Lutron High Bay Sensors.pdf
PDF 1 MB Posted
- Solicitation number
- RFP HAS 200000001821 1
- Issued by
- Genesee County, Michigan
About this file
This is a specification submittal document for Lutron wired occupancy sensors designed for high-bay applications. The document provides detailed technical specifications for four available sensor models: surface-mount and end-mount configurations, each available in 180-degree or 360-degree coverage options. The sensors are low-voltage, passive infrared devices engineered to control Lutron lighting systems in industrial environments such as warehouses, distribution centers, and gymnasiums, with maximum mounting heights of 45 feet and coverage radii up to 50 feet depending on installation height. All models are available in white, black, or gray finishes and feature adjustable timeout settings ranging from 8 seconds to 30 minutes for energy optimization.
The sensors operate on 20-24 volt DC input with maximum current draw of 30 milliamps and are controlled via a 12-pin DIP switch user interface. Installation specifications include detailed wiring requirements with maximum wire lengths varying by gauge and sensor quantity, compatibility with multiple Lutron control systems including QS Sensor Modules, EcoSystem ballasts, PP Series Power Packs, and Energi Savr Node units, and sensor placement guidelines that address line-of-sight requirements and environmental factors affecting performance. The devices are UL and CAN/USA certified for indoor use in climate-controlled environments with operating temperatures between 32-86 degrees Fahrenheit and non-condensing relative humidity of 0-95 percent. Construction features high-impact injection-molded plastic casing with dimensions of 4 inches in diameter and 1 inch in height, weighing approximately 7 ounces.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
®SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 1 01.24.2019
Lutron Sensors
Occupancy Sensors for High-Bay Applications
Features
| • | Surface-mount and end-mount models available. |
| • | 180° and 360° coverage lenses available. |
| • | Low-voltage, passive infrared (PIR) sensor. |
| • | Controls Lutron systems in high-bay applications. |
| • | End-mount model attaches directly to industrial T5HO |
and T8 fixtures through an extended ½ in (13 mm) chase nipple or junction box.
• Maximum 45 ft (14 m) mounting height.
(See next page for coverage diagrams.)
• Features an adjustable timeout for maximum energy savings.
• Ideal for warehouses, distribution centers, and gymnasiums.
Available Models
LUT-WSPSM24V-180-xx1-CPN6111 Surface-mount, 180° coverage LUT-WSPSM24V-360-xx1-CPN6111 Surface-mount, 360° coverage LUT-WSPEM24V-180-xx1-CPN6112 End-mount, 180° coverage LUT-WSPEM24V-360-xx1-CPN6112 End-mount, 360° coverage
Color WH White BL Black GR Gray
End-mount
Surface-mount
180° aisle lens
360° lens
1 �"xx" denotes the color. See choices above.
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 2 01.24.2019
Lutron Sensors ft
(9 m m ou nt in g he ig ht ft
(1 m ) m ou nt in g he ig ht
Coverage Diagrams Notes Sensor is designed to detect major motion (i.e., walking person) only A delay of 1 to 2 seconds from occupancy detection to turn-on may be experienced
42 ft (13 m) radius at 30 ft (9 m) mounting height
50 ft (15 m) radius at 45 ft (14 m) mounting height
Specifications
| • | 20 – 24 V- input 30 mA max. |
| • | User interface: 12-pin DIP switch |
| • | Available timer options: |
- 8 second test mode
- 4, 8, 16, and 30 minute timeouts
• Passive infrared: Dual element pyrometer and spherical Fresnel lens designed to detect major motion (i.e., walking person)
• Coverage: 360° or 180° See Coverage Diagrams for details.
Lens ratio:
- 30 ft (9 m) mounting height: 1.4:1
- 30 to 45 ft (9 to 14 m) mounting height: 1.1:1
• Construction: High-impact injection-molded plastic casing
• Size and weight: �4 in (102 mm) diameter 1½ in (38 mm) height 7 oz (198 g)
Sensor Placement
• To detect motion, the sensor requires line-of-sight of room occupants. The sensor must also have an unobstructed view of the room. Do NOT mount behind or near tall cabinets, shelves, hanging fixtures, ceiling fans, etc. The sensor cannot see through glass objects such as patio or shower doors.
• Hot objects and moving air currents can affect the performance of the sensor. To ensure proper operation, the sensor should be mounted at least 4 ft (1.2 m) away from HVAC vents and light bulbs that are below the ceiling line.
• The performance of the sensor depends on a temperature differential between the ambient room temperature and that of the room occupants.
Warmer rooms may reduce the ability of the sensor to detect occupants.
• Devices emitting Radio Frequency (RF) energy can affect the performance of sensors. To ensure proper operation, sensors should be mounted at least 4 ft (1.2 m) away from devices that emit radio waves (e.g., microwave ovens, wireless routers or other wireless devices).
• For additional information on placing sensors, please see the Occupancy/Vacancy Sensor Design and Application Guide (P/N 368-3197) located at www.lutron.com.
42 ft (13 m) at 30 ft (9 m) mounting height 50 ft (15 m) at 45 ft (14 m) mounting height
29 ft (9 m)
21 ft (6 m)
360° Lens Side View
180° Lens Top View
Operating Environment
| • | Indoor use only |
| • | Operating temperature: 32 °F – 86 °F (0 °C – 30 °C) |
| • | For use in climate controlled environments only |
| • | Relative humidity (non-condensing): 0 – 95% |
Certifications
| • | Conforms to UL STD 508, UL STD 244A |
| • | Certified to CAN/USA STD 22.2 No. 61010-1-04 |
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 3 01.24.2019
Lutron Sensors
Surface Mounting
Refer to this mounting template (rear view of sensor) for positioning mounting screw holes and wiring access hole.
Mounting hole
Use screws provided
Wiring access
Approx. 2 x 1 in (19 x 6 mm)
22 in (70 mm)
O N
1 2 3 4 5 6 7 8 9 10 11 12
Mounting: front view of sensor (lens removed)
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 4 01.24.2019
Lutron Sensors
Wiring Diagrams
Maximum Wire Lengths
Wire Size # Sensors 1 2 3
22 AWG
(0.5 mm2)
750 ft (229 m)
375 ft (114 m)
250 ft (76 m)
20 AWG
(0.65 mm2)
1200 ft (366 m)
600 ft (183 m)
400 ft (122 m)
18 AWG
(0.75 mm2)
2400 ft (732 m)
1200 ft (366 m)
800 ft (244 m)
Wiring to a QS Sensor Module (QSM)
| • | Maximum four (4) occupancy sensors per QSM |
| • | Refer to QSM Specification Submittal for additional details |
Note: Do NOT use blue wire for ANY installation.
Wiring to an EcoSystem Ballast
• Maximum one (1) occupancy sensor per EcoSystem ballast
• Refer to EcoSystem ballast Specification Submittal for additional details
Red (20 - 24 V-)
Gray (Signal)
Black (Common)
EcoSystem ballast To EcoSystem Bus
Occupancy sensor
Cap off remaining wires
Cap off remaining wires
Occupancy sensor
QS sensor module
R ed
(2
V
G ra y (S ig na l)
B la ck
(C om m on
To QS Link
C O M
O C C
V
COM
OCC
+20V
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 5 01.24.2019
Lutron Sensors
Wiring Diagrams
Maximum Wire Lengths
Wire Size # Sensors 1 2 3
22 AWG
(0.5 mm2)
750 ft (229 m)
375 ft (114 m)
250 ft (76 m)
20 AWG
(0.65 mm2)
1200 ft (366 m)
600 ft (183 m)
400 ft (122 m)
18 AWG
(0.75 mm2)
2400 ft (732 m)
1200 ft (366 m)
800 ft (244 m)
Wiring to a PP Series Power Pack
• Maximum three (3) occupancy sensors per power pack
Note: If using a power pack, the black wire on the occupancy sensor must be connected to the common terminal on both the Lutron lighting control system component and the power pack
Note: Do NOT use blue wire for ANY installation.
Wiring to an Energi Savr Node Unit
• Maximum one (1) occupancy sensor per Energi Savr Node input group
• Refer to Energi Savr Node Specification Submittal for additional details
Cap off remaining wires
Cap off
Cap off
Occupancy sensor
Occupancy sensor
Occupancy sensor
Lutron lighting control system component
Lutron lighting control system component
Lutron lighting control system component
Power pack Red (20 - 24 V-)
Black (Common)
B la ck
(C om m on
G ra y (S ig na l)
B la ck
(C om m on
G ra y (S ig na l)
B la ck
(C om m on
G ra y (S ig na l)
B la ck
B la ck
B la ck
Blue (cap off)
V
O C C
C O M
Cap off remaining wires
B la ck
(C om m on
Gray (Signal)
Red (20 - 24 V-)
Energi Savr Node Input Group
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 6 01.24.2019
Lutron Sensors
DIP Switch Function DIP Switch Setting 1: Mode
5 6
5 6
5 6
5 6
1 1
Off: Normal
5 6
5 6
5 6
1 1
On: Test (8 second time-out)
5 and 6: Timeout 8 minutes (default) 5 6
5 6
5 6
5: Off 6: Off 4 minutes
5 6
5 6
5 6
5: Off 6: On 16 minutes
5 6
5 6
5 6
5: On 6: Off 30 minutes
5 6
5 6
5 6
5: On 6: On
2 through 4 and 7 through 12:
MUST BE SET TO OFF
1 2 3 4 5 6 7 8 9 10 11 12
Set all to Off
O N
1 2 3 4 5 6 7 8 9 10 11 12
Occupancy Sensor with lens removed
Operation
The internal DIP switches allow the user to select Normal or Test mode, and to select the time-out. To access the DIP switches, rotate the lens counter-clockwise until a tab lines up with the single line, then remove the lens. (To lock the lens in place, rotate it clockwise until a tab lines up with the double line).
Lens locked in place Lens unlocked
DIP switches
)Lutron, Lutron, and EcoSystem are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.
Energi Savr Node is a trademark of Lutron Electronics Co., Inc.
| pdfformfields_file_11pages.pdf |
| pdfformfields_file_11pages.pdf |
| A: |
| B: |
| C: |
| D: |
| E: |
| F: |
| G: 1 |
| H: 2 |
| I: 3 |
| J: 4 |
| K: 5 |
| L: 6 |
File details come from the government source that posted it. Updated .