Proposed Generator Parts Lists Ladd and Sycamore.pdf
PDF 148 KB Posted
- Solicitation number
- 26-494DOT-FINAD-B-49168
- Issued by
- Dekalb County, Illinois
About this file
This is a cost estimate document for proposed generator additions at two Illinois Department of Transportation (IDOT) District 3 maintenance yards, prepared as of May 1, 2025. The project encompasses electrical infrastructure upgrades at the Ladd Maintenance Yard and Sycamore Maintenance Yard, with the primary objective of installing standby generator systems and associated electrical distribution components. The Ladd project includes a 96kW/120kVA generator set with a 400A automatic transfer switch, service entrance upgrades, multiple panel installations (PP-1, D0222 MDP, D0223, and Tire Shed panels), and associated feeder conductors and ground fields. The Sycamore project features a 60kW/75kVA generator set with a 225A automatic transfer switch and four electrical panels (A, B, C, and D), along with concrete generator pads, gas service modifications, and comprehensive electrical distribution infrastructure. Both projects include miscellaneous items such as overcurrent studies, legend plates, and labels.
The document provides a detailed line-item breakdown of materials and quantities required for each location but does not specify unit pricing, total project costs, funding sources, or contract award information. No response dates, bid deadlines, site visit requirements, or bidders' conferences are identified in this preliminary cost estimate. The document serves as a planning tool for estimating the scope and scale of generator addition work at these two IDOT facilities, with quantities listed in units such as lump sum (LS), linear feet (LF), square feet (SF), and each (EA).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Proposed Generator Plans Ladd and Sycamore.pdf | ||
| contract Ladd Sycamore~2.docx | DOCX document | |
| Sycamore Ladd IFB vendor-instructions-and-requirements~3.docx | DOCX document | |
| Blank vendor-disclosure-formerly-forms A~2.docx | DOCX document | |
| Blank ipg-active-registered-vendor-disclosure-formerly-forms B~2.docx | DOCX document | |
| Sycamore.Ladd IFB offer-to-the-state-of-illinois.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT: DESIGNED: DATE: 5/1/2025
CLIENT: CHECKED: DATE: 5/1/2025
COMPS FOR: REVISED: DATE: -
PROJ. NO.:
Description Unit Quantity
Ladd Maintenance Yard Generator Addition
Generator Set
LS 1
SF 50
EA 1
LF 30
EA 1
LF 30
LF 35
LS 1
Service Entrance
LF 5
EA 1
LF 5
Panel "PP-1"
LF 35
EA 1
Panel D0222 MDP
EA 3
LF 360
EA 2
LS 1
LS 1
IDOT District 3
PE#101.2302.02
Cost Estimate
Proposed Generator Additions NDR
GWW
Ground field for existing meter
Existing gas service connection/modifications
Concrete generator pad w/ aggregate base
96kW/120kVA , 240/120V, 1ϕ, 3W standby engine generator
(GEN-1) w/ weatherproof enclosure
400A, 240/120V, 1ϕ, 3W, 3-Pole, NEMA 3R, automatic transfer switch (ATS-1), remote annuciator, stop switch
Generator control conductors/conduit from GEN-1 to ATS-1
400A, NEMA 3R, service rated main disconnect switch
Feeder conductors/conduit from GEN-1to ATS-1
200A, 2-pole breaker
Generator maintenance conductors/conduit from panel "PP-
1" to GEN-1
Ground field for generator
Feeder conductors/conduit from existing meter to main disconnect
Feeder conductors/conduit from main disconnect to ATS-1
Remove existing feeders
Remove existing service entrance
Feeder conductors/conduit from ATS-1 to panel "PP-1"
20A, single pole breaker
Ground field for existing panel D0222 MDP
Underground pullbox
Feeder conductors/conduit from panel "PP-1" to panel "D0222
MDP"
Ground bar and connections
COMPS FOR: REVISED: DATE: -
PROJ. NO.:
Description Unit Quantity
IDOT District 3
PE#101.2302.02
Cost Estimate
Proposed Generator Additions NDR
GWW
Panel D0222
LS 1
LF 10
Panel D0222 Bay #2
100-Amp 2-pole main breaker EA 1
LF 50
EA 1
LS 1
Panel D0223 5-Bay
LS 1
40-Amp 2P main breaker EA 1
LF 130
Panel Tire Shed
EA 1
LF 125
LS 1
Miscellaneous
LS 1Overcurrent study, legend plates and labels
Feeder conductors/conduit from panel "D0222 MDP" to panel
"D0222 Bay #2"
Ground bar and connections
Remove existing feeders
Feeder conductors/conduit from panel "D0222 MDP" to panel
"D0223 5-Bay"
Reconnect existing branch circuits
100-Amp, 120/240V, 1ϕ, 3W, 12 circuit panel, main breaker
100A, 2-pole breaker
Remove existing feeders
Feeder conductors/conduit from panel "D0222 MDP" to panel
"D0222"
Feeder conductors/conduit from panel "D0222 MDP" to panel
"D0223 5-Bay"
Ground bar and connections
Remove existing feeders
Ground bar and connections
Remove existing feeders
COMPS FOR: REVISED: DATE: -
PROJ. NO.:
Description Unit Quantity
Sycamore Maintenance Yard Generator Addition
Generator Set
LS 1
SF 45
EA 9
EA 1
LF 175
EA 1
LF 175
LF 275
Service Entrance
LF 20
EA 1
LF 20
LS 1
Panel "A"
LS 1
EA 1
LF 100
LS 1
Panel "B"
LS 1
EA 1
LF 120
LS 1
400A, NEMA 3R, service rated main disconnect switch
Feeder conductors/conduit from GEN-2 to ATS-2
Existing gas service connection/modifications
Proposed Generator Additions NDR
IDOT District 3 GWW
Cost Estimate -
PE#101.2302.02
Concrete generator pad w/ aggregate base
60kW/75kVA , 240/120V, 3ϕ, 4W standby engine generator
(GEN-2) w/ weatherproof enclosure
225A, 240/120V, 3ϕ, 4W, 4-Pole, NEMA 3R, automatic transfer switch (ATS-2), remote annuciator, stop switch
Generator control conductors/conduit from ATS-2 to GEN-2
Generator maintenance conductors/conduit from Panel "C" to
GEN-2
Ground field for generator
Feeder conductors/conduit from existing meter to main disconnect
Feeder conductors/conduit from main disconnect to ATS-2
Ground field for existing meter
Remove existing panel and feeders
Remove existing panel and feeders
100-Amp, 120/240V, 3ϕ, 4W, 20 circuit panel, main breaker
Feeder conductors/conduit from panel "A" to panel "B"
Concrete filled bollard
Feeder conductors/conduit from ATS-2 to panel "A"
225-Amp, 120/240V, 3ϕ, 4W, 30 circuit panel, main breaker
Reconnect existing branch circuits
Reconnect existing branch circuits
Panel "C"
EA 1
LF 120
LS 1
Panel "D"
LS 1
EA 1
LF 50
LF 60
Miscellaneous
Feeder conductors/conduit from panel "D" to existing compressor disconnect switch
Reconnect existing branch circuits
Remove existing feeders
Feeder conductors/conduit from panel "C" to panel "D"
100-Amp, 120/240V, 1ϕ, 3W, 20 circuit panel, NEMA 3R, main breaker
Overcurrent study, legend plates and labels
Feeder conductors/conduit from panel "A" to panel "C"
Reconnect existing branch circuits
Remove existing panel and feeders
100-Amp, 120/240V, 3ϕ, 4W, 42 circuit panel, main lug