Propane Standby Inspection Report.pdf

PDF 49 KB Posted

Attached to
File No. 472/19087. RAA-Baraga CF-Propane Plant Upgrades
Solicitation number
RFQ 171 190000000639 3
Issued by
Baraga County, Michigan

About this file

This is a Propane Standby System Inspection Report for Baraga Maximum Correctional Facility located at 301 Wadaga Road, Baraga, Michigan 49908. The inspection was conducted on October 9, 2018, by MI Construction Service 2 and documented the condition and operational status of the facility's propane standby system. The inspection covered a Trinity-manufactured storage tank (Serial #118362) with a 30-gallon capacity, 131-inch diameter, and 561-foot length, along with associated equipment including internal valves, emergency shutdown systems, liquid pumps, bypass valves, and a vaporizer/mixer unit manufactured by Ely Energy (Model Na, Serial Na, Year Built 1990). The system was found to be in generally good working condition with all major components operational.

The inspection identified that the storage tank contained 65 percent propane at the time of inspection and documented specific pressure readings and temperature settings for the vaporizer/mixer unit, including pump pressure at 120 PSI, optimum operating temperature of 160 degrees Fahrenheit, and venturi regulator settings ranging from 35 to 45 PSI. One minor issue was noted: small leaks in the bypass line piping from tank valves to pump inlet. The facility representative present during the inspection was Tyler, and the inspection was conducted by Ken Oswald. The report was submitted by MI Construction Service 2, located at 303 W. Maple Street, PO Box 145, Byron, Michigan 48418, with contact phone number 810-266-4687.

View the file

Other files

File Type Posted
472_19087.RAA Addendum 1.pdf PDF
LEIN Request REV 04-2018.pdf PDF
Design Build Advertisement R10-17).pdf PDF
Site Photos.pdf PDF
Ely Energy Vaporizer.pdf PDF
Design Build Spec Final.pdf PDF
LPG Equipment Layout.pdf PDF
Ely Energy Mixer.pdf PDF
Gas Distribution-Shts.I--6.pdf PDF
472_19087.RAA Addendum 2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JOB INFORMATION

Job # 10990

Customer # M5-053

Customer Name & Billing Address BARAGA MAXIMUM CORRECTIONAL FACILITY [301

WADAGA ROAD BARAGA, MI 49908]

Location Name & Address BARAGA MAXIMUM CORRECTIONAL FACILITY [301

WADAGA ROAD BARAGA, MI 49908]

IPS Job Coordinator Dutch (Olin) Russell

STORAGE TANK INSPECTION

Any leaks at tank fittings? No

Multi-port in proper working condition? Yes

Relief valve stacks in good condition? Yes

Remarks

8d09

Relief valve stacks have their protective caps in place? Yes

Magnetel gauge in good working condition? Yes

Temperature and pressure gauges in good condition? Yes

Piers and tank pads in good condition? Yes

Product in tank at time of inspection? Yes

Remarks

65%

Any combustible materials inside of fenced areas? Yes

Remarks

Small weeds

INTERNAL VALVES & EMERGENCY SHUTDOWN SYSTEM

Internal valves in good working condition? Yes

ESV valves in good working condition? Yes

Emergency shutdown system working correctly? Yes

Emergency shutdown signs or decals in place and in good condition? Yes

TRANSPORT BULKHEAD

Any leaks in piping from bulkhead to tank (liquid and vapor)? No

Liquid and vapor acme adapters in good condition? Yes

Does the system have the required safety features and are they in good working condition?

Yes

Liquid and vapor decals in place? Yes

Emergency shutdown system in place and in good working condition? Yes

Emergency signs or decals in place and in good condition? Yes

LIQUID PUMPS & BYPASS VALVES

Are the pumps in working condition? Yes

Have the pumps been greased? Yes

Did IPS employee need to grease pumps? No

Any leaks in piping from tank valves to pump inlet? Yes

Remarks

Small flex on bypass line

Any leaks in pump assembly or pump flanges? No

Pump pressure checked. Yes

PSI Pump is running at 120

Pump pressure gauge in good condition? Yes

Pump bypass valve was checked for proper working condition? Yes

Checked pump motor wiring

(conduit, flexes, seal-offs)

Yes

Hydrostatic relief valves in required locations? Yes

Checked hydrostatic reliefs for debris, weep hole location & that protective caps are in place.

Yes

LIQUID LINE FROM PUMPS TO VAPORIZER INLET

303 W. Maple St. PO Box 145

Byron, MI 48418

P) 810-266-4687

Date: 10/09/2018Propane Standby System Inspection Report

Submitted by MI Construction Service 2 at 10/09/2018 14:43 EDT Page: 1

Captured at 10/09/2018 14:42 EDT gocanvas.com

Submission ID: C5B5FB8F-4848-44F9-8106-FE307BE6713F https://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

Any leaks in piping from pumps to vaporizer? No

Hydrostatic relief valves in required locations? Yes

Checked hydrostatic reliefs for debris, weep hole location & that protective caps are in place.

Yes

VAPORIZER / MIXER UNIT INFORMATION

Manufacturer Ely energy

Model # Na

Serial # Na

Year Built 1990

Has Pilot Relighter? Yes

Has thermocouple? No

Gas valve Make/Model # Yes

Has power pile? Yes

High Mix (PSI) 6

Low Mix (PSI) 5

Pump PSI 120

Optimum Temp (Degrees F) 160

Low Temp (Degrees F) 150

High Temp (Degrees F) 165

High Propane 1

Low Propane 1

Vaporizer/Mixer Info Surge Tank

Vaporizer/Mixer Info Venturi Regulator (PSI)

#1 45

#2 35

#3 35

Vaporizer/Mixer Info Gas Mix Setting

#1 1.32

#2 1.32

#3 1.32

STORAGE TANK SPECIFICATIONS

Manufacturer Trinity

Serial # 118362

Capacity 30

Diameter (inches) 131

Length (feet) 561

Manway?

Magnetel?

Rotor Gauge?

PSI Gauge 100

Materials Used

Sa615

Inspector Ken Oswald

Facility Representative(s)

Tyler

Date of Inspection 10/09/2018

303 W. Maple St. PO Box 145

Byron, MI 48418

P) 810-266-4687

Date: 10/09/2018Propane Standby System Inspection Report

Submitted by MI Construction Service 2 at 10/09/2018 14:43 EDT Page: 2

Captured at 10/09/2018 14:42 EDT gocanvas.com

Submission ID: C5B5FB8F-4848-44F9-8106-FE307BE6713F