Plans_Approved_1512B.pdf
PDF 45 MB Posted
- Solicitation number
- 0000040277
About this file
This is a set of approved construction plans for a state and local contract opportunity involving the California Department of General Services (DGS) and the California Department of Forestry and Fire Protection (Cal Fire). The project consists of the phased demolition and reconstruction of a Cal Fire remote radio communication site located at Bunchgrass/Hatchet Mountain (Phase V), identified as DGS Project 00000000001512B and OSFM Project No. 22-N-5731. The work involves removal of existing facilities, site preparation and improvements, and installation of a new communication tower and vault to be performed under a single general contractor in phases to allow for continuous operation of communications. The project is approximately 733 square feet and classified as Group U occupancy, Type II-B noncombustible construction. Key structural work includes a medium vault building measuring 22'-8" by 30'-8", a new lattice or monopole communication tower with foundation, propane tank installation, retaining walls, fencing with barbed wire, and a feedline bridge connecting the vault to the tower. The project site is located at latitude N 040 52' 29.30" and longitude W 121 46' 19.43" in Shasta County, California.
The construction plans were prepared by GHD, Inc. with structural design by NV5 and Western Utility/Telecom Inc. providing tower design services. The project is governed by multiple California Building Code sections and standards including Title 24 CCR, 2019 California Building Code, California Electrical Code, California Mechanical Code, and California Fire Code. Design criteria include bearing pressures of 3000 PSF for dead load on tower foundations and 2000 PSF for vault foundations, with allowable bearing of 4500 PSF and 3000 PSF respectively when combined with live loads. Wind loading design is based on an ultimate wind velocity of 106 MPH with ice thickness of 1.3 inches; snow loading uses ground snow load of 160 PSF per RWDI report. Seismic design category is D with spectral response coefficients appropriate to Site Class C. The plans underwent Division of the State Architect (DSA) review and received approval on February 25, 2026, with issue date of August 24, 2026. The project includes 85 total sheets covering architectural, structural, mechanical, electrical, and civil details with comprehensive erosion and sediment control measures and coordination requirements for utility providers.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
BG-G001
AS SHOWN
PROJECT
AREA
PROJECT
AREA
N
AREA MAP LOCATION MAP
N
PROJECT
AREA
PROJECT
AREA
SCOPE OF PROJECT
PROJECT CODE INFORMATION
STATEMENT
THIS PROJECT CONSISTS OF THE PHASED DEMOLITION AND
RECONSTRUCTION OF A CALIFORNIA DEPARTMENT OF
FORESTRY REMOTE RADIO SITE. TYPICAL WORK INCLUDES
REMOVAL OF EXISTING FACILITIES, SITE PREPARATION AND
IMPROVEMENTS, AND INSTALLATION OF NEW TOWER AND VAULT.
THE WORK WILL BE PERFORMED UNDER A SINGLE GENERAL
CONTRACTOR IN PHASES TO ALLOW FOR THE CONTINUOUS
OPERATION OF COMMUNICATIONS.
PROJECT MAPS
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS/HATCHET MTN - PHASE V
DGS PROJECT 00000000001512B
GHD PROJECT 11136839
OSFM PROJECT NO. 22-N-5731
PROJECT TEAM
DEPARTMENT OF GENERAL SERVICES
THIS PACKAGE CONTAINS SITE SPECIFIC DRAWINGS.
Aubree French, Project Director
(916)375-4230
GHD, INC.
Andrew Landeros, Mechanical Engineer
(707)921-7648
Chris Richards, Electrical Engineer
(707)540-9619
Sheet of
This document shall not be used for construction unless signed and sealed for construction.
DesignerDrawn
Scale
Date
Drafting Check
Design Check
Project Manager
Reuse of Documents
This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2025 GHD
0 1"
Bar is one inch on original size sheet
Original Size
Arch D
Project No.
Sheet No.
IssueNo. Drawn Approved Date
Title
Client
Project
Plot Date: Filename:25 November 2025 - 11:21 AM N:\US\Cameron Park\Projects\111\11136839\06-CAD\Bunchgrass\Sheets\0001 BGG001 Cover Sheet.dwgPlotted By: Becca Keating
M. WEBER 10/22/2024
11136839
GHD Inc.
943 Reserve Drive Roseville California 95678 USA T 1 916 782 8688 W www.ghd.com
STATE OF CALIFORNIA
DEPARTMENT OF GENERAL SERVICES
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS / HATCHET MTN - PHASE V
REV V3
REVIEWER:
REVIEWER SIGNATURE:
DATE REVIEWER:
PSC OPERATIONS PLAN REVIEW
NO EXCEPTIONS TAKEN
J E S
S
IC
A E. NA
P
IE
R
No. S5476
Exp. 6/30/26
DSA REVIEW
· GEOTECHNICAL AND GEOHAZARD STUDIES
· DESIGN CRITERIA
· SITE IMPROVEMENTS
· COMMUNICATION TOWER INCLUDING CABLE BRIDGE AND FOUNDATIONS
STATEMENT OF GENERAL CONFORMANCE
DEFERRED SUBMITTAL
· NONE
PROJECT LOCATION
LAT N 040° 52' 29.30"
LONG W 121° 46' 19.43"
1. APPLICABLE CODES AND STANDARDS
TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
TITLE 24 CCR, PART 1 - 2022 BUILDING STANDARDS ADMINISTRATIVE CODE
TITLE 24 CCR, PART 2 - CALIFORNIA BUILDING CODE, VOL 1 & 2 (CBC)
TITLE 24 CCR, PART 3 - CALIFORNIA ELECTRICAL CODE (CEC)
TITLE 24 CCR, PART 4 - 2019 CALIFORNIA MECHANICAL CODE (CMC)
TITLE 24 CCR, PART 5 - 2019 CALIFORNIA PLUMBING CODE (CPC)
TITLE 24 CCR, PART 6 - 2019 CALIFORNIA ENERGY CODE
TITLE 24 CCR, PART 9 - 2019 CALIFORNIA FIRE CODE (CFC)
TITLE 24 CCR, PART 11 - 2019 CALIFORNIA GREEN BUILDING STDS CODE
TITLE 24 CCR, PART 12 - 2019 CALIFORNIA REFERENCED STANDARDS
2016 NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER
2. BASIC SIGNAGE REQUIREMENTS FOR FIRE AND LIFE SAFETY
BUILDING ADDRESS AND STREET SIGNAGE, PER CFC 505.1 & 2
BATTERY/EQUIPMENT ROOMS: SIGNAGE PER CFC 604.3.1
ELECTRICAL ROOMS: SIGNAGE PER 604.3.1
NO SMOKING SIGNAGE FOR LPG
PORTABLE FIRE EXTINGUISHERS, PER CFC 906 AND TITLE 19
NFPA 704 SIGNAGE
3. UTILITY REQUIREMENTS / COORDINATION
UNDERGROUND AND OVERHEAD UTILITY SERVICES SHALL MEET THE
REQUIREMENTS OF THE UTILITY PROVIDER. COMPLY WITH UTILITY PROVIDER
STANDARD DETAILS AND SPECIFICATIONS FOR JOINT TRENCH, TRANSITIONS
AND TERMINATIONS AND ABOVE GROUND REQUIREMENTS
NV5
Chuck Kull, Geotechnical Engineer
(530)478-1305
Matt Weber, Project Director
(916)296-3222
Jessica Napier, Structural Engineer
(805)858-3474
Matt Weber, Civil Engineer
(916)296-3222
Scott Groff, Project Manager, Tower Design
(971)345-2041
WESTERN UTILITY/ TELECOM INC.
FOR ARCHITECTS/ENGINEERS WHO UTILIZE PLANS,
INCLUDING BUT NOT LIMITED TO SHOP DRAWINGS, PREPARED BY OTHER LICENSED
DESIGN PROFESSIONALS AND/OR CONSULTANTS
(Application No. _______________________ File No. _______________ )
The drawings or sheets listed on the cover or index sheet This drawing, page of specifications/calculations
Have been prepared by other design professionals or consultants who are licensed and/or authorized to prepare such drawings in this state. it has been examined by me for:
1) Design intent and appears to meet the appropriate requirements of Title 24, California Code of Regulations And the project specifications prepared by me, and
2) Coordination with my plans and specifications and is acceptable for incorporation into the construction of this project.
The statement of general Conformance "shall not be construed as relieving me of my rights, duties, and responsibilities under sections 17302 and 81138 of the education code and Sections 4-336, 4-341 and 4-344" of Title 24, Part 1. (Title 24, Part 1, Section 4-317 [b])
I find that: All drawings or sheets listed on the cover or index sheet This drawing or page is/are in general conformance with the project design intent, and has/have been coordinated with the project plans and specifications.
Signature Date
Architect or Engineer designated to be in general responsible charge
Print Name
License Number Expiration Date
02-120755 34-RESD
11/23/25
Jessica E. Napier
6/30/26S5476
BUILDING ANALYSIS
A. OCCUPANCY CLASSIFICATION AND USE
B. BUILDING CONSTRUCTION TYPE
C. NUMBER OF STORIES
D. ACTUAL BUILDING HEIGHT
E. BUILDING AREA IN SQUARE FEET
F. AREA OF THE PROJECT IN SQUARE FEET (I.E., TENANT IMPROVEMENTS)
G. SEPARATE OR NON-SEPARATED USE
H. ALLOWABLE AREA PER C.B.C.
I. AREA INCREASE
J. HEIGHT INCREASE
K. INCREASE
L. FIRE SPRINKLERS (YES OR NO) TYPE: WET, DRY, PREACTION, OR DELUGE
M. FIRE ALARM: (YES OR NO) TYPE: (MANUAL, AUTOMATIC, ETC)
N. SMOKE CONTROL SYSTEM (YES OR NO)
O. OCCUPANT LOAD FOR THE ENTIRE BUILDING AND EACH FLOOR
P. THE YEAR BUILDING WAS CONSTRUCTED
Q. IS THE BUILDING IN A HIGH FIRE SEVERITY ZONE (YES OR NO)
R. SEISMIC JOINTS (YES OR NO). IF YES, PROVIDE LOCATION.
S. EMERGENCY RESPONDER RADIO COVERAGE (YES OR NO)
GROUP U OCCUPANCY
TYPE II-B - NONCOMBUSTIBLE/ NONRATED
11'-4" N/A
SEPARATE
8,500
NO
NO
NO
NO
NO
NO
UNOCCUPIED - GROUP U OCCUPANCY
NEW CONSTRUCTION
YES
NO
YES, RADIO ANTENNA FOR OSFM
CHANGES TO THE APPROVED DRAWINGS AND SPECIFICATIONS SHALL BE
MADE BY AN ADDENDUM OR A CONSTRUCTION CHANGE DOCUMENT (CCD)
APPROVED BY THE DIVISION OF THE STATE ARCHITECT (DSA), AS REQUIRED
BY SECTION 4-338, PART 1, TITLE 24, CCR.
SUBSTITUTIONS AFFECTING DSA-REGULATED ITEMS SHALL BE CONSIDERED
AS CONSTRUCTION CHANGE DOCUMENTS (CCD'S) AND SHALL BE APPROVED
BY DSA PRIOR TO FABRICATION AND INSTALLATION PER DSA IR A-6 AND
SECTION 338(C) PART 1, TITLE 24 CCR.
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/12/26
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
22-5731
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
02-120755
✔ FLS ACS
02/25/2026
11-20-2025
ISSUE DATE: AUGUST 24, 2026
http://www.ghd.com/
+0
20+00 20+80
0+
+8
30+00 30+55
TRUE NORTH
LEG 1
LEG 2LEG 3
LEG 4
90°0'0"
0°
0' 0"
270°0'0'"
0° 0' 0"
0°
0' 0"
TRUE NORTH
LEG 1
LEG 2LEG 3
LEG 4
90°0'0"
0°
0' 0"
270°0'0'"
0° 0' 0"
0°
0' 0"
DRAWING INDEX,
DESIGN CRITERIA
AND SITE ORIENTATION
BG-G002
AS SHOWN
FOUNDATION DESIGN CRITERIA: (INCLUDES TOWER AND VAULTS)
FOUNDATION DESIGN IS BASED ON CRITERIA AND RECOMMENDATIONS IN THE
REPORT TITLED GEOTECHNICAL INVESTIGATION REPORT #11136839.30 BY
GHD, INC. DATED JULY 2019 AND THE CODE UPDATE MEMORANDUM
DATED DECEMBER 7, 2022.
1. BEARING PRESSURE:
BASED ON FOOTINGS BEARING ON FIRM NATIVE SOILS ENGINEERED
FILLS.
DEAD LOAD = 3000 PSF (TOWER)
= 2000 PSF (VAULT)
DEAD AND LIVE LOAD
COMBINED = 4500 PSF (TOWER)
= 3000 PSF (VAULT)
ALLOWABLE BEARING CAN BE INCREASED BY 1/3 FOR WIND &
SEISMIC LOADS IN BASIC LOAD CASES OF CBC 1605A.3.2.
2. LATERAL RESISTANCE:
ALLOWABLE PASSIVE RESISTANCE AT FOOTING SHALL BE 400 PCF
EQUIVALENT FLUID PRESSURE. COEFFICIENT OF FRICTION SHALL BE 0.4.
FRICTION AND PASSIVE RESISTANCE MAY BE COMBINED PROVIDED THE
UPPER FOOT OF PASSIVE PRESSURE IS IGNORED AND STRUCTURE IS
POURED AGAINST NEATLY EXCAVATED FORMS.
3. ALL FOOTINGS SHALL BEAR THE MINIMUM DEPTH BELOW THE LOWEST
ADJACENT GRADE SPECIFIED IN THE GEOTECHNICAL REPORT, BUT NOT
LESS THAN 36".
4. SOIL SUBGRADE MODULUS: = 200 PCI
5. RETAINING WALL LATERAL PRESSURES:
PACTIVE (DRAINED) = 32 PCF
(UNDRAINED) = 80 PCF
PREST (DRAINED) = 52 PCF
(UNDRAINED) = 88 PCF
SNOW LOAD:
GROUND SNOW LOAD PG = 70 PSF PER SHASTA COUNTY
PG = 160 PSF PER RWDI ICING AND SNOW LOADING
REPORT DATED JANUARY 25, 2021
FLAT ROOF SNOW LOAD (VAULT ONLY) PF = 63.5 PSF (SHASTA)
PF = 145.2 PSF (RWDI REPORT, GOVERNS DESIGN)
SNOW EXPOSURE FACTOR CE = 0.9 (VAULT)
CE = 0.7 (TOWER)
SNOW LOAD IMPORTANCE FACTOR IS = 1.2
THERMAL FACTOR CT = 1.2
ICE LOADING:
ICE THICKNESS = 1.3 INCHES PER RWDI ICING AND SNOW LOADING
REPORT DATED OCTOBER 30, 2022
WIND LOADING W/ ICE = 40 MPH
ICE THICKNESS IMPORTANCE FACTOR II = 1.25
WIND IMPORTANCE FACTOR IW = 1.0
WIND DESIGN DATA:
ULTIMATE WIND VELOCITY Vult = 106 MPH SERVICE WIND VELOCITY Vasd = 82 MPH
RISK CATEGORY = IV
WIND EXPOSURE = C
Kzt = 1.98 @ 10' AGL
= 1.86 @ 140' AGL
EARTHQUAKE DESIGN DATA:
SEISMIC IMPORTANCE FACTOR IE = 1.5
OCCUPANCY CATEGORY = IV (PER TABLE 1604.5)
SITE CLASS = C
SPECTRAL RESPONSE SS = 0.847g COEFFICIENTS S1 = 0.331g SPECTRAL RESPONSE SDS = 0.677g COEFFICIENTS SD1 = 0.331g
SEISMIC DESIGN CATEGORY = D
Fa = 1.2 Fv = 1.5
RESPONSE MODIFICATION
FACTOR R = 5.0 SPECIAL REINFORCED MASONRY SHEAR WALLS (VAULT)
R = 3.0 LATTICE SELF-SUPPORTING STRUCTURES (TOWER)
ANALYSIS PROCEDURE USED = EQUIVALENT LATERAL FORCE PROCEDURE (VAULT), SEE WESTERN
TOWER DESIGN FOR TOWER ANALYSIS
DESIGN BASE SHEAR V = 0.203W (VAULT ONLY) = 20.28k
SEE WESTERN TOWER DESIGN DRAWINGS FOR TOWER DESIGN BASE SHEAR
DESIGN CRITERIA
TOWER ORIENTATION PLAN
NTS
SITE ORIENTATION PLAN
NTS
13.99°
0° 6' 44.9"
T R U E N
O R T H
G R
ID
N O R T H
N O A A M
O D E L W
M M (2
4-
D A T A Q
U E R
IE
D O
C T 4, N
(D A
TA
IS
0.
C H A N G
IN
G B
Y .1 1°
W P
E R Y
E A R
NOTES:
1. THE DIFFERENCE BETWEEN GRID NORTH AND TRUE NORTH IS EXAGGERATED ABOVE
FOR DEPICTION PURPOSES.
2. GRID NORTH IS BASED ON THE CALIFORNIA STATE PLANE COORDINATE SYSTEM, ZONE 1
(NAD83) AND THE BEARINGS SHOWN IN THE TOPOGRAPHIC SURVEY AND GRADING
PLANS ARE ON GRID NORTH.
PROPOSED
TOWER LOCATION
PROPOSED VAULT
LOCATION
T-1COVER SHEET & DRAWING INDEX
S-1ELEVATION VIEW / NOTES
S-2UPPER POLE
S-3LOWER POLE
S-4TOWER SECTION 13V - NESTED POLE
S-5TOWER SECTION 13V
S-6TOWER SECTION 15ST
S-7TOWER SECTION 17ST
S-8TOWER SECTION 19ST
S-9TYPICAL GRATING / BRACING
S-10TYPICAL HAND RAIL / DIAGNOL PIPE LIGHTNING ROD
EXTENSION, & SAFETY CLIMB KITS
S-11CENTER MAST
COAX CAGE / CLIMBING LADDER, ANTI-CLIMB, & BUS BAR
S-13ANTENNA LOCATION ELEVATION VIEWS
S-14FULLY LOADED FACE MOUNTED MICROWAVES
S-15
S-15.1
MW ICE BRIDGE DETAILS
S-16MICROWAVE MOUNT KITS
S-17
S-18LEG/ELEVATION ID PLATES
WESTERN UTILITY TELECOM, INC. DRAWING INDEX
S-1.1SST SECTION ALLOWABLE MEMBER FORCES
S-1.2MONOPOLE SECTION ALLOWABLE MEMBER FORCES
S-6.1TOWER SECTION 15ST CONT.
S-7.1TOWER SECTION 17ST CONT.
MW ANTENNA ICE SHIELD DETAILS
UHF/VHF MOUNT KITS
S-19TOWER FOUNDATION SLAB / PIERS
Sheet of
This document shall not be used for construction unless signed and sealed for construction.
DesignerDrawn
Scale
Date
Drafting Check
Design Check
Project Manager
Reuse of Documents
This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2025 GHD
0 1"
Bar is one inch on original size sheet
Original Size
Arch D
Project No.
Sheet No.
IssueNo. Drawn Approved Date
Title
Client
Project
Plot Date: Filename:25 November 2025 - 11:22 AM N:\US\Cameron Park\Projects\111\11136839\06-CAD\Bunchgrass\Sheets\0002 BGG002 Dwg Index Dsgn Criteria.dwgPlotted By: Becca Keating
M.WEBER 10/22/2024
11136839
GHD Inc.
943 Reserve Drive Roseville California 95678 USA T 1 916 782 8688 W www.ghd.com
STATE OF CALIFORNIA
DEPARTMENT OF GENERAL SERVICES
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS / HATCHET MTN - PHASE V
REV V3
REVIEWER:
REVIEWER SIGNATURE:
DATE REVIEWER:
PSC OPERATIONS PLAN REVIEW
NO EXCEPTIONS TAKEN
J E S
S
IC
A E. NA
P
IE
R
No. S5476
Exp. 6/30/26
CO-TA1
CO-TA1.1
CO-TA2
CO-TA3
CO-TA4
CO-TA5
CO-TA5.1
CO-TA5.2
CO-TA5.3
CO-TA6
CO-TA6.1
CO-TA6.2
CO-TA6.3
CO-TA6.4
CO-TA6.5
CO-TA6.6
CO-TA6.7
CO-TA6.8
CO-TA7
CO-TA7.2
COVER SHEET AND INDEX
DSA 103
TOWER STRUCTURAL NOTES
SITE PRO BRACKET DETAILS
TOWER ANTENNA MOUNTING DETAILS (ANDREW)
TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL/ANDREW)
TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL)
TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL)
TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL)
TOWER ANTENNA MOUNTING DETAILS (ANDREW/COMMSCOPE)
TOWER ANTENNA MOUNTING DETAILS (ANDREW/COMMSCOPE)
TOWER ANTENNA MOUNTING DETAILS (PRODELIN/GABRIEL)
TOWER ANTENNA MOUNTING DETAILS (ANDREW)
TOWER ANTENNA MOUNTING DETAILS (MIKRO TIK/mWAVE)
TOWER ANTENNA MOUNTING DETAILS (UBIQUITI, GABRIEL)
TOWER ANTENNA MOUNTING DETAILS (COMMSCOPE/RADIOWAVES)
TOWER ANTENNA MOUNTING DETAILS (COMMSCOPE)
TOWER ANTENNA MOUNTING DETAILS (RADWIN, SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS
(HUSTLER/ANTENNA EXPERT/DIAMOND)
TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
CO-TA8
CO-TA9
CO-TA10
CO-TA10.1
CO-TA11
CO-TA11.1
CO-TA11.2
CO-TA12
CO-TA13
CO-TA14
CO-TA14.1
CO-TA15
CO-TA16
CO-TA17
CO-TA17.1
CO-TA17.2
CO-TA18
CO-TA18.1
CO-TA19
TOWER ANTENNA MOUNTING DETAILS (COMPROD)
TOWER ANTENNA MOUNTING DETAILS (M2/KRECO)
TOWER ANTENNA MOUNTING DETAILS (COMMSCOPE/RFS/SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (RFS/SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (SCALA)
TOWER ANTENNA MOUNTING DETAILS
(DB SPECTRA/RFI MOTOROLA/SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (DB SPECTRA/SCALA)
TOWER ANTENNA MOUNTING DETAILS (SCALA)
TOWER ANTENNA MOUNTING DETAILS (SCALA)
TOWER ANTENNA MOUNTING DETAILS (SCALA)
TOWER ANTENNA MOUNTING DETAILS (SCALA)
TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
TOWER ANTENNA MOUNTING DETAILS (TELEWAVE)
TOWER ANTENNA MOUNTING DETAILS (TELEWAVE)
TOWER ANTENNA MOUNTING DETAILS (HASKALL DENKE)
SUBTOTAL NO. SHEETS: 44
SUBTOTAL NO. SHEETS: 28
SUBTOTAL NO. SHEETS: 13
TOTAL NO. SHEETS: 85
OCCUPANCY: GROUP U
CONSTRUCTION: TYPE II-B
STANTEC
SHEET NO.
SHEET NUMBER DRAWING NUMBERSHEET TITLE
STRUCTURAL DETAILS FOR RADIO AND MICROWAVE ANTENNA MOUNTING BRACKETS
DSA APPLICATION NUMBER: 02-119809
STATE OF CALIFORNIA
SHEET NUMBER DRAWING NUMBERSHEET TITLE
S-13.1ANTENNA LOCATION PLAN VIEWS
S-14.1FULLY LOADED LEG MOUNTED MICROWAVES
S-14.2FULLY LOADED VHF/UHF ANTENNA LOCATIONS
N
ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA-APPROVED CONSTRUCTION DOCUMENTS. THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2019 CBC SECTIONS 1617A.1.18 THROUGH 1617A.1.26 AND ASCE 7-16 CHAPTERS 13, 26, AND 30:
1. ALL PERMANENT EQUIPMENT AND COMPONENTS.
2. TEMPORARY, MOVABLE OR MOBILE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS OR WATER. “PERMANENTLY ATTACHED” SHALL
INCLUDE ALL ELECTRICAL CONNECTIONS EXCEPT PLUGS FOR 110/220 VOLT RECEPTACLES HAVING A FLEXIBLE CABLE.
3. TEMPORARY, MOVABLE OR MOBILE EQUIPMENT WHICH IS HEAVIER THAN 400 POUNDS OR HAS A CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT
THE COMPONENT IS REQUIRED TO BE RESTRAINED IN A MANNER APPROVED BY DSA.
THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE BUT NEED NOT DEMONSTRATE DESIGN COMPLIANCE WITH THE REFERENCES NOTED ABOVE. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT. FLEXIBLE CONNECTIONS MUST ALLOW MOVEMENT IN BOTH
TRANSVERSE AND LONGITUDINAL DIRECTIONS:
A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVING A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT.
B. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
THE ANCHORAGE OF ALL MECHANICAL, ELECTRICAL AND PLUMBING COMPONENTS SHALL BE SUBJECT TO THE APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED RESPONSIBILITY AND ACCEPTANCE BY DSA. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH THE ABOVE REQUIREMENTS.
MEP COMPONENT ANCHORAGE NOTE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-16 SECTION 13.3 AS DEFINED IN ASCE 7-16 SECTIONS 13.6.5, 13.6.6, 13.6.7, 13.6.8; AND 2019 CBC, SECTIONS 1617A.1.24, 1617A.1.25 AND 1617A.1.26.
THE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM ARE AS NOTED BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE (E.G., OSHPD OPM FOR 2013 CBC OR LATER), COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
MECHANICAL PIPING (MP), MECHANICAL DUCTS (MD), PLUMBING PIPING (PP), ELECTRICAL DISTRIBUTION SYSTEMS (E):
MP MD PP E OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND
DETAILS.
MP MD PP E OPTION 2: SHALL COMPLY WITH THE APPLICABLE OSHPD PRE-APPROVAL (OPM #)
S-12
GHD DRAWING INDEX
Sheet Number Sheet Title Drawing Number
1 COVER SHEET BG-G001
2 DRAWING INDEX, DESIGN CRITERIA AND SITE ORIENTATION BG-G002
3 ABBREVIATIONS AND SYMBOLS BG-G003
4 EXISTING SITE DEMOLITION AND CONSTRUCTION SEQUENCING PLAN BG-C101
5 SITE AND GRADING PLAN BG-C102
6 COMMON SITE DETAILS BG-C501
7 COMMON SITE DETAILS BG-C502
8 VAULT FLOOR PLAN, ROOF PLAN AND BUILDING ELEVATIONS BG-A101
9 ARCHITECTURAL DETAILS BG-A501
10 ARCHITECTURAL DETAILS BG-A502
11 STRUCTURAL NOTES BG-S001
12 VAULT FOUNDATION, ROOF FRAMING PLAN AND SECTION BG-S101
13 TOWER FOUNDATION PLAN AND ELEVATION BG-S102
14 COMMON STRUCTURAL DETAILS BG-S501
15 STRUCTURAL DETAILS BG-S502
16 STRUCTURAL DETAILS BG-S503
17 FEEDLINE BRIDGE BG-S701
18 FEEDLINE BRIDGE BG-S702
19 MECHANICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND GENERAL NOTES BG-M001
20 MEDIUM VAULT - HVAC BG-M101
21 MECHANICAL DETAILS BG-M501
22 MECHANICAL SCHEDULES BG-M601
23 ELECTRICAL SYMBOLS, LEGEND, ABBREVIATIONS AND GENERAL NOTES BG-E001
24 ELECTRICAL SITE PLAN BG-E101
25 MEDIUM VAULT - LIGHTING, POWER, EQUIPMENT AND GROUNDING BG-E102
26 MEDIUM VAULT - INTERIOR ELEVATIONS BG-E103
27 ELECTRICAL DETAILS - 1 BG-E501
28 ELECTRICAL DETAILS - 2 BG-E502
29 ELECTRICAL DETAILS - 3 BG-E503
30 ELECTRICAL DETAILS - 4 BG-E504
31 ELECTRICAL DETAILS - 5 BG-E505
32 ELECTRICAL DETAILS - 6 BG-E506
33 SINGLE LINE DIAGRAM AND LOAD CALCULATION BG-E601
34 ELECTRICAL SCHEDULES - 1 BG-E602
35 ELECTRICAL SCHEDULES - 2 BG-E603
36 ALARM STATUS REPORTING SCHEMATICS BG-E604
37 ALARM POINT DESCRIPTIONS BG-E605
38 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF CABLING - 1 BG-E606
39 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF CABLING - 2 BG-E607
40 SITE ANTENNA LAYOUT AND PRESSURIZATION EQUIPMENT - 1 BG-E608
41 SITE ANTENNA LAYOUT AND PRESSURIZATION EQUIPMENT - 2 BG-E609
42 -48VDC CRIS OES INTERCONNECT DIAGRAM BG-E610
43 -48VDC MW OES INTERCONNECT DIAGRAM BG-E611
44 +12VDC OES INTERCONNECT DIAGRAM BG-E612
1 SFM RESUBMITTAL RK CR 11/20/25
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/12/26
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
22-5731
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
02-120755
✔ FLS ACS
02/25/2026
11-20-2025
S Y M B O L S
NEW CONTOURS
EXISTING SPOT ELEVATION
EXISTING STRUCTURE TO BE DEMOLISHED
EXISTING STRUCTURE TO REMAIN
999.8
EXISTING GUY ANCHOR AND WIRE
NEW BUILDING
EXISTING SURVEY MONUMENT
NEW SURVEY MONUMENT
FINISH PAD ELEVATION FP=1000.0
FINISH SLAB ELEVATION FS=1001.0
FF=1002.0FINISH FLOOR ELEVATION
NEW GROUND ELEVATION
NEW SLOPE BANK
PLACE 4" GRAVEL
EXISTING POLE
EXISTING POWER POLE
1000EXISTING CONTOURS
PROPOSED DRAINAGE FLOW DIRECTION
STRUCTURE TO BE DEMOLISHED (D) ANTENNA TOWER
CONCRETE PAD WITH
EXISTING SURVEY INFORMATION
40' TALL ANTENNA
NEW PERMANENT BOLLARD
NEW PROPANE TANK(S) WITH CONCRETE PAD
ON SHEET BG-A501
BUILDING SECTION B
SEE DETAIL 5 ON SHEET BG-A501
REVISION CLOUD AND NUMBER
CONTROL POINT
CENTERLINE
OBJECT HIDDEN FROM VIEW
STUD WALL
PLYWOOD
METAL
INSULATION
GYPSUM WALLBOARD
GRAVEL
RIGID INSULATION
EARTH
CONTINUOUS
BLOCKING
CONCRETE
MASONRY UNIT
CONCRETE
CEMENT PLASTER
BLOCKING
ASPHALT
DISTANCE BETWEEN OBJECTS
NOTE: DISTANCE FROM EXISTING
TREE IS RELATIVE TO THE
DISTANCE FROM THE CENTER OF
THE EXISTING TREE
19'-6"
NEW STRUCTURE ELEVATION
NEW GROUND ELEVATION @ SWALE FLOWLINE
FINISH GRAVEL ELEVATION FG=997.80
UNO TO BE (DD)
995.5
TOP OF STOOP
EL=995.52
980.0
SWALE
ABBREVIATIONS
AND SYMBOLS
BG-G003
NTS
BG-A501
B
BG-A501
Sheet of
This document shall not be used for construction unless signed and sealed for construction.
DesignerDrawn
Scale
Date
Drafting Check
Design Check
Project Manager
Reuse of Documents
This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2025 GHD
0 1"
Bar is one inch on original size sheet
Original Size
Arch D
Project No.
Sheet No.
IssueNo. Drawn Approved Date
Title
Client
Project
Plot Date: Filename:25 November 2025 - 11:22 AM N:\US\Cameron Park\Projects\111\11136839\06-CAD\Bunchgrass\Sheets\0003 BGG003 Abbreviations and Sym.dwgPlotted By: Becca Keating
M.WEBER 10/22/2024
11136839
GHD Inc.
943 Reserve Drive Roseville California 95678 USA T 1 916 782 8688 W www.ghd.com
STATE OF CALIFORNIA
DEPARTMENT OF GENERAL SERVICES
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS / HATCHET MTN - PHASE V
REV V3
REVIEWER:
REVIEWER SIGNATURE:
DATE REVIEWER:
PSC OPERATIONS PLAN REVIEW
NO EXCEPTIONS TAKEN
J E S
S
IC
A E. NA
P
IE
R
No. S5476
Exp. 6/30/26
A B B R E V I A T I O N S
MASONRY UNITMU
MTD MOUNTED
STAINLESS STEEL
WH WATER HEATER
WI WROUGHT IRON
W/O WITHOUT
WG WIRE GLASS
UNLESS NOTEDUNO
TYPICALTYP
THRU THROUGH
TOW TOP OF WALL
THRESHOLDTHR
SYM SYMMETRICAL
SUSPENDEDSUSP
STRUCT STRUCTURAL
SC SOLID CORE
SD STORM DRAIN
SECTIONSECT
SCHED SCHEDULE
REQ'D REQUIRED
ROOF DRAIN RD
WATER OR WEATHERWP
VERTICALVERT
WITHW/
WESTW
OR CONCRETE
TOP OF CURBTC
TOP & BOTTOMT&B
STANDARDSTD
STEELSTL
SS
SQUARESQ
SHEET METALSM
SIMILARSIM
SHEETSHT
SOUTHS
ROCK SLOPE PROTECTION RSP
REINFORCEREINF
REGISTER REG
RETURN AIR RA
GAUGE
GALVANIZED IRON
GLASS OR GLAZING
GYPSUM
HT HEIGHT
KPL KICKPLATE
MB MACHINE BOLT
MECH MECHANICAL
MEMB MEMBRANE
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
(N) NEW
OPP OPPOSITE
PL PLATE
PLAS PLASTER
PLYWD PLYWOOD
PR PAIR
PVC POLYVINYL CHLORIDE
GALVANIZED
GRADE
HOLLOW CORE
HM HOLLOW METAL
HEADERHDR
HOSE BIBB
LAG BOLTLB
LT LIGHT
MAXIMUMMAX
MTL METAL
MINIMUMMIN
MANUFACTURERMFR
MISC MISCELLANEOUS
NOT TO SCALENTS
OPENINGOPNG
OUTSIDE DIAMETEROD
ON CENTEROC
FRP FIBERGLAS REINFORCED
FOOT OR FEET
FTG FOOTING
FUR FURRING
EXH EXHAUST
EXIST EXISTING (SEE (E))
EXP EXPANSION
EQUIP EQUIPMENT
EASTE
(E) EXISTING
DOWNSPOUTDS
DR DOOR
DWG DRAWING(S)
DIMENSIONDIM
DOUBLE
CONTINUOUSCONT
CONST CONSTRUCTION
BLKG BLOCKING
BTM BOTTOM
BUILT UP ROOFINGBUR
BM BEAM
ASPH ASPHALT
ALUMINUM
FACE OF MASONRYFOM
FACE OF FINISHFOF
FACE OF CONC.FOC
FLOORFLR
FINISH
FIRE EXTINGUISHER
FOUNDATION
FLOOR DRAIN
FLAT BAR
EXPANSION JOINT
EQUAL
ELECTRICAL (AL)ELEC
ELEVATION
EACHEA
DIAGONALDIAG
DIAMETERDIA
DETAILDTL
COMPOSITIONCOMP
CONCRETECONC
COMMUNICATIONCOMM
CONC MASONRY UNITCMU
CAULKINGCLKG
CEILINGCLG
CONTROL JOINTCJ
CEMENTCEM
BLOCKBLK
BUILDINGBLDG
ARCHITECTURALARCH
ARCHITECT/ENGINEERA/E
ANCHOR BOLTAB
JOINTJT
JOISTJST
INCH OR INCHES
INSIDE DIAMETER
OVERO/
FOS FACE OF STUD
DELAYED DEMOLITION
DBL
PANEL
PROOF
BOW BOTTOM OF WALL
UG UNDERGROUND
SW SOUTHWEST
SE SOUTHEAST
NE NORTHEAST
NW NORTHWEST
DD
EQ
EL
EJ
FIN
FE
FDN
FD
FB
FT
HC
HB
GYP
GR
GL
GI
GALV
HDR
GA
IN
ID
ROUGH OPENING RO
AL
LIQUIFIED PETROLEUMLPG
RAIN WATER LEADER RWL
TOS TOP OF STEEL
TO TOP OF
BO BOTTOM OF
CAL FIRECDF
TOC TOP OF CONCRETE
ABOVE GRADE LEVELAGL
UNLESS OTHERWISEUON
GAS
NOTED
OTHERWISE
COLUMNCOL
1 SFM RESUBMITTAL RK CR 11/20/25
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/12/26
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
22-5731
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
02-120755
✔ FLS ACS
02/25/2026
11-20-2025
(E)TOWER ON CONC PAD
(P)FENCE LINE AND SLIDE GATE
CITIZENS UTILITIES COMPANY
OF CALIFORNIA LEASE
PER 49LS66
(E
) TA
N K
(E)
GEN
ER
AT
OR
VA
UL
T
(E)
CO
NC
(E)VAULT
(E)
PR
OPA
NE
TA
NK
(E)CHAINLINK FENCE
TO BE REMOVED
STATE OF CALIF. LEASE BOUNDARY
PER SITE MAP PROVIDED BY
CALFIRE. INCLUDES CORNER
CALLS, NOT REFERENCED IN
ACTUAL LEASE DOCUMENT WITH SPI
(E)BLDG
(E)FEEDLINE
(E
) TA
N K
(E)TOWER
TO BE REMOVED
9 8
(P)PROPANE TANK
(P)VAULT
(P)TOWER
5 2
(E) ACCESS R
OAD
(E) ACCESS ROAD
(E)
ACCES
S R
OAD
EXISTING SITE
DEMOLITION AND CONSTRUCTION
SEQUENCING PLAN
BG-C101
PEM PEM
MDH MDH
1" = 10'
N
0 20'10'
(E) EXISTING
PROPANE TANK
RADIO TOWER SIZE VARIES
(P)EDGE OF CONCRETE
(P)BARBWIRE FENCE
BOUNDARY LINE
EDGE OF GRAVEL ROAD
EXISTING STRUCTURE TO BE REMOVED
POWER POLE
CONCRETE
NTS NOT TO SCALE
DEMOLITION / CONSTRUCTION SEQUENCE:
SEE SHEET BG-C102 FOR PROPOSED IMPROVEMENTS.
LEGEND
1 CONSTRUCT FOUNDATION AND INSTALL NEW PROPANE TANK (REFERENCE SHEET BG-C102).
TEMPORARILY REESTABLISH GAS FEED TO (E) VAULT.
REMOVE (E) PROPANE TANK AND CONCRETE SLAB.
CONSTRUCT NEW VAULT PER PLAN (REFERENCE SHEET BG-C102) AND PROVIDE TEMPORARY FEED
LINE BRIDGE TO THE EXISTING TOWER.
PROVIDE GAS FEED TO NEW VAULT FROM NEW PROPANE TANK.
TRANSITION TOWER AND COMMUNICATIONS FROM EXISTING TOWER TO NEW VAULT.
DEMOLISH (E) VAULT, (E) GENERATOR VAULT, BLOCK WALL AND ADJACENT CONCRETE FLATWORK.
CONSTRUCT NEW TOWER PER PLAN (REFERENCE SHEET BG-C102) AND CONSTRUCT PERMANENT
FEED LINE BRIDGE FROM NEW VAULT TO TOWER.
TRANSITION COMMUNICATIONS FROM OLD TOWER TO NEW TOWER.
DEMOLISH (E) TOWERS (2).
REMOVE EXISTING CHAIN LINK FENCING, GATES, AND POST FOOTINGS.
CONSTRUCT NEW 6 FOOT FENCE WITH BARBED WIRE AND DRIVE THROUGH GATE PER PLAN.
PLACE AGGREGATE BASE FOR DRIVEWAY AND SITE ACCESS PER LIMITS SHOWN ON BG-C102.
(E)CONCRETE TO BE REMOVED
(E)BOLLARD TO BE REMOVED
(P) PROPOSED
Sheet of
This document shall not be used for construction unless signed and sealed for construction.
DesignerDrawn
Scale
Date
Drafting
Check
Design Check
Project Manager
Reuse of Documents
This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2025 GHD
0 1"
Bar is one inch on original size sheet
Original Size
Arch D
Project No.
Sheet No.
IssueNo. Drawn Approved Date
Title
Client
Project
Plot Date: Filename:25 November 2025 - 11:22 AM N:\US\Cameron Park\Projects\111\11136839\06-CAD\Bunchgrass\Sheets\0004 BGC101 Site Demo.dwgPlotted By: Becca Keating
M.WEBER 10/22/2024
11136839
GHD Inc.
943 Reserve Drive
Roseville California 95678 USA T 1 916 782 8688 W www.ghd.com
STATE OF CALIFORNIA
DEPARTMENT OF GENERAL SERVICES
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS / HATCHET MTN - PHASE V
REV V3
REVIEWER:
REVIEWER SIGNATURE:
DATE REVIEWER:
PSC OPERATIONS PLAN REVIEW
NO EXCEPTIONS TAKEN
(E)NON-STATE FACILITIES
OUTSIDE THE PROJECT AREA
SHALL BE PROTECTED.
OCCUPANCY: GROUP U
CONSTRUCTION: TYPE II-B
(E)NON-STATE FACILITIES
OUTSIDE THE PROJECT AREA
SHALL BE PROTECTED.
OCCUPANCY: GROUP U
CONSTRUCTION: TYPE II-B
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/12/26
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
22-5731
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
02-120755
✔ FLS ACS
02/25/2026
11-20-2025
5289.60 FS/FG
2%
2%
1%
1.2%
9.
2%
9.
2%
7.
2%
.5
.7%
1.1%
RE
DD
ING
7°
BURNEY DOT 82°
PROPOSED (N) FENCE LINE AND SLIDE GATE
CITIZENS UTILITIES COMPANY
OF CALIFORNIA LEASE
PER 49LS66
(E
) TA
N K
STATE OF CALIF. LEASE BOUNDARY
PER SITE MAP PROVIDED BY
CALFIRE. INCLUDES CORNER
CALLS, NOT REFERENCED IN
ACTUAL LEASE DOCUMENT WITH SPI
(E) BLDG
BIG
VA
LLE
Y M
NT.
(E
) TA
N K
11.5'
25' PROPANE TANK SETBACK LINE
3.3'
FF = 5289.87
S
LA
B
9.
.9
5283.20 FG
MATCH (EX)
(+/- 5278.8 FG)
2%
2%
2%
5289.70 FS/FG
MATCH ELEVATION
AT THRESHOLD
5294.90 FG
5283.50 FG
PROPOSED (N) BOLLARD (TYP) QNTY=5
PER DETAIL 3 ON SHEET BG-C501
34'
32'
A
B G -C
C
BG-C501
2%
15'
R=15'
R=30'
R=25'
R=25'
5285.00 FG
5294.90 FG
5289.50 FG
5288.66 FG/FL
1.2%
5280.70 FG
.7%
GRADE LEVEL AREA FOR
SLIDE GATE OPERATION
5288.80 FG
PROPOSED (N) MEDIUM
VAULT LOCATION
(22'-8" x 30'-8")
5%
D
B G -C
83 5284
5 2 81 52
1 2
6 7
8 9
10 11
12 13
14 15
18 19
22 23
38 39
3 4
2:
2:1
2:1
2:
2:
(E) ACCESS R
OAD
(E) ACCESS ROAD
(E)
ACC
ESS
ROAD4" PERFORATED
SUBDRAIN AT
RETAINING WALL
BG-C501
BG-501
B
BG-C501
BG-C501
BG-C501
SPOIL AREA - PLACE EXCESS SPOILS WITHIN
AREA DESIGNATED AS NECESSARY. COMPACT
AND KEY FILL PER SPECIFICATIONS.
5290.56 FG
2:1
2:1
2:1
5290.15 FG
LIMITS OF TOWER
EXCAVATION
N=2202048.36 E=6624696.79
LAT N040° 52' 29.30"
LONG W121° 46' 19.43"
SPOIL AREA - PLACE EXCESS SPOILS WITHIN
AREA DESIGNATED AS NECESSARY. COMPACT
AND KEY FILL PER SPECIFICATIONS.
5' T Y P
5288.80 FG
5288.80 FG
5288.05 FG
5285.20 FG
MATCH (EX)
(+/- 5283.5 FG)
5283.50 FG
5285.50 FG
5288.40 FG
5289.60 FG
5289.70 FG
5289.60 FS/FG
5289.70 FS/FG
5289.60 FG
5289.70 FG
5289.70 FG
5291.10 TW
(5288.60) FG
MATCH (E)
5286.50 TF
5291.10 TW
(5287.04) FG
MATCH (E)
5286.50 TF
R=15'
5283.32 FG
5289.60 FG
5295.40
TOP OF COLUMN
5295.40
TOP OF COLUMN
5295.20 FG
5289.35 FG
5289.20 FG
5289.05 FG
5291.10 TW
(5289.05) FG
MATCH (E)
5286.50 TF
5284.26 FG
5284.56 FG
5287.72 FG
5287.42 FG
5288.80 FG
5288.90 FG
5288.65 FG
5295.90 TW
5289.60 FG
5289.60 TF
5295.90 TW
5294.90 FG
5289.60 TF
5295.90 TW
(5291.32) MATCH (E)
5289.60 TF
5289.60 FG
5289.60 FG
5289.40 FL/FG
5291.10 TW
(5289.43) FG
MATCH (E)
5286.50 TF
5295.20 FG5290.40 FG
2:
2:1
2:
2:
5289.93 FG
5289.88 FG
5289.60 FG
5289.65 FG
5289.88 FG
5290.00 FG
5289.70 FG
PROPOSED (N)
PROPANE TANK
5.
0%
5289.95 FG
5295.90 TW
(5292.21) MATCH (E)
5289.60 TF
PROPOSED (N)
TOWER FOUNDATION
59 LF OF GAS LINE, SEE DETAIL
4/BG-C502 FOR TRENCHING DETAIL
(E) NON-STATE FACILITIES
OUTSIDE THE PROJECT AREA
SHALL BE PROTECTED
OCCUPANCY: GROUP U
CONSTRUCTION: TYPE II-B
(E) NON-STATE FACILITIES
OUTSIDE THE PROJECT AREA
SHALL BE PROTECTED
OCCUPANCY: GROUP U
CONSTRUCTION: TYPE II-B
5.81'
TRUE NORTH
LEG 1
LEG 2LEG 3
LEG 4
90°0'0"
0°
0'
270°0'0'"
0° 0' 0"
0°
0' 0"
POINT TABLE
POINT #
EASTINGS
6624680.78
6624712.78
6624687.29
6624706.29
6624696.79
6624687.29
6624706.29
6624681.44
6624712.78
NORTHINGS
2202064.35
2202064.35
2202057.86
2202057.86
2202048.36
2202038.86
2202038.86
2202033.02
2202032.35
POINT TABLE
POINT #
EASTINGS
6624642.90
6624651.49
6624651.49
6624661.82
6624661.82
6624673.57
6624673.54
6624642.88
6624635.87
NORTHINGS
2202032.58
2202032.57
2202037.57
2202037.56
2202032.56
2202032.54
2202009.88
2202009.91
2202004.25
POINT TABLE
POINT #
EASTINGS
6624666.30
6624674.49
6624680.78
6624680.78
6624692.28
6624679.40
6624679.80
6624678.57
6624635.90
NORTHINGS
2202004.22
2202007.54
2202040.78
2202032.35
2202032.35
2202009.88
2202009.04
2202030.87
2202032.58
POINT TABLE
POINT #
EASTINGS
6624616.37
6624595.10
6624611.38
6624560.64
6624576.58
6624584.06
6624600.35
6624606.95
6624606.95
NORTHINGS
2202024.50
2202001.36
2201976.69
2201963.16
2201985.84
2202011.51
2202029.23
2202046.12
2202051.12
POINT TABLE
POINT #
EASTINGS
6624600.37
6624600.39
6624606.98
6624606.99
6624645.62
6624661.82
6624673.57
NORTHINGS
2202051.13
2202071.13
2202071.12
2202079.98
2202079.89
2202044.57
2202037.56
SITE AND GRADING PLAN
BG-C102
PEM PEM
MDH MDH
1" = 10'
0 20'10'
TOWER ORIENTATION PLAN
NTS
N
THE BASIS OF BEARINGS FOR THIS SURVEY IS CCS83 (EPOCH 2010), ZONE 1 BASED ON
AN OPUS SOLUTION OF GPS OBSERVATIONS.
BENCH MARK
THE VERTICAL DATUM IS NAVD 88 BASED ON AN OPUS SOLUTION OF GPS OBSERVATIONS.
AB
BOW
(E) E
FG
FL
FS
AGGREGATE BASE
BOTTOM OF WALL
EXISTING
EASTING
FINISHED GRADE
FLOWLINE
FINISHED SURFACE
ABBREVIATIONS
BASIS OF BEARING
SHEET KEYNOTES
1. PROPOSED CONCRETE MAT FOUNDATION FOR TOWER (SEE STRUCTURAL SHEETS).
TOP OF FOUNDATION ELEVATION = 5295.40
BOTTOM OF FOUNDATION ELEVATION = 5286.10
2. PLACE 4" AB OVER COMPACTED SUBGRADE, COMPACTED TO 95% RELATIVE
COMPACTION
3. PROPOSED VAULT BUILDING. SEE STRUCTURAL SHEETS
4. PLACE 7" AB OVER GEOSYNTHETIC FABRIC (MIRAFI HP270 OR APPROVED EQUAL)
5. DAYLIGHT RETAINING WALL SUBDRAIN
6. SPOIL AREA
7. CONSTRUCT 8'x15' CONCRETE PAD FOR EMERGENCY GENERATOR PER DETAIL
1/BG-S503. ELEVATION TO BE FLUSH WITH ADJACENT GRADE.
8. CONSTRUCT 1,000 GALLON PROPANE TANK PER DETAIL 1/BG-M501 AND DETAIL
5/BG-E505 FOR GROUNDING AT PROPANE TANK PAD
9. CONSTRUCT BOLLARD PER DETAIL 3/BG-C501
10. CONSTRUCT FENCE AND SLIDING GATE PER DETAILS 2 & 3/BG-C502. SEE SHEET
BG-E506 FOR GROUNDING
EXISTINGPROPOSED
GROUND ELEVATION
TOP OF SLOPE
GROUND CONTOUR
CONCRETE
STRAW WATTLE
DITCH FLOWLINE
7839.1± EG
LEGEND
HORIZONTAL/ VERTICAL
SITE CONTROL
SHEET GENERAL NOTES
1. ALL CONSTRUCTION NOTED AS (N) IS NEW "ESSENTIAL" FACILITY CONSTRUCTION
PER THE 1986 ESSENTIAL SERVICES ACT.
2. ELEMENTS IDENTIFIED AS (E) OR (E) TO REMAIN, ARE NOT "ESSENTIAL" AND ARE NOT
PART OF THE COMMUNICATIONS FACILITY.
3. EXCESS EXCAVATION SOIL CAN BE SPREAD ONSITE AT SPECIFIED SPOIL AREA.
CONTRACTOR TO VERIFY LOCATION WITH DGS PRIOR TO SPREADING.
4. THE CONTRACTOR SHALL REPAIR ALL ACCESS ROAD SURFACES TO THE
SATISFACTION OF THE DGS PROJECT DIRECTOR UPON COMPLETION OF THE
PROJECT.
5. EXISTING UTILITY LOCATION NOTE: PROJECT CONTRACTOR TO VERIFY DEPTH AND
LOCATION OF EXISTING UTILITIES PRIOR TO CONSTRUCTION. PROJECT
CONTRACTOR TO CONTACT UNDERGROUND SERVICE ALERT (USA) 811 “CALL
BEFORE YOU DIG” PROGRAM AND COORDINATE LOCATING EXISTING UTILITIES VIA A
PRIVATE UNDERGROUND UTILITY LOCATOR CONTRACTOR THAT UTILIZES
ELECTROMAGNETIC LOCATION DETECTION AND/OR GROUND PENETRATING RADAR.
4" AB
GB
LAT
LONG
(N) N
TF
TW
GRADE BREAK
LATITUDE
LONGITUDE
NEW
NORTHING
TOP OF FOOTING
TOP OF WALL
7" CLASS 2 AB
Sheet of
This document shall not be used for construction unless signed and sealed for construction.
DesignerDrawn
Scale
Date
Drafting Check
Design Check
Project Manager
Reuse of Documents
This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2025 GHD
0 1"
Bar is one inch on original size sheet
Original Size
Arch D
Project No.
Sheet No.
IssueNo. Drawn Approved Date
Title
Client
Project
Plot Date: Filename:25 November 2025 - 2:41 PM N:\US\Cameron Park\Projects\111\11136839\06-CAD\Bunchgrass\Sheets\0005 BGC102 Site Grading Plan.dwgPlotted By: Becca Keating
M.WEBER 10/22/2024
11136839
GHD Inc.
943 Reserve Drive Roseville California 95678 USA T 1 916 782 8688 W www.ghd.com
STATE OF CALIFORNIA
DEPARTMENT OF GENERAL SERVICES
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS / HATCHET MTN - PHASE V
REV V3
REVIEWER:
REVIEWER SIGNATURE:
DATE REVIEWER:
PSC OPERATIONS PLAN REVIEW
NO EXCEPTIONS TAKEN
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/12/26
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
22-5731
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
02-120755
✔ FLS ACS
02/25/2026
11-20-2025
22.67'
PROPOSED (N) VAULT BUILDING
2:1
7" CLASS 2 AB OVER
COMPACTED SUBGRADE
SEE STRUCTURAL
SHEETS FOR VAULT
FOUNDATION DESIGN
(E) GROUND
PROPOSED
GRADE
PROPOSED (N) FENCE
PROPOSED (N) RETAINING
WALL SEE STRUCTURAL
SHEETS FOR DESIGN
TF=5286.50
LEASE BOUNDARY
PROPOSED (N) FENCE
LEASE BOUNDARY
30.67'
PROPOSED (N) VAULT BUILDING
SEE STRUCTURAL
SHEETS FOR VAULT
FOUNDATION DESIGN
4" AB OVER COMPACTED
SUBGRADE
(E) GROUND
PROPOSED
GRADE
4" AB OVER COMPACTED
SUBGRADE
2:1
PROPOSED (N) FENCE
PROPOSED GRADE
SEE STRUCTURAL
SHEETS FOR
FOUNDATION DESIGN
1' OVER EXCAVATE
32'
1' OVER EXCAVATE
TOC=5295.40
TOC=5289.10
4" AB OVER COMPACTED
SUBGRADE
4" AB OVER COMPACTED
SUBGRADE
7" CLASS 2 AB OVER
COMPACTED SUBGRADE
(E) GROUND
PROPOSED (N) FENCE
LEASE BOUNDARY
2:1
SEE STRUCTURAL SHEETS
FOR COLUMN DESIGN
2:1
4" PERFORATED SUBDRAIN
PROPOSED GRADE
PROPOSED
GRADE
SEE STRUCTURAL SHEETS
FOR FOUNDATION DESIGN
TOC=5295.40 TOC=5295.40
2:1
4" AB OVER COMPACTED
SUBGRADE SEE STRUCTURAL
SHEETS FOR COLUMN
DESIGN (TYP)
4" AB OVER COMPACTED
SUBGRADE
(E) GROUND
PROPOSED
GRADE
1' OVER EXCAVATE
32'
1' OVER EXCAVATE
(E) GROUND
4" AB OVER
COMPACTED
SUBGRADE
PROPOSED (N) RETAINING
WALL SEE STRUCTURAL
SHEETS FOR DESIGN
PROPOSED (N) FENCE
(E) FENCE TO BE REMOVED
4" PERFORATED SUBDRAIN
2:1
TOC=5289.10
CONCRETE PIER
NOTES:
CONCRETE FILLED 6" DIAMETER STEEL PIPE EXTENDED 48" ABOVE AND
BELOW GRADE OR SLAB. SHEATH WITH YELLOW BUMPER POST SLEEVES
MANUFACTURED IDEALSTEEL AND BUILDER SUPPLIES, INC.
1/2" ISOLATION JOINT
6" PIPE OVER FILLED W/
CONCRETE & PROVIDE DOME TOP.
FINISH GRADE
COMMON SITE DETAILS
BG-C501
PEM PEM
MDH MDH
AS SHOWN
3/4"x3/4"x24" WOOD STAKE AT START, FLOW
NOTES:
3"-5"
M
IN
OVERLAP STRAW WATTLES
12" MIN AT ENDS
EVERY 48" OC AND AT END
FLOW
3'-4'
ON BENCH
30' OR MID HEIGHT
SLOPE STEEPNESS
ON SOIL TYPE AND
SPACING DEPENDS
TIGHTLY ABUT
ADJACENT ROLLS SHALL
1. STRAW WATTLES SHALL BE MANUFACTURED
FROM RICE STRAW AND BE WRAPPED IN A
TUBULAR BLACK PLASTIC NETTING. THE NETTING
SHALL HAVE A STRAND THICKNESS OF 0.30 INCH,
AND A KNOT THICKNESS OF 0.055 AND A WEIGHT
OF 0.35 OUNCE PER FOOT (EACH ± 10%) AND
SHALL BE MADE FROM 85% HIGH DENSITY
POLYETHYLENE, 14% ETHYL VINYL ACETATE AND
1% COLOR FOR UV INHIBITION. STRAW WATTLE
SHALL BE TWENTY-FIVE FEET LONG (± 6") AND
WEIGH APPROXIMATELY 30 POUNDS (± 3LBS)
2. FIBER ROLL INSTALLATION REQUIRES THE
PLACEMENT AND SECURE STAKING OF THE ROLL
IN A TRENCH, 3"-5" (75-125mm) DEEP, DUG ON
CONTOUR. RUNOFF MUST NOT BE ALLOWED TO
RUN UNDER OR AROUND ROLL.
STRAW WATTLES MUST BE PLACED ALONG
SLOPE CONTOURS
SEDIMENT, ORGANIC MATTER, AND
NATIVE SEEDS ARE CAPTURED BEHIND
THE ROLLS
8"-10" DIAMETER RICE
STRAW WATTLE
ONE FOOT MIN KEY AT
BOTH ENDS OF DITCH
GEOTEXTILE FILTER FABRIC PER SPEC 31 20 00 EARTH MOVING
2:1 2:1
M
IN
12" 12"
PLACE CLASS NO. 3 RSP PER SPEC 31 20 00
EARTH MOVING. 12" MIN THICKNESS
A
SECTION A-A
SCALE: 1"=5'
B
SECTION B-B
SCALE: 1"=5'
STRAW WATTLE
SCALE: NTS
ROCK LINED DITCH
SCALE: NTS
EROSION AND SEDIMENT CONTROL NOTES
1. THE PRACTICE OF EROSION AND SEDIMENT CONTROL IS A DYNAMIC ACTIVITY WHICH REQUIRES FLEXIBILITY AND COMMITMENT BY THE CONTRACTOR TO SUCCESSFULLY IMPLEMENT. THE EROSION AND SEDIMENT CONTROL DETAILS ARE INTENDED TO PROVIDE GUIDANCE TO THE CONTRACTOR. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PREVENT DISCHARGE OF SEDIMENT FROM THE SITE TO ANY WATERCOURSE, DRAINAGE SYSTEM, OR ADJACENT PROPERTY AND TO PROTECT WATERCOURSES AND ADJACENT PROPERTIES FROM
DAMAGE BY EROSION OR DEPOSITION WHICH MAY RESULT FROM THE PERMITTED GRADING.
2. THE CONTRACTOR SHALL COMPLY WITH THE NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (N.P.D.E.S.) GENERAL PERMIT, WASTE DISCHARGE REQUIREMENTS AND ALL FEDERAL, STATE AND LOCAL LAWS AND REGULATIONS RELATING TO DISCHARGES OF STORM WATER
RUNOFF ASSOCIATED WITH CONSTRUCTION ACTIVITY.
3. THE LOCATION AND TYPE OF THE EROSION AND SEDIMENT CONTROL PRACTICES SHOWN ON THIS PLAN ARE GUIDELINES ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO IMPLEMENT THE PRACTICES IN SUCH A MANNER AS TO COMPLY WITH THE N.P.D.E.S. PERMIT. THE CONTRACTOR SHALL ADJUST MODIFY AND MAINTAIN THE EROSION AND SEDIMENT CONTROL MEASURES TO FIT THE PARTICULAR SITE
CONDITIONS AND PHASE OF CONSTRUCTION OR AS DIRECTED BY THE CONTRACTING OFFICER.
4. THE CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN EROSION AND SEDIMENT CONTROL MEASURES THROUGHOUT CONSTRUCTION UNTIL SUCH TIME THAT THE ENTIRE PROJECT HAS BEEN STABILIZED AND ACCEPTED BY THE STATE.
5. THE CONTRACTOR SHALL CONDUCT INSPECTIONS OF THE SITE PRIOR TO ANTICIPATED STORM EVENTS, AND AFTER ACTUAL EVENTS TO IDENTIFY AREAS CONTRIBUTING TO DISCHARGE OF STORM WATER ASSOCIATED WITH CONSTRUCTION ACTIVITY AND TO EVALUATE WHETHER CONTROL PRACTICES TO REDUCE POLLUTANT LOADINGS ARE ADEQUATE AND PROPERLY IMPLEMENTED IN ACCORDANCE WITH THE TERMS OF THE N.P.D.E.S. GENERAL PERMIT OR WHETHER ADDITIONAL CONTROL PRACTICES ARE NEEDED.
6. ALL TEMPORARY EROSION AND SEDIMENT CONTROL MEASURES MUST BE IN PLACE OR BE CAPABLE OF BEING IN PLACE WITHIN 24 HOURS.
7. STRAW WATTLES SHALL BE INSTALLED FOLLOWING THE CONTOUR TO PROTECT AREAS FROM SEDIMENTATION CAUSED BY SHEET AND RILL
EROSION.
8. ALL EROSION AND SEDIMENT CONTROL FEATURES SHALL BE MONITORED BY THE CONTRACTOR DURING AND AFTER ALL STORMS TO ENSURE CONTROL FEATURES ARE WORKING PROPERLY. ALTERNATIVE MEASURES MUST BE INSTALLED IF ORIGINAL MEASURES FAIL.
9. CONTRACTOR IS RESPONSIBLE FOR THE PREPARATION OF THE SWPPP PER SPECIFICATION SECTION 31 25 13.
6"
C
SECTION C-C
SCALE: 1"=5'
D
SECTION D-D
SCALE: 1"=5'
Sheet of
This document shall not be used for construction unless signed and sealed for construction.
DesignerDrawn
Scale
Date
Drafting Check
Design Check
Project Manager
Reuse of Documents
This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization. © 2025 GHD
0 1"
Bar is one inch on original size sheet
Original Size
Arch D
Project No.
Sheet No.
IssueNo. Drawn Approved Date
Title
Client
Project
Plot Date: Filename:25 November 2025 - 11:24 AM N:\US\Cameron Park\Projects\111\11136839\06-CAD\Bunchgrass\Sheets\0006 BGC501 Common Civil Dwgs.dwgPlotted By: Becca Keating
M.WEBER 10/22/2024
11136839
GHD Inc.
943 Reserve Drive Roseville California 95678 USA T 1 916 782 8688 W www.ghd.com
STATE OF CALIFORNIA
DEPARTMENT OF GENERAL SERVICES
CAL FIRE
TOWERS AND VAULTS
REPLACEMENT PROJECT
BUNCHGRASS / HATCHET MTN - PHASE V
REV V3
REVIEWER:
REVIEWER SIGNATURE:
DATE REVIEWER:
PSC OPERATIONS PLAN REVIEW
NO EXCEPTIONS TAKEN
BOLLARD TYPICAL DETAIL
SCALE: NTS
V3V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
01/12/26
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
22-5731
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS
APPROVED
DIV. OF THE STATE ARCHITECT
DATE:
02-120755
✔ FLS ACS
02/25/2026
11-20-2025
18" 4'-0"
2' -0
" DRAINROCK
GEOTEXTILE
FILTER FABRIC
PERFORTED PIPE
10'-0"
EXISTING GROUND SURFACE
BEFORE GRADING
ENGINEERED FILL
FINISHED SLOPE
2(h): 1(v) TYP
KEYWAY EXCAVATION
3' -0
TOE DRAIN
EXISTING GROUND SURFACE
CONCRETE-LINE V-DITCH
BENCHES (TYP)
SEEPAGE FLOW
EQUAL TO
KEYWAY DEPTH
TRENCH DRAIN
6' -0
(3) STRANDS
BARB WIRE
12"
3' -0
10' MAX SPACING
TENSION BAR
TENSION WIRE W/ TIES
2" M
IN
DIA
MIN
2"
MIN.
M
IN
MIN
MIN
M
IN
NOTES:
1. EXCAVATIONS FOR BENCHES AND KEYWAY SHALL REMOVE ALL LOOSE, SOFT, AND/OR DISTURBED ROCK, AS WELL AS ANY ORGANIC MATERIAL OR VEGETATION.
2. KEYWAY DEPTH INDICATED ABOVE IS A MINIMUM. ACTUAL DEPTH MAY VARY DEPENDING ON FIELD CONDITIONS. KEYWAY DEPTH MAY BE REDUCED TO LESS THAN 3 FEET IF HARD ROCK IS ENCOUNTERED.
3. IN GENERAL, CUT SLOPES BETWEEN BENCHES SHOULD BE NO STEEPER THAN 3/4(h): 1(v) OR FLATTER DEPENDING ON THE MATERIALS ENCOUNTERED AND SHOULD MEET ALL FEDERAL AND STATE OSHA REQUIREMENTS. THE MAXIMUM VERTICAL OFFSET BETWEEN ADJACENT BENCHES SHOULD BE LESS THAN 5 FEET. ALL BENCHES SHOULD EXTEND AT LEAST 2 FEET (HORIZONTALLY) INTO THE SLOPE.
4. THE BOTTOM OF THE KEYWAY SHOULD BE SLOPED DOWNWARD AT LEAST 2 PERCENT AND TOWARDS THE TOE DRAIN INDICATED ABOVE.
5. A TOE DRAIN SHOULD BE PLACED AT THE BOTTOM OF THE KEYWAY AT THE LOCATION INDICATED ABOVE. THIS DRAIN SHOULD EXTEND THE ENTIRE LENGTH OF THE KEYWAY AND BE CONSTRUCTED IN ACCORDANCE WITH DETAIL ABOVE AND
REQUIREMENTS PROVIDED BELOW.
6. IF WATER, FRACTURED ROCK, PERVIOUS SOILS, OR OTHER SUBSURFACE CONDITIONS ARE EXPOSED DURING GRADING WHICH WOULD INDICATE THE POTENTIAL FOR FUTURE WATER SEEPAGE INTO THE FILL, TRENCH DRAINS SHOULD BE INSTALLED AT THESE LOCATIONS IN ACCORDANCE WITH THE DETAIL ABOVE AND REQUIREMENTS PROVIDED BELOW.
A. DRAIN TRENCH DEPTH(S) WILL VARY DEPENDING ON THE SUBSURFACE CONDITIONS ENCOUNTERED DURING CONSTRUCTION. AS A MINIMUM, TRENCH DEPTH(S) SHOULD BE AT LEAST AS GREAT AS THE HEIGHT OF THE ADJOINING, DOWNSLOPE CUT; ACTUAL DEPTH(S) SHOULD BE DETERMINED IN THE FIELD BY THE PROJECT GEOTECHNICAL ENGINEER. THE TRENCH WALL SHOULD BE FREE OF OBSTRUCTIONS WHICH MIGHT PUNCTURE OR OTHERWISE HARM THE GEOTEXTILE FILTER FABRIC.
B. GEOTEXTILE FILTER FABRIC SHOULD BE STORED, HANDLED, AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
C. PERFORATED PIPE SHOULD BE AT LEAST 4 INCHES IN DIAMETER (FOR DRAINS LESS THAN 200 FEET IN LENGTH), OR 6 INCHES IN DIAMETER FOR DRAINS IN EXCESS OF 200 FEET IN LENGTH. PIPE ATTACHED WITHIN A WELL-DEFINED TRENCH (SUCH AS THE "TOE-DRAIN" INDICATED ABOVE) SHOULD CONSIST OF PERFORATED OR SLOTTED HIGH STRENGTH PLASTIC OR OTHER SIMILAR MATERIAL CAPABLE OF SUSTAINING THE INDUCED OVERBURDEN PRESSURE WITHOUT NOTICEABLE DEFORMATIONS. THE BOTTOM OF ALL PERFORATED PIPES SHOULD BE PLACED WITHIN 1 TO 3 INCHES OF THE TRENCH BOTTOM. ALL PERFORATED PIPES SHOULD BE CENTERED (HORIZONTALLY) WITHIN THE TRENCH.
D. WATER COLLECTED BY THE PERFORATED PIPE(S) SHOULD BE DIRECTED BY SOLID CONDUIT (OF SIMILAR TYPE TO PERFORATED) TO A SUMP, DITCH, STORM DRAIN, OR OTHER SUITABLE LOCATION FOR DISPOSAL.
E. ALL HDPE SECTIONS (IF USED) SHOULD BE JOINED USING SPLIT FITTINGS, SECURED USING NYLON WIRE TIES (TWO PER JOINT) AND POLYETHYLENE TAPE.
F. DRAINROCK SHOULD CONSIST OF POORLY-GRADED DURABLE STONE, SIZED SUCH THAT 100 PERCENT PASSES THE 1-INCH SIEVE AND LESS THAN 5 PERCENT PASSES THE NO. 4 SIEVE.
G. PERFORATED PIPE AND ANY SOLID CONDUIT COLLECTOR PIPES SHOULD BE SLOPED A MINIMUM OF ONE PERCENT (1%) TO DRAIN.
H. DRAIN LINE CLEANOUTS SHOULD BE PROVIDED AT 200-FOOT INTERVALS (MIN.). THE DESIGN AND LOCATION OF CLEANOUTS SHOULD BE PROVIDED BY THE PROJECT CIVIL ENGINEER. ALL CLEANOUTS SHOULD BE SECURED TO PREVENT VANDALISM
OR TAMPERING.
TYPICAL KEY AND BENCH DETAIL
SCALE:NTS
CHAIN-LINK FENCE
SCALE:NTS
TRENCH SECTIONS
SCALE:NTS
TOE DRAIN DETAIL TRENCH DRAIN DETAIL
EROSION CONTROL BLANKET
SCALE:NTS
CHAIN-LINK FENCE / GATE
SCALE:NTS
GATE
SEE NOTE 9
BARBED SELVAGE
FABRIC DETAIL
BOTTOM CORNER
TRUSS ROD
AND HINGE
GATE POST
GATE POST
TOP GATE HINGE
POST
BRACE ROD
8" GATE POST
POST DETAIL
TENSION BAR
TENSION BAND
TRUSS ROD
BRACE END
TURNBUCKLE
REINFORCING WIRE
PULLED TAUT
TENSION BAR
TENSION BAND
PIPE BRACE
BAND LINK
HOG RING
@ 12"OC
NO. 9 GAUGE
LINE POST
BRACE END
BRACE BAND
WIRE, WEAVE INTO
NO. 6 REINFORCING
FABRIC
LINE POST
FENCE ACCESSORIES
& BOTTOM MEMBERS
2" MAX. CLEAR TOP
8'-0"
GATE OPENING PER PLAN
6' -0
TOP TENSION WIRE
W
D
6"
GATE FOOTING TABLE:
GATE POST (8.62"O.D.)
D=48" W=32"Ø
(TYPICAL ALL 3)
STRETCHER
BAR & BANDS
3/8" DIA
TRUSS ROD
2" OD PIPE
(TYP)
TRUSS RODS WELDED AT
UPPER CORNERS
WELDED PLATE
WITH HOLE FOR
TRUSS ROD
6" THK x 12" WIDE
FIBERMESH CONC
2 1/2" OD PIPE
(TYP)
STEEL WHEEL
GATE POST
SEE NOTE 9.
STOP CURB PRIOR TO FENCE POST
AND FENCE POST FOOTING TYP
BOTH OF THE DRIVEWAY
X X X X X X X
X X X X X X
X X X X X X X
X X X X X
X X X X X
X X X X X
X X X X X X X X X
X X X X X X X X X
X X X X X X X X X
FITTINGS AND HARDWARE NOTES
1. ALL FERROUS METAL SHALL BE HOT DIPPED GALVANIZED PER ASTM A-153.
2. FENCE AND GATES SHALL BE FURNISHED COMPLETE WITH ALL NECESSARY FITTINGS.
3. FOR GATES-SIZES OF PIPES, SAG RODS, AND TURN BUCKLES SHALL BE MANUFACTURER'S
STANDARD MEETING REQUIREMENTS OF THIS DRAWING.
4. ALL POSTS AND STRUCTURAL SUPPORTS SHALL BE LOCATED ON INNER SIDE OF THE FENCING.
5. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI AT 28 DAYS
WITH 3" SLUMP AND 3/4" MAX. SIZE OF AGGREGATE.
6. FENCE FABRIC TO BE 96" UNLESS OTHERWISE SPECIFIED, AND GALVANIZED CONFORMING TO
ASTM-A392, CLASS 2 (2.0 OZ. PER S.Q. FOOT OF SURFACE AREA)
7. ALL HARDWARE SHALL BE PEENED OE WELDED IN SUCH A MANNER TO ALLOW PROPER
OPERATION OF COMPONENTS, BUT PREVENT DISASSEMBLY OF FENCING OR GATES.
8. MAINTAIN CONTINUITY OF BARBED WIRE WHEN TRANSITION FROM HIGH TO LOW FENCE.
9. FENCE MATERIAL SIZES.
LINE POST 2" O.D.
CORNER POST 3" O.D.
GATE POST 4" O.D.
GATE POST 13'-18' WIDE 6.62" O.D.
GATE POST 18'-OVER 8.62" O.D.
TOP RAIL 1-5/8" O.D.
BRACE RAIL 1-5/8" O.D.
FENCE FABRIC GAGE #9
TENSION ROD 3/8" DIAMETER
SECTION A-A
GATE POST SEE
NOTE 9
A
A
PROPANE GAS PIPE
12"
4"
SELECT PIPE BEDDING
SCARE TAPE
2" SAND
NATIVE SOIL
ELECTRIC POWER
12"
4"
SELECT PIPE BEDDING
SCARE TAPE
2" SAND
NATIVE SOIL
UNDERGROUND PROPANE GAS UNDERGROUND ELECTRIC POWER
FINISH GRADE
FINISH GRADE
2"-5"
20"
10"
2"-5"
3.3'
10"
3.75 SPIKES PER SQ YD
(4.8 SPIKES PER SQ M)
FOR BLANKETS WITH THE NORTH AMERICAN
GREEN DOT SYSTEM PLACE SPIKES AS SHOWN
SPIKES IN THE BOTTOM
OF THE TRENCH PLACED
APPROXIMATELY 12"
APART.
4'
12"
BERM
12"
SPACE SPIKES AT APPROX. 12" OC
(TOP, BOTTOM, AND BOTH SIDES)
SL
O
PE
V
AR
IE
S
SE
E
G R
AD
IN
G P
LA
N
NOTES:
1. SEED & FERTILIZE WITH USFS - APPROVED MIX PRIOR TO PLACING EROSION CONTROL CONTROL
BLANKET.
2. MATERIAL:
SLOPES…