R_PM_2026_VA Charleston_5.pdf
PDF 1 MB Posted
- Attached to
- J065--FY26: REPAIR MEDICAL GAS LEAK
- Solicitation number
- 36C24726Q0868
About this file
This document is a Preventative Maintenance Report for Medical Gas Source Equipment at Ralph H. Johnson VA Medical Center in Charleston, South Carolina, dated July 1, 2026. The report documents the completion of comprehensive preventative maintenance on multiple medical gas systems in compliance with NFPA 99 standards and The Joint Commission accreditation requirements.
The maintenance work was performed by Tanner Moore (Credential 6030 - 12454599) from Technical Safety Services and covers four primary systems: (1) Medical Vacuum Lubricated Rotary Vane Pump serving the entire facility excluding the OR Suite, with two Beacon pumps operating at 49,179 and 61,133 hours respectively; (2) Medical Vacuum/WAGD Claw Pump serving the OR Suite, with two Beacon Busch pumps at 7,348 and 7,021 hours; (3) Medical Air Scroll Compressor for the main facility, with two Atlas Copco units at 3,193 and 3,307 hours; and (4) Medical Air Reciprocating Compressor for the OR Suite, with two Beacon units at 8,585 and 7,551 hours. Additionally, the report documents maintenance on two gas manifolds—a Nitrogen manifold (HP type, Amico manufacturer) and a Nitrous Oxide manifold (HP type, Amico manufacturer)—both serving the OR Suite with 12 connections each. All systems passed operational and visual inspections with no leaks detected. Filters were changed, oil was serviced, pressure switches and relief valves were verified, and all labeling, alarms, and system checklists were confirmed as operational. One minor notation indicates that the Nitrogen and Nitrous Oxide manifolds lack dated manufacturer tags on their flexible connectors, though NFPA recommends replacement every five years; connections remain in functional condition.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24726Q0868_4.docx | DOCX document | |
| 36C24726Q0868_3.pdf | ||
| R_SYS_2026_VA Charleston_6.pdf | ||
| PXL_20260526_124550763_1.jpg | JPG image | |
| R_Boom Hose Inspections_2026_VA Charleston_4.pdf | ||
| PXL_20260526_124939323_3.jpg | JPG image | |
| PXL_20260526_124554514_2.jpg | JPG image | |
| 36C24726Q0868_2.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project ID: VA Charleston PM
Project Date: 7/1/2026
Project Date: 7/1/2026
Report Authored By: Tanner Moore
Credential: 6030 - 12454599
David Gatlin
Engineering
Project Contact:
(803)621-6104
Project Site:
Ralph H. Johnson VA Medical Center
109 Bee St
Charleston, SC
MEDICAL GAS SOURCE EQUIPMENT PM & SERVICE
Project ID:
Technical Safety Services
VA Charleston Preventative Maintenance
Lead Technician
Tanner Moore
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
PURPOSE
The purpose of the preventive maintenance documented in this report is to keep facility medical gas source systems in good repair, functioning at peak capacity, and maximize source system life as well as satisfy the NFPA
99 medical gas systems maintenance requirements.
REGULATORY REQUIREMENTS
Scheduled inspections for equipment and procedures shall be established through the risk assessment of the facility and developed with consideration of the original equipment manufacturer recommendations and other recommendations as required by the authority having jurisdication.
Additionally, The Joint Commission Standard EC 02.05.09 Ep 14 & other acceditation agencies requirements state that health care facilities must meet all applicable NFPA 99 codes related to medical gas systems. NFPA 99 sets out medical gas source system maintenance requirements including:
Facilities have a maintenance program for medical air compressor supply system(s) in accordance with the manufacturer's recommendations.
Facilities perform a testing and calibration procedure that ensures carbon monoxide monitors are calibrated at least annually or more often if recommended by the manufacturer.
Facilities have a maintenance program for the medical-surgical vacuum piping system to ensure the continued good performance of the entire medical-surgical vacuum system.
Facilities have a maintenance program for the WAGD system to ensure performance.
Audible and visual alarm indicators shall be periodically tested to determine that they are functioning properly.
Labels for shutoff valves shall be labeled and updated when modifications are made changing the area served.
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
1)
2)
3)
PROCESS AND QUALIFICATIONS
In addition to adhering to applicable regulatory requirements for the maintenance of medical gas source systems, EMS service technicians follow recommended maintenance as defined in original equipment manufacturer guidelines.
EMS service technicians are qualified to perform medical gas source system preventive maintenance to one or more of the following qualification requirements per NFPA 99:
Documented training by which such persons are qualified to work with specific equipment as installed in that facility.
Credentialing to the requirements of ASSE 6040, Professional Qualification Standard for Medical Gas
Maintenance Personnel.
Credentialing to the requirements of ASSE 6030, Professional Qualification Standard for Medical Gas Systems
Verifiers.
All technicians performing work on medical gas systems or components are qualifed per NFPA 99 5.1.14 to perform these services and have had adequate training to safely work on these systems.
The maintenance, inspection and testing operations requirements as follows, per NFPA 99, apply to all facilities with Category 1-3 Medical Gas, Vacuum, WAGD, and Medical Support Gas systems.
SCOPE AND APPLICATION
PERFORMED BY:
SYSTEM VOLTAGE 460
CHECK VALVES OK OK
PANEL LAMPS OK OK
MOTOR GREASE FITTINGS Greased Greased
MAXIMUM VACUUM 29
PRESSURE SWITCH IN / OUT 19 / 25 18 / 20
PRESSURE (PSI) Lead Switch Lag Switch
OIL TEMPERATURE (°F) 175 175
EXHAUST TEMPERATURE (°F) 180 180
N/A N/A
OPERATIONAL / VISUAL
INSPECTION / NOISE
OK OK
SIGHT GLASS
LEAKS NO NO
COOLING FAN/HEAT EXCHANGE Cleaned Cleaned
EXHAUST FILTERS Changed Changed
INLET FILTERS Changed Changed
COUPLING OK OK
AMP DRAW L1 / L2 / L3 18.5 / 18.9 / 19.6 19.4 / 19.2 / 18.9
OVERLOAD SETTINGS (AMPS) 22 22
HOURS 49179 61133
HORSEPOWER 15 15
SERIAL NUMBER 2830891 2830891
MODEL VAC03-015 VAC03-015
MANUFACTURER Beacon (Becker) Beacon (Becker)
PUMP INFO PUMP #1 PUMP #2 PUMP #3 PUMP #4
AREA(S) SERVED: Entire Facility (Excluding OR Suite)SYSTEM SERIAL #: 261708-2BW
SYSTEM TYPE: MEDICAL VACUUM SYS MODEL/JOB 4107102732
SYSTEM LOCATION: BB116 SYSTEM MFR: Beacon
FACILITY CITY / STATE / ZIP: Charleston, SC Tanner Moore
7/1/2026
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
FACILITY NAME: Ralph H. Johnson VA Medical CenterPROJECT ID: VA Charleston Preventative Maintenance
MEDICAL VACUUM LUBRICATED ROTARY VANE PUMP
FACILITY ADDRESS: 109 Bee St DATE OF SERVICE:
INLET FILTER HOUSING MODEL# Beacon Beacon
INLET FILTER MODEL # 4107 4001 87 4107 4001 87
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
MEDICAL VACUUM LUBRICATED ROTARY VANE PUMP
OIL LEVEL & COND Oil Changed / Oil level within manufacturer recommendations
ALTERNATION OK
LOCAL ALARMS OK
SYSTEM LABELING OK
VALVE LABELING OK
PIPE LABELING OK
COMMENTS
None
SYSTEM CHECKLIST
PERFORMED BY:
SYSTEM VOLTAGE 460 VFD #
COOLING FAN/HEAT EXCHANGE Cleaned Cleaned
28MAXIMUM VACUUM
PRESSURE SWITCH IN / OUT 19 / 25 18 / 20
PRESSURE (PSI) Lead Switch Lag Swithch
EXHAUST TEMPERATURE (°F) 165 155
OIL TEMPERATURE (°F) 185 185
OPERATIONAL / VISUAL
INSPECTION / NOISE / CHECKS
OK OK
LEAKS NO NO
PANEL LAMPS OK OK
OIL BREATHER CAP OK OK
MOTOR GREASE FITTINGS Greased Greased
COUPLING OK OK
AMP DRAW L1 / L2 / L3 13.3 / 13.9 / 14.1 13.9 / 14.6 / 13.5
OVERLOAD SETTINGS (AMPS) 20 20
HOURS 7348 7021
HORSEPOWER 10 10
SERIAL NUMBER 410765489 410765489
MODEL MM 1402 AV MM 1402 AV
MANUFACTURER Beacon (Busch) Beacon (Busch)
PUMP INFO PUMP #1 PUMP #2 PUMP #3 PUMP #4
AREA(S) SERVED: OR Suite SYSTEM SERIAL #: HOP302087
SYSTEM TYPE: MEDICAL VACUUM / WAGD SYSTEM MODEL: VHM10D-200V-DCV
SYSTEM LOCATION: C109 SYSTEM MFR: Beacon
FACILITY CITY / STATE / ZIP: Charleston, SC Tanner Moore
FACILITY ADDRESS: 109 Bee St DATE OF SERVICE: 7/1/2026
FACILITY NAME: Ralph H. Johnson VA Medical CenterPROJECT ID: VA Charleston Preventative Maintenance
MEDICAL VACUUM / WAGD CLAW PUMP
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
INLET FILTERS Changed Changed
INLET FILTER HOUSING MODEL# Beacon Beacon
INLET FILTER MODEL # 4107 4001 16 4107 4001 16
RELIEF VALVE SETTING OK OK
MEDICAL VACUUM / WAGD CLAW PUMP
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
None
VALVE LABELING OK
PIPE LABELING
COMMENTS
OK
LOCAL ALARMS OK
OIL LEVEL & COND Oil Changed / Oil level within manufacturer recommendations
SYSTEM LABELING OK
SYSTEM CHECKLIST
ALTERNATION OK
PERFORMED BY:
SYSTEM VOLTAGE 460 VFD # N/A
PRESSURE SWITCH IN / OUT 80 / 100 65 / 85
PRESSURE (PSI) Lead Switch Lag Switch
DISCHARGE TEMPERATURE (°F) 195 180
OPERATIONAL / VISUAL
INSPECTION / NOISE OK OK
LEAKS NO NO
PANEL LAMPS OK OK
CHECK VALVES OK OK
AFTERCOOLER DRAIN VALVES OK OK
INLET FILTER Changed Changed
BELT TENSION & CONDITION OK / OK OK / OK
AMP DRAW L1 / L2 / L3 19.8 / 20.6 / 21.3 20.6 / 20.9 / 21.1
OVERLOAD SETTINGS (AMPS) 25 25
HOURS 3193 3307
HORSEPOWER 15 15
SERIAL NUMBER AIA2064048 AIA2064048
MODEL 1916 7418 83 1916 7418 83
MANUFACTURER Atlas Copco Atlas Copco
COMPRESSOR INFO COMP #1 COMP #2 COMP #3 COMP #4
AREA(S) SERVED: Entire Facility (Excluding OR Suite)SYSTEM SERIAL #: HOP400765
SYSTEM TYPE: MEDICAL AIR SYSTEM MODEL: 4107005599
SYSTEM LOCATION: BB116 SYSTEM MFR: Beacon
FACILITY CITY / STATE / ZIP: Charleston, SC Tanner Moore
FACILITY ADDRESS: 109 Bee St DATE OF SERVICE: 7/1/2026
FACILITY NAME: Ralph H. Johnson VA Medical CenterPROJECT ID: VA Charleston Preventative Maintenance
MEDICAL AIR SCROLL COMPRESSOR
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
MEDICAL AIR SCROLL COMPRESSOR
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
MUFFLER
DRYER #4DRYER #3DRYER #2
VALVE LABELING OK
-45 PIPE LABELING OK
-45 AUTODRAIN OK
OK
COMMENTS
None
MODEL
SERIAL NUMBER 14 87875 14 87875
FILTRATION INFO PRE-FILTER AFTER-FILTER
MANUFACTURER Atlas Copco Atlas Copco
DRYER TYPE Dessicant Dessicant
DESSICANT MATERIAL COND. OK OK
MANUFACTURER Beacon Beacon
SERIAL NUMBER
DRYER SYSTEM INFO
MODEL LifeLine LifeLine
DEW POINT UNIT READING
DEW POINT (AS MEASURED)
MANUAL DRAIN OK
DRYER #1
LOCAL ALARMS
RECEIVER SIGHT GLASS
SYSTEM CHECKLIST
ALTERNATION CO UNIT READING 0
CO CALIBRATION Yes
SYSTEM LABELING
OK
OK
OK OK
PERFORMED BY:
SYSTEM VOLTAGE 460 VFD # N/A
PRESSURE SWITCH IN / OUT 80 / 100 65 / 85
OIL PRESSURE N/A
PRESSURE (PSI) Lead Switch Lag Switch
DISCHARGE TEMPERATURE (°F) 166 150
OIL TEMPERATURE (°F) N/A N/A
OPERATIONAL / VISUAL / NOISE OK OK
LEAKS NO NO
PANEL LAMPS OK OK
CRANK CASE FILTER Changed Changed
DISCHARGE CHECK VALVES OK OK
AFTERCOOLER DRAINS OK OK
UNLOADERS & SOLENOIDS OK OK
RIDER & PISTON RINGS OK OK
30 30
BELT TENSION / CONDITION OK / OK OK / OK
AMP DRAW L1 / L2 / L3 16.1 / 16.8 / 16.6 16.9 / 16.5 / 16.2
OVERLOAD SETTING (AMPS)
HOURS 8585 7551
HORSEPOWER 20 20
SERIAL NUMBER
MODEL 15U-9.5V5A 15U-9.5V5A
MANUFACTURER Beacon Beacon
COMPRESSOR INFO COMP #1 COMP #2 COMP #3 COMP #4
AREA(S) SERVED: OR Suite SYSTEM SERIAL #: 56635
SYSTEM TYPE: MEDICAL AIR SYSTEM MODEL: LSM-20DN-DCY-001
SYSTEM LOCATION: C109 SYSTEM MFR: Beacon
FACILITY CITY / STATE / ZIP: Charleston, SC Tanner Moore
FACILITY ADDRESS: 109 Bee St DATE OF SERVICE: 7/1/2026
FACILITY NAME: Ralph H. Johnson VA Medical CenterPROJECT ID: VA Charleston Preventative Maintenance
MEDICAL AIR RECIPROCATING COMPRESSOR
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
MEDICAL AIR RECIPROCATING COMPRESSOR
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
MUFFLER
DRYER #1 DRYER #2 DRYER #3 DRYER #4
OK OK
COMMENTS
None
FILTRATION INFO
MANUFACTURER
MODEL
SERIAL NUMBER No nameplate No nameplate
No nameplate No nameplate
SERIAL NUMBER
DRYER TYPE
DESSICANT MATERIAL COND.
DRYER SYSTEM INFO
MODEL
MANUFACTURER
LifeLine LifeLine
Beacon Beacon
No nameplate No nameplate
Dessicant Dessicant
DEW POINT UNIT READING
DEW POINT (AS MEASURED)
LOCAL ALARMS
RECEIVER SIGHT GLASS
OK VALVE LABELING OK
-13.6 PIPE LABELING OK
-13.5 AUTODRAIN OK
MANUAL DRAIN OK
SYSTEM CHECKLIST
ALTERNATION
PRE-FILTER AFTER-FILTER
Beacon Beacon
OK CO UNIT READING 0
OK CO CALIBRATION Yes
OK SYSTEM LABELING OK
PERFORMED BY:
COMMENTS
NFPA recommends replacing flexible connections (pigtails) every 5 years. Manufacture's tag with date is missing. Flexible connections are in functional condition.
OPERATIONAL / VISUAL INSPECTION OK
OK
PIPE LABELING OK
NFPA 99 COMPLIANCE OK
Local & Remote (Master
Alarm Panels)
CHANGE-OVER ACTUATION (PSI)
CHANGE-OVER ALARM
250 VALVE LABELING
Missing tag
4 SOURCE VALVE OK
250 SYSTEM LABELING OK
RIGHT BANK # OF CONNECTIONS
RIGHT # CONNECTIONS IN USE
RIGHT INTERMEDIATE PRESSURE
4 FLEXIBLE CONNECTORS DATE
PRV LINE (LABELING & LOCATION) OK
LEFT BANK # OF CONNECTIONS
1250 RESERVE ACTUATION (PSI) 250
4 LEAKS NO
LEFT BANK PRESSURE
LEFT # CONNECTIONS IN USE
LEFT INTERMEDIATE PRESSURE
RIGHT BANK PRESSURE 1600
CONTAINER/CYLINDER VALVES
SYSTEM CHECKLIST
MANIFOLD TYPE: (HP/LIQ) HP MANIFOLD MODEL: M2HD-D-HH-U-NIT
SYSTEM GAS: NITROGEN MANIFOLD SERIAL #: 20080915-I-A
AREA(S) SERVED: OR Suite
109 Bee St DATE OF SERVICE: 7/1/2026
FACILITY CITY / STATE / ZIP: Charleston, SC Tanner Moore
OK
250 HEADER BAR VALVES OK
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
NITROGEN MANIFOLD
FACILITY NAME: Ralph H. Johnson VA Medical CenterPROJECT ID: VA Charleston Preventative Maintenance
MANIFOLD LOCATION: 2 Fl Mechanical Manifold Room MANIFOLD MFR: Amico
FACILITY ADDRESS:
PERFORMED BY:
OPERATIONAL / VISUAL INSPECTION OK
COMMENTS
NFPA recommends replacing flexible connections (pigtails) every 5 years. Manufacture's tag with date is missing. Flexible connections are in functional condition.
CHANGE-OVER ALARM PIPE LABELING OK
NFPA 99 COMPLIANCE OK
Local & Remote (Master
Alarm Panels)
RIGHT INTERMEDIATE PRESSURE 150 SYSTEM LABELING OK
CHANGE-OVER ACTUATION (PSI) 150 VALVE LABELING OK
RIGHT BANK # OF CONNECTIONS 12 FLEXIBLE CONNECTORS DATE Missing Tag
RIGHT # CONNECTIONS IN USE 12 SOURCE VALVE OK
LEFT INTERMEDIATE PRESSURE 150 HEADER BAR VALVES OK
RIGHT BANK PRESSURE 200 PRV LINE (LABELING & LOCATION) OK
LEFT BANK # OF CONNECTIONS 12 LEAKS NO
LEFT # CONNECTIONS IN USE 12 CONTAINER/CYLINDER VALVES OK
SYSTEM CHECKLIST
LEFT BANK PRESSURE 750 RESERVE ACTUATION (PSI) 150
SYSTEM GAS: NITROUS OXIDE MANIFOLD SERIAL #: 20060831-O-A
AREA(S) SERVED: OR Suite
MANIFOLD TYPE: (HP/LIQ) HP MANIFOLD MODEL: M2HD-DHHH-U-N2O
FACILITY ADDRESS: 109 Bee St DATE OF SERVICE: 7/1/2026
FACILITY CITY / STATE / ZIP: Charleston, SC Tanner Moore
MANIFOLD LOCATION: C110 MANIFOLD MFR: Amico
MEDICAL GAS SOURCE SYSTEM PREVENTIVE MAINTENANCE
NITROUS OXIDE MANIFOLD
FACILITY NAME: Ralph H. Johnson VA Medical CenterPROJECT ID: VA Charleston Preventative Maintenance