This solicitation is for a combined underground utilities and storm water improvements project at Moore Air Base in Edinburg, Texas. The solicitation was issued by the Department of Agriculture Animal and Plant Health Inspection Service Marketing and Regulatory Programs Business Services. The project involves installing new underground electrical cabling and equipment as part of Phase 2 of the work. Bidders should disregard any references in the design drawings or specifications related to future work or Add Alternate 1B, as those aspects are not included in this project scope. The response due date and anticipated award date are not provided in the document.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M
O
O
R
E
F
I E
L D
R
C
O
U
N
T
Y
A
C
O
U
N
Y
MOORE AIR BASE
PROJECT
LOCATION
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
PHASE 2 ELECTRICAL CABLING AND EQUIPMENT DESIGN
EDINBURG, TEXAS
27100.26
MAY 09, 2022
DL MORITZ
EE LEAF
05-09-2022
116530
ERNEST E. LEAF
COVER SHEET
GG01 0
AS NOTED
DL MORITZ
BW DEEN
NM BROWN
NORTH
USDA-APHIS-PPQ
MOORE AIR BASE
PHASE 2 ELECTRICAL CABLING & EQUIPMENT DESIGN
EDINBURG, TEXAS
USDA CONTRACT NO: AG-6395-C-16-0119
PROJECT LOCATION PLAN
PROJECT LOCATION MAP
HORIZONTAL DATUM TEXAS STATE PLANE SOUTH US FOOT
VERTICAL DATUM (NAVD 88)
REGIONAL LOCATION PLAN
FOR REFERENCE ONLY
SHEET NO. SHEET TITLE REV NO.
GG01 COVER SHEET 0
GG02 INDEX SHEET 1
ELECTRICAL SHEETS
EO121D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TGH" - DEMO 0
EO121D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TGH" - NEW 0
EO122D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6021" - DEMO 0
EO122 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6021" - NEW 0
EP122 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6021" 0
EO123D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6017" - DEMO 0
EO123D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6017" - NEW 0
EP123 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6017" - SHT 1 0
EP123A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6017" - SHT 2 0
EO124D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6101" - DEMO 0
EO124D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6101" - NEW 0
EP124 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6205" - SHT 1 0
EP125 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6205" - SHT 1 0
EP125A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6205" - SHT 2 0
EO126D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TEWT" - DEMO 0
EO126D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TEWT" - NEW 0
EP126 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "TEWT" 0
EO127D ELECTRICAL - ONE-LINE DIAGRAM - XFER "T6415" & BLDG 6416 - DEMO 0
EO127 ELECTRICAL - ONE-LINE DIAGRAM - XFER "T6415" & BLDG 6416 - NEW 0
EP127 ELECTRICAL - ENLARGED SITE PLAN - XFER "T6415" & BLDG 6416 - SHT 1 0
EP127A ELECTRICAL - ENLARGED SITE PLAN - XFER "T6415" & BLDG 6416 - SHT 2 0
EP128 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6403" - SHT 1 0
EP128A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6403' - SHT 2 0
EO129D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6409" - DEMO 1
EO129 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6409" - NEW 1
EP129 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6409" 1
EP130 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6411" 0
EP131 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6414" 0
EP132 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6418" 0
EO133D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6407" - DEMO 0
EO133 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6407" - NEW 0
EP133 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6407" 0
EO134D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6420" - DEMO 0
EO134 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6420" - NEW 0
EP134 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6420" 0
EP135 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T3207" 0
EP136 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6417" - SHT 1 0
EP136A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6417" - SHT 2 0
EP137 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6430" 0
EP140 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "TMF" 0
EU503 SITE ELECTRICAL DETAILS - SHEET 3 0
EU507 SITE ELECTRICAL DETAILS - SHEET 7 0
EU508 SITE ELECTRICAL DETAILS - SHEET 8 0
EO00 ELECTRICAL OVERALL-ONE-LINE DIAGRAM 1
EO02 SITE ELECTRICAL PRIMARY-CABLE SCHEDULE - SHEET 1 0
EO03 SITE ELECTRICAL PRIMARY-CABLE SCHEDULE - SHEET 2 1
EO04 SITE ELECTRICAL SECONDARY-CABLE SCHEDULE 1
EO05 SITE ELECTRICAL-EXISTING TRANSFORMERS 1
EO06 SITE ELECTRICAL-NEW TRANSFORMER REQUIREMENTS 1
EO07 SITE ELECTRICAL-SECTIONALIZING CABINETS AND PAD MOUNTED SWITCHES 1
EO08 SITE ELECTRICAL-NEW ELECTRICAL MANHOLES 0
EO09 SITE ELECTRICAL-COMMUNICATION CONDUIT AND CABLE SCHEDULE - SHEET 1 0
INDEX SHEET
GG02 1
AS NOTED
DL MORITZ
BW DEEN
NM BROWN
1 REMOVED TCT AND TARS NAL NAL EEL 06-22-2022
D
A
1 2
C
AD
D D
3- R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com Texas Firm Registration No.: F-174
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA-APHIS-PPQ MOORE AIR BASE
PHASE 2 ELECTRICAL CABLING AND EQUIPMENT DESIGN
EDINBURG, TEXAS
27100.26
MAY 09, 2022
DL MORITZ
EE LEAF
NOTE: THE SIZE, NUMBER AND LOCATION OF EXISTING
UTILITIES SHOWN ON THIS DRAWING ARE APPROXIMATE AND
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
06-22-2022
DRAWING INDEX SCOPE OF WORK STATEMENT:
THIS CONTRACT IS TO INSTALL THE FOLLOWING CABLING AND EQUIPMENT. THERE IS ALSO SOME DEMOLITION OF
SOME OF THE EXISTING DISTRIBUTION SYSTEM AS SHOWN ON EACH LOCATION DRAWING:
MEDIUM VOLTAGE ELECTRICAL INSTALLATION:
MEDIUM VOLTAGE RISER POLE
MEDIUM VOLTAGE UG CONDUIT EXTENSIONS OF "EP2" AND "EP4" TO REQUIRED TRANSFORMER LOCATIONS
MEDIUM VOLTAGE 4 WAY JUNCTIONS INSTALLED IN EXISTING SECTIONALIZING CABINETS
MEDIUM VOLTAGE PME-9 PAD MOUNTED SWITCHES
PAD MOUNTED SERVICE TRANSFORMERS
MEDIUM VOLTAGE ELECTRICAL CABLE
MEDIUM VOLTAGE LOAD BREAK ELBOWS
LOW VOLTAGE ELECTRICAL SERVICES INSTALLATION:
LOW VOLTAGE UG CONDUIT EXTENSIONS OF "LV***" CIRCUITS FROM ASSOCIATED TRANSFORMERS TO
BUILDINGS/SERVICE ELECTRICAL EQUIPMENT ON EXTERIOR STANDS WHERE SHOWN.
LOW VOLTAGE BRANCH CIRCUIT MODIFICATIONS WHERE SHOWN TO RESERVICE EXISTING LOCATION LOADS
SUCH AS PANELS, SITE LIGHTING, DISCONNECTS, ETC.
LOW VOLTAGE SERVICE CABLES
LOW VOLTAGE BRANCH CIRCUIT CABLES
DEMOLITION TO INCLUDE REMOVAL OF EXISTING OVERHEAD SECONDARY SERVICE CONDUCTORS AS SHOWN ON
PLAN DRAWINGS AND NOTES.
DEMOLITION OF EXISTING TRANSFORMER MEDIUM VOLTAGE SERVICE RISER CONDUITS AND ASSOCIATED MV CABLE AFTER DISCONNECTION BY BASE AT THE EXISTING POLE TOP FUSED CUT OUT ASSEMBLIES.
COORDINATION WITH BASE OF EACH LOCATION SERVICE TRANSFER FROM EXISTING OVERHEAD ELECTRICAL DISTRIBUTION TO NEW UNDERGROUND MEDIUM VOLTAGE DISTRIBUTION SYSTEM SECTIONALIZING CABINET, OR
PAD MOUNTED SWITCH AND ASSOCIATED PAD MOUNTED TRANSFORMER.
EXISTING OVERHEAD ELECTRICAL DISTRIBUTION SYSTEM AND POLE MOUNTED TRANSFORMERS (EXCEPT FOR TRANSFORMER RISERS REMOVED IN DEMOLITION STATED ABOVE), WILL BE BY BASE AFTER COMPLETION OF
CONTRACT.
SEE REFERENCE DRAWINGS INCLUDED FROM PRIOR PROJECT WHICH HAVE INSTALLED THE FOLLOWING FOR
USE IN THIS SCOPE OF WORK:
UNDERGROUND "EP2" AND "EP4" CONDUIT SYSTEM FOR MEDIUM VOLTAGE CABLES TO BE INSTALLED . THERE WILL NEED TO BE EXTENSION OF THESE CONDUITS WHERE SHOWN ON DRAWINGS TO EXISTING PAD MOUNTED
TRANSFORMERS TO BE RESERVICED.
UNDERGROUND "MV****" CIRCUITS ARE SHOWN FROM PAD MOUNTED SWITCHES AND SECTIONALIZING CABINETS
THAT WILL NEED TO BE EXTENDED WHERE SHOWN ON DRAWINGS.
PAD MOUNTED TRANSFORMERS AND SWITCHES. CONCRETE PADS, BOX EXTENSIONS, AND SECTIONALIZING CABINET HOUSINGS FOR LOW VOLTAGE CONDUIT SERVICE STUBOUTS FROM NEW PAD MOUNTED TRANSFORMERS
EXTENDED AS SHOWN ON NEW INDIVIDUAL SITE PLAN DRAWINGS OF NEW WORK.
COMMUNICATION CONDUIT SYSTEM AND OPTICAL COMMUNICATION HOUSINGS AND HANDHOLE SYSTEMS WHICH
ARE NOT AFFECTED BY THIS CONTRACT.
WHEN TRANSFERRING ELECTRICAL SERVICES FOR FACILITIES, CONTACT BASE ELECTRICIANS MINIMUM OF 2
WEEKS PRIOR TO COORDINATE REQUIREMENTS.
FOR ALL SITE PLANS, DEMOLITION ONE LINE DIAGRAMS, AND NEW ONE LINE DIAGRAMS, SEE ALL EQUIPMENT
SCHEDULES, CABLE SCHEDULES, AND OVERALL SYSTEM RISER IN DRAWINGS EO00 - EO09.
OPTICAL CROSS CONNECT AND COMMUNICATION HANDHOLES ARE EXISTING. ONLY SHOWN FOR REFERENCE.
THIS PROJECT WILL REQUIRE COORDINATION AND A PHASING ISSUE WITH THE BASE AND BASE ELECTRICIANS. IT IS ANTICIPATED THAT THE UNDERGROUND SYSTEM WILL BE ENERGIZED IN PHASES AND SECTIONALIZING CABINETS AND SWITCHES WILL HAVE TO HAVE CERTAIN SECTIONS ISOLATED DURING INSTALLTION AND LOCK OUT/TAG OUT PROCEDURES IN PLACE. DAILY REVIEW OF ENERGIZED STATUS OF SECTIONS OF BOTH GRIDS MUST OCCUR BETWEEN BASE AND CONTRACTOR FROM START TO END OF PROJECT AND DUAL LOCKOUTS WITH BASE AND CONTRACTOR LOCKS ON SWITCHES MUST OCCUR AND BE VERIFIED BY ALL PARTIES DURING CONSTRUCTION.
BEFORE RELEASING SECTION OF LINE TO BE ENERGIZED, EACH PARTY MUST REMOVE OWN LOCKS AND TAGS AND
SIGN OFF ON DAILY OUTAGE FORM TO BE DETERMINED BETWEEN PARTIES.
CONTRACTOR TO COORDINATE PROTECTIVE FUSE SIZING AS REQUIRED AND PROVIDE CHANGES IN FUSE SIZES, IF
REQUIRED.
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
NOTE: THE SIZE, NUMBER AND LOCATION OF EXISTING
UTILITIES SHOWN ON THIS DRAWING ARE APPROXIMATE AND
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "TGH" - DEMO
EO121D 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
REMOVE EXISTING SECONDARY CONDUCTORS FROM POLE
MOUNTED TRANSFORMERS DOWN THE POLE AND INTO EXISTING
METER BASE ONCE THE NEW PAD MOUNTED TRANSFORMER TGH IS
READY TO BE PLACED IN SERVICE.
THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.
CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO
TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO
NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL
DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED
TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO
REMOVE CONDUITS AND SECONDARY SERVICE CONDUCTORS.
CONTRACTOR SHALL REMOVE ALL SERVICE CONDUITS TO BELOW
GRADE TO POINT OF RUNNING HORIZONTAL TO GRADE. BASE WILL
REMOVE POLES AND POLE MOUNTED TRANSFORMERS, AT A LATER
DATE WHERE APPLICABLE.
LEGEND:
REMOVE
ONE-LINE DIAGRAM FOR TRANSFORMER "TGH"
AutoCAD SHX Text
LIFT STATION
AutoCAD SHX Text
200A FUSE 3P S/N IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
GUARD HOUSE
AutoCAD SHX Text
GEN
AutoCAD SHX Text KOHLER 208V, 4P, 200A AUTOMATIC TRANSFER SWITCH IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
40KW STANDBY GENERATOR
AutoCAD SHX Text
METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND TO REMAIN
AutoCAD SHX Text
(2)3-#3/0, #4GND (3")C
AutoCAD SHX Text
EXISTING (3)25KVA POLE MOUNTED TRANSFORMER
AutoCAD SHX Text
EXISTING TO REMAIN
5A
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "TGH" - NEW
EO121 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
INSTALL NEW SECONDARY SERVICE CONDUCTORS FROM
TRANSFORMER TGH TO LINE SIDE OF EXISTING METER BASE. TAKE
OUTAGE TO REMOVE EXISTING SERVICE CONDUCTORS FROM POLE
MOUNTED TRANSFORMERS
EXISTING SERVICES TO THE LIFT STATION AND GUARD HOUSE
FROM THE TRANSFER SWITCH WILL REMAIN
SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND
EO06 FOR TRANSFORMER SCHEDULES
SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL
PRIMARY CABLE SCHEDULES
SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5
NEW ONE-LINE DIAGRAM FOR TRANSFORMER "TGH"
1 5
3 4
AutoCAD SHX Text
METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
"LVTGH"
AutoCAD SHX Text
LIFT STATION
AutoCAD SHX Text
200A FUSE 3P S/N IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
GUARD HOUSE
AutoCAD SHX Text
GEN
AutoCAD SHX Text KOHLER 208V, 4P, 200A AUTOMATIC TRANSFER SWITCH IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
40KW STANDBY GENERATOR
AutoCAD SHX Text
NEW PAD MOUNTED SWITCH SW#1
AutoCAD SHX Text
"MVSW1/3"
AutoCAD SHX Text
13.2KV 75KVA TRANSFORMER "TGH" 208Y/120V, 3ɸ, 4W
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
S
A
N
S
A
N
S
A
N
S
A
N
S
A
N
SAN SAN SAN
SS
SS
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
PROVIDE AEP CONNECTION
40' CLASS 2 WESTERN RED CEDAR
RISER AEP METER POLE, EXTEND EP2
CONDUITS AS SHOWN AT THIS
LOCATION FOR EXTENSION
TO AEP PRIMARY METERING POLE,
PROVIDE MUAEP CABLES
PME-9
PAD MOUNTED
SWITCHGEAR SW#1
4 WAY SECTIONALIZER SC#1
75KVA TRANSFORMER
208/120V 3Ø 4W, "TGH"
2-4" CONDUIT STUBBED
10' FROM PAD
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "TGH"
EP121 0
1" = 10'
DL MORITZ
BW DEEN
NM BROWN
M
V
S
C
M
V
S
C
OCC#1
CHH#1
C
P
E
P
E
P
U
A
E
P
IMAGE
A
EP121
SCALE: NONE
N
O
R
T
H
TO GUARD HOUSE
INSTALL NEW CONDUIT
FROM PAD MOUNTED
TRANSFORMER
TO METER BASE
I M
A
G
E
EXISTING
METER SOCKET
EXISTING SERVICES TO LIFT
STATION AND GUARD HOUSE
EXISTING SERVICES TO LIFT
STATION AND GUARD HOUSE
EXISTING ELECTRICAL
EQUIPMENT RACK
EXISTING KOHLER GENERATOR3
CIRCUIT "LVTGH"4
IMAGE
B
EP121
SCALE: NONE
IM
AG
E B
KEYNOTES:
REMOVE CONDUIT FROM POLE PER ONE LINE DIAGRAM ONCE NEW
SERVICE IS IN PLACE
SAW CUT CONCRETE AND INSTALL NEW “LVTGH” REQUIREMENTS
PER ONE LINE DIAGRAM INTO METER ENCLOSURE. PLACE
OVERSIZED PVC SLEEVE AROUND CONDUIT AND CAST INTO
CONCRETE WHEN REFORMING SAW CUT AREA. PLACE CONDUIT
SEAL IN OLD CONDUIT INTERNAL TO THE METER SOCKET TO
PREVENT INTRUSION WHICH MAY BE REMOVED IN FUTURE IF
NEEDED
EP2 MVSW1/3
TO TRANSFORMER
"TGH"
MOBILE BUILDING
IMAGE
C
EP121
SCALE: NONE
I
M
A
C
5 MOBILE BUILDING IS SERVICED FROM TRANSFORMER "TGH" BUT
CONFIRM WITH GOVT PRIOR TO OUTAGE
6 INSTALL EQUIPMENT ON EXISTING PAD POURED DURING PRIOR
PROJECT
MVSW1/2EP2
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "T6021" - DEMO
EO122D 0
NONE
DL MORITZ
BW DEEN
NM BROWN
BWD
KEYNOTES:
REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE
MOUNTED TRANSFORMER TO WEATHERHEAD AND CONDUIT DOWN
TO THE EXISTING EXTERIOR PANELBOARD 1P ONCE NEW METER
ENCLOSURE IS IN PLACE AND NEW SERVICES READY TO BE
PLACED IN SERVICE.
THE EXISTING POLE AND TRANSFOMRER WILL BE LEFT IN PLACE.
CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO
TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO
NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL
DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED
TRANSFORMER AND CONTRACTOR SHALL THEN BE ALLOWED TO
REMOVE CONDUITS AND SECONDARY SERVICE CONDUCTORS.
BASE WILL REMOVE POLES AT A LATER DATE WHERE APPLICABLE.
LEGEND:
REMOVE
THERE IS AN EXISTING BRANCH CIRCUIT FROM PANEL 1P ROUTED IN
SAME CONDUIT AND WEATHERHEAD AS THE SERVICE TO THE
BUILDING. IT IS FED FROM A 70A, 2 POLE BREAKER LOCATED IN THE
PANEL 1P. REMOVE THIS BRANCH CIRCUIT ONCE THE CIRCUIT IS
REROUTED THRU THE BUILDING PER THE NEW ONE LINE DIAGRAM
REQUIREMENTS. AT BUILDING REMOVE THE SECOND
WEATHERHEAD AND PLACE A METAL EXPANDABLE WATERPROOF
SEAL PLUG IN EXTERIOR OF BUILDING FOR THIS WEATHERHEAD
ENTRANCE INTO BUILDING. PLUG ALL REMOVED CONDUIT
PENETRATIONS WHICH HELD SERVICE CONDUIT DOWN SIDE OF
BUILDING TO PANEL 1P.
1 2
ONE-LINE DIAGRAM FOR TRANSFORMER "T6021"
AutoCAD SHX Text
EXISTING 25KVA POLE MOUNTED TRANSFORMER
AutoCAD SHX Text
PANEL #1 INSIDE BLDG
AutoCAD SHX Text 100A 2P
AutoCAD SHX Text 70A 2P
AutoCAD SHX Text
PANEL 1P
AutoCAD SHX Text
PANEL #2 INSIDE BLDG
3-#4
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "T6021" - NEW
EO122 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
PROVIDE A NEW 200 AMP METER ENCLOSURE FOR 1 PHASE, 3 WIRE
INSTALLATION. LOCATE ON STAINLESS STEEL UNISTRUT STANDOFF
FROM THE BUILDING AS REQUIRED FOR SIDING CORUGATIONS.
COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF
SERVICE TO POLE MOUNTED TRANSFORMER AND TO
ENERGIZE NEW PAD MOUNTED TRANSFORMER "T6021". AT
ADJACENT PAD MOUNTED SECTIONALIZING CABINET,
COORDINATE REQUIRED CONNECTIONS TO MAINTAIN OPEN
SECTIONS AS REQUIRED DURING PHASING OF WORK.
SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND
EO06 FOR TRANSFORMER SCHEDULES.
SEE DRAWING EO02 AND EO03FOR SITE ELECTRICAL
PRIMARY CABLE SCHEDULES.
SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES.5
PROVIDE A NEW 200A, 1 PHASE, 3 WIRE PANELBOARD IN
LOCKABLE NEMA 3R ENCLOSURE FOR PANEL 1P. PANEL TO
HAVE A 200A MAIN CIRCUIT BREAKER AND 100A, 2 POLE AND
70A, 2 POLE BREAKER BRANCH BREAKER TO RESERVICE
EXISTING LOADS. PANEL SHALL ALSO BE PROVIDED WITH
120KA SEVEN MODE TVSS DIRECTED CONNECTED TO BUS.
PANEL SHALL BE SERVICE ENTRANCE RATED. ROUTE THE
NEW SERVICE LVT6021 FRM NEW PAD MOUNT TRANSFORMER
INTO BOTTOM OF PANEL.
IN BACK OF PANEL 1P, PLACE A CONDUIT NIPPLE INTO
BUILDING AND ROUTE NEW BRANCH CIRCUIT AS SHOWN ON
ONE LINE DIAGRAM TO EXISTING PANEL 2 INSIDE OF
BUILDING. CONTRACTOR SHALL ROUTE WITH BUILDING LINES
AS DIRECTED BY GOVT.
LOCATE PANEL MDP6021 TO ALLOW EXISTING 100A, BRANCH
CIRCUIT CABLING TO REACH NEW 100 AMP BRANCH BREAKER
TERMINALS.
NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6021"
3 4
AutoCAD SHX Text
3#4 W/#8 GND (1.25") RGS CONDUIT
AutoCAD SHX Text 100A 2P
AutoCAD SHX Text 70A 2P
AutoCAD SHX Text
NEW PANEL "MDP6021"
AutoCAD SHX Text 5A
AutoCAD SHX Text
SECTIONALIZING CABINET SC#2
AutoCAD SHX Text 200A 2P
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
PANEL #1 INSIDE BLDG
AutoCAD SHX Text
PANEL #2 INSIDE BLDG
AutoCAD SHX Text
"LVT6021"
AutoCAD SHX Text
NEW 200 AMP METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON BUILDING
AutoCAD SHX Text
"LVT6021"
AutoCAD SHX Text
7.6KV 25KVA TRANSFORMER "T6021" 120/240V, 1ɸ, 3W
AutoCAD SHX Text
"MVSC2/3"
120/240V, 1ɸ, 3W 10KAIC
N
F
EXTEND CONDUIT
TO NEW METER
ENCLOSURE
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
N
O
R
T
H
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "T6021"
EP122 0
1" = 10'
DL MORITZ
BW DEEN
NM BROWN
25KVA TRANSFORMER
120/240V 1Ø 3W, "T6021"
E P
M V
S C
IMAGE
A
EP122
SCALE: NONE
IMAGE A
IMAGE
B
EP122
SCALE: NONE
TO BLDG LOADS
IMAGE
C
EP122
SCALE: NONE
IMAGE B
IMAGE C
KEYNOTES:
IN IMAGE “A” REMOVE EXISTING SECONDARY SERVICE
CONDUCTORS FROM TRANSFORMER POLE, WEATHERHEAD AND
EXISTING 70A BRANCH CIRCUIT AFTER NEW METER ENCLOSURE IS
IN PLACE AND PANEL 1P IS READY TO BE CHANGED OUT. CONTACT
BASE FOR VERIFICATION THAT TRANSFORMER IS DE-ENERGIZED
PRIOR TO REMOVAL FOR ALL OVERHEAD TRANSFORMER
SECONDARY SERVICE LOCATION REMOVALS.
IMAGE “B” SHOWS EXISTING PANEL 1P AND 100A AND 70A
BRANCH BREAKER TO BE REMOVED.
EXISTING WEATHERHEADS TO BE REMOVED ALONG WITH
CONDUITS AND ATTACHMENTS TO BUILDING. PROVIDE
WETAHERPROOF PLUGS AND APPROVED SEALING MEANS
FOR ALL OPENINGS LEFT AFTER CONDUITS AND
ATTACHMENTS HAVE BEEN REMOVED.
NEW PANEL 1P
EXISTING PANEL #1
EXISTING PANEL #2
SEE KEY NOTE 3
ON ONE-LINE DIAGRAM,
DWG EO122
LEGEND:
REMOVE
DETAIL A
DETAIL A
36" BELOW GRADE TO
TRANSFORMER T6021
EXISTING 100
AMP SERVICE
INTO BUILDING
70A NEW BRANCH
CIRCUIT TO PANEL #2
INSIDE BUILDING
NEW PANEL 1P NEW METER
ENCLOSURE
NOTES:
1. REFERENCE PHASE 1 DRAWINGS FOR ROUTES.
LOCATE NEW
PANEL TO REUSE
EXISTING 100A
BRANCH CIRCUIT
CONDUCTORS & CONDUITS
#6 AWG
TO GROUND GRID,
SEE DETAIL, ON DWG EU503
LOCATION TO BE VERIFIED
LOCATION TO BE VERIFIED
NEW METER
ENCLOSURE
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "T6017" - DEMO
EO123D 0
NONE
DL MORITZ
BW DEEN
NM BROWN
DLM
KEYNOTES:
REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE
MOUNTED TRANSFORMERS TO WEATHERHEAD AND IN CONDUIT
DOWN TO THE EXISTING MANUAL DOUBLE THROW SWITCH ONCE
NEW METER ENCLOSURE AND PANEL MDP IS IN PLACE AND NEW
SERVICES READY TO BE PLACED IN SERVICE
THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.
CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO
TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO
NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL
DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED
TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO
REMOVE AERIAL SECONDARY SERVICE CONDUCTORS. BASE WILL
REMOVE TOP OF THIS POLE AT A LATER DATE WHERE APPLICABLE
TO CONTINUE SERVICE TO EXISTING SITE LIGHTS AND HAZ MAT
DISCONNECT
LEGEND:
REMOVE
ONE-LINE DIAGRAM FOR TRANSFORMER "T6017"
AutoCAD SHX Text
EXISTING POLE MOUNTED 3-37.5KVA TRANSFORMER BANK
AutoCAD SHX Text 300A
AutoCAD SHX Text
200AF
AutoCAD SHX Text
EXISTING OH TO POLE MOUNTED SITE LIGHTS
AutoCAD SHX Text
TO BLDG 6017
AutoCAD SHX Text
TO BLDG 6017
AutoCAD SHX Text
EXISTING OH TO POLE MOUNTED DISCONNECT FOR HAZ-MAT
AutoCAD SHX Text
NON-FUSIBLE MANUAL DPDT MANUAL TRANSFER SWITCH IN LOCKABLE NEMA 3R ENCLOSURE
AutoCAD SHX Text
METER ENCLOSURE
AutoCAD SHX Text
GEN
AutoCAD SHX Text
TEMPORARY GENERATOR
EXISTING GENERATOR RECEPTACLE FOR TEMPORARY GENERATOR
8A
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "T6017" - NEW
EO123 0
NONE
DL MORITZ
BW DEEN
NM BROWN
BWD
KEYNOTES:
PROVIDE A NEW 600 AMP METER ENCLOSURE FOR 3 PHASE, 4 WIRE
INSTALLATION. LOCATE ON STAINLESS STEEL UNISTRUT
EQUIPMENT STAND EXTENSION FROM EXISTING POLES AND
STANDOFF FROM THE FRAME AS REQUIRED. PROVIDE AN
ADJACENT METERING TRANSFORMER ENCLOSURE WITH CT AND PT
TRANSFORMERS TO SERVICE METER
COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF
SERVICE TO POLE MOUNTED TRANSFORMERS AND TO ENERGIZE
NEW PAD MOUNTED TRANSFORMER T6017. AT ADJACENT PAD
MOUNTED SWITCH, COORDINATE REQUIRED CONNECTIONS TO
MAINTAIN OPEN SECTIONS AS REQUIRED DURING PHASING OF
WORK
SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND EO06
FOR TRANSFORMER SCHEDULES
SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL PRIMARY
CABLE SCHEDULES
SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5
PROVIDE A NEW 600A, 3 PHASE, 4 WIRE PANELBOARD IN LOCKABLE
NEMA 3R ENCLOSURE FOR PANEL MDP. PANEL TO HAVE A 500A
MAIN CIRCUIT BREAKER TRIP AND BRANCH BREAKERS AS SHOWN
TO RESERVICE EXISTING LOADS. PANEL SHALL ALSO BE
PROVIDED WITH 160KA SEVEN MODE TVSS DIRECTLY CONNECTED
TO BUS. PANEL SHALL BE SERVICE ENTRANCE RATED. ROUTE THE
NEW SERVICE LVT6017 FROM NEW PAD MOUNT TRANSFORMER
INTO BOTTOM OF METER ENCLOSURE AND THEN TO MDP PANEL
FROM 400A BRANCH BREAKER IN PANEL MDP, ROUTE
CONDUCTORS SHOWN TO EXISTING MANUAL TRANSFER SWITCH.
THE LOAD SIDE OF TRANSFER SWITCH WILL REMAIN AS IS WITH
EXISTING OVERHEAD SERVICES INTO THE BUILDING
PROVIDE CIRCUITS AS SHOWN FROM PANEL MDP BACK TO
EXISTING POLE UNDERGROUND AT 3' BELOW GRADE AND ROUTE
OVER AND UP POLE WITH CONDUIT STANDOFFS UP TO HEIGHT OF
EXISTING AERIAL SECONDARY SERVICE TO HAZ MAT AREA
DISCONNECT AND SITE LIGHTING. COMBINE CIRCUITS IN 2 INCH
RGS CONDUIT AND AT TOP OF THE 2 INCH RGS CONDUIT PLACE
WEATHERHEAD AND ROUTE CONDUCTORS OUT WITH DRIP LOOP
TO BE CRIMPED ONTO EXISTING CONDUCTORING. COVER
CONNECTIONS WITH HEAT SHRINK ONCE IN PLACE.
3 4
NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6017"
AutoCAD SHX Text
EXISTING 100A 3P
AutoCAD SHX Text
GEN
AutoCAD SHX Text
TEMPORARY GENERATOR
AutoCAD SHX Text
NEW 600 AMP METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
"LVT6017"
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text
NEW PANEL "MDP6017"
AutoCAD SHX Text
600AF 3P 500AT
AutoCAD SHX Text
NEW PAD MOUNTED SWITCH SW#2
AutoCAD SHX Text
"MVSW2/3"
AutoCAD SHX Text
"LVT6017"
AutoCAD SHX Text 30A 2P
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
22,000AIC
AutoCAD SHX Text
208V, 3ɸ, 4W, 600A BUS
AutoCAD SHX Text
4#2 W/#6 GND (2") RGS CONDUIT
AutoCAD SHX Text
4#600MCM W/ 1/0 GND (4") RGS CONDUIT
AutoCAD SHX Text
EXISTING GENERATOR RECEPTACLE FOR TEMPORARY GENERATOR
AutoCAD SHX Text 300A
AutoCAD SHX Text
200AF
AutoCAD SHX Text
HAZ-MAT
AutoCAD SHX Text 3#6
AutoCAD SHX Text
EXISTING SITE LIGHTING
AutoCAD SHX Text
METER ENCLOSURE
13.2KV 150KVA TRANSFORMER "T6017" 208Y/120V, 3ɸ, 4W
O/E
O/EO/EO/E
O/E
O/EO/E
O/EO/E
O/E
O/EO/E
O/EO/E
O/E
O/EO/E
O/EO/E
O/E
O/E O/E
O/EO/E
O/E
O/EO/EO/E
O/E
O/EO/E
O/EO/E
O/E
O/EO/E
O/EO/E
O/E
O/EO/E
O/EO/E
O/E
O/E O/E
O/EO/E
W
W
W
CO
ELECT. PANEL
FO DEPTH: 1.58'
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
PME-9 SW#2
150KVA TRANSFORMER
208/120V 3Ø 4W, "T6017"
EP2
EP2
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "T6017" - SHT 1
EP123 0
1" = 10'
DL MORITZ
BW DEEN
NM BROWN
EP2 MVSW2/3
MVSC1/2
MVSW2/4
N
O
R
T
H
IMAGE
B
EP123
SCALE: NONE
IMAGE
A
EP123
SCALE: NONE
I
M
A
B
IMAGE A
KEYNOTES:
EXISTING POLES AND SECONDARY BRANCH CIRCUIT AERIAL
CONDUCTORS FROM LOAD SIDE OF NEW PANEL MDP TO REMAIN
EXISTING POLE MOUNTED EQUIPMENT STAND TO REMAIN AND BE
ENLARGED TO ALLOW FOR NEW METER ENCLOSURE AND PANEL
MDP
I
M
A
CONTRACTOR HAS OPTION TO INSTALL WOOD POLE OR 6 INCH
STEEL PIPE FILLED WITH CONCRETE IN 12 INCH SONO TUBE
CONCRETE FILLED FOUNDATION DOWN 4 FEET FOR EXTENDING
ELECTRICAL EQUIPMENT STAND. USE GALVANIZED STEEL
UNISTRUT 1 7/8 INCH MINIMUM FOR CROSS BRACING
NEW PANEL "MDP6017" PER ONE LINE DIAGRAM4
NEW METER ENCLOSURE WITH INTEGRAL METERING
TRANSFORMERS AS REQUIRED
REUSE SPOOL INSULATORS FOR CONNECTION OF EXISTING AERIAL
CONDUCTORS TO HAZ MAT AND SITE LIGHTING CIRCUITS. SEE ONE
LINE DIAGRAM
REMOVE AERIAL SERVICE CONDUCTORS FROM TRANSFORMERS TO
MANUAL TRANSFER SWITCH PER DEMO ONE LINE DIAGRAM.
EXISTING BRANCH CIRCUITS SHOWN AND POLES TO REMAIN8
IMAGE C
TO T6017
3 5 4
NEW PANEL "MDP6017"
NEW
METER ENCLOSURE
EXISTING AERIAL
TO HAZ-MAT
DISCONNECT
EXISTING AERIAL
TO SITE LIGHTING
DISCONNECT
EXISTING TRANSFER
SWITCH
IMAGE E
OE
OE
OE
OE
OE OE OE OE
OE OE
OE
OE OE OE OE OE OE
EXISTING
100A HAZ MAT
DISCONNECT
OE OE
EXTEND EXISTING 4" CONDUIT TO THE NEW METER LOCATION,
PROVIDE A SECOND 4" CONDUIT PARALLEL TO THE EXISTING 4"
CONDUIT, SAW CUT AND PATCH EXISTING FOUNDATION AS NEEDED
TO INSTALL SECOND CONDUIT.
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "6017" - SHT 2
EP123A 0
NONE
DL MORITZ
BW DEEN
NM BROWN
IMAGE
D
EP123
SCALE: NONE
IMAGE
E
EP123
SCALE: NONE
LEGEND:
REMOVE
NOTES:
1. SEE DWG EP123, FOR KEYNOTES.
IMAGE
C
EP123
SCALE: NONE
TO GENERATOR
TO NEW PANEL
MDP6017
100A DISCONNECT
AT HAZ MAT
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "T6101" - DEMO
EO124D 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE
MOUNTED TRANSFORMERS TO WEATHERHEADS AND CONDUIT
DOWN TO THE EXISTING MANUAL DOUBLE THROW SWITCH, AND
PANEL CIRCUITS FOR BUILDINGS 6101 AND 6102 WHICH WILL BE
NEW UNDERGROUND BRACH CIRCUITS PER ONE LINE DIAGRAMS.
REMOVE ONCE NEW METER ENCLOSURE AND PANEL MDP IS IN
PLACE AND NEW SERVICES ARE READY TO BE PLACED IN SERVICE
THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.
CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO
TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO
NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL
DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED
TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO
REMOVE AERIAL SECONDARY SERVICE CONDUCTORS. BASE WILL
LEAVE EXISTING POLE AND AREA LIGHT AND CONTRACTOR TO
MAINTAIN SERVICE TO THIS LIGHT FROM NEW PANEL. BASE TO
REMOVE TRANSFORMERS AT A LATER DATE
LEGEND:
REMOVE
1 2
ONE-LINE DIAGRAM FOR TRANSFORMER "T6101"
AutoCAD SHX Text
EXISTING POLE MOUNTED 3-25KVA TRANSFORMER BANK
AutoCAD SHX Text 150A 3P
AutoCAD SHX Text
TO BLDG 6101 SERVICE PANEL
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text
TO BLDG 6102 SERVICE PANEL
EXISTING DOUBLE THROW MANUAL TRANSFER SWITCH, NEMA TYPE 3R 200A, RELOCATE TO ELECTRICAL EQUIPMENT STAND
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM & DETAILS
TRANSFORMER "T6101" - NEW
EO124 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
PROVIDE A NEW 600 AMP METER ENCLOSURE FOR 3 PHASE, 4 WIRE
INSTALLATION. LOCATE ON UNISTRUT EQUIPMENT STAND PER
DETAILS AS REQUIRED. PROVIDE METERING TRANSFORMER
ENCLOSURE WITH CT AND PT TRANSFORMERS TO SERVICE METER
COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF
SERVICE TO POLE MOUNTED TRANSFORMERS AND TO
ENERGIZE NEW PAD MOUNTED TRANSFORMER T6101.
COORDINATE REQUIRED CONNECTIONS TO MAINTAIN OPEN
SECTIONS OF NEW UNDERGROUND DISTRIBUTION AS
REQUIRED DURING PHASING OF WORK
GALVANIZED 4" STEEL
PIPE FILLED WITH
CONCRETE. SPACING
BETWEEN PIPES NOT TO
EXCEED 6 FEET. PROVIDE
ADDITIONAL SUPPORT
PIPES AS NEEDED (TYP)
RGS CONDUIT (TYP)
WHERE EXPOSED
EXTERIOR ELECTRICAL EQUIPMENT STAND DETAIL
NO SCALE
1'-6"
WEATHERPROOF
GFI SERVICE
RECEPTACLE
PLACE BITUMONOUS COATING
ON STEEL WHERE IN CONTACT
WITH CONCRETE (TYP)
GALVANIZED STEEL
UNISTRUT MOUNTING
BRACKETS (TYP)
18" SONOTUBE FILLED WITH
CONCRETE (TYP)
PANEL "MDP6101"
ON BACKSIDE OF METER
ENCLOSURE
600A METER
ENCLOSURE
SERVICE DISCONNECT
TO BLDG 6101
SERVICE DISCONNECT
TO BLDG 6102
RELOCATED EXISTING 200AMP
MANUAL THROW SWITCH
WRAP 3M TAPE 3" ABOVE
AND BELOW CONCRETE
FINISH (TYP)
USE MYERS HUBS
TO "T6101"
3 4
SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND
EO06 FOR TRANSFORMER SCHEDULES
SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL
PRIMARY CABLE SCHEDULES
SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5
PROVIDE A NEW 600A, 3 PHASE, 4 WIRE PANELBOARD IN
LOCKABLE NEMA 3R ENCLOSURE FOR PANEL MDP6101. PANEL
TO HAVE A 500A MAIN CIRCUIT BREAKER TRIP AND BRANCH
BREAKERS AS SHOWN TO RESERVICE EXISTING LOADS.
PANEL SHALL ALSO BE PROVIDED WITH 160KA SEVEN MODE
TVSS DIRECTED CONNECTED TO BUS. PANEL SHALL BE
SERVICE ENTRANCE RATED. ROUTE THE NEW SERVICE
LVT6101 FROM METER ENCLOSURE INTO SIDE OF NEW PANEL
FROM 200A BRANCH BREAKER IN PANEL MDP, ROUTE
CONDUCTORS SHOWN TO EXISTING MANUAL TRANSFER
SWITCH. AFTER RELCOATING TRANSFER SWITCH TO
EQUIPMENT STAND, THE LOAD SIDE OF EXISTING TRANSFER
SWITCH IS CURRENTLY NOT CONNECTED, WILL REMAIN OPEN
FOR FUTURE GOVT. USE
NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6101"
PROVIDE NEW BRANCH CIRCUITS AS SHOWN FOR PANELS AT
BUILDINGS 6101 AND 6102 TO BE ROUTED UNDERGROUND
FROM DISCONNECTS TO PANELS.
1/0 AWG TO GROUND
GRID, SEE DETAILS
1" C
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text
NEW PANEL "MDP6101"
AutoCAD SHX Text
600AF 3P 500AT
AutoCAD SHX Text
"LVT6101"
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
SECTIONALIZING CABINET SC#4
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text EXISTING DOUBLE THROW MANUAL TRANSFER SWITCH NEMA TYPE 3R, 200A RELOCATED TO ELECTRICAL EQUIPMENT STAND
AutoCAD SHX Text 8A
AutoCAD SHX Text
NEW 600A METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND
AutoCAD SHX Text
"LVT6101"
AutoCAD SHX Text
13.2KV 150KVA TRANSFORMER "T6101" 208Y/120V, 3ɸ, 4W
AutoCAD SHX Text
"MVSC4/3"
AutoCAD SHX Text 20A 1P
AutoCAD SHX Text 3#12(1")C
AutoCAD SHX Text
AREA LIGHT
AutoCAD SHX Text
200A NF
AutoCAD SHX Text 200A 3P
AutoCAD SHX Text 150A 3P
AutoCAD SHX Text
TO BLDG 6101
AutoCAD SHX Text
4#4/0, W/#6 GND (2.5")C
AutoCAD SHX Text
4#4/0, W/#6 GND (2.5")C
AutoCAD SHX Text
100A NF
AutoCAD SHX Text 100A 3P
AutoCAD SHX Text
TO BLDG 6102
AutoCAD SHX Text
4#2, W/#8 GND (1.25")C
AutoCAD SHX Text 20A 1P
AutoCAD SHX Text
X2 GFI WP
AutoCAD SHX Text 3#12(1")C
208V, 3ɸ, 4W, 600A BUS, 42,000AIC
O/E
O/E
O/E
O/E
O/E
O/E
O/E
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
EP2
4 WAY SECTIONALIZER SC#4
150KVA TRANSFORMER
208/120V 3Ø 4W, "T6101"
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "T6101"
EP124 0
1" = 10'
DL MORITZ
BW DEEN
NM BROWN
EP2
MVSC4/3
MVSC4/2
MVSC4/4
N
O
R
T
H
SERVICE DISCONNECT
TO 6102
NEW PANEL
"MDP6101"
RELOCATED EXISTING
200A TRANSFER
MANUAL THROW SWITCH
I
M
A
IMAGE
A
EP124
SCALE: NONE
IMAGE
B
EP124
SCALE: NONE
SERVICE DISCONNECT
TO 6101
600A
METER ENCLOSURE
KEYNOTES:
EXISTING POLE TO REMAIN AND RESERVICE OVERHEAD AREA
LIGHT WITH CIRCUIT SHOWN ON ONE LINE DIAGRAM
EXISTING OVERHEAD AREA LIGHT AT STRUCTURAL COLUMN TO
REMAIN AT BUILDING 6102
ROUTE SECONDARY CONDUITS AT 36 INCH MINIMUM BURIAL DEPTH
TYPICAL
REMOVE EXISTING OVERHEAD SECONDARY SERVICE
CONDUCTORS TO PANEL AT BLDG. 6102
REMOVE SERVICE WEATHERHEAD AND CONDUIT AT BUILDING 6102.
PLACE WEATHERPROOF SCREW TYPE CAP ON TOP OF EXISTING
PANEL TO SEAL. SERVICE TO OVERHEAD LIGHT TO REMAIN ALONG
WITH OTHER BRANCH CIRCUITS
REMOVE EXISTING GROUND CABLE, GROUND ROD, AND CONDUIT
AND PLACE WEATHER PROOF SCREW TYPE PLUG IN OPENING.
NEW GROUND WILL BE PART OF BRANCH CIRCUIT
NEW UNDERGROUND BRANCH CIRCUIT FROM 100A DISCONNECT
AT ELECTRICAL EQUIPMENT RACK
EXISTING YARD LIGHT TO REMAIN. ROUTE CONDUIT UP POLE FROM
BELOW GRADE AND CONNECT TO NEW MDP6101 PER ONE LINE
DIAGRAM. SECURE CONDUIT TO POLE AS REQUIRED AND
RECONNECT TO EXISTING DRIP LOOP
EXISTING 200A MANUAL THROW SWITCH TO BE RELOCATED TO
ELECTRICAL EQUIPMENT RACK FOR FUTURE USE
REMOVE EXISTING SERVICE SPOOLS AND PROVIDE APPROVED
MEANS TO WEATHERPROOF BUILDING OPENINGS LEFT FROM
REMOVAL. COORDINATE WITH GOVT. REMOVE THE WEATHERHEAD,
OVERHEAD SERVICE CONDUCTORS AS SHOWN
IMAGE
C
EP124
SCALE: NONE
IMAGE
D
EP124
SCALE: NONE
IMAGE
E
EP124
SCALE: NONE
I
M
A
IMAGE D
I
M
A
I
M
A
1 8
EXTEND EXISTING 4" CONDUIT TO THE NEW METER LOCATION,
PROVIDE A SECOND 4" CONDUIT PARALLEL TO THE EXISTING 4"
CONDUIT, SAW CUT AND PATCH EXISTING FOUNDATION AS NEEDED
TO INSTALL SECOND CONDUIT.
10" SAN
GRAVEL
T
MH 9
N: 16667886.43
E: 1038904.46
T
FO DEPTH:1.21'
36+00
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N S
A N
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N
S A
N S
A N
S A
N S
A N
FO DEPTH: 1.58'
FO DEPTH: 1.91'
DEPTH: 6.00'
DEPTH: 4.00'
42+00
43+00
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
N
O
R
T
H
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "T6205" - SHT 1
EP125 0
1" = 10'
DL MORITZ
BW DEEN
NM BROWN
EP4 MVSW3/4
C P
EXISTING 500KVA PAD MOUNT
TRANSFORMER
480/277V 3Ø, 4W TO BE SWITCHED TO
NEW SERVICE IN FUTURE
"T6205"
EMH#6
OCC#5
EP2
CP1
KEYNOTES:
EXISTING MANHOLE #EMH6 EXISTING MV RADIAL TAP TO BE
REROUTED THRU THIS MANHOLE AND SPLICED INTO NEW MVSW3/4
CIRCUIT INTERIOR TO MANHOLE TO PREVENT HAVING TO ROUTE
NEW CONDUITS INTO EXISTING TRANSFORMER
EXISTING MV CABLE FROM OVERHEAD POLE RISER IS NOT SHOWN
ON AS-BUILTS ALL THE WAY TO TRANSFORMER. ROUTE ON
DRAWING IS ASSUMED. CONTRACTOR SHALL LOCATE WITH
POTHOLE IF REQUIRED TO PLACE NEW MANHOLE EMH#6 AND
EXPOSE TO REROUTE INTO MANHOLE. CONTRACTOR SHALL USE
CARLON 4 INCH PVC SPLIT DUCT TO PROTECT CABLE INTO
MANHOLE WHEN CONCRETE IS POURED. TAPE HALVES OF SPLIT
DUCT TOGETHER SO MINIMUM OF 6 INCHES INTO NEW MANHOLE
AND 12 INCHES OUTSIDE OF MANHOLE IF EXISTING CABLE WAS NOT
PLACED IN CONDUIT. SEAL CONDUIT FROM ACCIDENTAL CONCRETE
ENTRY AND TO ALLOW CABLE TO BE REMOVED IN FUTURE IF
NEEDED
CONTRACTOR SHALL VERIFY THE SIZE OF THE EXISTING UG MV
CABLE TO ALLOW WATERPROOF 15KV CABLE SPLICE IN MANHOLE.
SPLICES SHALL BE PLACED ON SIDE OF MANHOLE WALL ONCE
COMPLETED
EXISTING UNDEGROUND MEDIUM RISER CABLE AND CONDUIT UP
EXISTING RISER POLE TO BE REMOVED BY CONTRACTOR TO
BELOW GRADE ONLY UPON DE-ENERGIZING IS COMPLETED BY
BASE AND THE BASE HAS LOWERED FUSE CUT OUT ASSEMBLIES
AND CABLE DOWN TO MAXIMUM 10' ABOVE GRADE ON POLE
EXISTING INTERNAL VIEW OF T6205 TO BE RESERVICED5
ROUTE NEW MVSW3/4 CIRCUIT IN CONDUIT ROUTE SHOWN AND
ALSO ON PLAN DRAWINGS EP106 AND EP107. COMPLETE ROUTE
NOT SHOWN ON THIS DRAWING
I M
A G
E
B
N
O
R
T
H
I
M
A
OCC#6
CHH#8
PME-9 SW#3
PME-9 SW#4
MVSW4/4
MVSW3/2
EP4
EP2
E O
S F
CP1
CP4
E P
C P
TO BE REMOVED
PLAN A (REFERENCE EP106) PLAN B (REFERENCE EP107)
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "T6205" - SHT 2
EP125A 0
NONE
DL MORITZ
BW DEEN
NM BROWN
NOTES:
1. FOR KEYNOTES, SEE DWG EP125.
IMAGE
A
EP125
SCALE: NONE
IMAGE
B
EP125
SCALE: NONE
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "TEWT" - DEMO
EO126D 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
EXISTING SECONDARY LOAD SIDE CONDUCTORS FROM POLE
MOUNTED DISCONNECT TO ELEVATED WATER TOWER TO REMAIN
ALONG WITH POLE MOUNTED EQUIPMENT NEAR TOWER. SERVICE
TO THE LINE SIDE OF THE EXISTING FUSED DISCONNECT MAY BE
SWITCHED OVER AND REMOVE WEATHERHEAD, CONDUIT, AND
CONDUCTORS, ONCE THE NEW PAD MOUNTED
TRANSFORMER “TEWT” IS READY TO BE PLACED IN SERVICE AND
NEW UNDERGROUND SECONDARY SERVICE CONDUCTORS ARE
MOUNTED INTO DISCONNECT AND READY TO BE TERMINATED
EXISTING POLE #25 AND SINGLE PHASE 25KVA TRANSFORMER WILL
BE LEFT IN PLACE. CONTRACTOR TO NOTIFY BASE ELECTRICIAN
WHEN READY TO TRANSFER SERVICE FROM POLE MOUNTED
TRANSFORMER TO NEW PAD MOUNTED TRANSFORMER “TEWT”. AT
THAT TIME BASE WILL DISCONNECT PRIMARY SERVICE TO THE
POLE MOUNTED TRANSFORMER AND CONTRACTOR SHALL THEN BE
ALLOWED TO REMOVE AERIAL SECONDARY SERVICE TO EXISTING
DISCONNECT LINE SIDE BY ELEVATED WATER TOWER. BASE WILL
REMOVE POLES AT A LATER DATE WHERE APPLICABLE
LEGEND:
REMOVE
ONE-LINE DIAGRAM FOR TRANSFORMER "TEWT"
AutoCAD SHX Text
EXISTING POLE MOUNTED 25KVA TRANSFORMER ON POLE 25 ALONG MISSION DRIVE
AutoCAD SHX Text
EXISTING EWT CONTROL PANEL AND EQUIPMENT
AutoCAD SHX Text
EXISTING POLE MOUNTED 100A FUSED DISCONNECT
5A
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
TRANSFORMER "TEWT" - NEW
EO126 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
INSTALL NEW SECONDARY SERVICE CONDUCTORS “LVEWT” FROM
PAD MOUNTED TRANSFORMER “TEWT” TO LINE SIDE OF EXISTING
FUSED DISCONNECT THROUGH BOTTOM OF DISCONNECT. TAKE
OUTAGE TO REMOVE EXISTING SERVICE CONDUCTORS FROM POLE
MOUNTED TRANSFORMER
SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND EO06
FOR TRANSFORMER SCHEDULES
NEW ONE-LINE DIAGRAM FOR TRANSFORMER "TEWT"
SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL PRIMARY
CABLE SCHEDULES
SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES4
PROVIDE GROUNDING GRID FOR DISCONNECT AS SHOWN IN
ELECTRICAL BUILDING SERVICE GROUNDING REQUIREMENT DETAIL
AutoCAD SHX Text
EXISTING EWT CONTROL PANEL AND EQUIPMENT
AutoCAD SHX Text
EXISTING POLE MOUNTED 100A FUSED DISCONNECT
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
NEW PAD MOUNTED SWITCH SW#4
AutoCAD SHX Text
"LVTEWT"
AutoCAD SHX Text
"MVSW4/3"
7.6KV 25KVA TRANSFORMER "TEWT" 120/240V, 1ɸ , 3W
E
O E
O E
O E
O E
O E
O E
O E
O E
O E
S A
N S
A N
S A
N S
A N
S A
N S
A N
S A
N S
A N
S A
N S
A N
G G
G
G
G
G
G
G
G
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
C
O
T
EP2
CP1
EP2
CP1
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
S A
N S
A N
S A
N S
A N
S A
N S
A N
S A
N S
A N
S A
N S
A N
G G
G
G
G
G
G
G
G
F O
F O
F O
F O
F O
F O
F O
F O
F O
F O
T
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
G G
G
G
G
G
G
G
G
MVSW4/3
D
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
N
O
R
T
H
ELECTRICAL
ENLARGED SITE PLAN
TRANSFORMER "TEWT"
EP126 0
1" = 20'
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
REMOVE SERVICE WEATHERHEAD AND CONDUIT AT EXISTING
DISCONNECT. PLACE WEATHERPROOF SCREW TYPE CAP ON TOP
OF EXISTING DISCONNECT TO SEAL
NEW SERVICE ENTRY SHALL COME IN BOTTOM OF EXISTIGN
DISCONNECT AND GROUND CONDUIT SHALL ALSO COME OUT OF
DISCONNECT WHERE SHOWN
REMOVE EXISTING OVERHEAD SECONDARY CONDUCTORING FROM
POLE MOUNTED TRANSFORMER ONCE NEW PAD MOUNT
TRANSFORMER “TEWT” IS IN SERVICE. POLE SHOWN IS
POLE 25 LOCATED ALONG MISSION DRIVE
SEE ORIGINAL LAYOUT DRAWINGS EP107, 107A, AND 107B FOR
COMPLETE ROUTING AND LOCATION OF TRANSFORMER “TEWT”
IMAGE
A
EP126
SCALE: NONE
I
M
A
IMAGE
B
EP126
SCALE: NONE
IMAGE
C
EP126
SCALE: NONE
IMAGE C
I M
A
OE OE
EXISTING OVERHEAD
ELECTRICAL SECONDARY
TO BE REMOVED
OE OE OE
OE
OE
OE
OE
OE OE OE
OE
OE
OE
OE
OE
EXISTING DISCONNECT,
TO BE RESERVICED
FROM BOTTOM PER
IMAGE A
NEW
TRANSFORMER
"TEWT"
CIRCUIT
"LVTEWT"
OE
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
XFER "T6415" & BLDG 6416 - DEMO
EO127D 0
1" = 10'
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE
MOUNTED TRANSFORMERS TO WEATHERHEADS AND CONDUIT
DOWN TO THE EXISTING DISCONNECTS AND WEATHERHEADS INTO
BUILDINGS. WHERE APPLICABLE REMOVE WEATHERHEADS AND
PLACE “LB” CONDUIT BODIES TO EXTEND NEW SERVICES FROM
ELECTRICAL EQUIPMENT STAND DISCONNECTS TO APPROPRIATE
CONDUIT BUILDING ENTRANCES FOR BUILDINGS 6415 AND 6416
WHICH WILL BE NEW UNDERGROUND BRANCH CIRCUITS PER ONE
LINE DIAGRAMS. REMOVE ONCE NEW METER ENCLOSURE AND
PANEL MDP IS IN PLACE AND NEW SERVICES ARE READY TO BE
PLACED IN SERVICE
THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.
CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO
TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO
NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL
DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED
TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO
REMOVE AERIAL SECONDARY SERVICE CONDUCTORS. BASE WILL
LEAVE EXISTING POLE. BASE TO REMOVE TRANSFORMERS AT A
LATER DATE
ONE-LINE DIAGRAM FOR TRANSFORMER "T6415"
LEGEND:
REMOVE
1 2
SIZE TO BE
FIELD VERIFIED
AutoCAD SHX Text
600A MCB
AutoCAD SHX Text
BLDG 6415 SERVICE PANEL
AutoCAD SHX Text
EXISTING POLE MOUNTED 3-100KVA TRANSFORMERS
AutoCAD SHX Text
XXX
AutoCAD SHX Text
150A MCB
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
400A 250AF
AutoCAD SHX Text
200A MCB
AutoCAD SHX Text
BLDG 6415 PANEL
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
METER ENCLOSURE ON POLE
AutoCAD SHX Text
225A MCB
AutoCAD SHX Text
BLDG 6416 SERVICE PANEL
METER ENCLOSURE TO BE RELOCATED TO ELECTRICAL EQUIPMENT STAND BY BLDG 6415
15A
A
1 2
C A
R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
Texas Firm Registration No.: F-174
AT FULL SIZE
IN
cm0 1
3 4
USDA-APHIS-PPQ MOORE AIR BASE
ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE
CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.
CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT
LOCATIONS OF EXISTING UTILITIES FROM UTILITY
COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
05-09-2022
116530
ERNEST E. LEAF
ELECTRICAL
ONE-LINE DIAGRAM
XFER "T6415" & BLDG 6416 - NEW
EO127 0
NONE
DL MORITZ
BW DEEN
NM BROWN
KEYNOTES:
PROVIDE A NEW 1,000 AMP METER ENCLOSURE FOR 3 PHASE, 4
WIRE INSTALLATION. LOCATE ON UNISTRUT EQUIPMENT STAND
PER DETAILS AS REQUIRED. PROVIDE METERING TRANSFORMER
ENCLOSURE WITH CT ANDF PT TRANSFORMERS TO SERVICE
METER
COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF
SERVICE TO POLE MOUNTED TRANSFORMERS AND TO ENERGIZE
NEW PAD MOUNTED TRANSFORMER T6415. COORDINATE
REQUIRED CONNECTIONS TO MAINTAIN OPEN SECTIONS OF NEW
UNDERGROUND DISTRIBUTION AS REQUIRED DURING PHASING OF
WORK
NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6415"
SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND EO06
FOR TRANSFORMER SCHEDULES
SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL PRIMARY
CABLE SCHEDULES
SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5
PROVIDE A NEW 1,000A, 3 PHASE, 4…