RFB936000-01 Drawings.pdf

PDF 2 MB Posted

Attached to
IPBS Fire Alarm Replacement
Solicitation number
RFB936000-01
Issued by
Muscatine County, Iowa

About this file

These are construction documents for a fire alarm replacement project for the Iowa Public Broadcasting System (IPBS), prepared by KCL Engineering for the Iowa Department of Administrative Services (DAS) located at 6450 Corporate Drive in Johnston, Iowa. The project involves a comprehensive update to the existing fire alarm system throughout a two-story building with partial sprinkler coverage, with no modifications to the building's existing configuration. The documents include detailed demolition plans, fire detection and alarm plans for the west and east wings, and a mezzanine level, with specific instructions for removing existing fire alarm components and installing new devices, notification appliances, and control panels.

The project involves replacing the current fire alarm system while maintaining the building's existing occupancy classifications (A-1 and B) and adhering to multiple building codes, including the 2015 International Building Code, 2015 International Fire Code, and 2017 National Electrical Code. The total building area is 56,823 square feet, with 48,782 square feet classified as B occupancy and 8,041 square feet as A-1 occupancy. The construction documents provide specific guidance for contractors, including detailed notes on device installation, reuse of existing conduits and pathways, coordination requirements, and alternates for potential cost adjustments, such as reusing existing notification devices.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that i am a duly licensed Professional Engineer under the laws of the State of Iowa

(signature)

License Number :

Pages or sheets covered by this seal:

(date)

My license renewal date is December 31, E N

G N

E E

R I

AOFESSION

S E

D

PR

AI O W

L

IC

E N

L

ERIC HEYNEN, P.E.

ERIC

HEYNEN

E. Sheets

P24706P24706

SHEET LIST

G001 LIFE SAFETY AND CODE SUMMARY

E000 ELECTRICAL GENERAL NOTES & SYMBOLS

ED101 FIRE ALARM DEMOLITION - WEST

ED102 FIRE ALARM DEMOLITION - EAST

ED103 FIRE ALARM DEMO AND NEW - MEZZANINE

E101 FIRE DETECTION & ALARM PLANS - WEST

E102 FIRE DETECTION & ALARM PLANS - EAST

OWNER

IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES

109 SE 13TH STREET

DES MOINES, IA 50319

OWNER PROJECT NUMBER: 9360.00

CONSTRUCTION MANAGER

ADAM DOUGLAS - PROJECT EXECUTIVE

MCGOUGH

217 E 2ND STREET, SUITE 120

DES MOINES, IOWA 50309

ENGINEER

ERIC HEYNEN, PE

KCL ENGINEERING

eheynen@kclengineering.com 515-300-8092

ENGINEER PROJECT NUMBER: 23249

1/29/2024 9:27:07 AM

CONSTRUCTION DOCUMENTS

2/1/2024

STATE OF IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES

9360.00 IOWA PBS FIRE ALARM REPLACEMENT

VICINITY MAP:

6450 CORPORATE DRIVE

JOHNSTON, IOWA 50131

M E

R L

E H

A Y

R O

A D

NW 62ND AVE

6450 CORPORATE DR

2/1/2024

APPLICABLE CODE INFORMATION

Building Characteristics

Project description: Project involves the update to the existing fire alarm system in the building. No other modifications to the building configuration to be done.

Building Area: 56,823 SF Building Height: 33'-0" Number of Stories: 2 (see below for detailed information) Fully Sprinkled: Partial Fire Alarm: Yes - Project specific to update fire alarm system throughout the building.

IC Chapter 3 - Use and Occupancy Classification

Occupancy Group: A-1, B (Nonseparated occupancy use)

IBC Chapter 4 - Special Detailed Requirements Based on Use and Occupancy No changes to existing building.

Building will continue to comply with applicaple requirements of Section 410.

IBC Chapter 5 - General Building Heights and Areas

Occupancy Group B Building Height: 33'-0" Number of Stories: 2 Building Area: 48,782 SF

Occupancy Group A-1 Building Height: 33'-0" Number of Stories: 1 Building Area: 8,041 SF

507 Unlimited Area Buildings No changes to existing building.

IBC Chapter 6 - Types of Construction Construction Classification: Type IIB - No changes to existing building.

Table 601 Fire Resistance Rating Required

Primary Structural Frame 0 HR Bearing Walls 0 HR Nonbearing Wall and Partition (Exterior) 0 HR Nonbearing Wall and Partitions (Interior) 1 HR - Corridor Construction Floor Construction and Secondary Members 0 HR Roof Construction and Secondary Members 0 HR

IBC Chapter 7 - Fire and Smoke Protection Features

705 Exterior Walls No changes to existing building.

713 Shaft Enclosures No changes to existing building.

IBC Chapter 9 - Fire Protection Systems

903 Automatic Sprinkler Systems Partial

- Partial coverage provided at Studio B and Scene shop only. No changes to existing building.

906 Portable Fire Extinguishers Required/Provided - No changes to existing building.

IBC Chapter 10 - Means of Egress No changes to existing building.

2015 International Energy Conservation Code No changes to existing building.

Iowa Administrative Code, Chapter 16, Division VII - Accessibility Requirements For Facilities Used by the General Public:

No changes to existing building.

Accessibility within the building will be maintained.

Plumbing Fixture Requirements per 2015 Uniform Plumbing Code (UPC) No changes to existing building.

The project shall comply with the following codes:

2015 International Building Code 2015 International Mechanical Code 2015 International Fire Code 2017 National Electrical Code 2015 Uniform Plumbing Code and the Iowa State Plumbing Code Iowa State Energy Code, 2015 International Energy Conservation Code Accessibility - Division 7 of Iowa State Building Code, Iowa State Accessibility Code, 2015 IBC and ANSI A117.1 - 2009 Edition

A

A

B B

C C

D D

ADMINISTRATION

COMMUNICATIONS

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

BOARDROOM

PRODUCTION

EDUCATION

VIDEO TAPE

LIBRARY

NETWORK

VIDEO

CENTER

TECH EQUIP.

CENTER

NETWORK

CONTROL

CENTER

AVID 5

FINAL CUT 4

EDIT SERVER

AVID 6

AVID 1

AVID 2

LUNCH ROOM

VENDING

1158VEST.

1155A

STORAGE

ROOM

WOMENS

MENS

ELEC. RM.

MECH RM.

CORRIDOR

EFP

FIBER

1169A

GENERAL

SERVICES

COMP.

ROOM

1170A

TECHNICAL

STORAGE

TECHNICAL

SHOP

PRODUCTION

SHOP

DESIGN

STUDIO 1

STUDIO 2

CC "B"

AUDIO PROD.

VIDEO

CONTROL 1

AUDIO

CONTROL 1

CONFERENCE

ROOM

FINAL CUT 1

FINAL CUT 2

FINAL CUT 3

1107 GREEN ROOM

OFFICE

OFFICE

OFFICE

OFFICE

COAT CLOSET

MENS

WOMEN

MAYTAG

LOBBY

VEST

STUDIO 3

MAYTAG

AUDITORIUM

SERVING

VIDEO ROOM

AUDIO ROOM

OFFICE

SOUTH CONF.

ROOM

MEETING

ROOM

1126AGRAPHICS &

DESIGN

MENS

WOMEN

CONF. ROOM

VEST.

DRESSING

DRESSING

DRESS.

MENS

WOMEN

DRESS.

VEST.

FINAL CUT 5

1138A

AVID 4

AVID 3

CC "A"

CORRIDOR

RECEIVING

MAIN LOBBY

JAN

CORRIDOR

ENGINEERING

VEST.

CORRIDOR

CLOSET

UPS RM.

STOR.

1104A

STOR.

1104B

VEST

VEST

1177A

ACCESS

CLOSET

JAN.

MOTION

GRAPHICS

DARK RM.

CORRIDOR

CORR.

VEST

CORR.

CORR.

STOR.

STOR.

1207A

HATCHED AREA INDICATES

PARTIAL AREA OF BUILING

THAT IS SPRINKLERED.

1 HOUR EXISTING

CORRIDOR

CONSTRUCTION - TYP.

2 HOUR EXISTING

SEPARATION BETWEEN FIRST

FLOOR AND EQUIPMENT

MEZZANINE - TYP.

C C

D D

CONDENSERS

EMERGENCY

GENERATOR

MECHANICAL

/ EQUIP.

EQUIP. ROOM

CONTROL

MECHANICAL

/ EQUIP.

2 HOUR EXISTING

SEPARATION BETWEEN FIRST

FLOOR AND EQUIPMENT

MEZZANINE - TYP.

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :3

P

M

G001

CD DOCUMENTS

2/1/2024

23844000

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T

LIFE SAFETY AND

CODE SUMMARY

3/64" = 1'-0"

LEVEL 1 OCCUPANCY PLAN

BUILDING OCCUPANCY COUNT

Level Number Name Area Occup ancy OLF

Occupant Load

A-1

Level 1 1179 MAYTAG AUDITORIUM 4962.48 SF A-1 15 340

15: 1 4962.48 SF 340

Level 1 1177 STUDIO 3 3078.39 SF A-1 35 90

35: 1 3078.39 SF 90

8040.87 SF 430

B

Level 1 1118 MENS 105.05 SF B 0

Level 1 1119 WOMEN 106.14 SF B 0

Level 1 1159 MENS 196.95 SF B 0

Level 1 1161 WOMENS 198.36 SF B 0

Level 1 1193 MENS 134.63 SF B 0

Level 1 1196 MENS 76.37 SF B 0

Level 1 1200 WOMEN 77.89 SF B 0

0: 7 895.39 SF 0

Level 1 1104 CONFERENCE ROOM 737.68 SF B 15

Level 1 1116 BOARDROOM 683.08 SF B 15

Level 1 1117 CONF. ROOM 204.84 SF B 15

Level 1 1125 SOUTH CONF. ROOM 317.91 SF B 15 130

15: 4 1943.50 SF 130

Level 1 1151 STUDIO 2 434.84 SF B 35

Level 1 1171 STUDIO 1 3462.59 SF B 35 112

35: 2 3897.43 SF 112

Level 1 1101 VEST. 66.04 SF B 150

Level 1 1102 MAIN LOBBY 1690.67 SF B 150

Level 1 1103 CORRIDOR 751.02 SF B 150

Level 1 1107 FINAL CUT 3 122.29 SF B 150

Level 1 1108 COMMUNICATIONS 2072.33 SF B 150

Level 1 1109 ADMINISTRATION 1183.59 SF B 150

Level 1 1110 OFFICE 184.60 SF B 150

Level 1 1111 OFFICE 185.20 SF B 150

Level 1 1112 OFFICE 185.79 SF B 150

Level 1 1114 OFFICE 206.38 SF B 150

Level 1 1115 OFFICE 275.72 SF B 150

Level 1 1120 PRODUCTION 4690.51 SF B 150

Level 1 1121 GRAPHICS & DESIGN 567.53 SF B 150

Level 1 1123 DARK RM. 82.57 SF B 150

Level 1 1126 OFFICE 206.93 SF B 150

Level 1 1126A MEETING ROOM 155.44 SF B 150

Level 1 1127 EDUCATION 3022.01 SF B 150

Level 1 1129 NETWORK VIDEO CENTER 1550.28 SF B 150

Level 1 1129 VEST. 50.65 SF B 150

Level 1 1130 CC "A" 42.32 SF B 150

Level 1 1131 AVID 2 88.06 SF B 150

Level 1 1134 AVID 1 95.88 SF B 150

Level 1 1135 AVID 6 96.69 SF B 150

Level 1 1136 AVID 3 74.12 SF B 150

Level 1 1137 AVID 4 74.74 SF B 150

Level 1 1138 EDIT SERVER 132.71 SF B 150

Level 1 1138A FINAL CUT 5 84.67 SF B 150

Level 1 1139 FINAL CUT 4 86.76 SF B 150

Level 1 1140 AVID 5 412.09 SF B 150

Level 1 1141 NETWORK CONTROL CENTER 242.23 SF B 150

Level 1 1142 TECH EQUIP. CENTER 682.07 SF B 150

Level 1 1143 VIDEO CONTROL 1 330.63 SF B 150

Level 1 1143 CORRIDOR 98.13 SF B 150

Level 1 1144 AUDIO CONTROL 1 198.23 SF B 150

Level 1 1145 CORR. 147.92 SF B 150

Level 1 1146 CORR. 185.97 SF B 150

Level 1 1147 VEST 97.56 SF B 150

Level 1 1148 CC "B" 139.37 SF B 150

BUILDING OCCUPANCY COUNT

Level Number Name Area Occup ancy OLF

Occupant Load

Level 1 1149 AUDIO PROD. 113.00 SF B 150

Level 1 1153 CORR. 409.95 SF B 150

Level 1 1154 TECHNICAL SHOP 505.86 SF B 150

Level 1 1155A VEST. 90.05 SF B 150

Level 1 1157 LUNCH ROOM 462.04 SF B 150

Level 1 1158 VENDING 145.63 SF B 150

Level 1 1160 JAN. 42.45 SF B 150

Level 1 1162 STORAGE ROOM 974.09 SF B 150

Level 1 1167 CORRIDOR 282.85 SF B 150

Level 1 1167A VEST. 84.51 SF B 150

Level 1 1168 RECEIVING 349.95 SF B 150

Level 1 1169 EFP 345.93 SF B 150

Level 1 1169A FIBER 248.61 SF B 150

Level 1 1174 DESIGN 145.59 SF B 150

Level 1 1175 DIMMER ROOM 101.93 SF B 150

Level 1 1176 VEST. 56.34 SF B 150

Level 1 1177A VEST 83.43 SF B 150

Level 1 1178 VEST. 116.85 SF B 150

Level 1 1180 AUDIO ROOM 263.08 SF B 150

Level 1 1181 VIDEO ROOM 231.19 SF B 150

Level 1 1182 SERVING 97.29 SF B 150

Level 1 1183 VEST 131.65 SF B 150

Level 1 1184 ACCESS 10.71 SF B 150

Level 1 1185 VEST 122.02 SF B 150

Level 1 1186 MAYTAG LOBBY 1160.88 SF B 150

Level 1 1188 DRESSING 141.41 SF B 150

Level 1 1189 CORRIDOR 403.10 SF B 150

Level 1 1190 DRESSING 148.66 SF B 150

Level 1 1192 COAT CLOSET 236.16 SF B 150

Level 1 1194 WOMEN 146.54 SF B 150

Level 1 1195 DRESS. 77.41 SF B 150

Level 1 1197 OFFICE 165.39 SF B 150

Level 1 1198 OFFICE 182.00 SF B 150

Level 1 1199 ENGINEERING 773.40 SF B 150

Level 1 1201 DRESS. 72.19 SF B 150

Level 1 1202 JAN 57.66 SF B 150

Level 1 1203 CORRIDOR 534.56 SF B 150

Level 1 1206 OFFICE 185.08 SF B 150

Level 1 1207 OFFICE 250.61 SF B 150

Level 1 1210 GREEN ROOM 121.48 SF B 150 205

150: 78 30631.24 SF 205

Level 2 1 MECHANICAL / EQUIP. 708.37 SF B 300

Level 2 2 CONDENSERS 834.46 SF B 300

Level 2 3 EMERGENCY GENERATOR 218.06 SF B 300

Level 2 4 MECHANICAL / EQUIP. 1395.83 SF B 300

Level 2 5 CONTROL 48.25 SF B 300

Level 2 6 EQUIP. ROOM 994.75 SF B 300

Level 1 1104A STOR. 36.78 SF B 300

Level 1 1104B STOR. 20.65 SF B 300

Level 1 1105 FINAL CUT 1 148.99 SF B 300

Level 1 1106 FINAL CUT 2 94.37 SF B 300

Level 1 1113 STORAGE 29.95 SF B 300

Level 1 1122 MOTION GRAPHICS 96.53 SF B 300

Level 1 1128 VIDEO TAPE LIBRARY 1995.93 SF B 300

Level 1 1156 TECHNICAL STORAGE 528.94 SF B 300

Level 1 1163 MECH RM. 309.96 SF B 300

Level 1 1164 ELEC. RM. 192.91 SF B 300

Level 1 1165 CLOSET 30.06 SF B 300

Level 1 1166 CLOSET 102.69 SF B 300

Level 1 1170 GENERAL SERVICES 662.05 SF B 300

Level 1 1170A COMP. ROOM 264.02 SF B 300

Level 1 1173 PRODUCTION SHOP 2318.56 SF B 300

Level 1 1207A STOR. 26.91 SF B 300

Level 1 1209 STOR. 50.74 SF B 300

Level 1 2000 UPS RM. 304.16 SF B 300 38

300: 24 11413.91 SF 38

48781.47 SF 485

Grand total: 117 56822.34 SF 915

3/64" = 1'-0"

Level 2

OCCUPANT COUNT OF

ALL 15 OLF SPACES.

OCCUPANT COUNT OF

ALL 35 OLF SPACES.

OCCUPANT COUNT OF

ALL 150 OLF SPACES.

OCCUPANT COUNT OF

ALL 300 OLF SPACES.

TOTAL OCCUPANT

LOAD FOR B SPACES.

TOTAL OCCUPANT

LOAD BUILDING.

THIS TOTAL BASED

ON FIXED SEATING

CAPACITY OF

AUDITORIUM.

OCCUPANT COUNT OF

ALL 35 OLF SPACES.

TOTAL OCCUPANT

LOAD FOR A SPACES.

TOTAL NUMBER

OF ROOMS:

OLF TYPE TOTAL:

(TYP).

USE TYPE:

(TYP).

TOTAL SF OF A-1 USE:

TOTAL SF OF B USE:

TOTAL SF OF BUILDING:

# Revision Date

CONSTRUCTION

DOCUMENTS

CONDUIT SLEEVE

EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE

GENERAL SYMBOLS

KEYNOTE#

XXX

X

JUNCTION BOX, CEILING OR FLOOR MOUNTED.

JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.

J

J

POWER SYMBOLS

DUPLEX RECEPTACLE, TAMPER-RESISTANT, WALL MOUNT +18", OR AS NOTED

EQUIPMENT CONNECTION, WALL MOUNT +18", OR AS NOTED, REFER TO ELECTRICAL

EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE

PANELBOARD - SURFACE MOUNTED

**NOTE: ALL SYMBOLS MAY NOT APPLY TO THIS PROJECT**

1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH ALL STATE CODES.

2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE

ELECTRICAL INSTALLATION. VERIFY WITH STATE OFFICIALS WHEN PERMITS ARE OBTAINED.

NOTIFY DESIGN TEAM OF ANY DISCREPANCIES BETWEEN THE PROJECT MANUAL OR

DRAWINGS AND THE GOVERNING CODE.

3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH

DISABILITIES ACT.

4. REFER TO PROJECT MANUAL AND PROJECT CODE REVIEW SHEET FOR LIST OF APPLICABLE

CODES.

CODE NOTES - ELECTRICAL

1. PROVIDE NEW FULLY FUNCTIONAL AND CODE COMPLIANT FIRE ALARM SYSTEM.

2. THE STATE FIRE MARSHAL HAS APPROVED THE USE OF DETECTION ON A ROOM-BY-ROOM

BASIS. DETECTION IS SHOWN IN SPACES THAT THE OWNER WOULD LIKE DETECTION WITHIN

THE SPACE. BIDS AND DESIGN SHALL INCLUDE COVERAGE OF ALL THE SPACES SHOWN IN

THE CURRENT DESIGN.

GENERAL PROJECT INTENT

DEMOLITION AND RENOVATION NOTES - ELECTRICAL

1. ELECTRICAL DEMOLITION DRAWINGS SHOWING EXISTING CONDITIONS HAVE BEEN PREPARED

BASED ON FIELD OBSERVATION AND ORIGINAL DRAWINGS. FIELD VERIFY EXISTING

CONDITIONS BEFORE WORK BEGINS. ADDITIONAL COMPONENTS MAY EXIST WHICH ARE NOT

SHOWN. BECOME FAMILIAR WITH EXISTING ELECTRICAL SYSTEM WHICH WILL BE AFFECTED

BY THE DEMOLITION WORK.

2. PROVIDE EQUIPMENT, LABOR, AND MATERIALS TO REMOVE ELECTRICAL FACILITIES AND

CLEAR THE AREA TO RECEIVE THE NEW WORK PROVIDED UNDER THIS CONTRACT.

3. IN OCCUPIED AREAS BEYOND THE DEMOLITION SCOPE, KEEP EXISTING SYSTEMS NOT

AFFECTED BY PROJECT SCOPE OPERATIONAL THROUGH THE DURATION OF THE PROJECT.

OBTAIN PERMISSION FROM OWNER'S REPRESENTATIVE TO SHUT OFF SERVICES OR SYSTEMS

WHICH MAY AFFECT OTHER AREAS BEYOND THE LIMITS OF THE DEMOLITION AREA. INFORM

OWNER’S REPRESENTATIVE OF THE REASON FOR AND DURATION OF THE SHUTDOWN AND

ENSURE THAT THE SHUTDOWN IS MADE WITH AS LITTLE INCONVENIENCE TO OTHER AREAS

AS POSSIBLE.

4. INSTALL NEW CONDUCTORS FOR NEW DEVICES UNLESS SPECIFICALLY NOTED OTHERWISE.

RETAIN EXISTING CONDUITS IN GOOD CONDITION WHERE APPROVED BY ENGINEER OR AS

INDICATED.

5. KEEP EXISTING SYSTEMS OPERATIONAL DURING ALL PHASES OF CONSTRUCTION. DO NOT

CUT EXISTING TELECOMMUNICATION WIRING, CABLES OR CONDUIT. CONTRACTORS WHO CUT

IN-SERVICE CABLES ARE RESPONSIBLE FOR ALL DOWNTIME AND COSTS TO REPAIR.

6. INSTALL BLANK COVER PLATES OVER OPENING AT REMOVED DEVICE LOCATIONS. THIS

INCLUDES BUT IS NOT LIMITED TO, CLOCKS, RECEPTACLES, SWITCHES, JUNCTION BOXES,

ETC.

7. PROVIDE CUTTING AND PATCHING OF EXISTING MATERIALS AS REQUIRED FOR THE PROPER

COMPLETION OF THE DEMOLITION WORK AND THE INSTALLATION OF THE NEW WORK.

8. MAINTAIN FULL FUNCTIONAL AND AESTHETIC INTEGRITY OF DEVICES IDENTIFIED TO BE

REMOVED AND RELOCATED, AND HANDLE WITH APPROPRIATE CARE TO ALLOW FOR

REINSTALLATION. REPLACE DEVICES DAMAGED DURING DEMOLITION WITH NEW AT

CONTRACTOR’S EXPENSE.

9. EQUIPMENT AND SYSTEM THAT ARE REMOVED REMAIN THE PROPERTY OF THE OWNER

UNLESS OTHERWISE NOTED. DISPOSE OF ALL MATERIALS NOT SALVAGED BY THE OWNER.

10. REMOVE AND REINSTALL CEILING TILES REQUIRED FOR THE WORK BEING DONE UNDER THIS

CONTRACT. REPLACE CEILING TILES DAMAGED DURING CONSTRUCTION TO MATCH EXISTING.

1. BECOME FAMILIAR WITH EXISTING CONDITIONS PRIOR TO BID.

2. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO

CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.

3. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO

NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.

4. CONTRACTOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, AND CEILINGS THAT

ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL PENETRATIONS IN

ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY. REFER TO OCCUPANCY

PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.

INSTALLATION NOTES - ELECTRICAL

ELECTRICAL ABBREVIATIONS

A DEVICE MOUNTED +8" ABOVE

COUNTER TOP (VERIFY LOCATION)

AFF ABOVE FINISHED FLOOR

ATS AUTOMATIC TRANSFER SWITCH

C CEILING

CB CIRCUIT BREAKER

CT CURRENT TRANSFORMER

E EXISTING ITEM TO REMAIN

EC ELECTRICAL CONTRACTOR

EM EMERGENCY LIGHT FIXTURE

ER NEW LOCATION OF EXISTING ITEM

F ROUGH IN FOR FUTURE DEVICE

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FSD FIRE SMOKE DAMPER

G GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

KVA KILO-VOLT-AMPERES

KW KILOWATTS

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUGS ONLY

N NEW DEVICE IN EXISTING LOCATION

NIC NOT IN CONTRACT

NM NONMETALLIC

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED,

OWNER INSTALLED

R EXISTING ITEM TO BE REMOVED

RR EXISTING ITEM TO BE REMOVED AND

RELOCATED

RN EXISTING ITEM TO BE REMOVED AND

REPLACED WITH NEW

SCCR SHORT CIRCUIT CURRENT RATING

T TAMPER PROOF DEVICE

TCC TEMPERATURE CONTROL CONTRACTOR

TV TELEVISION

TYP TYPICAL

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS

VA VOLT-AMPERES

W WEATHERPROOF DEVICE

WR WEATHER RESISTANT DEVICE

+24" INDICATES MOUNTING HEIGHT CENTER

LINE OF DEVICE TO FINISHED FLOOR

MANUAL FIRE ALARM PULL STATION

FIRE DETECTION AND ALARM SYMBOLS

SMOKE DETECTOR

SMOKE DETECTOR WITH 520Hz SOUNDER BASE

DUCT SMOKE DETECTOR

CARBON MONOXIDE DETECTOR

HEAT DETECTOR

WALL MOUNTED COMBINATION HORN WITH STROBE

CEILING MOUNTED STROBE

SPEAKER

FIRE FIGHTER TELEPHONE STATION

ADDRESSABLE INPUT MODULE; FS - SPRINKLER WATER FLOW SWITCH,

TS - TAMPER SWITCH, PIV - POST INDICATOR VALVE

MAGNETIC DOOR HOLD

FIRE ALARM CONTROL PANEL + EMERGENCY COMMUNICATIONS PANEL

COMBINATION FIRE/SMOKE DAMPER

SMOKE DAMPER

S

S

AIM

ADDRESSABLE OUTPUT MODULE; SD - FAN SHUT DOWN RELAY, AM - AUDIO MUTEAOM

S

SB

H HORN

S

SD

FSD

S

F

FAA

FACP

XX

XX

COMBINATION CARBON MONOXIDE / SMOKE DETECTORS

FIRE ALARM ANNUNCIATOR PANEL

WALL MOUNTED STROBE

CEILING MOUNTED COMBINATION HORN WITH STROBE

C

WALL MOUNTED WEATHERPROOF COMBINATION HORN WITH STROBE

W

COMMUNICATIONS - TELECOM SYSTEMS:

O

FO

I

COPPER HORIZONTAL CABLING, EXTENDED PHONE LINES

ROUGH-IN, PATHWAYS AND SLEEVES

SAFETY - FIRE DETECTION AND ALARM:

ROUGH-IN, PATHWAYS AND SLEEVES

INITIATING FIELD DEVICES (SMOKE, MANUAL PULL, MONITOR MODULES)

NOTIFICATION APPLIANCES (HORNS, STROBES, SPEAKERS)

MISCELLANEOUS DEVICES (RELAYS, TEST STATION, ANNUNCIATOR)

TECHNOLOGY RESPONSIBILITY MATRIX

PROVISION RESPONSIBILITIES DEFINED

OFOI

OFCI

CFCI

CFOI

OWNER FURNISHED & OWNER INSTALLED

OWNER FURNISHED & CONTRACTOR INSTALLED

CONTRACTOR FURNISHED & CONTRACTOR INSTALLED

CONTRACTOR FURNISHED & OWNER INSTALLED

GENERAL NOTE:

A. MATRIX IS NOT INTENDED TO BE EXHAUSTIVE TO COVER ALL MATERIALS NECESSARY FOR

SCOPE AND SHOULD ONLY BE USED TO QUICKLY IDENTIFY SYSTEMS AND RELATED

INFRASTRUCTURE INSIDE AND OUTSIDE THE BID OF THIS PROJECT. ANY ITEMS FURNISHED

OR INSTALLED BY THE BIDDING CONTRACTOR SHALL COVER ALL REQUIRED APPURTENANCES

NECESSARY FOR A COMPLETE SYSTEM. THIS SHALL INCLUDE BUT NOT BE LIMITED TO,

EQUIPMENT, ACCESSORIES, TERMINATIONS, TERMINATION COMPONENTS, ALL FINAL

CORDAGE CONNECTIVITY, SOFTWARE, PROGRAMMING, AND THE LABOR TO INSTALL.

O

FC

I

C

FC

I

C

FO

I

1. EXISTING FIRE DETECTION AND ALARM SYSTEM MUST REMAIN OPERATIONAL UNTIL

NEW FIRE ALARM PANEL IS FUNCTIONAL. COORDINATE EXISTING ZONES IN USE AND

PHASE REPLACEMENT OF SYSTEM TO MINIMIZE DOWNTIME.

2. METHODICALLY, AND IN CLOSE COORDINATION WITH THE OWNER, ROUTE NEW FIELD

WIRING TO ANTICIPATED DEVICE LOCATIONS. TAKE NO MORE THAN ONE EXISTING

SIGNAL LINE CIRCUIT OFFLINE AT ANY ONE TIME TO ENSURE A GRACEFUL MIGRATION

OCCURS FROM THE EXISTING SYSTEM TO THE NEW.

3. BIDDING CONTRACTOR IS ENCOURAGED TO RE-USE EXISTING PATHWAYS AND BOXES

WHERE IT IS APPROPRIATE. PROVIDE NEW PENETRATIONS AND SLEEVES WHERE

NECESSARY FOR DEVICE INSTALLATION. REFER TO PLAN SHEETS FOR NEW DEVICE

LOCATIONS AND WHERE EXISTING LOCATIONS CAN BE REUSED.

4. INTERFACE NEW DEVICES WITH NEW AND/OR EXISTING MECHANICAL EQUIPMENT FOR

FAN SHUT DOWN, SMOKE DAMPER AND COMBINATION FIRE/SMOKE DAMPER

PURPOSES.

5. NEW FIRE ALARM DEVICES FOR NOTIFICATION OR DETECTION SHALL BE INSTALLED IN

THE MIDDLE OF CEILING TILES. EXISTING TILE SIZE IS APPROXIMATELY 20" X 60".

INSTALL APPROPRIATE BRACKETS SO DEVICES ARE SUPPORTED FROM THE GRID OR

STRUCTURE ABOVE. TILES CANNOT BE USED FOR SUPPORT.

6. FIRE ALARM ITEMS AND DEVICES ARE SHOWN IN SUGGESTED LOCATIONS. FINAL

LAYOUTS, LOCATIONS, AND QUANTITIES SHALL BE IN ACCORDANCE WITH APPLICABLE

CODES, MANUFACTURER’S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.

COORDINATE LOCATIONS WITH LIGHTING AND AIR HANDLING SYSTEMS.

7. ALL FIRE ALARM CIRCUITRY IN EXPOSED CEILING SPACES SHALL BE IN ¾” CONDUIT PER

SPECIFICATIONS. EXPOSED CABLING SHALL NOT BE ACCEPTED.

8. ALL CONCEALED, ACCESSIBLE CEILING TILE LOCATIONS SHALL BE ALLOWED TO HAVE

OPEN AIR CABLING INSTALLED. PROVIDE J-HOOKS, BRIDLE RINGS AND ASSOCIATED

CABLE SUPPORTS TO KEEP INFRASTRUCTURE MANAGED AND OFF OF THE CEILING TILE.

9. ELECTRICAL CONTRACTOR SHALL PROVIDE FIRESTOPPING AT ALL PENETRATIONS PER

SPECIFICATION.

10. DEVICES SHALL BE WHITE UNLESS OTHERWISE NOTED.

FIRE DETECTION & ALARM NOTES

1. PROVIDE A COMPLETE REPLACEMENT OF THE EXISTING CONDUCTORS. CONTRACTORS

MAY REUSE PATHWAYS. THE EXISTING CONDUCTORS ARE NOTED TO BE 18/2 FOR

DETECTION DEVICES AND 14/2 FOR NOTIFICAITON DEVICES. THE EXISTING SYSTEM IS A

SIEMENS APOGEE SYSTEM. IF THE SELECTED SYSTEM CANNOT UTILIZE EXISTING

CONDUCTORS, LEAVE THIS LINE BLANK AND INCLUDE ALL NEW CONDUCTORS IN THE

BASE BID.

2. REUSE EXISTING NOTIFICATION DEVICES. EXISTING DEVICES WILL REMAIN INTACT AND

BE RECONNECTED TO THE NEW SYSTEM. PROVIDE DEDUCT ALTERNATE PRICING ON

BID FORM.

ALTERNATES

MAGNETIC LOCKML

ACCESS CONTROL SYMBOLS

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :0

A

M

E000

CONSTRUCTION

DOCUMENTS

2/1/2024

9360.00

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T C

O R

P O

R A

T E

D R

IV

E

J O

H N

S T

O N

IO

W A

ELECTRICAL GENERAL

NOTES & SYMBOLS

# Revision Date

F A

A

S S

F

F

C

C

S

S

S

S

F

S S S

S

S S

SS

SS

S S S

S

S SS

S

S

S S

S

SS

S

S

S

S

S

S

S

S

S

S

S

S

S

S

F

S

FAA

S

ML

M L

ML

ML

ML

ML

1. DEMOLITION DRAWINGS PRESENT LAYOUT OF EXISTING

CONDITIONS AND MAJOR ITEMS. THEY ARE NOT TO BE

CONSTRUED AS COMPLETE IN REPRESENTATION OF

ACCESSORIES AND INCIDENTALS TO BE REMOVED, REPLACED,

OR REWORKED. NOR SHOULD ACCESSIBILITY BE INFERRED.

THE CONTRACTOR IS RESPONSIBLE TO FAMILIARIZE

THEMSELVES WITH THE BUILDING AND EXISTING CONDITIONS,

PRIOR TO THE SUBMITTING OF A BID FOR THIS PROJECT.

2. REMOVE ELECTRICAL FACILITIES AND CLEAR THE AREA TO

RECEIVE THE NEW WORK TO BE PROVIDED UNDER THIS

CONTRACT.

3. THIS ELECTRICAL DEMOLITION DRAWING SHOWING EXISTING

CONDITIONS HAS BEEN PREPARED BASED ON FIELD

OBSERVATION. ADDITIONAL COMPONENTS MAY EXIST WHICH

DO NOT SHOW, AND SUCH ITEMS SHALL BE REMOVED TO

MATCH SIMILAR ITEMS WHICH DO SHOW. CONTRACTOR SHALL

VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING

CONDITIONS.

4. ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR

COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

ELECTRICAL DEMOLITION NOTES

ADMINISTRATION

COMMUNICATIONS

OFFICE

OFFICE

OFFICE1114

OFFICE

OFFICE

BOARDROOM

PRODUCTION

EDUCATION

VIDEO TAPE LIBRARY

NETWORK VIDEO CENTER

TECH EQUIP. CENTER

NETWORK CONTROL

CENTER

AVID 5

FINAL CUT 4

EDIT SERVER

AVID 6

AVID 1

AVID 2

LUNCH ROOM

VENDING

1155A

VEST.

TECHNICAL SHOP

STUDIO 2

CC "B"

AUDIO PROD.

VIDEO CONTROL 1

AUDIO CONTROL 1

CONFERENCE ROOM

FINAL CUT 1

FINAL CUT 2

FINAL CUT 3

OFFICE

SOUTH CONF. ROOM

1126A

MEETING ROOM

GRAPHICS & DESIGN

MENS

WOMEN

CONF. ROOM

VEST.

1138A

FINAL CUT 5

AVID 4

AVID 3

CC "A"

CORRIDOR

MAIN LOBBY

VEST.

CORRIDOR

RN

RN

RN RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN RN RN

RN

RN

RN

RN

RR

RN

RN RN

RNRN

RNRN

RN RN RN

RN

RN

R

RN

RN RN

RN

RN

RN RN

RN

RN

RN RN

RN

RN

RN

RN RN

RN

RN

RN

RNRN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RNRN

RN

RN

RN

RN

RN

RN

RN

RN

RN

MOTION GRAPHICS

DARK RM.

M A

T C

H L

IN

E

M A

T C

H L

IN

E

RN

RN

RN

E E

E

E

RN

RN

INSTALL NEW SMOKE DETECTOR IN SATELITE BUILDING.

REUSE EXISTING CONDUIT AND CONDUCTORS TO BUILDING.

REMOVE EXISTING HEAT DETECTOR IN TOWER.

REUSE EXISTING CONDUIT AND CONDUCTORS TO BUILDING.

RN

RN

2 2

2 2

E

E

E

E

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :0

A

M

ED101

CONSTRUCTION

DOCUMENTS

2/1/2024

9360.00

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T C

O R

P O

R A

T E

D R

IV

E

J O

H N

S T

O N

IO

W A

FIRE ALARM

DEMOLITION - WEST

1/8" = 1'-0"

FIRE ALARM DEMO FLOOR PLAN - WEST

KEYNOTES

1 REMOVE EXISTING DEVICE IN ROOM. PREPARE WIRNG FOR

REUSE AND EXTENSION TO NEW DEVICE LOCATIONS IN

ROOM. INSTALL BLANK COVER PLATE OVER EXISTING

DEVICE LOCATION.

2 EXISTING NOTIFICATION DEVICES CAN BE REUSED AS A

DEDUCT ALTERNATE. EXISTING DEVICES APPEAR TO BE

EDWARDS EST PRODUCTS. SEE DESCRIPTION OF

ALTERNATE ON SHEET E000 FOR MORE INFORMATION.

C P

FAA

S S

SS

S

S

S S

S

S

S

S

S

S

S

S

S

S

S

S

S S S S

S

F

F

S S

SS

S

S S

S

S

SS

SS

S

S

S

S

SSS

S

F

F

AIM

FS

AIM

TS

S

SS

N A

C

M L

M L

M L

ML

M L

ML

ML

1. DEMOLITION DRAWINGS PRESENT LAYOUT OF EXISTING

CONDITIONS AND MAJOR ITEMS. THEY ARE NOT TO BE

CONSTRUED AS COMPLETE IN REPRESENTATION OF

ACCESSORIES AND INCIDENTALS TO BE REMOVED, REPLACED,

OR REWORKED. NOR SHOULD ACCESSIBILITY BE INFERRED.

THE CONTRACTOR IS RESPONSIBLE TO FAMILIARIZE

THEMSELVES WITH THE BUILDING AND EXISTING CONDITIONS,

PRIOR TO THE SUBMITTING OF A BID FOR THIS PROJECT.

2. REMOVE ELECTRICAL FACILITIES AND CLEAR THE AREA TO

RECEIVE THE NEW WORK TO BE PROVIDED UNDER THIS

CONTRACT.

3. THIS ELECTRICAL DEMOLITION DRAWING SHOWING EXISTING

CONDITIONS HAS BEEN PREPARED BASED ON FIELD

OBSERVATION. ADDITIONAL COMPONENTS MAY EXIST WHICH

DO NOT SHOW, AND SUCH ITEMS SHALL BE REMOVED TO

MATCH SIMILAR ITEMS WHICH DO SHOW. CONTRACTOR SHALL

VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING

CONDITIONS.

4. ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR

COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

ELECTRICAL DEMOLITION NOTES

STORAGE ROOM

WOMENS

MENS

ELEC. RM.

MECH RM.

CORRIDOR

EFP

1169A

FIBER

GENERAL SERVICES

1170A

COMP. ROOM

TECHNICAL STORAGE

PRODUCTION SHOP

DESIGN

STUDIO 1

GREEN ROOM

OFFICE

OFFICE

OFFICE

COAT CLOSET

MENS

WOMEN

MAYTAG LOBBY

VEST

STUDIO 3

MAYTAG AUDITORIUM

SERVING

VIDEO ROOM

AUDIO ROOM

VEST.

DRESSING

DRESSING

DRESS.1196

MENS

WOMEN

DRESS.

RECEIVING

JAN

CORRIDOR

ENGINEERING

CLOSET

UPS RM.

RN

RN

R

RN

RN RN

RNRN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN RN RN RN

RN

RN

RN RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RN

RNRN

RNRN

RN

RN

RN

RN

RN

RNRNRN

RN

RN RN

RNRN

RN

RN RN

RN

RN

RN

RN

M A

T C

H L

IN

E

M A

T C

H L

IN

E

RN

RN

RN

E

E

RN

RN

E

E

RNRN

R

REMOVE EXISTING FIRE

ALARM FDC BELL AND

PREPARE AREA FOR

NEW HORN/STROBE

E

E

EEE

E

E

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :1

A

M

ED102

CONSTRUCTION

DOCUMENTS

2/1/2024

9360.00

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T C

O R

P O

R A

T E

D R

IV

E

J O

H N

S T

O N

IO

W A

FIRE ALARM

DEMOLITION - EAST

KEYNOTES

1 EXISTING SIEMENS FIRE ALARM APOGEE PANEL SURFACE

MOUNTED TO WALL. REMOVE EXISTING SYSTEM. REUSE

EXISTING CONDUIT IF DEEMED IN GOOD CONDITION. REUSE

PANEL ENCLOSURE IF NECESSARY AS A JUNCTION BOX TO

EXTEND PATHWAYS TO NEW FIRE ALARM PANEL. PER

ALTERNATE #2, EXTEND CONDUCTORS TO NEW FIRE ALARM

PANEL TO REUSE FOR NOTIFICATION DEVICES.

2 EXISTING NOTIFICATION DEVICES CAN BE REUSED AS A

DEDUCT ALTERNATE. EXISTING DEVICES APPEAR TO BE

EDWARDS EST PRODUCTS. SEE DESCRIPTION OF

ALTERNATE ON SHEET E000 FOR MORE INFORMATION.

3 EXISTING FIRE ALARM NAC PANEL ENCLOSURE WITH

CONDUCTORS. REMOVE EXISTING CONDUCTORS AND

ENCLOSURE UPON COMPLETION OF NEW SYSTEM.

1/8" = 1'-0"

FIRE ALARM DEMO FLOOR PLAN - EAST

AOM

AOM

S

S

AOM

S

F

F

AOM

S

AOM

S

AOM

AOM

AOM

S

S

SS

F

F

AOM

S

AOM

S

AOM

S

1. DEMOLITION DRAWINGS PRESENT LAYOUT OF EXISTING

CONDITIONS AND MAJOR ITEMS. THEY ARE NOT TO BE

CONSTRUED AS COMPLETE IN REPRESENTATION OF

ACCESSORIES AND INCIDENTALS TO BE REMOVED, REPLACED,

OR REWORKED. NOR SHOULD ACCESSIBILITY BE INFERRED.

THE CONTRACTOR IS RESPONSIBLE TO FAMILIARIZE

THEMSELVES WITH THE BUILDING AND EXISTING CONDITIONS,

PRIOR TO THE SUBMITTING OF A BID FOR THIS PROJECT.

2. REMOVE ELECTRICAL FACILITIES AND CLEAR THE AREA TO

RECEIVE THE NEW WORK TO BE PROVIDED UNDER THIS

CONTRACT.

3. THIS ELECTRICAL DEMOLITION DRAWING SHOWING EXISTING

CONDITIONS HAS BEEN PREPARED BASED ON FIELD

OBSERVATION. ADDITIONAL COMPONENTS MAY EXIST WHICH

DO NOT SHOW, AND SUCH ITEMS SHALL BE REMOVED TO

MATCH SIMILAR ITEMS WHICH DO SHOW. CONTRACTOR SHALL

VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING

CONDITIONS.

4. ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR

COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

ELECTRICAL DEMOLITION NOTES

CONDENSERS

EMERGENCY GENERATOR

MECHANICAL / EQUIP.

EQUIP. ROOM

AHU-2

AHU-1

N

N

N

N

CRAC-1

N

N N

N

N

N N

SF-1

N

N

RF-1

N

N

CONDENSERS

EMERGENCY GENERATOR

MECHANICAL / EQUIP.

EQUIP. ROOM

AHU-2

AHU-1

RN

RN

RN

RN

RN RN

RN

RN

RN

RN

RN

SF-1

RN

RN

CRAC-1

RN

RN

RF-1

RN

RN

GENERAL NOTES

A. COORDINATE LOCATION/INSTALLATION OF WORK WITH CM/OWNER. NO

ASPECT OF A SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL

COMMENCE UNTIL PROPER AND TIMELY COORDINATION HAS

TRANSPIRED.

B. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS THROUGH

THE BUILDING. REVIEW FIRE RATED WALL PENETRATIONS ON

OCCUPANCY PLAN AND PROVIDE CONDUIT SLEEVES AND FIRE STOPPING

TO MAINTAIN RATINGS.

C. ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

PHASE LEGEND

EXISTING DEVICE TO REMAIN

REPLACE EXISTING DEVICE WITH NEW, SAME LOCATION

NEW DEVICE, NEW LOCATION

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :1

A

M

ED103

CONSTRUCTION

DOCUMENTS

2/1/2024

9360.00

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T C

O R

P O

R A

T E

D R

IV

E

J O

H N

S T

O N

IO

W A

FIRE ALARM DEMO

AND NEW - MEZZANINE

1/8" = 1'-0"

FIRE ALARM FLOOR PLAN - MEZZANINE

1/8" = 1'-0"

FIRE ALARM DEMO FLOOR PLAN - MEZZANINE

KEYNOTES

1 EXISTING ACCESS CONTROL PANEL LOCATION. INSTALL

MODULE TO PROVIDE OUTPUT TO PANEL AND OPEN

MAGNETICALLY HELD DOORS UPON FIRE ALARM

ACTIVATION.

A

F

F

C

C

F

F

S S

S

S

S

S

S S S

S

S S

SS

SS S S S

S SS

S

S

S S

S

SS

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

FAA

S

S

S

S

S

S S

S

S

S

S

SS

S S S

S

S

S

S

S S

S

AOMAOM

AOMAOM

S

ML

ML

M L

ML

ML

ML

ML

S

GENERAL NOTES

A. COORDINATE LOCATION/INSTALLATION OF WORK WITH CM/OWNER. NO

ASPECT OF A SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL

COMMENCE UNTIL PROPER AND TIMELY COORDINATION HAS

TRANSPIRED.

B. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS THROUGH

THE BUILDING. REVIEW FIRE RATED WALL PENETRATIONS ON

OCCUPANCY PLAN AND PROVIDE CONDUIT SLEEVES AND FIRE STOPPING

TO MAINTAIN RATINGS.

C. ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

PHASE LEGEND

EXISTING DEVICE TO REMAIN

REPLACE EXISTING DEVICE WITH NEW, SAME LOCATION

NEW DEVICE, NEW LOCATION

N

N

N

N

N

N

N

N

N

N

N

N

N

N

N

N N

N

N

N

N

N

N

N

N

N

N

N

N

N

N N

N

N

N

N

N N

N

N

N

N

M A

T C

H L

IN

E

M A

T C

H L

IN

E

N

N N

N

N

N

N

N

N N

N

N N

NN

N N N N N

N NN

N

N

N N

N

NN

N

N

N

N

N

N

N

N

N

N

N

N

N N

N

E

E E N

N

REMOVE EXISTING SMOKE DETECTOR IN SATELITE BUILDING.

APPROXIMATELY 50' SOUTH OF THE MAIN BUILDING. REFER TO PICTURE

TO THE RIGHT FOR REFERENCE.

INTERCEPT AND REUSE EXISTING CONDUIT AND CONDUCTORS.

INSTALL NEW HEAT DETECTOR IN TOWER.

INTERCEPT AND REUSE EXISTING CONDUIT AND CONDUCTORS.

N

N

N

N

N

N

ADMINISTRATION

COMMUNICATIONS

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

BOARDROOM

PRODUCTION

EDUCATION

VIDEO TAPE LIBRARY

NETWORK VIDEO CENTER

TECH EQUIP. CENTER

NETWORK CONTROL

CENTER

AVID 5

FINAL CUT 4

EDIT SERVER

AVID 6

AVID 1

AVID 2

LUNCH ROOM

VENDING

1155A

VEST.

TECHNICAL SHOP

STUDIO 2

CC "B"

AUDIO PROD.

VIDEO CONTROL 1

AUDIO CONTROL 1

CONFERENCE ROOM

FINAL CUT 1

FINAL CUT 2

FINAL CUT 3

OFFICE

SOUTH CONF. ROOM

1126A

MEETING ROOM

GRAPHICS & DESIGN

MENS

WOMEN

CONF. ROOM

VEST.

1138A

FINAL CUT 5

AVID 4

AVID 3

CC "A"

CORRIDOR

MAIN LOBBY

VEST.

CORRIDOR

1104A

STOR.

1104B

STOR.

MOTION GRAPHICS

DARK RM.

CORR.

VEST

CORR.

CORR.

STORAGE

MAIN LOBBY

E

8 8

E

E

E

E

E

E

E6

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :1

A

M

E101

CONSTRUCTION

DOCUMENTS

2/1/2024

9360.00

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T C

O R

P O

R A

T E

D R

IV

E

J O

H N

S T

O N

IO

W A

FIRE DETECTION &

ALARM PLANS - WEST

KEYNOTES

1 EXISTING STROBE IS BELOW CODE REQUIRED MINIMUM

HEIGHT. EXTEND CONDUIT/CONDUCTOR VERTICALLY UP

WALL FOR NEW DEVICE. INSTALL BLANK COVERPLATE ON

REMOVED DEVICE LOCATION.

2 EXISTING FIRE ALARM ANNUNCIATOR PANEL IN LOCATION.

INSTALL NEW ANNUNCIATOR PANEL ON WALL. REUSE

EXISTING BACKBOX AND PROVIDE SKIRT AS REQUIRED FOR

SEMI-RECESSED INSTALLATION.

3 INSTALL CONDUIT ABOVE CEILING AND NEW RECESSED BOX

IN CEILING FOR PATHWAYS TO NEW DEVICE. IF ADJACENT

CEILING AND WALLS ARE NOT ACCESSIBLE, INSTALL

SURFACE MOUNTED RACEWAY TO DEVICE TO INSTALL NEW

DEVICE ON CEILING.

4 EXISTING DEVICES IN LOBBY APPEARED TO BE HEAT

DETECTORS. INSTALL NEW SMOKE DETECTORS IN SPACE.

REUSE PATHWAYS IF DEEMED IN GOOD CONDITION FOR

NEW CONDUCTORS TO DETECTORS.

5 INSTALL NEW SMOKE DETECTORS IN SPACE TO PROVIDE

FULL COVERAGE. SURFACE RACEWAY WILL NOT BE

ACCEPTABLE IN THIS SPACE. USE ACCESS HATCHES AND

ADJACENT ACCESSIBLE CEILINGS TO GAIN ACCESS TO

INSTALL ABOVE CEILING. INSTALL NEW DEVICES IN BEST

LOCATION TO PROVIDE CODE COMPLIANT COVERAGE.

6 EXISTING MAGNETIC LOCK ON DOOR. INSTALL NEW RELAY

DEVICE AT ACCESS CONTROL PANEL SUCH THAT DOORS

WILL RELEASE MAGNET UPON FIRE ALARM ACTIVATION.

TYPICAL FOR ALL MAGNETIC LOCKS IN BUILDING.

7 EXISTING HOLD OPEN DOORS TO REMAIN INTACT. INSTALL

NEW MODULE TO PROVIDE CONTACT CLOSURE TO DOOR

HOLDS.

8 EXISTING HARD LID CEILING AREA. REUSE CONDUCTORS

FOR DEVICES. ALTERNATE #1 PRICING SHALL NOT BE

INCLUDED FOR THE DEVICES IN THIS SPACE.

1/8" = 1'-0"

FIRE ALARM RCP - WEST

C P

F A

C P

F A

C P

FAA

F

F

F

F

AIM

FS

AIM

TS

C

S S

S

S

S S

S

S

S

S

S

S

S

S

S

S

S

S

S S S S

S

S S

SS

S

S S

S

S

S

SS

S

S

S

SSS

S

S

S

AOMAOM

S S

S

S

S

S

S

AOMAOM

AOMAOM AOMAOM

AOMAOM

S

M L

M L

M L

ML

M L

ML

ML

S

GENERAL NOTES

A. COORDINATE LOCATION/INSTALLATION OF WORK WITH CM/OWNER. NO

ASPECT OF A SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL

COMMENCE UNTIL PROPER AND TIMELY COORDINATION HAS

TRANSPIRED.

B. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS THROUGH

THE BUILDING. REVIEW FIRE RATED WALL PENETRATIONS ON

OCCUPANCY PLAN AND PROVIDE CONDUIT SLEEVES AND FIRE STOPPING

TO MAINTAIN RATINGS.

C. ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

PHASE LEGEND

EXISTING DEVICE TO REMAIN

REPLACE EXISTING DEVICE WITH NEW, SAME LOCATION

NEW DEVICE, NEW LOCATION

N

N

N

N

N

N

N

N

N

N

N

N

N

N

N

N

N N

N

N

N N N

N

N

N

N

N

N

N

N N

N

N

M A

T C

H L

IN

E

M A

T C

H L

IN

E

N

N

N

S

SURFACE MOUNTED DEVICE ON WALL.

INSTALL CONDUIT IN COATS ROOM TO

MINIMIZE VISIBLE CONDUIT IN LOBBY SPACE. SURFACE MOUNTED

DEVICE ON WALL.

PENETRATE THROUGH

WALL FROM EXISTING

HORN STROBE ON

OPPOSITE SIDE.

NEW SURFACE MOUNTED

DEVICE ON WALL. USE

SURFACE RACEWAY FOR

INSTALLATION.

AUDIO SYSTEM

RELAY

OVERRIDE

N

N N

NN

N

N N

N

N

N

N

N

N

N

N

N

N

N

N N N N

NN

NN

N

N

N

N

N

NN

N N

NN

N

N N

N

N

E

E

N

N

E

E

N N

AHU-3

(6) RED HEAT DETECTORS REQUIRED

ABOVE STAGE AREA.

W

MENS

TECHNICAL STORAGE

GREEN ROOM

OFFICE

CORR.

VEST

1207A

STOR.

CORRIDOR

STORAGE ROOM1161

WOMENS

ELEC. RM.

MECH RM.

CORRIDOR

EFP

1169A

FIBER

GENERAL SERVICES

1170A

COMP. ROOM

PRODUCTION SHOP

DESIGN

STUDIO 1

OFFICE

OFFICE

COAT CLOSET

MENS

WOMEN 1186

MAYTAG LOBBY

VEST

STUDIO 3

MAYTAG AUDITORIUM

SERVING 1181

VIDEO ROOM

AUDIO ROOM

VEST.

DRESSING

DRESSING

DRESS.

MENS

WOMEN

DRESS.

RECEIVING

JAN

CORRIDOR

ENGINEERING

CLOSET

UPS RM.

VEST

1177A

VEST

ACCESS

CLOSET

JAN.

STOR.

1167A

VEST.

DIMMER ROOM

VEST.

N

5 5

ABOVE CATWALK ABOVE CATWALK

N

N

STORAGE

81186

MAYTAG LOBBY

E

E

E

E E

E

E

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/2

/2

:2 :2

A

M

E102

CONSTRUCTION

DOCUMENTS

2/1/2024

9360.00

S T

A T

E O

F I

O W

A

D A

S

IP

B S

F

IR

E A

L A

R M

R E

P L

A C

E M

E N

T C

O R

P O

R A

T E

D R

IV

E

J O

H N

S T

O N

IO

W A

FIRE DETECTION &

ALARM PLANS - EAST

KEYNOTES

1 INSTALL NEW FIRE ALARM MODULE TO OVERRIDE AUDIO

SYSTEM. INSTALL RELAY AND ASSOCIATED EQUIPMENT TO

TURN OFF AUDIO SYSTEM OUTPUT DURING A FIRE ALARM

EVENT.

2 EXISTING FIRE ALARM ANNUNCIATOR PANEL IN LOCATION.

INSTALL NEW ANNUNCIATOR PANEL ON WALL. REUSE

EXISTING BACKBOX AND PROVIDE SKIRT AS REQUIRED FOR

SEMI-RECESSED INSTALLATION.

3 INSTALL NEW FIRE ALARM PANEL ON OPPOSITE SIDE OF

WALL FROM EXISTING PANEL. EXTEND EXISTING PHONE

LINES, FIRE ALARM CONDUCTORS, AND PATHWAYS FROM

EXISTING PANEL TO NEW PANEL LOCATION. EXTEND

EXISTING 120V CIRCUIT FROM EXISTING PANEL TO NEW.

4 EXISTING CEILING APPEARS TO HAVE LIMITED ACCESS.

REUSE CONDUCTORS AND PATHWAYS IN LOCATION IF

FEASIBLE. COORDINATE CEILING REMOVAL WITH OWNER

AND CM FOR TIMING.

5 EXISTING HOLD OPEN DOORS TO REMAIN INTACT. INSTALL

NEW MODULE TO PROVIDE CONTACT CLOSURE TO DOOR

HOLDS.

6 EXISTING MAGNETIC LOCK ON DOOR. INSTALL NEW RELAY

DEVICE AT ACCESS CONTROL PANEL SUCH THAT DOORS

WILL RELEASE MAGNET UPON FIRE ALARM ACTIVATION.

TYPICAL FOR ALL MAGNETIC LOCKS IN BUILDING.

7 PROVIDE AND INSTALL NEW DOOR HOLDS ON EXISTING

DOOR. INSTALL 120V CIRCUIT TO DOOR FROM NEAREST

BRANCH CIRCUIT PANELBOARD ON STAGE. PAINT EXPOSED

CONDUIT ON STAGE AND INSTALL WHITE SURFACE

RACEWAY IN CORRIDOR TO DOOR HOLD LOCATIONS.

8 EXISTING HARD LID CEILING AREA. REUSE CONDUCTORS

FOR DEVICES. ALTERNATE #1 PRICING SHALL NOT BE

INCLUDED FOR THE DEVICES IN THIS SPACE.

SURFACE MOUNT

TO EXISTING GYP CEILING

1/8" = 1'-0"

FIRE ALARM RCP - EAST

Sheets
00 - TITLE SHEET
E000 - ELECTRICAL GENERAL NOTES & SYMBOLS
E101 - FIRE DETECTION & ALARM PLANS - WEST
E102 - FIRE DETECTION & ALARM PLANS - EAST
ED101 - FIRE ALARM DEMOLITION - WEST
ED102 - FIRE ALARM DEMOLITION - EAST
ED103 - FIRE ALARM DEMO AND NEW - MEZZANINE

File details come from the government source that posted it. Updated .