LUTRON_Diva_Controls_and_Cover_Plates_Spec_Sheets.pdf
PDF 314 KB Posted
- Solicitation number
- RFP HAS 200000001821 1
- Issued by
- Genesee County, Michigan
About this file
This specification document details Lutron Diva Controls and Cover Plates for state and local procurement, providing comprehensive technical requirements and product information for lighting control devices and accessories. The specification establishes requirements for permanently installed, wallbox-mounted switches, dimmers, fan-speed controls, receptacles, and data/voice/cable jacks. The scope requires submission of manufacturer's standard catalog data, test data, and samples demonstrating conformance to specifications. All basic components and wallplate kits must be provided by a single manufacturer, with acceptable manufacturers limited to Lutron Electronics Co., Inc. The specification requires devices to be UL listed, CSA and NOM approved for specific load types including incandescent, electronic low voltage transformers, magnetic low voltage transformers, and fluorescent loads. Contractors are responsible for furnishing all devices, labor, and installation services according to manufacturer recommendations, with particular attention to proper derating of dimmer capacity when side sections are removed and installation of separate neutral wires in 120/208 VAC installations.
The specification mandates that dimmers and controls operate at 120VAC/277VAC, 60Hz with full-range, continuously variable control featuring soft-glow nightlights, square law dimming curves, and power-failure memory. All devices must incorporate resettable overload protection, be 100% function tested at manufacture, and withstand voltage surges up to 6000V and current surges up to 200A without damage. Incandescent dimmers are available in 600 and 1000 watt capacities, while electronic low voltage dimmers handle up to 300 watts and magnetic low voltage dimmers accommodate up to 1000 volt amps. High-power remote dimming modules are available for loads exceeding single dimmer capacity, rated up to 30,000 watts in 2,000 watt increments. Wallplates must be manufactured from polycarbonate with gloss finish, seamless design for up to six-ganged configurations, color variation not exceeding delta E of 1 per ASTM E 308-99, and ultraviolet stability per ASTM D4674-89. Manufacturers must maintain minimum ten years continuous experience in wallbox dimming products and current ISO 9001 certification, with all devices covered by minimum one-year warranty and 24/7 technical support available.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The designer dimmer that matches your paddle switches.
PRODUCT FAMILY FEATURES
• Large paddle switch with a captive linear-slide dimmer for a standard designer wallplate opening
• Full family of products for most lighting sources
• Dimmers feature built-in soft-glow nightlight
• Uses standard single-pole and 3-way wiring for easy installation in any home
• For more Diva choices, see the new Diva Satin Colors product line
DIMENSIONS
Front Profile
SPECIFICATION SUBMITTAL
CONTROLS AND ACCESSORIES
Preset Fan-Speed Switches Dimmers Controls
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
JOB NAME AREA CONTROLLED
LOCATION JOB NUMBER
TITLE PAGE NO.
SPECIFICATION SERIES
STANDARD FEATURES
• Square Law Dimming • RFI suppression
• Power-failure memory • Captive linear slider
• Electrostatic discharge tested • Precise color matching
• Mechanical air-gap switch to disconnect load power Lutron controls are rated at 120VAC, 60Hz unless otherwise noted.
Controls www.lutron.com/diva
Soft glow nightlight
Select light level with slider
Switch on to selected light level/off
Preset Dimmer
Preset Fan-Speed Controls
1.31" * (33mm)
2.75" (70mm)
2.94" (75mm)
4.69" (119mm)
0.30" (7.6mm)
* some models up to 1.44" (37mm)
Select fan speed with slider
Switch on to selected fan speed/off
Cable TV Jack
Single Telephone Jack
15A Receptacle
15A GFCI Receptacle
2-gang to 6-gang wallplates
Telephone/Cable TV Jacks
Standard Multigang Wallplates
Receptacles
Ports
6-Port Frame
Maximum Description Capacity 1 Model #
HI-POWER 2•4•6TM DIMMING MODULES
To increase load capacity up to 30,000W/VA in most popular sources, use one DV-600P- or DV-603P- and add up to five dimming modules. Cannot be used with 0-10VDC ballast.
FAN-SPEED CONTROLS
Quiet Controls
For use with one ceiling paddle fan.
Preset Fan-Speed Controls 3
Single pole/ 3-way, 1.5A DVFSQ-F- 3-speed Note: Does not have soft-glow nightlight. For 3-way and 4-way switching, use with Claro switches or other mechanical switches.
SWITCHES 3
General Purpose Switching of all Sources and Motor Loads
Single pole, 120/277V 15A CA-1PSH- 3-way, 120/277V 15A CA-3PSH- 4-way, 120/277V 15A CA-4PSH-
ACCESSORIES
Receptacles
Receptacle 3
15A, 125V CAR-15H-
GFCI Receptacle 3
15A, 125V CAR-15-GFCIH-
Telephone and Cable Television Jacks
A physical barrier (partition) must exist when ganging with line-voltage products Single Telephone Jack 4
6-conductor, RJ11 CA-PJH- Note: Also accepts most 4-conductor plugs.
Cable TV Jack 3, 4
F-STYLE
75-Ohm, coaxial cable jack CA-CJH-
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
Maximum Description Capacity 1 Model #
DIMMERS
Incandescent
Preset Dimmers with Nightlight Single pole 600W DV-600P- Single pole 1000W DV-10P- 3-way 600W DV-603P- 3-way 1000W DV-103P- Note: The nightlight is visible best on the lighter colors. For 3-way and 4-way switching, use with Claro® switches or other mechanical switches.
Electronic Low Voltage
Preset Dimmers with Nightlight Single pole 300W DVELV-300P- 3-way 300W DVELV-303P- Note: Requires neutral wire connection. The nightlight is visible best on the lighter colors. For 3-way and 4-way switching, use with Claro switches or other mechanical switches.
Magnetic Low Voltage
Preset Dimmers with Nightlight Single pole 600VA (450W 2) DVLV-600P- Single pole 1000VA (800W 2) DVLV-10P- 3-way 600VA (450W 2) DVLV-603P- 3-way 1000VA (800W 2) DVLV-103P- Note: The nightlight is visible best on the lighter colors. For 3-way and 4-way switching, use with Claro switches or other mechanical switches.
Fluorescent Dimming with Hi-lume® and Eco-10TM (ECO-Series) Electronic Ballasts
Preset Dimmers with Nightlight 3
Single pole/ 3-way 8A DVF-103P- Single pole/ 3-way, 277V 6A DVF-103P-277- Note: Use with Lutron Hi-lume or Eco-10 (ECO-Series) line voltage control Electronic Dimming Ballasts only. Requires neutral wire connection. The nightlight is visible best on the lighter colors. For 3-way and 4-way switching, use with Claro switches or other mechanical switches.
Fluorescent Dimming with Tu-Wire®
Electronic Ballasts
Preset Dimmers with Nightlight Single pole/ 3-way 5A DVFTU-5A3P- Note: Use with Lutron Tu-Wire line voltage control electronic dimming ballasts only. The nightlight is visible best on the lighter colors. For 3-way and 4-way switching, use with Claro switches or other mechanical switches.
1 For capacities in multigang installations see derating pg. 3.
2 Actual lamp wattages.
3 No derating required if ganged.
4 A physical barrier (partition) must exist when ganging with line-voltage products.
Controls
3 Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
Controls
Description Rating Model #
ACCESSORIES
Field Customizable Multi-Port Frame
6-Port Frame Shipped with 6 blanks CA-6PF- Shown with blanks
Product above: For use with Lutron connectors shown below. Also compatible with Hubble XceleratorTM and snap-fit connectors.
Connectors For use with 6-port frame (CA-6PF-). Each connector fills one port.
Phone Jack 6-conductor, RJ11, Category 3 CON-1P-C3-WH
Phone Jack 8-conductor, RJ45, Category 5e CON-1P-C5E-WH
Phone Jack 8-conductor, RJ45, Category 6 CON-1P-C6-WH
Fiber Jack MT-RJ Feed-Through CON-1F-MTRJ-WH
Fiber Jack SC Simplex CON-1F-SC-WH
Fiber Jack LC Non-Flush Mount CON-1F-LC-WH
Fiber Jack ST Style CON-1F-ST-WH
Cable Jack F-Style, 75-Ohm Coaxial cable CON-1C-WH
BNC Jack BNC connector CON-1B-WH
Connectors available in white (WH) only. For information about additional colors contact Lutron Customer Service.
DERATING/MAXIMUM CAPACITY
No side One side Two side sections section sections removed removed removed (Full Capacity) (End Units) (Middle Unit)
Incandescent Dimmers
600W 500W 400W 1000W 800W 650W
Electronic Low Voltage 1
300W 250W 200W
Magnetic Low Voltage
600VA 500VA 400VA
(450W 2) (375W 2) (300W 2)
1000VA 800VA 650VA
(800W 2) (650W 2) (500W 2)
Fluorescent
Hi-lume/Eco-10 20ballasts/8A No derating required (ECO-Series) Tu-Wire 3 5A 4A 3.3A
Fan-Speed Controls
1.5A No derating required
1 Requires 40W minimum load.
2 Actual lamp wattage.
3 Minimum capacity: 2 ballasts/0.25A
Description Model #
STANDARD WALLPLATES
1-Gang 2.94”W (75mm) x 4.69”H (119mm) x 0.30”D (7.6mm)
CW-1-
2-Gang 4.75”W (121mm) x 4.69”H (119mm) x 0.30”D (7.6mm)
CW-2-
3-Gang 6.56”W (167mm) x 4.69”H (119mm) x 0.30”D (7.6mm)
CW-3-
4-Gang 8.37”W (213mm) x 4.69”H (119mm) x 0.30”D (7.6mm) CW-4-
5-Gang 10.18”W (259mm) x 4.69”H (119mm) x 0.30”D (7.6mm) CW-5-
6-Gang 12.00”W (305mm) x 4.69”H (119mm) x 0.30”D (7.6mm) CW-6-
STANDARD COLORS/FINISHES
Gloss Finishes (Ships in 48 hours) Add color/finish suffix to model number to order.
Example: DV-600P-WH WH White IV Ivory AL Almond LA Light Almond GR Gray BR Brown BL Black
Have Questions? Call the Lutron Hotline 800-523-9466
Wiring Diagram 4 3-Way Wiring Model #
DVELV-303P-
CA-3PS-
Wiring Diagram 5 3-Way Used as Single Pole Model #
DVELV-303P-
WIRING DIAGRAMS
Wiring Diagram 1 Single-Pole Wiring Model #
DV-600P-
DV-10P-
DVLV-600P-
DVLV-10P-
CA-1PSH-
Wiring Diagram 2 Single-Pole Wiring of 3-Way Control Model #
DVFSQ-F-
DVLV-103P-
DVLV-603P-
DV-103P-
DV-603P-
Wiring Diagram 3 Single-Pole Wiring Model #
DVELV-300P-
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
Neutral
Black *
Dimmer/ Switch/Fan-Speed Control
Black or Red *Hot
120VAC
60Hz
Lighting Load or FanGreen **
**or Brass screw terminal **or Green screw terminal
Ground
Wire Connectors
Control Load Side
Neutral
YellowHot
Green White
120VAC
60Hz
Red***
Lighting Load
3-Way Switch
3-Way Dimmer
Neutral
YellowHot
Green White
120VAC
60Hz
Red
Red Lighting Load
3-Way Dimmer
Ground
Wire Connectors
***or Copper/Black *** screw terminal ***or Brass/Gold *** screw terminal
***or Copper/Black *** screw terminal ***or Brass/Gold *** screw terminal
Ground
Wire Connectors
Green ***
Neutral
Black *
Red **†
Red **Hot
120VAC
60Hz
Lighting Load or Fan
Ground
Wire Connectors
***or Copper/Black screw terminal ***or Brass screw terminal ***or Green screw terminal † or Red/White stripe (cap off)
Dimmer/ Switch/Fan-Speed Control
Red or Yellow
Green White
Neutral
Black
Dimmer/Switch/ Fan-Speed Control
Hot
120VAC
60Hz
Lighting Load or Fan
Ground
Wire Connectors
WIRING DIAGRAMS
Wiring Diagram 6 3-Way Wiring Model #
DV-603P-
DV-103P-
DVLV-603P-
DVLV-103P-
DVFSQ-F-
CA-3PSH-
Wiring Diagram 7 4-Way Wiring Model #
DV-603P-
DV-103P-
DVLV-603P-
DVLV-103P-
DVFSQ-F-
CA-3PSH-
CA-4-PSH-
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
Control Line Side 3-Way
Switch
Fan-Speed Control or 3-Way Dimmer/Switch
Fan-Speed Control or 3-Way Dimmer/Switch
Lighting Load or Fan
Neutral
Red *
Red *†
Green *** *** *** Green ***
Black **Hot
120VAC
60Hz
3-Way Switch
Lighting Load or Fan
Neutral
Red *
Red *†
Black **Hot
120VAC
60HzOR
Control Load Side
Ground
Wire Connectors
***or Brass/Gold *** screw terminal ***or Copper/Black *** screw terminal ***or Green screw *** terminal † or Red/White stripe
Control Line Side
Control Load Side
Black ** Red * *
Red *† *
Red *†*
Neutral
Hot
Green *** ***
120VAC
60Hz
3-Way Dimmer/Switch or Fan-Speed Control
4-Way Switch
Lighting Load or Fan
3-Way Switch
Neutral
Hot
Green ***
120VAC
60Hz
** Black **Red *
4-Way Switch
Lighting Load or Fan
3-Way Switch
3-Way Dimmer/Switch or Fan-Speed Control
OR
Ground
Wire Connectors
***or Copper/Black *** screw terminal ***or Brass/Gold *** screw terminal ***or Green *** screw terminal † or Red/White stripe
Wiring Diagram 8 Single-Pole Wiring of a 3-Way Control Model #
DVF-103P-
DVF-103P-277-
Wiring Diagram 9 3-Way Wiring Model #
DVF-103P-
DVF-103P-277-
CA-3PSH-
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
Green
120VAC
or
277VAC
60Hz
To Additional Ballasts
Dimmer
Orange or Brown **
White *
BlackBlack
Orange or Brown **
White *
Yellow or Orange
Black
Blue RedHot
Neutral
White
Violet or Blue *** must use lamp ***disconnect sockets ***with magnetic ***dimming ballasts *** or Yellow/Blue or ***Yellow/Green when ***used with magnetic ***dimming ballasts
Dimming Ballast
Dimming Ballast
Ground
Wire Connectors
Typical 4-Wire Connection
Control Load Side
* 3-Way switch must be wired on line side of dimmer ** must use lamp disconnect sockets with magnetic dimming ballasts *** or Yellow/Blue or Yellow/Green when used with magnetic dimming ballasts † † or Copper/Black screw terminal † † or Brass/Gold screw terminal
GreenGreen
120VAC
or
277VAC
60Hz
To Additional Ballasts
Dimmer 3-Way Switch*
Orange or Brown ***
White **
Black
Orange or Brown ***
White **
Black
RedHot
Neutral
White
Violet or Blue
Yellow or Orange
Blue† † †
Dimming Ballast
Dimming Ballast
Ground
Wire Connectors
Typical 4-Wire Connection
Controls
Wiring Diagram 10 Single-Pole Wiring Model #
DVFTU-5A3P-
Wiring Diagram 11 3-Way Wiring Model #
DVTU-5A3P-
CA-3PSH-Black**Black
Green
To additional ballasts * or Red/White ** terminals are provided
Neutral
Red*
Red Dimmer
Black
White**
Hot
120VAC
60Hz
Tu-Wire™ Ballast
Ground
Wire Connectors
Black**Black
To additional ballasts * or Red/White ** terminals are provided
White** Green
Neutral
Red*
Red Dimmer
3-way Switch
BlackHot
Green
120VAC
60Hz
Ground
Wire Connectors
Tu-Wire™ Ballast
Wiring Diagram 12 Cable TV Jack Wiring Model #
CA-CJH-
Wiring Diagram 13 Telephone Jack Wiring Model #
CA-PJH-
Wiring Diagram 14 Receptacle Wiring Model #
CAR-15H-
Wiring Diagram 15 GFCI Receptacle Wiring Model #
CAR-15-GFCIH-
75-Ohm Cable 75-Ohm
Cable
Cable TV Jack
Ground
Neutral
Hot
Black
White
Green or Screw Terminal
Green or Screw Terminal
Green or Screw Terminal
Black
White
120VAC
60Hz
GFCI
Receptacle (15A Shown)
NPNP PP PP
Line Load
Wire ConnectorsP-Protected NP-Not Protected
Building Ground (To Metal Box)
Have Questions? Call the Lutron Hotline 800-523-9466 To order—Call Lutron Customer Service 610-282-3800
6-Conductor Telephone Jack*
Wire Color
Jack Position
1 White 2 Black 3 Red 4 Green 5 Yellow 6 Blue
* accepts most 4-conductor jacks
Neutral
Black
Receptacle (15A Shown)
WhiteHot
120VAC
60Hz
Nickel Plated Screws
Brass Screws
Green Screw Ground or
Isolated Ground
Ground
Wire Connectors
c. When on, the slider shall change the light level/fan speed.
When off, the slider shall preselect the light level/fan speed that the control will turn on to. Paddle switch shall turn lights/fan on to the preselected level, or off.
d. Paddle switch and slider shall be captured internal to the control.
e. 3-Way controls shall be capable of multi-location on and mechanical air-gap off using standard 3-way and 4-way switches. Multi-location switches shall be Claro decorator style with a gloss finish.
f. Dimmer shall be backlit with soft glow locator light.
g. Within rated capacity, dimmers shall be available for direct control of incandescent, magnetic low voltage, electronic low voltage, and fluorescent. Matching fan-speed controls shall also be available.
h. Controls shall be capable of operating at the rated capacity;
this includes modified capacities for ganging configurations which require the removal of fins. Operation at rated capacity shall be possible across the full ambient temperature range, without shortening design lifetime.
i. To ensure a precise color match between all plastic parts, color variation of any gloss finish control shall not exceed a delta E of 1, CIE L*a*b* color units, as defined in ASTM E 308-99.
j. Dimmer shall provide smooth and continuous Square Law dimming curve, for the full slider travel, on their rated load per The IESNA Lighting Handbook, 9th edition, p. 27-4.
k. Controls shall meet the applicable requirements of UL 20 and UL 1472 referring to the inclusion of a visible, accessible air-gap off switch and the limited short circuit test.
l. Controls shall meet ANSI/IEEE Std. C62.41-1980, tested to withstand voltage surges of up to 6000V and current surges of up to 200A without damage.
m. Dimmers shall be designed to reduce interference with radio, audio, and video equipment.
n. Controls shall incorporate power-failure memory. Should power be interrupted and subsequently returned, the lights or fans will come back on to the same levels set prior to the power interruption. Restoration to some other default level is not acceptable.
o. Controls shall not be susceptible to damage or loss of memory due to static discharge.
p. Controls shall operate in an ambient temperature range of 0°C (32°F) to 40°C (104°F).
q. 3-Way controls shall wire using conventional 3-way and 4-way wire runs.
r. Contractors shall install all backboxes with a minimum wallbox depth of 2.5 inches.
2. Incandescent Dimmers
a. Provide single-pole and 3-way incandescent dimmers in 600
Watts and 1000 Watts capacities.
b. Dimmer shall be capable of operating in either 3-way switch location.
c. Dimmer shall be capable of operating in either 3-way switch location.
3. Electronic (Solid State) Low Voltage (ELV) Transformer Dimmers
a. Provide ELV dimmers for direct control of up to 300 watts of electronic low voltage load.
b. Dimmers shall contain circuitry specifically designed to control the input of electronic (solid state) low voltage transformers. Dimmers using standard phase control shall not be acceptable.
DIVA CONTROLS AND ACCESSORIES
PART 1 – GENERAL
1.01 SUMMARY
A. Scope: Provide, install and test all switches, dimmers and related devices as specified herein for the areas indicated on the drawings, specifications, and load schedules.
B. Related Sections: Section 16580 (Ballasts), Section 16570 (Dimming Systems).
1.02 REFERENCES
A. UL 20, UL 1472, CSA, NOM, ISO 9001
1.03 SYSTEM DESCRIPTION AND OPERATION
A. Permanently installed, wallbox mounted switches and dimmers B. Permanently installed, wallbox mounted fan-speed controls C. Permanently installed, wallbox mounted receptacles D. Permanently installed, wallbox mounted data, voice and cable jacks E. Screwless, seamless wallplates
1.04 SUBMITTALS
A. Submit manufacturer's standard catalog data giving all application, wiring, and installation information on basic components and wallplate kits. Provide test data and/or samples as required to demonstrate conformance with PART 2 of this specification.
1.05 QUALITY ASSURANCE
A. Manufacturer shall have a minimum of 10 years continuous experience in manufacturing wallbox dimming products.
B. Dimmers, switches and Fan-speed controls shall be UL listed, CSA and NOM approved specifically for each required load (i.e., tungsten, electronic low voltage transformer, magnetic low voltage transformer, and fluorescent). Manufacturer shall provide file card or certificate upon request. Universal load-type dimmers shall not be acceptable.
C. Manufacturer shall maintain ISO 9001 certification and provide a copy of the certificate upon request.
1.06 WARRANTY
A. All devices shall be covered by a minimum one-year warranty.
PART 2 – EQUIPMENT
2.01 ACCEPTABLE MANUFACTURERS
A. Lutron Electronics Co., Inc.
B. Unless otherwise noted, all basic components (dimmer, fan-speed control, switch, receptacle, telephone jack and cable TV jack) and wallplate kits shall be provided by one manufacturer.
2.02 EQUIPMENT
A. Controls Lutron Diva Style
1. Performance
a. Dimmers shall provide full-range, continuously variable control of light intensity.
b. Wall controls shall fit a decorator wallplate opening with a paddle switch. Dimmers shall have a small, raised slider to the right of the paddle switch. Controls shall have a gloss finish.
Have Questions? Call the Lutron Hotline 800-523-9466
b. Receptacles shall be two pole, three wire ground and rated for 15A at 125VAC. All receptacles shall be NEMA configuration type 5-15R.
c. Ground-fault interrupter receptacles shall be Lutron Claro style with two-pole, three-wire ground and rated 15A at 125VAC Configuration shall be of the duplex type with rectangular NEMA WD-6 design. Receptacles shall have a 5 milliampere ground-fault trip level with "test" and "reset" buttons.
3. Telephone Jack and Cable TV Jack Components Lutron Claro Style
a. Contractor shall provide an appropriate barrier (partition) to isolate jack from high-voltage wiring when ganged with a dimmer, fan-speed control, switch, or receptacle. This complies with NEC Articles 800-3 and 820-13.
b. Telephone jack shall be designed to mate with standard 4- or 6-conductor modular jacks, and be compatible with 2, 4, or 6 conductor lines. Telephone jacks shall meet FCC Part 68, paragraph F standards to ensure compatibility with U.S. telephone systems.
c. Cable TV jacks shall be the coaxial type, designed for use with standard 75-Ohm cables.
C. Wallplates Lutron Claro Style
1. Wallplates shall be manufactured from durable polycarbonate plastic with gloss finish, and shall attach to the basic components without using exposed hardware or screws.
2. Multigang wallplates shall provide a continuous, seamless cover for up to six-ganged decorator-style control and accessory combinations with no exposed hardware or screws.
3. Multigang wallplates shall include an adapter plate for proper device alignment and wallplate attachment.
4. Control, accessory and wallplate profiles shall not exceed .30 inches from wall surface to faceplate front surface.
5. To ensure a precise color match between all plastic parts, color variation of any gloss finish control or wallplate shall not exceed a delta E of 1, CIE L*a*b* color units, as defined in
ASTM E 308-99.
6. Visible parts of dimmers, switches, standard receptacles, cable jacks or any wallplate shall exhibit ultraviolet stability when tested with multiple actinic light sources as defined in ASTM D4674-89.
2.03 SOURCE QUALITY CONTROL
A. All dimming controls shall be 100% function tested at the time of manufacture. Statistical sampling plan shall not be acceptable.
c. Dimmers shall have a resettable overload protection that automatically shuts off when dimmer capacity is exceeded.
Protection methods that are non-resettable or require the device to be removed from the wall to reset shall not be acceptable.
d. Dimmers shall be designed to withstand a short, per UL 1472 section 5.10, between load hot and either neutral or ground without damage to the dimmer.
4. Magnetic Low Voltage (MLV) Transformer Dimmers
a. Provide MLV dimmers for direct control of up to 1000 volt amps of electronic low voltage load.
b. Dimmers shall contain circuitry specifically designed to control and provide a symmetrical AC waveform to the input of magnetic low voltage transformers per UL1472 section 5.11.
c. Dimmers shall not cause a magnetic low voltage transformer to operate above the transformers rated operating current or temperature.
d. Dimmer shall be capable of operating in either 3-way switch location.
5. Fluorescent Dimming Ballast Dimmers
a. Provide Fluorescent dimmers for direct control of fluorescent dimming ballasts up to the manufacturers specified rating.
b. Dimmers shall be designed to operate the following ballasts.
Dimmers and ballasts shall be produced by the same manufacturer to ensure proper ballast/control compatibility:
1) Hi-lume® Architectural Dimming Ballasts (1% 3-wire)
2) Hi-lume® CompactTM Lamp Dimming Ballasts
(5% 3-wire)
3) Eco-10TM Lighting Management Dimming Ballasts
(10% 3-wire)
4) Tu-Wire™ High Performance Dimming Ballasts
(5% 2-wire)
6. Remote dimming modules for high power loads
a. Where lighting loads exceed the full rated capacity of single dimmers, provide a Diva incandescent dimmer driving high power modules. High power module and dimmer shall be from the same manufacturer to ensure compatibility.
b. High power modules shall be remotely mounted.
c. High power module shall be rated and UL listed for control of incandescent, magnetic low voltage, electronic low voltage, fluorescent, and neon/cold cathode loads in increments of 2,000 Watts up to 30,000 Watts.
7. Fan-Speed Controls:
a. Fan-speed controls shall be UL Listed, CSA and NOM approved, Lutron Diva style.
b. Quiet fan-speed model shall provide three speed settings with paddle providing preset on and off.
c. Quiet fan-speed control shall provide single-pole/3-way control of one paddle fan (1.5A max.).
B. Accessories Lutron Claro Style
1. Switch Components Lutron Claro Style
a. Switches shall provide on/off control of any 120/277 VAC load up to 15A. Switches shall be UL Listed as general-use AC switches, Lutron Claro style.
b. Switches shall be available in single-pole, 3-way and 4-way configurations.
2. Receptacle Components Lutron Claro Style
a. All receptacles shall be UL Listed, CSA and NOM approved.
Controls
Have Questions? Call the Lutron Hotline 800-523-9466
PART 3 – EXECUTION
3.01 INSTALLATION
A. Contractor shall furnish all devices (dimmers, accessories, & wallplate kits), labor and other services necessary for the proper installation of the devices as indicated on the drawings and specified herein.
B. Contractor shall be responsible for derating dimmer capacity if side sections are removed.
C. Contractor shall run separate neutral wires in 120/208 VAC installations.
D. Devices shall be installed utilizing manufacturer's recommended application, wiring and installation instructions.
E. Contractor to provide seamless wallplate covers per specification
2.02 for all devices ganged in a common box. Contractor shall provide barriers within the box where required by code.
3.02 FIELD QUALITY CONTROL
A. Twenty-four hours a day, seven days a week, global customer service and technical hotline available.
B. Supplemental information shall be provided by manufacturer's Internet site.
Controls
Lutron Electronics Co., Inc.
7200 Suter Road • Coopersburg, PA 18036 U.S.A.
Made and printed in U.S.A. 03/2003 ©2003