Pricing Proposal - Scenarios.pdf

PDF 3 MB Posted

Attached to
EWEB RFP 26-013-Q Joint Use Inspection, Make-Ready Requirements, & Pole Loading Analysis
Solicitation number
S-P00140-00015672
Issued by
Lane County, Oregon

About this file

This file contains pole loading analysis reports and permit application spreadsheets for the Eugene Water & Electric Board (EWEB) in Oregon related to a fiber attachment project in the Santa Clara Phase 1 service area. The documents present two scenarios: Scenario 1 addresses pre-inspection requirements for nine poles on Rudy Avenue with associated make-ready work coordination with existing cable attachments, and Scenario 2 extends the analysis to nineteen additional poles along Crowther Drive, Arrowhead Street, Lansdown Road, and Impala Avenue. Both scenarios include completed EWEB permit application spreadsheets documenting pole specifications, attachment details, existing infrastructure, and required make-ready tasks. The requesting entity is Hunter Communications, with contact information for Kenji Nagareda provided for coordination purposes. Multiple O-Calc Pro pole loading analysis reports accompany these scenarios, dated September 2025 and August 2025, evaluating structural capacity for individual poles under various wind loading conditions and providing detailed assessments of pole adequacy and required reinforcements.

The pole loading analysis reports detail structural evaluations for poles categorized by length, class, species, and construction grade, with most poles consisting of Douglas Fir or Western Fir construction. The analyses incorporate NESC Rule 250B standards, heavy transverse wind loading conditions at 39.53 mph, ice thickness specifications, and pole strength factors of 0.65. Reports indicate that several poles have inadequate or near-capacity guy wire systems, with specific deficiencies noted for poles 947, 953, 961, and 964 requiring anchor reinforcement or system upgrades. The make-ready requirements documented in the spreadsheets include lowering of existing Comcast attachments, placement of new anchors by Hunter, and coordination with multiple utility owners including EWEB, ELI, and CTL. The analysis establishes baseline conditions and requirements necessary for Hunter Communications to attach 48-count fiber cables to EWEB poles while maintaining compliance with National Electrical Safety Code standards and local utility requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Scenario 1 - Request for Pre-Inspection Needing Pole Loading

Example of EWEB Permit Application Spreadsheet: Page 1

Example of EWEB Permit Application Spreadsheet: Page 2

***Map – This might change to system maps that Jeb is currently working on getting

PA #

Location

EWEB Pole No.

Existing

Permit# New Permit # Self-Disclosed

Pole Address

(Location) Latitude Longitude

Height

(Ft. &

In.)

Attachment

Action

Attachment

Point Method

Attachment

Type

Attachment

Side

New

Cable

Name

Diam lbs/

Ft.

Diam lbs/

Ft.

Lowest

Power

Secondary

Street

Light

Mast

Street Light

Conductor Cable TV

Tele-phone Fiber

1 23599 PA7052013 225 RUDY AVE 44.09914109 -123.1337847 20'5 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 24'2 20'5

2 26053 PA7052013 225 RUDY AVE 44.09886585 -123.13378 23'2 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 26'9 22'2

3 9410 PA7052013 225 RUDY AVE 44.09878956 -123.1337768 22',21'8 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 25'9 26'10 25'8 22',21'8

4 6979 PA7052013 199 RUDY AVE 44.09881371 -123.1331051 24'2 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 27'10 26'7 26'3 23'2

5 6978 PA7052013 197 RUDY AVE 44.09883909 -123.1324378 22'9 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 26'3 25'8 25'4 22'8

6 6976 PA7052013 127 RUDY AVE 44.0988675 -123.1318121 22' New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 26'11 28'5 28'1 21'

7 6975 PA7052013 105 RUDY AVE 44.09889495 -123.1311939 22'3 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 26'2 27'4 21'3

8 6974 PA7052013 85 RUDY AVE 44.09891699 -123.1305599 22'6 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 26'9 25'9 25'5 22'6

9 33745 PA7052013 75 RUDY AVE 44.09893096 -123.1303004 23'4 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 27'3 26'3 26'2 23'4

Santa Clara

Pole Number and Location Information New Cable Information Total Bundle

Existing Attachments

List distance from attachment to ground or street surface (Ft. & In.)Proposed Attachment

Project Name Zone 115 Santa Clara Ph 1

EWEB PERMIT APPLICATION SPREADSHEET

APPENDIX D

Requesting Entity Hunter Communications PA7052013

Date

Contact / Phone Kenji Nagareda / 5413013257

Make Ready

Other

Lowest Comm.

Midspan

Midspan

Pole

Reference #

Span to

Next Pole

(Ft.)

Describe all Make Ready Required to complete your attachment in compliance with NESC and Local standards

NJUNS

Ticket # (PA, PT or N/A)

Pre-

Inspection

(Date)

Condtionally

Approved

(Date)

EWEB Make

Ready

Completed

(Date)

Resubmit Ready for Post

Inspection

(Date)

Permit Final

Approval

(Date) EWEB Comments

17'11 - Pedestrian A0402268

Hunter will work with Comcast to lower them to 19'5

21'11 - Pedestrian 23599 Hunter to place new anchor

21'8 - Pedestrian 26053

Hunter to place new anchor; Hunter will work with Comcast to lower them to 20'2, 20'8

16'11 - Driveway 9410

17'6 - Driveway 6979 Lower Comcast to 21'9

18'7 - Driveway 6978

18'11 - Driveway 6976

16'1 - Driveway 6975 Lower Comcast to 21'6

18'7 - Pedestrian 6974

Hunter to place new anchor; Hunter will work with Comcast to lower them to 22'4

Make Ready Needed &

Approved (Date)

Existing Attachments

List distance from attachment to ground or street surface (Ft. & In.)

9/5/2025 d2d2 d2d2

6 6

6#

6#

6#

6#

6# 6#

6 6

6 6

6# òÝ òÝ òÝ òÝ

174 158

50 50

50177209 129 117

50 50

125 101

138144180180 1322453

150150

5050250

46147

115 105

144144

120162250

120156162

50 50

50 50

50 5050

50159215 135 103

186 126126

150 1502481

120120

230 210

2515225 199

138180

156162194

50116220

150 90

50118

50162

50 50

50 50

50 50153

50 50

197 127

138180

120162

50 50194 154

64110 5062 50238

50 50 50

50260

50 5094 70

50 50

132 130

DIVISION AVE

RUBY AVE

QUINCE ST

QUINCE ST

BELTLINE RD

JA

SM

IN

E S

T

BELTLINE RD

BELTLINE RD

RIVER RD

LEA AVE

SANTA CLARA AVE

RUBY AVE

868 COMCAST

EWEB None

6976 None

COMCAST

23514 ELI

19544 ELI

COMCAST

6974 None

COMCAST

23512 ELI

23599 COMCAST

19373

EWEB

COMCAST

31897

None

COMCAST

6979 COMCAST

862 COMCAST

EWEB None18976 EWEB

COMCAST None

6978 None

COMCAST

18551

COMCAST

EWEB

23513 ELI

23598

COMCAST

EWEB

23600 COMCAST

30892 COMCAST

23511 ELI

31898

6926 EWEB

COMCAST

31895

6975 None

COMCAST

861 COMCAST

EWEB None

19677 EWEB

COMCAST

33745 COMCAST

27682

865 EWEB

COMCAST None

18975 EWEB

COMCAST

864 COMCAST

EWEB None

34456

19374

COMCAST

EWEB

31896

26053 COMCAST

25170

COMCAST CTL

COMCAST

None

19676

COMCAST

EWEB

18977

COMCAST CTL

Scenario 2 - Request for Pre-Inspection with Pole Loading

Pole loading reports, EWEB Permit Application Spreadsheet and Map will be attached to request.

Checking Pole Stubs – Ready to be Pulled

PA #

Location

EWEB Pole No.

Existing

Permit#

New Permit

Self-

Disclosed

Pole Address

(Location) Latitude Longitude

Height

(Ft. &

In.)

Attachment

Action

Attachment

Point Method

Attachment

Type

Attachment

Side

New

Cable

Name

Diam lbs/

Ft.

Diam lbs/

Ft.

Lowest

Power

Secondary

Street

Light

Mast

Street Light

Conductor Cable TV

Tele-phone Fiber

Other

1 966 2602 CROWTHER DR 44.10310853 -123.157506

22'9, 23'1 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35' 23'1 24'1

2 965 2616 CROWTHER DR 44.10310309 -123.1568336 22'11 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 37'10 22'11 23'11

3 964 2644 CROWTHER DR 44.10313313 -123.1561751 20'8 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 38'2 37' 36'11 21'10 23'11

4 963 2668 CROETHER DR 44.10312687 -123.1555085 21'5 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35'6 31'2 30'10 20'5 22'5

5 961 2682 CROETHER DR 44.10313254 -123.1548264 23'8 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 36'10 22'5 24'8

6 33140 IRVING RD 44.1033 -123.1548542 23'1 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 36'3 32'10 32'5 22'1

7 960 2698 CROWTHER DR 44.10313069 -123.1541779 22'11 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 33'1 28'6 27'11 22'11 24'1

8 959

2720 ARROWHEAD

ST 44.10313887 -123.1535181 23'8 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 36'4 32'1 32'3 22'6 24'8

9 958

2720 ARROWHEAD

ST 44.1031615 -123.1527926 22'7 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35'3 30'5 30'3 21'7 23'7

10 957 2693 LANSDOWN RD 44.10318751 -123.1520342 23' New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 36'3 31'7 31'5 21'11 24'

11 955 977 IMPALA AVE 44.10326455 -123.1512074 23'7 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35'1 22'7 26'3

Santa Clara

Pole Number and Location Information New Cable Information Total Bundle

Existing Attachments

List distance from attachment to ground or street surface (Ft. & In.)Proposed Attachment

Project Name Zone 115 Santa Clara Ph. 1

EWEB PERMIT APPLICATION SPREADSHEET

APPENDIX D

Requesting Entity Hunter Communications PA7059552

12 953 977 IMPALA AVE 44.10335122 -123.1499776 23'6 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 34'8 30'11 31'11 22'4 24'6

13 952 855 IMPALA AVE 44.10337048 -123.1489691 22'8 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35'7 33'3 36'8 21'8

14 949 860 IRVING RD 44.10336759 -123.1481832 22' New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 34'8 21'

15 948

2694 CANTERBURY

ST 44.10336904 -123.1474697 23'1 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 37'2 33'9 22'1

16 947

2694 CANTERBURY

ST 44.10337193 -123.1468864 26'1 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35'9 32'6 34'9 23'8 25'1

17 946 2691 CARBONA ST 44.10337275 -123.1460654 22'4 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 36'3 32'1 31'4 20'2

18 945 2696 DONEGAL ST 44.10337481 -123.1456559 23'11 New

Three Bolt

Clamp

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 35' 32'1 34'3 21'9

19 35334 40 IRVING DR 44.10336037 -123.1326312 24'2 New Thimble Eye

Fiber and strand

Following existing comms

48 Count

Fiber 0.4 0.047 0.65 0.117 34'8 22' 19'9

Date

Contact / Phone Kenji Nagareda / 5413013257

Make Ready

Lowest Comm.

Midspan

Midspan

Pole

Reference #

Span to

Next Pole

(Ft.)

Describe all Make Ready Required to complete your attachment in compliance with NESC and Local standards

NJUNS

Ticket # (PA, PT or N/A)

Pre-

Inspection

(Date)

Condtionally

Approved

(Date)

EWEB Make

Ready

Completed

(Date)

Resubmit Ready for Post

Inspection

(Date)

Permit Final

Approval

(Date) EWEB Comments

21'9 - Roadway 25450

Hunter to place new anchor; Hunter will work with Comcast to lower them to 22'1

24'11 - Pedestrian 966

Hunter to place new anchor; Hunter will work with Comcast to lower them to 21'11

20' - Pedestrian 965

Hunter will work with Comcast to lower them to 19'8

20'3 - Roadway 964

19'10 - Pedestrian 963 Hunter to place new anchor

21'1 - Roadway 961

22'4 - Pedestrian 961

Hunter will work with Comcast to lower them to 21'11

21'5 - Pedestrian 960

21'1 - Pedestrian 959

20' - Roadway 958 Hunter to place new anchor

20'11 - Pedestrian 957

Make Ready Needed &

Approved (Date)

List distance from attachment to ground or street surface (Ft. & In.)

9/9/2025

20' - Roadway 955

18'10 - Pedestrian 953

18'7 - Driveway 952

19'9 - Driveway 949

21'1 - Roadway 948

17'11 - Roadway 947

20'1 - Pedestrian 946

14'8 - Driveway 915 Hunter to place new anchor

Pole ID:Not Saved O-Calc® Pro Analysis Report Report Created: 9/9/2025 8:56 AM

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 1 of 5 2 Worst Wind Per Guy Wire 3 Wind At 180.5°

Pole Num: A0402284 Pole Length / Class: 60 / 1 Code: NESC Structure Type: Unguyed Tangent Aux Data 1 Unset Species: DOUGLAS FIR NESC Rule: Rule 250B Status: Unguyed Aux Data 2 Unset Setting Depth (ft): 8.0 Construction Grade: B Pole Strength Factor: 0.65 Aux Data 3 Unset G/L Circumference (in): 47.22 Loading District: Heavy Transverse Wind LF: 2.50 Aux Data 4 Unset G/L Fiber Stress (psi): 8,000 Ice Thickness (in): 0.50 Wire Tension LF: 1.10 Aux Data 5 Unset Allowable Stress (psi): 5,200 Wind Speed (mph): 39.53 Vertical LF: 1.50 Aux Data 6 Unset Fiber Stress Ht. Reduc: No Wind Pressure (psf): 4.00 Latitude: 44.103375 Longitude: -123.145664 Elevation: 117.9M

Pole Capacity Utilization (%) Height (ft)

Wind Angle (deg)

Maximum 76.4 0.0 180.5 Groundline 76.4 0.0 180.5 Vertical 17.5 32.3 180.5

Pole Moments (ft-lb) Load Angle (deg)

Wind Angle (deg)

Max Cap Util 109,148 180.1 180.5 Groundline 109,148 180.1 180.5 GL Allowable 144,481

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 2 of 5 2 Worst Wind Per Guy Wire 3 Wind At 180.5°

Groundline Load Summary - Reporting Angle Mode: Load - Reporting Angle: 180.1° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

Powers 1,528 49.3 72,986 66.9 50.5 2,652 1,907 11 2,662 51.2 Comms 800 25.8 17,379 15.9 12.0 631 1,065 6 637 12.3 PowerEquipments 60 1.9 2,304 2.1 1.6 84 548 3 87 1.7 Pole 512 16.5 12,767 11.7 8.8 464 3,650 21 484 9.3 Crossarms 4 0.1 166 0.2 0.1 6 148 1 7 0.1 Streetlights 46 1.5 506 0.5 0.4 18 128 1 19 0.4 Risers 137 4.4 2,519 2.3 1.7 92 83 0 92 1.8 Insulators 11 0.4 521 0.5 0.4 19 92 1 19 0.4 Pole Load 3,096 100.0 109,148 100.0 75.5 3,965 7,620 43 4,008 77.1 Pole Reserve Capacity 35,333 24.5 1,235 1,192 22.9

Load Summary by Owner - Reporting Angle Mode: Load - Reporting Angle: 180.1° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

<Undefined> 2,584 83.5 96,381 88.3 66.7 3,501 3,970 22 3,524 67.8 Pole 512 16.5 12,767 11.7 8.8 464 3,650 21 484 9.3 Totals: 3,096 100.0 109,148 100.0 75.5 3,965 7,620 43 4,008 77.1

Detailed Load Components:

Power Owner Height

(ft) Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.31 11.73 0.8560 2.58 0.521 175.5 89.8 175.5 2,373 -703 -149 6,903 6,051

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.31 11.73 0.8560 1.19 0.521 105.1 269.1 105.1 2,373 2,381 -78 4,131 6,433

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.31 39.04 0.8560 2.58 0.521 175.5 89.8 175.5 2,373 -703 -578 6,903 5,622

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.31 39.04 0.8560 1.19 0.521 105.0 269.1 105.0 2,373 2,381 -304 4,129 6,207

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.31 39.65 0.8560 2.58 0.521 175.5 89.8 175.5 2,373 -703 589 6,902 6,788

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.31 39.65 0.8560 1.19 0.521 105.1 269.1 105.1 2,373 2,380 309 4,132 6,821

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 3 of 5 2 Worst Wind Per Guy Wire 3 Wind At 180.5°

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.39 45.71 0.8560 2.58 0.521 175.5 89.8 175.5 2,373 -622 -679 6,107 4,807

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.39 45.71 0.8560 1.19 0.521 105.0 269.1 105.0 2,373 2,106 -355 3,653 5,404

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.39 23.21 0.8560 2.58 0.521 175.5 89.8 175.5 2,373 -622 335 6,106 5,820

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.39 23.21 0.8560 1.19 0.521 105.1 269.1 105.1 2,373 2,105 176 3,656 5,937

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.39 45.78 0.8560 2.58 0.521 175.5 89.8 175.5 2,373 -622 681 6,106 6,166

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.39 45.78 0.8560 1.19 0.521 105.1 269.1 105.1 2,373 2,105 357 3,656 6,117

Neutral 1/0 COPPER 7

STRAND

36.64 7.75 0.3684 0.74 0.326 87.7 312.1 87.8 247 -6,600 -37 1,009 -5,628

Neutral 1/0 COPPER 7

STRAND

36.25 7.77 0.3684 2.10 0.326 174.9 90.1 174.9 1,452 -70 -73 3,581 3,438

Neutral 1/0 COPPER 7

STRAND

36.25 7.77 0.3684 1.01 0.326 105.1 269.1 105.1 1,263 898 -45 2,150 3,003

Totals: 3,713 149 69,125 72,986

Comm Owner Height (ft)

Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Overlashed Bundle 1/4" EHS 23.92 8.54 0.2500 4.89 0.121 174.8 90.1 175.1 400 -13 -57 2,685 2,615 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

23.87 8.54 0.8300 0.275 174.8 90.1 175.1 -71 957 886

Overlashed Bundle 1/4" EHS 23.92 8.54 0.2500 2.14 0.121 105.1 269.1 105.1 400 187 -33 1,613 1,766 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

23.87 8.54 0.8300 0.275 105.1 269.1 105.1 -42 575 533

Overlashed Bundle 1/4" EHS 22.92 8.60 0.2500 7.50 0.121 174.8 90.1 175.8 400 -12 -69 2,935 2,854

CATV CATV .50 22.83 8.60 0.5700 0.600 174.8 90.1 175.8 -114 1,276 1,162

Overlashed Bundle 1/4" EHS 22.92 8.60 0.2500 2.99 0.121 105.1 269.1 105.3 400 179 -41 1,763 1,901

CATV CATV .50 22.83 8.60 0.5700 0.600 105.1 269.1 105.3 -67 767 699

Overlashed Bundle 1/4" EHS 21.75 8.67 0.2500 7.45 0.121 174.8 90.1 175.8 400 -11 -55 2,361 2,296

CATV CATV .50 21.70 8.67 0.5700 0.600 174.8 90.1 175.8 -99 791 691

Overlashed Bundle 1/4" EHS 21.75 8.67 0.2500 2.95 0.121 105.1 269.1 105.3 400 170 -32 1,419 1,556

CATV CATV .50 21.70 8.67 0.5700 0.600 105.1 269.1 105.3 -59 475 416

Totals: 500 -739 17,617 17,379

PowerEquipment Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Transformer 1PH-25KVA 39.17 22.09 89.7 89.7 365.00 39.00 -- 22.00 -- -8 2,312 2,304 Totals: -8 2,312 2,304

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 4 of 5 2 Worst Wind Per Guy Wire 3 Wind At 180.5°

Crossarm Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth (in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Normal CROSSARM 3-1/2 X 4-

1/2 X 7

50.50 -6.14 89.7 89.7 46.00 4.50 3.50 84.00 0 88 88

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

44.58 -6.51 89.7 89.7 53.00 4.50 3.50 96.00 0 78 78

Totals: 1 165 166

Streetlight Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

General Streetlight - 10 ft. Arm 32.08 5.53 359.7 359.7 85.00 24.00 20.00 3.00 120.00 -951 1,457 506 Totals: -951 1,457 506

Riser Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Riser 89.7° H:20.83 Riser 20.83 7.76 89.7 89.7 20.83 249.96 4.00 4.00 249.96 0 955 955 Riser 129.7° H:34.67 Riser 34.67 7.76 129.7 129.7 34.67 416.04 3.00 3.00 416.04 25 1,540 1,564

Totals: 24 2,495 2,519

Insulator Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Pin Pin 7.5" 50.69 -10.00 328.1 -1.9 6.00 3.50 7.50 0 92 92 Pin Pin 7.5" 50.69 -38.55 350.6 -1.9 6.00 3.50 7.50 0 92 92 Pin Pin 7.5" 50.69 39.17 188.6 -1.9 6.00 3.50 7.50 0 92 92 Pin Pin 7.5" 44.77 -45.24 351.5 89.2 6.00 3.50 7.50 0 81 81 Pin Pin 7.5" 44.77 22.28 195.9 89.3 6.00 3.50 7.50 0 81 81 Pin Pin 7.5" 44.77 45.31 187.8 89.2 6.00 3.50 7.50 0 81 81 Bolt Three Bolt 36.64 0.00 359.1 -0.5 5.00 3.00 0.10 0 1 1 Bolt Three Bolt 36.25 0.00 353.9 174.2 5.00 3.00 0.10 0 1 1 Bolt Three Bolt 23.92 0.00 359.7 0.0 5.00 3.00 0.10 0 0 0 Bolt Single Bolt 22.92 0.00 359.7 0.0 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 21.75 0.00 359.7 0.0 5.00 3.00 0.10 0 0 0

Totals: 0 521 521

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 5 of 5 2 Worst Wind Per Guy Wire 3 Wind At 180.5°

Pole Buckling Buckling Constant

Buckling Column Height*

(ft)

Buckling Section Height

(% Buckling Col. Hgt.)

Buckling Section

Diameter (in)

Minimum Buckling

Diameter at

GL

(in)

Diameter at Tip (in)

Diameter at

GL

(in)

Modulus of Elasticity

(psi)

Pole Density

(pcf)

Ice Density (pcf)

Pole Tip Height

(ft)

Buckling Load

Capacity at Height (lbs)

Buckling Load

Applied at Height (lbs)

Buckling Load Factor of Safety

2.00 32.30 33.99 13.67 9.72 8.60 15.04 2.38e+6 60.00 56.00 52.00 43,579 435.44 5.71

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 1 of 5 2 Worst Wind Per Guy Wire 3 Wind At 358.6°

Pole Num: 946 Pole Length / Class: 60 / 1 Code: NESC Structure Type: Guyed Tangent Aux Data 1 Unset Species: DOUGLAS FIR NESC Rule: Rule 250B Status: Guy Wires Adequate Aux Data 2 Unset Setting Depth (ft): 8.25 Construction Grade: B Pole Strength Factor: 0.65 Aux Data 3 Unset G/L Circumference (in): 47.13 Loading District: Heavy Transverse Wind LF: 2.50 Aux Data 4 Unset G/L Fiber Stress (psi): 8,000 Ice Thickness (in): 0.50 Wire Tension LF: 1.65 Aux Data 5 Unset Allowable Stress (psi): 5,200 Wind Speed (mph): 39.53 Vertical LF: 1.50 Aux Data 6 Unset Fiber Stress Ht. Reduc: No Wind Pressure (psf): 4.00 Latitude: 44.103371 Longitude: -123.146065 Elevation: 117.8M

Pole Capacity Utilization (%) Height (ft)

Wind Angle (deg)

Maximum 74.7 22.3 358.6 Groundline 64.7 0.0 179.3 Vertical 4.7 26.1 0.4

Pole Moments (ft-lb) Load Angle (deg)

Wind Angle (deg)

Max Cap Util 55,095 355.6 358.6 Groundline 8,431 328.0 179.3 GL Allowable 143,591 Overturn 181,182

Guy System Component Summary Load From Worst Wind Angle on Pole

Individual Maximum Load With Overload Applied

Description Lead Length (ft)

Lead Angle (deg)

Height (ft)

Nominal Capacity (%)

Wind Angle (deg)

Max* Load Capacity (%)

Wind Angle (deg)

? Single - 14" - Soil Class 4 10.0 180.4 44.9 358.6 74.0 359.3 ? EHS 9/16 (Down) 22.3 44.1 358.6 72.8 359.3

System Capacity Summary: Adequate Adequate

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 2 of 5 2 Worst Wind Per Guy Wire 3 Wind At 358.6°

Groundline Load Summary - Reporting Angle Mode: Load - Reporting Angle: 328.0° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

Powers 1,717 -141.8 36,357 431.2 25.3 2,956 2,321 13 2,969 57.1 Comms 1,054 -87.0 10,139 120.3 7.1 824 1,265 7 832 16.0 GuyBraces -4,594 379.3 -45,689 -541.9 -31.8 -3,715 19,224 109 -3,606 -69.3 Pole 438 -36.2 4,887 58.0 3.4 397 3,622 20 418 8.0 Crossarms 11 -0.9 251 3.0 0.2 20 387 2 23 0.4 Streetlights 39 -3.3 926 11.0 0.6 75 128 1 76 1.5 Risers 107 -8.9 1,198 14.2 0.8 97 56 0 98 1.9 Insulators 17 -1.4 362 4.3 0.3 29 106 1 30 0.6 Pole Load -1,211 100.0 8,431 100.0 5.9 686 27,109 153 839 16.1 Pole Reserve Capacity 135,160 94.1 4,515 4,361 83.9

Load Summary by Owner - Reporting Angle Mode: Load - Reporting Angle: 328.0° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

<Undefined> -1,649 136.2 3,544 42.0 2.5 288 23,486 133 421 8.1 Pole 438 -36.2 4,887 58.0 3.4 397 3,622 20 418 8.0 Totals: -1,211 100.0 8,431 100.0 5.9 686 27,109 153 839 16.1

Detailed Load Components:

Power Owner Height

(ft) Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Primary AAC 556.5 KCM 19

STRAND DAHLIA

52.14 11.70 0.8560 1.19 0.521 105.1 89.1 105.1 2,731 -8,437 8 252 -8,177

Primary AAC 556.5 KCM 19

STRAND DAHLIA

52.14 11.70 0.8560 3.01 0.521 215.0 269.6 215.0 2,731 8,555 16 512 9,083

Primary AAC 556.5 KCM 19

STRAND DAHLIA

52.14 39.03 0.8560 1.19 0.521 105.0 89.1 105.0 2,731 -8,437 25 252 -8,161

Primary AAC 556.5 KCM 19

STRAND DAHLIA

52.14 39.03 0.8560 3.01 0.521 215.0 269.6 215.0 2,731 8,555 48 512 9,116

Primary AAC 556.5 KCM 19

STRAND DAHLIA

52.14 39.64 0.8560 1.19 0.521 105.1 89.1 105.1 2,731 -8,437 -21 252 -8,206

Primary AAC 556.5 KCM 19

52.14 39.64 0.8560 3.01 0.521 215.0 269.6 215.0 2,731 8,555 -40 512 9,027

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 3 of 5 2 Worst Wind Per Guy Wire 3 Wind At 358.6°

Primary AAC 556.5 KCM 19

STRAND DAHLIA

46.23 45.70 0.8560 1.19 0.521 105.0 89.1 105.0 2,731 -7,482 29 223 -7,230

Primary AAC 556.5 KCM 19

STRAND DAHLIA

46.23 45.70 0.8560 3.01 0.521 215.0 269.6 215.0 2,731 7,588 56 454 8,098

Primary AAC 556.5 KCM 19

STRAND DAHLIA

46.23 23.19 0.8560 1.19 0.521 105.1 89.1 105.1 2,731 -7,482 -11 223 -7,269

Primary AAC 556.5 KCM 19

STRAND DAHLIA

46.23 23.19 0.8560 3.01 0.521 215.0 269.6 215.0 2,731 7,596 -21 454 8,029

Primary AAC 556.5 KCM 19

STRAND DAHLIA

46.23 45.77 0.8560 1.19 0.521 105.1 89.1 105.1 2,731 -7,482 -24 223 -7,282

Primary AAC 556.5 KCM 19

STRAND DAHLIA

46.23 45.77 0.8560 3.01 0.521 215.0 269.6 215.0 2,731 7,582 -47 454 7,989

Neutral 1/0 COPPER 7

STRAND

36.33 7.75 0.3684 1.01 0.326 105.1 89.1 105.1 1,263 -2,716 3 129 -2,584

Neutral 1/0 COPPER 7

STRAND

36.33 7.75 0.3684 3.08 0.326 214.9 269.6 215.0 1,358 2,963 6 263 3,232

Totals: 920 27 4,717 5,664

Comm Owner Height (ft)

Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Overlashed Bundle 1/4" EHS 22.33 8.62 0.2500 2.14 0.121 105.1 89.1 106.2 400 -529 2 90 -436 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

22.28 8.62 0.8300 0.275 105.1 89.1 106.2 3 32 35

Overlashed Bundle 1/4" EHS 22.33 8.62 0.2500 6.96 0.121 214.9 269.6 215.5 400 536 4 184 724 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

22.28 8.62 0.8300 0.275 214.9 269.6 215.5 5 66 71

Overlashed Bundle 1/4" EHS 21.33 8.68 0.2500 2.99 0.121 105.1 89.1 108.6 400 -505 3 98 -404

CATV CATV .50 21.24 8.68 0.5700 0.600 105.1 89.1 108.6 4 43 47

Overlashed Bundle 1/4" EHS 21.33 8.68 0.2500 11.01 0.121 214.2 269.4 216.0 400 509 5 200 715

CATV CATV .50 21.24 8.68 0.5700 0.600 214.2 269.4 216.0 8 87 95

Overlashed Bundle 1/4" EHS 20.08 8.76 0.2500 2.95 0.121 105.1 89.1 108.6 400 -476 2 79 -395

CATV CATV .50 20.03 8.76 0.5700 0.600 105.1 89.1 108.6 4 26 30

Overlashed Bundle 1/4" EHS 20.08 8.76 0.2500 11.02 0.121 214.9 269.6 216.8 400 482 4 160 646

CATV CATV .50 20.03 8.76 0.5700 0.600 214.9 269.6 216.8 7 54 61

Overlashed Bundle 1/4" EHS 20.08 8.76 0.2500 1.52 0.121 71.8 30.4 71.9 333 355 -1 29 383

CATV CATV .50 20.03 8.76 0.5700 0.600 71.8 30.4 71.9 -2 10 8

Totals: 373 49 1,157 1,580

Crossarm Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth (in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Normal CROSSARM 3-1/2 X 4-

1/2 X 7

51.33 -6.07 90.4 90.4 46.00 4.50 3.50 84.00 1 8 9

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 4 of 5 2 Worst Wind Per Guy Wire 3 Wind At 358.6°

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

48.83 6.23 90.4 90.4 53.00 4.50 3.50 96.00 -2 8 6

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

48.33 6.26 90.4 90.4 53.00 4.50 3.50 96.00 0 15 15

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

45.42 -6.44 90.4 90.4 53.00 4.50 3.50 96.00 2 7 9

Totals: 1 38 39

Streetlight Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

General Streetlight - 10 ft. Arm 32.17 5.51 0.4 0.4 85.00 24.00 20.00 3.00 120.00 56 88 144 Totals: 56 88 144

Riser Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Riser 270.4° H:37.42 Riser 37.42 7.76 270.4 270.4 37.42 449.04 4.00 4.00 449.04 1 186 187 Totals: 1 186 187

Insulator Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Pin Pin 7.5" 51.52 -10.00 329.1 -1.9 6.00 3.50 7.50 0 6 6 Pin Pin 7.5" 51.52 -38.55 351.4 -1.9 6.00 3.50 7.50 0 6 6 Pin Pin 7.5" 51.52 39.17 189.2 -1.9 6.00 3.50 7.50 0 6 6 Deadend Deadend 12.75" 48.83 39.46 171.4 0.0 3.00 3.80 12.75 0 12 12 Deadend Deadend 12.75" 48.83 -40.69 9.1 0.0 3.00 3.80 12.75 0 12 12 Pin Pin 7.5" 45.61 -45.24 352.2 89.2 6.00 3.50 7.50 0 5 5 Pin Pin 7.5" 45.61 22.28 196.5 89.3 6.00 3.50 7.50 0 5 5 Pin Pin 7.5" 45.61 45.31 188.4 89.2 6.00 3.50 7.50 0 5 5 Bolt Three Bolt 36.33 0.00 354.6 174.2 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 22.33 0.00 0.4 0.0 5.00 3.00 0.10 0 0 0 Bolt Single Bolt 21.33 0.00 0.4 0.0 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 20.08 0.00 0.4 0.0 5.00 3.00 0.10 0 0 0 Bolt Single Bolt 20.08 0.00 90.4 0.0 5.00 3.00 0.10 0 0 0

Totals: 0 56 56

Guy Wire and Brace Owner Attach Height

(ft)

End Height (ft)

Lead/Span Length

(ft)

Wire Diameter

(in)

Percent Solid

Lead Angle (deg)

Incline Angle (deg)

Wire Weight (lbs/ft)

Rest Length (ft)

Stretch Length

(in)

EHS 9/16 Down 22.33 0.00 10.00 0.562 75.00 180.4 65.6 0.67 32.02 1.25

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 5 of 5 2 Worst Wind Per Guy Wire 3 Wind At 358.6°

Guy Wire and Brace (Loads and Reactions)

Elastic Modulus

(psi)

Rated Tensile

Strength (lbs)

Guy Strength Factor

Allowable Tension

(lbs)

Initial Tension

(lbs)

Loaded Tension*²

(lbs)

Maximum Tension²

(lbs)

Applied Tension³

(lbs)

Vertical Load (lbs)

Shear Load In Guy Dir

(lbs)

Shear Load At Report

Angle (lbs)

Proportional Moment at

GL³

(ft-lb)

EHS 9/16 Down 2.30e+7 35,000 0.90 31,500 700 22,945 13,906 13,905 12,666 5,738 -4,845 -45,689

Totals: 12,666 5,738 -4,845 -45,689

Anchor/Rod Load Summary Owner Rod Length

AGL

(in)

Lead Length (ft)

Lead Angle (deg)

Strength of Assembly

(lbs)

Anchor/Rod Strength Factor

Allowable Load (lbs)

Max Load² (lbs)

Load at Pole

MCU³

(lbs)

Max Required

Capacity² (%) Single - 14" - Soil Class 4 0.00 10.00 180.4 31,000 1.00 31,000 22,945 13,905 74.0

Pole Buckling Buckling Constant

Buckling Column Height*

(ft)

Buckling Section Height

(% Buckling Col. Hgt.)

Buckling Section

Diameter (in)

Minimum Buckling

Diameter at

GL

(in)

Diameter at Tip (in)

Diameter at

GL

(in)

Modulus of Elasticity

(psi)

Pole Density

(pcf)

Ice Density (pcf)

Pole Tip Height

(ft)

Buckling Load

Capacity at Height (lbs)

Buckling Load

Applied at Height (lbs)

Buckling Load Factor

0.71 26.10 33.23 13.93 6.99 8.60 15.01 2.38e+6 60.00 56.00 51.75 574,888 5767.80 21.28

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 1 of 5 2 Worst Wind Per Guy Wire 3 Wind At 359.3°

Pole Num: 947 Pole Length / Class: 75 / H1 Code: NESC Structure Type: Guyed Tangent Aux Data 1 Unset Species: DOUGLAS FIR NESC Rule: Rule 250B Status: Guy Wires Inadequate Aux Data 2 Unset Setting Depth (ft): 23.58 Construction Grade: B Pole Strength Factor: 0.65 Aux Data 3 Unset G/L Circumference (in): 48.75 Loading District: Heavy Transverse Wind LF: 2.50 Aux Data 4 Unset G/L Fiber Stress (psi): 8,000 Ice Thickness (in): 0.50 Wire Tension LF: 1.65 Aux Data 5 Unset Allowable Stress (psi): 5,200 Wind Speed (mph): 39.53 Vertical LF: 1.50 Aux Data 6 Unset Fiber Stress Ht. Reduc: No Wind Pressure (psf): 4.00 Latitude: 44.103367 Longitude: -123.146886 Elevation: 117.6M

Pole Capacity Utilization (%) Height (ft)

Wind Angle (deg)

Maximum 74.2 36.3 359.3 Groundline 40.8 0.0 353.5 Vertical 29.1 35.2 40.3

Pole Moments (ft-lb) Load Angle (deg)

Wind Angle (deg)

Max Cap Util 42,921 359.3 359.3 Groundline 64,663 351.1 353.5 GL Allowable 158,946 Overturn 8.46e+6

Guy System Component Summary Load From Worst Wind Angle on Pole

Individual Maximum Load With Overload Applied

Description Lead Length (ft)

Lead Angle (deg)

Height (ft)

Nominal Capacity (%)

Wind Angle (deg)

Max* Load Capacity (%)

Wind Angle (deg)

? F13-14-12-10" Triple Helix 6.0 180.3 78.2 359.3 129.1 356.9 ? EHS 5/8 (Down) 36.1 92.2 359.3 152.2 356.9 ? Single - 14" - Soil Class 4 16.0 260.3 7.6 359.3 27.8 90.0 ? EHS 5/8 (Down) 24.5 6.1 359.3 22.6 90.0

System Capacity Summary: Near Capacity Inadequate

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 2 of 5 2 Worst Wind Per Guy Wire 3 Wind At 359.3°

Groundline Load Summary - Reporting Angle Mode: Load - Reporting Angle: 351.1° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

Powers 5,019 211.7 142,895 221.0 89.9 7,279 2,660 14 7,293 140.3 Comms 1,850 78.0 29,664 45.9 18.7 1,511 1,471 8 1,519 29.2 GuyBraces -5,258 -221.8 -121,883 -188.5 -76.7 -6,209 55,261 292 -5,916 -113.8 Pole 525 22.1 8,445 13.1 5.3 430 3,948 21 451 8.7 Crossarms 99 4.2 2,724 4.2 1.7 139 308 2 140 2.7 Streetlights 45 1.9 1,557 2.4 1.0 79 128 1 80 1.5 Risers 70 2.9 651 1.0 0.4 33 33 0 33 0.6 Insulators 21 0.9 611 0.9 0.4 31 120 1 32 0.6 Pole Load 2,371 100.0 64,663 100.0 40.7 3,294 63,928 338 3,632 69.8 Pole Reserve Capacity 94,283 59.3 1,906 1,568 30.2

Load Summary by Owner - Reporting Angle Mode: Load - Reporting Angle: 351.1° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

<Undefined> 1,846 77.9 56,218 86.9 35.4 2,864 59,980 317 3,181 61.2 Pole 525 22.1 8,445 13.1 5.3 430 3,948 21 451 8.7 Totals: 2,371 100.0 64,663 100.0 40.7 3,294 63,928 338 3,632 69.8

Detailed Load Components:

Power Owner Height

(ft) Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.39 11.88 0.8560 3.01 0.521 215.0 89.6 215.0 2,764 -7,684 41 1,883 -5,761

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.39 11.88 0.8560 1.92 0.521 153.0 270.3 153.0 2,764 8,346 26 1,337 9,708

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.39 39.08 0.8560 3.01 0.521 215.0 89.6 215.0 2,764 -7,684 146 1,883 -5,656

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.39 39.08 0.8560 1.92 0.521 153.0 270.3 153.0 2,764 8,346 92 1,337 9,775

Primary AAC 556.5 KCM 19

STRAND DAHLIA

51.39 39.70 0.8560 3.01 0.521 215.0 89.6 215.0 2,764 -7,684 -140 1,883 -5,942

Primary AAC 556.5 KCM 19

51.39 39.70 0.8560 1.92 0.521 153.0 270.3 153.0 2,764 8,346 -88 1,337 9,595

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 3 of 5 2 Worst Wind Per Guy Wire 3 Wind At 359.3°

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.64 46.22 0.8560 3.01 0.521 215.0 89.6 215.0 2,764 -6,833 174 1,672 -4,987

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.64 46.22 0.8560 1.92 0.521 153.0 270.3 153.0 2,764 7,413 111 1,188 8,711

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.64 21.35 0.8560 3.01 0.521 215.0 89.6 215.0 2,764 -6,861 -71 1,672 -5,260

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.64 21.35 0.8560 1.92 0.521 153.0 270.3 153.0 2,764 7,413 -45 1,187 8,555

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.64 46.70 0.8560 3.01 0.521 215.0 89.6 215.0 2,764 -6,809 -168 1,672 -5,304

Primary AAC 556.5 KCM 19

STRAND DAHLIA

45.64 46.70 0.8560 1.92 0.521 153.0 270.3 153.0 2,764 7,413 -107 1,187 8,493

Primary AAC 556.5 KCM 19

STRAND DAHLIA

42.75 19.65 0.8560 1.24 0.521 110.7 3.1 110.8 488 7,485 12 11 7,509

Primary AAC 556.5 KCM 19

STRAND DAHLIA

42.75 46.44 0.8560 1.24 0.521 110.7 3.1 110.8 488 7,485 3 11 7,500

Primary AAC 556.5 KCM 19

STRAND DAHLIA

42.75 47.16 0.8560 1.24 0.521 110.6 3.1 110.7 488 7,485 7 11 7,503

Neutral 1/0 COPPER 7

STRAND

36.44 8.03 0.3684 1.36 0.326 113.2 3.3 113.3 247 3,224 12 8 3,245

Neutral 1/0 COPPER 7

STRAND

36.00 8.06 0.3684 3.08 0.326 214.9 89.6 215.0 1,358 -2,645 20 971 -1,654

Neutral 1/0 COPPER 7

STRAND

36.00 8.06 0.3684 1.81 0.326 153.0 270.3 153.0 1,323 2,799 13 690 3,502

Totals: 29,555 37 19,940 49,532

Comm Owner Height (ft)

Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Overlashed Bundle 1/4" EHS 26.08 8.66 0.2500 6.96 0.121 214.9 89.6 215.5 400 -564 15 800 252 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

26.03 8.66 0.8300 0.275 214.9 89.6 215.5 19 285 305

Overlashed Bundle 1/4" EHS 26.08 8.66 0.2500 3.92 0.121 153.0 270.3 153.2 400 613 11 568 1,193 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

26.03 8.66 0.8300 0.275 153.0 270.3 153.2 14 203 216

Overlashed Bundle 1/4" EHS 25.08 8.73 0.2500 3.30 0.121 112.5 3.1 112.9 333 3,001 10 6 3,017

CATV CATV .50 24.99 8.73 0.5700 0.600 112.5 3.1 112.9 16 3 19

Overlashed Bundle 1/4" EHS 24.42 8.77 0.2500 11.01 0.121 214.2 89.4 216.0 400 -516 -3 852 333

CATV CATV .50 24.33 8.77 0.5700 0.600 214.2 89.4 216.0 -5 371 366

Overlashed Bundle 1/4" EHS 23.67 8.81 0.2500 11.02 0.121 214.9 89.6 216.8 400 -512 15 702 206

CATV CATV .50 23.62 8.81 0.5700 0.600 214.9 89.6 216.8 27 235 262

Overlashed Bundle 1/4" EHS 23.67 8.81 0.2500 5.82 0.121 153.0 270.3 153.7 400 557 11 499 1,066

CATV CATV .50 23.62 8.81 0.5700 0.600 153.0 270.3 153.7 19 167 187

Overlashed Bundle 1/4" EHS 23.67 8.81 0.2500 3.30 0.121 112.5 3.1 112.9 333 2,832 8 5 2,845

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 4 of 5 2 Worst Wind Per Guy Wire 3 Wind At 359.3°

CATV CATV .50 23.62 8.81 0.5700 0.600 112.5 3.1 112.9 14 2 16

Totals: 5,412 172 4,699 10,283

Crossarm Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth (in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Normal CROSSARM 3-1/2 X 4-

1/2 X 7

50.58 -6.42 90.3 90.3 46.00 4.50 3.50 84.00 1 21 22

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

44.83 -6.77 90.3 90.3 53.00 4.50 3.50 96.00 2 19 20

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

42.75 6.90 0.3 0.3 53.00 4.50 3.50 96.00 0 902 902

Totals: 3 941 944

Streetlight Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

General Streetlight - 10 ft. Arm 32.50 5.77 0.3 0.3 85.00 24.00 20.00 3.00 120.00 211 328 540 Totals: 211 328 540

Riser Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Riser 105.3° H:22.0 Riser 22.00 8.96 105.3 105.3 22.00 264.00 4.00 4.00 264.00 -2 228 225 Totals: -2 228 225

Insulator Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Pin Pin 7.5" 50.77 -10.00 327.6 -1.9 6.00 3.50 7.50 0 20 20 Pin Pin 7.5" 50.77 -38.55 350.9 -1.9 6.00 3.50 7.50 0 20 20 Pin Pin 7.5" 50.77 39.17 189.6 -1.9 6.00 3.50 7.50 0 20 20 Pin Pin 7.5" 45.02 -45.72 351.9 -1.9 6.00 3.50 7.50 0 18 18 Pin Pin 7.5" 45.02 20.25 198.8 -1.9 6.00 3.50 7.50 0 18 18 Pin Pin 7.5" 45.02 46.21 188.7 -1.9 6.00 3.50 7.50 0 18 18 Deadend Deadend 12.75" 42.75 0.00 0.3 0.0 3.00 3.80 12.75 0 32 32 Deadend Deadend 12.75" 42.75 42.08 81.0 0.0 3.00 3.80 12.75 0 32 32 Deadend Deadend 12.75" 42.75 -42.87 279.5 0.0 3.00 3.80 12.75 0 32 32 Bolt Three Bolt 36.44 0.00 0.3 -0.1 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 36.00 0.00 354.6 174.2 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 26.08 0.00 0.3 0.0 5.00 3.00 0.10 0 0 0 Bolt Single Bolt 25.08 0.00 0.3 0.0 5.00 3.00 0.10 0 0 0 Bolt Single Bolt 24.42 0.00 90.3 0.0 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 23.67 0.00 0.3 0.0 5.00 3.00 0.10 0 0 0

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 5 of 5 2 Worst Wind Per Guy Wire 3 Wind At 359.3°

Bolt Three Bolt 23.67 0.00 0.3 180.0 5.00 3.00 0.10 0 0 0 Totals: 0 212 212

Guy Wire and Brace Owner Attach Height

(ft)

End Height (ft)

Lead/Span Length

(ft)

Wire Diameter

(in)

Percent Solid

Lead Angle (deg)

Incline Angle (deg)

Wire Weight (lbs/ft)

Rest Length (ft)

Stretch Length

(in)

EHS 5/8 Down 36.06 0.00 6.00 0.625 75.00 180.3 80.3 0.813 59.90 4.78 EHS 5/8 Down 24.50 0.00 16.00 0.625 75.00 260.3 56.7 0.813 50.51 0.27

Guy Wire and Brace (Loads and Reactions)

Elastic Modulus

(psi)

Rated Tensile

Strength (lbs)

Guy Strength Factor

Allowable Tension

(lbs)

Initial Tension

(lbs)

Loaded Tension*²

(lbs)

Maximum Tension²

(lbs)

Applied Tension³

(lbs)

Vertical Load (lbs)

Shear Load In Guy Dir

(lbs)

Shear Load At Report

Angle (lbs)

Proportional Moment at

GL³

(ft-lb)

EHS 5/8 Down 2.30e+7 42,400 0.90 38,160 700 58,079 35,199 35,191 34,685 5,948 -5,871 -122,139 EHS 5/8 Down 2.30e+7 42,400 0.90 38,160 700 8,621 5,225 2,347 1,960 1,290 -18 256

Totals: 36,645 7,238 -5,889 -121,883

Anchor/Rod Load Summary Owner Rod Length

AGL

(in)

Lead Length (ft)

Lead Angle (deg)

Strength of Assembly

(lbs)

Anchor/Rod Strength Factor

Allowable Load (lbs)

Max Load² (lbs)

Load at Pole

MCU³

(lbs)

Max Required

Capacity² (%) F13-14-12-10" Triple Helix 0.00 6.00 180.3 45,000 1.00 45,000 58,079 35,191 129.1 Single - 14" - Soil Class 4 0.00 16.00 260.3 31,000 1.00 31,000 8,621 2,347 27.8

Pole Buckling Buckling Constant

Buckling Column Height*

(ft)

Buckling Section Height

(% Buckling Col. Hgt.)

Buckling Section

Diameter (in)

Minimum Buckling

Diameter at

GL

(in)

Diameter at Tip (in)

Diameter at

GL

(in)

Modulus of Elasticity

(psi)

Pole Density

(pcf)

Ice Density (pcf)

Pole Tip Height

(ft)

Buckling Load

Capacity at Height (lbs)

Buckling Load

Applied at Height (lbs)

Buckling Load Factor

0.71 35.19 34.16 14.05 11.39 9.24 15.52 1.60e+6 60.00 56.00 51.42 220,032 2196.84 3.44

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 1 of 4 2 Worst Wind Per Guy Wire 3 Wind At 181.2°

Pole Num: 948 Pole Length / Class: 60 / H1 Code: NESC Structure Type: Unguyed Tangent Aux Data 1 Unset Species: DOUGLAS FIR NESC Rule: Rule 250B Status: Unguyed Aux Data 2 Unset Setting Depth (ft): 6.5 Construction Grade: B Pole Strength Factor: 0.65 Aux Data 3 Unset G/L Circumference (in): 50.80 Loading District: Heavy Transverse Wind LF: 2.50 Aux Data 4 Unset G/L Fiber Stress (psi): 8,000 Ice Thickness (in): 0.50 Wire Tension LF: 1.10 Aux Data 5 Unset Allowable Stress (psi): 5,200 Wind Speed (mph): 39.53 Vertical LF: 1.50 Aux Data 6 Unset Fiber Stress Ht. Reduc: No Wind Pressure (psf): 4.00 Latitude: 44.103369 Longitude: -123.14747 Elevation: 117.6M

Pole Capacity Utilization (%) Height (ft)

Wind Angle (deg)

Maximum 71.7 0.0 181.2 Groundline 71.7 0.0 181.2 Vertical 15.2 33.7 181.2

Pole Moments (ft-lb) Load Angle (deg)

Wind Angle (deg)

Max Cap Util 127,556 181.8 181.2 Groundline 127,556 181.8 181.2 GL Allowable 179,833

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 2 of 4 2 Worst Wind Per Guy Wire 3 Wind At 181.2°

Groundline Load Summary - Reporting Angle Mode: Load - Reporting Angle: 181.8° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

Powers 1,937 56.8 93,913 73.6 52.2 2,738 2,450 12 2,750 52.9 Comms 591 17.3 12,656 9.9 7.0 369 764 4 373 7.2 GenericEquipments 47 1.4 859 0.7 0.5 25 80 0 25 0.5 Pole 566 16.6 14,540 11.4 8.1 424 4,341 21 445 8.6 Crossarms 5 0.2 250 0.2 0.1 7 184 1 8 0.2 Streetlights 46 1.3 580 0.5 0.3 17 128 1 18 0.3 Risers 206 6.0 4,218 3.3 2.4 123 89 0 123 2.4 Insulators 11 0.3 540 0.4 0.3 16 76 0 16 0.3 Pole Load 3,410 100.0 127,556 100.0 70.9 3,719 8,112 40 3,759 72.3 Pole Reserve Capacity 52,277 29.1 1,481 1,441 27.7

Load Summary by Owner - Reporting Angle Mode: Load - Reporting Angle: 181.8° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

<Undefined> 2,844 83.4 113,016 88.6 62.8 3,295 3,771 18 3,314 63.7 Pole 566 16.6 14,540 11.4 8.1 424 4,341 21 445 8.6 Totals: 3,410 100.0 127,556 100.0 70.9 3,719 8,112 40 3,759 72.3

Detailed Load Components:

Power Owner Height

(ft) Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Primary AAC 556.5 KCM 19

STRAND DAHLIA

53.06 11.90 0.8560 1.92 0.521 153.0 90.3 153.0 2,753 -4,211 -148 6,227 1,868

Primary AAC 556.5 KCM 19

STRAND DAHLIA

53.06 11.90 0.8560 2.49 0.521 186.8 269.8 186.9 2,753 5,552 -151 7,602 13,002

Primary AAC 556.5 KCM 19

STRAND DAHLIA

53.06 39.09 0.8560 1.92 0.521 153.0 90.3 153.0 2,753 -4,211 -580 6,228 1,437

Primary AAC 556.5 KCM 19

STRAND DAHLIA

53.06 39.09 0.8560 2.49 0.521 186.8 269.8 186.9 2,753 5,552 -592 7,602 12,561

Primary AAC 556.5 KCM 19

STRAND DAHLIA

53.06 39.70 0.8560 1.92 0.521 153.0 90.3 153.0 2,753 -4,211 596 6,227 2,612

Primary AAC 556.5 KCM 19

53.06 39.70 0.8560 2.49 0.521 186.9 269.8 186.9 2,753 5,552 608 7,603 13,763

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 3 of 4 2 Worst Wind Per Guy Wire 3 Wind At 181.2°

Primary AAC 556.5 KCM 19

STRAND DAHLIA

47.14 46.23 0.8560 1.92 0.521 153.0 90.3 153.0 2,753 -3,742 -678 5,534 1,114

Primary AAC 556.5 KCM 19

STRAND DAHLIA

47.14 46.23 0.8560 2.49 0.521 186.8 269.8 186.9 2,753 4,933 -711 6,754 10,976

Primary AAC 556.5 KCM 19

STRAND DAHLIA

47.14 21.37 0.8560 1.92 0.521 153.0 90.3 153.0 2,753 -3,742 305 5,533 2,096

Primary AAC 556.5 KCM 19

STRAND DAHLIA

47.14 21.37 0.8560 2.49 0.521 186.9 269.8 186.9 2,753 4,933 320 6,755 12,008

Primary AAC 556.5 KCM 19

STRAND DAHLIA

47.14 46.71 0.8560 1.92 0.521 153.0 90.3 153.0 2,753 -3,742 692 5,533 2,482

Primary AAC 556.5 KCM 19

STRAND DAHLIA

47.14 46.71 0.8560 2.49 0.521 186.9 269.8 186.9 2,753 4,932 725 6,755 12,413

Neutral 1/0 COPPER 7

STRAND

37.42 8.16 0.3684 1.81 0.326 153.0 90.3 153.0 1,323 -1,423 -73 3,235 1,739

Neutral 1/0 COPPER 7

STRAND

37.42 8.16 0.3684 2.44 0.326 186.9 269.8 186.9 1,373 1,972 -81 3,951 5,842

Totals: 8,143 231 85,539 93,913

Comm Owner Height (ft)

Horiz.

Offset

(in)

Cable Diameter

(in)

Sag at Max

Temp (ft)

Cable Weight (lbs/ft)

Lead/Span Length

(ft)

Span Angle (deg)

Wire Length

(ft)

Tension (lbs)

Tension Moment*

(ft-lb)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Overlashed Bundle 1/4" EHS 23.08 9.09 0.2500 3.92 0.121 153.0 90.3 153.2 400 -263 -54 2,269 1,952 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

23.03 9.09 0.8300 0.275 153.0 90.3 153.2 -67 809 742

Overlashed Bundle 1/4" EHS 23.08 9.09 0.2500 5.48 0.121 186.9 269.8 187.3 400 355 -64 2,771 3,061 Fiber BELOPTIX MLD6144

- 144 FIBERS -

OUTDOOR (0.83)

23.03 9.09 0.8300 0.275 186.9 269.8 187.3 -81 988 907

Overlashed Bundle 1/4" EHS 22.08 9.15 0.2500 5.82 0.121 153.0 90.3 153.6 400 -252 -51 2,100 1,796

CATV CATV .50 22.03 9.15 0.5700 0.600 153.0 90.3 153.6 -93 703 610

Overlashed Bundle 1/4" EHS 22.08 9.15 0.2500 8.45 0.121 186.9 269.8 188.1 400 340 -62 2,564 2,842

CATV CATV .50 22.03 9.15 0.5700 0.600 186.9 269.8 188.1 -112 859 746

Totals: 179 -585 13,062 12,656

GenericEquipment Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Box Cran Box 20.33 14.37 0.0 0.0 53.00 25.50 8.60 -- 16.70 -94 954 859 Totals: -94 954 859

Crossarm Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth (in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Normal CROSSARM 3-1/2 X 4-

1/2 X 7

52.25 -6.45 90.0 90.0 46.00 4.50 3.50 84.00 1 92 93

Normal CROSSARM 3-1/2 X 4- 1/2 X 8

46.33 -6.83 90.0 90.0 53.00 4.50 3.50 96.00 1 82 83

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 4 of 4 2 Worst Wind Per Guy Wire 3 Wind At 181.2°

Normal 4'_Fuse Array 42.25 7.09 90.0 90.0 24.00 4.50 3.50 48.00 -1 74 73 Totals: 2 248 250

Streetlight Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

General Streetlight - 10 ft. Arm 33.75 5.90 0.0 0.0 85.00 24.00 20.00 3.00 120.00 -954 1,534 580 Totals: -954 1,534 580

Riser Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Height

(in)

Unit Depth

(in)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at GL* (ft-lb)

Riser 90.0° H:21.0 Riser 21.00 8.25 90.0 90.0 21.00 252.00 5.00 5.00 252.00 0 1,214 1,214 Riser 112.5° H:38.17 Riser 38.17 8.25 112.5 112.5 38.17 458.04 4.00 4.00 458.04 12 2,992 3,004

Totals: 12 4,207 4,218

Insulator Owner Height (ft)

Horiz.

Offset

(in)

Offset Angle (deg)

Rotate Angle (deg)

Unit Weight

(lbs)

Unit Diameter

(in)

Unit Length

(in)

Offset Moment*

(ft-lb)

Wind Moment*

(ft-lb)

Moment at

GL*

(ft-lb) Pin Pin 7.5" 52.44 -10.00 327.2 -1.9 6.00 3.50 7.50 0 95 95 Pin Pin 7.5" 52.44 -38.55 350.5 -1.9 6.00 3.50 7.50 0 95 95 Pin Pin 7.5" 52.44 39.17 189.4 -1.9 6.00 3.50 7.50 0 95 95 Pin Pin 7.5" 46.52 -45.72 351.5 -1.9 6.00 3.50 7.50 0 84 84 Pin Pin 7.5" 46.52 20.25 198.7 -1.9 6.00 3.50 7.50 0 84 84 Pin Pin 7.5" 46.52 46.21 188.4 -1.9 6.00 3.50 7.50 0 84 84 Bolt Three Bolt 37.42 0.00 354.3 174.2 5.00 3.00 0.10 0 1 1 Bolt Three Bolt 23.08 0.00 0.0 0.0 5.00 3.00 0.10 0 0 0 Bolt Three Bolt 22.08 0.00 0.0 0.0 5.00 3.00 0.10 0 0 0

Totals: 0 540 540

Pole Buckling Buckling Constant

Buckling Column Height*

(ft)

Buckling Section Height

(% Buckling Col. Hgt.)

Buckling Section

Diameter (in)

Minimum Buckling

Diameter at

GL

(in)

Diameter at Tip (in)

Diameter at

GL

(in)

Modulus of Elasticity

(psi)

Pole Density

(pcf)

Ice Density (pcf)

Pole Tip Height

(ft)

Buckling Load

Capacity at Height (lbs)

Buckling Load

Applied at Height (lbs)

Buckling Load Factor

2.00 33.69 34.05 14.68 10.10 9.24 16.18 2.38e+6 60.00 56.00 53.50 53,265 533.67 6.58

Pole ID:Not Saved O-Calc® Pro Analysis Report Report Created: 9/9/2025 8:55 AM

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 1 of 5 2 Worst Wind Per Guy Wire 3 Wind At 0.7°

Pole Num: 949 Pole Length / Class: 80 / 2 Code: NESC Structure Type: Guyed Tangent Aux Data 1 Unset Species: DOUGLAS FIR NESC Rule: Rule 250B Status: Guy Wires Adequate Aux Data 2 Unset Setting Depth (ft): 27.42 Construction Grade: B Pole Strength Factor: 0.65 Aux Data 3 Unset G/L Circumference (in): 43.12 Loading District: Heavy Transverse Wind LF: 2.50 Aux Data 4 Unset G/L Fiber Stress (psi): 8,000 Ice Thickness (in): 0.50 Wire Tension LF: 1.65 Aux Data 5 Unset Allowable Stress (psi): 5,200 Wind Speed (mph): 39.53 Vertical LF: 1.50 Aux Data 6 Unset Fiber Stress Ht. Reduc: No Wind Pressure (psf): 4.00 Latitude: 44.103368 Longitude: -123.148183 Elevation: 117.9M

Pole Capacity Utilization (%) Height (ft)

Wind Angle (deg)

Maximum 84.9 36.3 0.7 Groundline 72.2 0.0 180.0 Vertical 14.3 36.2 5.4

Pole Moments (ft-lb) Load Angle (deg)

Wind Angle (deg)

Max Cap Util 31,003 1.5 0.7 Groundline 14,774 287.6 180.0 GL Allowable 109,995

Guy System Component Summary Load From Worst Wind Angle on Pole

Individual Maximum Load With Overload Applied

Description Lead Length (ft)

Lead Angle (deg)

Height (ft)

Nominal Capacity (%)

Wind Angle (deg)

Max* Load Capacity (%)

Wind Angle (deg)

? F13-14-12-10" Triple Helix 14.0 185.4 27.9 0.7 46.0 1.2 ? EHS 5/8 (Down) 36.3 32.8 0.7 54.2 1.2

User:mmcevoy CORP OCP:7.00 * Includes Load Factor(s) Page 2 of 5 2 Worst Wind Per Guy Wire 3 Wind At 0.7°

Groundline Load Summary - Reporting Angle Mode: Load - Reporting Angle: 287.6° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

Powers 837 179.1 32,095 217.2 29.2 1,898 2,688 18 1,916 36.8 Comms 368 78.8 6,422 43.5 5.8 380 973 7 386 7.4 GuyBraces -922 -197.3 -26,780 -181.3 -24.4 -1,584 17,675 119 -1,464 -28.2 PowerEquipments 42 9.1 23 0.2 0.0 1 1,808 12 14 0.3 Pole 138 29.5 2,811 19.0 2.6 166 3,105 21 187 3.6 Crossarms 1 0.1 79 0.5 0.1 5 148 1 6 0.1 Insulators 3 0.7 124 0.8 0.1 7 76 1 8 0.2 Pole Load 467 100.0 14,774 100.0 13.4 874 26,475 179 1,053 20.2 Pole Reserve Capacity 95,221 86.6 4,326 4,147 79.8

Load Summary by Owner - Reporting Angle Mode: Load - Reporting Angle: 287.6° Shear Load* (lbs)

Applied Load

Bending Moment

(ft-lb)

Applied Moment

Pole Capacity

Bending Stress (+/- psi)

Vertical Load (lbs)

Vertical Stress (psi)

Total Stress (psi)

Pole Capacity

<Undefined> 1,252 267.8 38,743 262.2 35.2 2,291 5,694 38 2,329 44.8

LEC -922 -197.3 -26,780 -181.3 -24.4 -1,584 17,675…

This is the start of the file's text. The full file is on GovTribe.