RFQ27006847 Warwick Level 3 EVSE Plans.pdf
PDF 5 MB Posted
- Solicitation number
- RFQ27006847
- Issued by
- Providence County, Providence City, Rhode Island
About this file
This file comprises electrical engineering plans and specifications for the installation of Level 3 Direct Current Fast Charging (DCFC) stations at the Warwick Park & Ride location in Warwick, Rhode Island, prepared by the Rhode Island Office of Energy Resources in coordination with the Department of Transportation. The project involves the installation of two 150-kilowatt DC fast chargers, each capable of simultaneously charging four electric vehicles, with associated electrical infrastructure, site work, and civil improvements. The plans include nine sheets covering site layout, electrical distribution, single-line diagrams, civil details, and electrical specifications. A mandatory pre-bid site visit is scheduled for July 29, 2026, at 9:00 a.m., with quotations due on August 14, 2026. The contract term includes five years of prepaid Commercial Cloud Plan Subscription with station management features and five years of ChargePoint Assure or equivalent maintenance coverage, with all equipment, labor, configuration services, and subscriptions to be bundled into a single vendor price.
The specifications require full compliance with the Rhode Island Standard Specifications for Road and Bridge Construction (2026 Edition), the National Electric Code (NFPA 70), National Electric Vehicle Infrastructure (NEVI) requirements, and the National Electric Safety Code (NESC). All work must conform to current Rhode Island State Building and Electrical Codes and be performed by licensed contractors with UL-listed and labeled equipment and materials. The electrical contractor is responsible for field verification of all measurements, coordination of conduit routing, maintenance of existing facility operations, provision of temporary connections between new and existing work at no additional cost, and submission of electrical permit applications to the owner. General notes specify minimum 3/4-inch conduit sizing, proper grounding and bonding of all metallic raceways, separation of control and power cables into distinct conduits, and fire-rated sealing of all penetrations through fire-rated walls and floors. The project location is 292 Centerville Road, Warwick, Rhode Island, with no specific contract value or evaluation criteria provided in the plans.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R.I. CONTRACT NO. -- F.A. PROJECT NO. --
COVER SHEET
ABBREVIATIONS
GENERAL NOTES AND SYMBOLS
WARWICK SITE PLAN
WARWICK ELECTRICAL PLAN
WARWICK SINGLE LINE DIAGRAM - LEVEL 3 CHARGERS
CIVIL DETAILS SHEET 1
ELECTRICAL DETAILS SHEET 1
ELECTRICAL DETAILS SHEET 2
DESCRIPTION
SHEET NO.
INDEX
NEW EV CHARGING STATIONS - NEVI LEVEL 3 DCFC
WARWICK
CITY OF WARWICK
COUNTY OF KENT
RHODE ISLAND
OFFICE OF ENERGY RESOURCES
DEPARTMENT OF TRANSPORTATION
COVER SHEET
NEW EV CHARGING STATIONS
NEVI LEVEL 3 DCFC
AT PARK & RIDE
R.I. STANDARD SPECIFICATIONS AND STANDARD DETAILS
SPECIFICATIONS TO GOVERN THIS PROJECT ARE THE R.I. STANDARD SPECIFICATIONS
FOR ROAD AND BRIDGE CONSTRUCTION, 2026 EDITION, AND THE STATE AND
FEDERAL SPECIAL PROVISIONS INCLUDED IN THE CONTRACT DOCUMENTS.
STANDARD DETAILS FOR THIS PROJECT ARE R.I. STANDARD DETAILS, 2025 EDITION,
WITH ALL REVISIONS.
ABBREVIATIONS
A, AMP AMPERE(S)
AC ALTERNATING CURRENT
ABS ABOVE BACK SPLASH
AF AMPERE FRAME (CIRCUIT BREAKER)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFU AMPERE FUSE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AM AMMETER
AS AMMETER SWITCH
AT AMPERE TRIP (CIRCUIT BREAKER)
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
A/V AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BKR BREAKER
BLDG BUILDING
BP BYPASS
BSC BIOLOGICAL SAFETY CABINET
C CONDUCTOR
C/CDT CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COAX COAXIAL CABLE
COL COLUMN
COMM COMMUNICATIONS
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CPU CENTRAL PROCESSING UNIT
CR CARD READER
CRT CATHODE RAY TUBE MONITOR
CS CONTROL SWITCH
CU COPPER
CUH CABINET UNIT HEATER
CT CURRENT TRANSFORMER
D DEPTH
DC DIRECT CURRENT
DCFC DIRECT CURRENT FAST CHARGERS
DDC DIRECT DIGITAL CONTROL
DEMO DEMOLITION
DIA DIAMETER
DN DOWN
DISC DISCONNECT
DIST DISTRIBUTION
DWG DRAWING
E ELECTRIC / EMERGENCY
EC ELECTRICAL CONTRACTOR, EMPTY CONDUIT
EF EXHAUST FAN
EL ELEVATION
ELECT, ELEC ELECTRICAL
ELEV ELEVATOR
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EO ELECTRICALLY OPERATED
EOL END OF LINE DEVICE
EPO EMERGENCY POWER OFF
EQ EQUAL
EQUIP EQUIPMENT
ABBREVIATIONS (CONTINUED)
ER EXISTING TO BE RELOCATED
EVSE ELECTRICAL VEHICLE SUPPLY EQUIPMENT
EWC ELECTRIC WATER COOLER
EX EXISTING TO REMAIN
F FLUSH
FA FIRE ALARM
FCC FIRE COMMAND CENTER
FCU FAN COIL UNIT
FDDI FIBER DISTRIBUTED DATA INTERFACE
FDR FEEDER
FH FUME HOOD
FIP FIELD INTERFACE PANEL
FIXT FIXTURE
FLA FULL LOAD AMPERES
FLR,FL FLOOR
FLUOR FLUORESCENT
FO FIBER OPTIC
FPB FAN POWERED BOX
FU FUSE
FUT FUTURE
FVR FULL VOLTAGE REVERSIBLE
FVNR FULL VOLTAGE NON-REVERSIBLE
G GROUND (CONDUCTOR)
GA GAUGE
GEN GENERATOR
GF GROUND FAULT
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND, GRD GROUND
GPS GENERATOR PARALLELING SWITCH GEAR
GRC GALVANIZED RIGID STEEL CONDUIT
HH HAND HOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC SWITCH
HP HORSEPOWER
HT HEIGHT
HWP HOT WATER PUMP
HV HIGH VOLTAGE
HZ HERTZ
I/INST INSTANTANEOUS
ICM INTERCOM MASTER
ICR INTERCOM REMOTE
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INSTR INSTRUMENT/INSTRUMENTATION
JB, JBOX JUNCTION BOX
K KEY LOCK (KEY INTERLOCK SCHEME)
KA KILOAMPERES
KCM THOUSAND CIRCULAR MILS
KEF KITCHEN EXHAUST FAN
KW KILOWATTS
KWH KILOWATT HOUR
KV KILOVOLTS
KVA KILOVOLT-AMPERES
KVAR KVA REACTIVE
L LOCKING TYPE/LOAD
LA LIGHTING SURGE ARRESTER
LAB LABORATORY
LAN LOCAL AREA NETWORK
LT LONG TIME
LTG LIGHTING
LP LIGHTING PANEL
M METER
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
ABBREVIATIONS (CONTINUED)
MCCB MOLDED CASE CIRCUIT BREAKER
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MI MINERAL-INSULATED
MIC MEDIA INTERFACE CONNECTOR
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MILLIMETER
MM2 MILLIMETER SQUARED
MPS MANUAL PULL STATION
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
N NEUTRAL/NORMAL
NC NORMALLY-CLOSED
NEC NATIONAL ELECTRIC CODE
NEVI NATIONAL ELECTRIC VEHICLE INFRASTRUCTURE
NIC NOT IN CONTRACT
NO NORMALLY-OPEN / NUMBER
NORM NORMAL
NTS NOT TO SCALE
NWP NETWORK PROTECTOR
OCB OIL CIRCUIT BREAKER
OL OVERLOAD(S)
OC ON-CENTER
OS OCCUPANCY SENSOR
POLE POLE
PA PUBLIC ADDRESS SYSTEM
PB PUSHBUTTON/PULLBOX
PBX PRIVATE BRANCH EXCHANGE
PC PHOTOCELL
PDU POWER DISTRIBUTION UNIT
PF POWER FACTOR
PFCC POWER FACTOR CORRECTION CAPACITORS
PH PHASE
PNL PANEL
PP POWER PANEL
PR PAIR
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PWR POWER
QTY QUANTITY
RE REMOVE EXISTING
REC, RECPT RECEPTACLE
REPO REMOTE E.P.O.
REQ, REQD REQUIRED
RF RETURN FAN
RIM READER INTERFACE MODULE
RM ROOM
RO REVERSE-OSMOSIS
RP RECEPTACLE PANEL
RVAT REDUCED VOLTAGE AUTOTRANSFORMER
RTU REMOTE TERMINAL UNIT
RUPS ROTARY UPS
SCA SHORT CIRCUIT AMPERES
SD SMOKE DETECTOR
SEC SECONDARY
SF SUPPLY FAN
SF6 SULFERHEXAFLORIDE
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
ABBREVIATIONS (CONTINUED)
SPKR SPEAKER
SS STAINLESS STEEL/SOLID STATE
ST SHUNT TRIP/SHORT TIME
STD STANDARD
STP SHIELDED TWISTED PAIR
STS STATIC TRANSFER SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
T TRANSFORMER
TB TERMINAL BLOCK
TELECOM TELECOMMUNICATIONS
TDR TIME DOMAIN REFLECTOMETER
TEF TOILET EXHAUST FAN
TEL, TELE TELEPHONE
TR TELEPHONE ROOM
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UC UNDER-COUNTER
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
V VOLT(S)
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME BOX
VFD VARIABLE FREQUENCY DRIVE
VM VOLTMETER
VS VOLTMETER SWITCH
W WIRE/WATT/WIDTH
W/ WITH
WCR WITHSTAND CURRENT RATING
WD WALKER DUCT
WM WATTMETER
WP WEATHERPROOF
WT WATERTIGHT
XFMR TRANSFORMER
XP EXPLOSION-PROOF
ZI ZONE INTERLOCKING
ΔY DELTA-WYE
2S2W TWO SPEED TWO WINDING
2SR2W TWO SPEED REVERSING TWO WINDING
RHODE ISLAND
OFFICE OF ENERGY RESOURCES
DEPARTMENT OF TRANSPORTATION
ABBREVIATIONS
NEW EV CHARGING STATIONS
NEVI LEVEL 3 DCFC
AT PARK & RIDE
GENERAL NOTES:
1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE SPECIFICATIONS, DRAWINGS
LATEST EDITION OF THE NATIONAL ELECTRIC CODE (NFPA 70), NATIONAL ELECTRIC
VEHICLE INFRASTRUCTURE (NEVI) REQUIREMENTS, NATIONAL ELECTRIC SAFETY CODE
(NESC), AND THE REGULATIONS OF OTHER AUTHORITIES HAVING JURISDICTION.
2. LOCATIONS OF EQUIPMENT AND RACEWAYS UNLESS SPECIFICALLY DIMENSIONED ARE
APPROXIMATE ONLY. CONTRACTOR SHALL ESTABLISH EXACT LOCATION IN THE FIELD TO
CLEAR ALL OBSTACLES.
3. CONDUITS, JUNCTION BOXES AND OTHER ELECTRICAL EQUIPMENT INSTALLED SHALL NOT
INTERFERE WITH THE OPERATION OF WINDOWS, DOORS, CRANES, ETC.
4. ALL METALLIC CONDUITS AND RACEWAYS SHALL BE ELECTRICALLY CONTINUOUS AND
GROUNDED.
5. ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALL AND FLOORS SHALL BE
SEALED WITH FIRE RESISTANT SEALANT.
6. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN OPERATION OF EXISTING FACILITIES AS
REQUIRED. PROVIDE NECESSARY TEMPORARY CONNECTIONS BETWEEN NEW AND
EXISTING WORK, AT NO ADDITIONAL COST.
7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING DEVICES REQUIRED BY N.E.C.
INCLUDING BUT NOT LIMITED TO DISCONNECT SWITCHES, ETC.
8. PULL BOXES SHALL BE SIZED, FURNISHED AND INSTALLED AS REQUIRED BY THE N.E.C.
PROVIDE PULL BOXES OR PULL TYPE CONDUITS AS REQUIRED TO CONFORM TO N.E.C.
DETERMINE WHETHER TO USE A SINGLE PULL BOX, GROUP OF PULL BOXES OR PULL
CONDULETS BASED ON ACTUAL FIELD CONDITIONS AND AS APPROVED BY THE ENGINEER.
9. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT EVERY PULL BOX,
DETAIL OR EXACT LOCATION OF EQUIPMENT OR CONDUIT IS SHOW. EXISTING CONDITIONS
SHALL BE VERIFIED IN THE FIELD PRIOR TO COMMENCING ANY FABRICATION, ORDERING
ANY MATERIAL, OR PERFORMING ANY WORK. ANY DEPARTURE FROM CONCEPT SHOWN
ON THE CONTRACT DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
10. UPDATE ALL PANEL DIRECTORIES WHERE EXISTING CIRCUITS ARE MODIFIED.
11. ALL WIRING AND EQUIPMENT SHALL BE UL LISTED & LABELED, NEW AND INSTALLED IN
CONFORMANCE WITH THE LATEST RHODE ISLAND STATE BUILDING AND ELECTRICAL
CODES AND NFPA 72.
12. THESE ARE STANDARD COVER SHEET ABBREVIATION LISTS AND SYMBOLS. DISREGARD
UNUSED ABBREVIATIONS AND SYMBOLS.
13. PATCHING AND MAINTAINING FIRE RATINGS ARE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR.
14. ELECTRICAL CONTRACTOR SHALL COORDINATE ROUTING OF CONDUITS AND THE
INSTALLATION OF JUNCTION BOXES IN THE FIELD.
15. UNLESS OTHERWISE INDICATED, ALL WIRING SHALL BE IN ACCORDANCE WITH
MANUFACTURER RECOMMENDATIONS. CONDUIT SHALL BE 3/4" MINIMUM.
16. THE DRAWINGS ARE SCHEMATIC AND ARE NOT INTENDED TO SHOW ALL EXISTING
INTERIOR WALLS OR EVERY PROPOSED OFFSET OF FITTING. THE DRAWINGS ARE NOT
INTENDED TO SERVE AS SHOP DRAWINGS.
17. ELECTRICAL CONTRACTOR TO FURNISH A COPY OF THE ELECTRICAL PERMIT
APPLICATION AND COMPLETED PERMIT TO THE OWNER.
18. ELECTRICAL CONTRACTOR SHALL IMMEDIATELY CHECK ALL DRAWINGS FURNISHED UPON
THEIR RECEIPT AND SHALL PROMPTLY NOTIFY THE AUTHORITY OF ANY DISCREPANCIES.
19. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL MEASUREMENT BEFORE LAYING OUT
THE WORK AND SHALL BE RESPONSIBLE FOR ANY ERRORS WHICH MIGHT HAVE BEEN
AVOIDED THEREBY.
20. PROVIDE 10 AWG PHASE, NEUTRAL, AND GROUND CONDUCTORS FOR 120 VOLT, 20
AMPERE BRANCH CIRCUITS EXCEEDING 100 FEET AND FOR 277 VOLT, 20 AMPERE
CIRCUITS EXCEEDING 200 FEET.
21. VERIFY EXACT MOUNTING CONDITIONS AND PROVIDE APPROPRIATE ACCESSORIES AND
HARDWARE TO ACCOMMODATE REQUIREMENTS.
22. PROVIDE A GROUND CONDUCTOR IN EACH ELECTRICAL RACEWAY IN ACCORDANCE WITH
THE LATEST NATIONAL ELECTRICAL CODE AS FOLLOWS:
A. EQUIPMENT GROUND WIRES (INSULATED GREEN CONDUCTORS) SHALL BE PROVIDED IN
ALL FEEDERS AND ALL BRANCH CIRCUITS.
B. ALL FLEXIBLE METAL OR LIQUID-TIGHT CONDUIT CONNECTIONS TO EQUIPMENT MOTORS,
LIGHTING FIXTURES, ETC. SHALL CONTAIN EQUIPMENT GROUND WIRES. FLEXIBLE METAL
CONDUIT SHALL NOT BE USED AN AN EQUIPMENT GROUND CONDUCTOR.
C. ALL DEVICES, EQUIPMENT, FIXTURES, ETC. SHALL BE GROUNDED BY THE USE OF A
PROPERLY SIZED EQUIPMENT GROUNDING CONDUCTOR. MECHANICAL/ELECTRICAL
BONDS OF THE METALLIC RACEWAY SYSTEM SHALL ALSO BE MAINTAINED.
23. CONTROL AND POWER CABLES SHALL RUN IN SEPARATE CONDUITS.
HARD-WIRED CONNECTION
JUNCTION BOX
PANELBOARD
DISTRIBUTION/POWER PANEL
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MAGNETIC MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
EMERGENCY POWER OFF
GROUND ROD
START STOP PUSHBUTTON
RAISE-LOWER PUSHBUTTON WITH CENTER STOP
DRAWOUT CIRCUIT BREAKER OVER 600V
DRAWOUT CIRCUIT BREAKER
CIRCUIT BREAKER
DISCONNECT SWITCH
FUSED DRAWOUT CIRCUIT BREAKER
FUSE
0/
5 3
50/5
LIGHTNING ARRESTOR
TRANSFORMER CONNECTION
DELTA-
RESISTANCE GROUNDED WYE
TRANSFORMER
CONNECTION
DELTA-GROUNDED WYE
STATIC BYPASS SWITCH
GENERATOR
AUTOMATIC TRANSFER SWITCH
AUTOMATIC TRANSFER
AND
BYPASS ISOLATION
SWITCH
PANELBOARD
K
AM
AS
VM
VS
AMMETER
AMMETER SWITCH
VOLTMETER
VOLTMETER SWITCH
WM WATTMETER
KWH KILOWATT-HOUR METER WITH 15 MIN.
DEMAND REGISTER
KVH KILOVAR HOUR METER
PF POWER FACTOR METER
TB TERMINAL BLOCK
CS CONTROL SWITCH
CONTACT
PUSH-PLATE FOR AUTOMATIC DOOR
TC
DRAWOUT FUSES
MANHOLE
HANDHOLE
BATTERY
FEEDER CONNECTION REFERENCE
(1) MI CABLE, SINGLE CONDUCTOR
(1) MI CABLE, THREE CONDUCTOR
(3) MI CABLES, SINGLE CONDUCTOR EACH
1 MI
CABLE,1/
C
1 MI
CABLE,3/C
3 MI
CABLES,1/C
P F
MOTOR CONNECTION
WIRE/CONDUIT EXPOSED
FUSED DISCONNECT SWITCH
CIRCUIT BREAKER, ELECTRIC OPERATED.
F T
F F
G GROUNDING CONDUCTOR, SIZE AS INDICATED.
GROUND BUS
P
T
EQUIPMENT IDENTIFICATION TAGS
JB
POWER POLE
2W20
(20/2)
RP5-7,9
TRANSFORMER, (SEE
TRANSFORMER
SCHEDULE ON COVER SHEET 2)
WALL MOUNTED JUNCTION BOX FOR TEL/DATA/PWR
TO DEMOUNTABLE PARTITION WITH WHIP.
WHIP FURNISHED BY OTHERS, AND INSTALLED BY DIV. 16.
FIRE RATED THRU-FLOOR FITTING FOR TEL/DATA/POWER
TO DEMOUNTABLE PARTITION, WITH WHIP.
WHIP FURNISHED BY OTHERS, AND INSTALLED BY DIV. 16.
(F) INDICATES FLUSH MOUNTED.
FIRE RATED THROUGH-FLOOR FITTING WITH DEVICE AS
INDICATED.
(F) INDICATES FLUSH MOUNTED.
MULTI-OUTLET RACEWAY WITH RECEPTACLE.
TYPE AND CIRCUIT DESIGNATION AS
INDICATED
WIRE/CONDUIT CONCEALED
UNDERGROUND DUCT BANK - COMMUNICATION/DATA/TELEPHONE
RELAY
SEE RELAY SCHEDULE ON COVER SHEET 2.
DRAWOUT CIRCUIT BREAKER, ELECTRIC OPERATED.
CURRENT TRANSFORMER, QUANTITY AND
RATIO
AS INDICATED.
GROUND CURRENT, ZERO SEQUENCE
TYPE
TRANSFORMER. RATIO AS INDICATED.
POTENTIAL TRANSFORMER, QUANTITY AS INDICATED.
DRAWOUT POTENTIAL TRANSFORMER,
QUANTITY
AS INDICATED.
MULTIFUNCTION METER AS SPECIFIED.
A
SHIELDED K RATED POWER
TRANSFORMER
WITH VOLTAGES AS INDICATED
POWER TRANSFORMER WITH
VOLTAGES
AS INDICATED
JB
LIGHTNING PROTECTION THROUGH ROOF DOWN CONDUCTOR
LIGHTNING PROTECTION AIR TERMINAL
EO
E0
E0
L.A.
GEN
T30 CEILING MOUNTED TRANSFORMER
VARIABLE FREQUENCY DRIVE
VARIABLE FREQUENCY DRIVE WITH BYPASS
SPD
HOME RUN INDICATION WITH PANEL DESIGNATION (RP5), CIRCUIT
No.(7)&(9), OVERCURRENT PROTECTION "AMPS AND POLES" (20/2)
AND WIRE/CONDUIT DESIGNATION (2W20). SEE WIRE AND CONDUIT
SIZE SCHEDULE. PROVIDE 20A/1P AND 2 #12 FOR EACH HOMERUN
ARROW & 1 #12G IN 3/4 " CONDUIT, UNLESS OTHERWISE INDICATED.
SEE GENERAL NOTE 1.
POWER FACTOR CORRECTION CAPACITOR
CB
T1
VFD
VFD
BP
MH
HH
M
E
N E
L
N E
L
50N 51N
225A
SPD
INDICATES - MAIN CIRCUIT BREAKER (MCB)
PANEL AMPERAGE
PANEL VOLTAGE
PANEL NAME
PANEL WITH SURGE PROTECTIVE DEVICE
MOTORXX
HP
MAIN CONDUCTOR
120/208V
HARD-WIRED CONNECTION
JUNCTION BOX
PANELBOARD
DISTRIBUTION/POWER PANEL
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MAGNETIC MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
EMERGENCY POWER OFF
GROUND ROD
START STOP PUSHBUTTON
RAISE-LOWER PUSHBUTTON WITH CENTER STOP
DRAWOUT CIRCUIT BREAKER OVER 600V
DRAWOUT CIRCUIT BREAKER
CIRCUIT BREAKER
DISCONNECT SWITCH
FUSED DRAWOUT CIRCUIT BREAKER
FUSE
0/
5 3
50/5
LIGHTNING ARRESTOR
TRANSFORMER CONNECTION
DELTA-
RESISTANCE GROUNDED WYE
TRANSFORMER
CONNECTION
DELTA-GROUNDED WYE
STATIC BYPASS SWITCH
GENERATOR
AUTOMATIC TRANSFER SWITCH
AUTOMATIC TRANSFER
AND
BYPASS ISOLATION
SWITCH
PANELBOARD
GROUND CONNECTION
K KEY INTERLOCK
AM
AS
VM
VS
AMMETER
AMMETER SWITCH
VOLTMETER
VOLTMETER SWITCH
WM WATTMETER
KWH KILOWATT-HOUR METER WITH 15 MIN.
DEMAND REGISTER
KVH KILOVAR HOUR METER
PF POWER FACTOR METER
TB TERMINAL BLOCK
CS CONTROL SWITCH
CONTACT
PUSH-PLATE FOR AUTOMATIC DOOR
TC
DRAWOUT FUSES
MANHOLE
HANDHOLE
BATTERY
FEEDER CONNECTION REFERENCE
ELECTRICAL SYMBOLS SINGLE LINE DIAGRAM SYMBOLS
(1) MI CABLE, SINGLE CONDUCTOR
(1) MI CABLE, THREE CONDUCTOR
(3) MI CABLES, SINGLE CONDUCTOR EACH
1 MI
CABLE,1/
C
1 MI
CABLE,3/C
3 MI
CABLES,1/C
P F
MOTOR CONNECTION
WIRE/CONDUIT EXPOSED
FUSED DISCONNECT SWITCH
CIRCUIT BREAKER, ELECTRIC OPERATED.
ELECTRIC INTERLOCK
F T
F F
G GROUNDING CONDUCTOR, SIZE AS INDICATED.
GROUND BUS
P
T
EQUIPMENT IDENTIFICATION TAGS
JB
POWER POLE
2W20
(20/2)
RP5-7,9
TRANSFORMER, (SEE
TRANSFORMER
SCHEDULE ON COVER SHEET 2)
WALL MOUNTED JUNCTION BOX FOR TEL/DATA/PWR
TO DEMOUNTABLE PARTITION WITH WHIP.
WHIP FURNISHED BY OTHERS, AND INSTALLED BY DIV. 16.
FIRE RATED THRU-FLOOR FITTING FOR TEL/DATA/POWER
TO DEMOUNTABLE PARTITION, WITH WHIP.
WHIP FURNISHED BY OTHERS, AND INSTALLED BY DIV. 16.
(F) INDICATES FLUSH MOUNTED.
FIRE RATED THROUGH-FLOOR FITTING WITH DEVICE AS
INDICATED.
(F) INDICATES FLUSH MOUNTED.
MULTI-OUTLET RACEWAY WITH RECEPTACLE.
TYPE AND CIRCUIT DESIGNATION AS
INDICATED
WIRE/CONDUIT CONCEALED
UNDERGROUND DUCT BANK - COMMUNICATION/DATA/TELEPHONE
RELAY
SEE RELAY SCHEDULE ON COVER SHEET 2.
DRAWOUT CIRCUIT BREAKER, ELECTRIC OPERATED.
ENCLOSED FUSED DISCONNECT SWITCH, ELECTRIC
OPERATED.
CURRENT TRANSFORMER, QUANTITY AND
RATIO
AS INDICATED.
GROUND CURRENT, ZERO SEQUENCE
TYPE
TRANSFORMER. RATIO AS INDICATED.
POTENTIAL TRANSFORMER, QUANTITY AS INDICATED.
DRAWOUT POTENTIAL TRANSFORMER,
QUANTITY
AS INDICATED.
MULTIFUNCTION METER AS SPECIFIED.
A
SHIELDED K RATED POWER
TRANSFORMER
WITH VOLTAGES AS INDICATED
POWER TRANSFORMER WITH
VOLTAGES
AS INDICATED
JB
LIGHTNING PROTECTION THROUGH ROOF DOWN CONDUCTOR
LIGHTNING PROTECTION AIR TERMINAL
EO
E0
E0
L.A.
THERMAL OVERLOADS
GEN
T30 CEILING MOUNTED TRANSFORMER
VARIABLE FREQUENCY DRIVE
VARIABLE FREQUENCY DRIVE WITH BYPASS
SPD SURGE PROTECTION DEVICE
WIRE/CONDUIT CONCRETE ENCASED, DIRECT BURIED, UNDERGROUND
DUCT BANK
HOME RUN INDICATION WITH PANEL DESIGNATION (RP5), CIRCUIT
No.(7)&(9), OVERCURRENT PROTECTION "AMPS AND POLES" (20/2)
AND WIRE/CONDUIT DESIGNATION (2W20). SEE WIRE AND CONDUIT
SIZE SCHEDULE. PROVIDE 20A/1P AND 2 #12 FOR EACH HOMERUN
ARROW & 1 #12G IN 3/4 " CONDUIT, UNLESS OTHERWISE INDICATED.
SEE GENERAL NOTE 1.
POWER FACTOR CORRECTION CAPACITOR
CB
T1
VFD
VFD
BP
MH
HH
M
E
N E
L
N E
L
50N 51N
225A
SPD
INDICATES - MAIN CIRCUIT BREAKER (MCB)
PANEL AMPERAGE
PANEL VOLTAGE
PANEL NAME
PANEL WITH SURGE PROTECTIVE DEVICE
MOTORXX
HP
MAIN CONDUCTOR
120/208V
SINGLE LINE DIAGRAM SYMBOLS CONTINUED
LEVEL 2 ELECTRIC VEHICLE CHARGER
LEVEL 3 ELECTRIC VEHICLE CHARGER
RHODE ISLAND
OFFICE OF ENERGY RESOURCES
DEPARTMENT OF TRANSPORTATION
GENERAL NOTES
AND SYMBOLS
NEW EV CHARGING STATIONS
RHODE ISLAND
OFFICE OF ENERGY RESOURCES
DEPARTMENT OF TRANSPORTATION
WARWICK
SITE PLAN
NEW EV CHARGING STATIONS
NEVI LEVEL 3 DCFC
AT PARK & RIDE
ELECTRIC
CAR PARKING
ONLY WHILE
CHARGING
CHARGING
STATION
CHARGING
STATION
ELECTRIC CAR
PARKING
ONLY
WHILE CHARGING
ELECTRIC
CAR PARKING
ONLY WHILE
CHARGING
CHARGING
STATION
CHARGING
STATION
ELECTRIC CAR
PARKING
ONLY
WHILE CHARGING
DEPARTMENT OF TRANSPORTATION
WARWICK
ELECTRICAL PLAN
NEW EV CHARGING STATIONS
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
ET
H
ER
N
ET
VD
C A
U X.
BU
S
A1
0V
D C
BU
S
B1
0V
D C
0A
C
SS
VD
C
A U
X.
ET
H
ER
N
ET
VD
C
VD
C
0A
C
SS
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
ET
H
ER
N
ET
VD
C A
U X.
BU
S
A1
0V
D C
BU
S
B1
0V
D C
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
ET
H
ER
N
ET
VD
C A
U X.
BU
S
A1
0V
D C
BU
S
B1
0V
D C
0A
C
SS
VD
C
A U
X.
ET
H
ER
N
ET
VD
C
VD
C
0A
C
SS
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
ET
H
ER
N
ET
VD
C A
U X.
BU
S
A1
0V
D C
BU
S
B1
0V
D C
RHODE ISLAND
OFFICE OF ENERGY RESOURCES
DEPARTMENT OF TRANSPORTATION
WARWICK
SINGLE LINE DIAGRAM
LEVEL 3 CHARGERS
NEW EV CHARGING STATIONS
DEPARTMENT OF TRANSPORTATION
CIVIL
DETAILS SHEET 1
NEW EV CHARGING STATIONS
NEVI LEVEL 3 DCFC
AT PARK & RIDE
CHARGING
STATION
ELECTRIC CAR
PARKING
ONLY
WHILE CHARGING
CHARGING
STATION
ELECTRIC CAR
PARKING
ONLY
WHILE CHARGING
OFFICE OF ENERGY RESOURCES
DEPARTMENT OF TRANSPORTATION
ELECTRICAL
DETAILS SHEET 1
NEW EV CHARGING STATIONS
DEPARTMENT OF TRANSPORTATION
ELECTRICAL
DETAILS SHEET 2
NEW EV CHARGING STATIONS
| Sheets and Views |
| RIEV-Phase 4_Cover Sheet (Warwick)-Sheet |
| RIEV-Phase 4_Abbreviations (Warwick)-Sheet |
| RIEV-Phase 4_General Notes And Symbols (Warwick)-Sheet |
| RIEV-Phase 4_Site Plan (Warwick)-Sheet |
| RIEV-Phase 4_Electrical Plan (Warwick)-Sheet |
| RIEV-Phase 4_Single Line Diagram (Warwick Park and Ride)-Sheet |
| RIEV-Phase 4_Civil Details (Warwick)-Sheet |
| RIEV-Phase 4_Electrical Details (Warwick)-Sheet |
| RIEV-Phase 4_Electrical Details 2 (Warwick)-Sheet |
File details come from the government source that posted it. Updated .