC RUN

PVC-TO-PVC COUPLING

REINFORCED

CONCRETE WALL

TOP VIEW

2'-4"

4'-8"

2'-4"

2'- 4"

2'- 4"

4'- 8"

AA

SUMP 12"

GROUND ROD PER

SECTION 26 05 26.

GALVANIZED PULL/LIFT

IRON

(1 EACH CORNER)

2'-0" LG

GALVANIZED

"C" CHANNEL

4"

3'- 6"4'-

0"

6"

SPRING ASSISTED

GALVANIZED DIAMOND

PLATE DOOR

SECTION "A-A"

1'- 0"

6" 6"

CONCRETE PAVEMENT

SUB-BASE COURSE

STABILIZATION FABRIC

COMPACTED FILL OF PREPARED

SUB-GRADE (TO BE LEVEL)

1/4" SAW CUT

CONTRACTION JOINT

X X3"

6x6 W2.1xW2.1 WELDED

WIRE REINFORCEMENT

SECURE HVP TO VAULT

USING HILTI 1/2" CONCRETE

ANCHOR BOLTS

SECURE HVP TO VAULT

USING HILTI 1/2" CONCRETE

ANCHOR BOLTS

GALVANIZED

STEEL UNISTRUT

(TYP)

GALVANIZED

STEEL POST

(TYP)

PANEL

NEMA 3R

ENCLOSURE

ES502

4'- 0"

2"

1'-0"

TYPE "C" CONCRETE

FOOTING (TYP)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

SITE ELECTRICAL DETAILS BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES502

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

SCALE: NTS

BELOW-GRADE DUCTBANK FOUNDATION

STUB-UP DETAIL1 SCALE: NTS

MV CONDUCTORS CABLE STRESS

CONE TERMINATION DETAIL2

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.

3. SEE EG101 FOR GROUNDING SITE PLAN.

4. SEE EP101 FOR BUILDING 115 FLOOR PLAN.

5. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.

6. SEE SPECIFICATION 26 05 41 FOR UNDERGROUND ELECTRICAL CONSTRUCTION.

SCALE: NTS

DUCTBANK TO MANHOLE DETAIL3

SCALE: NTS

SWITCH VAULT HVS/HVP4 SCALE: 1 1/2"=1'-0"

TYPICAL CONCRETE PAD SECTION5 SCALE: NTS

TYPICAL HVP MOUNTING DETAIL6 SCALE: NTS

TYPICAL PANEL MOUNTING DETAIL7 SCALE: NTS

TYPICAL CONCRETE FOOTING DETAIL8

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL FEEDER SCHEDULE -

NEW WORK

BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES601

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

MEDIUM VOLTAGE FEEDER SCHEDULE - NEW WORK

15KV CABLE CONNECTION INSTALL

FAULT

INDICATOR

(1 PER

PHASE)

NOTE

CABLE

NUMBER TAG SIZES

TOTAL

CONDUCTOR

LENGTH (FT)

3-PHASES

GROUND

LENGTH

(FT)

REEL

NUMBER FROM VIA TO

1 NC-CBL-15KV-001 3 - 250KCMIL, 4/0 GND 2685 895 BLD 115 -

NW-4A

HVS-A

HVP-K HVS-SL1 X CONTRACTOR TO SUPPLY CABLE

2 NC-CBL-15KV-002 3 - 250KCMIL, 4/0 GND 1809 603 18 HVS-SL1 HVP-K

HVP-2 HVS-2 X VA SUPPLIED CABLE

3 NC-CBL-15KV-003 3 - 250KCMIL, 4/0 GND 1071 357 1 HVS-2 HVP-2 HVS-3 X VA SUPPLIED CABLE 4 NC-CBL-15KV-004 3 - 250KCMIL, 4/0 GND 1056 352 1 HVS-3 HVP-15 X VA SUPPLIED CABLE 5 NC-CBL-15KV-005 3 - 250KCMIL, 4/0 GND 1125 375 16 HVP-15 HVP-20 HVS-20 X VA SUPPLIED CABLE

6 NC-CBL-15KV-006 3 - 250KCMIL, 4/0 GND 1425 475 19 HVS-20 HVP-23

HVS-23A HVS-24 X VA SUPPLIED CABLE

7 NC-CBL-15KV-007 3 - 250KCMIL, 4/0 GND 1950 650 6 HVS-24 HVS-27 X VA SUPPLIED CABLE 8 NC-CBL-15KV-008 3 - 250KCMIL, 4/0 GND 612 204 16 HVS- 27 HVP-29 X VA SUPPLIED CABLE 9 NC-CBL-15KV-009 3 - 250KCMIL, 4/0 GND 1161 387 12 HVP-29 HVS-31 X VA SUPPLIED CABLE

10 NC-CBL-15KV-010 3 - 250KCMIL, 4/0 GND 1089 363 2 HVS-31 HVP-34 X VA SUPPLIED CABLE 11 NC-CBL-15KV-011 3 - 250KCMIL, 4/0 GND 1512 504 7 HVP-34 HVP-36 X VA SUPPLIED CABLE 12 NC-CBL-15KV-012 3 - 250KCMIL, 4/0 GND 3039 1013 HVP-36 HVS-12 X CONTRACTOR TO SUPPLY CABLE

13 NC-CBL-15KV-013 3 - 250KCMIL, 4/0 GND 4050 1350 HVS-12 BLD 115

CB-SE-4B X CONTRACTOR TO SUPPLY CABLE

14 NC-CBL-15KV-014 3 - 250KCMIL, 4/0 GND 75 25 19 HVS-SL1 XF-K X VA SUPPLIED CABLE 15 NC-CBL-15KV-015 3 - 250KCMIL, 4/0 GND 3000 1000 HVS-SL1 XF-SL1 X CONTRACTOR TO SUPPLY CABLE 16 NC-CBL-15KV-016 3 - 250KCMIL, 4/0 GND 1050 350 2 HVS-3 HVP-4 X VA SUPPLIED CABLE 17 NC-CBL-15KV-017 3 - 250KCMIL, 4/0 GND 231 77 12 HVP-4 HVS-4 XF-43 X VA SUPPLIED CABLE 18 NC-CBL-15KV-018 3 - 250KCMIL, 4/0 GND 1440 480 13 HVP-4 XF39 X VA SUPPLIED CABLE

19 NC-CBL-15KV-019 3 - 250KCMIL, 4/0 GND 849 283 22 HVP-15 HVP-16

HVS-16 XF-119 X VA SUPPLIED CABLE

20 NC-CBL-15KV-020 3 - 250KCMIL, 4/0 GND 726 242 22 HVP-15 HVP-18 X VA SUPPLIED CABLE

21 NC-CBL-15KV-021 2 - 250KCMIL, 4/0 GND (C-A) 630 210 17 HVP-18 HVP-18

HVS-18 XF-112 X VA SUPPLIED CABLE

22 NC-CBL-15KV-022 3 - 250KCMIL, 4/0 GND 420 140 8 HVP-18 XF-49 X VA SUPPLIED CABLE

23 NC-CBL-15KV-023 3 - 250KCMIL, 4/0 GND 585 195 8 HVS-20

XF-2

BLDG-102 X VA SUPPLIED CABLE

24 NC-CBL-15KV-024 3 - 250KCMIL, 4/0 GND 1065 355 8 HVS-20 HVP-22A XF-CL1 X VA SUPPLIED CABLE 25 NC-CBL-15KV-025 3 - 250KCMIL, 4/0 GND 2205 735 10 HVS-24 HVP-40 X VA SUPPLIED CABLE 26 NC-CBL-15KV-026 3 - 250KCMIL, 4/0 GND 795 265 3 HVP-40 HVP-41 X VA SUPPLIED CABLE 27 NC-CBL-15KV-027 2 - 250KCMIL, 4/0 GND (A-B) 645 215 3 HVP-41 HVP-42 X VA SUPPLIED CABLE 29 NC-CBL-15KV-029 3 - 250KCMIL, 4/0 GND 350 117 5 HVP-41 HVS-41 X VA SUPPLIED CABLE 30 NC-CBL-15KV-030 2 - 250KCMIL, 4/0 GND (B-C) 567 189 5 HVP-42 XF-17 X VA SUPPLIED CABLE 31 NC-CBL-15KV-031 2 - 250KCMIL, 4/0 GND (A-B) 606 202 5 HVP-42 XF-19 PNL-19 X VA SUPPLIED CABLE 32 NC-CBL-15KV-032 3 - 250KCMIL, 4/0 GND 60 20 5 HVS-27 XF-27 X VA SUPPLIED CABLE 33 NC-CBL-15KV-033 3 - 250KCMIL, 4/0 GND 594 198 17 HVS-27 XF-6 X VA SUPPLIED CABLE 34 NC-CBL-15KV-034 3 - 250KCMIL, 4/0 GND 1089 363 20 HVP-29 HVP-30 X VA SUPPLIED CABLE 35 NC-CBL-15KV-035 3 - 250KCMIL, 4/0 GND 90 30 14 HVP-29 XF-5 X VA SUPPLIED CABLE 36 NC-CBL-15KV-036 3 - 250KCMIL, 4/0 GND 90 30 14 HVP-30 XF-11 X VA SUPPLIED CABLE 37 NC-CBL-15KV-037 3 - 250KCMIL, 4/0 GND 261 87 14 HVP-30 XF-7 X VA SUPPLIED CABLE 38 NC-CBL-15KV-038 3 - 250KCMIL, 4/0 GND 552 184 17 HVS-31 XF-3 X VA SUPPLIED CABLE 39 NC-CBL-15KV-039 3 - 250KCMIL, 4/0 GND 552 184 20 HVS-31 XF-4 X VA SUPPLIED CABLE 40 NC-CBL-15KV-040 3 - 250KCMIL, 4/0 GND 93 31 14 HVP-34 XF-1 X VA SUPPLIED CABLE 41 NC-CBL-15KV-041 3 - 250KCMIL, 4/0 GND 180 60 14 HVP-36 XF-36 X VA SUPPLIED CABLE 42 NC-CBL-15KV-042 3 - 250KCMIL, 4/0 GND 735 245 15 HVP-36 XF-97 X VA SUPPLIED CABLE 43 NC-CBL-15KV-043 3 - 250KCMIL, 4/0 GND 732 244 15 HVP-36 XF-108 X VA SUPPLIED CABLE 44 NC-CBL-15KV-044 3 - 250KCMIL, 4/0 GND 96 32 15 HVP-36 XF-20 X VA SUPPLIED CABLE 45 NC-CBL-15KV-045 3 - 250KCMIL, 4/0 GND 1650 550 11 HVS-12 HVS-146 X VA SUPPLIED CABLE 47 NC-CBL-15KV-047 3 - 250KCMIL, 4/0 GND 600 200 14 HVS-2 XF-1301 X VA SUPPLIED CABLE

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL SCHEDULES BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES602

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.

MEDIUM VOLTAGE TRANSFORMER SCHEDULE

EQUIPMENT

TAG BUILDING KVA SIZE VOLTAGE PHASE MANUF.

DATE AGE (YR) ACTION

NOTES

KEEP REPLACE REMOVE NEW

XF-001 1 75 13.2KV - 208/120 3 1/1/1988 37 X BUILDING IS ON WE ENERGIES

REPLACE WITH COOPER/EATON CA202003EN

XF-002 2 500 13.2KV - 208/120 3 1/1/1983 42 X BUILDING IS ON WE ENERGIES

XF-003 3&4 225 13.2KV - 208/120 3 1/1/2005 20 X REPLACE WITH COOPER/EATON CA202003EN XF-004 5 225 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN XF-005 5 300 13.2KV - 208/120 3 1/1/1992 33 X REPLACE WITH COOPER/EATON CA202003EN XF-006 6 1000 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN XF-007 7 500 13.2KV - 208/120 3 1/1/1993 32 X REPLACE WITH COOPER/EATON CA202003EN XF-011 11 50 13.2KV - 240/120 1 1/1/2021 4 X REPLACE WITH COOPER/EATON CA201002EN

XF-012 12 75 13.2KV - 208/120 3 1/1/1988 37 X

XF-014 14ST LIGHTS 37.5 13.2KV - 240/120 1 1/1/1988 37 X

XF-016 GARAGE 50 13.2KV - 208/120 3 1/1/1988 37 X

XF-017 17ST LIGHTS 75 13.2KV - 240/120 1 8/29/2015 10 X

XF-019 18&19ST LIGHTS 75 13.2KV - 240/120 1 1/1/1988 37 X

TRANSFORMER IS REPLACED AND MOVED TO A NEW

LOCATION

REPLACE WITH COOPER/EATON CA201002EN

XF-020 20 112.5 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN

XF-027 ST LIGHTS 75 13.2KV - 208/120 3 1/1/1997 28 X PAD SHOWS SIGNS OF SINKING

REPLACE WITH COOPER/EATON CA202003EN

XF-036 PNL 2V 75 13.2KV - 208/120 3 1/1/1997 28 X REPLACE WITH COOPER/EATON CA202003EN XF-039 ST LIGHTS 37.5 13.2KV - 240/120 1 1/1/2021 4 X REPLACE WITH COOPER/EATON CA201002EN

XF-041 (HVP-41) 16ST LIGHTS 75 13.2KV - 208/120 3 1/1/1997 28 X BUILDING IS ON WE ENERGIES

XF-041 (HVP-8) 41 (VACANT) 225 13.2KV - 208/120 3 1/1/1988 37 X

XF-043 43 750 13.2KV - 480/277 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN

XF-049 49 GARAGE 75 13.2KV - 240/120 1 1/1/1988 37 X BUILDING IS ON WE ENERGIES

REPLACE WITH COOPER/EATON CA201002EN

XF-062 62, 18 &19ST LIGHTS 75 13.2KV - 240/120 1 1/1/1988 37 X BUILDING IS ON WE ENERGIES XF-097 99,T105,T106, T1 75 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN

XF-102 102 750 13.2KV - 208/120 3 1/1/2008 17 X

XF-108 107/108 112.5 13.2KV - 208/120 3 1/1/1988 37 X REPLACE WITH COOPER/EATON CA202003EN

XF-112 112 500/560 13.2KV - 480/277 3 1/1/2013 12 X

XF-119 119&150 225 13.2KV - 208/120 3 1/1/2014 11 X

XF-1301 1301 112.5 13.2KV - 208/120 3 1/1/1993 32 X REPLACE WITH COOPER/EATON CA202003EN

XF-146 146 225 13.2KV - 208/120 3 1/1/2013 12 X

XF-147 147 225 13.2KV - 208/120 3 1/1/2015 10 X

XF-148 148 225 13.2KV - 208/120 3 1/1/2015 10 X

XF-CL1 CRASH LAB 750 13.2KV - 480/277 3 1/1/1998 27 X REPLACE WITH COOPER/EATON CA202003EN XF-K ST LIGHTS, PUMPS 37.5 13.2KV - 240/120 1 1/1/2020 5 X REPLACE WITH COOPER/EATON CA201002EN

XF-MP-FDS 57 7.5 120/240 - 480/240 1 UNKNOWN UNKNOWN X CEMETERY GAZEBO AND LIGHTS XF-SL1 PARKING GARAGES 37.5 13.2KV - 120/240 1 UNKNOWN UNKNOWN X REPLACE WITH COOPER/EATON CA201002EN

MEDIUM VOLTAGE PEDESTAL SCHEDULE

EQUIPMENT TAG MANUF. DATE AGE (YR) PAD DIMENSIONS PAD CONDITION ACTION

NOTES

WIDTH DEPTH REPAIR REPLACE KEEP REPLACE REMOVE NEW

HVP-002 NA 62" 59" X USED AS A PASS-THROUGH

HVP-003 NA 62" 59" X REPLACED WITH AN HVS

HVP-004 NA 62" 59" X

HVP-008 NA 62" 59" X

HVP-011 NA 62" 59" X USED AS A PASS-THROUGH

HVP-015 NA 62" 59" X

HVP-016 NA 62" 59" X USED AS A PASS-THROUGH

HVP-018 NA 62" 59" X

HVP-020 NA 62" 59" X USED AS A PASS-THROUGH

HVP-022 NA 62" 59" X USED AS A PASS-THROUGH

HVP-023 NA 62" 59" X USED AS A PASS-THROUGH

HVP-024 NA 62" 59" X REPLACED WITH AN HVS

HVP-027 NA 62" 59" X REPLACED WITH AN HVS

HVP-029 NA 62" 59" X

HVP-030 NA 62" 59" X

HVP-031 NA 62" 59" X REPLACED WITH AN HVS

HVP-034 NA 62" 59" X

HVP-036 NA 62" 59" X

HVP-040 NA 62" 59" X

HVP-041 NA 62" 59" X

HVP-042 NA 62" 59" X

HVP-044 NA 62" 59" X

HVP-K NA 62" 59" X USED AS A PASS-THROUGH

LOW VOLTAGE PANEL SCHEDULE

EQUIPMENT

TAG MANUF. DATE AGE (YR)

PAD CONDITION ACTION

NOTES

KEEP REPAIR/

REPLACE KEEP REPLACE REMOVE NEW

107/108-DS-A NA X X DOES NOT EXIST, LOCAL

DISCONNECT LOCATED IN PLACE

PNL-001 12/1/1988 36 X X

PNL-002V 2/3/1998 27 X X

PNL-003 X X

PNL-011 NA X X

PNL-014 NA X X

PNL-016 7/1/1988 37 X X

PNL-017 NA X X

PNL-019 NA X X PANEL IS REPLACED AND MOVED TO

A NEW LOCATION

PNL-027 2/3/1998 27 X X PANEL AND TRANSFORMER PAD

SHOWS SIGNS OF SINKING

PNL-039 NA X X

PNL-041 2/3/1998 27 X X

PNL-049 NA X X

PNL-062 NA X X

PNL-CLC NA X X

PNL-K NA X X

PNL-SL1 NA X X

MEDIUM VOLTAGE SWITCH SCHEDULE

EQUIPMENT

TAG MANUF. DATE AGE (YR)

PAD

DIMENSIONS ACTION NOTES

WIDTH DEPTH REPAIR REPLACE KEEP REPLACE REMOVE NEW

HVS-001/HVS-A 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH

HVS-002(1301) 7/1/1993 32 62" 74" X REPLACE WITH EATON/COOPER POWER

MOST-6

HVS-004 5/1/2016 9 62" 74" X USED AS A PASS-THROUGH HVP-4A

HVS-011 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH HVP-11A

HVS-016 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH HVP-16A

HVS-018 3/1/1988 37 62" 74" X USED AS A PASS-THROUGH HVP-18A

HVS-020 3/1/1988 37 62" 74" X REPLACE WITH EATON/COOPER POWER

MOST-6

HVS-022 9/1/1998 27 75" 69" X USED AS A PASS-THROUGH HVP-22A

HVS-023A 3/1/2017 8 72" 40" X USED AS A PASS-THROUGH HVP-23A

HVS-023B 3/1/2017 8 72" 40" X

HVS-036 11/1/1997 27 67" 60.5" X

HVS-041 11/1/1997 27 67" 60.5" X USED AS PASS-THROUGH HVS-41A

HVS-146 5/1/2013 12 - - X NEW SWITCH, NO NEED TO REPLACE

HVS-147 10/1/2015 9 - - X NEW SWITCH, NO NEED TO REPLACE

HVS-148 10/1/2015 9 - - X NEW SWITCH, NO NEED TO REPLACE

HVS-SL1 3/1/1996 29 58" 66" X REPLACE WITH EATON/COOPER POWER

MOST-9

HVS-003 62" 59" X EATON/COOPER POWER MOST-6

HVS-012 62" 74" X REPLACE WITH EATON/COOPER POWER

MOST-9. INSTALL VAULT FOR HVS.

HVS-024 62" 59" X REPLACE WITH EATON/COOPER POWER

MOST-6

HVS-027 62" 59" X REPLACE WITH EATON/COOPER POWER

MOST-9

HVS-031 62" 59" X REPLACE WITH EATON/COOPER POWER

MOST-9

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL SCHEDULES BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES603

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

GOVERNMENT FURNISHED EQUIPMENT SCHEDULE

ITEM DESCRIPTION QTY SUPPLIER MANUFACTURER CATALOG

NUMBER NOTES

COLD SHRINK TERMINATION KIT 4 WERNER ELECTRIC SUPPLY 3M 7693-S-4

250KCMIL LONG BARREL COPPER LUG 1/2IN STUD TWO-HOLE

COMPLETION TYPE 12 WERNER ELECTRIC SUPPLY PANDUIT LCC250-12-X

LOAD BREAK ELBOW WITH TEST POINT AND SHIELD ADAPTER 55 WERNER ELECTRIC SUPPLY CPS LE215CC09T-SA2

2-WAYDEADBREAK SPLICE WITH TEST POINT, COMPRESSION

CONNECTORS, CABLE ADAPTERS, AND SHIELD ADAPTER 26 WERNER ELECTRIC SUPPLY CPS SSPL625CC16A2T-SA2

3-WAY DEAD BREAK SPLICE WITH TEST POINT, COMPRESSION

CONNECTORS, CABLE ADAPTERS, AND SHIELD ADAPTER 48 WERNER ELECTRIC SUPPLY CPS SSPL625CC16A3T-SA2

4-WAY DEAD BREAK SPLICE WITH TEST POINT, COMPRESSION

CONNECTORS, CABLE ADAPTERS, AND SHIELD ADAPTER 21 WERNER ELECTRIC SUPPLY CPS SSPL625CC16A4T-SA2

DEAD BREAK DEAD-END KIT WITH TEST POINT AND SHIELD ADAPTER 33 WERNER ELECTRIC SUPPLY CPS BT625CC16A1T-SA2+DI P625A

CABLE CAPS FOR FIELD INSTALL AFTER PULLING BUT BEFORE

TERMINATING 300 WERNER ELECTRIC SUPPLY ALR 766749-000 VERIFY WITH COR THAT ITEMS ARE STORED ON SITE READY FOR USE ON

PROJECT

GREEN 4/0 XHHW GROUNDING WIRE 14225 WERNER ELECTRIC SUPPLY SOUTHWIRE SIMpull CH-XHHW VERIFY WITH COR THAT ITEMS ARE STORED ON SITE READY FOR USE ON

PROJECT

GOVERNMENT FURNISHED EQUIPMENT - MEDIUM VOLTAGE CABLE

REEL NO. QTY

(FT)

AVAILABLE

LENGTH

(FT)

SUPPLIER MANUFACTURER CATALOG

NO.

CONDUCT

OR SIZE

(KCMIL)

APPROXIMATE

O.D. (IN)

AMPACITY

UNDERGROUND

DUCT BANK

NOTES

1 2190 730 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

2 2190 730 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

3 1599 533 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

4 1599 533 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

5 1965 655 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

6 1965 655 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

7 1527 509 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

8 2097 699 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

9 2205 735 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

10 2217 739 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

11 1737 579 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

12 1557 519 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

13 1551 517 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

14 1632 544 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

15 1623 541 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

16 1803 601 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

17 1980 651 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

18 1860 620 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

19 1530 510 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

20 1683 561 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

21 1683 561 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

22 1662 554 WERNER ELECTRIC SUPPLY OKONITE 115-23-3123 250 1.26 345 REEL CONTAINS 3 CONDUCTORS EQUALING TOTAL LENGTH ON REEL.

BRANCH PANEL: PNL-001

LOCATION: BUILDING 1 VOLTS: 208/120 A.I.C RATING: 10000

SUPPLY FROM: XF-1 PHASE: 3 MAINS TYPE: MCB

MOUNTING: CLOSE COUPLED WIRES: 4 MAINS RATING: 400A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 225A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

FOUNTAIN 20 A 2

1664.00 VA 1919.15 VA

3 20 A STEET LIGHTS

3 1664.00 VA 1919.15 VA 4

5 SPARE 20 A 1 0000.00 VA 1919.15 VA 6

7 PHOTOCELL/ COIL 20 A 1 1920.00 VA 0000.00 VA 1 20 A SPARE 8

9 UNKNOWN 20 A 1 1920.00 VA 0000.00 VA 1 20 A SPARE 10

SPARE 20 A 3

0000.00 VA 0000.00 VA

3 20 A SPARE

13 0000.00 VA 0000.00 VA 14

15 0000.00 VA 0000.00 VA 16

SPARE 20 A 2

0000.00 VA 0000.00 VA

2 20 A SPARE

19 0000.00 VA 0000.00 VA 20

21 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 22

23 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 24

25 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 26

27 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 28

29 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 30

TOTAL LOAD: 5503.15 VA 5503.15 VA 1919.15 VA

TOTAL AMPS: 0045.86 A 0045.86 A 0015.99 A

BRANCH PANEL: PNL-002V

LOCATION: BUILDING 20 VOLTS: 208/120 A.I.C RATING: 10000

SUPPLY FROM: XF-36 PHASE: 3 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 4 MAINS RATING: 250 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 250 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

1 COIL & PHOTOCELL 20 A 1 1920.00 VA 1919.15 VA

3 20 A STREET LIGHTS

POLES 68-73

STREET LIGHTS

POLES 74-81 20 A 3

1919.15 VA 1919.15 VA 4

5 1919.15 VA 1919.15 VA 6

7 1919.15 VA 0000.00 VA

3 20 A SPARE

SPARE 20 A 3

0000.00 VA 0000.00 VA 10

11 0000.00 VA 0000.00 VA 12

13 0000.00 VA 0000.00 VA

3 20 A SPARE

SPARE 20 A 3

0000.00 VA 0000.00 VA 16

17 0000.00 VA 0000.00 VA 18

19 0000.00 VA 0000.00 VA

2 20 A SPARE

SPARE 20 A 2

0000.00 VA 0000.00 VA 22

23 0000.00 VA 0000.00 VA

2 20 A SPARE

SPARE 20 A 2

0000.00 VA 0000.00 VA 26

27 0000.00 VA 0000.00 VA 1 20 A SPARE 28

29 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 30

31 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 32

33 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 34

35 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 36

37 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 38

39 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 40

41 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 42

TOTAL LOAD: 5758.30 VA 3838.30 VA 3838.30 VA

TOTAL AMPS: 0047.99 A 0031.99 A 0031.99 A

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.

3. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.

4. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.

5. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS.

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

ELECTRICAL SCHEDULES BID DOCUMENTS

UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES604

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

BRANCH PANEL: PNL-027

LOCATION: BLDG 6 / HANK ARRON TRAIL VOLTS: 208/120 A.I.C RATING: 10000

SUPPLY FROM: XF-27 PHASE: 3 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 4 MAINS RATING: 250 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 250 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

1 COIL & PHOTOCELL 20 A 1 1920.00 VA 0000.00 VA

3 20 A SPARE

3 STREET LIGHTING 20 A 1 1920.00 VA 0000.00 VA 4

5 STREET LIGHTING 20 A 1 1920.00 VA 0000.00 VA 6

7 STREET LIGHTING 20 A 1 1920.00 VA 0000.00 VA

3 20 A SPARE

9 SPARE 20 A 1 0000.00 VA 0000.00 VA 10

11 SPARE 20 A 1 0000.00 VA 0000.00 VA 12

13 SPARE 20 A 1 0000.00 VA 0000.00 VA

2 20 A SPARE

15 SPARE 20 A 1 0000.00 VA 0000.00 VA 16

17 SPARE 20 A 1 0000.00 VA 0000.00 VA

2 20 A SPARE

19 SPARE 20 A 1 0000.00 VA 0000.00 VA 20

21 SPARE 20 A 1 0000.00 VA 0000.00 VA

2 20 A SPARE

23 SPARE 20 A 1 0000.00 VA 0000.00 VA 24

25 SPARE 20 A 1 0000.00 VA 0000.00 VA

3 20 A SPARE

27 SPARE 20 A 1 0000.00 VA 0000.00 VA 28

29 SPARE 20 A 1 0000.00 VA 0000.00 VA 30

TOTAL LOAD: 3840.00 VA 1920.00 VA 1920.00 VA

TOTAL AMPS: 0032.00 A 0016.00 A 0016.00 A

BRANCH PANEL: PNL-039

LOCATION: BUILDING 39 VOLTS: 240/120 A.I.C. RATING: 10000

SUPPLY FROM: XF-39 PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 400 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 400 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

STREET LIGHTS 20 A 2

1920.00 VA 1920.00 VA

2 20 A STREET LIGHTS

3 1920.00 VA 1920.00 VA 4

STREET LIGHTS 20 A 2

1920.00 VA 2880.00 VA

2 30 A SHED / PHOTOCELL

7 1920.00 VA 2880.00 VA 8

SPARE 20 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 10

11 0000.00 VA 0000.00 VA 1 20 A SPARE 12

SPARE 20 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 14

15 0000.00 VA 0000.00 VA 1 20 A SPARE 16

SPARE 20 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 18

19 0000.00 VA 0000.00 VA 1 20 A SPARE 20

SPARE 20 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 22

23 0000.00 VA 0000.00 VA 1 20 A SPARE 24

TOTAL LOAD: 8640.00 VA 8640.00 VA

TOTAL AMPS: 0072.00 A 0072.00 A

BRANCH PANEL: PNL-CLC

LOCATION: CLC LOOP VOLTS: 208/120 A.I.C. RATING: 10000

SUPPLY FROM: XF-146 PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 100 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 100 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

1 NORTH POLE LIGHTS 20 A 1 1 20 A SPARE 2

3 SPARE 20 A 1 1 20 A WEST POLE LIGHTS 4

5 CIRCLE DR POLE LIGHTS 20 A 1 1 20 A POLE LIGHTS BY XMFR 6

7 SPARE 20 A 1 1 20 A SPARE 8

FLAG POLE LIGHTS 20 A 2

1 20 A PHOTOCELL 10

11 1 20 A RECEPTICAL 12

13 SPARE 20 A 1

2 20 A SPARE

15 SPARE 20 A 1 16

17 SPARE 20 A 1

2 20 A SPARE

19 SPARE 20 A 1 20

21 SPARE 20 A 1

2 20 A SPARE

23 SPARE 20 A 1 24

TOTAL LOAD: 0000.00 VA 0000.00 VA

TOTAL AMPS: 0000.00 A 0000.00 A

BRANCH PANEL: PNL-K

LOCATION: HVS-SL1 VOLTS: 240/120 A.I.C RATING: 10000

SUPPLY FROM: XF-K PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 200 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 200 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

STREET LIGHTS 30 A 2

2880.00 VA 2880.00 VA

2 30 A FISHER HOUSE

3 2880.00 VA 2880.00 VA 4

SOUTH SIDE OF 43 30 A 2

2880.00 VA 2880.00 VA

2 30 A FISHER HOUSE

7 2880.00 VA 2880.00 VA 8

9 STEAM MH REC. 20 A 1 1920.00 VA 1920.00 VA 1 20 A MH 1 REC 10

11 ISLAND REC. 20 A 1 1920.00 VA 1920.00 VA 1 20 A POND 12

13 POND 20 A 1 1920.00 VA 0000.00 VA 1 20 A SPARE 14

SPARE 30 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 16

17 0000.00 VA 0000.00 VA 1 20 A SPARE 18

SPARE 30 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 20

21 0000.00 VA 0000.00 VA 1 20 A SPARE 22

SPARE 30 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 24

25 0000.00 VA 0000.00 VA 1 20 A SPARE 26

SPARE 30 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 28

29 0000.00 VA 0000.00 VA 1 20 A SPARE 30

TOTAL LOAD: 17280.00 VA 15360.00 VA

TOTAL AMPS: 0144.00 A 0128.00 A

BRANCH PANEL: PNL-SL1

LOCATION: BUILDING 152 VOLTS: 240/120 A.I.C RATING: 10000

SUPPLY FROM: XF-SL1 PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 225 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 225 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

SPARE 30 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 2

3 0000.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #1

5 LOT 35 GATE 20 A 1 1920.00 VA 1920.00 VA 6

BUS SHELTER HEATER 20 A 2

1920.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #2

9 1920.00 VA 1920.00 VA 10

STREET LIGHT CIRCUIT #8 LOT 35 20 A 2

1920.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #3

13 1920.00 VA 1920.00 VA 14

15 SPARE 20 A 1 0000.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #4

17 SPARE 20 A 1 0000.00 VA 1920.00 VA 18

19 TALK-A-PHONES 20 A 1 1920.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #5

21 GATES/CTRLS DR. LOT 20 A 1 1920.00 VA 1920.00 VA 22

23 LIGHTING CONTACTOR 20 A 1 1920.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #6

25 SPARE 20 A 1 0000.00 VA 1920.00 VA 26

27 NORTH GATES 20 A 1 1920.00 VA 1920.00 VA

2 20 A STREET LIGHT CIRCUIT #7 LOT 35

29 SPARE 20 A 1 0000.00 VA 1920.00 VA 30

TOTAL LOAD: 21120.00 VA 23040.00 VA

TOTAL AMPS: 0176.00 A 0192.00 A

BRANCH PANEL: PNL-019

LOCATION: MH-43 VOLTS: 240/120 A.I.C. RATING: 10000

SUPPLY FROM: XF-19 PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 400 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 400 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

1 SPARE 40 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 2

3 SPARE 20 A 1 0000.00 VA 0000.00 VA

2 70 A SPARE

5 SPARE 20 A 1 0000.00 VA 0000.00 VA 6

7 COIL & PHOTOCELL 20 A 1 1920.00 VA 5760.00 VA

2 60 A PNL - OUTDOOR SERVICE NORTH LOT

9 STREET LIGHTING NORTH

12-14, 21, 21A, 22 20 A 2

1920.00 VA 5760.00 VA 10

11 1920.00 VA 0000.00 VA

2 200 A SPARE

13 STREET LIGHTING SOUTH

15-20, 23-28 20 A 2

1920.00 VA 0000.00 VA 14

15 1920.00 VA 0000.00 VA

2 200 A SPARE

17 SPARE 20 A 1 0000.00 VA 0000.00 VA 18

SPARE 60 A 2

0000.00 VA 0000.00 VA

2 60 A SPARE

21 0000.00 VA 0000.00 VA 22

23 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 24

TOTAL LOAD: 9600.00 VA 11520.00 VA

TOTAL AMPS: 0080.00 A 0096.00 A

BRANCH PANEL: PNL-011

LOCATION: BUILDING 11 VOLTS: 240/120 A.I.C RATING: 10000

SUPPLY FROM: XF-11 PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 400 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 400 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

EAST BUILDING 11 225 A 2

21600.00 VA 21600.00 VA

2 225 A WEST BUILDING 11

3 21600.00 VA 21600.00 VA 4

PARKING LOT LIGHTS 15 A 2

1440.00 VA 1920.00 VA 1 20 A PANEL GFCI 6

7 1440.00 VA 0000.00 VA 1 20 A SPARE 8

SPARE 20 A 2

0000.00 VA 0000.00 VA 1 15 A SPARE 10

11 0000.00 VA 0000.00 VA 1 15 A SPARE 12

SPARE 15 A 2

0000.00 VA 0000.00 VA 1 15 A SPARE 14

15 0000.00 VA 0000.00 VA 1 15 A SPARE 16

SPARE 15 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 18

19 0000.00 VA 0000.00 VA 1 20 A SPARE 20

SPARE 20 A 2

0000.00 VA 0000.00 VA 1 20 A SPARE 22

23 0000.00 VA 0000.00 VA 1 20 A SPARE 24

TOTAL LOAD: 46560.00 VA 44640.00 VA

TOTAL AMPS: 0388.00 A 0372.00 A

BRANCH PANEL: PNL-017

LOCATION: BUILDING 17 VOLTS: 240/120 A.I.C. RATING: 14000

SUPPLY FROM: XF-17 PHASE: 1 MAINS TYPE: MCB

MOUNTING: PAD MOUNTED WIRES: 3 MAINS RATING: 200 A

ENCLOSURE: NEMA 3R SERVICE BRANCH: NORMAL MCB RATING: 200 A

NOTES:

CKT CIRCUIT DESCRIPTION TRIP POLES L1 L2 POLES TRIP CIRCUIT DESCRIPTION CKT

1 SPARE 20 A 1 0000.00 VA 1920.00 VA 1 20 A COIL/ PHOTOCELL 2

SURGE PROTECTOR 30 A 2

2880.00 VA 1920.00 VA 1 20 A SIGNS AND GFI 4

5 2880.00 VA 3840.00 VA

2 40 A STREET LIGHTS

XF-MP-FDS 40 A 2

3840.00 VA 3840.00 VA 8

9 3840.00 VA 0000.00 VA

2 20 A SPARE

SPARE 30 A 2

0000.00 VA 0000.00 VA 12

13 0000.00 VA 0000.00 VA

2 30 A SPARE

SPARE 20 A 2

0000.00 VA 0000.00 VA 16

17 0000.00 VA 0000.00 VA 1 20 A SPARE 18

19 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 20

21 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 22

23 SPARE 20 A 1 0000.00 VA 0000.00 VA 1 20 A SPARE 24

TOTAL LOAD: 12480.00 VA 12480.00 VA

TOTAL AMPS: 0104.00 A 0104.00 A

GENERAL NOTES

1. SEE E-001 FOR E-SERIES NOTES AND LEGENDS.

2. SEE ED101 FOR ELECTRICAL DEMOLITION SITE PLAN.

3. SEE ES101 FOR POWER DISTRIBUTION PROPOSED SITE PLAN.

4. SEE EP601 FOR NEW SINGLE LINE DIAGRAM.

5. SEE GC101 THROUGH GC113 FOR PHASING DRAWINGS.

Exp.: 12/31/2028

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

K2 K2 OPEN

CLOSED

K1 K2

K2 K1

K2 K1

LOAD BREAK FUSES

LOOP LOAD BREAK SWITCHES

K2HVS-SL1 HVS-2 HVS-3 HVS-20 HVS-24 HVS-12HVS-31

TIE

SE-4B

WE H-69165

NW-4A

WE H-3257

13.2 KV 13.2 KV

N.C. N.C.

HVS-27

N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.O. N.C. N.C. N.C. N.C.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

23 MECHANIC STREET, SPRINGVILLE, NY 14141

KIRK KEY INFORMATION BID DOCUMENTS UPGRADE NORTH CAMPUS MEDIUM

VOLTAGE FEEDER CLEMENT J.

ZABLOCKI VAMC

5000 W. NATIONAL AVE.

MILWAUKEE, WI 53295

2025/10/09

ES605

SITE

695-22-123

CJR DAK

REV 0 - BID DOCUMENTS 2025-10-09

"Unauthorized alteration or addition to any plans, specifications or reports bearing a Licensed Professional Engineer's seal is a violation of Section 7209, subdivision 2, of the New York State Education Law".

CERTIFICATE OF AUTHORIZATION NUMBER: 0020000

GENERAL NOTES

1. DANGER - ELECTRICAL HAZARD. ENSURE THE SYSTEM IS ELECTRICALLY ISOLATED AND

THAT NO HAZARDOUS VOLTAGES ARE PRESENT BEFORE PERFORMING MAINTENANCE

WORK WITHIN ENCLOSURES.

2. FOR A COMPLETE LIST OF DANGERS AND HAZARDS PLEASE CONSULT THE APPROPRIATE

SUPPLIER'S EQUIPMENT MAINTENANCE, INSTALLATION, AND OPERATION MANUAL(S)

SUPPLIED WITH THE EQUIPMENT.

3. THERE ARE A TOTAL OF 8 KIRK KEYED SWITCHES BEING…

This is the start of the file's text. The full file is on GovTribe.