Proposed Generator Plans Ladd and Sycamore.pdf
PDF 6 MB Posted
- Solicitation number
- 26-494DOT-FINAD-B-49168
- Issued by
- Dekalb County, Illinois
About this file
This document consists of proposed generator addition plans prepared by Prairie Engineers for the Illinois Department of Transportation (IDOT) covering two maintenance yard locations in Bureau County (Ladd) and DeKalb County (Sycamore). The project involves the installation of standby natural gas engine generator systems at both facilities to provide backup power during utility outages. At the Ladd Maintenance Yard, a 96KW/120KVA generator (GEN-1) will be installed with a 400A automatic transfer switch (ATS-1), while the Sycamore Maintenance Yard will receive a 60KW/75KVA generator (GEN-2) with a 225A automatic transfer switch (ATS-2). The scope of work includes installation of new electrical panels, conduit systems, grounding fields, concrete generator pads, and coordination with existing utility infrastructure. All trenching, excavation, backfill material, and surface material removal and replacement will be performed by IDOT staff. The contractor must complete all work within six weeks of beginning operations and provide minimum 14 days advance notice for any power shutdowns, which cannot exceed 24 hours in duration. No construction operations interrupting yard access shall occur during IDOT's winter operation schedule (November 1 through April 1).
The contractor is responsible for providing all generator and automatic transfer switch equipment with complete programming and appurtenances necessary for a fully functional standby system. IDOT will be responsible for removal and disposal of excavation material, while the contractor bears responsibility for removal and legal disposal of all electrical products and equipment. Utility coordination is required with Ameren Illinois for the Ladd facility (electric and gas service) and ComEd and Nicor for the Sycamore facility; Nicor has provided a quote of approximately $7,500 for gas service upgrades at Sycamore, and Ameren has quoted $7,500 for similar work at Ladd. The contractor must obtain all necessary licenses, permits, and inspections required by applicable jurisdictions and comply with the National Electrical Code (2023 Edition) and NFPA 70E standards. Prairie Engineers will provide periodic construction site observation visits and will be on-site during certain milestone events such as concrete work, gas/electric connections, and equipment startup, with the contractor providing minimum seven days notice of such milestone events.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| contract Ladd Sycamore~2.docx | DOCX document | |
| Proposed Generator Parts Lists Ladd and Sycamore.pdf | ||
| Sycamore Ladd IFB vendor-instructions-and-requirements~3.docx | DOCX document | |
| Blank vendor-disclosure-formerly-forms A~2.docx | DOCX document | |
| Blank ipg-active-registered-vendor-disclosure-formerly-forms B~2.docx | DOCX document | |
| Sycamore.Ladd IFB offer-to-the-state-of-illinois.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUREAU COUNTY
SPRING VALLEY, IL 61362
1525 N. AVE
LADD MAINTENANCE YARD
DEKALB COUNTY
SYCAMORE, IL 60178
351 E. PAGE ST.
SYCAMORE MAINTENANCE YARD
LOCATION MAP
LOCATION MAP
NOT TO SCALE
SECTION COUNTY
ILLINOIS
VARIOUS
TOTAL
SHEETS
SHEET
NO.RTE.
(011,032) ELE,EG,MG
F.A.
JO DAVIESS
WINNEBAGO
CARROLL
OGLE
BOONE MC HENRY LAKE
DE KALB
KANE
COOK
DU PAGE
WHITESIDE LEE
WILL
KENDALL
GRUNDY
LA SALLE
KANKAKEE
HENRY BUREAU
PUTNAM
ROCK ISLAND
MERCER
KNOX
H E
N D
E R
S O
N
STARK
MARSHALL
PEORIA
LIVINGSTON
IROQUOIS
FORD
MC LEANFULTONMC DONOUGH
WARREN
TAZEWELL
HANCOCK
ADAMS
SCHUYLER
BROWN
CASS
MASON
LOGAN
DE WITT
MENARD
CHAMPAIGN VERMILION
DOUGLAS
PIATT
MACON
SANGAMON
MORGAN
SCOTT
CHRISTIAN
PIKE
GREENE
JERSEY
MACOUPIN
C A
L H
O U
N
SHELBY
MOULTRIE
MONTGOMERY
COLES
EDGAR
CLARK
CUMBERLAND
JASPER CRAWFORD
EFFINGHAM
CLAY
RICHLAND LAWRENCE
WAYNE
E D
W A
R D
S
W A
B A
S H
BOND
FAYETTE
MARION
CLINTON
WASHINGTON
JEFFERSON
MADISON
ST. CLAIR
MONROE
RANDOLPH
PERRY
FRANKLIN
HAMILTON WHITE
SALINE GALLATIN
JACKSON
WILLIAMSON
JOHNSON POPE
HARDIN
MASSACPULASKI
A L E
X A
N D
E R
UNION
WOODFORD
STEPHENSON
CONTRACT NO.
LOCATION OF SECTION INDICATED THUS: -
STATE OF ILLINOIS
DEPARTMENT OF TRANSPORTATION
SUBMITTED 20
ENGINEER OF DESIGN AND ENVIRONMENT
PRINTED BY THE AUTHORITY
OF THE STATE OF ILLINOIS
DIRECTOR OF HIGHWAYS PROJECT IMPLEMENTATION
STATE OF ILLINOIS
DEPARTMENT OF TRANSPORTATION
FOR INDEX OF SHEETS, REFER TO SHEET NO. 2
PROPOSED
GENERATOR ADDITIONS
GENERATOR ADDITIONS
BUREAU AND DEKALB COUNTIES
50'
50'
50'
50'
10' 20' 30'
100'
100'
100'
100'
100' 200' 300'
1''= 20'
1''= 30'
1''= 40'
1''= 50'
1''= 10'
1''= 100'
FULL SIZE PLANS HAVE BEEN PREPARED USING STANDARD
ON REDUCED PLANS, THE ABOVE SCALES MAY BE USED.
ENGINEERING SCALES. REDUCED SIZED PLANS WILL NOT
CONFORM TO STANDARD SCALES. IN MAKING MEASUREMENTS
JOINT UTILITY LOCATION INFORMATION FOR EXCAVATION
J.U.L.I.E.
PROJECT ENGINEER:
PROJECT MANAGER:
REGIONAL ENGINEER
CONTRACT NO.
1-800-892-0123
OR 811
VARIOUS MAINTENANCE YARDS
(011, 037) ELE, EG, MG SECTION
N/A 8
NOT TO SCALE
Expires: 11/30/2025
Date: 5/1/2025
Copyright Prairie Engineers, P.C. 2022 professional design firm no. 184-005965 www.prairieengineers.com
J JUNCTION BOX
DISCONNECT SWITCH
SURFACE MOUNTED PANEL AND CABINET
E ELECTRIC METER
T TRANSFORMER
ATS AUTOMATIC TRANSFER SWITCH
PNL.
SCH
SW
PANEL
SWITCH
SCHEDULE
ELECTRICAL ABBREVIATION LIST
GROUND FAULT CIRCUIT INTERRUPTER
EXIST.
IN.
MIN
N
GFI
GND
SYMBOL
A
INCHES
NEUTRAL
MINIMUM
EXISTING
GROUND
DESCRIPTION
AMP
CONDUITC.
TYP. TYPICAL
STOR STORAGE
CKT CIRCUIT
KW KILOWATT
PP-X POWER PANEL
I.G. ISOLATED GROUND
RECEPT. RECEPTACLE
V VOLT
PVC POLY VINYL CHLORIDE
A.T.S. AUTOMATIC TRANSFER SWITCH
ETCETERAETC.
HZ HERTZ
VERT. VERTICAL
A.F.F. ABOVE FINISHED FLOOR
A/E ARCHITECT/ENGINEER
CENTER/CENTERC/C
HP HORSE POWER
RIGID METAL CONDUITRMC
APPROX. APPROXIMATELY
ACCESS ACCESSIBLE
ARCH. ARCHITECT/ARCHITECTURAL DRAWINGS
ELECT. ELECTRIC
EER ENERGY EFFICIENCY RATING
EFF EFFICIENCY
ELEV. ELEVATION
EXTERNAL STATIC PRESSUREESP
FULL LOAD AMPSFLA
GA GAUGE
FT FEET
GALV. GALVANIZED
GEN-X GENERATOR
INT. INTEGRAL
LRA LOCKED ROTOR AMPS
MANUF. MANUFACTURER
MAX. MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
RE: REFERENCE
REC. RECEPTACLE
REQ'D REQUIRED
RATED LOAD AMPSRLA
QTY QUANTITY
REVOLUTIONS PER MINUTERPM
TEMP. TEMPERATURE
TRANS. TRANSFER
WITH WITH
WP WATER PROOF
EXISTING OVERHEAD ELECTRICAL
UNDERGROUND ELECTRICAL TO BE REMOVED
PROPOSED UNDERGROUND ELECTRICAL/EXISTING
EXISTING UNDERGROUND ELECTRICAL
FIRE HYDRANT
MANHOLE
POWER POLE
GAS METER
EXISTING UNDERGROUND SANITARY
G
SYMBOL DESCRIPTION
INDEX OF SHEETS
UTILITY INFORMATION
GRSC GALVANIZED RIGID STEEL CONDUIT
#P 1P-SINGLE POLE, 2P-DOUBLE POLE, ETC
#PH 1PH-SINGLE PHASE, 3PH-THREE PHASE, ETC
XHHW HIGH HEAT-RESISTANT WATER-RESISTANT POLYETHYLENE
THWN THERMOPLASTIC HEAT & WATER RESISTANT NYLON COATED
ELECTRIC METALLIC TUBE CONDUIT EMT
(815)343-8303 athompson4@ameren.com
ELECTRIC/GAS: AMEREN ILLINOIS
LADD IDOT YARD;
OVERHEAD ELECTRCAL TO BE REMOVED
PROPOSED OVERHEAD ELECTRICAL/EXISTING
GENERAL NOTES:
ALL GRASS AREAS THAT ARE DISTURBED SHALL BE FINISH GRADED, FERTILIZED, SEEDED AND MULCHED.29.
ALL DAMAGE TO EXISTING PAVED OR UNPAVED SURFACES NOT IN THE SCOPE OF WORK SHALL BE REPAIRED TO THE SATISFACTION OF I.D.O.T., AT THE CONTRACTOR'S EXPENSE. 28.
WORK AT EACH RESPECTIVE PROJECT/JOB SITE.
CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, AND INSPECTIONS REQUIRED BY RESPECTIVE AUTHORITY OF JURISDICTION AND THE RESPECTIVE LAWS, ORDINANCES, AND RULES FOR THE ELECTRICAL 27.
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE TEMPORARY POWER AS REQUIRED TO COMPLETE THE WORK.26.
CONDUCTOR FROM BUSHING TO GROUND BUS IN THE RESPECTIVE SERVICE ENTRANCE EQUIPMENT OR OTHER DEVICE.
PROVIDE GROUNDING BUSHINGS AT ALL CONDUITS ENTERING SERVICE ENTRANCE EQUIPMENT (METER BASES, SERVICE DISCONNECTS, SERVICE PANELBOARDS, ETC.) AND THE TRANSFER SWITCH WITH BONDING 25.
DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
MAXIMUM AVAILABLE FAULT CURRENT PER NEC 408.6 "SHORT CIRCUIT CURRENT RATING". THE FIELD MARKING SHALL INCLUDE THE DATE THE FAULT CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT
INCLUDE FIELD MARKING TO IDENTIFY THE MAXIMUM AVAILABLE FAULT CURRENT AS REQUIRED BY NEC 110.24 "AVAILABLE FAULT CURRENT". THE SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
PROVIDE OVER CURRENT PROTECTIVE DEVICE COORDINATION STUDY AND APPROPRIATE LABELS ON ELECTRICAL EQUIPMENT AT THE LADD AND SYCAMORE MAINTENANCE YARDS. EACH SERVICE DISCONNECT SHALL 24.
EACH SERVICE DISCONNECT SHALL BE IDENTIFIED IN ACCORDANCE WITH NEC 230.70 (B) "MARKING".23.
COORDINATE INSTALLATIONS AND ELECTRICAL WORK WITH THE EXISTING CONDITIONS, BUILDING LAYOUT, CONCRETE WORK, SITE WORK, AND ALL OTHER TRADES.22.
LIGHTING, RECEPTACLES, OR OTHER DEVICE.
REMOVING, DISCONNECTING, WORKING ON, RELOCATING, CONNECTING, OR RECONNECTING THE SERVICE EQUIPMENT, DISTRIBUTION EQUIPMENT, SAFETY SWITCH, LOAD CENTER, PANELBOARD, CIRCUIT BREAKER, FUSES, EXAMINE THE SITE TO DETERMINE THE EXTENT OF THE WORK. CONTRACTOR SHALL FIELD VERIFY EXISTING SITE CONDITIONS. CONTRACTOR SHALL VERIFY RESPECTIVE CIRCUITS AND POWER SOURCES PRIOR TO 21.
ELECTRICAL SERVICE AND DISTRIBUTION EQUIPMENT LOCATED OUTDOORS OR IN WET LOCATIONS SUBJECT TO CORROSION SHALL BE IN NEMA 3R STAINLESS STEEL ENCLOSURE, UNLESS OTHERWISE NOTED.20.
GREATER THAN THE AVAILABLE FAULT CURRENT.
SHALL ALSO BE SIZED PER THE ENGINE GENERATOR SET MANUFACTURER'S WRITTEN RECOMMENDATION FOR THE RESPECTIVE SET FURNISHED. AUTO TRANSFER SWITCH SHALL HAVE WITHSTAND AND CLOSING RATING, SERVICE BREAKER AND THE GENERATOR BREAKER SHALL BE SELECTED AND COORDINATED TO MAINTAIN THE WITHSTAND AND CLOSING RATING OF THE RESPECTIVE AUTO TRANSFER SWITCH. GENERATOR BREAKER 19.
ENLARGE OR IN-FILL EXISTING WALL OPENING FROM ALL REMOVED PANELS AS REQUIRED TO MAINTAIN FINISHED APPEARANCE AROUND NEW PANEL INSTALLATIONS.18.
SOURCE PER THE REQUIREMENTS OF NEC 408.4 (B) SOURCE OF SUPPLY.
PROVIDE EACH NEW AND EXISTING PANELBOARD WITH A LEGEND PLATE THAT IDENTIFIES THE COLOR CODING SYSTEM FOR THE POWER WIRING CORRESPONDING TO THE RESPECTIVE VOLTAGE SYSTEM AND ITS POWER 17.
PROVIDE ALL RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, DISCONNECT SWITCHES, CIRCUIT BREAKERS, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM AND AS SPECIFIED.16.
JUMPER OF INTERNAL EQUIPMENT GROUNDING CONDUCTOR PER NEC 350.60. DO NOT INSTALL LTFMC THAT IS NOT U.L. LISTED. CONFIRM LTFMC BEARS THE U.L. LABEL PRIOR TO INSTALLATION.
THE REQUIREMENTS OF NEC 350.60. LIQUID TIGHT FLEXIBLE METAL CONDUIT THAT IS USED FOR FLEXIBILITY (INCLUDING CONNECTIONS TO ENGINE GENERATORS & TRANSFORMERS) SHALL REQUIRE AN EXTERNAL BONDING
LTFMC DENOTES LIQUID TIGHT FLEXIBLE METAL CONDUIT U.L. LISTED, SUNLIGHT RESISTANT & SUITABLE FOR GROUNDING. LIQUID TIGHT FLEXIBLE METAL CONDUIT AND ASSOCIATED FITTINGS SHALL BE U.L. LISTED TO MEET 15.
COMPLY WITH THE APPLICABLE REQUIREMENTS OF NFPA 70E - STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE.14.
KEEP A COPY OF THE PLANS, SPECIFICATIONS, INCLUDING ADDENDA, COPIES OF ANY CHANGE ORDERS, AND A COPY OF THE LATEST NEC (2023 EDITION) IN FORCE ON SITE ALWAYS DURING CONSTRUCTION.13.
COORDINATE THE UTILITY CONNECTION REQUIREMENTS WITH AMEREN & COMED RESPECTFULLY. REFER TO CONTACT INFORMATION ON THIS SHEET.12.
PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS, PER THE REQUIREMENTS OF NEC 110.16 "FLASH PROTECTION".
FURNISH AND INSTALL A WEATHERPROOF WARNING LABEL FOR EACH NEW AND EXISTING SERVICE DISCONNECT, SAFETY SWITCH, PANELBOARD AND LOAD CENTER AT LADD AND SYCAMORE MAINTENANCE YARDS TO WARN 11.
DISPOSAL OF ALL EXCAVATION MATERIAL.
CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL, HAULING, AND LEGAL DISPOSAL OF ALL ELECTRICAL PRODUCTS, EQUIPMENT AND MATERIAL. I.D.O.T. SHALL BE RESPONSIBLE FOR REMOVAL, HAULING AND LEGAL 10.
GREENGROUND
GREENGROUND WHITENEUTRAL
WHITENEUTRAL BLUEPHASE C
REDPHASE BORANGEPHASE B
BLACKPHASE A BLACKPHASE A
240/120 VAC, 1 PHASE, 3 WIRE240/120 VAC, 3 PHASE, 4 WIRE
INSULATION FOR NO.6 AWG AND SMALLER TO MEET THE REQUIREMENTS OF NEC 200.6 STANDARD COLORS FOR POWER WIRING AND BRANCH CIRCUITS SHALL BE AS FOLLOWS:
LARGER. INSULATED GROUND CONDUCTORS SHALL HAVE GREEN COLORED INSULATION FOR ALL CONDUCTORS AWG AND/OR KCMIL TO COMPLY WITH NEC 250.119. NEUTRAL CONDUCTORS SHALL HAVE WHITE COLORED
COLOR CODE PHASE AND NEUTRAL CONDUCTOR INSULATION FOR N0.6 AWG OR SMALLER. PROVIDE COLORED INSULATION OR COLORED MARKING TAPE FOR PHASE AND NEUTRAL CONDUCTORS FOR NO.4 AWG AND 9.
APPLICATION. ANY INSTALLATIONS WHICH VOID THE UL LISTING, INTERTEK TESTING SERVICES VERIFICATION/ETL LISTING, FM APPROVAL, OR THE MANUFACTURERS WARRANTY WILL NOT BE PERMITTED.
LAWS, ORDINANCES, AND REQUIREMENTS IN FORCE. ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN CONFORMANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN DIRECTIONS AND RECOMMENDATIONS FOR THE
MANNER, TO THE SATISFACTION OF THE A/E. ALL ELECTRICAL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE NFPA 70-NATIONAL ELECTRICAL CODE (NEC) 2023 EDITION, AND ALL OTHER APPLICABLE LOCAL CODES, PLANS. PROVIDE EXPERIENCED, QUALIFIED, AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE
CONTRACTOR SHALL FURNISH AND INSTALL MATERIALS NECESSARY FOR COMPLETE AND FULLY FUNCTIONAL INSTALLATION OF THE ELECTRICAL EQUIPMENT AND MATERIALS, AS SPECIFIED HEREIN AND AS SHOWN ON THE 8.
PROVIDE NEW TYPED CIRCUIT DESCRIPTIONS ON THE PANEL INDEX CARD FOR PANELS AS INDICATED ON THE PANEL SCHEDULES. ANY ALTERATIONS TO EXISTING PANELS MUST BE REFLECTED ON THE PANEL INDEX CARD.7.
IN LOCATING UNDERGROUND CABLES OR UTILITIES AT THE FACILITIES, COORDINATE WORK WITH ALL ABOVE GROUND UTILITIES.
LINES SHALL BE LOCATED BY THE RESPECTIVE UTILITY. CONTACT J.U.L.I.E. (JOINT UTILITY LOCATION INFORMATION FOR EXCAVATORS) FOR UTILITY INFORMATION. ALSO CONTACT THE OWNER PERSONNEL FOR ASSISTANCE
IMMEDIATELY NOTIFIED. ANY DAMAGE TO SUCH MAINS AND SERVICES SHALL BE RESTORED TO SERVICE AT ONCE AND PAID FOR BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACT. ALL UTILITY CABLES AND
IS ENCOUNTERED DURING CONSTRUCTION, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE UTILITY COMPANY OF JURISDICTION. THE OWNER'S REPRESENTATIVE AND/OR THE RESIDENT ENGINEER SHALL ALSO BE
ASSISTANCE RELATIVE TO THE LOCATION OF THEIR FACILITIES AND THE WORKING SCHEDULE OF THE COMPANIES FOR REMOVAL OR ADJUSTMENT, WHERE REQUIRED. IN THE EVENT AN UNEXPECTED UTILITY INTERFERENCE
UTILITIES. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL NOTIFY THE UTILITY COMPANIES OF HIS OPERATIONAL PLANS, AND SHALL OBTAIN, FROM THE RESPECTIVE UTILITY COMPANIES, DETAILED INFORMATION AND
ENCOUNTERED IN THE CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ACTUAL LOCATION OF ALL SUCH FACILITIES INCLUDING SERVICE CONNECTIONS TO THE UNDERGROUND
OF THE INFORMATION. THERE IS NO GUARANTEE, EITHER EXPRESS OR IMPLIED, THAT THE LOCATIONS, SIZE, AND TYPE OF MATERIAL EXISTING UNDERGROUND UTILITIES INDICATED ARE REPRESENTATIVE OF THOSE TO BE
NOT REPRESENTED AS ACCURATE, SUFFICIENT, OR COMPLETE. NEITHER THE OWNER NOR THE ENGINEER ASSUMES ANY RESPONSIBILITY WHATSOEVER IN RESPECT TO THE ACCURACY, COMPLETENESS, OR SUFFICIENCY
CONTRACTOR SHALL LOCATE EXISTING UNDERGROUND UTILITIES AND CABLES. THE LOCATION, SIZE, AND TYPE OF MATERIAL OF EXISTING UNDERGROUND AND/OR ABOVEGROUND UTILITIES INDICATED ON THE PLANS ARE 6.
CONTRACTOR CONSTRUCTION OPERATIONS OR VEHICLES SHALL NOT BLOCK ACCESS TO THE YARD OR BUILDINGS.5.
MORE THAN ONE PANEL OUT OF OPERATION AT A TIME. POWER SHUT-DOWN SHALL NOT BE GREATER THAN 24 HOURS.
PREVENT ISSUES. ALL PERSONNEL SHALL FOLLOW SAFE PRACTICES PUT FORWARD BY THE U.S. DEPARTMENT OF LABOR OCCUPATIONAL SAFETY & HEATH ADMINISTRATION (OSHA). WHEN REPLACING PANELS, DO NOT TAKE
DURING YARD OFF HOURS OR WEEKENDS TO MINIMIZE THE IMPACT ON YARD DAY TO DAY OPERATIONS AND SHALL BE KEPT TO A MINIMUM DURATION. ONCE SHUTDOWN, THE CIRCUITS SHALL BE LABELED AS SUCH TO
COORDINATE WORK AND ANY POWER OUTAGES (GENERATOR/ATS TIE-IN OR PANEL REPLACEMENT) WITH THE I.D.O.T. REPRESENTATIVE, PROVIDE A MINIMUM OF 14 DAYS ADVANCED NOTICE. ALL SHUTDOWNS SHALL OCCUR 4.
OF BEGINNING WORK.
CONTRACTOR SHALL HAVE ALL EQUIPMENT AND SUPPLIES ON HAND PRIOR TO BEGINNING WORK AT EACH YARD. ALL WORK SHALL BE COMPLETED AND THE GENERATORS/PANELS SHALL BE OPERATIONAL WITHIN 6 WEEKS 3.
NO CONSTRUCTION OPERATIONS INTERRUPTING MAINTENANCE YARD ACCESS SHALL OCCUR DURING I.D.O.T. WINTER OPERATION SCHEDULE (NOVEMBER 1 THROUGH APRIL 1).2.
SUPERVISOR A MINIMUM OF 14 DAYS IN ADVANCE OF TRENCHING/EXCAVATION NEEDS.
INSTALLATION OF CONCRETE PADS, CONDUITS, GROUNDING FIELDS, PULL BOXES, BOLLARDS, ETC. WITH I.D.O.T. ALL TRENCHING/EXCAVATION REQUIREMENTS SHALL BE COORDINATED WITH EACH I.D.O.T. YARD
ALL SURFACE MATERIAL REMOVAL/REPLACEMENT, EXCAVATION, TRENCH EXCAVATION, BACKFILL MATERIAL, COMPACTION AND DISPOSAL SHALL BE THE RESPONSIBILITY OF I.D.O.T. CONTRACTOR SHALL COORDINATE 1.
1-888-642-6748
GAS:NICOR
224-890-3367
Michael.Adams@Comed.com
ELECTRIC: COMED
SYCAMORE IDOT YARD;
FLAG POLE
ABANDONED UNDERGROUND ELECTRIC
8 - ELECTRICAL DETAILS
7 - PANEL SCHEDULES
6 - ONE LINE DIAGRAMS - LADD MAINTENANCE YARD
5 - ONE LINE DIAGRAMS - SYCAMORE MAINTENANCE YARD
4 - ELECTRCIAL SITE PLAN - LADD MAINTENANCE YARD
3 - ELECTRICAL SITE PLAN - SYCAMORE MAINTENANCE YARD
2 - INDEX OF SHEETS, GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
1 - COVER SHEET
EXISTING UNDERGROUND DOMESTIC WATER
EXISTING UNDERGROUND GAS
EXISTING UNDERGROUND TELEPHONE LINE
SYMBOLS LIST
PULL BOX
EMERGENCY SHUT-DOWN SWITCH
GENSET ANNUNCIATOR PANEL
E
SECTION COUNTY
ILLINOIS
TOTAL
SHEETS
SHEET
NO.RTE.
(011,037) ELE,EG,MG
USER NAME =
PLOT DATE = DATE
DESIGNED
CHECKED
DRAWN
REVISED
REVISED
REVISED
REVISED
F.A.
SHEET 2 OF 8 SHEETS STA. TO STA.
CWB
5/1/2025
SCALE: NO SCALE
STATE OF ILLINOIS
DEPARTMENT OF TRANSPORTATION
INDEX OF SHEETS, GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
I:
\J o b s \2
\1
.2
.0
O
P S
W O
-3
L a d d a n d S y c a m o re
G e n e ra to rs
\D ra w in g s \S h e e t\
.d g n
F
IL
E N
A M
E
.1
-6
S h e e t]
M O
D E
L jmasset
4/24/2025
8 2
N/A VARIOUS
Date: 5/1/2025
A professional design firm no. 184-005965 www.prairieengineers.com
Copyright Prairie Engineers of Illinois, P.C. 2023
Columbia, IL 62236
(217) 605-0403
404 N. Main Street
Prairie Engineers, P.C.
KEYED NOTES:
REQUIRED FOR REPLACEMENT/INSTALLATION OF PANEL "C".
RELOCATE EXISTING ELECTRICAL DEVICES AND CIRCUITRY AS FOR BREAKER REQUIREMENTS.
REFER TO PANEL SCHEDULE ON SHEET 7 TO RECONNECT EXISTING BRANCH CIRCUITRY TO REMAIN.
PROVIDE BREAKERS AS REQUIRED AND #8 GROUND IN 1-1/4” CONDUIT FROM PANEL “A” TO PANEL "C".
PROVIDE 100A, 240/120VAC, 3ϕ, 4W, NEMA 1, 42 CIRCUIT MAIN LUG POWER PANEL “C”. PROVIDE (4) #3
SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS.
REFER TO PANEL BREAKERS AS REQUIRED TO RECONNECT EXISTING BRANCH CIRCUITRY TO REMAIN.
PROVIDE BREAKER. PROVIDE (4) #3 AND #8 GROUND IN 1-1/4” CONDUIT FROM PANEL “A” TO PANEL "B".
PROVIDE 100A, 240/120VAC, 3ϕ, 4W, NEMA 1, 20 CIRCUIT POWER PANEL “B” WITH 100 AMP MAIN
.REPLACEMENT/INSTALLATION OF PANEL "A"
RELOCATE EXISTING ELECTRICAL DEVICES AND CIRCUITRY AS REQUIRED FOR
REFER TO PANEL SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS. CIRCUITRY TO REMAIN.
PRACTICAL, AT 4'-0" INTERVALS. PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING BRANCH
MOUNT CONDUIT, ABOVE GRADE, SECURELY TO BUILDING 205, AS HIGH AS (ATS-2) TO PANEL "A".
BREAKER. PROVIDE (4) #4/0 AND #2 GROUND IN 2-1/2” CONDUIT FROM AUTOMATIC TRANSFER SWITCH PROVIDE 225A, 240/120VAC, 3ϕ, 4W, NEMA 1, 30 CIRCUIT POWER PANEL “A” WITH 225 AMP MAIN
SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS.
REFER TO PANEL BREAKERS AS REQUIRED TO RECONNECT EXISTING BRANCH CIRCUITRY TO REMAIN.
TRENCHING, BACKFILL MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T. PROVIDE GFCI
PENETRATION WITH NON-SHRINK GROUT AND MAKE WATER/WEATHER TIGHT. COORDINATE
SEAL ANNULAR SPACE AROUND CONDUIT CONDUIT BELOW GRADE FROM PANEL “C” TO PANEL "D".
BREAKER SECURELY FASTENED TO EXTERIOR OF BUILDING. PROVIDE (3) #3 AND #8 GROUND IN 1-1/4” PROVIDE 100A, 240/120VAC, 1ϕ, 3W, NEMA 3R, 20 CIRCUIT POWER PANEL “D” WITH 100 AMP MAIN
EXISTING CONDENSING UNIT, REFRIGERANT PIPING AND WIRING TO REMAIN.
EXISTING ANTENNA TOWER TO REMAIN.
EXISTING POWER POLE TO REMAIN.
EXISTING OVERHEAD ELECTRICAL CONDUCTORS TO REMAIN.
EXISTING GATE AND FENCE TO REMAIN.
EXISTING ROCK STORAGE TO REMAIN.
EXISTING FENCE TO REMAIN.
EXISTING MANHOLE AND SEPTIC TANK TO REMAIN.
EXISTING CONCRETE PAD TO REMAIN.
EXISTING ASPHALT PAVEMENT TO REMAIN.
EXISTING GRASS AREA TO REMAIN.
EXISTING FLAG POLE TO REMAIN.
EXISTING WATER TANKS TO REMAIN.
EXISTING FUEL ISLAND TO REMAIN.
EXISTING NATURAL GAS SERVICE/METER AND PRESSURE REGULATOR TO REMAIN.
EXISTING ELECTRICAL METER AND METER BASE TO REMAIN.
EXISTING POLE MOUNTED 50 KVA TRANSFORMER TO REMAIN.
X
DEMOLITION NOTES:
GENERATOR EQUIPMENT PROVIDED.
BY I.D.O.T. BASED UPON THE SIZE REQUIREMENTS OF THE ACTUAL
ITS ENTIRETY. VERIFY EXACT LIMITS OF PAVEMENT TO BE REMOVED
SUB-BASE MATERIAL IN A 9' +/- X 5' +/- RECTANGLE AND REMOVE IN
EXISTING ASPHALT PAVEMENT AND I.D.O.T. STAFF SHALL SAW CUT
RECONNECTED TO NEW PANEL BREAKERS.
“B”, "C" AND “D”. EXISTING BRANCH CIRCUITRY TO REMAIN AND BE
EXISTING PANELS AND FEEDER CIRCUITRY TO PANELS “A”, REMOVE
X
NOTES:
T
E ATS
GENERATOR SYSTEM
REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL STAND BY
EQUIPMENT, PROGRAMMING AND APPURTENANCES AS
CONTRACTOR SHALL PROVIDE ALL GENERATOR/ATS 8.
AT SYCAMORE MAINTENANCE YARD.
STUDY AND APPROPRIATE LABELS ON ELECTRICAL EQUIPMENT
PROVIDE OVER CURRENT PROTECTIVE DEVICE COORDINATION 7.
INFORMATION.
UTILITY LOCATION INFORMATION FOR EXCAVATORS) FOR UTILITY
RESPECTIVE UTILITY CONTRACTOR. CONTACT J.U.L.I.E. (JOINT
ALL UTITLITY CABLES AND LINES SHALL BE LOCATED BY THE 6.
REFER TO SHEET 2 FOR GENERAL NOTES AND SYMBOLS LIST.5.
SHALL NOT BLOCK ACCESS TO THE YARD OR BUILDINGS.
CONTRACTOR CONSTRUCTION OPERATIONS OR VEHICLES 4.
SHUT-DOWN SHALL NOT BE GREATER THAN 24 HOURS.
YARD SUPERVISOR A MINIMUM OF 14 DAYS IN ADVANCE. POWER
SHALL BE COORDINATED AND PRE-APPROVED BY THE I.D.O.T.
REPLACEMENT FOR ANY PORTION OF THE ELECTRICAL SYSTEM
ALL TEMPORARY POWER SHUT-DOWN FOR SYSTEM TIE-IN OR 3.
OPERATION SCHEDULE (NOVEMBER 1 THROUGH APRIL 1)
YARD ACCESS SHALL OCCUR DURING I.D.O.T. WINTER
NO CONSTRUCTION OPERATIONS INTERRUPTING MAINTENANCE 2.
OF 14 DAYS IN ADVANCE,
COORDINATED WITH THE I.D.O.T. YARD SUPERVISOR A MINIMUM
I.D.O.T. ALL TRENCHING/EXCAVATION REQUIREMENTS SHALL BE
CONDUITS, GROUND FIELDS, PULL BOXES, BOLLARDS, ETC. WITH
BE BY I.D.O.T. COORDINATE INSTALLATION OF CONCRETE PADS,
TRENCH EXCAVATION, BACKFILL MATERIAL AND COMPACTION TO
ALL SURFACE MATERIAL REMOVAL/REPLACEMENT, EXCAVATION, 1.
DOME TO REMAIN
EXISTING SALT
TO REMAIN
EXISTING BUILDING 206
TO REMAIN
EXISTING BUILDING 205
SHED TO REMAIN
EXISTING STORAGE
TO REMAIN
EXISTING BUILDING 205
SCALE:
1" = 30'
ELECTRICAL SITE PLAN - SYCAMORE MAINTENANCE YARD
PNL "D"
PNL "C"
PNL "A"
PNL "B"
G
22 24
E. PAGE ST.
N . W
A
LN
U T
S T.
151515 14
MOUNTING LOCATIONS OF ANNUNCIATOR AND SHUT-DOWN SWITCH.
INSTRUCTIONS. COORDINATE WITH I.D.O.T. FIELD REPRESENTITIVE AND YARD SUPERVISOR FOR EXACT PROVIDE ANNUNCIATOR AND SHUT-DOWN SWITCH WIRING, INSTALLED PER MANUFACTURER'S WRITTEN
PROVIDE GENSET REMOTE ANNUNCIATOR PANEL AND GENSET EMERGENCY SHUT-DOWN SWITCH.
REFER TO DETAIL 1 THIS SHEET FOR CONTINUATION.
AT 4'-0" INTERVALS.
INSTRUCTIONS. MOUNT CONDUITS SECURELY TO BUILDING 205, AS HIGH ON BUILDING AS PRACTICAL, SYSTEM. PROVIDE QUANTITY OF CONDUIT/CONDUCTORS PER MANUFACTURER'S WRITTEN
INSTRUCTIONS FROM AUTOMATIC TRANSFER SWITCH (ATS-2) TO GENREATOR (GEN-2) FOR CONTROL
PROVIDE CONTROL WIRING IN 1" CONDUIT OR AS REQUIRED PER MANUFACTURER'S WRITTEN
PRACTICAL, AT 4'-0" INTERVALS.
WRITTEN INSTRUCTIONS. MOUNT CONDUITS SECURELY TO BUILDING 205, AS HIGH ON BUILDING AS
PROVIDE BREAKERS, CONDUCTORS AND CONDUITS FOR EACH CIRCUIT PER MANUFACTURER'S
REQUIRED PER MANUFACTURER'S WRITTEN REQUIREMENTS FROM PANEL "C" TO GENERATOR (GEN-2).
PROVIDE MAINTENANCE CIRCUITS IN 1" CONDUIT (ENGINE BLOCK HEATER, BATTERY CHARGER, ETC.) AS
EXISTING AIR COMPRESSOR DISCONNECT TO REMAIN.
REQUIREMENTS.
COMPRESSOR DISCONNECT IN BUILDING 206. REFER TO PANEL SCHEDULE ON SHEET 7 FOR BREAKER PROVIDE 50 AMP, 2-POLE BREAKER AND (3) #8 AND #10 GROUND IN 1" CONDUIT FROM PANEL "D" TO AIR
EXISTING UNDERGROUND SANITARY PIPING TO REMAIN.
EXISTING UNDERGROUND GAS LINE TO REMAIN.
EXISTING UNDERGROUND DOMESTIC WATER LINE TO REMAIN.
EXCAVATION REQUIREMENTS WITH I.D.O.T.
PROVIDE BOLLARDS. REFER TO DETAIL 3 ON SHEET 8 FOR ADDITIONAL INFORMATION. COORDINATE
BUILDING AS PRACTICAL, AT 4'-0" INTERVALS.
AUTOMATIC TRANSFER SWITCH (ATS-2). MOUNT CONDUIT SECURELY TO BUILDING 205, AS HIGH ON PROVIDE (4) #4/0 AND #2 GROUND IN 2-1/2” CONDUIT ABOVE GRADE FROM GENERATOR (GEN-2) TO
LOCATION.
TRANSFER SWITCH WITH COMED REGARDING TRANSFER SWITCH REQUIREMENTS, INSTALLATION, AND
COORDINATE INSTALLATION OF FROM DISCONNECT SWITCH TO AUTOMATIC TRANSFER SWITCH.
MOUNTED TO BUILDING EXTERIOR. PROVIDE (4) #4/0 AND #2 GROUND IN 2-1/2” CONDUIT ABOVE GRADE PROVIDE NEMA 3R, 225A, 240/120VAC, 3ϕ, 4W, 4-POLE AUTOMATIC TRANSFER SWITCH (ATS-2) SECURELY
GENERATOR PAD INFORMATION.
REFER TO DETAIL 4 ON SHEET 8 FOR ADDITIONAL COORDINATE PAD WITH BOLLARD INSTALLATION.
EQUIPMENT PROVIDED, PAD SHALL EXTEND 1'-0" BEYOND LIMITS OF EQUIPMENT IN ALL DIRECTIONS.
MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T. COORDINATE PAD DIMESIONS WITH ACTUAL GENERATOR PAD. COORDINATE SURFACE MATERIAL REMOVAL, EXCAVATION, TRENCHING, BACKFILL FOR TEMPORARY GAS SERVICE DISCONNECTION. PROVIDE 9' +/- X 5' +/- X 6" THICK CONCRETE PROVIDE STRAINER AND SHUT-OFF VALVE IN GAS PIPING TO GENERATOR. COORDINATE WITH NICOR SERVICE PIPING. CONTRACTOR TO FIELD VERIFY SIZE OF EXISTING NATURAL GAS SERVICE PIPING.
(COORDINATE REQUIREMENTS WITH ACTUAL EQUIPMENT INSTALLED) TO EXISTING 2" NATURAL GAS
HOUSING. PROVIDE FITTINGS AS REQUIRED TO CONNECT NEW 2" GAS FEED FOR GENERATOR
PROVIDE 60KW/75KVA STANDBY NATURAL GAS ENGINE GENERATOR (GEN-2) IN WEATHERPROOF
MOUNTED SECURELY TO BUILDING EXTERIOR FROM EXISTING METER BASE TO DISCONNECT SWITCH.
SECURELY MOUNTED TO BUILDING EXTERIOR. PROVIDE (4) #4/0 AND #2 GROUND IN 2-1/2" CONDUIT PROVIDE 400A, NEMA 3R, HEAVY-DUTY SERVICE RATED FUSED DISCONNECT SWITCH (FUSED AT 225A), 22
"4'-0"
4'-0"
2'-0"
(TYP.)26
SCALE:
1" = 10'
ENLARGED GENSET PLAN
TO REMAIN
EXISTING BUILDING 205
4'-0"
E 35
AS REFERENCE ONLY.
$7,500.00 TO COMPLETE THE WORK. THIS QUOTE IS BEING PROVIDED
PROJECT. NICOR HAS QUOTED TO THE ENGINEER APPROXIMATELY
THE UTILITY WORK IS DONE IN SUCH A MANNER AS TO NOT DELAY THE
CONTRACTOR WILL ASSUME THE RESPONSIBILITY TO ENSURE THAT
COMPANY WILL BE PAID IN FULL BY THE CONTRACTOR. THE
WITH THE UTILITY COMPANY. CHARGES REQUIRED BY THE UTILITY
SCHEDULE THE UPGRADE OF THE GAS SERVICE TO THE BUILDING
THE CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH AND
NOTE:
UTILITY INFORMATION
1-888-642-6748
GAS:NICOR
224-890-3367 Michael.Adams@Comed.com
ELECTRIC: COMED
SYCAMORE IDOT YARD
608-4255) FOR MILESTONE EVENT COORDINATION.
DAYS NOTICE OF MILESTONE EVENTS. CONTACT BILL WHITLOW (217-
CONTRACTOR SHALL PROVIDE PRAIRIE ENGINEERS A MINIMUM OF 7
GAS/ELECTRIC CONNECTIONS, EQUIPMENT STARTUP, ETC.).
AND AT CERTAIN MILESTONE EVENTS (CONCRETE WORK,
DOCUMENTS. PRAIRIE ENGINEERS WILL BE ON SITE PERIODICALLY
WORKMANSHIP ARE IN ACCORDANCE WITH THE CONTRACT
CONSTRUCTION SCHEDULE AND THAT THE MATERIALS, FINISHES AND
WORK IS PROGRESSING IN ACCORDANCE WITH THE APPROVED
THE WORK BEING PERFORMED TO DETERMINE, IN GENERAL, THAT THE
OBSERVATION VISITS TO REPORT ON THE PROGRESS AND QUALITY OF
PRAIRIE ENGINEERS WILL PROVIDE CONSTRUCTION SITE
CONSTURCTION INSPECTION:
SHEET
NO.RTE.
USER NAME =
PLOT DATE = DATE
DESIGNED
CHECKED
DRAWN
REVISED
REVISED
REVISED
REVISED
F.A.
SHEET 3 OF 8 SHEETS STA. TO STA.
CWB
5/1/2025
SCALE: 1" = 30'
STATE OF ILLINOIS
ELECTRICAL SITE PLAN - SYCAMORE MAINTENANCE YARD
o b s \2
\1
.2
.0
O
P S
W O
-3
L a d d a n d S y c a m o re
G e n e ra to rs
\D ra w in g s \S h e e t\ .d g n
F
IL
E N
A M
.2
S h e e t]
M O
D E
L cbozarth
4/29/2025
8 3
(011,037) ELE,EG,MG DEKALB
30'-0"15'-0"0
Date: 5/1/2025
E
A
N/A
Copyright Prairie Engineers of Illinois, P.C. 2023
Columbia, IL 62236
(217) 605-0403
404 N. Main Street
TO PANEL "D0222".
REMOVE EXISTING FEEDER CIRCUITY AND ABOVE GRADE CONDUIT FROM PANEL "D0222 MDP"
"D0223 5 BAY". ABANDON EXISTING BELOW-GRADE FEEDER CIRCUITRY IN PLACE.
REMOVE EXISTING ABOVE-GRADE FEEDER CIRCUITRY FROM PANEL "DO222 MDP" TO PANEL
EXISTING MAIN DISTRIBUTION PANEL "PP-1".
REMOVE EXISTING CONDUIT/CONDUCTORS FROM EXISTING 400A CT METER CABINET TO
BAY #2".
REMOVE EXISTING FEEDER CIRCUITRY FROM PANEL "D0222 MDP" TO EXISTING PANEL "D0222
EXISTING CONCRETE SLAB AND FOUNDATION TO BE REMOVED IN ITS ENTIRETY BY I.D.O.T.
BRANCH CIRCUITRY TO REMAIN AND BE RECONNECTED TO NEW PANEL BREAKERS.
"D0222 BAY #2". ABANDON EXISTING BELOW-GRADE FEEDER CIRCUITRY IN PLACE. EXISTING
REMOVE EXISTING TIRE SHED PANEL AND ABOVE-GRADE FEEDER CIRCUITRY FROM PANEL
ENTRANCE CONDUCTORS WITH AMEREN.
CONDUCTORS. COORDINATE DISCONNECTION AND REMOVAL OF OVERHEAD SERVICE
REMOVE EXISTING ELECTRICAL METER, WEATHERHEAD, AND SERVICE ENTRANCE
X
NOTES:
E T
T
E
DEMOLITION NOTES:
ATS
CONTRACTOR SHALL PROVIDE ALL GENERATOR/ATS EQUIPMENT, PROGRAMMING AND APPURTENANCES AS REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL STAND BY GENERATOR SYSTEM.8.
PROVIDE OVER CURRENT PROTECTIVE DEVICE COORDINATION STUDY AND APPROPRIATE LABELS ON ELECTRICAL EQUIPMENT AT LADD MAINTENANCE YARD.7.
REFER TO SHEET 2 FOR GENERAL NOTES AND SYMBOLS LIST.6.
ALL UTITLITY CABLES AND LINES SHALL BE LOCATED BY THE RESPECTIVE UTILITY CONTRACTOR. CONTACT J.U.L.I.E. (JOINT UTILITY LOCATION INFORMATION FOR EXCAVATORS) FOR UTILITY INFORMATION.5.
CONTRACTOR CONSTRUCTION OPERATIONS OR VEHICLES SHALL NOT BLOCK ACCESS TO THE YARD OR BUILDINGS.4.
SUPERVISOR A MINIMUM OF 14 DAYS IN ADVANCE. POWER SHUT-DOWN SHALL NOT BE GREATER THAN 24 HOURS.
ALL TEMPORARY POWER SHUT-DOWN FOR SYSTEM TIE-IN OR REPLACEMENT FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE COORDINATED AND PRE-APPROVED BY THE I.D.O.T. YARD 3.
NO CONSTRUCTION OPERATIONS INTERRUPTING MAINTENANCE YARD ACCESS SHALL OCCUR DURING I.D.O.T. WINTER OPERATION SCHEDULE (NOVEMBER 1 THROUGH APRIL 1)2.
DAYS IN ADVANCE,
CONDUITS, GROUND FIELDS, PULL BOXES, BOLLARDS, ETC. WITH I.D.O.T. ALL TRENCHING/EXCAVATION REQUIREMENTS SHALL BE COORDINATED WITH THE I.D.O.T. YARD SUPERVISOR A MINIMUM OF 14
ALL SURFACE MATERIAL REMOVAL/REPLACEMENT, EXCAVATION, TRENCH EXCAVATION, BACKFILL MATERIAL AND COMPACTION TO BE BY I.D.O.T. COORDINATE INSTALLATION OF CONCRETE PADS, 1.
BARN TO REMAIN
EXISTING SALT
SHED TO REMAIN
EXISTING TIRE
D0222 TO REMAIN
EXISTING BUILDING
PANEL "PP-1"
FRONTAGE ROAD
G
SCALE:
1" = 30'
ELECTRICAL SITE PLAN - LADD MAINTENANCE YARD
G
D0223 TO REMAIN
EXISTING BUILDING
42'-0"
TO REMAIN
EXISTING SHED
D0390 TO REMIAN
EXISTING BUILDING
PANEL "252-A"
PANEL "D0223 5-BAY"
PANEL "D0222 MDP"
PANEL "D0222"
PANEL "D0222 BAY #2"
TIRE SHED PANEL
KEYED NOTES:
REPRESENTITIVE AND YARD SUPERVISOR FOR EXACT MOUNTING LOCATIONS OF ANNUNCIATOR AND SHUT-DOWN SWITCH.
SHUT-DOWN SWITCH WIRING, INSTALLED PER MANUFACTURER'S WRITTEN INSTRUCTIONS. COORDINATE WITH I.D.O.T. FIELD
PROVIDE GENSET REMOTE ANNUNCIATOR PANEL AND GENSET EMERGENCY SHUT-DOWN SWITCH. PROVIDE ANNUNCIATOR AND
AND CONDUITS FOR EACH CIRCUIT PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
MANUFACTURER'S WRITTEN REQUIREMENTS FROM PANEL "PP-1" TO GENERATOR (GEN-1). PROVIDE BREAKERS, CONDUCTORS
PROVIDE MAINTENANCE CIRCUITS IN 1" CONDUIT (ENGINE BLOCK HEATER, BATTERY CHARGER, ETC.) AS REQUIRED PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
TRANSFER SWITCH (ATS-1) TO GENERATOR (GEN-1) FOR CONTROL SYSTEM. PROVIDE QUANTITY OF CONDUIT/CONDUCTORS PER
PROVIDE CONTROL WIRING IN 1" CONDUIT OR AS REQUIRED PER MANUFACTURER'S WRITTEN INSTRUCTIONS FROM AUTOMATIC
INSTALLATION AND SEAL ANNULAR SPACE WITH NON-SHRINK GROUT AND MAKE WATER/WEATHER TIGHT.
BUILDING ABOVE OFFICE CEILING TO EXISTING MAIN DISTRIBUTION PANEL "D0222 MDP". CORE DRILL BRICK WALL FOR CONDUIT
ROUTE CONDUIT/CONDUCTORS FROM PULL BOX, UP EXTERIOR BRICK WALL (SECURELY FASTENED AT 4'-0" INTERVALS), INTO
EXISTING SEPTIC TANK AND SANITARY LINES TO REMAIN.
EXISTING ABANDONED UNDERGROUND ELECTRIC TO REMAIN.
EXISTING UNDERGROUND CONDUIT/CONDUCTORS TO REMAIN.
EXISTING UNDERGROUND TELEPHONE LINE TO REMAIN.
EXISTING UNDERGROUND DOMESTIC WATER PIPING TO REMAIN.
EXISTING CULVERT TO REMAIN.
TRENCHING, BACKFILL MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T.
GRADE. DISCONNECT ANY EXISTING GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO NEW GROUND BAR. COORDINATE
MAIN BREAKER AND GROUND BAR IN EXISTING PANEL "D0223 5-BAY". PROVIDE (3) #3 AND #8 GROUND IN 1-1/4” CONDUIT BELOW EXISTING POWER PANEL "D0223 5-BAY" (SQUARE D, QO LOAD CENTER, 100A, 240/120V, 1ϕ, 3W) TO REMAIN. PROVIDE NEW 40A
EXISTING BOLLARDS TO REMAIN.
REFER TO DETAIL 1 ON SHEET 8 FOR ADDITIONAL INFORMATION.REQUIREMENTS WITH I.D.O.T.
COORDINATE EXCAVATION, TRENCHING, BACKFILL MATERIAL AND COMPACTION PROVIDE NEW UNDERGROUND PULL BOXES.
REQUIREMENTS. REFER TO DETAIL 2 ON SHEET 8 FOR ADDITIONAL INFORMATION.
TO MAIN DISTRIBUTION PANEL "D0222 MDP" MAIN BREAKER. REFER TO PANEL SCHEDULES ON SHEET 7 FOR BREAKER REQUIREMENTS WITH I.D.O.T. CONNECT TO NEW 200 AMP,3-POLE SUB FEED BREAKER IN MAIN DISTRIBUTION PANEL "PP-1" AND PROVIDE (3) #4/0 AND #4 GROUND IN 2-1/2" CONDUIT, COORDINATE TRENCHING, BACKFILL MATERIAL AND COMPACTION
TRANSFER SWITCH (ATS-1). COORDINATE TRENCHING REQUIREMENTS FOR BELOW-GRADE CONDUIT INSTALLATION WITH I.D.O.T.
PROVIDE 2 SETS OF (3) #3/0 AND #3 GROUND IN (2) 2" CONDUIT BELOW GRADE FROM GENERATOR (GEN-1) TO AUTOMATIC
INSTALLATION OF AUTOMATIC TRANSFER SWITCH WITH AMEREN REGARDING REQUIREMENTS, INSTALLATION AND LOCATION.
AUTOMATIC TRANSFER SWITCH AND FROM AUTOMATIC TRANSFER SWITCH TO EXISTING PANEL "PP-1". COORDINATE EXTERIOR. PROVIDE 2 SETS OF (3) #3/0 AND #3 GROUND IN (2) 2" CONDUIT ABOVE GRADE FROM DISCONNECT SWITCH TO PROVIDE NEMA 3R, 400A, 240/120VAC, 1ϕ, 3W, 3-POLE AUTOMATIC TRANSFER SWITCH (ATS-1), SECURELY MOUNTED TO BUILDING
ADDITIONAL GENERATOR PAD INFORMATION.
REFER TO DETAIL 5 ON SHEET 8 FOR ALL DIRECTIONS. COORDINATE PAD INSTALLATION WITH CONDUIT INSTALLATIONS.
COORDINATE PAD DIMESIONS WITH ACTUAL EQUIPMENT PROVIDED, PAD SHALL EXTEND 1'-0" BEYOND LIMITS OF EQUIPMENT IN GENERATOR PAD. COORDINATE EXCAVATION, TRENCHING, BACKFILL MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T.
COORDINATE WITH AMEREN FOR TEMPORARY GAS SERVICE DISCONNECTION. PROVIDE 10' +/- X 5' +/- X 6" THICK CONCRETE SERVICE PIPING. PROVIDE PRESSURE REGULATOR, STRAINER AND SHUT-OFF VALVE IN GAS PIPING TO GENERATOR.
INSTALLED) TO EXISTING 2" NATURAL GAS SERVICE PIPING. CONTRACTOR TO FIELD VERIFY SIZE OF EXISTING NATURAL GAS AS REQUIRED TO CONNECT NEW 2" GAS FEED FOR GENERATOR (COORDINATE REQUIREMENTS WITH ACTUAL EQUIPMENT PROVIDE 96KW/120KVA STANDBY NATURAL GAS ENGINE GENERATOR (GEN-1) IN WEATHERPROOF HOUSING. PROVIDE FITTINGS
DISCONNECT SWITCH.
TO BUILDING EXTERIOR. PROVIDE 2 SETS OF (3) #3/0 AND #3 GROUND IN (2) 2" CONDUITS FROM EXISTING METER BASE TO PROVIDE 400A, NEMA 3R, HEAVY-DUTY SERVICE RATED FUSED DISCONNECT SWITCH (FUSED AT 400 AMPS), SECURELY MOUNTED
FOR BREAKER REQUIREMENTS.
BRANCH CIRCUITRY. RECONNECT ANY EXISTING GROUND WIRES TO GROUND BAR. REFER TO PANEL SCHEDULE ON SHEET 7 MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T. PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING CONDUIT PENETRATION WITH NON-SHRINK GROUT AND MAKE WATER/WEATHER TIGHT. COORDINATE TRENCHING, BACKFILL AND #8 GROUND IN 1-1/4” CONDUIT FROM EXISTING PANEL "D0222 BAY #2" TO TIRE SHED PANEL. SEAL ANNULAR SPACE AROUND PROVIDE 100A, 240/120VAC, 1ϕ, 3W, NEMA 1, 12 CIRCUIT POWER PANEL WITH 100A MAIN BREAKER IN TIRE SHED. PROVIDE (3) #3
GROUND BAR.
EXISTING BUILDING "D0222 MDP". DISCONNECT ANY EXISTING GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO MAIN BREAKER AND GROUND BAR IN EXISTING PANEL "D0222 BAY #2". PROVIDE (3) #3 AND #8 GROUND IN 1-1/4” CONDUIT FROM EXISTING POWER PANEL "D0222 BAY #2" (SQUARE D, QDC16UF, 100A, 240/120V, 1ϕ, 3W) TO REMAIN. PROVIDE NEW 100A, 2-POLE
EXISTING MAIN DISTRIBUTION PANEL "D0222 MDP" (SIEMANS, TYPE SE, 200A, 1ϕ, 240/120V, 3W) TO REMAIN.
EXISTING RIP RAP TO REMAIN.
EXISTING ROCK SURFACE TO REMAIN.
EXISTING CONCRETE PAVEMENT TO REMAIN.
EXISTING ASPHALT PAVEMENT TO REMAIN.
EXISTING OVERHEAD ELECTRICAL CONDUCTORS TO REMAIN, OR BE REMOVED BY UTILITY COMPANY.
EXISTING FENCE TO REMAIN.
EXISTING FENCE AND GATE TO REMAIN.
EXISTING WATER TANKS TO REMAIN.
EXISTING MANHOLES AND SEPTIC TANK TO REMAIN.
EXISTING OIL SEPERATOR TO REMAIN.
EXISTING GRASS AREA TO REMAIN.
EXISTING CONCRETE PAD TO REMAIN.
EXISTING UTILITY POLE TO REMAIN, OR BE REMOVED BY UTILITY COMPANY.
EXISTING FLAG POLE TO REMAIN.
EXISTING FIRE HYDRANT TO REMAIN.
EXISTING FUEL ISLAND TO REMAIN.
EXISTING POWER PANEL "252-A" (GENERAL ELECTRIC, AQF, 100A, 240/120V, 1ϕ, 3W) TO REMAIN.
EXISTING MAIN DISTRIBUTION PANEL "PP1" (SIEMENS, TYPE P1, 400A, 240/120V, 1ϕ, 3W) TO REMAIN.
DISCONNECT ANY EXISTING GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO NEW GROUND BAR.
IN EXISTING PANEL "D0222". PROVIDE (3) #8 AND #10 GROUND IN 3/4" CONDUIT ABOVE GRADE FROM PANEL "D0222 MDP".
EXISTING POWER PANEL "D0222" (SQUARE D, QO LOAD CENTERE, 50A, 240/120V, 1ϕ, 3W) TO REMAIN. PROVIDE NEW GROUND BAR
EXISTING NATURAL GAS SERVICE/METER TO REMAIN.
EXISTING 400 AMP CT METER/CABINET TO REMAIN.
EXISTING 50KVA, 7200V TO 120/240VAC, 1ϕ, 3W PAD MOUNT TRANSFORMER TO REMAIN.
X
UTILITY INFORMATION
(815)343-8303 athompson4@ameren.com
ELECTRIC/GAS: AMEREN ILLINOIS
LADD IDOT YARD;
AS REFERENCE ONLY.
$7,500.00 TO COMPLETE THE WORK. THIS QUOTE IS BEING PROVIDED
PROJECT. AMEREN HAS QUOTED TO THE ENGINEER APPROXIMATELY
THE UTILITY WORK IS DONE IN SUCH A MANNER AS TO NOT DELAY THE
CONTRACTOR WILL ASSUME THE RESPONSIBILITY TO ENSURE THAT
COMPANY WILL BE PAID IN FULL BY THE CONTRACTOR. THE
WITH THE UTILITY COMPANY. CHARGES REQUIRED BY THE UTILITY
SCHEDULE THE UPGRADE OF THE GAS SERVICE TO THE BUILDING
THE CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH AND
NOTE:
608-4255) FOR MILESTONE EVENT COORDINATION.
DAYS NOTICE OF MILESTONE EVENTS. CONTACT BILL WHITLOW (217-
CONTRACTOR SHALL PROVIDE PRAIRIE ENGINEERS A MINIMUM OF 7
GAS/ELECTRIC CONNECTIONS, EQUIPMENT STARTUP, ETC.).
AND AT CERTAIN MILESTONE EVENTS (CONCRETE WORK,
DOCUMENTS. PRAIRIE ENGINEERS WILL BE ON SITE PERIODICALLY
WORKMANSHIP ARE IN ACCORDANCE WITH THE CONTRACT
CONSTRUCTION SCHEDULE AND THAT THE MATERIALS, FINISHES AND
WORK IS PROGRESSING IN ACCORDANCE WITH THE APPROVED
THE WORK BEING PERFORMED TO DETERMINE, IN GENERAL, THAT THE
OBSERVATION VISITS TO REPORT ON THE PROGRESS AND QUALITY OF
PRAIRIE ENGINEERS WILL PROVIDE CONSTRUCTION SITE
CONSTURCTION INSPECTION:
SECTION COUNTY
ILLINOIS
BUREAU
TOTAL
SHEETS
SHEET
NO.RTE.
(011,037) ELE,EG,MG
USER NAME =
PLOT DATE = DATE
DESIGNED
CHECKED
DRAWN
REVISED
REVISED
REVISED
REVISED
F.A.
SHEET OF 8 SHEETS STA. TO STA.
CWB
5/1/2025
SCALE: 1" = 30'
STATE OF ILLINOIS
DEPARTMENT OF TRANSPORTATION
ELECTRICAL SITE PLAN - LADD MAINTENANCE YARD
I:
\J o b s \2
\1
.2
.0
O
P S
W O
-3
L a d d a n d S y c a m o re
G e n e ra to rs
\D ra w in g s \S h e e t\ .d g n
F
IL
E N
A M
.3
S h e e t]
M O
D E
L cbozarth
4/29/2025
8 4
30'-0"15'-0"0
Date: 5/1/2025
AE
Copyright Prairie Engineers of Illinois, P.C. 2023
Columbia, IL 62236
(217) 605-0403
404 N. Main Street
PROVIDE (3) #3 AND #8 GROUND IN 1-1/4" CONDUIT FROM PANEL "C" TO PANEL "D".
TO PANEL "C".
PROVIDE (4) #3 AND #8 GROUND IN 1-1/4" CONDUIT FROM PANEL "A" TO PANEL "B" AND
INSTALLATION. COORDINATE WITH I.D.O.T. FOR REQUIRED LIMITS OF REMOVAL.
AGGREGATE SUB-BASE MATERIAL AS REQUIRED FOR CONCRETE PAD AND CONDUIT
I.D.O.T. STAFF SHALL REMOVE AND REPLACE ALL EXISTING ASPHALT PAVEMENT AND
SERVICE AS REQUIRED FOR ELECTRICAL SERVICE MODIFICATION.
COORDINATE WITH COMED FOR DISCONNECTION/RECONNECTION OF ELECTRICAL
TO GROUND RODS SHALL BE EXOTHERMIC WELDS.
BELOW FINISH GRADE OR BELOW FROST LINE, WHICHEVER IS DEEPER. CONNECTION
BARE STRANDED COPPER GROUND FIELD CONDUCTOR. GROUND FIELD SHALL BE 30"
PROVIDE 3/4" X 10'-0" COPPER CLAD GROUNDING ROD (TYP. OF 3) CONNECTED TO #2
USED ABOVE GRADE TO PROTECT CONDUCTORS FROM PHYSICAL DAMAGE.
40 PVC CONDUIT TO TRIAD GROUND FIELD BELOW GRADE. SCHEDULE 80 PVC TO BE
PROVIDE #2 INSULATED STRANDED COPPER GROUND CONDUCTOR IN 1/2" SCHEDULE
ADDITIONAL BOLLARD INFORMATION.
ADDITIONAL GENERATOR PAD INFORMATION. REFER TO DETAIL 3 ON SHEET 8 FOR
REFER TO DETAIL 4 ON SHEET 8 FOR COORDINATE PAD WITH BOLLARD INSTALLATION.
PROVIDED, PAD SHALL EXTEND 1'-0" BEYOND LIMITS OF EQUIPMENT IN ALL DIRECTIONS.
REMOVAL AND REPLACEMENT. COORDINATE PAD DIMESIONS WITH ACTUAL EQUIPMENT
I.D.O.T. FOR PAD EXCAVATION REQUIREMENTS AND PAVEMENT AND AGGREGATE
PROVIDE 9' +/- X 5' +/- X 6" THICK CONCRETE GENERATOR PAD. COORDINATE WITH
SECURELY TO BUILDING 205, AS HIGH ON BUILDING AS PRACTICAL, AT 4'-0" INTERVALS.
MOUNT CONDUITS FOR EACH CIRCUIT PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
PANEL "C" TO GENERATOR (GEN-2). PROVIDE BREAKERS, CONDUCTORS AND CONDUITS
CHARGER, ETC) AS REQUIRED PER MANUFACTURER'S WRITTEN REQUIREMENTS FROM
PROVIDE MAINTENANCE CIRCUITS IN 1" CONDUIT (ENGINE BLOCK HEATER, BATTERY
BUILDING 205, AS HIGH ON BUILDING AS PRACTICAL, AT 4'-0" INTERVALS.
MOUNT CONDUITS SECURELY TO MANUFACTURER'S WRITTEN INSTRUCTIONS.
(GEN-2) FOR CONTROL SYSTEM. PROVIDE QUANTITY OF CONDUIT/CONDUCTORS PER
WRITTEN INSTRUCTIONS FROM AUTOMATIC TRANSFER SWITCH (ATS-2) TO GENERATOR
PROVIDE CONTROL WIRING IN 1" CONDUIT OR AS REQUIRED PER MANUFACTURER'S
SECURELY TO BUILDING 205, AS HIGH ON BUILDING AS PRACTICAL, AT 4'-0" INTERVALS.
PROVIDE (4) #4/0 AND #2 GROUND IN 2-1/2” CONDUIT ABOVE GRADE. MOUNT CONDUIT
REQUIREMENTS.
BOND NEUTRAL AND GROUNDING LUGS IN THIS LOCATION ONLY PER NEC
SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS.
PANEL "D" TO AIR COMPRESSOR DISCONNECT IN BUILDING 206. REFER TO PANEL
PROVIDE 50 AMP, 2-POLE BREAKER AND (3) #8 AND #10 GROUND IN 1" CONDUIT FROM
ON SHEET 7 FOR BREAKER REQUIREMENTS.
REFER TO PANEL SCHEDULE RECONNECT EXISTING BRANCH CIRCUITRY TO REMAIN.
PROVIDE GFCI BREAKERS AS REQUIRED TO COMPACTION REQUIREMENTS WITH I.D.O.T.
WATER/WEATHER TIGHT. COORDINATE TRENCHING, BACKFILL MATERIAL AND
SPACE AROUND CONDUIT PENETRATION WITH NON-SHRINK GROUT AND MAKE
AMP MAIN BREAKER SECURELY FASTENED TO EXTERIOR OF BUILDING. SEAL ANNULAR
PROVIDE 100A, 240/120VAC, 1ϕ, 3W, NEMA 3R, 20 CIRCUIT POWER PANEL “D” WITH 100
REPLACEMENT/INSTALLATION OF PANEL "C".
RELOCATE EXISTING ELECTRICAL DEVICES AND CIRCUITRY AS REQUIRED FOR
REFER TO PANEL SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS. REMAIN.
PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING BRANCH CIRCUITRY TO
PROVIDE 100A, 240/120VAC, 3ϕ, 4W, NEMA 1, 42 CIRCUIT MAIN LUG POWER PANEL “C”.
BREAKER REQUIREMENTS.
REFER TO PANEL SCHEDULE ON SHEET 7 FOR BRANCH CIRCUITRY TO REMAIN.
PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING AMP MAIN BREAKER.
PROVIDE 100A, 240/120VAC, 3ϕ, 4W, NEMA 1, 20 CIRCUIT POWER PANEL “B” WITH 100
AS REQUIRED FOR REPLACEMENT/INSTALLATION OF PANEL "A".
BREAKER REQUIREMENTS. RELOCATE EXISTING ELECTRICAL DEVICES AND CIRCUITRY
REFER TO PANEL SCHEDULE ON SHEET 7 FOR BRANCH CIRCUITRY TO REMAIN.
PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING AMP MAIN BREAKER.
PROVIDE 225A, 240/120VAC, 3ϕ, 4W, NEMA 1, 30 CIRCUIT POWER PANEL “A” WITH 225
(FUSED AT 225A), MOUNTED SECURELY TO BUILDING 205 EXTERIOR.
PROVIDE 400A, NEMA 3R, HEAVY-DUTY SERVICE RATED FUSED DISCONNECT SWITCH
INSTALLATION, AND LOCATION.
OF TRANSFER SWITCH WITH COMED REGARDING TRANSFER SWITCH REQUIREMENTS,
COORDINATE INSTALLATION (ATS-2) SECURELY MOUNTED TO BUILDING 205 EXTERIOR.
PROVIDE NEMA 3R, 225A, 240/120VAC, 3ϕ, 4W, 4-POLE AUTOMATIC TRANSFER SWITCH
TEMPORARY GAS SERVICE DISCONNECTION.
SHUT-OFF VALVE IN GAS PIPING TO GENERATOR. COORDINATE WITH NICOR FOR
VERIFY SIZE OF EXISTING NATURAL GAS SERVICE PIPING. PROVIDE STRAINER AND
INSTALLED) TO EXISTING 2" NATURAL GAS SERVICE PIPING. CONTRACTOR TO FIELD
FEED FOR GENERATOR (COORDINATE REQUIREMENTS WITH ACTUAL EQUIPMENT
WEATHERPROOF HOUSING. PROVIDE FITTINGS AS REQUIRED TO CONNECT NEW 2" GAS
PROVIDE 60KW/75KVA STANDBY NATURAL GAS ENGINE GENERATOR (GEN-2) IN
X
1-888-642-6748
GAS:NICOR
1-224-290-3367
MICHAEL.ADAMS@COMED.COM
ELECTRIC: COMED
SYCAMORE IDOT YARD;
DEMOLITION NOTES:
EXITSING GROUND FIELD TO BE REMOVED OR ABANDONED IN PLACE.
EXISTING AIR COMPRESSOR DISCONNECT.
REMOVE EXISTING BRANCH CONDUIT/CONDUCTORS FROM BUILDING 206 PANEL "D" TO
RECONNECTED TO NEW BREAKERS.
CONDUIT/CONDUCTORS. EXISTING BRANCH CIRCUITRY TO REMAIN AND BE
REMOVE EXISTING POWER PANEL, ASSCIATED BREAKERS, AND FEEDER
X
UTILITY INFORMATIONSCALE:
NO SCALE
EXISTING SYCAMORE MAINTENANCE YARD - ONE LINE ELECTRICAL DIAGRAM
SCALE:
NO SCALE
PROPOSED SYCAMORE MAINTENANCE YARD - ONE LINE ELECTRICAL DIAGRAM
GENERATOR DATA - SYCAMORE
KVA (MINIMUM)
VOLTAGE
FREQUENCY
PHASE
WIRE
POWER FACTOR
FUEL
12 11
EQUIPMENT IS REMOVED WHILE ALTERNATE SOURCE IS ENERGIZED".
ELECTRODE CONDUCTOR OR BONDING JUMPER CONNECTION IN THIS
LABELED "WARNING SHOCK HAZARD EXISTS IF GROUNDING
GENERATOR SET (THAT IS NOT A SEPARATELY DERIVED SYSTEM)
EACH SERVICE DISCONNECT THAT HAS A BACKUP ENGINE
INCLUDE WEATHERPROOF ENGRAVED PHENOLIC LEGEND PLATE FOR 10.
NEC 408.3 (F)(I)" HIGH LEG IDENTIFICATION".
PLATE LABELED "CAUTION B PHASE HAS 208 VOLT TO GROUND" PER
, 4W PANELBOARD WITH A LEGEND ϕPROVIDE EACH 240/120VAC, 39.
BAR FOR EACH PANEL.
PANEL SHALL BE COPPER. INCLUDE COPPER EQUIPMENT GROUND
PANELBOARD BUSSES SHALL BE COPPER, NEUTRAL BAR FOR EACH 8.
AND/OR NOTING THE RESPECTIVE EQUIPMENT.
DISCONNECTS, EQUIPMENT, ETC. IDENTIFYING THE EQUIPMENT
INCLUDE LEGEND PLATES FOR ALL PANELBOARDS, LOAD CENTERS, 7.
MACHINE SCREWS.
BACKGROUND. SECURE WITH WEATHERPROOF ADHESIVE AND/OR
PHENOLIC MATERIAL, 1/4” HIGH BLOCK LETTERS ON A WHITE
OR LEGEND PLATES SHALL BE WEATHERPROOF ENGRAVED PLASTIC 6.
STAND-BY ENGINE GENERATOR”.
, 4W, NOTE PANEL "A" IS BACKED UP BY WHOLE YARD ϕ240/120VAC, 3
PANEL LABELED PANEL "A", FED FROM AUTO TRANSFER SWITCH,
DISTRIBUTION FURNISH AND INSTALL A LEGEND PLATE FOR THE MAIN 5.
GROUND AT THE MAIN SERVICE DISCONNECT”.
, 4W” AND “NOTE GENERATOR NEUTRAL IS BONDED TO ϕ240/120VAC, 3
GENERATOR BREAKER LABELED “GENERATOR BREAKER, 225A,
FURNISH AND INSTALL A LEGEND PLATE FOR THE ENGINE 4.
, 4WϕTOR 240/120VAC, 3GENERA
-EMERGENCY SOURCE FROM WHOLE YARD STAND-BY ENGINE
-NORMAL SOURCE FROM UTILITY TRANSFORMER THROUGH PANEL "A"
-AUTO TRANSFER SWITCH
SWITCH AS FOLLOWS:
FURNISH AND INSTALL LEGEND PLATE FOR AUTOMATIC TRANSFER 3.
DISCONNECT”.
“NOTE GENERATOR NEUTRAL IS BONDED TO GROUND AT SERVICE
DISCONNECT LABELED “BUILDING MAIN SERVICE DISCONNECT”AND
FURNISH LEGEND PLATES FOR THE BUILDING MAIN SERVICE 2.
REQUIREMENTS.
SWITCH SHALL BE INSTALLED IN FULL COMPLIANCE WITH COMED
SERVICE ENTRANCE EQUIPMENT, GENERATOR AND TRANSFER 1.
ONE LINE DIAGRAM NOTES:
AUTOMATIC TRANSFER SWITCH (ATS-2)225A NEWA 3R
NATURAL GAS
0.8
60HZ
240/120
(GEN-2)75
SECTION COUNTY
ILLINOIS FED. AID PROJECT
DEKALB
TOTAL
SHEETS
SHEET
NO.RTE.
(011,037) ELE,EG,MG
USER NAME =
PLOT DATE = DATE
DESIGNED
CHECKED
DRAWN
REVISED
REVISED
REVISED
REVISED
F.A.
SHEET 5 OF 8 SHEETS STA. TO STA.
CWB
5/1/2025
SCALE:
STATE OF ILLINOIS
ONE LINE DIAGRAMS - SYCAMORE MAINTENANCE YARD
o b s \2
\1
.2
.0
O
P S
W O
-3
L a d d a n d S y c a m o re
G e n e ra to rs
\D ra w in g s \S h e e t\ .d g n
F
IL
E N
A M
.2
S h e e t]
M O
D E
L cbozarth
3/26/2025
8 5
GN
, 4Wϕ240/120V, 3
225 AMP,
NEW PANEL "A"
100A
50A
100A
TO REMAIN
TRANSFORMER
MOUNTED 50 KVA
EXISTING POLE
GN
E
MB
100A
REMAIN
AND METER BASE TO
ELECTRICAL METER
EXISTING
225A
ATS-2
TO REMAIN
DISCONNECT SWITCH
COMPRESSOR
EXISTING AIR
TO REMAIN
DISCONNECT SWITCH
COMPRESSOR
EXISTING AIR
TO REMAIN
TRANSFORMER
MOUNTED 50 KVA
EXISTING POLE
GEN-2
BASE TO REMAIN
METER AND METER
EXISTING ELECTRICAL
NG
100A
NG NG NG
, 4Wϕ240/120V, 3
100 AMP,
NEW PANEL "B"
, 4Wϕ240/120V, 3
100 AMP,
NEW PANEL "C"
, 3W1ϕ240/120V, 100 AMP, NEW PANEL "D"
REMOVED
TO BE
PANEL "D"
EXISTING
REMOVED
TO BE
PANEL "C"
EXISTING
REMOVED
TO BE
PANEL "B"
EXISTING
REMOVED
TO BE
PANEL "A"
EXISTING
50A 60A
100A
100A
225A
20A
MB
100A
MB
225A
N
P
Copyright Prairie Engineers of Illinois, P.C. 2023
Columbia, IL 62236
(217) 605-0403
INSTALLATION WITH I.D.O.T.
COORDINATE TRENCHING REQUIREMENTS FOR BELOW-GRADE CONDUIT
INSTALLATION WITH I.D.O.T.
COORDINATE TRENCHING REQUIREMENTS FOR BELOW-GRADE CONDUIT
AS HIGH AS PRACTICAL, FASTENED SECURELY TO BUILDING AT 4'-0" INTERVALS.
PROVIDE (3) #3 AND #8 GROUND IN 1-1/4" CONDUIT. MOUNT ABOVE-GRADE CONDUITS
AMEREN AS REQUIRED FOR ELECTRICAL SERVICE MODIFICATIONS.
COORDINATE DISCONNECTION/RECONNECTION OF ELECTRICAL SERVICE WITH
ON SHEET 8 FOR ADDITIONAL GENERATOR PAD INFORMATION.
REFER TO DETAIL 5 COORDINATE PAD INSTALLATION WITH CONDUIT INSTALLATIONS.
PAD SHALL EXTEND 1'-0" BEYOND LIMITS OF EQUIPMENT IN ALL DIRECTIONS.
REPLACEMENT.. COORDINATE PAD DIMESIONS WITH ACTUAL EQUIPMENT PROVIDED,
I.D.O.T. FOR PAD EXCAVATION REQUIREMENTS AND AGGREGATE REMOVAL AND
PROVIDE 10' +/- X 5' +/- X 6" THICK CONCRETE GENERATOR PAD.COORDINATE WITH
WELDS.
BELOW FINISH GRADE. CONNECTION TO GROUND RODS SHALL BE EXOTHERMIC
BARE STRANDED COPPER GROUND FIELD CONDUCTOR. GROUND FIELD SHALL BE 30"
PROVIDE 3/4" X 10'-0" COPPER CLAD GROUNDING ROD (TYP. OF 3) CONNECTED TO #2
GRADE TO PROTECT CONDUCTORS FROM PHYSICAL DAMAGE.
40 PVC CONDUIT TO TRIAD GROUND FIELD. SCHEDULE 80 PVC TO BE USED ABOVE
PROVIDE #2 INSULATED STRANDED COPPER GROUND CONDUCTOR IN 1/2" SCHEDULE
EXOTHERMIC WELDS.
BE 30" BELOW FINISH GRADE. CONNECTION TO GROUND RODS SHALL BE
#1/0 BARE STRANDED COPPER GROUND FIELD CONDUCTOR. GROUND FIELD SHALL
PROVIDE 3/4" X 10'-0" COPPER CLAD GROUNDING ROD (TYP. OF 3) CONNECTED TO
USED ABOVE GRADE TO PROTECT CONDUCTORS FROM PHYSICAL DAMAGE.
SCHEDULE 40 PVC CONDUIT TO TRIAD GROUND FIELD. SCHEDULE 80 PVC TO BE
PROVIDE #1/0 INSULATED STRANDED COPPER GROUND CONDUCTOR IN 3/4"
SECURELY TO BUILDING AT 4'-0" INTERVALS.
PROVIDE 2 SETS OF (3) #3/0 AND #3 GROUND IN (2) 2" CONDUIT ABOVE-GRADE. MOUNT
AND CONDUITS FOR EACH CIRCUIT PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
FROM PANEL "PP-1" TO GENERATOR (GEN-1). PROVIDE BREAKERS, CONDUCTORS
CHARGER, ETC) AS REQUIRED PER MANUFACTURER'S WRITTEN REQUIREMENTS
PROVIDE MAINTENANCE CIRCUITS IN 1" CONDUIT (ENGINE BLOCK HEATER, BATTERY
CONDUIT/CONDUCTORS PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
GENERATOR (GEN-1) FOR CONTROL SYSTEM. PROVIDE QUANTITY OF
WRITTEN INSTRUCTIONS FROM AUTOMATIC TRANSFER SWITCH (ATS-1) TO
PROVIDE CONTROL WIRING IN 1" CONDUIT OR AS REQUIRED PER MANUFACTURER'S
COORDINATE WITH I.D.O.T. FOR REQUIRED LIMITS OF REMOVAL.
MATERIAL AS REQUIRED FOR CONCRETE PAD AND CONDUIT INSTALLATION.
I.D.O.T. STAFF SHALL REMOVE AND REPLACE EXISTING AGGREGATE SUB-BASE
WIRES TO NEW GROUND BAR.
PROVIDE GROUND BAR IN PANEL. RECONNECT EXISTING BRANCH CIRCUIT GROUND
FROM NEUTRAL BAR AND RECONNECT TO NEW GROUND BAR.
EXISTING PANEL "D0222". DISCONNECT EXISTING BRANCH CIRCUIT GROUND WIRES
EXISTING POWER PANEL "D0222" TO REMAIN. PROVIDE NEW GROUND BAR IN
REFER TO PANEL SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS.
REMAIN. RECONNECT EXISTING BRANCH CIRCUIT GROUND WIRES TO GROUND BAR.
PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING BRANCH CIRCUITRY TO
TRENCHING, BACKFILL MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T.
WITH NON-SHRINK GROUT AND MAKE WATER/WEATHER TIGHT. COORDINATE
MAIN BREAKER IN TIRE SHED. SEAL ANNULAR SPACE AROUND CONDUIT PENETRATION
PROVIDE 100A, 240/120VAC, 1ϕ, 3W, NEMA 1, 12 CIRCUIT POWER PANEL WITH 100A
NEW GROUND BAR.
EXISTING BRANCH CIRCUIT GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO
BREAKER AND GROUND BAR IN EXISTING PANEL "D0222 BAY #2". DISCONNECT
EXISTING POWER PANEL "D0222 BAY #2" TO REMAIN. PROVIDE NEW 100A, 2-POLE MAIN
COMPACTION TO BE BY I.D.O.T.
BAR. ALL SURFACE MATERIAL REMOVAL/REPLACEMENT, BACKFILL MATERIAL AND
CIRCUIT GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO NEW GROUND
AND GROUND BAR IN EXISTING PANEL "D0223 5-BAY". DISCONNECT EXISTING BRANCH
EXISTING POWER PANEL "D0223 5-BAY" TO REMAIN. PROVIDE NEW 40A MAIN BREAKER
REFER TO DETAIL 2 ON SHEET 8 FOR ADDITIONAL INFORMATION
REMOVAL/REPLACEMENT, BACKFILL MATERIAL AND COMPACTION TO BE BY I.D.O.T.
DISTRIBUTION PANEL "D0222 MDP" MAIN BREAKER. ALL SURFACE MATERIAL
2-POLE SUB FEED BREAKER IN MAIN DISTRIBUTION PANEL "PP-1" TO MAIN
PROVIDE (3) #4/0 AND #4 GROUND IN 2-1/2" CONDUIT BELOW-GRADE FROM NEW 200A,
(FUSED AT 400 AMPS), SECURELY MOUNTED TO BUILDING EXTERIOR.
PROVIDE 400A, NEMA 3R, HEAVY-DUTY SERVICE RATED FUSED DISCONNECT SWITCH
INSTALLATION AND LOCATION.
AUTOMATIC TRANSFER SWITCH WITH AMEREN REGARDING REQUIREMENTS,
(ATS-1), SECURELY MOUNTED TO BUILDING EXTERIOR. COORDINATE INSTALLATION OF
PROVIDE NEMA 3R, 400A, 240/120VAC, 1ϕ, 3W, 3-POLE AUTOMATIC TRANSFER SWITCH
DISCONNECTION.
GENERATOR. COORDINATE WITH AMEREN FOR TEMPORARY GAS SERVICE
PROVIDE PRESSURE REGULATOR, STRAINER AND SHUT-OFF VALVE IN GAS PIPING TO
CONTRACTOR TO FIELD VERIFY SIZE OF EXISTING NATURAL GAS SERVICE PIPING.
EQUIPMENT INSTALLED) TO EXISTING 2" NATURAL GAS SERVICE PIPING.
GAS FEED FOR GENERATOR (COORDINATE REQUIREMENTS WITH ACTUAL
WEATHERPROOF HOUSING. PROVIDE FITTINGS AS REQUIRED TO CONNECT NEW 2"
PROVIDE 96KW/120KVA STANDBY NATURAL GAS ENGINE GENERATOR (GEN-1) IN
BOND NEUTRAL AND GROUNDING LUGS IN THIS LOCATION PER NEC REQUIREMENTS.
X
DEMOLITION NOTES:
PANEL"D0222 MDP" TO PANEL "D0222".
REMOVE EXISTING FEEDER CIRCUITRY AND ABOVE-GRADE CONDUIT FROM
PANEL "D0223 5 BAY". ABANDON EXISTING BELOW GRADE FEEDER CIRCUITRY IN PLACE.
REMOVE EXISTING ABOVE-GRADE FEEDER CIRCUITRY FROM PANEL "D0222 MDP" TO
TIRE SHED PANEL. ABANDON EXISTING BELOW GRADE FEEDER CIRCUITRY IN PLACE.
REMOVE EXISTING ABOVE-GRADE FEEDER CIRCUITRY FROM PANEL "D0222 BAY #2" TO
EXISTING MAIN DISTRIBUTION PANEL "PP-1".
REMOVE EXISTING CONDUIT/CONDUCTORS FROM EXISTING 400A CT METER CABINET TO
REMOVE EXISTING GROUND FIELD OR ABANDON IN PLACE.
#2".
REMOVE EXISTING FEEDER CIRCUITRY FROM PANEL "D0222 MDP" TO PANEL "D0222 BAY
RECONNECTED TO NEW BREAKERS.
REMOVE EXISTING TIRE SHED PANEL, EXISTING BRANCH CIRCUITRY TO REMAIN AND BE
ENTRANCE CONDUCTORS WITH AMEREN.
CONDUCTORS. COORDINATE DISCONNECTION AND REMOVAL OF OVERHEAD SERVICE
REMOVE EXISTING ELECTRICAL METER, WEATHERHEAD, AND SERVICE ENTRANCE 1
X
(815)343-…