RFB922600-01 - Drawings.pdf

PDF 10 MB Posted

Attached to
Montauk Historic Site Main House Site Work and Outbuilding Repairs
Solicitation number
RFB922600-01
Issued by
Dickinson County, Iowa

About this file

This is a technical drawings document for RFB922600-01, a state and local contract opportunity involving the State of Iowa and Clermont, Iowa for site work and outbuilding repairs at 2623 Harding Road. The project encompasses multiple repairs to the main house and related structures, with a bid package release date of February 4, 2026. The drawings include mechanical and electrical plans and specifications for system installations and modifications. Key mechanical work includes installation of a dehumidification unit (DHU-1) with a 4-inch concrete housekeeping pad, condensate piping routed to an existing receptor with a 3-inch minimum trap, and a 24V Honeywell DG115EZIAQ digital humidistat for control. Electrical work involves routing three new 3/0 copper conductors overhead from an existing utility pole to a new Panel A on the second floor, approximately 130 feet in horizontal distance. The project requires coordination with local code officials, Alliant Energy, and the property owner. All work must conform to applicable local, state, and national codes, and contractors must provide as-built drawings and operation and maintenance manuals within thirty days of final completion. The license renewal date is December 31, 2026.

The specifications require all materials to be new and meet equipment capacities as specified, with installation strictly in accordance with manufacturer's instructions and code requirements. All contractors must provide third-party testing and balancing of mechanical systems and unconditionally warrant all materials, equipment, and workmanship for one year from the date of owner acceptance, including free service during the warranty period. Ductwork supports must be secured to structure at 5-foot on-center intervals, and all exposed materials and cabling must be plenum-rated. The document establishes detailed mechanical and electrical notes including coordination requirements for ductwork routing, conduit installation per NECA 1 standards, and the removal and backfeeding of existing electrical service without removing the existing electrical service until the new service is in place and operational.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2/4/2026

LICENSE RENEWAL DATE: 12/31/26

FA

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

M0.0

M

EC

H

AN

IC

AL

N O

TE

S

GENERAL MECHANICAL NOTES

1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF ALL APPLICABLE LOCAL,

STATE, AND NATIONAL CODES, AS WELL AS LOCAL UTILITY REQUIREMENTS. PROVIDE

ALL REQUIRED ACCESSORIES AND EQUIPMENT FOR A COMPLETE OPERATIONAL

SYSTEM AND MAINTAIN WARRANTY REQUIREMENTS. VERIFY ALL EQUIPMENT

PROVIDED IS SUITABLE FOR INTENDED USE.

2. WORK NOT SPECIFICALLY SHOWN IN DETAIL, REFERENCED, OR OTHERWISE IMPLIED,

SHALL BE PROVIDED IN ACCORDANCE WITH TRADE OR INDUSTRY BEST STANDARD

PRACTICES TO PROVIDE A COMPLETE OPERATIONAL SYSTEM.

3. ALL MATERIALS SHALL BE NEW AND SHALL BE OF THE TYPE AND SHALL MEET THE

CAPACITIES OF EQUIPMENT SPECIFIED ON THE DRAWINGS.

4. ALL EQUIPMENT LISTED UNDER THESE SPECIFICATIONS SHALL BE LIMITED TO

PRODUCTS REGULARLY PRODUCED AND RECOMMENDED FOR SERVICE IN

ACCORDANCE WITH ENGINEERING DATA, RATINGS, OR OTHER COMPREHENSIVE

LITERATURE MADE AVAILABLE TO THE PUBLIC AND IN EFFECT AT THE TIME OF

OPENING BIDS.

5. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE

MANUFACTURER'S INSTRUCTIONS AND CODE REQUIREMENTS FOR TYPE AND

CAPACITY OF EACH PIECE OF EQUIPMENT USED.

6. ALL CUTTING AND PATCHING REQUIRED FOR MECHANICAL WORK SHALL BE

PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS NOTED OTHERWISE. ALL

FINISHED SURFACES THAT ARE CUT SHALL BE REPLACED IN KIND SO THERE IS NO

VISIBLE EVIDENCE OF CUTTING AND/OR PATCHING.

7. INSTALL HANGERS AND SUPPORTS AS REQUIRED TO ADEQUATELY AND SECURELY

SUPPORT MECHANICAL SYSTEM COMPONENTS IN A NEAT AND WORKMANLIKE

MANNER. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR

CONDUIT.

8. COORDINATE DUCTWORK ROUTING AND EQUIPMENT WITH BUILDING STRUCTURE,

LIGHTING, AND FIRE ALARM DEVICES.

9. DUCTWORK SUPPORTS SHALL BE SECURED TO STRUCTURE AT 5'-0" ON CENTER.

10. ALL EXPOSED MATERIALS SHALL BE PLENUM RATED.

11. NO LOADS SHALL BE PERMITTED TO BE HUNG FROM ROOF DECKING. ALL HANGERS

SHALL BE HUNG DIRECTLY FROM STRUCTURE.

12. PROVIDE THIRD PARTY TESTING AND BALANCING OF MECHANICAL SYSTEM.

13. PROVIDE AS-BUILT DRAWINGS FOR MECHANICAL SYSTEMS WITHIN 30 DAYS OF FINAL

COMPLETION.

14. PROVIDE O&M MANUALS FOR ALL SYSTEMS AND EQUIPMENT TO OWNER WITHIN 30

DAYS OF FINAL COMPLETION.

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

M0.1

M

EC

H

AN

IC

AL

SC

H

ED

U

LE

S

S-1 8"x6"

150 CFM

EX

FURNACE

EX

EWH

EX

BOILER

EX

BOILER

"Ø

S A

8"Ø SA 8"Ø SA

DHU-1

8x6 SA

S-1 8"x6"

150 CFM

S-1 8"x6"

150 CFM

"Ø

S A

3/4" CD

3/ 4"

C D

3/ 4"

C D

3/4" CD

P-1

H

DHU-1

FA

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

M1.11N

BA

SE

M

EN

T M

EC

H

AN

IC

AL

PL

AN

1/8" = 1'-0"

BASEMENT MECHANICAL PLAN

KEYED NOTES

PROVIDE 4" CONCRETE HOUSEKEEPING PAD FOR

DEHUMIDIFICATION UNIT.

ROUTE CONDENSATE PIPING TO EXISTING RECEPTOR.

3/4" CD DOWN TO CONDENSATE PUMP. CONNECT

CONDENSATE FROM DEHUMIDIFICATION UNIT TO

CONDENSATE PUMP WITH A MINIMUM 3" TRAP.

PROVIDE 24V HONEYWELL DG115EZIAQ DIGITAL HUMIDISTAT

TO CONTROL DHU-1.

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

E0.0

EL

EC

TR

IC

AL

N

O

TE

S

GENERAL ELECTRICAL NOTES

1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF ALL

APPLICABLE LOCAL, STATE, AND NATIONAL CODES, AS WELL AS

LOCAL UTILITY REQUIREMENTS. CONTRACTOR SHALL

COORDINATE WITH LOCAL CODE OFFICIALS TO DETERMINE IF

ANY CODE INTERPRETATIONS BY CODE ENFORCEMENT

OFFICIALS WILL IMPACT PLANNED WORK.

2. PROVIDE ALL REQUIRED ACCESSORIES AND EQUIPMENT FOR A

COMPLETE OPERATIONAL SYSTEM AND MAINTAIN WARRANTY

REQUIREMENTS. VERIFY ALL EQUIPMENT PROVIDED IS SUITABLE

FOR INTENDED USE. INSTALL ALL EQUIPMENT IN STRICT

ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

3. WORK NOT SPECIFICALLY SHOWN IN DETAIL, REFERENCED, OR

OTHERWISE IMPLIED, SHALL BE PROVIDED IN ACCORDANCE

WITH TRADE OR INDUSTRY BEST STANDARD PRACTICES TO

PROVIDE A COMPLETE OPERATIONAL SYSTEM.

4. CIRCUIT ROUTING INDICATED IS DIAGRAMMATIC. WHEN CIRCUIT

DESTINATION IS INDICATED AND ROUTING IS NOT SHOWN,

DETERMINE EXACT ROUTING REQUIRED.

5. COORDINATE EXACT WIRING REQUIREMENTS WITH

MANUFACTURER'S REQUIREMENTS FOR EACH FIXTURE AND

PIECE OF EQUIPMENT.

6. INSTALL HANGERS AND SUPPORTS AS REQUIRED TO

ADEQUATELY AND SECURELY SUPPORT ELECTRICAL SYSTEM

COMPONENTS IN A NEAT AND WORKMANLIKE MANNER AS

SPECIFIED IN NECA 1. DO NOT FASTEN SUPPORTS TO PIPES,

DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT.

7. INSTALL CONDUIT SECURELY IN A NEAT AND WORKMANLIKE

MANNER AS SPECIFIED IN NECA 1.

8. EQUIPMENT CONNECTIONS: MAKE CONDUIT CONNECTIONS TO

EQUIPMENT USING FLEXIBLE CONDUIT.

9. INSTALL DISCONNECT SWITCHES, CONTROLLERS, CONTROL

STATIONS, AND CONTROL DEVICES TO COMPLETE EQUIPMENT

WIRING REQUIREMENTS.

10. TEST LIGHTING SYSTEMS TO ENSURE PROPER CALIBRATION,

ADJUSTMENT, PROGRAMMING, AND OPERATION.

11. PROVIDE TYPE-WRITTEN PANEL DIRECTORY ON ELECTRICAL

PANELS. HANDWRITTEN TEXT IS NOT ACCEPTABLE.

12. COORDINATE COLOR OF RECEPTACLES AND COVER PLATES TO

MATCH THE COLOR SCHEME PER ARCHITECTURAL DRAWINGS.

13. PROVIDE AS-BUILT DRAWINGS FOR ELECTRICAL SYSTEMS

WITHIN 30 DAYS OF FINAL COMPLETION.

14. PROVIDE O&M MANUALS FOR ALL SYSTEMS AND EQUIPMENT

TO OWNER WITHIN 30 DAYS OF FINAL COMPLETION.

15. ALL EXPOSED CABLING SHALL BE PLENUM RATED.

16. CONTRACTOR(S) SHALL UNCONDITIONALLY WARRANTY IN

WRITING ALL MATERIALS, EQUIPMENT, AND WORKMANSHIP FOR

ONE YEAR FROM DATE OF ACCEPTANCE BY OWNER.

CONTRACTOR(S) SHALL PROVIDE FREE SERVICE FOR ALL

EQUIPMENT INVOLVED IN THEIR CONTRACT DURING THE

WARRANTY PERIOD.

ELECTRICAL LEGEND

EQUIPMENT POWER CONNECTION

EQUIPMENT DISCONNECT SWITCH

SINGLE POLE SWITCH - DECORATOR STYLE

S

0-10V DIMMER SWITCH - DECORATOR STYLE

SDM

PUMP W/ DISCONNECT SWITCH

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

E0.1

EL

EC

TR

IC

AL

SC

H

ED

U

LE

S

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

E1.01 N

KEYED NOTES

ROUTE (3) NEW 3/0 COPPER CONDUCTORS OVERHEAD FROM

EXISTING UTILITY POLE TO NEW PANEL A ON 2ND FLOOR.

HORIZONTAL DISTANCE IS APPROXIMATELY 130 FEET. FIELD

VERIFY EXACT MEASUREMENTS AND CONDITIONS.

EL

EC

TR

IC

AL

S

IT

E

PL

AN

NOT TO SCALE

ELECTRICAL SITE PLAN

DHU-1

A-1,3

GFI

A-10

GFI

FA

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

E1.11N

KEYED NOTES

ROUTE CONDUIT FOR DEHUMIDIFICATION UNIT TIGHT TO

BASEMENT CEILING. ROUTE CONDUIT UP THROUGH 1ST

FLOOR BREAK ROOM AND 2ND FLOOR OFFICE TIGHT TO WALL.

FIELD VERIFY EXACT ROUTING TO AVOID CONFLICTS WITH

EXISTING SYSTEMS PRIOR TO START OF WORK. PAINT

CONDUIT WHERE EXPOSED IN BREAK ROOM AND OFFICE

(COLOR BY ARCHITECT).

BA

SE

M

EN

T

EL

EC

TR

IC

AL

PL

AN

1/8" = 1'-0"

BASEMENT ELECTRICAL PLAN

X:

-4

-1

W

ES

T D

ES

M

O

IN

ES

, I

A

O

FF

IC

E

PA

R

K R

D

#1

TE

L:

-4

-1

9226.00

DC

A

M

ON

M

AI

N

HO

US

E

SI

TE

W

OR

K

AN

D

OU

TB

UI

LD

IN

G

RE

PA

IR

S

BI

D

PA

CK

AG

E

FO

R M

UL

TI

PA

L

RE

PA

IR

S

HA

RD

IN

G

RD

CL

ER

M

ON

T, IO

W A

02/04/2026

E1.2A

KEYED NOTES

REMOVE EXISTING ELECTRICAL SERVICE CONDUCTORS AND

ELECTRICAL PANEL. BACKFEED EXISTING CIRCUITS FROM NEW

ELECTRICAL SERVICE. PAINT NEW CONDUITS TO MATCH

WALL. PATCH AND PAINT ANY ABANDONED CONDUIT

PENETRATIONS. DO NOT REMOVE EXISTING ELECTRICAL

SERVICE UNTIL NEW ELECTRICAL SERVICE IS IN PLACE AND

OPERATIONAL. COORDINATE WORK WITH OWNER AND

ALLIANT ENERGY.

INSTALL NEW PANEL A IN LOCATION OF DEMO'D DISCONNECT

AND JUNCTION BOX. BACKFEED EXISTING 30A-2P

CONDENSING UNIT, 20A-2P WATER HEATER, 15A-1P LIGHTING,

AND 15-1P RECEPTACLE CIRCUITS. FIELD VERIFY EXISTING

CONDITIONS AND ROUTING. DESIGN TEAM SHALL APPROVE

CONDUIT ROUTING PRIOR TO INSTALLATION.

INSTALL NEW EMERGENCY LIGHT "EL1" IN PLACE OF DEMO'D

ELECTRICAL PANEL.

REUSE EXISTING ELECTRICAL SERVICE ENTRANCE CONDUIT

PENETRATION FOR NEW SERVICE CONDUIT. REFER TO SITE

PLAN.

EXISTING FIRE ALARM PANEL TO REMAIN.

SE

C

O N

D F

LO

O

R

EL

EC

TR

IC

AL

N O

TE

S

D

ET

AI

LS

NO SCALE

SECOND FLOOR EXISTING ELECTRICAL PANEL

A0 COVER SHT -MONTAUK FINAL DWGS -ELM signed
A01 MONTAUK FINAL DWGS
A02 MONTAUK FINAL DWGS
A10 MONTAUK FINAL DWGS
A20 MONTAUK FINAL DWGS
A30 MONTAUK FINAL DWGS
A31 MONTAUK FINAL DWGS
A40 MONTAUK FINAL DWGS
A50 MONTAUK FINAL DWGS
A60 MONTAUK FINAL DWGS
S1 MONTAUK FINAL DWGS

File details come from the government source that posted it. Updated .