Plans.pdf
PDF 6 MB Posted
- Attached to
- Wekiva Golf Club Lift Station Improvements
- Solicitation number
- CC-5832-24/LTT
- Issued by
- Seminole County, Florida
About this file
The provided file is a comprehensive set of construction plans for the Wekiva Golf Club Pump Station project, prepared by CPH, Inc. for the Seminole County Board of County Commissioners' Environmental Services Department. The plans detail the construction of a new sanitary sewer pump station, including a fiberglass wet well, force main, electrical components, and associated site improvements. The project involves installing approximately 395 linear feet of 6-inch PVC sanitary sewer pipe, a new lift station with pumps, electrical controls, and necessary connections to existing infrastructure. The plans are dated August 2023 and include detailed civil, electrical, and site development drawings covering aspects such as topographic survey, plan and profile, electrical site plan, and various technical details.
The project is located within the Wekiva Golf Club area in Seminole County, Florida, and appears to be funded through the county's Environmental Services Department. The estimated project cost is $350,000.00, with the work involving abandonment of an existing drain field, construction of a new lift station, installation of gravity sewer and force main, electrical panel and control upgrades, and restoration of parking lot, sidewalks, and landscaping. The plans specify technical requirements for pipe materials, electrical installations, and site preparation, including details on excavation, bedding, and utility connections. The project seems designed to improve the existing wastewater infrastructure at the golf club facility, with careful attention to engineering standards and local utility requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© 2022 Microsoft Corporation © 2022 Maxar ©CNES (2022) Distribution Airbus DS © 2022 TomTom
J:
\S
0\ C iv il\
D W
G
C ur re nt
_P la n_ Se t\1
S0
C ov er .d w g
Ja n
, 2
- 1 :3
6p m n ni da
Know what's below.
before you dig.Call
R c 2023 FL P.E. No. 75410 Jeremy Morton, P.E.
*NOTICE*
THIS SET OF PLANS IS NOT VALID FOR CONSTRUCTION PURPOSES WITHOUT BEING STAMPED
"APPROVED FOR CONSTRUCTION BY CPH INC." PLANS WITHOUT THIS STAMP ARE GIVEN FOR
INFORMATIONAL PURPOSES ONLY.
BOARD OF COUNTY COMMISSIONERS
JOB# S09110
DATE: August 2023
CPH, corp.
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
C 2023 mwww.cphcorp.co
SEMINOLE COUNTY BOARD OF COUNTY COMMISSIONERS
ENVIRONMENTAL SERVICES DEPARTMENT
CONSTRUCTION PLANS FOR
Wekiva Golf Club Pump Station BOB DALLARI
JAY ZEMBOWER
LEE CONSTANTINE
AMY LOCKHART Chair ANDRIA HERR Vice Chair
DARREN GRAY
CHAIR, DISTRICT 1
DISTRICT 2
DISTRICT 3
DISTRICT 4
DISTRICT 5
COUNTY MANAGER
VICINITY MAP
SITE
ENVIRONMENTAL SERVICES DEPARTMENT
500 W LAKE MARY BLVD, SANFORD FL, 32773
407-665-2110
DIRECTOR DIRECTOR OF
ENVIRONMENTAL SERVICES:
UTILITIES ENGINEER.
DIVISION MANAGER:
PROJECT MANAGER:
CONSTRUCTION MANAGER:
KIM ORNBERG, P.E.
WILLIAM WHITE, P.E., CFM
DAN HEACOCK
DAVE MCBROOM
POC
Index of Sheets
C0.1 COVER SHEET
V1.1 TOPOGRAPHIC SURVEY
C0.2 GENERAL NOTES
C1.0 WEKIVA GOLF CLUB PUMP STATION
C2.0 PLAN AND PROFILE
C2.1 PLAN AND PROFILE
C5.0 ELECTRICAL SITE PLAN
C6.0 ELECTRICAL DETAILS
C7.0 ELECTRICAL CALCULATIONS
C8.0 DETAILS
C9.0 DETAILS
AutoCAD SHX Text A Full Service A & E Firm
SITE BENCHMARK #103
SITE BENCHMARK #101
SITE BENCHMARK #107
WEKIVA CLUB COURT
1234567
C 2023
Checked By:
Drawn By:
Approved By:
Job No.:
Date:
Field Crew:
8/29/2022
S09110
P. Katrek
T. Galloway J. Fleming
J. Castel
Sheet No.
V1.1
TO
PO
G R
A
PH
IC
S
U R
VE
Y
SE
C
TI
O
N
-T O
W N
SH
IP
SO
U
TH
-R
A N
G E
E
A
ST
SE
M
IN
O
LE
C
O U
N
TY
, F
LO
R
ID
A
W
EK
IV
A
G O
LF
C
LU
B
SE
M
IN
O
LE
C
O U
N
TY
B y
R ev is io n D at e
N o.
3/
/2
A dd s ep tic ta nk in fo rm at io n
PK
N
TITLE BLOCK ABBREVIATIONS
Eng. = ENGINEERING L.B. = LICENSED BUSINESS
C.O.A. = CERTIFICATE OF AUTHORIZATION Arch.= ARCHITECTURAL Landscp. = LANDSCAPE N/A = NOT APPLICABLE Lic. = LICENSED
No. = NUMBER P.O. = POST OFFICE © = COPYRIGHT
020 20 40
Scale: 1" = 20'
CPH, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida License:
Surveyor No. LB7143
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841 www.cphcorp.com Building Better
Communities Together
THIS SURVEY IS NOT VALID
WITHOUT SURVEY SHEETS
1 AND 2 OF 2.
Survey Sheet 2
AutoCAD SHX Text
2 STORY BRICK & WOOD FRAME BLDG
AutoCAD SHX Text
BRICK WALL
AutoCAD SHX Text
4' WOOD FENCE
AutoCAD SHX Text
METAL STAIRCASE
AutoCAD SHX Text
AC UNIT
AutoCAD SHX Text
4' WOOD FENCE
AutoCAD SHX Text
AC UNIT
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
CONCRETE BLOCK WALL
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
2' WOODEN FENCE
AutoCAD SHX Text
1 STORY METAL FRAME BUILDING FF ELEV=113.71
AutoCAD SHX Text
2' WOODEN FENCE
AutoCAD SHX Text
2' WOODEN FENCE
AutoCAD SHX Text
COOLER
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
BROKEN ASPHALT PAVEMENT
AutoCAD SHX Text
BROKEN ASPHALT PAVEMENT
AutoCAD SHX Text
BROKEN CONCRETE PAVEMENT
AutoCAD SHX Text
DIRT/GRAVEL AREA
AutoCAD SHX Text
DIRT/GRAVEL AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
PUTTING GREEN
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
EOI
AutoCAD SHX Text
EOI
AutoCAD SHX Text 60.1'
AutoCAD SHX Text 7.9'
AutoCAD SHX Text 3.5'
AutoCAD SHX Text 10.2'
AutoCAD SHX Text 3.6'
AutoCAD SHX Text
SEPTIC TANK ACCESS HOLE TOP ELEV=110.69 SE INV ELEV(4" PVC)=108.08
AutoCAD SHX Text
GTMH#1
AutoCAD SHX Text
GOLF CART PARKING AREA
AutoCAD SHX Text
GTMH#2
AutoCAD SHX Text SMH TOP ELEV=113.43 W INV ELEV(4" PVC)=111.46 TOP OF WATER ELEV=111.91 BOTTOM ELEV=107.7
AutoCAD SHX Text
FGI TOP ELEV=112.62 TOP OF WATER=112.10 TOP OF 'MUCK'=111.54 BOTTOM ELEV=109.74
AutoCAD SHX Text
8" ROUND DRAIN TOP ELEV=113.41
AutoCAD SHX Text 50.2'
AutoCAD SHX Text
SAND TRAP MATERIAL STOCKPILE AREA
AutoCAD SHX Text
METAL STORAGE SHED (OPEN SIDED)
AutoCAD SHX Text
4.5' HIGH BRICK WALL W/ 5'+ HIGH COLUMNS
AutoCAD SHX Text
4.5' HIGH BRICK WALL W/ 5'+ HIGH COLUMNS
AutoCAD SHX Text
2 STORY BRICK & WOOD FRAME BLDG FF ELEV=
AutoCAD SHX Text
4.5' HIGH BRICK WALL W/ 5'+ HIGH COLUMNS
AutoCAD SHX Text SANITARY SCHEDULE GTMH#1 TOP ELEV=110.03 NW INV ELEV(4" PVC)=108.08 BOTTOM ELEV=104.76 GTMH#2 TOP ELEV=110.05 SE INV ELEV(4" PVC)=108.26 BOTTOM ELEV=104.80
AutoCAD SHX Text SMH TOP ELEV=114.84 NE INV ELEV(8" PVC)=110.88 SW INV ELEV(8" PVC)=111.04 S INV ELEV(8" PVC)=111.10
AutoCAD SHX Text
SMH TOP ELEV=115.26 NE INV ELEV=RECESSED SW INV ELEV(8" PVC)=111.33
AutoCAD SHX Text
SMH TOP ELEV=115.82 NE INV ELEV(8" PVC)=111.93 NW, SW & S INV PIPES RECESSED
AutoCAD SHX Text
FF ELEV=110.47
AutoCAD SHX Text
FF ELEV=110.41
AutoCAD SHX Text 2.0'
AutoCAD SHX Text
COLUMN
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
SPIGOT
AutoCAD SHX Text
VISIBLE EDGE OF PAVEMENT
AutoCAD SHX Text
VISIBLE EDGE OF PAVEMENT
AutoCAD SHX Text
PLANTER
AutoCAD SHX Text SEPTIC TANK ACCESS HOLE TOP ELEV=111.07 TOP 4" PVC=107.85 INV ELEV (4"PVC)=107.52 BOTTOM ELEV=103.45
AutoCAD SHX Text SEPTIC TANK ACCESS HOLE TOP 4" PVC=107.61 INV ELEV (4"PVC)=107.28 BOTTOM ELEV=103.23
J:\S09110\Civil\DWG\_Current_Plan_Set\2 - S09110 TOPOGRAPHIC SURVEY.dwg, 11/7/2023 1:29:07 PM, Nida, Nicholas, 11/7/2023 1:29:07 PM, Nida, Nicholas11/7/2023 1:29:07 PM, Nida, Nicholas, Nida, NicholasNida, Nicholas
WEKIVA GOLF CLUB LS
LIFT STATION ADDRESS
STATION NAME STATION I.D. ADDRESS
4100 WEKIVA CLUB CT, LONGWOODWEKIVA GOLF CLUB LS
GENERAL PROVISIONS
1. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL MAKE A PRE-CONSTRUCTION VIDEO (DVD FORMAT) ALONG THE PROPOSED ROUTE IN ACCORDANCE WITH THE SPECIFICATIONS. IN PARTICULAR, THE VIDEO SHALL DOCUMENT THE CONDITION OF EXISTING DRIVEWAYS, BUILDINGS, STRUCTURES, MAILBOXES, SIGNS, FENCES, AND LANDSCAPING ALONG PROPOSED CONSTRUCTION AREAS.
2. THE CONTRACTOR SHALL RECOGNIZE AND ABIDE BY ALL OSHA EXCAVATION SAFETY STANDARDS, INCLUDING THE FLORIDA TRENCH SAFETY ACT (FS 553.60-553.64). ANY MATERIAL, CONSTRUCTION METHODS, OR MATERIAL COST TO COMPLY WITH THESE LAWS SHALL BE INCIDENTAL TO THE CONTRACT.
3. THE CONTRACTOR SHALL OBTAIN FROM THE OWNER COPIES OF ALL AVAILABLE REGULATORY AGENCY
PERMITS AND LOCAL AGENCY PERMITS.
4. ALL CONSTRUCTION PROJECTS 1 OR MORE ACRES IN SIZE THAT DISCHARGE TO OFFSITE AREAS ARE
REQUIRED TO COMPLY WITH THE REQUIREMENTS OF THE NATIONAL POLLUTANT DISCHARGE
ELIMINATION SYSTEM (NPDES) GENERAL PERMIT FOR STORMWATER DISCHARGE FROM SMALL AND LARGE CONSTRUCTION ACTIVITIES. IN ORDER TO MEET NPDES REQUIREMENTS, THE CONTRACTOR IS RESPONSIBLE FOR PREPARING A STORMWATER POLLUTION PREVENTION PLAN (SWPPP), IMPLEMENTING, INSPECTING, MAINTAINING, AND REPORTING ON ALL ELEMENTS OF THE SWPPP, COMPLETING AND SUBMITTING THE REQUIRED NOTICE OF INTENT (NOI) AND NOTICE OF TERMINATION (NOT) FORMS AS THE
OPERATOR, AND PAYING ALL ASSOCIATED FEES.
5. THE EROSION AND SEDIMENT CONTROL MEASURES SHOWN ON THE PLANS REPRESENT A MINIMUM REQUIREMENT. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ADDITIONAL EROSION AND SEDIMENT CONTROL MEASURES NEEDED IN ORDER TO PREVENT THE TRANSFER OF SEDIMENT FROM THE PROJECT AREA AND PREVENT THE EROSION OF SURFACES DURING CONSTRUCTION, AS NEEDED TO
PROTECT ADJACENT PROPERTIES AND WATER BODIES.
6 IN THE EVENT THAT WATER IS ENCOUNTERED DURING CONSTRUCTION, DEWATERING SHALL BE CONDUCTED. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION, OPERATION, AND SUBSEQUENT REMOVAL OF DEWATERING SYSTEMS AND THEIR SAFETY AND CONFORMITY WITH
LOCAL CODES AND REGULATIONS. IF DEWATERING EQUIPMENT NEEDED EXCEEDS ANY OF THE
FOLLOWING: 1) 6" PUMP VOLUTE; 2) 100,000 GPD TOTAL 24 HOUR (1 DAY) DEWATERING, AND; 3) 1,000,000 GPD PUMP CAPACITY, THE CONTRACTOR SHALL BE REQUIRED TO PERMIT THE DEWATERING SYSTEM WITH THE ST. JOHNS RIVER WATER MANAGEMENT DISTRICT (SJRWMD). THE ENGINEER AND/OR OWNER
SHALL BE NOTIFIED IMMEDIATELY IF ANY OF THE ABOVE THRESHOLDS ARE EXCEEDED.
7. DEWATERING DISCHARGE FROM THE SITE SHALL COMPLY WITH ALL NPDES GENERAL PERMIT
REQUIREMENTS AND STATE WATER QUALITY STANDARDS. PROVIDE ALL TESTING AND PERMITTING REQUIRED AND COMPLY WITH ALL TREATMENT OR DISPOSAL METHODS REQUIRED TO MEET ALL LOCAL, STATE AND FEDERAL REQUIREMENTS.
8. UNLESS OTHERWISE DIRECTED BY THE OWNER OR ENGINEER, THE CONTRACTOR IS EXPECTED TO CONTAIN ALL CONSTRUCTION ACTIVITIES WITHIN THE PROPERTY BOUNDARY, RIGHT-OF-WAY AND EASEMENTS, AND OTHER AREAS SPECIFICALLY DESIGNATED FOR CONSTRUCTION. AT NO TIME SHALL THE CONTRACTOR DISTURB SURROUNDING PROPERTIES OR TRAVEL ON SURROUNDING PROPERTIES
WITHOUT WRITTEN CONSENT FROM THE PROPERTY OWNER. ANY REPAIR OR RECONSTRUCTION OF
DAMAGED AREAS IN SURROUNDING PROPERTIES SHALL BE REPAIRED BY THE CONTRACTOR ON AN IMMEDIATE BASIS. ALL COSTS FOR REPAIRS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND
NO EXTRA COMPENSATION SHALL BE PROVIDED.
9. UNLESS OTHERWISE NOTED ON THE PLANS, THE CONTRACTOR SHALL USE THE GEOMETRY PROVIDED ON THE CONSTRUCTION PLANS. BENCHMARK INFORMATION SHALL BE PROVIDED TO THE CONTRACTOR BY THE OWNER OR OWNER'S SURVEYOR. ANY DISCREPANCIES BETWEEN FIELD MEASUREMENTS AND
CONSTRUCTION PLAN INFORMATION SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER
IMMEDIATELY.
10. BASE SURVEY INFORMATION INCLUDING BUT NOT LIMITED TO ELEVATIONS, EASEMENTS, RIGHTS OF WAY, AND OTHER TOPOGRAPHIC INFORMATION HAS BEEN PREPARED BY OTHER PROFESSIONALS. CPH, LLC ASSUMES NO RESPONSIBILITY FOR THE ACCURACY OF THIS INFORMATION.
11. THIS SET OF PLANS MAY CONTAIN DRAWINGS PREPARED BY OTHER PROFESSIONALS, WHICH CONTAIN THE NAME, ADDRESS, AND LOGO OF THE PROFESSIONAL. CPH, LLC IS NOT RESPONSIBLE FOR DRAWINGS
PREPARED BY OTHER PROFESSIONALS.
12. THE ENTIRE PROJECT SITE SHALL BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK.
CLEAN ALL INSTALLED PIPELINES, STRUCTURES, SIDEWALKS, PAVED AREAS, ACCUMULATED SILT IN PONDS, PLUS ALL ADJACENT AREAS AFFECTED BY CONSTRUCTION, AS DIRECTED BY THE OWNER OR JURISDICTIONAL AGENCY. EQUIPMENT TO CLEAN THESE SURFACES SHALL BE SUBJECT TO APPROVAL BY
THE OWNER.
EXISTING UTILITIES
1. THE UTILITY DATA SHOWN ON THESE PLANS WAS LOCATED BY THE RESPECTIVE UTILITY, OR
IS BASED ON UTILITY DRAWINGS, MAPS, OR FIELD RECONNAISSANCE.
2. THE LOCATION, MATERIAL TYPE, AND SIZE OF ALL EXISTING UTILITIES SHOWN ON THE PLANS
HAVE BEEN DETERMINED FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN FOR THE
CONVENIENCE OF THE CONTRACTOR. THE OWNER ASSUMES NO RESPONSIBILITY FOR THEIR
ACCURACY. PRIOR TO THE START OF ANY CONSTRUCTION ACTIVITY, THE CONTRACTOR
SHALL CONDUCT ALL INVESTIGATIONS NEEDED TO DETERMINE THE HORIZONTAL AND
VERTICAL ELEVATIONS OF EXISTING UTILITIES THAT WILL BE CONNECTED TO, CROSSED, OR
OTHERWISE BE LOCATED IN THE VICINITY OF THE PROPOSED CONSTRUCTION. AT PROPOSED
CONNECTIONS, INVESTIGATIONS SHALL EXTEND BEYOND THE POINT OF CONNECTION AS
NEEDED TO ADJUST PROPOSED CONNECTION POINTS DUE TO UTILITY CONFLICTS. IN THE
EVENT SIDEWALK OR PAVEMENT IS IMPACTED IN ORDER TO CONDUCT THESE
INVESTIGATIONS, THE COST OF TRAFFIC CONTROL AND RESTORATION IS INCIDENTAL TO THE
CONTRACT. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY ALL UTILITIES OF
THE CONSTRUCTION AND TO MAKE THE NECESSARY ARRANGEMENTS TO PROTECT ALL
EXISTING UTILITIES. ANY UTILITIES THAT INTERFERE WITH THE PROPOSED CONSTRUCTION
SHALL BE CLOSELY COORDINATED WITH THE OWNER AND THE RESPECTIVE UTILITY
COMPANY FOR RELOCATION OR PROPER INSTRUCTION.
3. A SINGLE POINT UTILITY IDENTIFICATION SERVICE HAS BEEN SET UP FOR EXISTING UTILITIES.
THE CONTRACTOR IS TO CONTACT THE SUNSHINE STATE ONE CALL CENTER BY DIALING “811”
AT LEAST TWO (2) AND NO MORE THAN FIVE (5) WORKING DAYS PRIOR TO THE SPECIFIC
CONSTRUCTION ACTIVITY FOR FIELD LOCATION. NOTE THAT NOT ALL UTILITIES PARTICIPATE
IN THIS PROGRAM. THE CONTRACTOR SHOULD CONTACT ALL NON-PARTICIPATING UTILITIES
SEPARATELY FOR FIELD LOCATION OF THEIR FACILITIES AT LEAST TWO (2) WORKING DAYS
PRIOR TO CONSTRUCTION.
4. THE FOLLOWING UTILITIES HAVE PREVIOUSLY INDICATED THAT THEY MAY HAVE FACILITIES IN
THE VICINITY OF THE CONSTRUCTION AREA:
THE CONTRACTOR SHALL KEEP LOCATE TICKETS UP TO DATE AT ALL TIMES.
5. THE CONTRACTOR IS RESPONSIBLE FOR ALL COORDINATION WITH EACH UTILITY AND ALL
COSTS ASSOCIATED WITH THE PROTECTION OF EXISTING FACILITIES DURING
CONSTRUCTION. THE CONTRACTOR SHALL ALSO COORDINATE NECESSARY RELOCATIONS
OR OTHER CONSTRUCTION RELATED MATTERS WITH EACH UTILITY.
6. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN IN SERVICE ALL EXISTING
PIPING ENCOUNTERED DURING CONSTRUCTION UNLESS OTHERWISE INDICATED IN THE
DRAWINGS. ANY PIPING WHICH CAN BE REMOVED DURING CONSTRUCTION WITHOUT
UNDUE INTERRUPTION OF SERVICE MAY BE REMOVED AND REPLACED BY THE
CONTRACTOR WITH THE PERMISSION OF THE OWNER AND THE ENGINEER.
7. THE CONTRACTOR SHALL FIELD LOCATE ALL WATER AND SEWER SERVICES AND LATERALS
WITHIN THE PROPOSED CONSTRUCTION AREA PRIOR TO CONSTRUCTION AND ADJUST THE
PROPOSED CONSTRUCTION AS NEEDED TO ACCOMMODATE THESE EXISTING LINES.
8. TYPICAL DETAILS AND PROPOSED CONSTRUCTION AS SHOWN ILLUSTRATE THE ENGINEER'S
INTENT AND ARE NOT PRESENTED AS A SOLUTION TO ALL CONSTRUCTION PROBLEMS
ENCOUNTERED IN THE FIELD. THE CONTRACTOR MAY ALTER THE PROPOSED
CONSTRUCTION TO SUIT FIELD CONDITIONS, PROVIDED IT COMPLIES WITH THE PROJECT
SPECIFICATIONS AND APPROVAL IS RECEIVED FROM THE ENGINEER. WHERE SUCH
PROPOSED REVISIONS DEVIATE FROM THE FDEP CONSTRUCTION PERMIT, THEN SUCH
REVISIONS WILL ALSO REQUIRE APPROVAL FROM FDEP.
9. FOR EACH RESPECTIVE PIPELINE CONSTRUCTION REQUIRED, THE CONTRACTOR SHALL
FIELD VERIFY THE LOCATION, DEPTH, SIZE, MATERIAL TYPE, AND ALIGNMENT OF ALL
EXISTING PIPES, CABLES, ETC. TO BE CROSSED OR CONNECTED TO. IF THE CONTRACTOR
DEEMS NECESSARY (A) A CHANGE IN ALIGNMENT OR DEPTH, OR THE NEED FOR ADDITIONAL
FITTINGS, BENDS, OR COUPLINGS, WHICH REPRESENT A DEPARTURE FROM THE CONTRACT
DRAWING, OR (B) A NEED FOR RELOCATION OF EXISTING UTILITIES, THEN DETAILS OF SUCH
DEPARTURES, RELOCATIONS, OR ADDITIONAL FITTINGS, INCLUDING CHANGES IN RELATED
PORTIONS OF THE PROJECT AND THE REASONS THEREFORE, SHALL BE SUBMITTED WITH
SHOP DRAWINGS. APPROVED DEPARTURES FOR THE CONTRACTOR'S CONVENIENCE SHALL
BE MADE AT NO ADDITIONAL COST TO THE OWNER.
TRAFFIC CONTROL
1. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A TEMPORARY TRAFFIC CONTROL
PLAN (TTCP) PRIOR TO CONSTRUCTION. THE TTCP (ALSO CALLED A MAINTENANCE OF
TRAFFIC (MOT) PLAN) SHALL SHOW ALL PROPOSED TRAFFIC CONTROL SIGNS, PAVEMENT
MARKINGS, AND BARRICADES, AND SHALL DETAIL ALL PROPOSED CONSTRUCTION
SEQUENCING. THE TTCP PLAN AND INSTALLED TRAFFIC CONTROL MEASURES SHALL BE
APPROVED BY THE ENGINEER, OWNER, AND ROADWAY JURISDICTIONAL AGENCY. IN
GENERAL, ROADWAY LANE CLOSURES AND DRIVEWAY CLOSURES ARE PROHIBITED
DURING CONSTRUCTION UNLESS SPECIFICALLY DETAILED ON THESE PLANS. IN THE
EVENT IT IS DETERMINED THAT ROADWAY AND DRIVEWAY CLOSURES WILL BE ALLOWED,
THE CLOSURES SHALL BE RESTRICTED TO THE HOURS BETWEEN 9:00 A.M. AND 3:00 P.M.
UNLESS OTHERWISE AUTHORIZED IN THE APPROVED TTCP PLAN.
2. ALL TRAFFIC CONTROL MEASURES SHALL BE IN ACCORDANCE WITH FDOT STANDARD
PLANS FOR ROAD CONSTRUCTION, INDEX NO. 102-600 AND THE MANUAL ON UNIFORM
TRAFFIC CONTROL DEVICES (MUTCD). ALL TRAFFIC CONTROL MEASURES SHALL BE
INSTALLED PRIOR TO CONSTRUCTION AND MAINTAINED DURING CONSTRUCTION.
3. INSPECT TRAFFIC CONTROL DEVICES ON A DAILY BASIS TO ENSURE PLACEMENT OF
BARRICADES AND FUNCTION OF LIGHTS IS MAINTAINED THROUGHOUT CONSTRUCTION.
4. CONTACT PROPERTY OWNERS AFFECTED BY CONSTRUCTION. COORDINATE TEMPORARY
DRIVEWAY CLOSURES AND SEQUENCING. MAINTAIN ACCESS FOR ALL PROPERTY
OWNERS DURING CONSTRUCTION.
5. WET UNSTABILIZED AREAS AS NECESSARY TO CONTROL DUST.
6. ADJUST TRAFFIC CONTROL DEVICES AS REQUIRED UNDER EMERGENCY CONDITIONS.
7. THE CONTRACTOR IS EXPECTED TO COORDINATE ITS ACTIVITIES WITH OTHER
CONTRACTORS WHO MAY BE WORKING IN THE IMMEDIATE VICINITY.
8. WHEN WORK OCCURS ALONG TWO LANE, TWO WAY ROADS AND IS WITHIN 15-FT OF
ACTIVE ROAD TRAVEL WAY BUT NO CLOSER THAN 2-FT FROM THE TRAVEL WAY, SIGNAGE
AND WARNING DEVICES ARE TO BE INSTALLED IN ACCORDANCE WITH FDOT INDEX NO.
102-600 AND 102-602. WHEN WORK OCCURS ALONG TWO LANE, TWO WAY ROADS
BETWEEN THE ROAD CENTERLINE AND A LINE 2-FT OUTSIDE THE EDGE OF THE TRAVEL
WAY, SIGNAGE AND WARNING DEVICES ARE TO BE INSTALLED IN ACCORDANCE WITH FDOT
INDEX NO. 102-600 AND 102-603.
9. TYPE I OR TYPE II BARRICADES AT 20-FT CENTERS SHALL BE PLACED AND MAINTAINED
ALONG THE EDGE OF THE ROAD WHEREVER HAZARDS EXIST AND TO BLOCK ENTRANCE
INTO COMPLETED OR PARTIALLY COMPLETED PAVEMENTS UNTIL SUCH PAVEMENTS ARE
OPEN TO PUBLIC USE.
10. WHERE A DROP-OFF CONDITION IN THE WORK ZONE OCCURS, IT SHALL BE MITIGATED IN
ACCORDANCE WITH FDOT INDEX 102-600. REFER TO FDOT INDEX NO. 102-600 FOR THE
DEFINITION OF A DROP-OFF.
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com C 2023
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS.
CPH ,LLC
A Full Service A & E Firm
Plans Prepared By:
Building Better
Communities Together
C0.2 GENERAL NOTES
WEKIVA GOLF CLUB
FORCE MAIN AND PUMP STATION
SEMINOLE COUNTY
N.NIDA
N.NIDA
J.Morton 6/2023 S09110# #
JEREMY CRAIG MORTON
PE FL 75410
J:\S09110\Civil\DWG\_Current_Plan_Set\S09110 - General Notes.dwg, 11/7/2023 1:44:07 PM, Nida, Nicholas, , 11/7/2023 1:44:07 PM, Nida, Nicholas, 11/7/2023 1:44:07 PM, Nida, Nicholas, , Nida, Nicholas, Nida, Nicholas, , PUMPS: (3 YR. WARRANTY)
R
IL
E Y
C om pa ny , I nc
B en ch m ar k
La ne
Sa nf or d, F L
PH
. 4
-2
-9
ALUMINUM COVER
w/ (LOCKABLE)
ACCESS HATCH
FIBERGLASS WETWELL
H-20 LOAD RATED
w/ 20 YR. WARRANTY
S.S. HINGES
"A"
FIBERGLASS VALVE BOX (LOCKABLE)
NOTE: PUMP CONTROL PANEL
SHALL BE LOCATED 3 FEET
FROM WETWELL PERIMETER
AT POINT "A"
CONCRETE AS REQ'D BY ENGINEER TO PREVENT FLOTATION
CU. YDS. MAKE MONOLITHIC POUR WITH BOTTOM SLAB
BASIN ANTI-FLOTATION FLANGE
CONCRETE BASE SLAB AS PER
SPECIFICATIONS w/ #4 REBAR 18" O.C.
INTEGRAL FIBERGLASS SLOPE
(2") CAST-IRON FLANGED CHECK VALVE
(2") CAST-IRON FLANGED BALL VALVE
EMERGENCY PUMP-OUT
w/ BALL VALVE
2.5" SS (0-100 PSI) PRESSURE GAUGE
w/ SHUT-OFF VALVE
5.5
After the H-20 load rated wetwell has been installed, the ASTM Certification Number and Serial Tracking Number must be visible inside wetwell.
The H-20 Load Rated Fiberglass Wetwell Must Be Manufactured By L.F.
Manufacturing, Giddings, Texas, Which Includes a 20 Yr. Warranty.
Certification of the wetwell H-20 load rating must be supplied with submittals.
H-20 certification must be signed and sealed by an engineer registered in the State of Florida.
INTEGRAL
LIFTING LUGS
3- (2") FIELD
INSTALLED KNOCKOUTS
FOR ELECTRICAL
CONDUITS
2' MIN.
84"
18"
6"
6"
INTEGRAL
FIBERGLASS
SLOPE
316SS
LIFTING
CHAIN
48"
HLA
LAG
LEAD
OFF
2" PVC
DRAIN
("P-TRAP")
INLET
FIELD INSTALLED
6"
RILEY & COMPANY
3" ACTIVATED
CHARCOAL
FILTER VENT
8"1
316SS CABLE
BRACKET
COMPOSITE WATER-TIGHT
INLET SLEEVE w/SS NUTS
& BOLTS
6"
LIFT STATION WILL BE PRIVATELY
OWNED AND MAINTAINED.
NO SUBSTITUTIONS - NO ALTERNATES
1. Water service with hose bibb and reduced pressure backflow preventer to be installed near lift station. (See Electrical Riser Illustration)
2. System shall be operated and maintained to provide uninterrupted service as required by DEP Chapter 62-604.500.
3. Approved Operation & Maintenance Manual(O&M) shall be kept available for operation and maintenance personnel
4. A weather resistant emergency contact sign shall be installed at the lift station and made visible to the public (Lettering shall be min. 2" in height.
SEE ELECTRICAL
RISER
RILEY & COMPANY, INC.
W E
K
IV
A G
O
LF
C
LU
B P
U M
P
ST
A
TI
O N
SANFORD, FL 32773
(407)265-9963
DUPLEX CONTROL PANEL: (3 YR. WARRANTY)
The Enclosure shall be NEMA 4X, minimum 30" high x 30" wide x 10" deep fiberglass with 4 point latching system.
The enclosure shall have external mounting feet to allow for wall mounting.
The following components shall be mounted through the enclosure:
1- ea. Red Alarm Beacon (Light) 4" x 4" Minimum Diameter 1- ea. Alarm Horn (minimum 95 DCB) 1- ea. Generator Receptacle w/ weatherproof cover(SCM460 -UL 1686) 1- ea. Alarm Silence Pushbutton
The back panel shall be fabricated from .125, 5052-H32 marine alloy aluminum. All components shall be mounted by machined stainless steel screws.
The following components shall be mounted to back panel:
2- ea. Motor Contactors 1- ea. Phase Monitor (1 Ph) w/2 N/O & 1 N/C Contacts 1- ea. Control Transformer (480 Volt Only) (Min. 500VA) 1- ea. Lightning Arrestor 1- ea. Silence Relay Module 1- ea. Duplex Alternator w/ Pump Selector Switch 1- ea. Model RCBB5AH Battery Back-Up w/ Smart Charger For The High Level Alarm System 20- ea. Terminals For Field Connections 6- ea. Terminals For Motor Connections (Single Phase Only) 7- ea. Grounding Lugs 1- ea. Seal Failure Relay
The inner door shall be fabricated from .080, 5052-H32 marine alloy aluminum. The inner door shall have a continuous aluminum piano hinge.
The following components shall be mounted through the inner door:
1- ea. Main Circuit Breaker 1- ea. Emergency Circuit Breaker 1- ea. Mechanical Interlock For Emergency And Main Breakers (UL Listed) 2- ea. Short Circuit Protectors w/ Auxiliary Contacts 1- ea. Control Circuit Breaker 2- ea. Seal Failure Indicator Lights 1- ea. Hand-Off-Auto Selector Switches 2- ea. Pump Run Pilot Lights 1- ea. Power On Pilot Light 2- ea. Elapse Time Meters (Non-Resetable) 1- ea. GFI Duplex Convenience Outlet
To insure complete unit and warranty responsibility the electrical control panel must be manufactured and built by the pump supplier. The pump supplier must be a TUV (UL508A CERTIFIED) manufacturing facility, with a minuimum of 10 years history in the manufacturing of electrical control panels.
5. INSPECTION & TESTING: A factory representative shall be provide for a one (1) time start-up and shall have complete knowledge of the proper operation and maintenance for the complete system.
SWITCH DISCONNECT
CONTROL PANEL
GENERATOR RECEPTOR
MODEL UL 1686 SCM460
GALVANIZED
UNISTRUT
3/4" HOSE BIB
3/4"GALV. RISER
SLEEVE REQUIRED
ELECTRIC METER OR PULL
POWER FROM BUILDING
2" CAPS
LIGHTNING ARRESTOR FIELD
MOUNTED BY ELECTRICIAN
3- SEAL-OFFS ( 2" ) BY ELECTRICIAN
PUMP POWER CABLES (2" RIGID CONDUITS)
2" RIGID ALUMINUM POSTS
M
IN
CONCRETE AROUND POSTS
12" DIA. x 24" DEEP
TO SERVICE LOCATION
(VERIFY w/ POWER CO.)
TO WATER SUPPLY
REDUCED PRESSURE (RPZ) BACKFLOW PREVENTER
TO BE INSTALLED IN WATER SUPPLY LINE TO
LIFT STATION "FEBCO WATTS" (OAE)
NOTE: GROUND
ROD
" FLOAT SWITCHES (2" RIGID CONDUIT)
ELECTRICAL RISER FOR
ILLUSTRATION PURPOSES ONLY
NOTES:
* ELECTRICIAN NOTES:
1. DRAWING NOT TO SCALE
2. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES
3. ELECTRICIAN SHALL SEAL OFF CONDUIT RUNS
4. ELECTRICIAN TO MOUNT LIGHTNING ARRESTOR AT SWITCH DISCONNECT
5. CONTRACTOR SHALL VERIFY POWER SOURCE PRIOR TO ORDERING EQUIPMENT
6. NEUTRAL TO BE SUPPLIED FOR 230V-SINGLE PHASE POWER.
RILEY & Company, Inc. (H-20 GP) c w/ BATTERY BACK-UP FOR AUDIO - VISUAL ALARMS
3'
NOTE: COMPLETE SYSTEM TO BE SUPPLIED BY:
HOMA
'TDH
PRIMARY PUMP CAPACITY
PRIMARY TDH
PUMP MANUFACTURER
PUMP MODEL #
R.P.M.
HORSEPOWER
ELECTRICAL/ VOLTS / PHASE
FULL LOAD AMPS/ PER PUMP
GPM
PUMP DATA
29.8 19.8
RC10056
3 3/4" 230V/1
2"PUMP DISCHARGE SIZE
3.2
TOP OF WETWELL
INLET INVERT
HIGH LEVEL ALARM (HLA)
2nd PUMP ON (LAG)
1st PUMP ON (LEAD)
PUMPS OFF (OFF)
BOTTOM OF WETWELL
WETWELL DIAMETER
ELEVATIONS
113.60
102.20 101.70
101.20
98.10 48"
100.40
IMPELLER DIAMETER
1.0
08-22-23SR
VENT
Submersible pumps shall be HOMA RC10056. The pumps shall be installed in the H-20 GP FRP wetwell utilizing a slide rail system.
pump and the HDPE discharge piping.
Stator winding shall be open type with Class H insulation and shall be heat-shrink fitted into the stator housing. The use of pins, bolts, or other fastening devices is not acceptable.
winding and shall be connected in series with the magnetic contactor coil in the control panel to stop motor if winding temperature exceeds 140 C., but shall automatically reset when the winding temperature returns to normal.
Two heat sensor thermostats shall be used on three phase motors.
The grinder unit shall be capable of macerating materials normally found in domestic and commercial sewage into a fine slurry which will pass through the
A heat sensor thermostat shall be attached to the top end of the motor
The pump motor grinder shaft shall be AISI 430F SS threaded to take the pump impeller and the grinder impeller.
Upper & lower mechanical seals shall be Silicon Carbide vs Silicon Carbide.
102.70
24"
36"
PRIVATE
SANITARY SEWER
PUMP STATION
IN CASE OF EMERGENCY CONTACT THE
FOLLOWING NUMBERS:
FACILITY OWNED BY:
18"
NAME:
PHONE NUMBER:
FACILITY MAINTAINED BY:
NAME:
PHONE NUMBER:
STATION NUMBER:
24"
NOTE: CONTRACTOR MUST SUPPLY
INFORMATION SIGN AT START-UP.
SLIDE RAILS SCH.40 AISI 304SS PIPE 2"
HDPE SDR11 w/ HEAT-FUSED CONNECTIONS 2"
SS DISCHARGE PIPE SUPPORTS
FIN GRADE
M
IN
2" F.M.
MIN. 1/2" DIA. x 3" SS BOLTS WELDED TO A (2" x 18" x 1/4" )
SS ANCHOR PLATE EMBEDDED IN FIBERGLASS
WETWELL BOTTOM BOLT DETAIL
PUMP DISCHARGE
BASE
9" COMPACTED #57 STONE
ELECTRICAL INFORMATION IS SHOWN FOR REFERENCE ONLY AND IS NOT
INCLUDED AS PART OF THE ENGINEERING DESIGN OR CERTIFICATION BY THE
PROFESSIONAL ENGINEER. ANY ELECTRICAL DESIGN NEEDED FOR THE LIFT
STATION SHALL BE CONFIRMED AND CERTIFIED BY A PROFESSIONAL
ELECTRICAL ENGINEER.
THIS IS A COPYRIGHTED DRAWING. ANY CHANGES OR
MODIFICATIONS WITHOUT WRITTEN APPROVAL FROM
RILEY & COMPANY, INC. IS STRICTLY PROHIBITED. C
8"1
SS CHANNEL - PIPING
& VALVE SUPPORTS
(32" x 30" x 24" DEEP)
FIBERGLASS VALVE BOX
C1.0 S09110
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
REVISIONS BY
AutoCAD SHX Text
* 2. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES
AutoCAD SHX Text
* 3. ELECTRICIAN SHALL SEAL OFF CONDUIT RUNS 3. ELECTRICIAN SHALL SEAL OFF CONDUIT RUNS
AutoCAD SHX Text
* 4. ELECTRICIAN TO MOUNT LIGHTNING ARRESTOR AT SWITCH DISCONNECT 4. ELECTRICIAN TO MOUNT LIGHTNING ARRESTOR AT SWITCH DISCONNECT
AutoCAD SHX Text
* 5. CONTRACTOR SHALL VERIFY POWER SOURCE PRIOR TO ORDERING EQUIPMENT
SITE BENCHMARK #107
109.924
113.347
113.569
11+00 12+00
SCALE: 1" = 20' HORZ
1" = 2' VERT
13+00 14+00
EXISTING GRADE
N
Graphic Scale in Feet
20 20 40
SMH-1
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com C 2024
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS.
CPH ,LLC
A Full Service A & E Firm
Plans Prepared By:
Building Better
Communities Together
C2.0WEKIVA GOLF CLUB
FORCE MAIN AND PUMP STATION
SEMINOLE COUNTY
N.NIDA
N.NIDA
J.Morton 6/2023 S09110# #
JEREMY CRAIG MORTON
PE FL 75410
15+00
PROP 395 LF 6" PVC SAN@.50% SLOPE
LS-1
LS-1, PER SCUEM 16
AND LS DETAIL C1.0
RIM 113.50
INV (NW) 102.62
INV (E) 109.14
TOP FM (S) 110.50
INV (E) 102.62
(EXTERNAL DROP)
SMH-1
PER SCUEM
TOP ELEV. 109.92
INV (N) 105.00
INV (SE) 104.90
SMH-1
PER SCUEM 12
AND DETAIL S-1
RIM 109.92
INV (N) 105.07
INV (SE) 104.97
PROP 395 LF 6" PVC SAN @ .50% SLOPE
EXISTING SEPTIC TANK AND
DRAINFIELD TO BE ABANDONED IN
PLACE. CONTRACTOR TO PERMIT
ABANDONMENT WITH FDEP PRIOR
TO CONSTRUCTION
PROP. 6" PVC WYE WITH CLEANOUT
RIM. 109.33
INV. (S) 105.79
EXIST. PVC SAN C/O
CONTRACTOR TO VERIFY LOCATION
PRIOR TO CONSTRUCTION
PROP. ~ 31 LF 6" PVC SAN SERVICE @ 1% MIN. SLOPE
CONNECT TO EXIST. C/O
PROP. 122 LF 6" PVC SAN SERVICE @ 0.5% MIN. SLOPE
SEPTIC FIELD TO BE
REMOVED AND AREA
RESTORED
CORE BORE EXIST. GREASE INTERCEPTOR (SW).
RECONFIGURE INTERNAL SKIMMER TO ORIGINAL
DESIGN SPECIFICATIONS, AND INVERT, AS REQUIRED.
3 LF 6" PVC GL SERVICE @ 1% MIN. SLOPE
CONTRACTOR TO CONFIRM MATERIAL AND SIZE
PRIOR TO CONSTRUCTION
EX. GREASE LINE TO BE CUT AND CAPPED AT THE
GREASE INTERCEPTOR. CAP SHALL BE PRESSURE RATED, OR
ENTIRE LINE REMOVED AND EX. CORE GROUTED/MUDDED.
EXISTING SEPTIC TANK AND DRAINFIELD TO BE
ABANDONED IN PLACE. CONTRACTOR TO PERMIT
ABANDONMENT WITH FDEP PRIOR TO CONSTRUCTION
PROP. 6" PVC SAN SERVICE PER
SEMINOLE COUNTY DETAIL 301
RIM. 110.05
INV. (S) 105.18
LS-1
PER SCUEM 16
AND LS DETAIL C1.0
RIM 113.50
INV (NW) 102.62
INV (E) 109.14
INV (E) 102.62
(INTERNAL DROP)
116 LF 4" PVC SAN @ 2.0% SLOPE
122 LF 6" PVC SAN @
.50%
SLO
PE
2" HDPE SAN FM
TOP 110.50
PROP 116 LF 4" PVC SAN @ 2% SLOPE
3' C
O
VE
R , T
YP
PROP. 116 LF
4" PVC SAN W/ C/O
PLAN AND PROFILE
PROP. 4" PVC
SAN CONNECTION
4" SAN PVC 111.46
PROP. C/O
CONNECT EX.
SERVICES
PROP.
116 LF 4" PVC SAN
INV (W) 111.46
CONNECT EXISTING
SAN SERVICES AT C/O
EXI. SEPTIC TANK AND
DRAINFIELD TO BE
ABANDONED IN PLACE.
CONTRACTOR TO PERMIT
ABANDONMENT WITH FDEP
PRIOR TO CONSTRUCTION
AutoCAD SHX Text 60.1'
AutoCAD SHX Text 7.9'
AutoCAD SHX Text 3.5'
AutoCAD SHX Text 10.2'
AutoCAD SHX Text 3.6'
AutoCAD SHX Text
SEPTIC TANK ACCESS HOLE TOP ELEV=110.69 SE INV ELEV(4" PVC)=108.08
AutoCAD SHX Text
GTMH#1
AutoCAD SHX Text
GTMH#2
AutoCAD SHX Text SMH TOP ELEV=113.43 W INV ELEV(4" PVC)=111.46 TOP OF WATER ELEV=111.91 BOTTOM ELEV=107.7
AutoCAD SHX Text 50.2'
AutoCAD SHX Text SEPTIC TANK ACCESS HOLE TOP ELEV=111.07 TOP 4" PVC=107.85 INV ELEV (4"PVC)=107.52 BOTTOM ELEV=103.45
AutoCAD SHX Text SEPTIC TANK ACCESS HOLE TOP 4" PVC=107.61 INV ELEV (4"PVC)=107.28 BOTTOM ELEV=103.23
\\cph\pz\Jobs\S09110\Civil\DWG\_Current_Plan_Set\S09110 - PLAN AND PROFILE Altnn.dwg, 1/4/2024 8:31:19 AM, Nida, Nicholas, , 1/4/2024 8:31:19 AM, Nida, Nicholas, 1/4/2024 8:31:19 AM, Nida, Nicholas, , Nida, Nicholas, Nida, Nicholas, , WEKIVA CLUB COURT
113.347
113.569
16+00 17+00
18+00
EXISTING GRADE
SCALE: 1" = 20' HORZ
1" = 2' VERT
N
Graphic Scale in Feet
20 20 40
PLAN AND PROFILE
17+60
EX. MH
POC
EX. MH, POC
RIM ELEV=115.26
NE INV ELEV=RECESSED
SW INV ELEV(8" PVC)=111.33
CORE BORE AND CONNECT
PROP. 2" HDPE SAN FM
INV (N) 112.07
LS-1
LS-1
PER SCUEM 12
RIM 113.50
INV (NW) 102.62
INV (E) 109.14
TOP FM (S) 110.57
INV (E) 102.62
(EXTERNAL DROP)
2" HDPE
SAN FM TOP 110.50
2" HDPE SAN FM
TOP 112.26
INV 112.07
PROP. 116 LF
4" PVC SAN W/ C/O
CONNECT EXISTING
SAN SERVICES AT C/O
EXI. SEPTIC TANK AND
DRAINFIELD TO BE
ABANDONED IN PLACE.
CONTRACTOR TO PERMIT
ABANDONMENT WITH FDEP
PRIOR TO CONSTRUCTION
EX. MH POC
CORE BORE
AND CONNECT
PROP. 2" HDPE SAN FM
TOP 112.26
INV 112.07
NOTE:
1) KOR-N-SEAL COUPLING, OR SIMILAR
QUALIFICATION, AT FM CONNECTION.
2) INTERIOR OF MANHOLE TO BE COATED WITH
PPG RAVEN® 405 EPOXY. APPLICATION SHALL
BE PER MANUFACTURE GUIDELINES.
LS-1
PER SCUEM 12
RIM 113.50
INV (NW) 102.62
INV (E) 109.14
INV (E) 102.62
(INTERNAL DROP)
116 LF 4" PVC SAN @ 2.0% SLOPE
LS-1
PROP 116 LF
4" PVC SAN
@ 2% SLOPE
3' C
O
VE
R , T
YP
PROP 395 LF
6" PVC SAN
@.50% SLOPE
240 LF 2" HDPE SAN FM AND DIRECTIONAL DRILL
240 LF 2" HDPE SAN FM AND DIRECTIONAL DRILL
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com C 2024
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS.
CPH ,LLC
A Full Service A & E Firm
Plans Prepared By:
Building Better
Communities Together
C2.1WEKIVA GOLF CLUB
FORCE MAIN AND PUMP STATION
SEMINOLE COUNTY
N.NIDA
N.NIDA
J.Morton 6/2023 S09110# #
JEREMY CRAIG MORTON
PE FL 75410
AutoCAD SHX Text
CONCRETE BLOCK WALL
AutoCAD SHX Text
DECREPIT STRIPING IS DIFFICULT TO DESIGNATE
AutoCAD SHX Text
ASPHALT PAVEMENT
AutoCAD SHX Text
BROKEN ASPHALT PAVEMENT
AutoCAD SHX Text
BROKEN ASPHALT PAVEMENT
AutoCAD SHX Text
BROKEN CONCRETE PAVEMENT
AutoCAD SHX Text
DIRT/GRAVEL AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text
GRASS AREA
AutoCAD SHX Text SMH TOP ELEV=113.43 W INV ELEV(4" PVC)=111.46 TOP OF WATER ELEV=111.91 BOTTOM ELEV=107.7
AutoCAD SHX Text
FGI TOP ELEV=112.62 TOP OF WATER=112.10 TOP OF 'MUCK'=111.54 BOTTOM ELEV=109.74
AutoCAD SHX Text
SAND TRAP MATERIAL STOCKPILE AREA
AutoCAD SHX Text
4.5' HIGH BRICK WALL W/ 5'+ HIGH COLUMNS
AutoCAD SHX Text SMH TOP ELEV=114.84 NE INV ELEV(8" PVC)=110.88 SW INV ELEV(8" PVC)=111.04 S INV ELEV(8" PVC)=111.10
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
TREELINE
AutoCAD SHX Text
SPIGOT
AutoCAD SHX Text
PLANTER
AutoCAD SHX Text
SMH TOP ELEV=115.26 NE INV ELEV=RECESSED SW INV ELEV(8" PVC)=111.33
J:\S09110\Civil\DWG\_Current_Plan_Set\S09110 - PLAN AND PROFILE Altnn.dwg, 1/12/2024 11:05:13 AM, Nida, Nicholas, , 1/12/2024 11:05:13 AM, Nida, Nicholas, 1/12/2024 11:05:13 AM, Nida, Nicholas, , Nida, Nicholas, Nida, Nicholas, , SEE LIFT STATION
RISER DIAGRAM 1/C6.0
MAINTENANCE
BLDG 4080
SEE BUILDING
ENTRY DETAIL
2/C6.0
APPROX. LOCATION
OF ABANDONED
5HP PUMP3#8, 1#8G, IN 1"C.
E5.0
N
Graphic Scale in Feet
10 10 20
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298 Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
A Full Service A & E Firm
C 2023
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS.
C5.0
WEKIVA GOLF CLUB
PUMP STATION
SEMINOLE COUNTY
G. TAYLOR
E. PALMER
G. TAYLOR
11/02/2023 S09110# #
Gregory D. Taylort P.E
PE FL 77811
# # ELECTRICAL
SITE PLAN
SITE PLAN - EXPANDED VIEW
SCALE: 1" = 10'2
SITE PLAN - EXPANDED VIEW
SCALE: N.T.S.1
GR
EG
ORY D . TAYLORL I C E N S E
F L O R I D A
P R O F E S S I O N A L E N G I N E
E R No. 77811
STATE OF
APPROX. LOCATION OF LIFT STATION- SEE CIVIL
PLANS FOR EXACT LOCATION.
GOLF
SID
E C
OVE
G O
LF
C
LU
B
D R
WEKIVA CLUB CT.
WEKIVA CLUB CT.
AutoCAD SHX Text SMH TOP ELEV=113.43 W INV ELEV(4" PVC)=111.46 TOP OF WATER ELEV=111.91 BOTTOM ELEV=107.7
AutoCAD SHX Text 50.2'
AutoCAD SHX Text SMH TOP ELEV=113.43 W INV ELEV(4" PVC)=111.46 TOP OF WATER ELEV=111.91 BOTTOM ELEV=107.7
AutoCAD SHX Text 50.2'
AutoCAD SHX Text
SMH TOP ELEV=115.26 NE INV ELEV=RECESSED SW INV ELEV(8" PVC)=111.33
AutoCAD SHX Text J:\S09110\MEP\01_CAD\S09110 - C5.0 Electrical Floor Plan.dwg, 11/2/2023 5:18:27 PM, Palmer, Eric, , 11/2/2023 5:18:27 PM, Palmer, Eric, 11/2/2023 5:18:27 PM, Palmer, Eric, , Palmer, Eric, Palmer, Eric, , AutoCAD SHX Text CPH, Inc.
M
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298 Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
A Full Service A & E Firm
C 2023
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS.
C6.0
WEKIVA GOLF CLUB
PUMP STATION
SEMINOLE COUNTY
G. TAYLOR
E. PALMER
G. TAYLOR
10/02/2023 S09110# #
Gregory D. Taylor P.E
PE FL 77811
# # ELECTRICAL
DETAILS
GR
EG
ORY D . TAYLORL I C E N S E
F L O R I D A
P R O F E S S I O N A L E N G I N E
E R
No. 77811
STATE OF
NEMA 3R GENERATOR RECEPTACLE
MODEL UL 1686 SCM460 BY SUPPLIER
INSTALLED BY CONTRACTOR
APPROVED BY OWNER.
CONTROL PANEL
BY PUMP SUPPLIER
( RILEY AND CO.)
5' MIN.
6' MAX.
PROVIDE 5/8 ", 8', COPPER ROD WITH #6 WIRE. CONNECT
ALL METAL PARTS OF UNISTRUT AND BOXES AT ONE POINT
TO THE COPPER ROD.
CONCRETE AROUND POSTS 12" DIA. X 36" DEEP
OR TO MATCH WIND LOAD REQUIREMENTS
LOCAL CODE
GFI RECEPTACLE BY
CABINET SUPPLIER
GALVANIZED UNISTRUT
24' MIN.
4" RIGID ALUMINUM
POSTS
(3) SEAL-OFFS (2")
FROM MAINT. BLDG.- SEE SITE
PLAN 2/C5.0 FOR CONDUTOR
AND CONDUIT SIZE
2- (2") PVC COATED RIGID BY ELECTRICAL
CONTRACTOR TO LIFT STATION FOR PUMPS.
PROVIDE PULL WIRE FOR CABLES BY PUMP
VENDOR.
1- (2") PVC COATED RIGID BY
ELECTRICAL CONTRACTOR TO LIFT
STATION FOR FLOAT SWITCHES
WARNING LIGHT BY
PUMP SUPPLIER
(3)TRANSITIONS TO UNDERGROUND PVC
CONTRACTOR TOO COORDINATE
WITH SUPPLIER FOR KNOCKOUTS
AND CONNECTIONS OF WIRES TO LIFT
STATION BY SUPPLIER
GRADE
SEE C5.0 FOR WIRE AND CONDUIT SIZE.
NEW 30 AMP DISCONNECT,
NEMA 3R, 600V, 3P, WITH
LIGHTNING ARRESTOR
#6AWG
LIFT STATION RISER DIAGRAM
SCALE: N.T.S.1
4" PVC
6' MIN.
POWER
CABLE
1. DRAWING NOT TO SCALE.
2. ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH NEC AND LATEST LOCAL
CODES.
3. ELECTRICIAN SHALL SEAL OFF CONDUIT RUNS.
4. ELECTRICIAN TO MOUNT LIGHTNING ARRRESTOR AT DISCONNECT SWITCH.
5. CONTRACTOR SHALL VERIFY POWER SOURCE PRIOR TO ORDERING
EQUIPMENT.
6. NEUTRAL TO BE SUPPLIED FOR 230V-3 PHASE OR 230V-SINGLE PHASE
POWER.
7. REFER TO SHEET C1.0 FOR FURTHER INFORMATION ON LIFT STATION.
ELECTRICIAN NOTES:
GRADE
SLAB
LIGHTING ARRESTOR
AHEAD OF CONTROL
PANEL (GE OR EQUAL)
AUDIBLE ALARM SILENCER BUTTON
ALARM HORN (WEATHERPROOF)
MINIMUM 3 EACH 2" SCH.
80 P.V.C. CONDUITS.
4" ALUMINUM STAINLESS STEEL
OR CONCRETE PANEL
SUPPORTS WITH CAPS.
SIDE VIEWFRONT VIEW
BUILDING ENTRY DETAIL
SCALE: N.T.S.2
EXISTING
PANELBOARD
EXISTING
TO LIFT STATION
SEE 2/C5.0
EXISTING METER,
200A MAIN CB, AND
DISCONNECT SWITCH
3#10, 1#10G, 1"C.
REMOVE EXISTING CONDUTORS ON EXISTING 30A/2P CIRCUIT BREAKER IN POSITION 15 AND 16.
REMOVE CONDUCTORS TO ABANDONED 5HP PUMP - SEE 2/C5.0 FOR APPROX. LOCATION.
CONNECT LIFT STATION CIRCUIT TO CIRCUIT BREAKER AND LABEL "LIFT STATION".
KEY NOTE
AutoCAD SHX Text J:\S09110\MEP\01_CAD\S09110 - C6.0- Electrical Detail.dwg, 11/2/2023 5:27:18 PM, Palmer, Eric, , 11/2/2023 5:27:18 PM, Palmer, Eric, 11/2/2023 5:27:18 PM, Palmer, Eric, , Palmer, Eric, Palmer, Eric, , CPH, Inc.
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298 Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
A Full Service A & E Firm
C 2023
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS.
C7.0
WEKIVA GOLF CLUB
PUMP STATION
SEMINOLE COUNTY
G. TAYLOR
E. PALMER
G. TAYLOR
11/02/2023 S09110# #
Gregory D. Taylor P.E
PE FL 77811
# # ELECTRICAL
CALCULATIONS
GR
EG
ORY D . TAYLORL I C E N S E
F L O R I D A
P R O F E S S I O N A L E N G I N E
E R
No. 77811
STATE OF
AutoCAD SHX Text J:\S09110\MEP\01_CAD\S09110 - C7.0 ELECTRICAL CALCULATIONS.dwg, 11/2/2023 5:33:23 PM, Palmer, Eric, , 11/2/2023 5:33:23 PM, Palmer, Eric, 11/2/2023 5:33:23 PM, Palmer, Eric, , Palmer, Eric, Palmer, Eric, , CPH, Inc.
6-IN PVC AWWA C900-16 DR18
NOTES:
1. PIPE MARKING SHALL CONFORM TO THE REQUIREMENTS TO AWWA C900.
2. MARKING MARKING SHALL BE OF CONTRASTING COLOR AND REMAIN LEGIBLE AFTER NORMAL HANDLING, STORAGE AND
INSTALLATION.
3. THE PIPE SHALL BE INSTALLED SUCH THAT LETTERING IS ORIENTATED AT THE TOP OF THE PIPE.
4. PVC PIPE COLOR SHALL BE BLUE (WATER MAINS), GREEN (FORCE MAINS), OR PANTONE PURPLE (RECLAIMED WATER
MAINS).
PVC PIPE
DUCTILE IRON PIPE AND PVC PIPE
RECLAIMED WATER MAIN RECLAIMED WATER MAIN
3" TAPE IS CENTERED
ALONG TOP HALF OF PIPE
SERVICE USED AS EXAMPLE,
SEE NOTE 1 ABOVE (TYP)
TYPICAL PVC PIPE, SEE NOTE 4
RECLAIMED WATER MAIN RECLAIMED WATER MAIN
6" TAPE IS PLACED ALONG BOTH
SIDES OF THE TOP HALF OF PIPE
RECLAIMED WATER MAIN RECLAIMED WATER MAIN
RECLAIMED WATER MAIN RECLAIMED WATER MAIN
TAPE IS PLACED ON BOTH SIDES OF THE
TOP HALF OF THE PIPE WITH A THIRD STRIP
CENTERED ALONG THE TOP HALF OF PIPE
RECLAIMED WATER MAIN RECLAIMED WATER MAIN
RECLAIMED WATER MAIN RECLAIMED WATER MAIN
RECLAIMED WATER MAIN
RECLAIMED WATER MAIN
RECLAIMED WATER MAIN
RECLAIMED WATER MAIN RECLAIMED WATER ED WATER MAIN
SP
EC
IF
IE
D
PE
R P
IP
E
D
IA
M
ET
ER
12" MAX
1"
SERVICE SPECIFIC COLORED TAPE WITH WHITE OR OTHER CONTRASTING
PERMANENTLY IMPREGNATED LETTERING SHALL BE USED. THE TAPE
SHALL RUN FROM JOINT TO JOINT ALONG THE LENGTH OF THE PIPE.
2.5" TO 4"
DIP
6" TO 16"
DIP
18" &
GREATER
DIP
6-IN PVC AWWA C900-16 DR18
VINYL ADHESIVE TAPE (TYP)
(I.D. TAPE REQUIRED ON ALL D.I. AND PVC PIPE)
DATE:
FIGURE:
SEMINOLE COUNTY ENVIRONMENTAL SERVICES - UTILITY ENGINEERING DIVISION
PIPE IDENTIFICATION
05/18/21
NOTES:
1. Bc = PIPE O.D.
Bd = TRENCH WIDTH AT TOP OF PIPE MAX Bd = Bc + 24" MIN Bd = MAX DIM. OF BELL + 8" (UNSHEETED TRENCH)
MAX DIM. OF BELL + 12" (SHEETED TRENCH)
2. DEPTH FOR REMOVAL OF UNSUITABLE MATERIAL
SHALL BE AS REQUIRED TO REACH SUITABLE
FOUNDATION FOR NON-CUSHIONING MATERIAL, DEPTH
SHALL BE 6" BELOW BOTTOM OF UTILITY.
3. SHEETING SHALL BE DRIVEN BELOW THE UTILITY
INVERT IF REQUIRED FOR LATERAL SUPPORT OR
UNSUITABLE MATERIAL REMOVAL. WHERE DRIVEN
BELOW PIPE INVERT, SHEETING SHALL BE CUT OFF A
MINIMUM OF 12" ABOVE TOP OF PIPE, OR HIGHER AS
AUTHORIZED BY THE ENGINEER, AND LEFT IN PLACE.
IN NO CASE SHALL SHEETING LEFT IN PLACE EXTEND
HIGHER THAN 30" BELOW SURFACE GRADE UNLESS
SPECIFICALLY APPROVED. BRACING SHALL BE
APPROVED AS REQUIRED.
4. PROTECTIVE CONCRETE SLABS ARE REQUIRED
WHENEVER DEPTH OF COVER IS LESS THAN 36" AND IF
APPROVED BY THE UTILITY.
5. BACKFILL TO BE COMPACTED TO 98% DENSITY OF
AASHTO T180 MODIFIED PROCTOR IN AREAS TO BE
PAVED AND 95% IN OTHERS.
6. REF. STANDARD DETAIL
############################ FOR FULL LOCATION
MATERIAL REQUIREMENTS.
Bd (SEE NOTE 1)
Bc
TR
EN
C H
W
AL
LS
AS
V
ER
TI
C
AL
AS
P O
SS
IB
LE
VE
R
TI
C
AL
TR
EN
C
H W
AL
LS
Bd (SEE NOTE 1)
Bc
TR
EN
C H
W
AL
LS
AS
V
ER
TI
C
AL
AS
P O
SS
IB
LE
VE
R
TI
C
AL
TR
EN
C
H W
AL
LS
" M
IN
" M
IN
Bc / 2
Bc / 4
(4" MIN)
Bc / 4
(6" MIN)
Bc / 2
SEE
NOTE 2
Bc / 4
(6" MIN)
CONCRETE ARCH
ENCASEMENTCONCRETE CRADLE
0.6 Bc (TOTAL)
GRANULAR BEDDINGNORMAL TRENCH
CONCRETE
CONCRETE
PIPE BELL
SEE NOTE 6
SEE NOTE 6
COMPACTED
SELECT
MATERIAL
COMPACTED
BACK FILL
COMPACTED
BACK FILL
COMPACTED
SELECT
MATERIAL
COMPACTED GRANULAR
BEDDING MATERIAL
UNDISTURBED
SOIL
UNDISTURBED SOIL
CLASS "A" BEDDING - SPECIAL CONDITIONS
CLASS "B" BEDDING - NORMAL CONDITIONS
SPECIAL DETAIL
SHEETED TRENCH
PROTECTIVE
CONCRETE SLAB
Bd (SEE NOTE 1)
Bc
PIPE BELL
COMPACTED
BACKFILL AS
SPECIFIED FOR
BEDDING TYPE
COMPACTED GRANULAR
BEDDING MATERIAL
UNDISTURBED SOIL
TH
IS
P O
R
TI
O N
T O
B E
C U
T
AN
D R
EM
O
VE
D
BRACING
SHEETING12
" M
IN
SEE NOTE 6
12"
MIN6" MIN
AS REQ.
COMPACTED BACK
FILL OR OTHER FINISH
CONC SLAB,
SCREENED FINISH
6X6-6/6 W.W.F.
DATE:
FIGURE:
SEMINOLE COUNTY ENVIRONMENTAL SERVICES - UTILITY ENGINEERING DIVISION
TRENCHING AND BEDDING
05/18/21
HORIZONTAL SEPARATION CROSSING [1] JOINT SPACING [2]
STORM SEWER,
STORMWATER FORCE MAIN,
RECLAIMED WATER [3]
VACUUM SANITARY SEWER
GRAVITY SANITARY SEWER,
PRESSURE SANITARY
SEWER,SANITARY SEWER
FORCE MAIN, RECLAIMED
WATER [4]
WATER MAIN
OTHER MAIN
OTHER MAIN
OTHER MAIN
WATER MAIN
O
TH
ER
AI
N
ON-SITE SEWAGE
TREATMENT & DISPOSAL
SYSTEM
WATER MAIN
OTHER MAIN OTHER MAIN
WATER MAIN
OTHER MAIN OTHER MAIN
10' MIN. --- ---
CENTER ONE FULL
LENGTH OF PIPE
WATER MAIN
CENTER ONE FULL
LENGTH OF PIPE
WATER MAIN
CENTER ONE FULL
LENGTH OF PIPE
ALTERNATIVELY
3' MIN.
WATER
MAIN
WATER
MAIN
WATER
MAIN
O
N O
N
' P
R
EF
ER
R
ED
3'
M
IN
3' M
IN
' P R
EF
ER
R
ED
6' M
IN
[6
ALTERNATIVELY
3' MIN.
ALTERNATIVELY
6' MIN.
" M
IN
. [5
" P R
EF
ER
R
ED
6" M
IN
" M
IN
. [7
NOTES:
1. WATER MAIN SHOULD CROSS ABOVE ANY OTHER PIPE. WHEN WATER MAIN MUST BE BELOW ANOTHER PIPE, THE MINIMUM SEPARATION BETWEEN OUTSIDE OF
WATER MAIN AND OUTSIDE OF OTHER PIPE IS 12".
2. AT ALL UTILITY CROSSINGS ONE FULL LENGTH OF WATER MAIN PIPE SHALL BE CENTERED ABOVE OR BELOW THE OTHER PIPELINE SO THE WATER MAIN JOINTS
WILL BE AS FAR AS POSSIBLE FROM THE OTHER PIPELINE. SEE ALTERNATIVE ARRANGEMENTS.
3. RECLAIMED WATER REGULATED UNDER PART III OF CHAPTER 62-610 F.A.C.
4. RECLAIMED WATER NOT REGULATED UNDER PART III OF CHAPTER 62-610 F.A.C.
5. FOR STORM SEWER: 12" PREFERRED, 6" MIN
6. FOR GRAVITY SANITARY SEWER WHERE THE BOTTOM OF THE WATER MAIN IS LAID AT LEAST 6" ABOVE THE TOP OF THE GRAVITY SANITARY SEWER MAIN
HORIZONTAL SEPARATION SHALL BE 3' MIN.
7. FOR GRAVITY SANITARY SEWER: 12" PREFERRED, 6" MIN.
8. NO WATER PIPE SHALL PASS THROUGH OR BE CONSTRUCTED TOUCHING ANY PART OF A SANITARY OR STORM WATER MANHOLE OR STRUCTURE.
9. PROP. OR RELOCATED FIRE HYDRANTS WITH UNDERGROUND DRAINS MUST BE AT LEAST 10 FEET FROM ANY EXISTING OR PROP. "ON-SITE SEWAGE TREATMENT
AND DISPOSAL SYSTEM" AS DEFINED IN SECTION 381.0065 (2), F.S., AND RULE 64E-6.002, F.A.C.
10. WHERE IT IS NOT POSSIBLE TO MEET THE SEPARATION REQUIREMENTS, THE FOLLOWING ALTERNATIVE CONSTRUCTION VARIANCES ARE ACCEPTABLE ONLY WITH
THE EXPRESSED WRITTEN CONSENT OF THE UTILITIES ENGINEERING DIVISION:
10.1. WHERE A WATER MAIN IS BEING LAID LESS THAN THE REQUIRED MINIMUM HORIZONTAL DISTANCE AND/OR WHERE A WATER MAIN CROSSING HAS LESS THAN
THE MINIMUM REQUIRED DISTANCE BETWEEN JOINTS:
10.1.1. USE OF PRESSURE RATED PIPE CONFORMING TO AWWA STANDARDS, FOR A GRAVITY OR VACUUM TYPE PIPE LINE.
10.1.2. USE OF WELDED, FUSED OR OTHERWISE RESTRAINED JOINTS FOR EITHER PIPE.
10.1.3. USE OF WATERTIGHT CASING PIPE OR CONCRETE ENCASEMENT AT LEAST 6" PREFERRED, 4" MIN. THICK FOR EITHER PIPE. REFERENCE DETAIL ###.
10.2. WHERE A WATER MAIN IS BEING LAID LESS THAN 3 FEET HORIZONTALLY FROM ANOTHER PIPE LINE AND/OR WHERE A WATER MAIN IS BEING LAID WITH LESS
THAN THE REQUIRED MINIMUM VERTICAL SEPARATION:
10.2.1. USE OF PIPE OR CASING PIPE, HAVING HIGH IMPACT STRENGTH (AT LEAST EQUAL TO 0.25" THICK D.I.P.), OR CONCRETE ENCASEMENT AT 6" PREFERRED, 4" MIN. THICK FOR THE WATER MAIN AND THE OTHER PIPE LINE IF THE OTHER PIPE LINE CONVEYS WASTEWATER OR RECLAIMED WATER. REFERENCE
DETAIL ###.
11. FOR PIPE CROSSING CONFLICTS REFERENCE DETAIL ###. CONFLICTS SHALL NOT BE RESOLVED BY DEFLECTING PIPE JOINTS.
12. THIS DETAIL IS PROVIDED FOR CONVENIENCE. REFERENCE FAC 62-555.314 FOR FULL REQUIREMENTS.
DATE:
FIGURE:
SEMINOLE COUNTY ENVIRONMENTAL SERVICES - UTILITY ENGINEERING DIVISION
FAC 62-555.314 SEPARATION REQUIREMENTS
05/18/21
NOTES:
1. REFERENCE DETAIL ### FOR SEPARATION REQUIREMENTS.
2. ALL FITTINGS AND JOINTS TO BE RESTRAINED MECHANICAL JOINT.
3. DEFLECTION OF PIPE JOINTS TO AVOID CROSSING CONFLICT IS NOT PERMITTED.
10' MIN. 10' MIN.
NO JOINTS BETWEEN FITTINGS
22-1/2° BENDS (PREFERRED)
OR 45° BENDS, RESTRAINED
MECHANICAL JOINTS (TYP)
" M
IN
C
O
VE
R
CONFLICT PIPE
SE
E
N O
TE
DATE:
FIGURE:
SEMINOLE COUNTY ENVIRONMENTAL SERVICES - UTILITY ENGINEERING DIVISION
PIPE CROSSING CONFLICT
05/18/21
NOTES:
1. REF. UTILITY ENGINEERING MANUAL, FOR REQUIRED COLORS AND TEXT FOR ALL LOCATE MATERIALS.
2. LOCATING WIRE SHALL BE CONTINUOUS, COLOR CODED, INSULATED, 10 GAUGE SOLID CORE COPPER, AND SUITABLE FOR
DETECTION WITH LOCATION EQUIPMENT.
3. LOCATING WIRE SHALL BE BURIED DIRECTLY ABOVE THE CENTERLINE OF THE PIPE, AFFIXED TO THE PIPE WITH TAPE OR
TIE WRAPS.
4. LOCATING WIRE SHALL TERMINATE PER DETAILS ### AND/OR ###.
5. LOCATING WIRE IS NOT REQUIRED FOR GRAVITY SEWER
6. LOCATE TAPE SHALL BE MINIMUM WIDTH OF 4" FOR PIPES UP TO 12" IN DIAMETER, 6" FOR PIPES 14" AND GREATER, PLASTIC
AND METALIZED FOIL, COLOR CODED WITH TEXT APPROPRIATE FOR SERVICE, AND SUITABLE FOR DETECTION WITH
LOCATION EQUIPMENT.
7. LOCATING TAPE SHALL BE BURIED 12 INCHES DIRECTLY ABOVE THE CENTERLINE OF THE PIPE, WITH PRINTED SIDE UP FOR
VISUAL IDENTIFICATION.
8. MARKER BALLS SHALL BE 4 INCHES IN DIAMETER, COLOR CODED, AND A PASSIVE DEVICE CAPABLE OF REFLECTING A
SPECIFICALLY DESIGNATED REPULSE FREQUENCY TUNED TO THE UTILITY BEING USED.
9. MARKER BALLS SHALL BE BURIED DIRECTLY ABOVE THE CENTERLINE OF THE PIPE, UNLESS MARKER BALL DEPTH IS GREATER THAN 6' BELOW FINISHED GRADE, IN WHICH CASE THE MARKER BALL SHALL BE SET AT 18" TO 24" BELOW FINISHED GRADE. SPACING SHALL BE EVERY 100 LINEAR FEET AND AT EVERY BEND, TEE, REDUCER AND VALVE. MARKER
BALLS SHALL BE INDICATED ON RECORD DRAWINGS AS "E.M.B."
#10 COLOR CODED
COPPER WIRE
(CONTINUOUS)
WATER, RECLAIM,
OR FORCE MAIN1"
M
AX
#10 COLOR CODED
COPPER WIRE
(CONTINUOUS)
WATER, RECLAIM,
OR FORCE MAIN
LOCATING TAPE
LOCATING TAPE
COLOR CODED
MARKER BALL,
SEE NOTE 9
FINISHED GRADE
FINISHED GRADE
"1" M
AX
LOCATING WIRE
TO BE AFFIXED TO
PIPE WITH TAPE
OR TIE WRAPS
SECTION VIEW
PROFILE VIEW
UNDISTURBED SOILS
COLOR CODED MARKER BALL,
SEE NOTE 9
DATE:
FIGURE:
SEMINOLE COUNTY ENVIRONMENTAL SERVICES - UTILITY ENGINEERING DIVISION
PIPE MATERIAL LOCATION
05/18/21
A
SE
C
TI
O
N A
-A
PL
AN
EV
ER
Y 5'
F T
SA
W
C U
T
JO
IN
TS
SI
D
EW
AL
K C
O N
C R
ET
E
N O
TE
S:
5' 5'
A
5' S
ID
EW
AL
K
2% M
AX
C O
M
PA
C
TE
D B
AS
E
4" T
H
IC
K C
O N
C R
ET
E
(3
PS
I)
1.
S
AW
C
U T
0.
-IN
C H
J O
IN
TS
E
VE
R Y
5-
FT
O N
C
EN
TE
R
(1 .5
0-
IN
C H
D
EE
P)
SA
W
C U
T W
IT
H
IN
H
O U
R S.
2.
S
AW
C
U T
0.
-IN
C
H J
O
IN
TS
E
VE
R
Y
-F T
O N
C
EN
TE
R
(1 .5
0-
IN
C H
D
EE
P)
SA
W
C U
T W
IT
H
IN
H
O U
R S.
3.
F
O R
M
.5 0-
IN
C
H E
XP
AN
SI
O
N J
O
IN
T
EV
ER
Y
0-
FT
M
AX
IM
U M
S
PA
C
IN
G A
LO
N
G S
ID
EW
AL
K
AN
D
B
ET
W
EE
N T
H E
SI
D
EW
AL
K
AN
D T
H E
C U
R B
O R
D R
IV
EW
AY
O
R A
T
FI
XE
D
O
BJ
EC
TS
A N
D S
ID
EW
AL
K
IN
TE
R
SE
C
TI
O N
S W
IT
H
A P
R
EF
O R
M
ED
JO
IN
T
FI
LL
ER
M
EE
TI
N
G T
H E
R
EQ
U
IR
EM
EN
TS
O
F
FD
O T
SP
EC
IF
IC
AT
IO
N
4.
C
M
PA
C
T
FI
LL
A
R
EA
S, IN
C
LU
D
IN
G C
U T
AR
EA
S U
N D
ER
T
H E
SI
D
EW
AL
K
TH
AT
H
AV
E
BE
EN
E
XC
AV
AT
ED
M
O R
E
TH
AN
IN
C
H
ES
B
EL
O W
T H
E
BO
TT
O
M O
F
SI
D
EW
AL
K, T O
A M
IN
IM
U M
O F
O F
AA
SH
TO
T
D
EN
SI
TY
. T
H E
AR
EA
T O
B E
C O
M
PA
C
TE
D
IS
D
EF
IN
ED
A S
TH
AT
A R
EA
D
IR
EC
TL
Y
U N
D
ER
T H
E
SI
D
EW
AL
K
AN
D
F
O O
T
BE
YO
N
D E
AC
H
S
ID
E O
F
TH
E
SI
D
EW
AL
K.
5.
C
N
C R
ET
E
SI
D
EW
AL
K
TO
B E
6-
IN
T H
IC
K
AC
R
O
SS
A
LL
D R
IV
EW
AY
S
ST
AN
D
AR
D C
O N
C R
ET
E
SI
D
EW
AL
K N
.T .S
GRAVITY SEWER
PRE-CAST MANHOLE
BASE WALL
GRAVITY SEWER
(SEE NOTE 4)
6"
6"
2"
FULL CONCRETE
ENCASEMENT OF
VERTICAL PIPE
PVC PLUG
W/ TOP HALF
AREA OPEN
TYPICAL INSTALLATION
OUTSIDE DROP INSTALLATION
NOTES:
1. ALL MATERIALS SHALL BE NON CORROSIVE.
2. INSIDE DROP CONNECTION SHALL NOT BE PERMITTED ON NEW MANHOLES.
3. DROP CONNECTION SHALL BE REQUIRED WHENEVER THE INVERT OF AN INFLUENT SEWER IS LOCATED TWO (2) OR
MORE FEET ABOVE THE INVERT OF THE MAIN FLOW CHANNEL.
4. DROP PIPE SHALL BE OF EQUAL SIZE AS THE INFLUENT SEWER. DROP PIPE SHALL BE PVC. IF A TRANSITION TO OTHER
TYPE OF PIPE IS REQUIRED, THE TRANSITION SHALL BE OUTSIDE OF DROP.
5. RESILIENT "BOOT" TYPE CONNECTORS PERMISSIBLE ON GRAVITY SEWER INVERTS LESS THAN 12" DIAMETER AND LESS
THAN 15' BELOW FINISHED GRADE. DEEPER OR LARGER INVERTS SHALL UTILIZE CAST IN PLACE SEALS.
PRE-CAST
MANHOLE WALL
PVC TEE
PVC 90° BEND
MANHOLE TO GRAVITY SEWER
SEAL (TYP), SEE NOTE 5
MANHOLE TO GRAVITY
SEWER SEAL (TYP),
SEE NOTE 5
DATE:
FIGURE:
SEMINOLE COUNTY ENVIRONMENTAL SERVICES - UTILITY ENGINEERING DIVISION
NEW MANHOLE CONNECTION
05/18/21
NOTES:
1. MILL AND RESURFACING REQUIREMENTS PER SEMINOLE COUNTY PUBLIC WORKS REQUIREMENTS OR WHICH EVER
GOVERNING MUNICIPALITY.
2. BACKFILL SHALL BE PLACED IN 6" LAYERS FROM BENEATH THE HAUNCHES OF THE PIPE TO THE BASE AND COMPACTED TO
98% DENSITY PER AASHTO T-180 MODIFIED PROCTER.
3. BASE MATERIALS SHALL BE PLACED IN TWO OR THREE LAYERS ROLLED AND TAMPED TO ABOVE SPECIFIED DENSITY.
4. PARTIAL LANE REPLACEMENT SHALL HAVE FULL LANE WIDTH MILLED AND RESURFACED.
5. REF. DETAIL 104 FOR PIPE RESTRAINT REQUIREMENTS.
12" VARIES 12"
TRENCH WIDTH (W) 1.5'1.5'
TRENCH WIDTH (W) + 4'
SURFACE REPLACEMENT
2T
" M
IN
3' M
IN
MILL AND RESURFACE (SEE NOTE 1)
REPLAC…
This is the start of the file's text. The full file is on GovTribe.