Relay Testing Report Biloxi VA.pdf

PDF 8 MB Posted

Attached to
6110--Project No. 520-22-108 Upgrade Emergency Electrical Systems, Biloxi
Solicitation number
36C25621R0055
Issued by

About this file

This federal contract opportunity notice seeks proposals for an upgrade of emergency electrical systems at the Gulf Coast Veterans Health Care System in Biloxi, Mississippi. The project number is 520-22-108 with an estimated construction cost range between $500,000 and $1,000,000.

The solicitation will be issued as a 100% set-aside for service-disabled veteran-owned small businesses. Interested contractors can expect the request for proposals to be released on or around January 25th, 2021, with proposals due approximately 30 days later on February 25th. The contract award date is anticipated within 30 days after receipt of proposals. The performance period will be 120 calendar days from the notice to proceed.

The selected contractor must perform at least 15% of the on-site labor costs using its own employees or those of other eligible SDVOSBs for general construction. For specialty trades, 25% of labor costs must be performed by eligible firms. Offerors must be verified as SDVOSBs in the Vendor Information Pages database and registered in the System for Award Management at the time of proposal submission.

View the file

Other files

File Type Posted
36C25621R0055 0004.docx DOCX document
WD General Decision No MS20210050 02-12-2021.pdf PDF
Register containing all RFI Inquiries _ Responses.pdf PDF
36C25621R0055 0003.docx DOCX document
36C25621R0055 0002.docx DOCX document
Site Visit Sign-In Sheets - Proj 520-22-108.pdf PDF
36C25621R0055 0001.docx DOCX document
Solicitaiton 36C25621R0055.docx DOCX document
EXHIBIT A PERFORMANCE RELEVANCY SURVEY.docx DOCX document
260511 Requirements for Electrical Installations.doc DOC document
EXHIBIT E SURETY FORM.docx DOCX document
EXHIBIT F REQUEST FOR INFORMATION FORM.docx DOCX document
SITE VISIT MAP Biloxi VA.pdf PDF
Dwg No EP110 Power Plan Level 1 Utility Plant Addition Utility Upgrades Phase 2.pdf PDF
EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY.docx DOCX document
Dwg No E-601 One Line Diagram Utility Plant Addition - Utility Upgrades Phase 2.pdf PDF
Dwg No E-401 Large Scale Plans - Mental Health Facility.pdf PDF
Dwg No EP-111 Partial Bldg Nos 2 3 19 Power Plan Level 1 Utility Upgrades Phase 2.pdf PDF
EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT.docx DOCX document
Test Report Deficiencies Biloxi VA.pdf PDF
WD General Decision No MS20210050 01-01-2021.docx DOCX document
Dwg No ES-604 15KV Primary Distr One Line Diagram - Utility Upgrades Phase 2.pdf PDF
ICRA 520-22-108.pdf PDF
262726 Wiring Devices.doc DOC document
EXHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx DOCX document
260526 Grounding and Bonding for Electrical Systems.doc DOC document
Dwg No I-E1 Electrical Plot Plan Phasing Modernize Various Bldgs Bldgs 1 5 19 and 53.pdf PDF
Dwg No E-601 One Line Diagram - Mental Health Facility.pdf PDF
010000 General Requirements.docx DOCX document
36C25621R0055_1.docx DOCX document
263623 Automatic Transfer Switches.docx DOCX document
260521 Low Voltage Electrical Power Conductors and Cables 600 Volts and Below.doc DOC document
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Electrical Testing Solutions

Field Service Letter

Work Completed:

November 14, 2019

Prepared For:

Department of Veterans Affair

Gulf Coast Health Care System 400 Veterans Avenue

Biloxi, MS 39531

VHABILDAVENC

Text Box

Project No. 520-22-108 Upgrade Emergency Electrical Systems, Biloxi

Relay Testing Report for:

Gulf Coast Health Care System

400 Veterans Avenue

Biloxi, MS 39531

2909 Green Hill Ct., STE I • Oshkosh, WI 54904 • p920.420.2986 f920.235.7136 www.electricaltestingsolutions.com

October 7, 2019

Attn: Tina Harris

Gulf Coast Veterans Health Care System

RE: Gulf Coast Veterans Health Care System Relay testing.

Dear Tina, This report contains the detailed information related to the relay testing conducted at the Gulf Coast Veterans Health Care System facility located at 400 Veterans Avenue, Biloxi, MS 39531.

Objective

ETS was to perform relay testing as part of the preventative maintenance schedule of Gulf Coast Veterans Health Care System facility, located at 400 Veterans Avenue, Biloxi, MS 39531.

Results and Recommendations

All the relays tested well and are ready for normal use. Detailed results of the tested relays are provided in this report.

We appreciate this opportunity to be of service to you. If you have any questions regarding this report feel free to contact me.

Sincerely, Ranniery Ribeiro Electrical Engineer Electrical Testing Solutions Office: (920) 420-2986 Email: rribeiro@electricaltestingsolutions.com http://electricaltestingsolutions.com/

Relay Testing Report

Work Completed:

November 14, 2019

Prepared For:

Gulf Coast Health Care System

Building 31 2

Building 61 5

Building 91 24

BLDG. 31 FEEDER 9 2

BLDG. 31 FEEDER 10 3

Building 31 2

RTS Relay Test Results

AL PASSPass/Fail:AF/AL:

Lib Version:

Lib Routine: SR-750/760.FST_LIB

09/11/2019Test Date:2.4

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 31 EQUIP_POSITION: FDR. No. 9 DEVICE_NUMBER:

MANUFACTURER: RELAY_TYPE: GE-SR750

MODEL: ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER:

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PH TIME OC1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 0.768 0.750 2.33 PASS

B-N 0.752 0.750 0.33 PASS

C-N 0.752 0.750 0.33 PASS

Relay Test Results for: A PH TOC1 TIMING TEST

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 1.500 266.28 4.438 4.361 1.77 PASS

3.00 2.250 99.94 1.666 1.648 1.05 PASS

4.00 3.000 55.22 0.920 0.920 0.06 PASS

A PH TOC1 TIMING TEST

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Relay Test Results for: PH INST OC1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 11.360 11.250 0.98 PASS

B-N 11.248 11.250 -0.02 PASS

C-N 11.248 11.250 -0.02 PASS

Page 1 of 111-Sep-2019Print Date:

Building 31 3

Lib Version:

Lib Routine: SR-750/760.FST_LIB

09/11/2019Test Date:2.4

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 31 EQUIP_POSITION: FDR. No. 10 DEVICE_NUMBER:

MANUFACTURER: RELAY_TYPE: GE-SR750

MODEL: ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER:

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PH TIME OC1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 0.760 0.750 1.33 PASS

B-N 0.760 0.750 1.33 PASS

C-N 0.760 0.750 1.33 PASS

Relay Test Results for: A PH TOC1 TIMING TEST

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 1.500 264.20 4.403 4.361 0.97 PASS

3.00 2.250 99.92 1.665 1.648 1.02 PASS

4.00 3.000 56.27 0.938 0.920 1.96 PASS

A PH TOC1 TIMING TEST

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Relay Test Results for: PH INST OC1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 11.360 11.250 0.98 PASS

B-N 11.360 11.250 0.98 PASS

C-N 11.360 11.250 0.98 PASS

Page 1 of 111-Sep-2019Print Date:

Building 31 4

FEEDER NO. 1 2

FEEDER NO. 2 4

FEEDER NO. 3 6

FEEDER NO. 4 8

FEEDER NO. 5 10

FEEDER NO. 7 12

FEEDER NO. 8 14

FEEDER NO. 9 16

FEEDER NO. 10 18

Building 61 5

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/10/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/9/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 1 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC10000066

FIRMWARE_ID: A09MA570.000 EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RUN AND READ SETTING NOTIFICATION MESSAGE

OK?

RAN

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 1.535 1.500 2.33 PASS

B-N 1.520 1.500 1.33 PASS

C-N 1.505 1.500 0.33 PASS

Page 1 of 210-Sep-2019Print Date:

Building 61 6

Relay Results (continued) for: UR-F35.FST19942

Relay Test Results for: PHASE TOC 1 TIMING

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 223.87 3.731 3.746 -0.39 PASS

3.00 4.500 91.13 1.519 1.514 0.29 PASS

5.00 7.500 38.10 0.635 0.614 3.37 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 223.63 3.727 3.746 -0.50 PASS

3.00 4.500 91.31 1.522 1.514 0.48 PASS

5.00 7.500 37.66 0.628 0.614 2.18 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 223.37 3.723 3.746 -0.62 PASS

3.00 4.500 91.13 1.519 1.514 0.29 PASS

5.00 7.500 37.57 0.626 0.614 1.93 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.250 25.000 1.00 PASS

B-N 25.250 25.000 1.00 PASS

C-N 25.250 25.000 1.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.300 10.000 3.00 PASS

Page 2 of 210-Sep-2019Print Date:

Building 61 7

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/13/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/13/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 2 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC10000067

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 3.828 3.750 2.07 PASS

B-N 3.790 3.750 1.07 PASS

C-N 3.790 3.750 1.07 PASS

Page 1 of 213-Sep-2019Print Date:

Building 61 8

Relay Results (continued) for: UR-F35.FST10778

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 7.500 69.30 1.155 1.040 TO 1.208 PASS

3.00 11.250 28.33 0.472 0.404 TO 0.505 PASS

5.00 18.750 12.22 0.204 0.147 TO 0.222 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 7.500 66.54 1.109 1.040 TO 1.208 PASS

3.00 11.250 28.75 0.479 0.404 TO 0.505 PASS

5.00 18.750 12.02 0.200 0.147 TO 0.222 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 7.500 68.49 1.142 1.040 TO 1.208 PASS

3.00 11.250 28.54 0.476 0.404 TO 0.505 PASS

5.00 18.750 11.99 0.200 0.147 TO 0.222 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.250 25.000 1.00 PASS

B-N 25.250 25.000 1.00 PASS

C-N 25.250 25.000 1.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Page 2 of 213-Sep-2019Print Date:

Building 61 9

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/12/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 3 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC10000063

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 3.191 3.125 2.12 PASS

B-N 3.160 3.125 1.12 PASS

C-N 3.160 3.125 1.12 PASS

Building 61 10

Relay Results (continued) for: UR-F35.FST18962

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 6.250 90.82 1.514 1.395 TO 1.601 PASS

3.00 9.375 37.38 0.623 0.548 TO 0.664 PASS

5.00 15.625 15.76 0.263 0.205 TO 0.286 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 6.250 90.50 1.508 1.395 TO 1.601 PASS

3.00 9.375 37.68 0.628 0.548 TO 0.664 PASS

5.00 15.625 15.53 0.259 0.205 TO 0.286 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 6.250 90.95 1.516 1.395 TO 1.601 PASS

3.00 9.375 37.30 0.622 0.548 TO 0.664 PASS

5.00 15.625 15.49 0.258 0.205 TO 0.286 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.000 25.000 0.00 PASS

B-N 25.250 25.000 1.00 PASS

C-N 25.250 25.000 1.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Building 61 11

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/10/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/10/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 4 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC10000069

FIRMWARE_ID: A09MA570.000 EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 2.530 2.500 1.20 PASS

B-N 2.530 2.500 1.20 PASS

C-N 2.530 2.500 1.20 PASS

Building 61 12

Relay Results (continued) for: UR-F35.FST02220

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 5.000 137.72 2.295 2.107 TO 2.388 PASS

3.00 7.500 57.07 0.951 0.835 TO 0.982 PASS

5.00 12.500 23.55 0.392 0.322 TO 0.415 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 5.000 137.78 2.296 2.107 TO 2.388 PASS

3.00 7.500 56.80 0.947 0.835 TO 0.982 PASS

5.00 12.500 23.43 0.390 0.322 TO 0.415 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 5.000 137.51 2.292 2.107 TO 2.388 PASS

3.00 7.500 56.66 0.944 0.835 TO 0.982 PASS

5.00 12.500 23.77 0.396 0.322 TO 0.415 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.500 25.000 2.00 PASS

B-N 25.250 25.000 1.00 PASS

C-N 25.250 25.000 1.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Building 61 13

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/10/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/10/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 5 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC9001456

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 2.555 2.500 2.20 PASS

B-N 2.555 2.500 2.20 PASS

C-N 2.530 2.500 1.20 PASS

Building 61 14

Relay Results (continued) for: UR-F35.FST31604

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 5.000 137.74 2.296 2.107 TO 2.388 PASS

3.00 7.500 56.41 0.940 0.835 TO 0.982 PASS

5.00 12.500 23.24 0.387 0.322 TO 0.415 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 5.000 136.91 2.282 2.107 TO 2.388 PASS

3.00 7.500 56.26 0.938 0.835 TO 0.982 PASS

5.00 12.500 23.16 0.386 0.322 TO 0.415 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 5.000 137.56 2.293 2.107 TO 2.388 PASS

3.00 7.500 56.17 0.936 0.835 TO 0.982 PASS

5.00 12.500 23.43 0.390 0.322 TO 0.415 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.250 25.000 1.00 PASS

B-N 25.250 25.000 1.00 PASS

C-N 25.250 25.000 1.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Building 61 15

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/13/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/13/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 7 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL:

F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER:

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 3.160 3.125 1.12 PASS

B-N 3.160 3.125 1.12 PASS

C-N 3.160 3.125 1.12 PASS

Building 61 16

Relay Results (continued) for: UR-F35.FST22399

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 6.250 91.22 1.520 1.395 TO 1.601 PASS

3.00 9.375 37.45 0.624 0.548 TO 0.664 PASS

5.00 15.625 15.65 0.261 0.205 TO 0.286 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 6.250 91.10 1.518 1.395 TO 1.601 PASS

3.00 9.375 37.70 0.628 0.548 TO 0.664 PASS

5.00 15.625 15.70 0.262 0.205 TO 0.286 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

2.00 6.250 91.27 1.521 1.395 TO 1.601 PASS

3.00 9.375 37.79 0.630 0.548 TO 0.664 PASS

5.00 15.625 15.86 0.264 0.205 TO 0.286 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.000 25.000 0.00 PASS

B-N 25.000 25.000 0.00 PASS

C-N 25.000 25.000 0.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Building 61 17

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/12/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 8 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC10001780

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 1.520 1.500 1.33 PASS

B-N 1.535 1.500 2.33 PASS

C-N 1.550 1.500 3.33 PASS

Page 1 of 212-Sep-2019Print Date:

Building 61 18

Relay Results (continued) for: UR-F35.FST24322

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 224.32 3.739 3.746 -0.19 PASS

3.00 4.500 91.63 1.527 1.514 0.83 PASS

5.00 7.500 37.67 0.628 0.614 2.21 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 224.71 3.745 3.746 -0.02 PASS

3.00 4.500 91.33 1.522 1.514 0.51 PASS

5.00 7.500 37.96 0.633 0.614 2.98 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 224.03 3.734 3.746 -0.32 PASS

3.00 4.500 91.42 1.524 1.514 0.61 PASS

5.00 7.500 37.93 0.632 0.614 2.89 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 25.000 25.000 0.00 PASS

B-N 25.000 25.000 0.00 PASS

C-N 25.000 25.000 0.00 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Page 2 of 212-Sep-2019Print Date:

Building 61 19

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/11/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 9 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER:

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 1.565 1.500 4.33 PASS

B-N 1.535 1.500 2.33 PASS

C-N 1.520 1.500 1.33 PASS

Page 1 of 211-Sep-2019Print Date:

Building 61 20

Relay Results (continued) for: UR-F35.FST08930

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 229.58 3.826 3.746 2.15 PASS

3.00 4.500 92.81 1.547 1.514 2.13 PASS

5.00 7.500 38.20 0.637 0.614 3.64 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 229.09 3.818 3.746 1.93 PASS

3.00 4.500 93.11 1.552 1.514 2.46 PASS

5.00 7.500 38.00 0.633 0.614 3.09 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 228.39 3.806 3.746 1.62 PASS

3.00 4.500 92.46 1.541 1.514 1.75 PASS

5.00 7.500 38.21 0.637 0.614 3.68 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 22.730 22.500 1.02 PASS

B-N 22.505 22.500 0.02 PASS

C-N 22.730 22.500 1.02 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Page 2 of 211-Sep-2019Print Date:

Building 61 21

Lib Version:

Lib Routine: UR-F35.FST_LIB

09/11/2019Test Date:2.1

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 10 DEVICE_NUMBER:

MANUFACTURER: GE RELAY_TYPE: GE F-35

MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:

Feeder

EQUIP_CLASS: SERIAL_NUMBER: AAIC09001529

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: PHASE TOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 1.535 1.500 2.33 PASS

B-N 1.520 1.500 1.33 PASS

C-N 1.505 1.500 0.33 PASS

Building 61 22

Relay Results (continued) for: UR-F35.FST23718

PHASE TOC 1 TIMING (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 227.87 3.798 3.746 1.39 PASS

3.00 4.500 92.57 1.543 1.514 1.87 PASS

5.00 7.500 38.02 0.634 0.614 3.14 PASS

PHASE TOC 1 TIMING (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 228.10 3.802 3.746 1.49 PASS

3.00 4.500 92.71 1.545 1.514 2.03 PASS

5.00 7.500 38.18 0.636 0.614 3.58 PASS

PHASE TOC 1 TIMING (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.000 228.26 3.804 3.746 1.56 PASS

3.00 4.500 92.38 1.540 1.514 1.66 PASS

5.00 7.500 38.34 0.639 0.614 4.02 PASS

PHASE TOC 1 TIMING

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

Relay Test Results for: PHASE IOC 1 PICKUP

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 22.730 22.500 1.02 PASS

B-N 22.505 22.500 0.02 PASS

C-N 22.730 22.500 1.02 PASS

Relay Test Results for: GROUND IOC 1 PICKUP

PICKUP CURRENT IDEAL %ERROR OK?

10.200 10.000 2.00 PASS

Building 61 23

52FA 2

52FB 4

52TA 6

52TB 9

52UA 12

52UB 15

GEN. 1 18

GEN. 2 22

GEN. 3 25

GEN. 4 30

GEN. 5 35

GEN. 6 39

Building 91 24

Lib Version:

Lib Routine: SEL-551.FST_LIB

09/12/2019Test Date:5.4

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: 52FA DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-551

MODEL: 0551003X531X ZONE_OF_PROTECTION: L

EQUIP_CLASS: SERIAL_NUMBER: 2009286475

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

FEEDER 52FA Date: 09/12/19 Time: 17:01:17.307

52FA -SWGR-A

FID=SEL-551-R513-Vf-Z002002-D20080104 CID=2A63

SELF TESTS

W=Warn F=Fail

IA IB IC IN MOF

OS 3 3 3 3 0

+5V_PS +5V_REG -5V_REG +10V_PS -10V_PS VBAT

PS 4.98 5.03 -4.96 9.95 -9.99 3.55

TEMP RAM ROM CR_RAM EEPROM

32.8 OK OK OK OK

Relay Enabled

Relay Test Results for: 50P1P PICKUP TEST (50P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 15.000 15.000 0.00 PASS

B-N 15.000 15.000 0.00 PASS

C-N 15.150 15.000 1.00 PASS

Page 1 of 212-Sep-2019Print Date:

Building 91 25

Relay Results (continued) for: SEL-551.FST00881

Relay Test Results for: 50G1P PICKUP TEST (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

0.614 0.600 2.33 PASS

Relay Test Results for: 51P1P PICKUP TEST (51P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 1.796 1.800 -0.22 PASS

B-N 1.814 1.800 0.78 PASS

C-N 1.814 1.800 0.78 PASS

Relay Test Results for: 51P1P TIMING TEST (51P1T)

51P1P TIMING TEST (51P1T) (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.600 261.68 4.361 4.332 0.69 PASS

3.00 5.400 100.94 1.682 1.674 0.50 PASS

4.00 7.200 56.60 0.943 0.930 1.47 PASS

51P1P TIMING TEST (51P1T) (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.600 261.40 4.357 4.332 0.58 PASS

3.00 5.400 100.38 1.673 1.674 -0.05 PASS

4.00 7.200 55.87 0.931 0.930 0.16 PASS

51P1P TIMING TEST (51P1T) (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.600 263.68 4.395 4.332 1.45 PASS

3.00 5.400 101.46 1.691 1.674 1.02 PASS

4.00 7.200 56.69 0.945 0.930 1.63 PASS

51P1P TIMING TEST (51P1T)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Page 2 of 212-Sep-2019Print Date:

Building 91 26

Lib Version:

Lib Routine: SEL-551.FST_LIB

09/11/2019Test Date:5.4

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: 52FB DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-551

MODEL: 0551003X531X ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER: 2009286476

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

FEEDER 52FB Date: 09/11/19 Time: 21:50:00.343

52FB -SWGR-B

FID=SEL-551-R513-Vf-Z002002-D20080104 CID=2A63

SELF TESTS

W=Warn F=Fail

IA IB IC IN MOF

OS 3 3 3 3 0

+5V_PS +5V_REG -5V_REG +10V_PS -10V_PS VBAT

PS 4.98 5.03 -5.11 9.97 -10.07 3.56

TEMP RAM ROM CR_RAM EEPROM

30.7 OK OK OK OK

Relay Enabled

Relay Test Results for: 50P1P PICKUP TEST (50P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 15.000 15.000 0.00 PASS

B-N 15.000 15.000 0.00 PASS

C-N 15.000 15.000 0.00 PASS

Building 91 27

Relay Results (continued) for: SEL-551.FST09690

Relay Test Results for: 50G1P PICKUP TEST (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

0.614 0.600 2.33 PASS

Relay Test Results for: 51P1P PICKUP TEST (51P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 1.796 1.800 -0.22 PASS

B-N 1.778 1.800 -1.22 PASS

C-N 1.796 1.800 -0.22 PASS

Relay Test Results for: 51P1P TIMING TEST (51P1T)

51P1P TIMING TEST (51P1T) (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.600 261.23 4.354 4.332 0.51 PASS

3.00 5.400 100.26 1.671 1.674 -0.17 PASS

4.00 7.200 56.22 0.937 0.930 0.79 PASS

51P1P TIMING TEST (51P1T) (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.600 259.70 4.328 4.332 -0.08 PASS

3.00 5.400 99.98 1.666 1.674 -0.45 PASS

4.00 7.200 56.18 0.936 0.930 0.71 PASS

51P1P TIMING TEST (51P1T) (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 3.600 259.12 4.319 4.332 -0.30 PASS

3.00 5.400 100.33 1.672 1.674 -0.10 PASS

4.00 7.200 56.00 0.933 0.930 0.39 PASS

51P1P TIMING TEST (51P1T)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Building 91 28

Lib Version:

Lib Routine: SEL-351A.FST_LIB

09/12/2019Test Date:5.11

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: 52TA DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-351A

MODEL: 0351A00323551XX ZONE_OF_PROTECTION: L

EQUIP_CLASS: SERIAL_NUMBER: 2009296158

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

TIE TA Date: 09/12/19 Time: 17:49:55.946

52TA

FID=SEL-351A-R402-V0-Z009007-D20071226 CID=C547

SELF TESTS

W=Warn F=Fail

IA IB IC IN VA VB VC VS MOF

OS -1 -1 -0 1 0 0 -2 -0 -0

+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS

PS 5.00 4.95 -5.05 12.05 -11.96 15.05 -15.13

TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD

39.5 OK OK OK OK OK OK

Relay Enabled

Page 1 of 312-Sep-2019Print Date:

Building 91 29

Relay Results (continued) for: SEL-351A.FST09882

Relay Test Results for: METER TEST

APPLIED APPLIED CURRENT

SEC VOLT SEC AMP PH LAG

67.00 2.00 30.00

PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

PRI KV PRI KV PRI CUR PRI CUR

A-B 11.4 11.4 -0.0 432.0 431.3 -0.2 PASS

B-C 11.8 11.8 -0.0 480.0 478.7 -0.3 PASS

C-A 11.6 11.6 -0.1 528.0 526.4 -0.3 PASS

CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

MEGA WATT MEGA WATT MEGA VAR MEGA VAR

8.4 8.3 -0.4 4.8 4.8 -0.4 PASS

Relay Test Results for: 50G1P PICKUP (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

0.394 0.400 -1.50 PASS

Relay Test Results for: 51PP PH PICKUP (51P)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 2.270 2.250 0.89 PASS

B-N 2.270 2.250 0.89 PASS

C-N 2.270 2.250 0.89 PASS

Relay Test Results for: 51P PH TIMING (51PT)

51P PH TIMING (51PT) (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.500 753.52 12.559 12.514 0.36 PASS

3.00 6.750 291.42 4.857 4.836 0.44 PASS

5.00 11.250 106.24 1.771 1.764 0.35 PASS

51P PH TIMING (51PT) (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.500 755.66 12.594 12.514 0.64 PASS

3.00 6.750 292.06 4.868 4.836 0.66 PASS

5.00 11.250 106.16 1.769 1.764 0.28 PASS

51P PH TIMING (51PT) (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.500 755.19 12.586 12.514 0.58 PASS

3.00 6.750 291.29 4.855 4.836 0.40 PASS

5.00 11.250 106.56 1.776 1.764 0.66 PASS

51P PH TIMING (51PT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Relay Test Results for: 27PP UV PICKUP (27AB)

PICKUP VOLTS IDEAL %ERROR OK?

5.002 5.000 0.04 PASS

Relay Test Results for: 59PP OV PICKUP (59AB)

PICKUP VOLTS IDEAL %ERROR OK?

118.000 118.000 -0.00 PASS

Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)

PICKUP VOLTS IDEAL %ERROR OK?

107.060 106.000 1.00 PASS

Page 2 of 312-Sep-2019Print Date:

Building 91 30

Relay Results (continued) for: SEL-351A.FST09882

Relay Test Results for: 25VLO VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

119.690 118.500 1.00 PASS

Relay Test Results for: 25VHI VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

130.897 130.900 -0.00 PASS

Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)

LAGGING ANGLE IDEAL RANGE OK?

10.00 10.00 6.00 TO 14.00 PASS

LEADING ANGLE IDEAL RANGE OK?

351.00 350.00 346.00 TO 354.00 PASS

Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)

LAGGING ANGLE IDEAL RANGE OK?

15.00 15.00 11.00 TO 19.00 PASS

LEADING ANGLE IDEAL RANGE OK?

346.00 345.00 341.00 TO 349.00 PASS

Page 3 of 312-Sep-2019Print Date:

Building 91 31

Lib Version:

Lib Routine: SEL-351A.FST_LIB

09/12/2019Test Date:5.11

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: 52TB DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-351A

MODEL: 0351A00323551XX ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER: 2009293274

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

TIE TB Date: 09/11/19 Time: 22:47:36.750

52TB

FID=SEL-351A-R402-V0-Z009007-D20071226 CID=C547

SELF TESTS

W=Warn F=Fail

IA IB IC IN VA VB VC VS MOF

OS 2 1 -2 1 80W -1 35W 1 0

+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS

PS 5.03 4.97 -5.02 12.13 -12.06 14.93 -15.01

TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD

37.4 OK OK OK OK OK OK

Relay Enabled

Building 91 32

Relay Results (continued) for: SEL-351A.FST07033

APPLIED APPLIED CURRENT

SEC VOLT SEC AMP PH LAG

67.00 2.00 30.00

PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

PRI KV PRI KV PRI CUR PRI CUR

A-B 11.4 11.4 -0.0 432.0 431.0 -0.2 PASS

B-C 11.8 11.8 0.0 480.0 479.4 -0.1 PASS

C-A 11.6 11.6 -0.0 528.0 526.6 -0.3 PASS

CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

MEGA WATT MEGA WATT MEGA VAR MEGA VAR

8.4 8.3 -0.3 4.8 4.8 -0.4 PASS

Relay Test Results for: 50G1P PICKUP (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

0.394 0.400 -1.50 PASS

Relay Test Results for: 51PP PH PICKUP (51P)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 2.270 2.250 0.89 PASS

B-N 2.270 2.250 0.89 PASS

C-N 2.270 2.250 0.89 PASS

Relay Test Results for: 51P PH TIMING (51PT)

51P PH TIMING (51PT) (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.500 754.18 12.570 12.514 0.45 PASS

3.00 6.750 291.71 4.862 4.836 0.54 PASS

5.00 11.250 106.54 1.776 1.764 0.64 PASS

51P PH TIMING (51PT) (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.500 753.72 12.562 12.514 0.39 PASS

3.00 6.750 291.73 4.862 4.836 0.55 PASS

5.00 11.250 106.21 1.770 1.764 0.33 PASS

51P PH TIMING (51PT) (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.500 755.50 12.592 12.514 0.62 PASS

3.00 6.750 291.53 4.859 4.836 0.48 PASS

5.00 11.250 106.39 1.773 1.764 0.50 PASS

51P PH TIMING (51PT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Relay Test Results for: 27PP UV PICKUP (27AB)

PICKUP VOLTS IDEAL %ERROR OK?

5.002 5.000 0.04 PASS

Relay Test Results for: 59PP OV PICKUP (59AB)

PICKUP VOLTS IDEAL %ERROR OK?

119.180 118.000 1.00 PASS

Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)

PICKUP VOLTS IDEAL %ERROR OK?

107.060 106.000 1.00 PASS

Building 91 33

Relay Results (continued) for: SEL-351A.FST07033

Relay Test Results for: 25VLO VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

119.690 118.500 1.00 PASS

Relay Test Results for: 25VHI VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

130.897 130.900 -0.00 PASS

Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)

LAGGING ANGLE IDEAL RANGE OK?

10.00 10.00 6.00 TO 14.00 PASS

LEADING ANGLE IDEAL RANGE OK?

351.00 350.00 346.00 TO 354.00 PASS

Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)

LAGGING ANGLE IDEAL RANGE OK?

15.00 15.00 11.00 TO 19.00 PASS

LEADING ANGLE IDEAL RANGE OK?

346.00 345.00 341.00 TO 349.00 PASS

Building 91 34

Lib Version:

Lib Routine: SEL-351.FST_LIB

09/12/2019Test Date:5.13

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: 52UA DEVICE_NUMBER:

MANUFACTURER: RELAY_TYPE: SEL-351

MODEL: ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER:

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

UA_UPR Date: 09/12/19 Time: 19:39:39.990

UTILITY A 52UA

FID=SEL-351-7-R402-V0-Z008006-D20080103 CID=19F9

SELF TESTS

W=Warn F=Fail

IA IB IC IN VA VB VC VS MOF

OS 0 0 1 1 -1 1 1 1 0

+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS

PS 5.02 4.97 -5.04 12.05 -11.95 14.99 -15.04

TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD

38.3 OK OK OK OK OK OK

Relay Enabled

Building 91 35

Relay Results (continued) for: SEL-351.FST20134

APPLIED APPLIED CURRENT

SEC VOLT SEC AMP PH LAG

67.00 2.00 30.00

PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

PRI KV PRI KV PRI CUR PRI CUR

A-B 11.4 11.4 -0.0 432.0 431.4 -0.1 PASS

B-C 11.8 11.8 0.0 480.0 479.2 -0.2 PASS

C-A 11.6 11.6 0.1 528.0 526.7 -0.2 PASS

CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

MEGA WATT MEGA WATT MEGA VAR MEGA VAR

8.4 8.3 -0.3 4.8 4.8 -0.1 PASS

Relay Test Results for: 50P1P PICKUP (50P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 20.200 20.000 1.00 PASS

B-N 20.200 20.000 1.00 PASS

C-N 20.200 20.000 1.00 PASS

Relay Test Results for: 50G1P PICKUP (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

0.394 0.400 -1.50 PASS

Relay Test Results for: 51PP PH PICKUP (51P)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 2.118 2.100 0.86 PASS

B-N 2.118 2.100 0.86 PASS

C-N 2.118 2.100 0.86 PASS

Relay Test Results for: 51P PH TIMING (51PT)

51P PH TIMING (51PT) (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.200 463.66 7.728 7.701 0.35 PASS

3.00 6.300 179.71 2.995 2.976 0.65 PASS

4.00 8.400 100.31 1.672 1.653 1.16 PASS

51P PH TIMING (51PT) (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.200 465.09 7.752 7.701 0.66 PASS

3.00 6.300 180.46 3.008 2.976 1.07 PASS

4.00 8.400 100.21 1.670 1.653 1.05 PASS

51P PH TIMING (51PT) (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.200 464.75 7.746 7.701 0.58 PASS

3.00 6.300 179.75 2.996 2.976 0.68 PASS

4.00 8.400 100.49 1.675 1.653 1.34 PASS

51P PH TIMING (51PT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Relay Test Results for: 27PP UV PICKUP (27AB)

PICKUP VOLTS IDEAL %ERROR OK?

107.999 108.000 -0.00 PASS

Relay Test Results for: 81D1P FREQ PICKUP (81D1)

PICKUP HZ IDEAL RANGE OK?

59.100 59.100 59.050 TO 59.150 PASS

Building 91 36

Relay Results (continued) for: SEL-351.FST20134

Relay Test Results for: 81D1D FREQ TIME (81D1T)

APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?

58.900 2.079 122.47 120.00 TO 124.50 PASS

Relay Test Results for: 81D2P FREQ PICKUP (81D2)

PICKUP HZ IDEAL RANGE OK?

59.800 59.800 59.750 TO 59.850 PASS

Relay Test Results for: 81D2D FREQ TIME (81D2T)

APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?

59.600 5.0685 302.083 300.000 TO 304.500 PASS

Relay Test Results for: 81D3P FREQ PICKUP (81D3)

PICKUP HZ IDEAL RANGE OK?

60.100 60.100 60.050 TO 60.150 PASS

Relay Test Results for: 81D3D FREQ TIME (81D3T)

APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?

60.300 2.024 122.05 120.00 TO 124.50 PASS

Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)

PICKUP VOLTS IDEAL %ERROR OK?

111.100 110.000 1.00 PASS

Relay Test Results for: 25VLO VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

118.505 118.500 0.00 PASS

Relay Test Results for: 25VHI VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

130.897 130.900 -0.00 PASS

Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)

LAGGING ANGLE IDEAL RANGE OK?

10.00 10.00 6.00 TO 14.00 PASS

LEADING ANGLE IDEAL RANGE OK?

351.00 350.00 346.00 TO 354.00 PASS

Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)

LAGGING ANGLE IDEAL RANGE OK?

15.00 15.00 11.00 TO 19.00 PASS

LEADING ANGLE IDEAL RANGE OK?

346.00 345.00 341.00 TO 349.00 PASS

Building 91 37

Lib Version:

Lib Routine: SEL-351.FST_LIB

09/12/2019Test Date:5.13

Relay Data:

TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: 52UB DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-351

MODEL: 03517033551XXX ZONE_OF_PROTECTION: L

EQUIP_CLASS: SERIAL_NUMBER: 2009303171

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

UB_UPR Date: 09/11/19 Time: 23:33:56.574

UTILITY A 52UB

FID=SEL-351-7-R402-V0-Z008006-D20080103 CID=19F9

SELF TESTS

W=Warn F=Fail

IA IB IC IN VA VB VC VS MOF

OS -1 -1 -1 -1 -0 -1 -0 -1 -1

+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS

PS 4.99 5.01 -4.97 11.86 -12.03 15.01 -15.03

TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD

32.5 OK OK OK OK OK OK

Relay Enabled

Building 91 38

Relay Results (continued) for: SEL-351.FST24882

APPLIED APPLIED CURRENT

SEC VOLT SEC AMP PH LAG

67.00 2.00 30.00

PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

PRI KV PRI KV PRI CUR PRI CUR

A-B 11.4 11.4 -0.1 432.0 431.3 -0.2 PASS

B-C 11.8 11.8 0.1 480.0 479.4 -0.1 PASS

C-A 11.6 11.6 0.0 528.0 526.6 -0.3 PASS

CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

MEGA WATT MEGA WATT MEGA VAR MEGA VAR

8.4 8.4 -0.3 4.8 4.8 -0.4 PASS

Relay Test Results for: 50P1P PICKUP (50P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 20.200 20.000 1.00 PASS

B-N 20.000 20.000 -0.00 PASS

C-N 20.200 20.000 1.00 PASS

Relay Test Results for: 50G1P PICKUP (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

0.394 0.400 -1.50 PASS

Relay Test Results for: 51PP PH PICKUP (51P)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

A-N 2.118 2.100 0.86 PASS

B-N 2.118 2.100 0.86 PASS

C-N 2.118 2.100 0.86 PASS

Relay Test Results for: 51P PH TIMING (51PT)

51P PH TIMING (51PT) (PHASE A-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.200 464.38 7.740 7.701 0.51 PASS

3.00 6.300 180.12 3.002 2.976 0.88 PASS

4.00 8.400 99.97 1.666 1.653 0.81 PASS

51P PH TIMING (51PT) (PHASE B-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.200 464.17 7.736 7.701 0.46 PASS

3.00 6.300 180.23 3.004 2.976 0.94 PASS

4.00 8.400 100.09 1.668 1.653 0.93 PASS

51P PH TIMING (51PT) (PHASE C-N)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.200 465.59 7.760 7.701 0.77 PASS

3.00 6.300 179.86 2.998 2.976 0.73 PASS

4.00 8.400 100.24 1.671 1.653 1.08 PASS

51P PH TIMING (51PT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.2

0.5

1.0

2.0

5.0

10.0

20.0

Relay Test Results for: 27PP UV PICKUP (27AB)

PICKUP VOLTS IDEAL %ERROR OK?

107.999 108.000 -0.00 PASS

Relay Test Results for: 81D1P FREQ PICKUP (81D1)

PICKUP HZ IDEAL RANGE OK?

59.100 59.100 59.050 TO 59.150 PASS

Building 91 39

Relay Results (continued) for: SEL-351.FST24882

Relay Test Results for: 81D1D FREQ TIME (81D1T)

APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?

58.900 2.078 122.38 120.00 TO 124.50 PASS

Relay Test Results for: 81D2P FREQ PICKUP (81D2)

PICKUP HZ IDEAL RANGE OK?

59.800 59.800 59.750 TO 59.850 PASS

Relay Test Results for: 81D2D FREQ TIME (81D2T)

APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?

59.600 5.0641 301.820 300.000 TO 304.500 PASS

Relay Test Results for: 81D3P FREQ PICKUP (81D3)

PICKUP HZ IDEAL RANGE OK?

60.100 60.100 60.050 TO 60.150 PASS

Relay Test Results for: 81D3D FREQ TIME (81D3T)

APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?

60.300 2.018 121.67 120.00 TO 124.50 PASS

Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)

PICKUP VOLTS IDEAL %ERROR OK?

111.100 110.000 1.00 PASS

Relay Test Results for: 25VLO VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

118.505 118.500 0.00 PASS

Relay Test Results for: 25VHI VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

130.897 130.900 -0.00 PASS

Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)

LAGGING ANGLE IDEAL RANGE OK?

10.00 10.00 6.00 TO 14.00 PASS

LEADING ANGLE IDEAL RANGE OK?

351.00 350.00 346.00 TO 354.00 PASS

Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)

LAGGING ANGLE IDEAL RANGE OK?

15.00 15.00 11.00 TO 19.00 PASS

LEADING ANGLE IDEAL RANGE OK?

346.00 345.00 341.00 TO 349.00 PASS

Building 91 40

Lib Version:

Lib Routine: SEL-300G.FST_LIB

11/12/2019Test Date:5.9

Relay Data:

TESTED_BY: Bill Liss DATE_: 11/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: GEN. 1 DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-300G

MODEL: 0300G303325XX12XX ZONE_OF_PROTECTION: G

EQUIP_CLASS: SERIAL_NUMBER: 2009288184

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

GENERATOR 1 Date: 11/12/19 Time: 09:24:59.056

G1_GPR

FID=SEL-300G-R326-V203325XX12XX-Z302302-D20081231 CID=0340

SELF TESTS

W=Warn F=Fail

IA IB IC IN VA VB VC VN MOF

OS -1 -2 -1 -1 -1 -0 -2 0 -0

VS

OS 1

+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS

PS 5.01 4.99 -4.99 12.00 -12.00 15.07 -15.08

TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD

37.0 OK OK OK OK OK OK

Relay Enabled

Page 1 of 412-Nov-2019Print Date:

Building 91 41

Relay Results (continued) for: SEL-300G.FST10926

APPLIED APPLIED CURRENT

SEC VOLT SEC AMP PH LAG

72.00 2.00 30.00

PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

PRI KV PRI KV PRI CUR PRI CUR

A-B 12.1 12.3 1.5 72.0 71.8 -0.3 PASS

B-C 12.5 12.6 1.4 80.0 79.8 -0.2 PASS

C-A 12.8 12.5 -2.7 88.0 87.8 -0.3 PASS

CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

MEGA WATT MEGA WATT MEGA VAR MEGA VAR

1.5 1.5 -0.1 0.9 0.9 -0.9 PASS

Relay Test Results for: 32P1P PWR PICKUP (32P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

3PH 0.146 0.145 0.66 PASS

Relay Test Results for: 32P1D PWR DELAY (32P1T)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

1.20 0.174 1202.18 20.036 19.000 TO 21.000 PASS

Relay Test Results for: 32P2P PWR PICKUP (32P2)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

3PH 0.322 0.319 0.91 PASS

Relay Test Results for: 32P2D PWR DELAY (32P2T)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

1.20 0.383 302.18 5.036 4.725 TO 5.275 PASS

Relay Test Results for: 50G1P OC PICKUP (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

2.505 2.500 0.20 PASS

Relay Test Results for: 50G1D OC DELAY (50G1T)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

1.20 3.000 55.25 0.921 0.830 TO 0.970 PASS

Relay Test Results for: 51GP OC PICKUP (51G)

PICKUP CURRENT IDEAL %ERROR OK?

2.505 2.500 0.20 PASS

Relay Test Results for: 51G OC TIMING (51GT)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 5.000 116.48 1.941 1.925 0.84 PASS

3.00 7.500 45.43 0.757 0.744 1.78 PASS

4.00 10.000 25.67 0.428 0.413 3.53 PASS

51G OC TIMING (51GT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: 51VP (100%) PICKUP (51V)

PICKUP CURRENT IDEAL %ERROR OK?

3.334 3.300 1.03 PASS

Relay Test Results for: 51VP (75%) PICKUP (51V)

PICKUP CURRENT IDEAL %ERROR OK?

2.498 2.475 0.93 PASS

Page 2 of 412-Nov-2019Print Date:

Building 91 42

Relay Test Results for: 51V (100%) TIMING (51VT)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 6.600 116.58 1.943 1.925 0.92 PASS

3.00 9.900 45.07 0.751 0.744 0.96 PASS

4.00 13.200 25.58 0.426 0.413 3.17 PASS

51V (100%) TIMING (51VT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: 51V (75%) TIMING (51VT)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.950 116.71 1.945 1.925 1.04 PASS

4.00 9.900 25.10 0.418 0.413 1.23 PASS

6.00 14.850 12.16 0.203 0.197 2.74 PASS

51V (75%) TIMING (51VT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: 81D1P FREQ PICKUP (81D1)

PICKUP HZ IDEAL RANGE OK?

57.500 57.500 57.450 TO 57.550 PASS

Relay Test Results for: 81D1D FREQ DELAY (81D1T)

APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?

57.300 289.72 5.056 5.000 TO 5.150 PASS

Relay Test Results for: 81D2P FREQ PICKUP (81D2)

PICKUP HZ IDEAL RANGE OK?

57.000 57.000 56.950 TO 57.050 PASS

Relay Test Results for: 81D2D FREQ DELAY (81D2T)

APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?

56.800 176.82 3.113 3.000 TO 3.150 PASS

Relay Test Results for: 27VSP UV VS PICKUP (27VS)

PICKUP VOLTS IDEAL %ERROR OK?

5.000 5.000 0.00 PASS

Relay Test Results for: 25VLO VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

113.120 112.000 1.00 PASS

Relay Test Results for: 25VHI VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

134.640 136.000 -1.00 PASS

Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)

LAGGING ANGLE IDEAL RANGE OK?

10.00 10.00 6.00 TO 14.00 PASS

LEADING ANGLE IDEAL RANGE OK?

351.00 350.00 346.00 TO 354.00 PASS

Page 3 of 412-Nov-2019Print Date:

Building 91 43

Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)

LAGGING ANGLE IDEAL RANGE OK?

15.00 15.00 11.00 TO 19.00 PASS

LEADING ANGLE IDEAL RANGE OK?

345.00 345.00 341.00 TO 349.00 PASS

Page 4 of 412-Nov-2019Print Date:

Building 91 44

Lib Version:

Lib Routine: SEL-300G.FST_LIB

11/12/2019Test Date:5.9

Relay Data:

TESTED_BY: Bill Liss DATE_: 11/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: GEN. 2 DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-300G

MODEL: ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER: 2009288183

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine Notes:

Relay Settings Used for Testing:

[Suppressed]

Relay Test Results for: RELAY STATUS CHECK

N/A

Additional Data:

STA

GENERATOR 2 Date: 11/12/19 Time: 12:37:57.303

G2_GPR

FID=SEL-300G-R326-V203325XX12XX-Z302302-D20081231 CID=0340

SELF TESTS

W=Warn F=Fail

IA IB IC IN VA VB VC VN MOF

OS -1 -2 -0 0 -0 1 -1 -1 0

VS

OS 2

+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS

PS 5.02 4.95 -4.98 11.94 -11.99 15.02 -14.99

TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD

34.4 OK OK OK OK OK OK

Relay Enabled

Page 1 of 312-Nov-2019Print Date:

Building 91 45

Relay Results (continued) for: SEL-300G.FST15455

APPLIED APPLIED CURRENT

SEC VOLT SEC AMP PH LAG

72.00 2.00 30.00

PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

PRI KV PRI KV PRI CUR PRI CUR

A-B 12.1 12.3 1.5 72.0 71.8 -0.2 PASS

B-C 12.5 12.6 1.4 80.0 79.8 -0.2 PASS

C-A 12.8 12.5 -2.8 88.0 87.8 -0.3 PASS

CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?

MEGA WATT MEGA WATT MEGA VAR MEGA VAR

1.5 1.5 -0.2 0.9 0.9 -0.5 PASS

Relay Test Results for: 32P1P PWR PICKUP (32P1)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

3PH 0.147 0.145 1.66 PASS

Relay Test Results for: 32P1D PWR DELAY (32P1T)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

1.20 0.174 1202.18 20.036 19.000 TO 21.000 PASS

Relay Test Results for: 32P2P PWR PICKUP (32P2)

PHASE PICKUP CURRENT IDEAL %ERROR OK?

3PH 0.322 0.319 0.91 PASS

Relay Test Results for: 32P2D PWR DELAY (32P2T)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

1.20 0.383 302.09 5.035 4.725 TO 5.275 PASS

Relay Test Results for: 50G1P OC PICKUP (50G1)

PICKUP CURRENT IDEAL %ERROR OK?

2.505 2.500 0.20 PASS

Relay Test Results for: 50G1D OC DELAY (50G1T)

MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?

1.20 3.000 55.43 0.924 0.830 TO 0.970 PASS

Relay Test Results for: 51VP (100%) PICKUP (51V)

PICKUP CURRENT IDEAL %ERROR OK?

3.301 3.300 0.03 PASS

Relay Test Results for: 51VP (75%) PICKUP (51V)

PICKUP CURRENT IDEAL %ERROR OK?

2.498 2.475 0.93 PASS

Relay Test Results for: 51V (100%) TIMING (51VT)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 6.600 117.22 1.954 1.925 1.48 PASS

3.00 9.900 45.27 0.754 0.744 1.42 PASS

4.00 13.200 24.97 0.416 0.413 0.73 PASS

51V (100%) TIMING (51VT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Page 2 of 312-Nov-2019Print Date:

Building 91 46

Relay Results (continued) for: SEL-300G.FST15455

Relay Test Results for: 51V (75%) TIMING (51VT)

MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?

2.00 4.950 116.94 1.949 1.925 1.24 PASS

4.00 9.900 25.41 0.424 0.413 2.49 PASS

6.00 14.850 11.98 0.200 0.197 1.22 PASS

51V (75%) TIMING (51VT)

MULTIPLE OF TAP

1.5 2 2.5 4 6 8 10 20

T

IM

E

IN

S E

C O

N D

S

0.02

0.05

0.10

0.20

0.50

1.00

2.00

5.00

10.00

Relay Test Results for: 81D1P FREQ PICKUP (81D1)

PICKUP HZ IDEAL RANGE OK?

57.490 57.500 57.450 TO 57.550 PASS

Relay Test Results for: 81D1D FREQ DELAY (81D1T)

APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?

57.300 293.03 5.114 5.000 TO 5.150 PASS

Relay Test Results for: 81D2P FREQ PICKUP (81D2)

PICKUP HZ IDEAL RANGE OK?

56.990 57.000 56.950 TO 57.050 PASS

Relay Test Results for: 81D2D FREQ DELAY (81D2T)

APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?

56.800 176.77 3.112 3.000 TO 3.150 PASS

Relay Test Results for: 27VSP UV VS PICKUP (27VS)

PICKUP VOLTS IDEAL %ERROR OK?

5.000 5.000 0.00 PASS

Relay Test Results for: 25VLO VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

113.120 112.000 1.00 PASS

Relay Test Results for: 25VHI VS THRESHOLD (59VS)

PICKUP VOLTS IDEAL %ERROR OK?

134.640 136.000 -1.00 PASS

Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)

LAGGING ANGLE IDEAL RANGE OK?

10.00 10.00 6.00 TO 14.00 PASS

LEADING ANGLE IDEAL RANGE OK?

349.00 350.00 346.00 TO 354.00 PASS

Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)

LAGGING ANGLE IDEAL RANGE OK?

15.00 15.00 11.00 TO 19.00 PASS

LEADING ANGLE IDEAL RANGE OK?

346.00 345.00 341.00 TO 349.00 PASS

Page 3 of 312-Nov-2019Print Date:

Building 91 47

Lib Version:

Lib Routine: SEL-300G.FST_LIB

11/13/2019Test Date:5.9

Relay Data:

TESTED_BY: Bill Liss DATE_: 11/13/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91

EQUIP_POSITION: GEN. 3 DEVICE_NUMBER:

MANUFACTURER: Schweitzer RELAY_TYPE: SEL-300G

MODEL: 0300G303325XX12XX ZONE_OF_PROTECTION:

EQUIP_CLASS: SERIAL_NUMBER: 2009295106

FIRMWARE_ID: EQUIP_NUMBER:

NERC_PRC_002: NERC_PRC_005:

UFLS: PREVIOUS_TESTDATE:

CURRENT_TESTDATE: NEXT_TESTDATE:

TESTSET_CALDATE: 5/9/2019 APPROVED_BY:

LOCATION_POSITION:

Global Defines:

[Suppressed]

Routine