RFQ 24_001 ADDENDUM _2.pdf

PDF 296 KB Posted

Attached to
RFQ 24-001 Water Tank Painting and Inspection
Solicitation number
PE-77111-NONST-2024-000000001
Issued by
Jasper County, Georgia

About this file

This document is an addendum to a Request for Quotation (RFQ) issued by the City of Commerce for the Bowden Street Tank Painting and Inspection project. The addendum provides details on the scope of work, which includes interior and exterior surface preparation and coating application requirements. For the interior, the work involves abrasive blasting to a near-white metal finish and application of a three-coat system with a total dry film thickness of 10.5-15.5 mils. For the exterior, the work includes abrasive blasting to a commercial finish and application of a three-coat system with a total dry film thickness of 6-9 mils. Additionally, the addendum outlines the requirements for an exterior overcoat system, which involves high-pressure water blasting, power tool cleaning, and application of a three-coat system with a minimum dry film thickness of 5 mils.

The addendum clarifies that this document should be signed and returned with the proposal, and failure to do so may result in the proposal being deemed non-responsive.

View the file

Other files

File Type Posted
Bid Evaluation 24_001.pdf PDF
RFQ 24_001 ADDENDUM 7.pdf PDF
RFQ 24_001 Bowden St Tank.pdf PDF
RFQ 24_001 ADDENDUM 5.pdf PDF
NOIA.pdf PDF
RFQ 24_001 ADDENDUM _4.pdf PDF
RFQ 24_001 ADDENDUM 8.pdf PDF
RFQ 24_001 ADDENDUM _1.pdf PDF
RFQ 24_001 ADDENDUM _3.pdf PDF
Tally Sheet 24_001.pdf PDF
RFQ 24_001 ADDENDUM 6.pdf PDF
24_001 NOA.pdf PDF
RFQ 24_001 ADDENDUM 9.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM #2

RFQ 24-001

Bowden Street Tank Painting and Inspection

This addendum is being issued to address questions submitted on RFQ 24-001

Q1. Can you please provide a comprehensive listing of the Scope of Work we would be bidding?

A1. Interior Full Blast Surface Preparation – Abrasive blast to a SSPC-SP10 Near White Metal Blast standard. Prior to coating the substrate must be clean, dry and free of all contaminants.

1st Coat – Tnemec Series 91/94 or equivalent applied at 2.5-3.5 mils dry Stripe Coat - Tnemec Series N140-15BL or equivalent applied at 2-3 mils dry 2nd Coat – Tnemec Series 21-WH16 or equivalent applied at 10-12 mils dry Total Dry Film Thickness – 10.5-15.5 mils dry

Exterior Full Blast Surface Preparation – Abrasive blast to a SSPC-SP6 Commercial Blast standard. Prior to coating the substrate must be clean, dry and free of all contaminants.

1st Coat – Tnemec Series 91/94 or equivalent applied at 2-3 mils dry 2nd Coat – Tnemec Series N69 or equivalent applied at 2-3 mils dry 3rd Coat – Tnemec Series 1094 or equivalent applied at 2-3 mils dry Total Dry Film Thickness – 6-9 mils dry

Exterior Overcoat System Surface Preparation – High Pressure Water Blast at a minimum 3,000 psi. Power tool clean (SSPC-SP3) all visible rusty areas. Feather all edges. Prior to coating the substrate must be clean, dry and free of all contaminants.

Spot Prime (visible rusty areas) – Tnemec Series 135 or equivalent applied at 3 mils dry 1st Coat – Tnemec Series 135 or equivalent applied at 3 mils dry 2nd Coat – Tnemec Series 1094 or equivalent applied at 2-3 mils dry Total Minimum Dry Film Thickness – 5 mils dry

This addendum should be signed and returned with your proposal. Failure to do so may result in the proposal being non-responsive.

Christy Case Finance Director City of Commerce

Company Name __________________________________________________________