R_SYS_2026_VA Charleston_6.pdf
PDF 4 MB Posted
- Attached to
- J065--FY26: REPAIR MEDICAL GAS LEAK
- Solicitation number
- 36C24726Q0868
About this file
This is a medical gas systems inspection report for Ralph H. Johnson VA Medical Center in Charleston, South Carolina, conducted June 2-4, 2026, by Technical Safety Services. The facility operates a comprehensive medical gas system serving multiple areas including patient care units, operating rooms, intensive care units, and diagnostic areas. The inspection tested systems to NFPA 99 standards across 47 master alarm signals, 88 area alarm signals, 115 valves, 1,216 outlets and inlets, 16 contaminant test sites, and 7 source systems, achieving 99.0% overall system health compliance.
The report identifies 15 total deficiencies across multiple components. Nine outlets and inlets in rooms 3A 301-306 require patient terminal removal, locking devices, or zone valve installation to control access. Six valves present deficiencies: three zone valves in rooms A301-A303, A305, A306 require installation or terminal control, and three service valves at ED Main Nurses Station are blocked by wall-mounted medical equipment. Additionally, three area alarms and three zone valves at the Radiology Front Desk required labeling corrections for new holding bays. Corrective actions completed during testing included repairs to 19 leaking inner checks across multiple patient care areas, removal of damaged secondary equipment and faceplate repairs at ICU 2, and system labeling updates. Source equipment, master alarm signals, gas contaminant testing, and all other inspected components passed compliance standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24726Q0868_4.docx | DOCX document | |
| 36C24726Q0868_3.pdf | ||
| R_PM_2026_VA Charleston_5.pdf | ||
| PXL_20260526_124550763_1.jpg | JPG image | |
| R_Boom Hose Inspections_2026_VA Charleston_4.pdf | ||
| PXL_20260526_124939323_3.jpg | JPG image | |
| PXL_20260526_124554514_2.jpg | JPG image | |
| 36C24726Q0868_2.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project ID(s): 2026 Medical Gas Inspection
Project Date(s): 6/2-4/2026
8047 Castleton Road
Indianapolis, IN 46250
109 Bee St
12454599
123456789
11225
Tanner Moore ASSE Credential #:
ASSE Credential #:
ASSE Credential #:
ASSE Credential #:
Charleston, SC
Project Contact:
David Gatlin
Engineering
(803)621-6104
Project Site:
123546
Ralph H. Johnson VA Medical Center
Technician 5: ASSE Credential #:
Report Authored By:
Technician 2:
Technician 3:
Technician 4:
Technical Safety Services
1-(800)-727-8321 www.Techsafety.com
MEDICAL GAS SYSTEMS MAINTENANCE INSPECTION
Project ID(s): 2026 Medical Gas Inspection
Project Date(s): 6/2-4/2026
Tested to NFPA 99:
Report Section: COVERSHEET
Page: 1 of 90
Filename: R_SYS_2026_VA Charleston
Report Version: 3.7,5K
TESTING & INSPECTION PROCEDURES
TSS has designed its testing & inspection scope and procedure around applicable NFPA 99 codes and pertinent inspection and accreditation requirements, and manufacturer recommendations following industry best practices. However, your facility's risk assessment committee has the ultimate responsibility in deciding the scope and frequency of scheduled inspections for medical gas components and the associated procedures. These inspections are to be developed with consideration of the original equipment manufacturer recommendations and other recommendations as required by the authority having jurisdiction.
The testing & inspection procedures represented in this report are as follows unless otherwise directed and document by the facility's risk assessment team:
MASTER ALARMS :
Master alarm panel location is recorded along with manufacturer and model of alarm and location of initiating device. Master alarm panels are tested for proper audible and visual alarm activation & deactivation, each signal is inspected for proper labeling and wiring is inspected for independence to initiating device.
All master alarm signals* are tested by simulating each alarm condition and/or actuating the signal at the initiating device wherever possible.
If it is not possible to simulate an alarm condition or actuate the signal by changing system conditions then the alarm's wiring will be tested for continuity from the initiating to the master alarm panels.
* Cryogenic liquid central supply system master alarm signals that terminate within the supplier-owned equipment are not tested per the TSS maintenance inspection
SOP as such signals are required to be tested by the supplier/equipment owner annually and TSS views this testing as sufficient in satisfying the NFPA 99 inspection requirement. TSS can test these signals per request, however the facility will have to direct the method used to perform this testing.
Per NFPA 99, the maintenance, inspection and testing operations of medical gas systems apply to all facilities—new and existing—with Category 1-3 Medical Gas, Vacuum, WAGD, and Medical Support Gas systems.
MEDICAL GAS SYSTEMS MAINTENANCE INSPECTION
PURPOSE
The inspection and testing documented in this report is designed around satisfying the medical gas systems maintenance program requirements laid out in NFPA 99 section 5.1.14. The purpose driving these maintenance program requirements is to ensure that medical gas system components are compliant with applicable NFPA 99 codes and standards, remain in good repair, and are operating within manufacturer specifications or recommendations.
SCOPE AND APPLICATION
Report Section: SCOPE & PROCEDURES
Page: 2 of 90
MEDICAL GAS SYSTEMS MAINTENANCE INSPECTION
AREA ALARMS :
Area alarm panel location and area monitored is recorded along with manufacturer and model of alarm. Area alarm panels are tested for proper audible and visual alarm activation and deactivation through use of the alarm "test" function. Condition of area alarm and components are inspected.
System gas, high & low alarm setpoints are recorded and pressure reading is recorded and tested for accuracy.
Area monitored labeling and transducer location can only be verified by tracing piping and/or altering zone pressure. Actual alarm function under alarm conditions
(high or low pressure) can only be verified by altering zone pressure. These tests can be performed by request but are not included in TSS's maintenance inspection
SOP.
VALVES :
Valve location and labeling (including area(s) served, system gas and other required verbiage), manufacturer, valve type and pressure reading are inspected and recorded. Gauge pressure is recorded and tested for accuracy. Condition of valve assembly and enclosure are inspected and valves are checked for leaks.
Area served labeling can only be verified by tracing piping and/or altering zone pressure. This test can be performed by request but is not included in TSS's maintenance inspection SOP.
OUTLETS & INLETS :
Outlet or inlet location, manufacturer, model, position and labeling is inspected and recorded. Outlets/inlets are tested for proper connect & release, leaks and general condition.
One outlet/inlet per zone is tested for static pressure and compared with zone valve gauge reading and/or area alarm pressure reading.
All outlets/inlets are tested for dynamic pressure/operational flow pressure drop.
All positive pressure medical gases are tested for oxygen concentration as a way of determining if existing cross-connections between two medical gases exist.
Report Section: SCOPE & PROCEDURES
Page: 3 of 90
MEDICAL GAS SYSTEMS MAINTENANCE INSPECTION
1)
2)
3)
TSS service technicians are qualified to perform medical gas systems inspections and maintenance to one or more of the following qualification requirements per NFPA
99 5.1.14:
Documented training by which such persons are qualified to work with specific equipment as installed in that facility.
Credentialing to the requirements of ASSE 6040, Professional Qualification Standard for Medical Gas Maintenance Personnel.
Credentialing to the requirements of ASSE 6030, Professional Qualification Standard for Medical Gas Systems Verifiers.
QUALIFICATIONS
SOURCE EQUIPMENT :
All source systems' manufacturer, model number and specifications are recorded. Proper functioning of each system is observed and recorded. Each source type is inspected based on the associated inspection checklist visible on the page(s) of this report specific to that source system.
GAS CONTAMINANTS :
Particulate Contaminants - A representative sampling of each gas system pipeline is tested for particulate contaminants using a 0.45 micron filter membrane connected to an outlet of each gas. Results of this test are then recorded.
Dew Point - A representative sampling of medical air and instrument air pipeline is tested for dew point using a portable dew point monitor connected to an outlet of each gas. Results of this test are then recorded.
Odor - All positive pressure outlets are tested for objectionable or pronounced odor and the results are then recorded.
Gaseous Contaminants - Testing each gas system pipeline and source for total nonmethane hydrocarbons and halogenated hydrocarbons can be performed by request but is not included in EMS's maintenance inspection SOP.
Report Section: SCOPE & PROCEDURES
Page: 4 of 90
TABLE OF CONTENTS
■ Summary of Findings
■ Master Alarms
■ Area Alarms
■ Valves
■ Outlets & Inlets
■ Contaminants
■ Source Equipment
■ Annex
Technical Safety Services has evaluated the medical piping systems indicated in this report in accordance with applicable NFPA 99 Health Care Facilities Code and ASSE 6000 Standards. These systems have been found to be within applicable guidelines except as noted within this report. Any deficiencies cited are based on the most applicable edition of NFPA 99. See coversheet for relevent NFPA 99 edition.
Per NFPA 99 an existing system that is not in strict compliance with the applicable codes may continue to be used as long as it is not a distinct hazard to safety. Fire/explosion hazards, labeling, manifold enclosures, medical air usage, & maintenance codes apply to new & existing facilities.
The information recorded in this report represents the state of the medical gas systems for the indicated inspection date(s) only. Any action taken in response to recommendations included in this report should be recorded on the appropriate pages. This report should not be copied unless in its entirety.
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Master Alarm
Signals (47)
Area Alarm Signals (88)
Valves (115) Outlets & Inlets (1216)
Contaminant Test Sites
(16)
Source Systems (7)
Deficient 0 0 6 9 0 0
Compliant 47 88 109 1207 16 7
47 88 109 1207 16 7
6 9
MEDICAL GAS SYSTEMS HEALTH BY COMPONENT
99.0%
OVERALL MEDICAL
GAS SYSTEMS HEALTH
Report Section: SYSTEMS OVERVIEW
Page: 5 of 90
MASTER ALARMS
No deficiencies at time of test
No corrective action reported
AREA ALARMS
No deficiencies at time of test
CORRECTIVE ACTION DETAIL - AREA ALARMS ALARM PANEL LOCATION(S) QTY
Area monitored labeling missing/incorrect: Added new holding bays (1 &
2) opp. D205C to label.
Radiology Front Desk 3
VALVES
DEFICIENCY DETAIL - VALVES VALVE LOCATION(S) QTY
Remove patient terminal, install locking device or locate/install Zone Valve to control rooms A301-A303, A305, A306.
0 1
Service valves shall be placed in the branch piping prior to any zone valve box assembly on that branch. Wall mounted medical equipment blocks removal of Zone(Service) Valve box hard cover
ED Main Nurses Station 3
System depressurized. Remove patient terminal, install locking device or locate/install Zone Valve to control rooms A301-A303, A305, A306.
0 2
CORRECTIVE ACTION DETAIL - VALVES VALVE LOCATION(S) QTY
Labeling inaccurate - rooms/area served: Added new holding bays (1 & 2) opp. D205C to label.
O/S D205 3
SUMMARY OF DEFICIENCIES
Individual deficiencies and corrective action notes can be found in the component sections ( 'Master Alarms', 'Area Alarms', 'Valves', 'Outlets & Inlets', 'Contaminants', 'Sources & Pipeline' ). This summary provides an overview of deficiency or corrective action type, location and quantity. For discussion regarding what constitutes a deficiency, please note the "Scope & Procedures" section of this report. For findings that have not been marked as deficient but instead TSS has provided a recommendation, please note the "Annex" section of this report.
Report Section: SUMMARY OF FINDINGS
Page: 6 of 90
SUMMARY OF DEFICIENCIES
Individual deficiencies and corrective action notes can be found in the component sections ( 'Master Alarms', 'Area Alarms', 'Valves', 'Outlets & Inlets', 'Contaminants', 'Sources & Pipeline' ). This summary provides an overview of deficiency or corrective action type, location and quantity. For discussion regarding what constitutes a deficiency, please note the "Scope & Procedures" section of this report. For findings that have not been marked as deficient but instead TSS has provided a recommendation, please note the "Annex" section of this report.
OUTLET & INLETS
DEFICIENCY DETAIL - OUTLETS & INLETS OUTLET/INLET LOCATION(S) / ASSET # QTY
Remove patient terminal, install locking device and label "Not in Use" or locate/install Zone Valve to control patient terminal.
3A 301, 3A 302, 3A 303, 3A 305, 3A 306 9
CORRECTIVE ACTION DETAIL - OUTLETS & INLETS OUTLET/INLET LOCATION(S) / ASSET # QTY
Damaged adapter connection - Removed damaged secondary equipment at time of testing
2nd Fl ICU A214 (ICU 2) 1
Damaged faceplate - Repaired at time of testing 2nd Fl ICU A214 (ICU 2) 1
Leaking inner check - Repaired at time of testing 4A 421, 4B South 415, 4B North 437, 3B South 358, 3B GI
Suite (Endoscopy) 322 (GI Proc. 2), Surgery A239 (OR 1), Surgery A238 (OR 2), Surgery A234 (OR 3), Surgery A235
(OR 4), Surgery A236A (OR 5), Surgery C205 (OR 6), ED 5, ED 12
GAS CONTAMINANTS
No deficiencies at time of test
No corrective action reported
SOURCE EQUIPMENT
No deficiencies at time of testing
No corrective action reported
Report Section: SUMMARY OF FINDINGS
Page: 7 of 90
MASTER ALARM SIGNALS
BY SYSTEM GAS:
12 16 6 6 0 7 0 0 0
47TOTAL MASTER
ALARM SIGNALS
TOTAL MASTER ALARM PANELS:
MANUFACTURER MODEL MASTER ALARM PANEL DESCRIPTION
O
M A
N
O
N
C O
V A
C
W A
G D
IA
O th e r
Amico A2M Gray Cover with Red LED Indicators 6 8 3 3 4
Beacon Mega Digital Module 6 8 3 3 3
47TOTAL MASTER
ALARM SIGNALS
MASTER ALARMS BREAKDOWN (*EACH MASTER ALARM SIGNAL COUNTED AS SEPARATE ALARM BY SYSTEM GAS BELOW)
Report Section: MASTER ALARM INVENTORY
Page: 8 of 90
Master Alarm Panel
Location/#* *If multiple panels per location
(e.g. "Engineering Panel 1")
System MFR Model Condition
Monitored
Switch or
Source
Location S e t
P o in t
U n it o f
M e a s u re Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
1 Facilities O2 Beacon Mega Liquid Level Low O2 Bulk
Enclosure
60 PSI PASS
2 Facilities O2 Beacon Mega Reserve in Use O2 Bulk
Enclosure
100 PSI PASS
3 Facilities O2 Beacon Mega Reserve Liquid
Level Low
O2 Bulk
Enclosure
60 PSI PASS
4 Facilities O2 Beacon Mega Reserve
Pressure Low
O2 Bulk
Enclosure
50 PSI PASS
5 Facilities O2 Beacon Mega High Line
Pressure Hospital 60 PSI PASS
6 Facilities O2 Beacon Mega Low Line
Pressure Hospital 40 PSI PASS
7 Facilities N2O Beacon Mega Reserve in Use Manifold Room 100 PSI PASS
8 Facilities N2O Beacon Mega High Line
Pressure Manifold Room 60 PSI PASS
9 Facilities N2O Beacon Mega Low Line
Pressure Manifold Room 40 PSI PASS
10 Facilities MA Beacon Mega (1-2) High Dew
Point
Mechanical
Room
32 PSI PASS
11 Facilities MA Beacon Mega (1-2) High CO Mechanical
Room
10 PPM PASS
12 Facilities MA Beacon Mega
(1-2) Lag
Compressor in
Use
Mechanical
Room
65 PSI PASS
13 Facilities MA Beacon Mega High Line
Pressure Hospital 60 PSI PASS
14 Facilities MA Beacon Mega Low Line
Pressure Hospital 40 PSI PASS
15 Facilities VAC Beacon Mega (1-2) Lag Pump in Use
Mechanical
Room 18 inHg PASS
16 Facilities MA Beacon Mega (3-4) High Dew
Point
Mechanical
Room
32 PSI PASS
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
Report Section: MASTER ALARMS
Page: 9 of 90
Master Alarm Panel
Location/#* *If multiple panels per location
(e.g. "Engineering Panel 1")
System MFR Model Condition
Monitored
Switch or
Source
Location S e t
P o in t
U n it o f
M e a s u re Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
17 Facilities MA Beacon Mega
(116)
Maintenance
Required
Mechanical
Room
PASS
18 Facilities MA Beacon Mega
(116) High Dew
Point
Mechanical
Room
32 PSI PASS
19 Facilities N2 Beacon Mega Low Line
Pressure
2nd Fl Manifold
Rm
140 PSI PASS
20 Facilities N2 Beacon Mega High Line
Pressure
2nd Fl Manifold
Rm
200 PSI PASS
21 Facilities N2 Beacon Mega Reserve in Use 2nd Fl Manifold
Rm
250 PSI PASS
22 Facilities VAC Beacon Mega (New) Lag
Pump in Use
Mechanical
Room 18 inHg PASS
23 Facilities VAC Beacon Mega Low Line
Pressure Hospital 12 inHg PASS
24 Boiler Rm Shop O2 Amico A2M Liquid Level Low O2 Bulk
Enclosure
60 PSI PASS
25 Boiler Rm Shop O2 Amico A2M Reserve in Use O2 Bulk
Enclosure
100 PSI PASS
26 Boiler Rm Shop O2 Amico A2M Reserve Liquid
Level Low
O2 Bulk
Enclosure
60 PSI PASS
27 Boiler Rm Shop O2 Amico A2M Reserve
Pressure Low
O2 Bulk
Enclosure
50 PSI PASS
28 Boiler Rm Shop O2 Amico A2M High Line
Pressure Hospital 60 PSI PASS
29 Boiler Rm Shop O2 Amico A2M Low Line
Pressure Hospital 40 PSI PASS
30 Boiler Rm Shop N2O Amico A2M Reserve in Use Manifold Room 100 PSI PASS
31 Boiler Rm Shop N2O Amico A2M High Line
Pressure Manifold Room 60 PSI PASS
32 Boiler Rm Shop N2O Amico A2M Low Line
Pressure Manifold Room 40 PSI PASS
Report Section: MASTER ALARMS
Page: 10 of 90
Master Alarm Panel
Location/#* *If multiple panels per location
(e.g. "Engineering Panel 1")
System MFR Model Condition
Monitored
Switch or
Source
Location S e t
P o in t
U n it o f
M e a s u re Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
MASTER ALARMS: LOCATION & SPECIFICATION FUNCTION & CONDITION
33 Boiler Rm Shop MA Amico A2M (1-2) High Dew
Point
Mechanical
Room
32 PSI PASS
34 Boiler Rm Shop MA Amico A2M (1-2) High CO Mechanical
Room
10 PPM PASS
35 Boiler Rm Shop MA Amico A2M
(1-2) Lag
Compressor in
Use
Mechanical
Room
65 PSI PASS
36 Boiler Rm Shop MA Amico A2M High Line
Pressure Hospital 60 PSI PASS
37 Boiler Rm Shop MA Amico A2M Low Line
Pressure Hospital 40 PSI PASS
38 Boiler Rm Shop VAC Amico A2M (1-2) Lag Pump in Use
Mechanical
Room 18 inHg PASS
39 Boiler Rm Shop VAC Amico A2M Low Line
Pressure Hospital 12 inHg PASS
40 Boiler Rm Shop MA Amico A2M (3-4) High Dew
Point
Mechanical
Room
32 PSI PASS
41 Boiler Rm Shop MA Amico A2M
(116)
Maintenance
Required
Mechanical
Room
PASS
42 Boiler Rm Shop MA Amico A2M
(116) High Dew
Point
Mechanical
Room
32 PSI PASS
43 Boiler Rm Shop N2 Amico A2M Low Line
Pressure
2nd Fl Manifold
Rm
140 PSI PASS
44 Boiler Rm Shop N2 Amico A2M High Line
Pressure
2nd Fl Manifold
Rm
200 PSI PASS
45 Boiler Rm Shop N2 Amico A2M Reserve in Use 2nd Fl Manifold
Rm
250 PSI PASS
46 Boiler Rm Shop VAC Amico A2M (New) Lag
Pump in Use
Mechanical
Room 18 inHg PASS
47 Boiler Rm Shop VAC Amico A2M Low Line
Pressure Hospital 12 inHg PASS
Report Section: MASTER ALARMS
Page: 11 of 90
TOTAL AREA ALARM SIGNALS
BY SYSTEM GAS:
31 27 1 1 0 28 0 0 0
88TOTAL AREA
ALARM SIGNALS
TOTAL AREA ALARM PANELS:
MANUFACTURER
(Or Current Parent
Company )
MODEL AREA ALARM DESCRIPTION
O
M A
N
O
N
C O
V A
C
W A
G D
IA
O th e r
Allied Impact Ivory Cover - Digital LEDs 5 4 5
Amico A2A Gray Cover with Digital Pressure 6 6 1 1 5
Amico A3A LCD Display 10 10 10
Beacon Infinity Touch Screen LCD 1 1 1
Beacon Mega Digital Module 3 1
Beacon Mega 2 Tan Cover - Digital LEDs 1 1 1
Beacon P0321 White with Murphy gauges-"Area Line Press. Alm" 5 5 5
AREA ALARMS BREAKDOWN (EACH AREA ALARM SIGNAL COUNTED AS SEPARATE ALARM BY SYSTEM GAS BELOW)
TOTAL AREA
ALARM SIGNALS
Report Section: AREA ALARMS INVENTORY
Page: 12 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s u re
R e a d in g
(A ll G a s e s P
S I/
V A
C
W A
G D
H g
H ig h P re s s
S tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
MSA Desk Opp 4A
Nurses Station
(Left)
A419-423, A426, A429, A430 O2 Allied Impact 52 60 40 PASS
MSA Desk Opp 4A
Nurses Station
(Left)
A419-423, A426, A429, A430 MA Allied Impact 48 60 40 PASS
MSA Desk Opp 4A
Nurses Station
(Left)
A419-423, A426, A429, A430 VAC Allied Impact 21 12 PASS
MSA Desk Opp 4A
Nurses Station
(Right)
A401-404, AS407,
A409, A410, A413-
O2 Allied Impact 52 60 40 PASS
MSA Desk Opp 4A
Nurses Station
(Right)
A401-404, AS407,
A409, A410, A413-
MA Allied Impact 48 60 40 PASS
MSA Desk Opp 4A
Nurses Station
(Right)
A401-404, AS407,
A409, A410, A413-
VAC Allied Impact 21 12 PASS
7 Opp A470 A468-A470 VAC Amico A3A 22 12 PASS
8 Opp A470 A468-A470 O2 Amico A3A 53 60 40 PASS
9 Opp A470 A468-A470 MA Amico A3A 50 60 40 PASS
4B South Nurses
Station
B404-B409, B412, B415-B417, B420-
B422, B424-B427
O2 Allied Impact 53 60 40 PASS
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
Report Section: AREA ALARMS
Page: 13 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
4B South Nurses
Station
B404-B409, B412, B415-B417, B420-
B422, B424-B427
MA Allied Impact 49 60 40 PASS
4B South Nurses
Station
B404-B409, B412, B415-B417, B420-
B422, B424-B427
VAC Allied Impact 20 12 PASS
4B North Nurses
Station
B428-B431, B433-
B435, B437-B439, B441, B444, B445, B447-B450
O2 Amico A2A 53 60 40 PASS
4B North Nurses
Station
B428-B431, B433-
B435, B437-B439, B441, B444, B445, B447-B450
MA Amico A2A 50 60 40 PASS
4B North Nurses
Station
B428-B431, B433-
B435, B437-B439, B441, B444, B445, B447-B450
VAC Amico A2A 21 12 PASS
16 I/S 4B Chemo B451 Chemo B451 O2 Allied Impact 52 60 40 PASS
17 I/S 4B Chemo B451 Chemo B451 VAC Allied Impact 21 12 PASS
Behavioral Nurses
Station Not in Use O2 Beacon Mega PASS Powered off. Labeled "Not In Use"
Report Section: AREA ALARMS
Page: 14 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
Behavioral Nurses
Station Not in Use O2 Beacon Mega PASS Powered off. Labeled "Not In Use"
20 Opp B382 B381, B382, B391 O2 Beacon P0321 52 60 40 PASS
21 Opp B382 B381, B382, B391 VAC Beacon P0321 21 60 40 PASS
22 Opp B382 B381, B382, B391 MA Beacon P0321 51 12 PASS
3B South Nurses
Station (Left)
B310, B312, B315, B317, B318 MA Amico A3A 51 60 40 PASS
3B South Nurses
Station (Left)
B310, B312, B315, B317, B318 O2 Amico A3A 53 60 40 PASS
3B South Nurses
Station (Left)
B310, B312, B315, B317, B318 VAC Amico A3A 22 12 PASS
3B South Nurses
Station (Center)
B304-B307, B355, B358 MA Amico A3A 51 60 40 PASS
3B South Nurses
Station (Center)
B304-B307, B355, B358 VAC Amico A3A 21 12 PASS
Report Section: AREA ALARMS
Page: 15 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
3B South Nurses
Station (Center)
B304-B307, B355, B358 O2 Amico A3A 53 60 40 PASS
3B South Nurses
Station (Right)
B321, B322, B325, B326, B366B MA Amico A3A 51 60 40 PASS
3B South Nurses
Station (Right)
B321, B322, B325, B326, B366B O2 Amico A3A 53 60 40 PASS
3B South Nurses
Station (Right)
B321, B322, B325, B326, B366B VAC Amico A3A 21 12 PASS
3B North Nurses
Station
B329-B334, B336-
B338, B342, B347, B348
O2 Amico A2A 52 60 40 PASS
3B North Nurses
Station
B329-B334, B336-
B338, B342, B347, B348
MA Amico A2A 50 60 40 PASS
3B North Nurses
Station
B329-B334, B336-
B338, B342, B347, B348
VAC Amico A2A 21 12 PASS
35 Opp AA205 AA204A & AA206 O2 Amico A3A 54 60 40 PASS
36 Opp AA205 AA204A & AA206 MA Amico A3A 48 60 40 PASS
37 Opp AA205 AA204A & AA206 VAC Amico A3A 21 12 PASS
Report Section: AREA ALARMS
Page: 16 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
38 Opp AA206 AA205 O2 Beacon P0321 54 60 40 PASS
39 Opp AA206 AA205 MA Beacon P0321 50 60 40 PASS
40 Opp AA206 AA205 VAC Beacon P0321 22 12 PASS
41 Opp AA220 AA223 O2 Amico A2A 55 60 40 PASS
42 Opp AA220 AA223 MA Amico A2A 48 60 40 PASS
43 Opp AA220 AA223 VAC Amico A2A 22 12 PASS
44 I/S AA239 AA239 O2 Amico A2A 55 60 40 PASS
45 I/S AA239 AA239 MA Amico A2A 48 60 40 PASS
46 Opp A281
A213-A215, A221-
A223, A281, A282, A287
O2 Amico A3A 55 60 40 PASS
Report Section: AREA ALARMS
Page: 17 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
47 Opp A281
A213-A215, A221-
A223, A281, A282, A287
MA Amico A3A 48 60 40 PASS
48 Opp A281 A213-A215, A221-
A223, A281, A282 VAC Amico A3A 21 12 PASS
49 Opp A217 A216-A220 O2 Amico A3A 55 60 40 PASS
50 Opp A217 A216-A220 MA Amico A3A 48 60 40 PASS
51 Opp A217 A216-A220 VAC Amico A3A 21 12 PASS
52 Opp A229 A224-A231 O2 Amico A3A 54 60 40 PASS
53 Opp A229 A224-A231 MA Amico A3A 48 60 40 PASS
54 Opp A229 A224-A231 VAC Amico A3A 21 12 PASS
55 I/S C212 OR Suite O2 Amico A2A 55 60 40 PASS
56 I/S C212 OR Suite VAC Amico A2A 20 12 PASS
Report Section: AREA ALARMS
Page: 18 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
57 I/S C212 OR Suite N2 Amico A2A 169 200 140 PASS
58 I/S C212 OR Suite MA Amico A2A 48 60 40 PASS
59 I/S C212 OR Suite N2O Amico A2A 50 60 40 PASS
60 Opp A237 A264 (Beds 1-11), A232A (Beds 1 & 2) O2 Allied Impact 52 60 40 PASS
61 Opp A237 A264 (Beds 1-11), A232A (Beds 1 & 2) MA Allied Impact 50 60 40 PASS
62 Opp A237 A264 (Beds 1-11), A232A (Beds 1 & 2) VAC Allied Impact 21 12 PASS
63 I/S B212 B212, B212B O2 Amico A2A 54 60 40 PASS
64 I/S B212 B212, B212B MA Amico A2A 50 60 40 PASS
65 I/S B212 B212, B212B VAC Amico A2A 22 12 PASS
66 I/S B206 B204, B206(A,B,D&E) O2 Beacon Mega 53 60 40 PASS
Report Section: AREA ALARMS
Page: 19 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
67 I/S B206 B206D VAC Beacon Mega 21 12 PASS
68 I/S BB208
BB203, BB208,
BB209, BB210
O2 Beacon P0321 54 60 40 PASS
69 I/S BB208
BB203, BB208,
BB209, BB210
MA Beacon P0321 48 60 40 PASS
70 I/S BB208
BB203, BB208,
BB209, BB210
VAC Beacon P0321 22 12 PASS
Radiology Front
Desk
D205, D205C, Holding bays 1 & 2 opp. D205C, D211, D237, D238, D241, D242, D243, D245
(Bay 1 & 2), D247, D269(A, B, & J)
O2 Amico A3A 54 60 40 REPAIRED
Area monitored labeling missing/incorrect: Added new holding bays (1 & 2) opp. D205C to label.
Radiology Front
Desk
D205, Holding bays opp. D205C, D211, D237, D238, D241, D242, D243, D245
(Bay 1 & 2), D247, D269(A, B, & J)
MA Amico A3A 48 60 40 REPAIRED
Area monitored labeling missing/incorrect: Added new holding bays (1 & 2) opp. D205C to label.
Report Section: AREA ALARMS
Page: 20 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
Radiology Front
Desk
D205, D205C, Holding bays 1 & 2 opp. D205C, D211, D237, D238, D241, D242, D243, D245
(Bay 1 & 2), D247, D269(A, B, & J)
VAC Amico A3A 22 12 REPAIRED
Area monitored labeling missing/incorrect: Added new holding bays (1 & 2) opp. D205C to label.
74 O/S D225 D222 O2 Beacon P0321 54 60 40 PASS
75 O/S D225 D222 MA Beacon P0321 54 60 40 PASS
76 O/S D225 D222 VAC Beacon P0321 24 12 PASS
77 I/S A164A
A110-A112, A114-
A116, A119-A127, A167
O2 Amico A3A 52 60 40 PASS
78 I/S A164A A167 MA Amico A3A 50 60 40 PASS
79 I/S A164A
A110-A112, A114-
A116, A119-A127, A167
VAC Amico A3A 23 12 PASS
Report Section: AREA ALARMS
Page: 21 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
Main ED Nurses
Station
ED 4-18 (Alarm sensors located downstream of ED
4-10 Service
Valves)
O2 Beacon Mega 2 52 60 40 PASS
Main ED Nurses
Station
ED 4-18 (Alarm sensors located downstream of ED
4-10 Service
Valves)
MA Beacon Mega 2 46 60 40 PASS
Main ED Nurses
Station
ED 4-18 (Alarm sensors located downstream of ED
4-10 Service
Valves)
VAC Beacon Mega 2 21 12 PASS
Rear ED Nurses
Station
ED 4-18 (Alarm sensors located upstream of ED 4-
10 Service Valves)
O2 Beacon Infinity 52 60 40 PASS
Rear ED Nurses
Station
ED 4-18 (Alarm sensors located upstream of ED 4-
10 Service Valves)
MA Beacon Infinity 46 60 40 PASS
Rear ED Nurses
Station
ED 4-18 (Alarm sensors located upstream of ED 4-
10 Service Valves)
VAC Beacon Infinity 21 12 PASS
86 O/S F215 G200 O2 Beacon P0321 55 60 40 PASS
Report Section: AREA ALARMS
Page: 22 of 90
# Physical Location Area/Rooms
Monitored System MFR Model
P re s s a d
G a s e s P
S I/
V A
C
W A g
H ig h P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
L o w P re s s tt in g
(A ll
G a s e s P
S I/
V A
C
W A g
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
AREA ALARMS: LOCATION & SPECIFICATION FUNCTION AND CONDITION
87 O/S F215 G200 MA Beacon P0321 52 60 40 PASS
88 O/S F215 G200 VAC Beacon P0321 22 12 PASS
Report Section: AREA ALARMS
Page: 23 of 90
TOTAL VALVES
BY SYSTEM GAS:
36 33 6 6 0 34 0 0 0
115TOTAL
VALVES
TOTAL ZONE VALVE BOXES
MANUFACTURER VALVE TYPE VALVE DESCRIPTION
O
M A
N O
N
C O
V A
C
W A
G D
IA
O th e r
Allied Zone - 1/4 Turn Accessible valve through which all station outlets/inlets are served 3 2 2
Amico Zone - 1/4 Turn Accessible valve through which all station outlets/inlets are served 20 19 5 5 19
Beacon Service - 1/4 Turn For servicing or modification of lateral branch piping 1 1 1
Beacon Zone - 1/4 Turn Accessible valve through which all station outlets/inlets are served 12 11 1 1 12
VALVES BREAKDOWN (EACH SYSTEM GAS COUNTED AS SEPARATE ZONE VALVE)
115TOTAL
VALVES
Report Section: VALVES INVENTORY
Page: 24 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
O/S A413
A401-A404, A407, A409, A410, A413-
A417
O2 Allied Zone - 1/4 Turn 54 PASS
O/S A413
A401-A404, A407, A409, A410, A413-
A417
MA Allied Zone - 1/4 Turn 50 PASS
O/S A413
A401-A404, A407, A409, A410, A413-
A417
VAC Allied Zone - 1/4 Turn 21 PASS
Opp A423
A419-A423, A426, A429, A430 O2 Allied Zone - 1/4 Turn 54 PASS
Opp A423
A419-A423, A426, A429, A430 MA Allied Zone - 1/4 Turn 50 PASS
Opp A423
A419-A423, A426, A429, A430 VAC Allied Zone - 1/4 Turn 21 PASS
7 O/S A469 A468-A470 O2 Amico Zone - 1/4 Turn 53 PASS
8 O/S A469 A468-A470 MA Amico Zone - 1/4 Turn 50 PASS
9 O/S A469 A468-A470 VAC Amico Zone - 1/4 Turn 22 PASS
4B South Nurses
Station
B404-409, B412, B415-B417, B420-
B422, B424-B427
O2 Beacon Zone - 1/4 Turn 50 PASS
4B South Nurses
Station
B404-409, B412, B415-B417, B420-
B422, B424-B427
MA Beacon Zone - 1/4 Turn 42 PASS
4B South Nurses
Station
B404-409, B412, B415-B417, B420-
B422, B424-B427
VAC Beacon Zone - 1/4 Turn 21 PASS
Opp 4B North Nurses
Station
B428-B431, B433-
B435, B437-B439, B441, B444, B445, B447-B450
VAC Amico Zone - 1/4 Turn 22 PASS
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
Report Section: VALVES
Page: 25 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
Opp 4B North Nurses
Station
B428-B431, B433-
B435, B437-B439, B441, B444, B445, B447-B450
MA Amico Zone - 1/4 Turn 50 PASS
Opp 4B North Nurses
Station
B428-B431, B433-
B435, B437-B439, B441, B444, B445, B447-B450
O2 Amico Zone - 1/4 Turn 52 PASS
16 Opp B405 Chemo B451 O2 Amico Zone - 1/4 Turn 58 PASS
17 Opp B405 Chemo B451 VAC Amico Zone - 1/4 Turn 23 PASS
A301, A302, A303, A305, A306
O2 FAIL
System depressurized. Remove patient terminal, install locking device or locate/install Zone Valve to control rooms A301-A303, A305, A306.
A301, A302, A303, A305, A306
MA FAIL
System depressurized. Remove patient terminal, install locking device or locate/install Zone Valve to control rooms A301-A303, A305, A306.
A301, A302, A303, A305, A306
VAC FAIL
Remove patient terminal, install locking device or locate/install Zone Valve to control rooms A301-A303, A305, A306.
21 3rd Fl Behavioral
Health Entrance Not In Use O2 Beacon Zone - 1/4 Turn X PASS Labeled "Not in Use"
22 Opp B382 B381, B382, B391 MA Amico Zone - 1/4 Turn 52 PASS
23 Opp B382 B381, B382, B391 O2 Amico Zone - 1/4 Turn 52 PASS
24 Opp B382 B381, B382, B391 VAC Amico Zone - 1/4 Turn 22 PASS
O/S B307
B304-B307, B355, B358 MA Beacon Zone - 1/4 Turn 52 PASS
O/S B307
B304-B307, B355, B358 O2 Beacon Zone - 1/4 Turn 52 PASS
O/S B307
B304-B307, B355, B358 VAC Beacon Zone - 1/4 Turn 21 PASS
Report Section: VALVES
Page: 26 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
28 3B South Nurses
Station
B310, B312, B315,B317, B318 MA Amico Zone - 1/4 Turn 52 PASS
29 3B South Nurses
Station
B310, B312, B315,B317, B318 O2 Amico Zone - 1/4 Turn 54 PASS
30 3B South Nurses
Station
B310, B312, B315,B317, B318 VAC Amico Zone - 1/4 Turn 21 PASS
31 O/S 3B South Nurses
Station
B321, B322, B325, B326, B366B MA Amico Zone - 1/4 Turn 50 PASS
32 O/S 3B South Nurses
Station
B321, B322, B325, B326, B366B O2 Amico Zone - 1/4 Turn 52 PASS
33 O/S 3B South Nurses
Station
B321, B322, B325, B326, B366B VAC Amico Zone - 1/4 Turn 22 PASS
Opp 3B North Nurses
Station
B329-B334, B336-
B338, B342, B347, B348
O2 Beacon Zone - 1/4 Turn 50 PASS
Opp 3B North Nurses
Station
B329-B334, B336-
B338, B342, B347, B348
MA Beacon Zone - 1/4 Turn 50 PASS
Opp 3B North Nurses
Station
B329-B334, B336-
B338, B342, B347, B348
VAC Beacon Zone - 1/4 Turn 21 PASS
37 O/S C318 Not In Use O2 Allied Zone - 1/4 Turn X PASS Labeled "Not in Use"
38 Opp AA205 AA204A & AA206 O2 Amico Zone - 1/4 Turn 54 PASS
39 Opp AA205 AA204A & AA206 MA Amico Zone - 1/4 Turn 48 PASS
40 Opp AA205 AA204A & AA206 VAC Amico Zone - 1/4 Turn 22 PASS
41 Opp AA207 AA205 O2 Beacon Zone - 1/4 Turn 54 PASS
42 Opp AA207 AA205 MA Beacon Zone - 1/4 Turn 50 PASS
43 Opp AA207 AA205 VAC Beacon Zone - 1/4 Turn 24 PASS
44 Opp AA220 AA223 O2 Beacon Zone - 1/4 Turn 54 PASS
45 Opp AA220 AA223 MA Beacon Zone - 1/4 Turn 50 PASS
46 Opp AA220 AA223 VAC Beacon Zone - 1/4 Turn 24 PASS
Report Section: VALVES
Page: 27 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
47 O/S AA239 AA239 MA Amico Zone - 1/4 Turn 50 PASS
48 O/S AA239 AA239 O2 Amico Zone - 1/4 Turn 56 PASS
Opp A215
A213-A215, A221-
A223, A281, A282, A287
O2 Amico Zone - 1/4 Turn 56 PASS
Opp A215
A213-A215, A221-
A223, A281, A282, A287
MA Amico Zone - 1/4 Turn 52 PASS
Opp A215
A213-A215, A221-
A223, A281, A282 VAC Amico Zone - 1/4 Turn 21 PASS
52 Opp A216 A216-A220 O2 Amico Zone - 1/4 Turn 54 PASS
53 Opp A216 A216-A220 MA Amico Zone - 1/4 Turn 50 PASS
54 Opp A216 A216-A220 VAC Amico Zone - 1/4 Turn 22 PASS
55 Opp A224 A224-A231 O2 Amico Zone - 1/4 Turn 54 PASS
56 Opp A224 A224-A231 MA Amico Zone - 1/4 Turn 50 PASS
57 Opp A224 A224-A231 VAC Amico Zone - 1/4 Turn 22 PASS
58 I/S Sub Sterile A238B
(O/S OR 1)
A239 (OR 1) N2 Amico Zone - 1/4 Turn 180 PASS
59 I/S Sub Sterile A238B
(O/S OR 1)
A239 (OR 1) MA Amico Zone - 1/4 Turn 50 PASS
60 I/S Sub Sterile A238B
(O/S OR 1)
A239 (OR 1) N2O Amico Zone - 1/4 Turn 50 PASS
61 I/S Sub Sterile A238B
(O/S OR 1)
A239 (OR 1) O2 Amico Zone - 1/4 Turn 54 PASS
62 I/S Sub Sterile A238B
(O/S OR 1)
A239 (OR 1) VAC Amico Zone - 1/4 Turn 22 PASS
63 I/S Sub Sterile A238B
(O/S OR 2)
A238 (OR 2) N2 Amico Zone - 1/4 Turn 180 PASS
64 I/S Sub Sterile A238B
(O/S OR 2)
A238 (OR 2) MA Amico Zone - 1/4 Turn 52 PASS
65 I/S Sub Sterile A238B
(O/S OR 2)
A238 (OR 2) N2O Amico Zone - 1/4 Turn 50 PASS
Report Section: VALVES
Page: 28 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
66 I/S Sub Sterile A238B
(O/S OR 2)
A238 (OR 2) O2 Amico Zone - 1/4 Turn 54 PASS
67 I/S Sub Sterile A238B
(O/S OR 2)
A238 (OR 2) VAC Amico Zone - 1/4 Turn 23 PASS
68 I/S Sub Sterile A234B
(O/S OR 3)
A234 (OR 3) N2 Amico Zone - 1/4 Turn 180 PASS
69 I/S Sub Sterile A234B
(O/S OR 3)
A234 (OR 3) MA Amico Zone - 1/4 Turn 52 PASS
70 I/S Sub Sterile A234B
(O/S OR 3)
A234 (OR 3) N2O Amico Zone - 1/4 Turn 50 PASS
71 I/S Sub Sterile A234B
(O/S OR 3)
A234 (OR 3) O2 Amico Zone - 1/4 Turn 54 PASS
72 I/S Sub Sterile A234B
(O/S OR 3)
A234 (OR 3) VAC Amico Zone - 1/4 Turn 21 PASS
73 I/S Sub Sterile A234B
(O/S OR 4)
A235 (OR 4) N2 Amico Zone - 1/4 Turn 180 PASS
74 I/S Sub Sterile A234B
(O/S OR 4)
A235 (OR 4) MA Amico Zone - 1/4 Turn 52 PASS
75 I/S Sub Sterile A234B
(O/S OR 4)
A235 (OR 4) N2O Amico Zone - 1/4 Turn 50 PASS
76 I/S Sub Sterile A234B
(O/S OR 4)
A235 (OR 4) O2 Amico Zone - 1/4 Turn 54 PASS
77 I/S Sub Sterile A234B
(O/S OR 4)
A235 (OR 4) VAC Amico Zone - 1/4 Turn 23 PASS
78 Opp A236A A236A (OR 5) N2 Amico Zone - 1/4 Turn 180 PASS
79 Opp A236A A236A (OR 5) MA Amico Zone - 1/4 Turn 52 PASS
80 Opp A236A A236A (OR 5) N2O Amico Zone - 1/4 Turn 50 PASS
81 Opp A236A A236A (OR 5) O2 Amico Zone - 1/4 Turn 54 PASS
82 Opp A236A A236A (OR 5) VAC Amico Zone - 1/4 Turn 21 PASS
83 O/S C205 C205 (OR 6) O2 Beacon Zone - 1/4 Turn 54 PASS
84 O/S C205 C205 (OR 6) MA Beacon Zone - 1/4 Turn 50 PASS
85 O/S C205 C205 (OR 6) N2O Beacon Zone - 1/4 Turn 50 PASS
Report Section: VALVES
Page: 29 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
86 O/S C205 C205 (OR 6) N2 Beacon Zone - 1/4 Turn 180 PASS
87 O/S C205 C205 (OR 6) VAC Beacon Zone - 1/4 Turn 21 PASS
88 O/S A233 A232A, A264 O2 Beacon Zone - 1/4 Turn 54 PASS
89 O/S A233 A232A, A264 MA Beacon Zone - 1/4 Turn 50 PASS
90 O/S A233 A232A, A264 VAC Beacon Zone - 1/4 Turn 22 PASS
91 O/S B212 B212 B212B O2 Beacon Zone - 1/4 Turn 54 PASS
92 O/S B212 B212 B212B MA Beacon Zone - 1/4 Turn 50 PASS
93 O/S B212 B212 B212B VAC Beacon Zone - 1/4 Turn 22 PASS
O/S B206
B204, B206(A,B,D&E) O2 Beacon Zone - 1/4 Turn 54 PASS
95 O/S B206 206D VAC Beacon Zone - 1/4 Turn 23 PASS
O/S BB232
BB203, BB208,
BB209, BB210
O2 Beacon Zone - 1/4 Turn 54 PASS
O/S BB232
BB203, BB208,
BB209, BB210
MA Beacon Zone - 1/4 Turn 48 PASS
O/S BB232
BB203, BB208,
BB209, BB210
VAC Beacon Zone - 1/4 Turn 22 PASS
99 Opp BB211 Not In Use MA Beacon Zone - 1/4 Turn 0 PASS
100 Opp BB211 Not In Use VAC Beacon Zone - 1/4 Turn 0 PASS
O/S D205
D205, D205C, Holding bays 1 & 2 opp. D205C, D211, D237, D238, D241, D242, D243, D245
(Bay 1 & 2), D247, D269(A, B, & J)
O2 Beacon Zone - 1/4 Turn 50 REPAIRED Labeling inaccurate - rooms/area served: Added new holding bays (1 &
2) opp. D205C to label.
Report Section: VALVES
Page: 30 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
O/S D205
D205, Holding bays 1
& 2 opp. D205C, D211, D237, D238, D241, D242, D243, D245 (Bay 1 & 2), D247, D269(A, B, &
J)
MA Beacon Zone - 1/4 Turn 50 REPAIRED Labeling inaccurate - rooms/area served: Added new holding bays (1 &
2) opp. D205C to label.
O/S D205
D205, D205C, Holding bays 1 & 2 opp. D205C, D211, D237, D238, D241, D242, D243, D245
(Bay 1 & 2), D247, D269(A, B, & J)
VAC Beacon Zone - 1/4 Turn 23 REPAIRED Labeling inaccurate - rooms/area served: Added new holding bays (1 &
2) opp. D205C to label.
104 O/S D225 D222 O2 Amico Zone - 1/4 Turn 56 PASS
105 O/S D225 D222 MA Amico Zone - 1/4 Turn 54 PASS
106 O/S D225 D222 VAC Amico Zone - 1/4 Turn 24 PASS
O/S A119
A110-A112, A114-
A116, A119-A127, A167
O2 Amico Zone - 1/4 Turn 52 PASS
108 O/S A119 A167 MA Amico Zone - 1/4 Turn 50 PASS
O/S A119
A110-A112, A114-
A116, A119-A127, A167
VAC Amico Zone - 1/4 Turn 23 PASS
Report Section: VALVES
Page: 31 of 90
# Physical Location Area/Rooms Served System MFR Valve Type
Gauge
Reading (All Gases PSI/
VAC & WAGD
inHg)
Component
Condition / Test
Results
Deficiency Detail or
Corrective Action
Needed/Taken
VALVES: LOCATION & SPECIFICATION FUNCTION AND CONDITION
ED Main Nurses
Station
ED 4-10 (Labeled as
"Service Valves") O2 Beacon Service - 1/4 Turn X FAIL
Service valves shall be placed in the branch piping prior to any zone valve box assembly on that branch. Wall mounted medical equipment blocks removal of Zone(Service) Valve box hard cover
ED Main Nurses
Station
ED 4-10 (Labeled as
"Service Valves") MA Beacon Service - 1/4 Turn X FAIL
Service valves shall be placed in the branch piping prior to any zone valve box assembly on that branch. Wall mounted medical equipment blocks removal of Zone(Service) Valve box hard cover
ED Main Nurses
Station
ED 4-10 (Labeled as
"Service Valves") VAC Beacon Service - 1/4 Turn X FAIL
Service valves shall be placed in the branch piping prior to any zone valve box assembly on that branch. Wall mounted medical equipment blocks removal of Zone(Service) Valve box hard cover
O/S CC117
ED 4-18 (B172, B174,
B180-B185, CC102-
CC105, CC107-
CC109)
O2 Amico Zone - 1/4 Turn 54 PASS
O/S CC117
ED 4-18 (B172, B174,
B180-B185, CC102-
CC105, CC107-
CC109)
MA Amico Zone - 1/4 Turn 49 PASS
O/S CC117
ED 4-18 (B172, B174,
B180-B185, CC102-
CC105, CC107-
CC109)
VAC Amico Zone - 1/4 Turn 22 PASS
116 O/S F215 G200 O2 Amico Zone - 1/4 Turn 55 PASS
117 O/S F215 G200 MA Amico Zone - 1/4 Turn 52 PASS
118 O/S F215 G200 VAC Amico Zone - 1/4 Turn 22 PASS
Report Section: VALVES
Page: 32 of 90
TOTAL
OUTLETS/
INLETS:
TOTAL OUTLETS/INLETS
BY SYSTEM GAS:
322 6 6 0 499 15 0 0
MANUFACTURER MODEL OUTLET/INLET DESCRIPTION
O
M A
N O
N
C O
V A
C
W A
G D
IA
O th e r
Amico O-CHEM Original Style - Chemetron Quick Connect 176 147 258 6
Amico O-DISS Original Style - DISS 35 29 35 2
Beacon B-CHEM Series B - CHEM 18 18 18
Beacon B-DISS Series B - DISS 12 6 5 24 6
Beacon CP-Ohmeda N2 Control Panel (Older Stainless Finish) 6
Beacon DIA III Diamond III Plastic Poppet w/ "Y" (Console Style Galvanized Plate) 33 27 28
Beacon DISS III Diamond III/Gemini w/ DISS Connection 2 2 1 3 1
Beacon O-CHEM 1 2 2
Schrader QC 1/8 turn quick connect 9 9 9
Tritech GRAD-CHEM CHEM - White Trim Plate/Color Graduated Front Plate 82 82 122
OUTLETS, INLETS & MANUFACTURED ASSEMBLY INVENTORY BREAKDOWN:
Report Section: OUTLETS & INLETS INVENTORY
Page: 33 of 90
OUTLETS & INLETS: LOCATION & SPECIFICATION
# Area or Zone Room, Bed or
Asset # System MFR Model Position/Style
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
1 4A 401 O2 Amico O-CHEM Artwall PASS
2 4A 401 MA Amico O-CHEM Artwall PASS
3 4A 401 VAC Amico O-CHEM Artwall PASS
4 4A 402 O2 Amico O-CHEM Artwall PASS
5 4A 402 MA Amico O-CHEM Artwall PASS
6 4A 402 VAC Amico O-CHEM Artwall PASS
7 4A 403 O2 Amico O-CHEM Artwall PASS
8 4A 403 MA Amico O-CHEM Artwall PASS
9 4A 403 VAC Amico O-CHEM Artwall PASS
10 4A 404 O2 Amico O-CHEM Artwall PASS
11 4A 404 MA Amico O-CHEM Artwall PASS
12 4A 404 VAC Amico O-CHEM Artwall PASS
13 4A 407 O2 Amico O-CHEM Artwall PASS
14 4A 407 MA Amico O-CHEM Artwall PASS
15 4A 407 VAC Amico O-CHEM Artwall PASS
16 4A 409 O2 Amico O-CHEM Artwall PASS
17 4A 409 MA Amico O-CHEM Artwall PASS
18 4A 409 VAC Amico O-CHEM Artwall PASS
19 4A 410 O2 Amico O-CHEM Artwall PASS
20 4A 410 MA Amico O-CHEM Artwall PASS
21 4A 410 VAC Amico O-CHEM Artwall PASS
22 4A 413 O2 Amico O-CHEM Artwall PASS
23 4A 413 MA Amico O-CHEM Artwall PASS
24 4A 413 VAC Amico O-CHEM Artwall PASS
25 4A 414 O2 Amico O-CHEM Artwall PASS
26 4A 414 MA Amico O-CHEM Artwall PASS
27 4A 414 VAC Amico O-CHEM Artwall PASS
FUNCTION & CONDITION
Report Section: OUTLETS & INLETS
Page: 34 of 90
OUTLETS & INLETS: LOCATION & SPECIFICATION
# Area or Zone Room, Bed or
Asset # System MFR Model Position/Style
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
FUNCTION & CONDITION
28 4A 415 O2 Amico O-CHEM Artwall PASS
29 4A 415 MA Amico O-CHEM Artwall PASS
30 4A 415 VAC Amico O-CHEM Artwall PASS
31 4A 416 O2 Amico O-CHEM Artwall PASS
32 4A 416 MA Amico O-CHEM Artwall PASS
33 4A 416 VAC Amico O-CHEM Artwall PASS
34 4A 417 O2 Amico O-CHEM Artwall PASS
35 4A 417 MA Amico O-CHEM Artwall PASS
36 4A 417 VAC Amico O-CHEM Artwall PASS
37 4A 419 O2 Amico O-CHEM Artwall PASS
38 4A 419 MA Amico O-CHEM Artwall PASS
39 4A 419 VAC Amico O-CHEM Artwall PASS
40 4A 420 O2 Amico O-CHEM Artwall PASS
41 4A 420 MA Amico O-CHEM Artwall PASS
42 4A 420 VAC Amico O-CHEM Artwall PASS
43 4A 421 O2 Amico O-CHEM Artwall PASS
44 4A 421 MA Amico O-CHEM Artwall PASS
45 4A 421 VAC Amico O-CHEM Artwall REPAIRED Leaking inner check - Repaired at time of testing
46 4A 422 O2 Amico O-CHEM Artwall PASS
47 4A 422 MA Amico O-CHEM Artwall PASS
48 4A 422 VAC Amico O-CHEM Artwall PASS
49 4A 423 O2 Amico O-CHEM Artwall PASS
50 4A 423 MA Amico O-CHEM Artwall PASS
51 4A 423 VAC Amico O-CHEM Artwall PASS
52 4A 426 O2 Amico O-CHEM Artwall PASS
53 4A 426 MA Amico O-CHEM Artwall PASS
54 4A 426 VAC Amico O-CHEM Artwall PASS
Report Section: OUTLETS & INLETS
Page: 35 of 90
OUTLETS & INLETS: LOCATION & SPECIFICATION
# Area or Zone Room, Bed or
Asset # System MFR Model Position/Style
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
FUNCTION & CONDITION
55 4A 429 O2 Amico O-CHEM Artwall PASS
56 4A 429 MA Amico O-CHEM Artwall PASS
57 4A 429 VAC Amico O-CHEM Artwall PASS
58 4A 430 O2 Amico O-CHEM Artwall PASS
59 4A 430 MA Amico O-CHEM Artwall PASS
60 4A 430 VAC Amico O-CHEM Artwall PASS
61 4A 468 O2 Amico O-CHEM Artwall PASS
62 4A 468 MA Amico O-CHEM Artwall PASS
63 4A 468 VAC Amico O-CHEM Artwall PASS
64 4A 469 O2 Amico O-CHEM Artwall PASS
65 4A 469 MA Amico O-CHEM Artwall PASS
66 4A 469 VAC Amico O-CHEM Artwall PASS
67 4A 470 O2 Amico O-CHEM Artwall PASS
68 4A 470 MA Amico O-CHEM Artwall PASS
69 4A 470 VAC Amico O-CHEM Artwall PASS
70 4B South 404 VAC Amico O-CHEM Headwall (Wall) PASS
71 4B South 404 MA Amico O-CHEM Headwall (Wall) PASS
72 4B South 404 VAC Amico O-CHEM Headwall (Wall) PASS
73 4B South 404 O2 Amico O-CHEM Headwall (Wall) PASS
74 4B South 404 VAC Amico O-CHEM Headwall (Wall) PASS
75 4B South 404 MA Amico O-CHEM Headwall (Wall) PASS
76 4B South 404 VAC Amico O-CHEM Headwall (Wall) PASS
77 4B South 404 O2 Amico O-CHEM Headwall (Wall) PASS
78 4B South 405 VAC Amico O-CHEM Headwall (Wall) PASS
79 4B South 405 MA Amico O-CHEM Headwall (Wall) PASS
80 4B South 405 VAC Amico O-CHEM Headwall (Wall) PASS
81 4B South 405 O2 Amico O-CHEM Headwall (Wall) PASS
Report Section: OUTLETS & INLETS
Page: 36 of 90
OUTLETS & INLETS: LOCATION & SPECIFICATION
# Area or Zone Room, Bed or
Asset # System MFR Model Position/Style
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
FUNCTION & CONDITION
82 4B South 406 VAC Amico O-CHEM Headwall (Wall) PASS
83 4B South 406 MA Amico O-CHEM Headwall (Wall) PASS
84 4B South 406 VAC Amico O-CHEM Headwall (Wall) PASS
85 4B South 406 O2 Amico O-CHEM Headwall (Wall) PASS
86 4B South 407 VAC Amico O-CHEM Headwall (Wall) PASS
87 4B South 407 MA Amico O-CHEM Headwall (Wall) PASS
88 4B South 407 VAC Amico O-CHEM Headwall (Wall) PASS
89 4B South 407 O2 Amico O-CHEM Headwall (Wall) PASS
90 4B South 408 VAC Amico O-CHEM Headwall (Wall) PASS
91 4B South 408 MA Amico O-CHEM Headwall (Wall) PASS
92 4B South 408 VAC Amico O-CHEM Headwall (Wall) PASS
93 4B South 408 O2 Amico O-CHEM Headwall (Wall) PASS
94 4B South 408 VAC Amico O-CHEM Headwall (Wall) PASS
95 4B South 408 MA Amico O-CHEM Headwall (Wall) PASS
96 4B South 408 VAC Amico O-CHEM Headwall (Wall) PASS
97 4B South 408 O2 Amico O-CHEM Headwall (Wall) PASS
98 4B South 409 VAC Amico O-CHEM Headwall (Wall) PASS
99 4B South 409 MA Amico O-CHEM Headwall (Wall) PASS
100 4B South 409 VAC Amico O-CHEM Headwall (Wall) PASS
101 4B South 409 O2 Amico O-CHEM Headwall (Wall) PASS
102 4B South 412 VAC Amico O-CHEM Headwall (Wall) PASS
103 4B South 412 MA Amico O-CHEM Headwall (Wall) PASS
104 4B South 412 VAC Amico O-CHEM Headwall (Wall) PASS
105 4B South 412 O2 Amico O-CHEM Headwall (Wall) PASS
106 4B South 415 VAC Amico O-CHEM Headwall (Wall) PASS
107 4B South 415 MA Amico O-CHEM Headwall (Wall) PASS
108 4B South 415 VAC Amico O-CHEM Headwall (Wall) PASS
Report Section: OUTLETS & INLETS
Page: 37 of 90
OUTLETS & INLETS: LOCATION & SPECIFICATION
# Area or Zone Room, Bed or
Asset # System MFR Model Position/Style
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
FUNCTION & CONDITION
109 4B South 415 O2 Amico O-CHEM Headwall (Wall) REPAIRED Leaking inner check - Repaired at time of testing
110 4B South 416 VAC Amico O-CHEM Headwall (Wall) PASS
111 4B South 416 MA Amico O-CHEM Headwall (Wall) PASS
112 4B South 416 VAC Amico O-CHEM Headwall (Wall) PASS
113 4B South 416 O2 Amico O-CHEM Headwall (Wall) PASS
114 4B South 417 VAC Amico O-CHEM Headwall (Wall) PASS
115 4B South 417 MA Amico O-CHEM Headwall (Wall) PASS
116 4B South 417 VAC Amico O-CHEM Headwall (Wall) PASS
117 4B South 417 O2 Amico O-CHEM Headwall (Wall) PASS
118 4B South 420 VAC Amico O-CHEM Headwall (Wall) PASS
119 4B South 420 MA Amico O-CHEM Headwall (Wall) PASS
120 4B South 420 VAC Amico O-CHEM Headwall (Wall) PASS
121 4B South 420 O2 Amico O-CHEM Headwall (Wall) PASS
122 4B South 421 VAC Amico O-CHEM Headwall (Wall) PASS
123 4B South 421 MA Amico O-CHEM Headwall (Wall) PASS
124 4B South 421 VAC Amico O-CHEM Headwall (Wall) PASS
125 4B South 421 O2 Amico O-CHEM Headwall (Wall) PASS
126 4B South 422 VAC Amico O-CHEM Headwall (Wall) PASS
127 4B South 422 MA Amico O-CHEM Headwall (Wall) PASS
128 4B South 422 VAC Amico O-CHEM Headwall (Wall) PASS
129 4B South 422 O2 Amico O-CHEM Headwall (Wall) PASS
130 4B South 424 VAC Amico O-CHEM Headwall (Wall) PASS
131 4B South 424 MA Amico O-CHEM Headwall (Wall) PASS
132 4B South 424 VAC Amico O-CHEM Headwall (Wall) PASS
133 4B South 424 O2 Amico O-CHEM Headwall (Wall) PASS
134 4B South 425 VAC Amico O-CHEM Headwall (Wall) PASS
135 4B South 425 MA Amico O-CHEM Headwall (Wall) PASS
Report Section: OUTLETS & INLETS
Page: 38 of 90
OUTLETS & INLETS: LOCATION & SPECIFICATION
# Area or Zone Room, Bed or
Asset # System MFR Model Position/Style
Component
Condition /
Test Results
Deficiency Detail or
Corrective Action
Needed/Taken
FUNCTION & CONDITION
136 4B South 425 VAC Amico O-CHEM Headwall (Wall) PASS
137 4B South 425 O2 Amico O-CHEM Headwall (Wall) PASS
138 4B South 426 VAC Amico O-CHEM Headwall (Wall) PASS
139 4B South 426 MA Amico O-CHEM Headwall (Wall) PASS
140 4B South 426 VAC Amico O-CHEM Headwall (Wall) PASS
141 4B South 426 O2 Amico O-CHEM Headwall (Wall) PASS
142 4B South 426 VAC Amico O-CHEM Headwall (Wall) PASS
143 4B South 426 MA Amico O-CHEM Headwall (Wall) PASS
144 4B South 426 VAC Amico O-CHEM Headwall (Wall) PASS
145 4B South 426 O2 Amico O-CHEM Headwall (Wall) PASS
146 4B South 427 VAC Amico O-CHEM Headwall (Wall) PASS
147 4B South 427 MA Amico O-CHEM Headwall…
This is the start of the file's text. The full file is on GovTribe.