This is a Project Manual for a state and local contract opportunity issued by the State of California Department of General Services Real Estate Services Division, in conjunction with the California Department of Forestry and Fire Protection (CALFire), for Phase V Communication Facilities Replacement across three sites in Humboldt and Shasta Counties. The project encompasses the replacement of communication facilities at Pratt Mountain (Project 1512A), Bunchgrass Mountain (Project 1512B), and Mt. Pierce (Project 1512E). The scope of work includes demolition of existing structures, construction of new 120-foot-tall telecommunications towers with 28-foot lightning masts, vault structures, generator installations, propane tank placement, and comprehensive electrical, mechanical, and structural systems. The project manual contains five books organized by procurement and contracting requirements, site-specific construction documents for each mountain location, and appendices including geotechnical investigations, environmental commitment tables, and tower equipment specifications. Courtney Wetsell serves as the Project Director (279.799.4650), with GHD Inc. as the consultant, represented by Project Manager Matt Weber (916-296-3222).
The manual establishes detailed bidding and contracting procedures including invitation for bids, instructions to bidders, bid forms, performance bonds, payment bonds, and general conditions of contract for construction. Specifications address site preparation, demolition, concrete work, masonry, structural steel, HVAC systems, plumbing, electrical systems including grounding and bonding requirements, and antenna installation across all three sites. Geotechnical investigations recommend shallow foundations with 3,000 psf allowable bearing capacity for dead loads and 4,500 psf for dead plus live loads, with alternative deep foundation options using pipe piles. Environmental compliance requirements include erosion and sedimentation control, storm water pollution prevention, and construction waste management. The project incorporates seismic design criteria with peak ground acceleration of 0.51 to 0.6 g based on ASCE 7-10 provisions, and includes provisions for DVBE participation and small business subcontractor requirements consistent with California state contracting standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATE OF CALIFORNIA DEPARTMENT OF GENERAL SERVICES
REAL ESTATE SERVICES DIVISION
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
PROJECT MANUAL – Book V of V:
INTRODUCTORY INFORMATION
APPENDICES
A. Geotechnical Investigations
1. Pratt Mountain
2. Bunchgrass Mountain
3. Mt. Pierce
B. Environmental Commitment Tables
1. Pratt Mountain
2. Bunchgrass Mountain
3. Mt. Pierce
C. Miscellaneous Tower Equipment Information
1. Antenna Testing and Analysis
2. Antenna Wrapping Procedure
3. Cal OES PSC and General Contractor Inspection & Acceptance Criteria
4. Grounding Requirements for Vault & Tower
5. Tower Install Coax - Waveguide
FOR:
PHASE V COMMUNICATION FACILITIES
REPLACEMENT – GROUP A:
1512A - PRATT MTN.
1512B - BUNCHGRASS MTN.
1512E - MT. PIERCE
CALIFORNIA DEPARTMENT OF FORESTRY AND
FIRE PROTECTION (CALFIRE)
HUMBOLDT & SHASTA COUNTIES, CALIFORNIA
Courtney Wetsell, Project Director Telephone Number 279.799.4650 West Sacramento, California
Consultants: GHD
8/14/2026 1512A, 1512B, 1512E
PROJECT TITLE PAGE
RESDMSTR: 02/03/2014v1 00 01 01 - 1 01512A, B, E
DOCUMENT 00 01 01
PROJECT TITLE PAGE
Title: REPLACE COMMUNICATION FACILITIES, PHASE V – GROUP A:
1. PRATT MOUNTAIN
2. BUNCHGRASS MOUNTAIN
3. MT. PIERCE
Client Agency: DEPARTMENT OF FORESTRY AND FIRE
PROTECTION (CALFIRE)
Location: PRATT MOUNTAIN/ BUNCHGRASS
MOUNTAIN/ MT.PIERCE
HUMBOLDT & SHASTA COUNTIES,
CALIFORNIA
Project Number: 1512A, 1512B, 1512E
Project Director: Courtney Wetsell State of California Department of General Services Real Estate Services Division Project Management and Development Branch 707 Third Street, 4th Floor West Sacramento, California 95605 Telephone Number: 279.799.
Email: Courtney.Wetsell@dgs.ca.gov
Consultant: GHD, Inc.
Matt Weber, Project Manager 943 Reserve Drive Roseville, CA 95678 Telephone Number: (916) 296-3222 Email: Matt.Weber@ghd.com
CERTIFICATIONS PAGE
RESDMSTR: 02/03/2014v1 00 01 05 - 1 001512A, B, E
DOCUMENT 00 01 05
CERTIFICATIONS PAGE
PROJECT TITLE:
1. PRATT MOUNTAIN
2. BUNCHGRASS MOUNTAIN
3. MT. PIERCE
CLIENT AGENCY :
LOCATION:
PROJECT NUMBER :
OWNER :
PROJECT DIRECTOR :
CONSULTANT
REPLACE COMMUNICATION FACILITIES, PHASE V –
GROUP A:
DEPARTMENT OF FORESTRY AND FIRE PROTECTION
(CALFIRE)
A - PRATT MOUNTAIN
(Coordinates: 41°29'56.58"N, 124° 3'36.30"W)
B - BUNCHGRASS MTN.
(Coordinates: 41°29'56.58"N, 124° 3'36.30"W)
E - MT. PIERCE
(Coordinates: 41°29'56.58"N, 124° 3'36.30"W)
HUMBOLDT & SHASTA COUNTIES, CALIFORNIA
1512A, 1512B, 1512E
STATE OF CALIFORNIA
Courtney Wetsell Department of General Services Project Management and Development Branch 707 Third Street, 4th Floor West Sacramento, California 95605 Telephone Number: 279.799.4650 Email: Courtney.Wetsell@dgs.ca.gov
GHD, Inc. Matt.Weber@ghd.com
RESDMSTR: 02/03/2014v1 00 01 05 - 2 001512A, B, E
REGULATORY REVIEWS:
RESDMSTR: 02/03/2014v1 00 01 05 - 3 001512A, B, E
See Site Books 2, 3, & 4 for site Specific Regulatory Stamps
See Site Books 2, 3, & 4 for site Specific Regulatory Stamps
DSA ACCESS COMPLIANCE SFM
TABLE OF CONTENTS
RESDMSTR: 6/20/2025 00 01 10 - 1 1512A, B, E
DOCUMENT 00 01 10
TABLE OF CONTENTS
PROCUREMENT AND CONTRACTING REQUIREMENTS GROUP
BOOK I
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
INTRODUCTORY INFORMATION
Pages Document 00 01 01 Project Title Page .......................................................................... 1 only 00 01 05 Certifications Page ........................................................................ 1 through 3 00 01 10 Table of Contents .......................................................................... 1 through 9 00 01 15 List of Drawings ............................................................................. 1 through 8
BIDDING REQUIREMENTS
Document 00 11 00 Invitation for Bids ........................................................................... 1 through 4 00 21 00 Instructions to Bidders ................................................................... 1 through 8 Appendix 00 21 00.01 Request for Bidding Interpretation ................................................. 1 only Document 00 22 00 Supplementary Instructions to Bidders .......................................... 1 only 00 22 10 DVBE Participation Program Requirements ................................... 1 through 3 00 41 00 Bid Form (Sample) ........................................................................ 1 through 10 00 43 13 Bidder’s Bond (Sample) ................................................................. 1 only 00 43 16 Certified Small Business Subcontractor(s) Summary (Sample) ..... 1 through 2 00 45 46 Payee Data Record (Sample) ........................................................ 1 through 2 00 91 13 Addendum (Sample)……………………………………………………1 through 3
CONTRACTING REQUIREMENTS
Document 00 52 00 Agreement (Sample) ..................................................................... 1 only 00 61 13 Performance Bond (Sample) ......................................................... 1 only 00 61 14 Payment Bond to Accompany Construction Contract (Sample) ..... 1 only 00 63 63 Construction Contract Change Order (Sample) ............................. 1 only 00 72 00 General Conditions of the Contract for Construction ...................... 1 through 31 00 73 00 Supplementary Conditions ............................................................. 1 through 13
SPECIFICATIONS GROUP
GENERAL REQUIREMENTS SUBGROUP
DIVISION 01 - GENERAL REQUIREMENTS
Section 01 10 00 Summary ....................................................................................... 1 through 8 01 21 00 Allowances .................................................................................... 1 through 2 01 25 00 Substitution Procedures ................................................................. 1 through 2
RESDMSTR: 6/20/2025 00 01 10 - 2 1512A, B, E
01 29 00 Payment Procedures ..................................................................... 1 through 4 01 31 00 Project Management and Coordination .......................................... 1 through 6 01 32 00 Construction Progress Documentation .......................................... 1 through 7 01 32 33 Photographic Documentation ........................................................ 1 through 3 01 33 00 Submittal Procedures .................................................................... 1 through 8 01 33 29.08 Buy Clean California Act Requirements ......................................... 1 through 2 01 40 00 Quality Requirements .................................................................... 1 through 6 01 50 00 Temporary Facilities and Controls ................................................. 1 through 7 01 56 39 Temporary Tree and Plant Protection ............................................ 1 through 5 01 57 23 Temporary Storm Water Pollution Control ..................................... 1 through 4 01 60 00 Product Requirements ................................................................... 1 through 5 01 64 00 Owner-furnished Products ............................................................. 1 through 3 01 73 00 Execution ...................................................................................... 1 through 7 01 74 19 Construction Waste Management and Disposal ............................ 1 through 5 Form 01 74 19.01 Construction Waste Estimate (A,B,& E) ......................................... 1 only 01 74 19.02 Waste Management Report (A, B & E) .......................................... 1 through 2 Section 01 74 20 Recycled Content Certification (A, B & E) ...................................... 1 through 3 Form 01 74 20.01 Recycled Content Certification Worksheet (Example) .................... 1 through 2 01 74 20.02 State Agency Buy Recycled Campaign Procurement Summary (Example) (A, B & E) ...................................................................................... 1 through 2 Section 01 75 00 Starting and Adjusting ................................................................... 1 through 3 01 77 00 Closeout Procedures ..................................................................... 1 through 12 Form STD 817 Prime Contractor’s Certifications – DVBE Subcontractor Report ... 1 through 5 01 77 00.01 Contractor’s Certification of Small Business Participation .............. 1 only 01 77 00.02 Contractor’ Certification of Small Business Participation ................ 1 only Section 01 79 00 Demonstration and Training .......................................................... 1 through 4
BOOK II - PRATT MTN.
DIVISION 02 – EXISTING CONDITIONS
Section 02 4000 Demolition ..................................................................................... 1 through 2 02 41 16 Groundwork for Structures ............................................................. 1 through 3
DIVISION 03 – CONCRETE
Section 03 10 00 Concrete Forming and Accessories ............................................... 1 through 5 03 20 00 Concrete Reinforcing ..................................................................... 1 through 3 03 30 00 Cast-In-Place Concrete ................................................................. 1 through 8
DIVISION 04 – MASONRY
Section 04 22 00 Concrete Unit Masonry .................................................................. 1 through 9
DIVISION 05 – METALS
Section 05 05 23 Metal Fastenings ........................................................................... 1 through 9 05 12 00 Structural Steel Framing ................................................................ 1 through 3 05 30 00 Metal Decking ................................................................................ 1 through 3 05 41 00 Steel Studs .................................................................................... 1 through 4
DIVISION 06 – WOOD, PLASTICS, AND COMPOSITES
RESDMSTR: 6/20/2025 00 01 10 - 3 1512A, B, E
Section 06 10 00 Rough Carpentry ........................................................................... 1 through 2
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
Section 07 21 00 Thermal Insulation ......................................................................... 1 through 2 07 92 00 Joint Sealants ................................................................................ 1 through 4
DIVISION 08 – OPENINGS
Section 08 11 13 Standard Hollow Metal Doors ........................................................ 1 through 2 08 12 13 Hollow Metal Frames ..................................................................... 1 through 2 08 71 00 Door Hardware .............................................................................. 1 through 3
DIVISION 09 – FINISHES
Section 09 20 00 Plaster and Gypsum Board ............................................................ 1 through 2 09 54 53 Fiberglass Reinforced Panel .......................................................... 1 through 2 09 67 16 Epoxy Flooring .............................................................................. 1 through 3 09 91 00 Painting ......................................................................................... 1 through 7
DIVISION 13 – SPECIAL CONSTRUCTION
Section 13 36 13.13 Self-Supporting Steel Communications Tower ............................... 1 through 8 13 50 00 Antennas ....................................................................................... 1 through 17
DIVISION 15 – RESERVED (NOT USED)
DIVISION 16 – RESERVED (NOT USED)
DIVISION 17 – RESERVED (NOT USED)
DIVISION 18 – RESERVED (NOT USED)
DIVISION 19 – RESERVED (NOT USED)
FACILITY SERVICES SUBGROUP
DIVISION 20 – RESERVED (NOT USED)
DIVISION 22 – PLUMBING
Section 22 00 00 Plumbing ....................................................................................... 1 through 15
DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
Section 23 00 00 Heating, Ventilating and Air Conditioning ....................................... 1 through 17 23 05 00 General Requirements for Mechanical Work ................................. 1 through 15
DIVISION 24 – RESERVED (NOT USED)
DIVISION 25 – INTEGRATED AUTOMATION (NOT USED)
DIVISION 26 – ELECTRICAL
RESDMSTR: 6/20/2025 00 01 10 - 4 1512A, B, E
Section 26 01 00 Basic Electrical Requirements ....................................................... 1 through 9 26 01 26 Electrical Testing ........................................................................... 1 through 9 26 05 19 Low-Voltage Power Conductors and Cables .................................. 1 through 10 26 05 26 Grounding and Bonding ................................................................. 1 through 16 26 05 29 Electrical Hangers and Supports ................................................... 1 through 5 26 05 33.13 Conduit .......................................................................................... 1 through 10 26 05 33.16 Electrical Boxes ............................................................................. 1 through 3 26 05 36 Interior Cable Tray ......................................................................... 1 through 3 26 05 43 Underground Ducts and Structures ............................................... 1 through 6 26 05 48 Seismic Restraint for Electrical Equipment .................................... 1 only 26 05 53 Electrical Identification ................................................................... 1 through 7 26 24 16 Panelboards .................................................................................. 1 through 8 26 27 26 Wiring Devices .............................................................................. 1 through 7 26 27 26.10 Miscellaneous Electrical Devices ................................................... 1 through 4 26 28 16 Overcurrent Protection Devices ..................................................... 1 through 7 26 32 13 Standby System Generator Set ..................................................... 1 through 14 26 36 23 Automatic Transfer Switches ......................................................... 1 through 10 26 51 13 Interior Lighting .............................................................................. 1 through 9
DIVISION 27 – COMMUNICATIONS
Section 27 53 19 Internal Cellular, Paging and Antenna Systems ............................. 1 only
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY (NOT USED)
DIVISION 29 – RESERVED (NOT USED)
SITE AND INFRASTRUCTURE SUBGROUP
DIVISION 30 – RESERVED (NOT USED)
DIVISION 31 – EARTHWORK
Section 31 01 50 Maintenance of Excavation Support and Protection ....................... 1 through 2 31 10 00 Site Preparation (Clearing and Grubbing) ...................................... 1 only 31 20 00 Earth Moving ................................................................................. 1 through 11 31 23 13 Subgrade Preparation ................................................................... 1 through 8 31 23 16.26 Rock Removal ............................................................................... 1 through 2 31 23 33 Trenching and Backfill ................................................................... 1 through 7 31 25 00 Erosion and Sedimentation Control ............................................... 1 through 5 31 25 13 Storm Water Pollution Prevention Plan .......................................... 1 through 2
DIVISION 32 – EXTERIOR IMPROVEMENTS
Section 32 11 23 Aggregate Base Courses ............................................................... 1 only 32 31 13 Chain Link Fence ........................................................................... 1 through 4
DIVISION 33 – UTILITIES (NOT USED)
DIVISION 34 – TRANSPORTATION (NOT USED)
RESDMSTR: 6/20/2025 00 01 10 - 5 1512A, B, E
DIVISION 35 – WATERWAY AND MARINE CONSTRUCTION (NOT USED)
DIVISION 36 – RESERVED (NOT USED)
DIVISION 37 – RESERVED (NOT USED)
DIVISION 38 – RESERVED (NOT USED)
DIVISION 39 – RESERVED (NOT USED)
PROCESS EQUIPMENT SUBGROUP (NOT USED)
BOOK III – BUNCHGRASS MTN
DIVISION 02 – EXISTING CONDITIONS
Section 02 40 00 Demolition ..................................................................................... 1 through 2 02 41 16 Groundwork for Structures ............................................................. 1 through 3
DIVISION 03 – CONCRETE
Section 03 10 00 Concrete Forming and Accessories ............................................... 1 through 5 03 20 00 Concrete Reinforcing ..................................................................... 1 through 3 03 30 00 Cast-In-Place Concrete ................................................................. 1 through 8
DIVISION 04 – MASONRY
Section 04 22 00 Concrete Masonry Unit .................................................................. 1 through 9
DIVISION 05 – METALS
Section 05 05 23 Metal Fastenings ........................................................................... 1 through 9 05 12 00 Structural Steel Framing ................................................................ 1 through 3 05 30 00 Metal Decking ................................................................................ 1 through 3 05 41 00 Steel Studs .................................................................................... 1 through 4
DIVISION 06 – WOOD
Section 06 10 00 Rough Carpentry ........................................................................... 1 through 2
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
Section 07 21 00 Thermal Insulation ......................................................................... 1 through 2 07 92 00 Joint Sealants ................................................................................ 1 through 4
DIVISION 08 – WINDOWS AND DOORS
Section 08 11 13.13 Standard Hollow Metal Doors ........................................................ 1 through 2 08 12 13 Hollow Metal Frames ..................................................................... 1 through 2 08 71 00 Door Hardware .............................................................................. 1 through 3
DIVISION 09 – FINISHES
Section 09 20 00 Plaster Gypsum Board................................................................... 1 through 2
RESDMSTR: 6/20/2025 00 01 10 - 6 1512A, B, E
09 54 53 Fiberglass Reinforced Panel .......................................................... 1 through 2 09 67 16 Epoxy Flooring .............................................................................. 1 through 3 09 91 00 Painting ......................................................................................... 1 through 7
DIVISION 13 – SPECIAL CONSTRUCTION
Section 13 36 13.13 Self-Supporting Steel Communications Tower ............................... 1 through 8 13 50 00 Antennas ....................................................................................... 1 through 17
DIVISION 22 – PLUMBING
Section 22 00 00 Plumbing ....................................................................................... 1 through 14
DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING
Section 23 00 00 Heating, Ventilating and Air Conditioning ....................................... 1 through 17 23 05 00 General Requirements for Mechanical Work ................................. 1 through 15
DIVISION 26 – ELECTRICAL
Section 26 01 00 Basic Electrical Requirements ....................................................... 1 through 9 26 01 26 Electrical Testing ........................................................................... 1 through 9 26 05 19 Low-Voltage Power Conductors and Cables .................................. 1 through 10 26 05 26 Grounding and Bonding ................................................................. 1 through 16 26 05 29 Electrical Hangers and Supports ................................................... 1 through 4 26 05 33.13 Conduit .......................................................................................... 1 through 10 26 05 33.16 Electrical Boxes ............................................................................. 1 through 3 26 05 36 Interior Cable Tray ......................................................................... 1 through 3 26 05 43 Underground Ducts and Structures ............................................... 1 through 6 26 05 48 Seismic Restraint for Electrical Equipment .................................... 1 only 26 05 53 Electrical Identification ................................................................... 1 through 7 26 24 16 Panelboards .................................................................................. 1 through 8 26 27 26 Wiring Devises .............................................................................. 1 through 7 26 27 26.10 Miscellaneous Electrical Devices ................................................... 1 through 4 26 28 16 Overcurrent Protection Devices ..................................................... 1 through 7 26 32 13 Stanby System Generator Set ....................................................... 1 through 15 26 36 23 Automatic Transfer Switches ......................................................... 1 through 10 26 51 13 Interior Lighting .............................................................................. 1 through 9
DIVISION 27 – COMMUNICATIONS
Section 27 53 19 Internal Cellular, Paging and Antenna Systems ............................. 1 only
DIVISION 31 – EARTHWORK
Section 31 01 50 Maintenance of Excavation Support and Protection ....................... 1 through 2 31 10 00 Site Preparation (Clearing and Grubbing) ...................................... 1 only 31 20 00 Earth Moving ................................................................................. 1 through 11 31 23 13 Subgrade Preparation ................................................................... 1 through 8 31 23 16.26 Rock Removal ............................................................................... 1 through 2 31 23 33 Trenching and Backfill ................................................................... 1 through 7 31 25 00 Erosion and Sedimentation Control ............................................... 1 through 5 31 25 13 Strom Water Pollution Prevention Plan .......................................... 1 through 2
RESDMSTR: 6/20/2025 00 01 10 - 7 1512A, B, E
DIVISION 32 – EXTERIOR IMPROVEMENTS
Section 32 11 23 Aggregate Base Courses ............................................................... 1 only 32 31 13 Chain Link Fence ........................................................................... 1 through 4
BOOK IV - MT. PIERCE
DIVISION 02 – EXISTING CONDITIONS
Section 02 40 00 Demolition ..................................................................................... 1 through 2 02 41 16 Groundwork for Structures ............................................................. 1 through 3
DIVISION 03 – CONCRETE
Section 03 10 00 Concrete Forming and Accessories ............................................... 1 through 5 03 20 00 Concrete Reinforcing ..................................................................... 1 through 3 03 30 00 Cast-In-Place Concrete ................................................................. 1 through 8
DIVISION 04 – MASONRY
Section 04 22 00 Concrete Masonry Units ................................................................ 1 through 9
DIVISION 05 – METALS
Section 05 05 23 Metal Fastenings ........................................................................... 1 through 9 05 12 00 Structural Steel Framing ................................................................ 1 through 3 05 30 00 Metal Decking ................................................................................ 1 through 3 05 41 00 Steel Studs .................................................................................... 1 through 4
DIVISION 06 – WOOD, PLASTICS AND COMPOSITES
Section 06 10 00 Rough Carpentry ........................................................................... 1 through 2
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
Section 07 21 00 Thermal Insulation ......................................................................... 1 through 2 07 92 00 Joint Sealants ................................................................................ 1 through 4
DIVISION 08 – OPENINGS
Section 08 11 13.13 Standard Hollow Metal Doors ........................................................ 1 through 2 08 12 13 Hollow Metal Frames ..................................................................... 1 through 2 08 71 00 Door Hardware .............................................................................. 1 through 3
DIVISION 9 – FINISHES
Section 09 20 00 Plaster Gypsum Board................................................................... 1 through 2 09 54 53 Fiberglass Reinforced Panel .......................................................... 1 through 2 09 67 16 Epoxy Flooring .............................................................................. 1 through 3 09 91 00 Painting ......................................................................................... 1 through 7
DIVISIOIN 13 – SPECIAL CONSTRUCTION
Section 13 36 13.13 Self-Supporting Steel Communications Tower ............................... 1 through 8
RESDMSTR: 6/20/2025 00 01 10 - 8 1512A, B, E
13 50 00 Antennas ....................................................................................... 1 through 18
DIVISION 22 – PLUMBING
Section 22 00 00 Plumbing ....................................................................................... 1 through 14
DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING
Section 23 00 00 Heating, Ventilating and Air Conditioning ....................................... 1 through 17 23 05 00 General Requirements for Mechanical Work ................................. 1 through 15
DIVISION 26 – ELECTRICAL
Section 26 01 00 Basic Electrical Requirements ....................................................... 1 through 9 26 01 26 Electrical Testing ........................................................................... 1 through 9 26 05 19 Low-Voltage Power Conductors and Cables .................................. 1 through 10 26 05 26 Grounding and Bonding ................................................................. 1 through 16 26 05 29 Electrical Hangers and Supports ................................................... 1 through 4 26 05 33.13 Conduit .......................................................................................... 1 through 10 26 05 33.16 Electrical Boxes ............................................................................. 1 through 3 26 05 36 Interior Cable Tray ......................................................................... 1 through 3 26 05 43 Underground Ducts and Structures ............................................... 1 through 6 26 05 48 Seismic Restraint for Electrical Equipment .................................... 1 only 26 05 53 Electrical Identification ................................................................... 1 through 7 26 24 16 Panelboards .................................................................................. 1 through 8 26 27 26 Wiring Devices .............................................................................. 1 through 7 26 27 26.10 Miscellaneous Electrical Devices ................................................... 1 through 4 26 28 16 Overcurrent Protection Devices ..................................................... 1 through 7 26 32 13 Standby System Generator Set ..................................................... 1 through 14 26 36 23 Automatic Transfer Switches ......................................................... 1 through 10 26 51 13 Interior Lighting .............................................................................. 1 through 9
DIVISION 27 – COMMUNICATIONS
Section 27 53 19 Internal Cellular, Paging and Antenna System ............................... 1 only
DIVISION 31 – EARTHWORK
Section 31 01 50 Maintenance of Excavation Support and Protection ....................... 1 through 2 31 10 00 Site Preparation (Clearing and Grubbing) ...................................... 1 only 31 20 00 Earth Moving ................................................................................. 1 through 11 31 23 13 Subgrade Preparation ................................................................... 1 through 8 31 23 16.26 Rock Removal ............................................................................... 1 through 2 31 23 33 Trenching and Backfill ................................................................... 1 through 7 31 25 00 Erosion and Sedimentation Control ............................................... 1 through 5 31 25 13 Strom Water Pollution Prevention Plan .......................................... 1 through 2
DIVISION 32 – EXTERIOR IMPROVEMENTS
Section 32 11 23 Aggregate Base Courses ............................................................... 1 only 32 31 13 Chain Link Fence ........................................................................... 1 through 4
RESDMSTR: 6/20/2025 00 01 10 - 9 1512A, B, E
BOOK V - APPENDICES
A. Geotechnical Investigations:
A Pratt Final Geotechnical
Investigation 1 through 37
B Bunchgrass Final Geotechnical Investigation
1 through 39
E Pierce Final Geotechnical Investigation
1 through 52
B. Environmental Commitment Tables
A Pratt EC Table 1 through 6 B Bunchgrass EC Table 1 through 6 E Mt. Pierce EC Table 1 through 5
C. Miscellaneous Tower Equipment Information
1 Antenna Testing &
Analysis 1 through 11
2 Antenna Wrapping Procedure
1 through 5
3 Cal OES PSC & General Contractor Inspection and Acceptance Criteria
1 through 4
4 Grounding Requirement for Vault and Tower
1 through 13
5 Tower Install Coax - Waveguide
1 through 3
END OF DOCUMENT
LIST OF DRAWINGS
RESDMSTR: 02/03/2014 00 01 15 - 1 01512A, B, E
DOCUMENT 00 01 15
PRATT MTN. – INCREMENT 1
Sheet Number Description
GENERAL
PM -G001 COVER SHEET
PM -G002 DRAWING INDEX, DESIGN CRITERIA AND SITE ORIENTATION
PM -G003 ABBREVIATIONS AND SYMBOLS
CIVIL
PM -C101 EXISTING SITE DEMOLITION AND CONSTRUCTION
SEQUENCING PLAN
PM -C102 SITE AND GRADING PLAN
PM -C501 CIVIL SECTIONS AND DETAILS
PM-C502 COMMON SITE DETAILS
ARCHITECTURAL
PM -A101 VAULT FLOOR PLAN, ROOF PLAN AND BUILDING
ELEVATIONS
PM -A102 GENERATOR VAULT PLANS, ELEVATIONS AND SECTION
PM -A501 ARCHITECTURAL DETAILS
PM -A502 ARCHITECTURAL DETAILS
STRUCTURAL
PM -S001 STRUCTURAL NOTES
PM -S101 VAULT FOUNDATION AND ROOF FRAMING PLAN AND
SECTION
PM -S102 TOWER FOUNDATION PLAN AND ELEVATION
PM -S501 COMMON STRUCTURAL DETAILS
PM -S502 STRUCTURAL DETAILS
PM -S503 STRUCTURAL DETAILS
PM -S701 FEEDLINE BRIDGE
PM -S702 FEEDLINE BRIDGE
MECHANICAL
PM -M001 MECHANICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND
GENERAL NOTES
PM -M101 LARGE VAULT – HVAC
PM -M102 GENERATOR VAULT – HVAC
PM -M501 MECHANICAL DETAILS
PM -M601 MECHANICAL SCHEDULES
RESDMSTR: 02/03/2014 00 01 15 - 2 01512A, B, E
ELECTRICAL
PM -E001 ELECTRICAL SYMBOLS LEGEND, ABBREVIATIONS AND
GENERAL NOTES
PM -E101 ELECTRICAL SITE PLAN
PM -E102 LARGE VAULT – LIGHTING, POWER, EQUIPMENT AND
GROUNDING
PM -E103 GENERATOR VAULT LIGHTING, POWER, EQUIPMENT AND
GROUNDING
PM -E104 LARGE VAULT INTERIOR ELEVATIONS – 1
PM -E105 LARGE VAULT INTERIOR ELECATIONS – 2
PM -E501 ELECTRICAL DETAILS – 1
PM -E502 ELECTRICAL DETAILS – 2
PM -E503 ELECTRICAL DETAILS – 3
PM -E504 ELECTRICAL DETAILS – 4
PM -E505 ELECTRICAL DETAILS – 5
PM -E506 ELECTRICAL DETAILS – 6
PM -E601 SINGLE LINE DIAGRAM AND LOAD CALCULATION
PM -E602 ELECTRICAL SCHEDULES – 1
PM -E603 ELECTRICAL SCHEDULES – 2
PM -E604 ALARM STATUS REPORTING SCHEMATICS
PM -E605 ALARM POINT DESCRIPTIONS
PM -E606 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 1
PM -E607 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 2
PM -E608 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 3
PM -E609 SITE ANTENNA LAYOUT AND PRESSURIZATION
EQUIPMENT – 1
PM -E610 SITE ANTENNA LAYOUT AND PRESSURIZATION
EQUIPMENT – 2
PM-E611 -48VDC CRIS OES INTERCONNECT DIAGRAM
PM-E612 -48VDC MW OES INTERCONNECT DIAGRAM
PM-E613 +12VDC OES INTERCONNECT DIAGRAM
TOWER STRUCTURAL DRAWINGS
T-1 COVER SHEET & DRAWING INDEX
S-1 ELEVATION VIEW/NOTES
S-1.1 SST SECTION ALLOWABLE MEMBER FORCES
S-1.2 MONOPOLE SECTIONS ALLOWABLE FORCES
S-2 UPPER POLE
S-3 LOWER POLE
S-4 TOWER SECTION 13V - NESTED POLE
RESDMSTR: 02/03/2014 00 01 15 - 3 01512A, B, E
S-5 TOWER SECTION 13V
S-6 TOWER SECTION 15ST
S-6.1 TOWER SECTION 15ST CONT.
S-7 TOWER SECTION 17ST
S-7.1 TOWER SECTION 17ST CONT.
S-8 TOWER SECTION 19ST
S-9 TYPICAL GRATING/BRACING
S-10 TYPICAL HANDRAIL/DIAGONAL PIPE LIGHTING ROD
EXTENTSION, & SAFETY CLIMB KITS
S-11 CENTER MAST
S-12 COAX CAGE / CLIMBING LADDER, ANTI-CLIMB, & BUS BAR
S-13 ANTENNA LOCATION ELEVATION VIEWS
S-13.1 ANTENNA LOCATION PLAN VIEWS
S-14 FULLY LOADED FACE MOUNTED MICROWAVES
S-14.1 FULLY LOADED LEG MOUNTED MICROWAVES
S-14.2 FULLY LOADED VHF/UHF ANTENNA LOCATIONS
S-15 MW ICE BRIDGE DETAILS
S-15.1 MW ANTENNA ICE SHIELD DETAILS
S-16 MICROWAVE MOUNT KITS
S-17 UHF / VHF ANTENNA MOUNT KITS
S-18 LEG – ELEVATION ID PLATES
S-19 TOWER FOUNDATION SLAB/PIERS
RADIO AND MICROWAVE ANTENNA MOUNTING BRACKETS DRAWINGS
CO-TA1 COVER SHEET AND INDEX
CO-TA1.1 DSA 103
CO-TA2 TOWER STRUCTURAL NOTES
CO-TA3 SITE PRO BRACKET DETAILS
CO-TA5.2 TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL)
CO-TA6 TOWER ANTENNA MOUNTING DETAILS
(ANDREW/COMMSCOPE)
CO-TA7.2 TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
CO-TA9 TOWER ANTENNA MOUNTING DETAILS (M2/KRECO)
CO-TA10 TOWER ANTENNA MOUNTING DETAILS
(COMMSCOPE/RFS/SINCLAIR)
CO-TA12 TOWER ANTENNA MOUNTING DETAILS (SCALA)
CO-TA18.1 TOWER ANTENNA MOUNTING DETAILS (TELEWAVE)
BUNCHGRASS MTN. – INCREMENT 2
GENERAL
BG-G001 COVER SHEET
BG-G002 DRAWING INDEX, DESIGN CRITERIA AND SITE ORIENTATION
BG-G003 ABBREVIATIONS AND SYMBOLS
CIVIL
BG-C101 EXISTING SITE DEMOLITION AND CONSTRUCTION
RESDMSTR: 02/03/2014 00 01 15 - 4 01512A, B, E
SEQUENCING PLAN
BG-C102 SITE AND GRADING PLAN
BG-C501 COMMON SITE DETAILS
BG-C502 COMMON SITE DETAILS
ARCHITECTURAL
BG-A101 VAULT FLOOR PLAN AND ROOF PLAN AND BUILDING
ELEVATIONS
BG-A501 ARCHITECTURAL DETAILS
BG-A502 ARCHITECTURAL DETAILS
STRUCTURAL
BG-S001 STRUCTURAL NOTES
BG-S101 VAULT FOUNDATION, ROOF FRAMING PLAN AND
SECTION
BG-S102 TOWER FOUNDATION PLAN AND ELEVATION
BG-S501 COMMON STRUCTURAL DETAILS
BG-S502 STRUCTURAL DETAILS
BG-S503 STRUCTURAL DETAILS
BG-S701 FEEDLINE BRIDGE
BG-S702 FEEDLINE BRIDGE
MECHANICAL
BG-M001 MECHANICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND
GENERAL NOTES
BG-M101 MEDIUM VAULT – HVAC
BG-M501 MECHANICAL DETAILS
BG-M601 MECHANICAL SCHEDULES
ELECTRICAL
BG-E001 ELECTRICAL SYMBOLS LEGEND, ABBREVIATIONS AND
GENERAL NOTES
BG-E101 ELECTRICAL SITE PLAN
BG-E102 MEDIUM VAULT – LIGHTING, POWER, EQUIPMENT AND
GROUNDING
BG-E103 MEDIUM VAULT INTERIOR ELEVATIONS
BG-E501 ELECTRICAL DETAILS – 1
BG-E502 ELECTRICAL DETAILS – 2
BG-E503 ELECTRICAL DETAILS – 3
BG-E504 ELECTRICAL DETAILS – 4
BG-E505 ELECTRICAL DETAILS – 5
BG-E506 ELECTRICAL DETAILS – 6
BG-E601 SINGLE LINE DIAGRAM AND LOAD CALCULATION
BG-E602 ELECTRICAL SCHEDULES – 1
BG-E603 ELECTRICAL SCHEDULES – 2
BG-E604 ALARM STATUS REPORTING SCHEMATICS
BG-E605 ALARM POINT DESCRIPTIONS
BG-E606 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 1
RESDMSTR: 02/03/2014 00 01 15 - 5 01512A, B, E
BG-E607 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 2
BG-E608 SITE ANTENNA LAYOUT AND PRESSURIZATION
EQUIPMENT – 1
BG-E609 SITE ANTENNA LAYOUT AND PRESSURIZATION
EQUIPMENT – 2
BG-E610 -48VDC CRIS OES INTERCONNECT DIAGRAM
BG-E611 -48VDC MW OES INTERCONNECT DIAGRAM
BG-E612 +12VDC OES INTERCONNECT DIAGRAM
WESTERN UTILITY TELECOM, INC. DRAWING INDEX
T-1 COVER SHEET & DRAWING INDEX
S-1 ELEVATION VIEW/NOTES
S-1.1 SST SECTION ALLOWABLE MEMBER FORCES
S-1.2 MONOPOLE SECTION ALLOWABLE MEMBER FORCES
S-2 UPPER POLE
S-3 LOWER POLE
S-4 TOWER SECTION 13V NESTED POLE
S-5 TOWER SECTION 13V
S-6 TOWER SECTION 15ST
S-6.1 TOWER SECTION 15ST CONT.
S-7 TOWER SECTION 17ST
S-7.1 TOWER SECTION 17ST CONT.
S-8 TOWER SECTION 19ST
S-9 TYPICAL GRATING/BRACING
S-10 TYPICAL HAND RAIL/DIAGNOL PIPE LIGHTING ROD
EXTENSION, SAFETY & SAFETYCLIMB KITS
S-11 CENTER MAST
S-12 COAX CAGE/CLIMBING LADDER, ANTI-CLIMB, & BUS BAR
S-13 ANTENNA LOCATION ELEVATION VIEWS
S-13.1 ANTENNA LOCATION PLAN VIEWS
S-14 FULLY LOADED FACE MOUNTED MICROWAVES
S-14.1 FULLY LOADED LEG MOUNTED MICROWAVES
S-14.2 FULLY LOADED VHF/UHF ANTENNA LOCATIONS
S-15 MW ICE BRIDGE DETAILS
S-15.1 MW ANTENNA ICE SHIELD DETAILS
S-16 MICROWAVE MOUNT KITS
S-17 UHF/VHF ANTENNA MOUNT KITS
S-18 LEG/ELEVATION ID PLATES
S-19 TOWER FOUNDATION SLAB/PIERS
SATE OF CALIFORNIA
CO-TA1 COVER SHEET AND INDEX
CO-TA1.1 DSA 103
CO-TA2 TOWER STRUCTURAL NOTES
CO-TA3 SITE PRO BRACKET DETAILS
CO-TA5.2 TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL)
CO-TA6 TOWER ANTENNA MOUNTING DETAILS
(ANDREW/COMMSCOPE)
CO-TA7.2 TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
RESDMSTR: 02/03/2014 00 01 15 - 6 01512A, B, E
CO-TA9 TOWER ANTENNA MOUNTING DETAILS (M2/KRECO)
CO-TA10 TOWER ANTENNA MOUNTING DETAILS
(COMMSCOPE/RFS/SINCLAIR)
CO-TA10.1 TOWER ANTENNA MOUNTING DETAILS (RFS/SINCLAIR)
CO-TA14.1 TOWER ANTENNA MOUNTING DETAILS (SCALA)
CO-TA18 TOWER ANTENNA MOUNTING DETAILS (TELEWAVE)
MT. PIERCE – INCREMENT 3
GENERAL
MP-G001 COVER SHEET
MP-G002 DRAWING INDEX, DESIGN CRITERIA AND SITE ORIENTATION
MP-G003 ABBREVIATIONS AND SYMBOLS
CIVIL
MP-C101 EXISTING SITE DEMOLITION AND CONSTRUCTION
SEQUENCING
MP-C102 SITE AND GRADING PLAN
MP-C501 CIVIL SECTIONS AND DETAILS
MP-C502 COMMON SITE DETAILS
ARCHITECTURAL
MP-A101 VAULT FLOOR PLAN, ROOF PLAN AND BUILDING
ELEVATIONS
MP-A102 GENERATOR VAULT PLANS, ELEVATIONS AND SECTION
MP-A501 ARCHITECTURAL DETAILS
MP-A502 ARCHITECTURAL DETAILS
CIVIL
MP-S001 STRUCTURAL NOTES
MP-S101 VAULT FOUNDATION AND ROOF FRAMING PLAN AND
SECTION
MP-S102 TOWER FOUNDATION PLAN AND ELEVATION
MP-S501 COMMON STRUCTURAL DETAILS
MP-S502 STRUCTURAL DETAILS
MP-S503 STRUCTURAL DETAILS
MP-S701 FEEDLINE BRIDGE
MP-S702 FEEDLINE BRIDGE
MECHANICAL
MP-M001 MECHANICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND
GENERAL NOTES
MP-M101 LARGE VAULT – HVAC
MP-M102 GENERATOR VAULT – HVAC
RESDMSTR: 02/03/2014 00 01 15 - 7 01512A, B, E
MP-M501 MECHANICAL DETAILS
MP-M601 MECHANICAL SCHEDULES
ELECTRICAL
MP-E001 ELECTRICAL SYMBOLS LEGEND, ABBREVIATIONS AND
GENERAL NOTES
MP-E101 ELECTRICAL SITE PLAN
MP-E102 LARGE VAULT – LIGHTING, POWER, EQUIPMENT AND
GROUNDING
MP-E103 GENERATOR VAULT – LIGHTING, POWER, EQUIPMENT AND
GROUNDING
MP-E104 LARGE VAULT – INTERIOR ELEVATIONS – 1
MP-E105 LARGE VAULT – INTERIOR ELEVATIONS – 2
MP-E501 ELECTRICAL DETAILS – 1
MP-E502 ELECTRICAL DETAILS – 2
MP-E503 ELECTRICAL DETAILS – 3
MP-E504 ELECTRICAL DETAILS – 4
MP-E505 ELECTRICAL DETAILS – 5
MP-E506 ELECTRICAL DETAILS – 6
MP-E601 SINGLE LINE DIAGRAM AND LOAD CALCULATION
MP-E602 ELECTRICAL SCHEDULES – 1
MP-E603 ELECTRICAL SCHEDULES – 2
MP-E604 ALARM STATUS REPORTING SCHEMATICS
MP-E605 ALARM POINT DESCRIPTIONS
MP-E606 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 1
MP-E607 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 2
MP-E608 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 3
MP-E609 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 4
MP-E610 INTERCONNECT DIAGRAM VHF ANTENNAS AND RF
CABLING – 5
MP-E611 SITE ANTENNA LAYOUT AND PRESSURIZATION
EQUIPMENT – 1
MP-E612 SITE ANTENNA LAYOUT AND PRESSURIZATION
EQUIPMENT – 2
PM-E613 -48VDC CRIS OES INTERCONNECT DIAGRAM
PM-E614 -48VDC MW OES INTERCONNECT DIAGRAM
PM-E615 +12VDC OES INTERCONNECT DIAGRAM
TOWER STRUCTURAL SHEETS
T-1 COVER SHEET/DRAWING INDEX
S-1 ELEVATION VIEW/NOTES
S-1.1 SST SECTION ALLOWABLE MEMBER FORCES
S-1.2 MONOPOLE SECTION ALLOWABLE MEMBER FORCES
S-2 UPPER POLE
S-3 LOWER POLE
S-4 TOWER SECTION 13V – NESTED POLE
RESDMSTR: 02/03/2014 00 01 15 - 8 01512A, B, E
S-5 TOWER SECTION 13V
S-6 TOWER SECTION 15ST
S-6.1 TOWER SECTION 15ST CONT.
S-7 TOWER SECTION 17ST
S-7.1 TOWER SECTION 17ST CONT.
S-8 TOWER SECTION 19ST
S-9 TYPICAL GRATING/BRACING
S-10 TYPICAL HAND RAIL/DIAGANOL PIPE, LIGHTING ROD
EXTENSION, & SAFETY CLIMB KITS
S-11 CENTER MAST
S-12 COAX CAGE/CLIMBING LADDER, ANTI-CLIMB, & BUS BAR
S-13 ANETNNA LOCATION ELEVATION VIEWS
S-13.1 ANTENNA LOCATION PLAN VIEWS
S-14 FULLY LOADED FACE MOUNTED MICROWAVES
S-14.1 FULLY LOADED LEG MOUNTED MICROWAVES
S-14.2 FULLY LOADED VHF/UHF ANTENNA LOCATIONS
S-15 MW ICE BRIDGE DETAILS
S-15.1 MW ANTENNA ICE SHIELD DETAILS
S-16 MICROWAVE MOUNT KITS
S-17 UHF/VHF ANTENNA MOUNT KITS
S-18 LEG/ELEVATION ID PLATES
S-19 TOWER FOUNDATION SLAB/PIERS
STRUCTURAL DETAILS FOR RADIO AND MICROWAVE ANTENNA MOUNTING
BRACKETS
CO-TA1 COVER SHEET AND INDEX
CO-TA1.1 DSA 103
CO-TA2 TOWER STRUCTURAL NOTES
CO-TA3 SITE PRO BRACKET DETAILS
CO-TA4 TOWER ANTENNA MOUNTING DETAILS (ANDREW)
CO-TA5.2 TOWER ANTENNA MOUNTING DETAILS (AMPHENOL ANTEL)
CO-TA6 TOWER ANTENNA MOUNTING DETAILS
(ANDREW/COMMSCOPE)
CO-TA6.1 TOWER ANTENNA MOUNTING DETAILS
(ANDREW/COMMSCOPE)
CO-TA7 TOWER ANTENNA MOUNTING DETAILS (HUSTLER/ANTENNA
EXPERT/DIAMOND)
CO-TA7.2 TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
CO-TA9 TOWER ANTENNA MOUNTING DETAILS (M2/KRECO)
CO-TA10 TOWER ANTENNA MOUNTING DETAILS
(COMMSCOPE/RFS/SINCLAIR)
CO-TA11.2 TOWER ANTENNA MOUNTING DETAILS (DB SPECTRA/SCALA)
CO-TA13 TOWER ANTENNA MOUNTING DETAILS (SCALA)
CO-TA14 TOWER ANTENNA MOUNTING DETAILS (SCALA)
CO-TA14.1 TOWER ANTENNA MOUNTING DETAILS (SCALA)
CO-TA15 TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
CO-TA17 TOWER ANTENNA MOUNTING DETAILS (SINCLAIR)
CO-TA18 TOWER ANTENNA MOUNTING DETAILS (TELEWAVE)
END OF DOCUMENT
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Appendix A – Geotechnical Investigations
A. Geotechnical Investigations
1. Pratt Mountain
2. Bunchgrass Mountain
3. Mt. Pierce
FOR:
PHASE V COMMUNICATION FACILITIES
REPLACEMENT – GROUP A:
1512A - PRATT MTN.
1512B - BUNCHGRASS MTN.
1512E - MT. PIERCE
CALIFORNIA DEPARTMENT OF FORESTRY AND
FIRE PROTECTION
HUMBOLDT & SHASTA COUNTIES, CALIFORNIA
Courtney Wetsell, Project Director Telephone Number 279.799.4650 West Sacramento, California
8/14/2026 1512A, 1512B, 1512E
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Geotechnical Investigation - A.1
1. Pratt Mountain
FOR:
PHASE V COMMUNICATION FACILITIES
REPLACEMENT – GROUP A:
1512A - PRATT MTN.
CALIFORNIA DEPARTMENT OF FORESTRY AND
FIRE PROTECTION
HUMBOLDT & SHASTA COUNTIES, CALIFORNIA
Courtney Wetsell, Project Director Telephone Number 279.799.4650 West Sacramento, California
8/14/2026 1512A
Geotechnical Investigation Pratt Mountain Telecommunications Replacement Humboldt County, CA
Department of General Services
11136839.70 July 2019
GHD | Geotechnical Investigation | 11136839.70 | Page i
July 8, 2019
Aubree French Department of General Services, Real Estate Services Division Project Management and Development Branch 707 Third Street, 4th Floor Sacramento, California 95605
RE: Geotechnical Investigation, Pratt Mountain Telecommunications Replacement Humboldt County, California
Dear Ms. French, GHD Inc (GHD) is pleased to present the attached report containing the results of our geotechnical investigation for the proposed Calfire Phase V Telecommunications Replacement project at Pratt Mountain in Humboldt County, California. It is our understanding that improvements are planned for the site that include a new 120-foot-tall tower with a 28-foot lightning mast, vault structure, generator and propane tank.
The accompanying report presents our findings, conclusions, and recommendations developed from our geotechnical investigation. Contained in the report are geotechnical design criteria and recommendations for design and construction of the proposed improvements. The results of the subsurface exploration and laboratory testing programs, which form the basis of our recommendations, are also included in the report.
On the basis of our investigation, the site is suitable, from a geotechnical perspective, to receive the planned improvements provided the recommendations presented in the report are incorporated into the design and construction of the project.
If you have any questions regarding the information contained in this report, or if we may be of further assistance, please do not hesitate to contact us.
Sincerely, GHD Inc
Eric S. Smith, P.E. Christopher D. Trumbull, P.E., G.E., DG.E Project Engineer Senior Geotechnical Engineer
GHD | Geotechnical Investigation | 11136839.70 | Page ii
Table of Contents
1. Introduction
1.1 Project Description
1.2 Purpose and Scope of Work
2. Field Exploration and Laboratory Testing
2.1 Field Exploration
2.2 Seismic Refraction
2.3 Geotechnical Laboratory Testing
3. Geologic and Subsurface Conditions
3.1 Site Conditions
3.2 General Geology and Faulting
3.2.1 Geologic Setting
3.2.2 Nearest Faulting
3.3 Subsurface Conditions
4. Conclusions
4.1 Excavatability
4.2 Ground Shaking
4.3 Corrosion
4.3.1 Corrosion Potential for Ferrous Pipes
4.3.2 Corrosion Potential for Reinforced Concrete
4.3.3 Summary of Results
4.4 Expansion Potential
4.5 Liquefaction
5. Recommendations
5.1 Earthwork
5.1.1 Excavatability
5.1.2 Site Preparation
5.1.3 General Subgrade Preparation
5.1.4 Engineered Fill
5.1.5 Compaction
5.1.6 Trench Backfill and Pipe Bedding
5.1.7 Temporary Slopes/Shoring
5.2 Foundations
5.2.1 Shallow Foundations
5.3 Deep Foundations
5.3.2 Foundation Excavation Observation
5.4 Seismic Design
GHD | Geotechnical Investigation | 11136839.70 | Page iii
5.5 Surface Drainage and Erosion Control
5.6 Access Road Recommendations
5.7 Plan Review and Construction Observation
6. References
7. Limitations
Figure Index
Figure 5.1 Allowable Pile Capacity
Table Index
Table 4.1 Soil Corrosion Results
Table 5.1 Import Fill Specifications
Table 5.2 LPILE Material Parameters
Table 5.3 Seismic Design Criteria
Table 5.4 Aggregate Surface Thickness Recommendations
Appendix Index Appendix A Figures
Appendix B Logs of Borings
Appendix C Seismic Refraction
Appendix D Geotechnical Laboratory Test Results
GHD | Geotechnical Investigation | 11136839.70 | Page iv
Distribution
To: Department of General Services
Aubree French
707 Third Street, 4th Floor
West Sacramento, CA 95605
From: GHD
Christopher Trumbull, P.E., G.E., D.GE
Eric Smith, P.E.
4080 Plaza Goldorado Circle, Suite B
Cameron Park, CA 95682
GHD | Geotechnical Investigation | 11136839.70 | Page 1
1. Introduction
This report presents the findings, conclusions, and recommendations developed from a geotechnical engineering investigation for the Calfire Phase V Telecommunications Replacement Project at Pratt Mountain. The investigation was conducted in accordance with Agreement Number 2130 between GHD, Inc. (GHD) and the Department of General Services, RESD, Project Management & Development Branch, dated October 24, 2017. A geologic hazards report, under separate cover, was also prepared for this site.
1.1 Project Description
Pratt Mountain Telecommunications Tower is located in Humboldt County east of Garberville, California, as shown on Figure A-1, Vicinity Map (40.119 latitude, -123.693 longitude). The site is along the north coast backbone of Calfire facilities and serves as the only microwave path to the Humboldt-Del Norte Unit Local Net, used to dispatch three fire stations and one inmate camp.
Failure at the site would impair emergency response to structure fires, traffic accidents, hazardous material spills, and wildfires in the service area.
To maintain these existing services, a 80-foot-tall, 22-foot-wide (at base) tower is proposed at the site in addition to a new generator, propane tank, and vault structure. The tower will also include a 28-foot-tall lightning mast. The vault structure will be supported on continuous strip footing, and the tower will be supported on a large mat foundation or a combination of mat and pile foundation system. The layout of the proposed features is shown on Figure A-2, Exploration Map.
1.2 Purpose and Scope of Work
The purpose of this study was to evaluate the suitability of the project site, from a geotechnical perspective, for the proposed improvements. The main objectives of the investigation were to characterize the subsurface materials, perform engineering analyses, develop geotechnical recommendations and criteria, and document our findings, conclusions, and recommendations in this report.
The scope of the geotechnical investigation included the following tasks:
• A review of published geologic and geotechnical material pertaining to the site vicinity
• A field exploration program consisting of three exploratory borings drilled to a maximum depth of approximately 35 feet below ground surface (bgs) and one seismic refraction line within the site to characterize the subsurface conditions
• Geotechnical laboratory testing on select soil samples collected from the borings
• Engineering analyses to develop geotechnical design criteria and recommendations for the proposed project
• Preparation of this report
GHD | Geotechnical Investigation | 11136839.70 | Page 2
2. Field Exploration and Laboratory Testing
2.1 Field Exploration
Three borings were drilled between June 27 and August 10, 2018 at the approximate locations shown on Figure A-2. The borings were located in the field based on measured distances from existing features and aerial maps. The borings were drilled to a maximum depth of approximately 35 feet bgs under the supervision of GHD technical personnel utilizing truck- and track-mounted CME-55 drill rigs equipped with an automatic hammer with a weight of 140 pounds and a drop of 30 inches. Coring was started at a depth of 21½ feet bgs on Boring B-1.
The number of blows required for each 6-inch increment of drive were recorded and the cumulative blow count for the 12 inches of drive (following the first 6 inches of “seating” drive), or fraction thereof where resistance was encountered, is presented in the logs of borings. The blow counts presented in the logs are uncorrected and shown as they were recorded in the field. Both the samples and drill cuttings were visually classified in the field based on the Unified Soil Classification System (USCS) in general accordance with ASTM D2488.
The standardized N60 value is also presented and is calculated based on field blow counts and coefficients for hammer energy correction to normalize the automatic hammer blow count to the energy of the original SPT rope and cathead hammer (approximately 60%), borehole diameter to normalize the blow count for the diameter of the borehole, sampler type to account for the type of sampler and the presence of liners, and rod length to normalize the blow count to a standard length of 33 feet.
Subsurface conditions encountered are summarized in Section 3.3. Logs of the borings were prepared based on the field logging, visual examination of the soil samples, and the…