REVISED - Generator Maintenance - Attachment A.docx

DOCX document 436 KB Posted

Attached to
EMA - Generator Maintenance & Repair - ARG
Solicitation number
24-588IEMA-MGMTA-B-39605
Issued by
Dekalb County, Monroe County, Will County, Illinois

About this file

This document is a specification for a contract opportunity issued by the Illinois Emergency Management Agency and Office of Homeland Security (IEMA-OHS) to establish a three-year contract for preventative maintenance and as-needed repairs on generators and small equipment located at various IEMA-OHS locations throughout the State of Illinois. The equipment to be covered includes GEMS Generators located at Illinois Power Plants, as well as various portable generators, diesel generators, and air compressors located at IEMA-OHS facilities in Springfield. The contract will require the vendor to provide routine maintenance services, including oil changes, filter replacements, and systems checks, as well as respond to emergency repairs within four hours of notification.

The pricing for these services will be submitted separately in Attachment B. This contract will be awarded as a Basic Ordering Agreement (BOA), with individual orders placed against the master contract as needed. The solicitation includes several mandatory requirements the vendor must meet, including compliance with RICE/NESHAPS regulations for nuclear power plant generators, proper disposal of waste fluids and materials, and the ability to obtain access to the nuclear power plant sites.

View the file

Other files

File Type Posted
standard-illinois-certifications-v.23.1~44.docx DOCX document
standard terms and conditions.pdf PDF
B39605 Questions and Answers.docx DOCX document
Generator Maintenance - Attachment B.docx DOCX document
Generator Maintenance - Attachment A.docx DOCX document
REVISED - Generator Maintenance - Attachment B.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Please note all changes made are in Red.

The Illinois Emergency Management Agency and Office of Homeland Security (IEMA-OHS) is seeking quotes from vendors to establish a three-year contract that covers preventative maintenance and as-needed repairs on generators and small equipment located at various IEMA-OHS locations throughout the State. The equipment to be covered under this contract will include:

GEMS Generators located at the Illinois Power Plants/ Mazon Resident Inspector’s Office Braidwood Generating Station – 35100 S. Route 53, Suite 84, Braceville, IL 60407

Kohler Model 50REOZK Diesel Generator (S/N: 33H3GMGN0016) w/ Kohler Model KSS-DCTA-0225S Transfer Switch (S/N: SGM3228M5)

Byron Power Plant – 4450 N. German Church Rd, Byron, IL 61010

Kohler Model 50REOZJC Diesel Generator (S/N:2255773; Tag 031776) w/ Kohler Model KSS-DCTA-0225S Transfer Switch (S/N: SGM3228M4)

Clinton Power Plant – 8401 Power Rd., Clinton, IL 61727

Kohler Model 50REOZJC Diesel Generator (S/N: 2283921; Tag 033427) w/ Kohler Model KSS-DCTA-0225S Transfer Switch (S/N: SGM3228M6

Dresden Power Plant – 6500 N. Dresden Rd., Morris, IL 60450

Cummins-Onan C50D6 Diesel Generator (S/N: I210978678) w/ Kohler Model KSS-DCTA-0225S Transfer Switch (S/N: SGM32284C)

LaSalle Power Plant – 2601 N. 21st Rd., Marseilles, IL 61341

Kohler Model 50REOZJC Diesel Generator (S/N:2315937; Tag 034009) w/ Kohler Model KSS-DCTA-0225S Transfer Switch (S/N: SGM322)

Mazon Resident Inspector’s Office – 1011 North St., Mazon, IL 60444

Kohler Model 100RZG Natural Gas Generator (S/N:2054709; Tag 026243) w/ Kohler Model KDT-AFNA-0400S Transfer Switch (S/N: K2054047)

Quad Cities Power Plant – 22710 206th Avenue North., Cordova, IL 61242

Cummins-Onan C50D6 Diesel Generator (S/N: H210975079) w/ Kohler Model KSS-DCTA-0225S Transfer Switch (S/N: SGM322FDM)

Generators/ Small Equipment Located at IEMA-OHS Springfield Facilities

Location:KS = 1301 Knotts St., Springfield, IL
RS = 4800 Rodger St., Springfield, IL
OP= 1305 Outer Park Drive Springfield, Il
Make/Model
Tag #
Loc.
Honda Model EU2000i Portable Generator
033732
KS
Honda Model EU2000i Portable Generator
033733
KS
Honda Model EU2000i Portable Generator (S/N: EAAJ-2067101)
033731
KS

Onan, Model 15.0 JC-18R/17637AB (S/N: 0860814405E)

474822
KS
Onan Pro5000E Portable Generator
500307
KS

Cummins/Kubota 12KW Diesel Generator Model 12HDKCD-2209 Ser#K100172499

Mobile Lab trailer
KS

Baldor Model 250kw Generator Set

(S/N: 4TCSU1098AH910289)

032196
RS

Baldor Model 250kw Generator Set

(S/N: 4TCSU1095AH910279)

032197
RS

Baldor Model 250kw Generator Set

(S/N: 4TCSU1091AH910280)

032198
RS
Honda Model EB5000 Portable Generator (S/N: EA7-3150222)
501315
RS
Yanmar (Model 361TSL1601) 16 valve engine that drives a 40 KW Magnaplus genset (S/N: 1M105972-0205)
UAC
RS
Kubota (Model 20HDKAW-2008A) 2.4-liter engine that drives 20 KW Cummins ONAN gensets (S/N: H100148216)
NOMAD

#1

RS

Kubota (Model 20HDKAW-2008A) 2.4-liter engine that drives 20 KW Cummins ONAN gensets (S/N: H100146296)
NOMAD

#2

RS

Kubota D1703 (Engine) – S/N: AJO643 (Genset S/N: M1OL500681)
Satellite on Wheels (SOW) – Ops
RS
Kohler 15KW genset, a Yanmar TR41 engine that drives the genset (S/N: 29489-51340)
Command #216
RS
Cummins/Kubota 12KW Diesel Generator Model 12HDKCD-2209
IT Trailer
RS
Onan Marquis 7000 7KW Gas Generator Model 7HGJAB-1036C (S/N: D030492315)
030895
RS
Cummins Onan RVQD 12500, 12.5HDKCB11506C (diesel) (S/N: G090018582)
Sample Prep/CC
RS
Onan Model E900321776 w/ Cummins Engine Model NT-955-G/S Transfer Switch and Model G90257577 15G Battery Charger
483767
RS
Kohler Model 200REOZJF Diesel Generator (S/N: SGM327G44)
035053
OP
Kohler Model KSP-DCVG-0600S Transfer Switch (S/N: SGM327PF5)
035054
OP

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018213726)

033251
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018213725)

033252
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018214476)

033260
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018213730)

033256
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018213728)

033254
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018214475)

033259
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018214474)

033258
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018213727)

033253
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator (S/N: 1018213725)

033257
RS

Briggs & Stratton Elite Series Model 030471 Portable Generator

033255
RS

Shindaiwa KWIET 25K VA (S/N: D16201000441)

035804
RS

Shindaiwa KWIET 25K VA (S/N: D16201000512)

035803
RS

AIRCO Quincy QR-350 Air Compressor

RS

Craftsman 26” Snowblower
030891
RS

Please provide all pricing information in Attachment B. Services for these items will be placed via a Basic Ordering Agreement (BOA) and placed as orders against the master contract.

Vendors are to specify whether each of the Mandatory Requirements is agreed to and satisfied by checking the appropriate “Met” or “Not Met” box, and where appropriate, provide the requested information.

If any mandatory requirement is not met, or requested information is not provided, the entire bid will not be considered. If all responding vendors fail to meet a particular mandatory, that mandatory may, at the sole discretion of the State, be removed so the evaluation process may continue.

Mandatory Specification M1: The Vendor agrees that every service and/or inspection should include “repair, replace, adjust as necessary” to ensure generator is performing optimally.

☐ Met ☐ Not Met

Mandatory Specification M2: Service Record - The Vendor agrees that all services performed will be recorded and a record of the service provided to IEMA-OHS.

☐ Met

Mandatory Specification M3: Generator Service - The Vendor agrees that GEMS Generator Service shall meet all RICE/NESHAPS regulations for Emergency Diesel Engines at Nuclear Power Plants. Maintenance for all generators on this contract should include but not be limited to the following services as applicable:

· Remove and replace engine oil with manufacturer’s recommended lubricant or approved equivalent.

· Remove and replace oil filter with manufacturer’s recommended filter or approved equivalent.

· Inspect air filter/cleaner and replace as needed

· Inspect fuel filters where applicable and replace as needed.

· Inspect block heater.

· Inspect all hoses and belts and replace as needed

· Check antifreeze, test, replace fluid and or flush system as needed

· Inspect battery condition (physical and electrical).

· Replace batteries as needed or once every three years at minimum.

· Perform physical/visual inspection for signs of leaks or other visible issues

· Check fuel, underground or above ground storage tank, as applicable, for signs of water intrusion, algae, or other issues

· Check fuel delivery, secondary pump assembly

· Start-up and test generator

· Check proper operation, engine operation and output, RPM level, stator voltage and frequency output and adjust/repair as necessary.

· Start-up, operation, testing and shutdown of DG using proper procedure ☐ Met

Mandatory Specification M4: Transfer Switch Service - The Vendor agrees that the service will include checking the following on the transfer switch if generator is paired with transfer switch:

· Check – physical/visual inspection of transfer switch

· Check operation of transfer switch

· Test operation in simulated emergency power situation

· Open main circuit breaker to simulate loss of power

· Ensure generator starts and comes up in appropriate amount of time

· Ensure proper transfer of power occurs (this will include uninterruptible power supply (UPS) holding the load until generator is able to accept the transfer of power load)

· Test Generator output while unit is running: Voltage and frequency tested on each of three legs and any reading found out of tolerance should be noted and dealt with as necessary.

· Close breaker

· Check that transfer switch allows return to Utility power source and if not, troubleshoot, discern, reasons and implement changes necessary to remedy the situation

· Observe ten-minute cool down of generator

· Visually inspect generator again for issues ☐ Met

Mandatory Specification M5: Disposal - The Vendor agrees that the service will be done in a safe manner, utilizing all necessary PPE and precautions to collect used fluids and material and transport for proper disposal off-site ☐ Met

Mandatory Specification M6: Power Plant Entry - Vendor or vendor’s agents involved with preventative maintenance or break/fix, must be willing to comply with Constellation nuclear power plant entry requirements, safety rules and regulations, and procedures. These may include, and not limited to, urinalysis, background review, escorted visitor/contractor requirements, and vehicle search.

☐ Met

Note: If the vendor is not approved by the Nuclear Power Plant Owner for entry, the contract will become void. The agency reserves the right to terminate the contract immediately if the vendor cannot obtain proper access with the Nuclear Power Plant Owner.

Mandatory Specification M7: Response Time – Vendor agrees to respond on-site to any break/fix or emergency repairs within four hours of being notified of a need for service.

☐ Met image1.jpg image2.jpg image3.jpg