This Request for Information (RFI) #2 is for Contract Number 3CA07152 with CAL FIRE regarding Fire Suppression Loading & Pit Replacement. The document addresses contractor questions about underground piping materials, with questions due by February 18, 2025, and program responses due by February 21, 2025. The RFI specifically addresses material requirements for underground storm drain and water lines referenced in Sheet C4.2, Keynotes #2 and #5.
The program response specifies that all unregulated pressure piping coming from the water main line must use C900 DR18, as lower pressure classes rated for 200 and 165 psi would be insufficient. For non-pressured underground storm drain lines, C900 DR 32.5 is specified as sufficient. Both specifications align with the provided requirements for C900 underground piping.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Request For Information (RFI) #2
Contract Number 3CA07152, Fire Suppression Loading & Pit Replacement
Questions Due 02/18/2025
Program Response Due 02/21/2025
Contractor- Per Sheet C4.2, Keynotes #2 and #5 show underground storm Drain and water line. Please give details on what material is needed for the underground lines.
Program-
• For all piping, unregulated for pressure, coming of the water main line C900 DR18 will be required; the next lower pressure classes are only rated for 200 and 165 psi which would be insufficient
• For non-pressured, underground storm drain lines, C900 DR 32.5 would be sufficient
These both fall in line with the provided specifications requiring C900 be used for underground piping