This is a specification submittal document for PP and UPP Series Power Packs (Model Numbers -DV, -DV-M, -347H, -SH), devices designed to provide 24V power supply and line-voltage relay control for lighting loads and occupancy sensor systems. The power packs are compact units that can be mounted inside ballast enclosures or junction boxes and are available in multiple configurations to accommodate different voltage requirements and control scenarios. The PP-DV and UPP-DV models operate on 120-277V at 50/60 Hz with a 16A relay contact rating for all lighting loads and up to 1 HP motor loads, while the PP-347H model operates on 347V at 60 Hz with a 15A ballast rating. The manual-ON Power Pack (-DV-M) variant provides vacancy solutions when paired with occupancy sensors, and the auxiliary Power Pack (-SH) enables switching of multiple loads in conjunction with primary power pack units. All units feature high-impact UL94 flammability-rated plastic construction with Class B insulating material and silver alloy contacts, and are rated for indoor use within temperature ranges of 32°F to 104°F and humidity levels from 0% to 90% non-condensing.
The devices comply with UL and cUL listing requirements and meet NEC 2014 standards for use in plenum spaces. Power pack units feature 7-inch wire leads (18 AWG for input and 16 AWG for contacts) and mount within standard 4-inch by 4-inch junction boxes or fluorescent fixture ballast cavities using 6/32-inch pan head screws. Each primary power pack can control up to three total devices, with auxiliary PP-SH/UPP-SH units counting as one device and each occupancy sensor counting as one device toward this limit. The specification document includes detailed wiring diagrams for various configurations, including single power pack installations, multi-load switching with multiple power packs, and auxiliary power pack arrangements with occupancy sensor integration.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544g 1 06.22.16
PP and UPP Series Power Packs
PP and UPP 1 Series Power Packs provide both the
24 V- power supply to operate Lutron® wired occupancy sensors, as well as the 16 A line-voltage relay to control the load, in one compact housing. The unit can be mounted inside a ballast enclosure or inside / outside a junction box.
The manual-ON Power Pack (-DV-M) is used to provide a vacancy solution when paired with Lutron® wired occupancy sensors. A low-voltage momentary switch should be used to manually turn ON the load while the sensor automatically shuts the load OFF when unoccupied.
Pressing the momentary switch can also turn the load OFF.
The auxiliary Power Pack (-SH) must be used in conjunction with at least one line-voltage Power Pack and one Lutron wired occupancy sensor to switch additional loads.
Features
• High-impact UL94 flammability-rated plastic case construction
• Relay: Class B 266 °F (130 °C) insulating material; silver alloy contacts
• Power Pack units (PP-DV / UPP-DV, PP-347H, PP-DV-M / UPP-DV-M) power up to 3 total devices.
PP-SH / UPP-SH counts as 1 device, each occupancy sensor counts as 1 device.
• For indoor use only, 32 °F to 104 °F (0 °C to 40 °C), 0% to
90% humidity, non-condensing
(-DV)
(-DV-M)
(-347H)
(-SH)
Model Power Input Relay Contact Rating Control Input IEC PELV/ NEC® Class 2 Output
PP-DV
UPP-DV
PP-DV-M
UPP-DV-M
120-277 V~
50/60 Hz
6.5 W
• 120-277 V~ 16 A;
All lighting loads 2
• 120-277 V~ 1 HP Motor Load
24 V- 5 mA 24 V- 150 mA up to 3 Devices 3
PP-347H 347 V~ 60 Hz
6.5 W
• 347 V~ 15 A Ballast 24 V- 5 mA 24 V- 100 mA up to 3 Devices 3
PP-SH
UPP-SH
24 V-
(At least one line-voltage Power
Pack must be used)
• 120-277 V~ 16 A;
All lighting loads 2
• 120-277 V~ 1 HP Motor Load
• 347 V~ 15 A Ballast
24 V- 5 mA N/A
1 “U” denotes BAA compliance 2 Lighting loads include (but are not limited to): Incandescent, MLV, ELV, Resistive, Inductive 3 PP-SH / UPP-SH counts as 1 device and each occupancy sensor counts as 1 device
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544g 2 06.22.16
Specifications
Regulatory Approvals
• UL® and cUL® Listed
• Complies with requirements for use in other spaces used for environmental air (plenums) per
NEC® 2014 300.22(C)(3)
Power / Performance
• PP-DV, UPP-DV, PP-DV-M, UPP-DV-M:
120-277 V~ 50/60 Hz
• PP-347H: 347 V~ 60 Hz only
Wiring
• 7 in (178 mm) wire leads, 18 AWG (0.75 mm2) input;
7 in (178 mm) leads, 16 AWG (1.5 mm2) contacts.
Mounting
• Fits inside standard 4 in x 4 in (102 mm x 102 mm) junction box or standard fluorescent fixture ballast cavity
• Mount with 6/32 in (5 mm) x 11⁄4 in (32 mm) pan head screws
• Mounts inside junction box through knockout, with 1/2 in (13 mm) Electrical Metallic Tubing (EMT) threaded nipple. Recommended volume is 30 in3
(762 mm3).
Dimensions
1.36 in
(35 mm)
2.33 in
(59 mm)
3.69 in
(94 mm)
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544g 3 06.22.16
3 Sensors with Power Pack - Vacancy Solution (PP-DV-M, UPP-DV-M) 1
Maximum 3 devices (excluding low-voltage momentary switches) can be used with PP-DV-M / UPP-DV-M. Each PP-SH / UPP-SH counts as one device, each occupancy sensor counts as one device.
NTRCS-1 (Nova T*® momentary switch) or any low voltage momentary switch rated for at least 24 V-, 100 mA.
Power Pack
(-DV-M)
120-277 V~ 50/60 Hz
Lighting
Load
Red (24 V-)
Black (common)
Blue (control)Black
White
Red
Red
Neutral
Ground
Line / Hot
Orange
(manual override)
Low-Voltage
Momentary
Switch 2 Occupancy Sensors
Wiring
3 Sensors with Power Pack (PP-DV, UPP-DV or PP-347H) 1
Maximum 3 occupancy sensors can be used with PP-DV / UPP-DV or PP-347H.
When lights are manually turned off, switch must be returned back to the on position for occupancy sensors to function as set.
Lighting
Load
120-277 V~ 50/60 Hz (PP-DV / UPP-DV)
347 V~ 60 Hz (PP-347H)
Neutral
Power Pack
(-DV or-347H)
Manual switch OFF 2
(optional – sold separately)
Red (24 V-)
Blue (control)
Black (common)
Black
White
Red
Red
Line / Hot
Ground
Occupancy Sensors continued on next page...
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544g 4 06.22.16
Wiring (continued)
Power Pack
(-DV or -347H)
Power Pack
(-DV or -347H)
Switching Multiple Loads with 2 Power Packs (PP-DV / UPP-DV)
Lighting
Load Lighting
Load
Red (24 V-)
Black
(common)
Occupancy Sensors
Blue (control)Black Black
White White
Red Red
Red 1
Red
Red
Neutral
Neutral
Ground Ground
Line / Hot
Lighting
Load
Lighting
Load Auxiliary
Power Pack
(-SH)
Red
Red
Red (24 V-)
Black (common)
Maximum of 3 devices can be used with PP-DV, UPP-DV, or PP-347H. Each PP-SH / UPP-SH counts as one device, each occupancy sensor counts as one device.
Neutral
Line / Hot
Blue (control) Black White
Red
Red
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
Ground Ground
Occupancy Sensors
Power Pack
(-DV or-347H)
Only 1 Power Pack (PP-DV / UPP-DV) should power the occupancy senors. This 24 V- output is left disconnected.
Switching Multiple Loads with 1 Power Pack and 1 Auxiliary Power Pack 1
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H) 120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
| Copy of pdfformfields_file_11pages |
| Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of Copy of pdfformfields_file_11pages |
| Form Fields (1).pdf |
| Copy of pdfformfields_file_11pages |
| Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of Copy of pdfformfields_file_11pages |
| Blank Page |
| Form Fields (1) - Copy.pdf |
| Copy of pdfformfields_file_11pages |
| Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of Copy of pdfformfields_file_11pages |
| Form Fields (1).pdf |
| Copy of pdfformfields_file_11pages |
| Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of pdfformfields_file_11pages |
| Copy of Copy of Copy of Copy of pdfformfields_file_11pages |
| A: |
| B: |
| C: |
| D: |
| E: |
| F: |
| H: 2 |
| I: 3 |
| J: 4 |
| G: 1 |
File details come from the government source that posted it. Updated .