Relay Testing Report Biloxi VA.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25621R0055
About this file
This federal contract opportunity notice seeks proposals for an upgrade of emergency electrical systems at the Gulf Coast Veterans Health Care System in Biloxi, Mississippi. The project number is 520-22-108 with an estimated construction cost range between $500,000 and $1,000,000.
The solicitation will be issued as a 100% set-aside for service-disabled veteran-owned small businesses. Interested contractors can expect the request for proposals to be released on or around January 25th, 2021, with proposals due approximately 30 days later on February 25th. The contract award date is anticipated within 30 days after receipt of proposals. The performance period will be 120 calendar days from the notice to proceed.
The selected contractor must perform at least 15% of the on-site labor costs using its own employees or those of other eligible SDVOSBs for general construction. For specialty trades, 25% of labor costs must be performed by eligible firms. Offerors must be verified as SDVOSBs in the Vendor Information Pages database and registered in the System for Award Management at the time of proposal submission.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Electrical Testing Solutions
Field Service Letter
Work Completed:
November 14, 2019
Prepared For:
Department of Veterans Affair
Gulf Coast Health Care System 400 Veterans Avenue
Biloxi, MS 39531
VHABILDAVENC
Text Box
Project No. 520-22-108 Upgrade Emergency Electrical Systems, Biloxi
Relay Testing Report for:
Gulf Coast Health Care System
400 Veterans Avenue
Biloxi, MS 39531
2909 Green Hill Ct., STE I • Oshkosh, WI 54904 • p920.420.2986 f920.235.7136 www.electricaltestingsolutions.com
October 7, 2019
Attn: Tina Harris
Gulf Coast Veterans Health Care System
RE: Gulf Coast Veterans Health Care System Relay testing.
Dear Tina, This report contains the detailed information related to the relay testing conducted at the Gulf Coast Veterans Health Care System facility located at 400 Veterans Avenue, Biloxi, MS 39531.
Objective
ETS was to perform relay testing as part of the preventative maintenance schedule of Gulf Coast Veterans Health Care System facility, located at 400 Veterans Avenue, Biloxi, MS 39531.
Results and Recommendations
All the relays tested well and are ready for normal use. Detailed results of the tested relays are provided in this report.
We appreciate this opportunity to be of service to you. If you have any questions regarding this report feel free to contact me.
Sincerely, Ranniery Ribeiro Electrical Engineer Electrical Testing Solutions Office: (920) 420-2986 Email: rribeiro@electricaltestingsolutions.com http://electricaltestingsolutions.com/
Relay Testing Report
Work Completed:
November 14, 2019
Prepared For:
Gulf Coast Health Care System
Building 31 2
Building 61 5
Building 91 24
BLDG. 31 FEEDER 9 2
BLDG. 31 FEEDER 10 3
Building 31 2
RTS Relay Test Results
AL PASSPass/Fail:AF/AL:
Lib Version:
Lib Routine: SR-750/760.FST_LIB
09/11/2019Test Date:2.4
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 31 EQUIP_POSITION: FDR. No. 9 DEVICE_NUMBER:
MANUFACTURER: RELAY_TYPE: GE-SR750
MODEL: ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER:
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PH TIME OC1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 0.768 0.750 2.33 PASS
B-N 0.752 0.750 0.33 PASS
C-N 0.752 0.750 0.33 PASS
Relay Test Results for: A PH TOC1 TIMING TEST
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 1.500 266.28 4.438 4.361 1.77 PASS
3.00 2.250 99.94 1.666 1.648 1.05 PASS
4.00 3.000 55.22 0.920 0.920 0.06 PASS
A PH TOC1 TIMING TEST
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Relay Test Results for: PH INST OC1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 11.360 11.250 0.98 PASS
B-N 11.248 11.250 -0.02 PASS
C-N 11.248 11.250 -0.02 PASS
Page 1 of 111-Sep-2019Print Date:
Building 31 3
Lib Version:
Lib Routine: SR-750/760.FST_LIB
09/11/2019Test Date:2.4
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 31 EQUIP_POSITION: FDR. No. 10 DEVICE_NUMBER:
MANUFACTURER: RELAY_TYPE: GE-SR750
MODEL: ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER:
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PH TIME OC1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 0.760 0.750 1.33 PASS
B-N 0.760 0.750 1.33 PASS
C-N 0.760 0.750 1.33 PASS
Relay Test Results for: A PH TOC1 TIMING TEST
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 1.500 264.20 4.403 4.361 0.97 PASS
3.00 2.250 99.92 1.665 1.648 1.02 PASS
4.00 3.000 56.27 0.938 0.920 1.96 PASS
A PH TOC1 TIMING TEST
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Relay Test Results for: PH INST OC1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 11.360 11.250 0.98 PASS
B-N 11.360 11.250 0.98 PASS
C-N 11.360 11.250 0.98 PASS
Page 1 of 111-Sep-2019Print Date:
Building 31 4
FEEDER NO. 1 2
FEEDER NO. 2 4
FEEDER NO. 3 6
FEEDER NO. 4 8
FEEDER NO. 5 10
FEEDER NO. 7 12
FEEDER NO. 8 14
FEEDER NO. 9 16
FEEDER NO. 10 18
Building 61 5
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/10/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/9/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 1 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC10000066
FIRMWARE_ID: A09MA570.000 EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RUN AND READ SETTING NOTIFICATION MESSAGE
OK?
RAN
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 1.535 1.500 2.33 PASS
B-N 1.520 1.500 1.33 PASS
C-N 1.505 1.500 0.33 PASS
Page 1 of 210-Sep-2019Print Date:
Building 61 6
Relay Results (continued) for: UR-F35.FST19942
Relay Test Results for: PHASE TOC 1 TIMING
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 223.87 3.731 3.746 -0.39 PASS
3.00 4.500 91.13 1.519 1.514 0.29 PASS
5.00 7.500 38.10 0.635 0.614 3.37 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 223.63 3.727 3.746 -0.50 PASS
3.00 4.500 91.31 1.522 1.514 0.48 PASS
5.00 7.500 37.66 0.628 0.614 2.18 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 223.37 3.723 3.746 -0.62 PASS
3.00 4.500 91.13 1.519 1.514 0.29 PASS
5.00 7.500 37.57 0.626 0.614 1.93 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.250 25.000 1.00 PASS
B-N 25.250 25.000 1.00 PASS
C-N 25.250 25.000 1.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.300 10.000 3.00 PASS
Page 2 of 210-Sep-2019Print Date:
Building 61 7
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/13/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/13/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 2 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC10000067
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 3.828 3.750 2.07 PASS
B-N 3.790 3.750 1.07 PASS
C-N 3.790 3.750 1.07 PASS
Page 1 of 213-Sep-2019Print Date:
Building 61 8
Relay Results (continued) for: UR-F35.FST10778
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 7.500 69.30 1.155 1.040 TO 1.208 PASS
3.00 11.250 28.33 0.472 0.404 TO 0.505 PASS
5.00 18.750 12.22 0.204 0.147 TO 0.222 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 7.500 66.54 1.109 1.040 TO 1.208 PASS
3.00 11.250 28.75 0.479 0.404 TO 0.505 PASS
5.00 18.750 12.02 0.200 0.147 TO 0.222 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 7.500 68.49 1.142 1.040 TO 1.208 PASS
3.00 11.250 28.54 0.476 0.404 TO 0.505 PASS
5.00 18.750 11.99 0.200 0.147 TO 0.222 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.250 25.000 1.00 PASS
B-N 25.250 25.000 1.00 PASS
C-N 25.250 25.000 1.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Page 2 of 213-Sep-2019Print Date:
Building 61 9
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/12/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 3 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC10000063
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 3.191 3.125 2.12 PASS
B-N 3.160 3.125 1.12 PASS
C-N 3.160 3.125 1.12 PASS
Building 61 10
Relay Results (continued) for: UR-F35.FST18962
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 6.250 90.82 1.514 1.395 TO 1.601 PASS
3.00 9.375 37.38 0.623 0.548 TO 0.664 PASS
5.00 15.625 15.76 0.263 0.205 TO 0.286 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 6.250 90.50 1.508 1.395 TO 1.601 PASS
3.00 9.375 37.68 0.628 0.548 TO 0.664 PASS
5.00 15.625 15.53 0.259 0.205 TO 0.286 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 6.250 90.95 1.516 1.395 TO 1.601 PASS
3.00 9.375 37.30 0.622 0.548 TO 0.664 PASS
5.00 15.625 15.49 0.258 0.205 TO 0.286 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.000 25.000 0.00 PASS
B-N 25.250 25.000 1.00 PASS
C-N 25.250 25.000 1.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Building 61 11
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/10/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/10/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 4 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC10000069
FIRMWARE_ID: A09MA570.000 EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 2.530 2.500 1.20 PASS
B-N 2.530 2.500 1.20 PASS
C-N 2.530 2.500 1.20 PASS
Building 61 12
Relay Results (continued) for: UR-F35.FST02220
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 5.000 137.72 2.295 2.107 TO 2.388 PASS
3.00 7.500 57.07 0.951 0.835 TO 0.982 PASS
5.00 12.500 23.55 0.392 0.322 TO 0.415 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 5.000 137.78 2.296 2.107 TO 2.388 PASS
3.00 7.500 56.80 0.947 0.835 TO 0.982 PASS
5.00 12.500 23.43 0.390 0.322 TO 0.415 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 5.000 137.51 2.292 2.107 TO 2.388 PASS
3.00 7.500 56.66 0.944 0.835 TO 0.982 PASS
5.00 12.500 23.77 0.396 0.322 TO 0.415 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.500 25.000 2.00 PASS
B-N 25.250 25.000 1.00 PASS
C-N 25.250 25.000 1.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Building 61 13
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/10/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/10/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 5 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC9001456
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 2.555 2.500 2.20 PASS
B-N 2.555 2.500 2.20 PASS
C-N 2.530 2.500 1.20 PASS
Building 61 14
Relay Results (continued) for: UR-F35.FST31604
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 5.000 137.74 2.296 2.107 TO 2.388 PASS
3.00 7.500 56.41 0.940 0.835 TO 0.982 PASS
5.00 12.500 23.24 0.387 0.322 TO 0.415 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 5.000 136.91 2.282 2.107 TO 2.388 PASS
3.00 7.500 56.26 0.938 0.835 TO 0.982 PASS
5.00 12.500 23.16 0.386 0.322 TO 0.415 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 5.000 137.56 2.293 2.107 TO 2.388 PASS
3.00 7.500 56.17 0.936 0.835 TO 0.982 PASS
5.00 12.500 23.43 0.390 0.322 TO 0.415 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.250 25.000 1.00 PASS
B-N 25.250 25.000 1.00 PASS
C-N 25.250 25.000 1.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Building 61 15
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/13/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/13/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 7 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL:
F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER:
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 3.160 3.125 1.12 PASS
B-N 3.160 3.125 1.12 PASS
C-N 3.160 3.125 1.12 PASS
Building 61 16
Relay Results (continued) for: UR-F35.FST22399
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 6.250 91.22 1.520 1.395 TO 1.601 PASS
3.00 9.375 37.45 0.624 0.548 TO 0.664 PASS
5.00 15.625 15.65 0.261 0.205 TO 0.286 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 6.250 91.10 1.518 1.395 TO 1.601 PASS
3.00 9.375 37.70 0.628 0.548 TO 0.664 PASS
5.00 15.625 15.70 0.262 0.205 TO 0.286 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
2.00 6.250 91.27 1.521 1.395 TO 1.601 PASS
3.00 9.375 37.79 0.630 0.548 TO 0.664 PASS
5.00 15.625 15.86 0.264 0.205 TO 0.286 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.000 25.000 0.00 PASS
B-N 25.000 25.000 0.00 PASS
C-N 25.000 25.000 0.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Building 61 17
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/12/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 8 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC10001780
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 1.520 1.500 1.33 PASS
B-N 1.535 1.500 2.33 PASS
C-N 1.550 1.500 3.33 PASS
Page 1 of 212-Sep-2019Print Date:
Building 61 18
Relay Results (continued) for: UR-F35.FST24322
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 224.32 3.739 3.746 -0.19 PASS
3.00 4.500 91.63 1.527 1.514 0.83 PASS
5.00 7.500 37.67 0.628 0.614 2.21 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 224.71 3.745 3.746 -0.02 PASS
3.00 4.500 91.33 1.522 1.514 0.51 PASS
5.00 7.500 37.96 0.633 0.614 2.98 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 224.03 3.734 3.746 -0.32 PASS
3.00 4.500 91.42 1.524 1.514 0.61 PASS
5.00 7.500 37.93 0.632 0.614 2.89 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 25.000 25.000 0.00 PASS
B-N 25.000 25.000 0.00 PASS
C-N 25.000 25.000 0.00 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Page 2 of 212-Sep-2019Print Date:
Building 61 19
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/11/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 9 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER:
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 1.565 1.500 4.33 PASS
B-N 1.535 1.500 2.33 PASS
C-N 1.520 1.500 1.33 PASS
Page 1 of 211-Sep-2019Print Date:
Building 61 20
Relay Results (continued) for: UR-F35.FST08930
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 229.58 3.826 3.746 2.15 PASS
3.00 4.500 92.81 1.547 1.514 2.13 PASS
5.00 7.500 38.20 0.637 0.614 3.64 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 229.09 3.818 3.746 1.93 PASS
3.00 4.500 93.11 1.552 1.514 2.46 PASS
5.00 7.500 38.00 0.633 0.614 3.09 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 228.39 3.806 3.746 1.62 PASS
3.00 4.500 92.46 1.541 1.514 1.75 PASS
5.00 7.500 38.21 0.637 0.614 3.68 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 22.730 22.500 1.02 PASS
B-N 22.505 22.500 0.02 PASS
C-N 22.730 22.500 1.02 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Page 2 of 211-Sep-2019Print Date:
Building 61 21
Lib Version:
Lib Routine: UR-F35.FST_LIB
09/11/2019Test Date:2.1
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 61 EQUIP_POSITION: FDR. No. 10 DEVICE_NUMBER:
MANUFACTURER: GE RELAY_TYPE: GE F-35
MODEL: F35N00VLHF8LH6NM8LPXXZONE_OF_PROTECTION:
Feeder
EQUIP_CLASS: SERIAL_NUMBER: AAIC09001529
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: PHASE TOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 1.535 1.500 2.33 PASS
B-N 1.520 1.500 1.33 PASS
C-N 1.505 1.500 0.33 PASS
Building 61 22
Relay Results (continued) for: UR-F35.FST23718
PHASE TOC 1 TIMING (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 227.87 3.798 3.746 1.39 PASS
3.00 4.500 92.57 1.543 1.514 1.87 PASS
5.00 7.500 38.02 0.634 0.614 3.14 PASS
PHASE TOC 1 TIMING (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 228.10 3.802 3.746 1.49 PASS
3.00 4.500 92.71 1.545 1.514 2.03 PASS
5.00 7.500 38.18 0.636 0.614 3.58 PASS
PHASE TOC 1 TIMING (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.000 228.26 3.804 3.746 1.56 PASS
3.00 4.500 92.38 1.540 1.514 1.66 PASS
5.00 7.500 38.34 0.639 0.614 4.02 PASS
PHASE TOC 1 TIMING
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
Relay Test Results for: PHASE IOC 1 PICKUP
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 22.730 22.500 1.02 PASS
B-N 22.505 22.500 0.02 PASS
C-N 22.730 22.500 1.02 PASS
Relay Test Results for: GROUND IOC 1 PICKUP
PICKUP CURRENT IDEAL %ERROR OK?
10.200 10.000 2.00 PASS
Building 61 23
52FA 2
52FB 4
52TA 6
52TB 9
52UA 12
52UB 15
GEN. 1 18
GEN. 2 22
GEN. 3 25
GEN. 4 30
GEN. 5 35
GEN. 6 39
Building 91 24
Lib Version:
Lib Routine: SEL-551.FST_LIB
09/12/2019Test Date:5.4
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: 52FA DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-551
MODEL: 0551003X531X ZONE_OF_PROTECTION: L
EQUIP_CLASS: SERIAL_NUMBER: 2009286475
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
FEEDER 52FA Date: 09/12/19 Time: 17:01:17.307
52FA -SWGR-A
FID=SEL-551-R513-Vf-Z002002-D20080104 CID=2A63
SELF TESTS
W=Warn F=Fail
IA IB IC IN MOF
OS 3 3 3 3 0
+5V_PS +5V_REG -5V_REG +10V_PS -10V_PS VBAT
PS 4.98 5.03 -4.96 9.95 -9.99 3.55
TEMP RAM ROM CR_RAM EEPROM
32.8 OK OK OK OK
Relay Enabled
Relay Test Results for: 50P1P PICKUP TEST (50P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 15.000 15.000 0.00 PASS
B-N 15.000 15.000 0.00 PASS
C-N 15.150 15.000 1.00 PASS
Page 1 of 212-Sep-2019Print Date:
Building 91 25
Relay Results (continued) for: SEL-551.FST00881
Relay Test Results for: 50G1P PICKUP TEST (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
0.614 0.600 2.33 PASS
Relay Test Results for: 51P1P PICKUP TEST (51P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 1.796 1.800 -0.22 PASS
B-N 1.814 1.800 0.78 PASS
C-N 1.814 1.800 0.78 PASS
Relay Test Results for: 51P1P TIMING TEST (51P1T)
51P1P TIMING TEST (51P1T) (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.600 261.68 4.361 4.332 0.69 PASS
3.00 5.400 100.94 1.682 1.674 0.50 PASS
4.00 7.200 56.60 0.943 0.930 1.47 PASS
51P1P TIMING TEST (51P1T) (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.600 261.40 4.357 4.332 0.58 PASS
3.00 5.400 100.38 1.673 1.674 -0.05 PASS
4.00 7.200 55.87 0.931 0.930 0.16 PASS
51P1P TIMING TEST (51P1T) (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.600 263.68 4.395 4.332 1.45 PASS
3.00 5.400 101.46 1.691 1.674 1.02 PASS
4.00 7.200 56.69 0.945 0.930 1.63 PASS
51P1P TIMING TEST (51P1T)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Page 2 of 212-Sep-2019Print Date:
Building 91 26
Lib Version:
Lib Routine: SEL-551.FST_LIB
09/11/2019Test Date:5.4
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/11/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: 52FB DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-551
MODEL: 0551003X531X ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER: 2009286476
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
FEEDER 52FB Date: 09/11/19 Time: 21:50:00.343
52FB -SWGR-B
FID=SEL-551-R513-Vf-Z002002-D20080104 CID=2A63
SELF TESTS
W=Warn F=Fail
IA IB IC IN MOF
OS 3 3 3 3 0
+5V_PS +5V_REG -5V_REG +10V_PS -10V_PS VBAT
PS 4.98 5.03 -5.11 9.97 -10.07 3.56
TEMP RAM ROM CR_RAM EEPROM
30.7 OK OK OK OK
Relay Enabled
Relay Test Results for: 50P1P PICKUP TEST (50P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 15.000 15.000 0.00 PASS
B-N 15.000 15.000 0.00 PASS
C-N 15.000 15.000 0.00 PASS
Building 91 27
Relay Results (continued) for: SEL-551.FST09690
Relay Test Results for: 50G1P PICKUP TEST (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
0.614 0.600 2.33 PASS
Relay Test Results for: 51P1P PICKUP TEST (51P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 1.796 1.800 -0.22 PASS
B-N 1.778 1.800 -1.22 PASS
C-N 1.796 1.800 -0.22 PASS
Relay Test Results for: 51P1P TIMING TEST (51P1T)
51P1P TIMING TEST (51P1T) (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.600 261.23 4.354 4.332 0.51 PASS
3.00 5.400 100.26 1.671 1.674 -0.17 PASS
4.00 7.200 56.22 0.937 0.930 0.79 PASS
51P1P TIMING TEST (51P1T) (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.600 259.70 4.328 4.332 -0.08 PASS
3.00 5.400 99.98 1.666 1.674 -0.45 PASS
4.00 7.200 56.18 0.936 0.930 0.71 PASS
51P1P TIMING TEST (51P1T) (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 3.600 259.12 4.319 4.332 -0.30 PASS
3.00 5.400 100.33 1.672 1.674 -0.10 PASS
4.00 7.200 56.00 0.933 0.930 0.39 PASS
51P1P TIMING TEST (51P1T)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Building 91 28
Lib Version:
Lib Routine: SEL-351A.FST_LIB
09/12/2019Test Date:5.11
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: 52TA DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-351A
MODEL: 0351A00323551XX ZONE_OF_PROTECTION: L
EQUIP_CLASS: SERIAL_NUMBER: 2009296158
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
TIE TA Date: 09/12/19 Time: 17:49:55.946
52TA
FID=SEL-351A-R402-V0-Z009007-D20071226 CID=C547
SELF TESTS
W=Warn F=Fail
IA IB IC IN VA VB VC VS MOF
OS -1 -1 -0 1 0 0 -2 -0 -0
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 5.00 4.95 -5.05 12.05 -11.96 15.05 -15.13
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
39.5 OK OK OK OK OK OK
Relay Enabled
Page 1 of 312-Sep-2019Print Date:
Building 91 29
Relay Results (continued) for: SEL-351A.FST09882
Relay Test Results for: METER TEST
APPLIED APPLIED CURRENT
SEC VOLT SEC AMP PH LAG
67.00 2.00 30.00
PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
PRI KV PRI KV PRI CUR PRI CUR
A-B 11.4 11.4 -0.0 432.0 431.3 -0.2 PASS
B-C 11.8 11.8 -0.0 480.0 478.7 -0.3 PASS
C-A 11.6 11.6 -0.1 528.0 526.4 -0.3 PASS
CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
MEGA WATT MEGA WATT MEGA VAR MEGA VAR
8.4 8.3 -0.4 4.8 4.8 -0.4 PASS
Relay Test Results for: 50G1P PICKUP (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
0.394 0.400 -1.50 PASS
Relay Test Results for: 51PP PH PICKUP (51P)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 2.270 2.250 0.89 PASS
B-N 2.270 2.250 0.89 PASS
C-N 2.270 2.250 0.89 PASS
Relay Test Results for: 51P PH TIMING (51PT)
51P PH TIMING (51PT) (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.500 753.52 12.559 12.514 0.36 PASS
3.00 6.750 291.42 4.857 4.836 0.44 PASS
5.00 11.250 106.24 1.771 1.764 0.35 PASS
51P PH TIMING (51PT) (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.500 755.66 12.594 12.514 0.64 PASS
3.00 6.750 292.06 4.868 4.836 0.66 PASS
5.00 11.250 106.16 1.769 1.764 0.28 PASS
51P PH TIMING (51PT) (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.500 755.19 12.586 12.514 0.58 PASS
3.00 6.750 291.29 4.855 4.836 0.40 PASS
5.00 11.250 106.56 1.776 1.764 0.66 PASS
51P PH TIMING (51PT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Relay Test Results for: 27PP UV PICKUP (27AB)
PICKUP VOLTS IDEAL %ERROR OK?
5.002 5.000 0.04 PASS
Relay Test Results for: 59PP OV PICKUP (59AB)
PICKUP VOLTS IDEAL %ERROR OK?
118.000 118.000 -0.00 PASS
Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)
PICKUP VOLTS IDEAL %ERROR OK?
107.060 106.000 1.00 PASS
Page 2 of 312-Sep-2019Print Date:
Building 91 30
Relay Results (continued) for: SEL-351A.FST09882
Relay Test Results for: 25VLO VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
119.690 118.500 1.00 PASS
Relay Test Results for: 25VHI VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
130.897 130.900 -0.00 PASS
Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)
LAGGING ANGLE IDEAL RANGE OK?
10.00 10.00 6.00 TO 14.00 PASS
LEADING ANGLE IDEAL RANGE OK?
351.00 350.00 346.00 TO 354.00 PASS
Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)
LAGGING ANGLE IDEAL RANGE OK?
15.00 15.00 11.00 TO 19.00 PASS
LEADING ANGLE IDEAL RANGE OK?
346.00 345.00 341.00 TO 349.00 PASS
Page 3 of 312-Sep-2019Print Date:
Building 91 31
Lib Version:
Lib Routine: SEL-351A.FST_LIB
09/12/2019Test Date:5.11
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: 52TB DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-351A
MODEL: 0351A00323551XX ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER: 2009293274
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
TIE TB Date: 09/11/19 Time: 22:47:36.750
52TB
FID=SEL-351A-R402-V0-Z009007-D20071226 CID=C547
SELF TESTS
W=Warn F=Fail
IA IB IC IN VA VB VC VS MOF
OS 2 1 -2 1 80W -1 35W 1 0
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 5.03 4.97 -5.02 12.13 -12.06 14.93 -15.01
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
37.4 OK OK OK OK OK OK
Relay Enabled
Building 91 32
Relay Results (continued) for: SEL-351A.FST07033
APPLIED APPLIED CURRENT
SEC VOLT SEC AMP PH LAG
67.00 2.00 30.00
PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
PRI KV PRI KV PRI CUR PRI CUR
A-B 11.4 11.4 -0.0 432.0 431.0 -0.2 PASS
B-C 11.8 11.8 0.0 480.0 479.4 -0.1 PASS
C-A 11.6 11.6 -0.0 528.0 526.6 -0.3 PASS
CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
MEGA WATT MEGA WATT MEGA VAR MEGA VAR
8.4 8.3 -0.3 4.8 4.8 -0.4 PASS
Relay Test Results for: 50G1P PICKUP (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
0.394 0.400 -1.50 PASS
Relay Test Results for: 51PP PH PICKUP (51P)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 2.270 2.250 0.89 PASS
B-N 2.270 2.250 0.89 PASS
C-N 2.270 2.250 0.89 PASS
Relay Test Results for: 51P PH TIMING (51PT)
51P PH TIMING (51PT) (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.500 754.18 12.570 12.514 0.45 PASS
3.00 6.750 291.71 4.862 4.836 0.54 PASS
5.00 11.250 106.54 1.776 1.764 0.64 PASS
51P PH TIMING (51PT) (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.500 753.72 12.562 12.514 0.39 PASS
3.00 6.750 291.73 4.862 4.836 0.55 PASS
5.00 11.250 106.21 1.770 1.764 0.33 PASS
51P PH TIMING (51PT) (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.500 755.50 12.592 12.514 0.62 PASS
3.00 6.750 291.53 4.859 4.836 0.48 PASS
5.00 11.250 106.39 1.773 1.764 0.50 PASS
51P PH TIMING (51PT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Relay Test Results for: 27PP UV PICKUP (27AB)
PICKUP VOLTS IDEAL %ERROR OK?
5.002 5.000 0.04 PASS
Relay Test Results for: 59PP OV PICKUP (59AB)
PICKUP VOLTS IDEAL %ERROR OK?
119.180 118.000 1.00 PASS
Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)
PICKUP VOLTS IDEAL %ERROR OK?
107.060 106.000 1.00 PASS
Building 91 33
Relay Results (continued) for: SEL-351A.FST07033
Relay Test Results for: 25VLO VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
119.690 118.500 1.00 PASS
Relay Test Results for: 25VHI VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
130.897 130.900 -0.00 PASS
Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)
LAGGING ANGLE IDEAL RANGE OK?
10.00 10.00 6.00 TO 14.00 PASS
LEADING ANGLE IDEAL RANGE OK?
351.00 350.00 346.00 TO 354.00 PASS
Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)
LAGGING ANGLE IDEAL RANGE OK?
15.00 15.00 11.00 TO 19.00 PASS
LEADING ANGLE IDEAL RANGE OK?
346.00 345.00 341.00 TO 349.00 PASS
Building 91 34
Lib Version:
Lib Routine: SEL-351.FST_LIB
09/12/2019Test Date:5.13
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: 52UA DEVICE_NUMBER:
MANUFACTURER: RELAY_TYPE: SEL-351
MODEL: ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER:
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
UA_UPR Date: 09/12/19 Time: 19:39:39.990
UTILITY A 52UA
FID=SEL-351-7-R402-V0-Z008006-D20080103 CID=19F9
SELF TESTS
W=Warn F=Fail
IA IB IC IN VA VB VC VS MOF
OS 0 0 1 1 -1 1 1 1 0
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 5.02 4.97 -5.04 12.05 -11.95 14.99 -15.04
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
38.3 OK OK OK OK OK OK
Relay Enabled
Building 91 35
Relay Results (continued) for: SEL-351.FST20134
APPLIED APPLIED CURRENT
SEC VOLT SEC AMP PH LAG
67.00 2.00 30.00
PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
PRI KV PRI KV PRI CUR PRI CUR
A-B 11.4 11.4 -0.0 432.0 431.4 -0.1 PASS
B-C 11.8 11.8 0.0 480.0 479.2 -0.2 PASS
C-A 11.6 11.6 0.1 528.0 526.7 -0.2 PASS
CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
MEGA WATT MEGA WATT MEGA VAR MEGA VAR
8.4 8.3 -0.3 4.8 4.8 -0.1 PASS
Relay Test Results for: 50P1P PICKUP (50P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 20.200 20.000 1.00 PASS
B-N 20.200 20.000 1.00 PASS
C-N 20.200 20.000 1.00 PASS
Relay Test Results for: 50G1P PICKUP (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
0.394 0.400 -1.50 PASS
Relay Test Results for: 51PP PH PICKUP (51P)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 2.118 2.100 0.86 PASS
B-N 2.118 2.100 0.86 PASS
C-N 2.118 2.100 0.86 PASS
Relay Test Results for: 51P PH TIMING (51PT)
51P PH TIMING (51PT) (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.200 463.66 7.728 7.701 0.35 PASS
3.00 6.300 179.71 2.995 2.976 0.65 PASS
4.00 8.400 100.31 1.672 1.653 1.16 PASS
51P PH TIMING (51PT) (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.200 465.09 7.752 7.701 0.66 PASS
3.00 6.300 180.46 3.008 2.976 1.07 PASS
4.00 8.400 100.21 1.670 1.653 1.05 PASS
51P PH TIMING (51PT) (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.200 464.75 7.746 7.701 0.58 PASS
3.00 6.300 179.75 2.996 2.976 0.68 PASS
4.00 8.400 100.49 1.675 1.653 1.34 PASS
51P PH TIMING (51PT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Relay Test Results for: 27PP UV PICKUP (27AB)
PICKUP VOLTS IDEAL %ERROR OK?
107.999 108.000 -0.00 PASS
Relay Test Results for: 81D1P FREQ PICKUP (81D1)
PICKUP HZ IDEAL RANGE OK?
59.100 59.100 59.050 TO 59.150 PASS
Building 91 36
Relay Results (continued) for: SEL-351.FST20134
Relay Test Results for: 81D1D FREQ TIME (81D1T)
APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?
58.900 2.079 122.47 120.00 TO 124.50 PASS
Relay Test Results for: 81D2P FREQ PICKUP (81D2)
PICKUP HZ IDEAL RANGE OK?
59.800 59.800 59.750 TO 59.850 PASS
Relay Test Results for: 81D2D FREQ TIME (81D2T)
APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?
59.600 5.0685 302.083 300.000 TO 304.500 PASS
Relay Test Results for: 81D3P FREQ PICKUP (81D3)
PICKUP HZ IDEAL RANGE OK?
60.100 60.100 60.050 TO 60.150 PASS
Relay Test Results for: 81D3D FREQ TIME (81D3T)
APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?
60.300 2.024 122.05 120.00 TO 124.50 PASS
Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)
PICKUP VOLTS IDEAL %ERROR OK?
111.100 110.000 1.00 PASS
Relay Test Results for: 25VLO VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
118.505 118.500 0.00 PASS
Relay Test Results for: 25VHI VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
130.897 130.900 -0.00 PASS
Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)
LAGGING ANGLE IDEAL RANGE OK?
10.00 10.00 6.00 TO 14.00 PASS
LEADING ANGLE IDEAL RANGE OK?
351.00 350.00 346.00 TO 354.00 PASS
Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)
LAGGING ANGLE IDEAL RANGE OK?
15.00 15.00 11.00 TO 19.00 PASS
LEADING ANGLE IDEAL RANGE OK?
346.00 345.00 341.00 TO 349.00 PASS
Building 91 37
Lib Version:
Lib Routine: SEL-351.FST_LIB
09/12/2019Test Date:5.13
Relay Data:
TESTED_BY: Bill Liss DATE_: 9/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: 52UB DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-351
MODEL: 03517033551XXX ZONE_OF_PROTECTION: L
EQUIP_CLASS: SERIAL_NUMBER: 2009303171
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
UB_UPR Date: 09/11/19 Time: 23:33:56.574
UTILITY A 52UB
FID=SEL-351-7-R402-V0-Z008006-D20080103 CID=19F9
SELF TESTS
W=Warn F=Fail
IA IB IC IN VA VB VC VS MOF
OS -1 -1 -1 -1 -0 -1 -0 -1 -1
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 4.99 5.01 -4.97 11.86 -12.03 15.01 -15.03
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
32.5 OK OK OK OK OK OK
Relay Enabled
Building 91 38
Relay Results (continued) for: SEL-351.FST24882
APPLIED APPLIED CURRENT
SEC VOLT SEC AMP PH LAG
67.00 2.00 30.00
PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
PRI KV PRI KV PRI CUR PRI CUR
A-B 11.4 11.4 -0.1 432.0 431.3 -0.2 PASS
B-C 11.8 11.8 0.1 480.0 479.4 -0.1 PASS
C-A 11.6 11.6 0.0 528.0 526.6 -0.3 PASS
CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
MEGA WATT MEGA WATT MEGA VAR MEGA VAR
8.4 8.4 -0.3 4.8 4.8 -0.4 PASS
Relay Test Results for: 50P1P PICKUP (50P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 20.200 20.000 1.00 PASS
B-N 20.000 20.000 -0.00 PASS
C-N 20.200 20.000 1.00 PASS
Relay Test Results for: 50G1P PICKUP (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
0.394 0.400 -1.50 PASS
Relay Test Results for: 51PP PH PICKUP (51P)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
A-N 2.118 2.100 0.86 PASS
B-N 2.118 2.100 0.86 PASS
C-N 2.118 2.100 0.86 PASS
Relay Test Results for: 51P PH TIMING (51PT)
51P PH TIMING (51PT) (PHASE A-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.200 464.38 7.740 7.701 0.51 PASS
3.00 6.300 180.12 3.002 2.976 0.88 PASS
4.00 8.400 99.97 1.666 1.653 0.81 PASS
51P PH TIMING (51PT) (PHASE B-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.200 464.17 7.736 7.701 0.46 PASS
3.00 6.300 180.23 3.004 2.976 0.94 PASS
4.00 8.400 100.09 1.668 1.653 0.93 PASS
51P PH TIMING (51PT) (PHASE C-N)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.200 465.59 7.760 7.701 0.77 PASS
3.00 6.300 179.86 2.998 2.976 0.73 PASS
4.00 8.400 100.24 1.671 1.653 1.08 PASS
51P PH TIMING (51PT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.2
0.5
1.0
2.0
5.0
10.0
20.0
Relay Test Results for: 27PP UV PICKUP (27AB)
PICKUP VOLTS IDEAL %ERROR OK?
107.999 108.000 -0.00 PASS
Relay Test Results for: 81D1P FREQ PICKUP (81D1)
PICKUP HZ IDEAL RANGE OK?
59.100 59.100 59.050 TO 59.150 PASS
Building 91 39
Relay Results (continued) for: SEL-351.FST24882
Relay Test Results for: 81D1D FREQ TIME (81D1T)
APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?
58.900 2.078 122.38 120.00 TO 124.50 PASS
Relay Test Results for: 81D2P FREQ PICKUP (81D2)
PICKUP HZ IDEAL RANGE OK?
59.800 59.800 59.750 TO 59.850 PASS
Relay Test Results for: 81D2D FREQ TIME (81D2T)
APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?
59.600 5.0641 301.820 300.000 TO 304.500 PASS
Relay Test Results for: 81D3P FREQ PICKUP (81D3)
PICKUP HZ IDEAL RANGE OK?
60.100 60.100 60.050 TO 60.150 PASS
Relay Test Results for: 81D3D FREQ TIME (81D3T)
APPLIED VALUE TIME(SEC) TIME(CY) RANGE OK?
60.300 2.018 121.67 120.00 TO 124.50 PASS
Relay Test Results for: 59S1P OV1 VS PICKUP (59S1)
PICKUP VOLTS IDEAL %ERROR OK?
111.100 110.000 1.00 PASS
Relay Test Results for: 25VLO VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
118.505 118.500 0.00 PASS
Relay Test Results for: 25VHI VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
130.897 130.900 -0.00 PASS
Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)
LAGGING ANGLE IDEAL RANGE OK?
10.00 10.00 6.00 TO 14.00 PASS
LEADING ANGLE IDEAL RANGE OK?
351.00 350.00 346.00 TO 354.00 PASS
Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)
LAGGING ANGLE IDEAL RANGE OK?
15.00 15.00 11.00 TO 19.00 PASS
LEADING ANGLE IDEAL RANGE OK?
346.00 345.00 341.00 TO 349.00 PASS
Building 91 40
Lib Version:
Lib Routine: SEL-300G.FST_LIB
11/12/2019Test Date:5.9
Relay Data:
TESTED_BY: Bill Liss DATE_: 11/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: GEN. 1 DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-300G
MODEL: 0300G303325XX12XX ZONE_OF_PROTECTION: G
EQUIP_CLASS: SERIAL_NUMBER: 2009288184
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
GENERATOR 1 Date: 11/12/19 Time: 09:24:59.056
G1_GPR
FID=SEL-300G-R326-V203325XX12XX-Z302302-D20081231 CID=0340
SELF TESTS
W=Warn F=Fail
IA IB IC IN VA VB VC VN MOF
OS -1 -2 -1 -1 -1 -0 -2 0 -0
VS
OS 1
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 5.01 4.99 -4.99 12.00 -12.00 15.07 -15.08
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
37.0 OK OK OK OK OK OK
Relay Enabled
Page 1 of 412-Nov-2019Print Date:
Building 91 41
Relay Results (continued) for: SEL-300G.FST10926
APPLIED APPLIED CURRENT
SEC VOLT SEC AMP PH LAG
72.00 2.00 30.00
PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
PRI KV PRI KV PRI CUR PRI CUR
A-B 12.1 12.3 1.5 72.0 71.8 -0.3 PASS
B-C 12.5 12.6 1.4 80.0 79.8 -0.2 PASS
C-A 12.8 12.5 -2.7 88.0 87.8 -0.3 PASS
CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
MEGA WATT MEGA WATT MEGA VAR MEGA VAR
1.5 1.5 -0.1 0.9 0.9 -0.9 PASS
Relay Test Results for: 32P1P PWR PICKUP (32P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
3PH 0.146 0.145 0.66 PASS
Relay Test Results for: 32P1D PWR DELAY (32P1T)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
1.20 0.174 1202.18 20.036 19.000 TO 21.000 PASS
Relay Test Results for: 32P2P PWR PICKUP (32P2)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
3PH 0.322 0.319 0.91 PASS
Relay Test Results for: 32P2D PWR DELAY (32P2T)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
1.20 0.383 302.18 5.036 4.725 TO 5.275 PASS
Relay Test Results for: 50G1P OC PICKUP (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
2.505 2.500 0.20 PASS
Relay Test Results for: 50G1D OC DELAY (50G1T)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
1.20 3.000 55.25 0.921 0.830 TO 0.970 PASS
Relay Test Results for: 51GP OC PICKUP (51G)
PICKUP CURRENT IDEAL %ERROR OK?
2.505 2.500 0.20 PASS
Relay Test Results for: 51G OC TIMING (51GT)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 5.000 116.48 1.941 1.925 0.84 PASS
3.00 7.500 45.43 0.757 0.744 1.78 PASS
4.00 10.000 25.67 0.428 0.413 3.53 PASS
51G OC TIMING (51GT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: 51VP (100%) PICKUP (51V)
PICKUP CURRENT IDEAL %ERROR OK?
3.334 3.300 1.03 PASS
Relay Test Results for: 51VP (75%) PICKUP (51V)
PICKUP CURRENT IDEAL %ERROR OK?
2.498 2.475 0.93 PASS
Page 2 of 412-Nov-2019Print Date:
Building 91 42
Relay Test Results for: 51V (100%) TIMING (51VT)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 6.600 116.58 1.943 1.925 0.92 PASS
3.00 9.900 45.07 0.751 0.744 0.96 PASS
4.00 13.200 25.58 0.426 0.413 3.17 PASS
51V (100%) TIMING (51VT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: 51V (75%) TIMING (51VT)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.950 116.71 1.945 1.925 1.04 PASS
4.00 9.900 25.10 0.418 0.413 1.23 PASS
6.00 14.850 12.16 0.203 0.197 2.74 PASS
51V (75%) TIMING (51VT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: 81D1P FREQ PICKUP (81D1)
PICKUP HZ IDEAL RANGE OK?
57.500 57.500 57.450 TO 57.550 PASS
Relay Test Results for: 81D1D FREQ DELAY (81D1T)
APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?
57.300 289.72 5.056 5.000 TO 5.150 PASS
Relay Test Results for: 81D2P FREQ PICKUP (81D2)
PICKUP HZ IDEAL RANGE OK?
57.000 57.000 56.950 TO 57.050 PASS
Relay Test Results for: 81D2D FREQ DELAY (81D2T)
APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?
56.800 176.82 3.113 3.000 TO 3.150 PASS
Relay Test Results for: 27VSP UV VS PICKUP (27VS)
PICKUP VOLTS IDEAL %ERROR OK?
5.000 5.000 0.00 PASS
Relay Test Results for: 25VLO VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
113.120 112.000 1.00 PASS
Relay Test Results for: 25VHI VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
134.640 136.000 -1.00 PASS
Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)
LAGGING ANGLE IDEAL RANGE OK?
10.00 10.00 6.00 TO 14.00 PASS
LEADING ANGLE IDEAL RANGE OK?
351.00 350.00 346.00 TO 354.00 PASS
Page 3 of 412-Nov-2019Print Date:
Building 91 43
Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)
LAGGING ANGLE IDEAL RANGE OK?
15.00 15.00 11.00 TO 19.00 PASS
LEADING ANGLE IDEAL RANGE OK?
345.00 345.00 341.00 TO 349.00 PASS
Page 4 of 412-Nov-2019Print Date:
Building 91 44
Lib Version:
Lib Routine: SEL-300G.FST_LIB
11/12/2019Test Date:5.9
Relay Data:
TESTED_BY: Bill Liss DATE_: 11/12/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: GEN. 2 DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-300G
MODEL: ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER: 2009288183
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine Notes:
Relay Settings Used for Testing:
[Suppressed]
Relay Test Results for: RELAY STATUS CHECK
N/A
Additional Data:
STA
GENERATOR 2 Date: 11/12/19 Time: 12:37:57.303
G2_GPR
FID=SEL-300G-R326-V203325XX12XX-Z302302-D20081231 CID=0340
SELF TESTS
W=Warn F=Fail
IA IB IC IN VA VB VC VN MOF
OS -1 -2 -0 0 -0 1 -1 -1 0
VS
OS 2
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 5.02 4.95 -4.98 11.94 -11.99 15.02 -14.99
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
34.4 OK OK OK OK OK OK
Relay Enabled
Page 1 of 312-Nov-2019Print Date:
Building 91 45
Relay Results (continued) for: SEL-300G.FST15455
APPLIED APPLIED CURRENT
SEC VOLT SEC AMP PH LAG
72.00 2.00 30.00
PHASE CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
PRI KV PRI KV PRI CUR PRI CUR
A-B 12.1 12.3 1.5 72.0 71.8 -0.2 PASS
B-C 12.5 12.6 1.4 80.0 79.8 -0.2 PASS
C-A 12.8 12.5 -2.8 88.0 87.8 -0.3 PASS
CALCULATED MEASURED % ERROR CALCULATED MEASURED % ERROR OK?
MEGA WATT MEGA WATT MEGA VAR MEGA VAR
1.5 1.5 -0.2 0.9 0.9 -0.5 PASS
Relay Test Results for: 32P1P PWR PICKUP (32P1)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
3PH 0.147 0.145 1.66 PASS
Relay Test Results for: 32P1D PWR DELAY (32P1T)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
1.20 0.174 1202.18 20.036 19.000 TO 21.000 PASS
Relay Test Results for: 32P2P PWR PICKUP (32P2)
PHASE PICKUP CURRENT IDEAL %ERROR OK?
3PH 0.322 0.319 0.91 PASS
Relay Test Results for: 32P2D PWR DELAY (32P2T)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
1.20 0.383 302.09 5.035 4.725 TO 5.275 PASS
Relay Test Results for: 50G1P OC PICKUP (50G1)
PICKUP CURRENT IDEAL %ERROR OK?
2.505 2.500 0.20 PASS
Relay Test Results for: 50G1D OC DELAY (50G1T)
MULTIPLE VALUE TIME(CY) TIME(SEC) RANGE OK?
1.20 3.000 55.43 0.924 0.830 TO 0.970 PASS
Relay Test Results for: 51VP (100%) PICKUP (51V)
PICKUP CURRENT IDEAL %ERROR OK?
3.301 3.300 0.03 PASS
Relay Test Results for: 51VP (75%) PICKUP (51V)
PICKUP CURRENT IDEAL %ERROR OK?
2.498 2.475 0.93 PASS
Relay Test Results for: 51V (100%) TIMING (51VT)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 6.600 117.22 1.954 1.925 1.48 PASS
3.00 9.900 45.27 0.754 0.744 1.42 PASS
4.00 13.200 24.97 0.416 0.413 0.73 PASS
51V (100%) TIMING (51VT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Page 2 of 312-Nov-2019Print Date:
Building 91 46
Relay Results (continued) for: SEL-300G.FST15455
Relay Test Results for: 51V (75%) TIMING (51VT)
MULTIPLE VALUE TIME(CY) TIME(SEC) IDEAL %ERROR OK?
2.00 4.950 116.94 1.949 1.925 1.24 PASS
4.00 9.900 25.41 0.424 0.413 2.49 PASS
6.00 14.850 11.98 0.200 0.197 1.22 PASS
51V (75%) TIMING (51VT)
MULTIPLE OF TAP
1.5 2 2.5 4 6 8 10 20
T
IM
E
IN
S E
C O
N D
S
0.02
0.05
0.10
0.20
0.50
1.00
2.00
5.00
10.00
Relay Test Results for: 81D1P FREQ PICKUP (81D1)
PICKUP HZ IDEAL RANGE OK?
57.490 57.500 57.450 TO 57.550 PASS
Relay Test Results for: 81D1D FREQ DELAY (81D1T)
APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?
57.300 293.03 5.114 5.000 TO 5.150 PASS
Relay Test Results for: 81D2P FREQ PICKUP (81D2)
PICKUP HZ IDEAL RANGE OK?
56.990 57.000 56.950 TO 57.050 PASS
Relay Test Results for: 81D2D FREQ DELAY (81D2T)
APPLIED VALUE TIME(CY) TIME(SEC) RANGE OK?
56.800 176.77 3.112 3.000 TO 3.150 PASS
Relay Test Results for: 27VSP UV VS PICKUP (27VS)
PICKUP VOLTS IDEAL %ERROR OK?
5.000 5.000 0.00 PASS
Relay Test Results for: 25VLO VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
113.120 112.000 1.00 PASS
Relay Test Results for: 25VHI VS THRESHOLD (59VS)
PICKUP VOLTS IDEAL %ERROR OK?
134.640 136.000 -1.00 PASS
Relay Test Results for: 25ANG1 SYNC ANGLE (25A1)
LAGGING ANGLE IDEAL RANGE OK?
10.00 10.00 6.00 TO 14.00 PASS
LEADING ANGLE IDEAL RANGE OK?
349.00 350.00 346.00 TO 354.00 PASS
Relay Test Results for: 25ANG2 SYNC ANGLE (25A2)
LAGGING ANGLE IDEAL RANGE OK?
15.00 15.00 11.00 TO 19.00 PASS
LEADING ANGLE IDEAL RANGE OK?
346.00 345.00 341.00 TO 349.00 PASS
Page 3 of 312-Nov-2019Print Date:
Building 91 47
Lib Version:
Lib Routine: SEL-300G.FST_LIB
11/13/2019Test Date:5.9
Relay Data:
TESTED_BY: Bill Liss DATE_: 11/13/2019 ELECTRIC_SUBSTATION: VA hospital Biloxi LOCATION: Bldg 91
EQUIP_POSITION: GEN. 3 DEVICE_NUMBER:
MANUFACTURER: Schweitzer RELAY_TYPE: SEL-300G
MODEL: 0300G303325XX12XX ZONE_OF_PROTECTION:
EQUIP_CLASS: SERIAL_NUMBER: 2009295106
FIRMWARE_ID: EQUIP_NUMBER:
NERC_PRC_002: NERC_PRC_005:
UFLS: PREVIOUS_TESTDATE:
CURRENT_TESTDATE: NEXT_TESTDATE:
TESTSET_CALDATE: 5/9/2019 APPROVED_BY:
LOCATION_POSITION:
Global Defines:
[Suppressed]
Routine