This solicitation is for a combined underground utilities and storm water improvements project at Moore Air Base in Edinburg, Texas. The solicitation was issued by the Department of Agriculture Animal and Plant Health Inspection Service Marketing and Regulatory Programs Business Services. The project involves installing new underground electrical cabling and equipment as part of Phase 2 of the work. Bidders should disregard any references in the design drawings or specifications related to future work or Add Alternate 1B, as those aspects are not included in this project scope. The response due date and anticipated award date are not provided in the document.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

O

O

R

E

F

I E

L D

R

C

O

U

N

T

Y

A

C

O

U

N

Y

MOORE AIR BASE

PROJECT

LOCATION

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

PHASE 2 ELECTRICAL CABLING AND EQUIPMENT DESIGN

EDINBURG, TEXAS

27100.26

MAY 09, 2022

DL MORITZ

EE LEAF

05-09-2022

116530

ERNEST E. LEAF

COVER SHEET

GG01 0

AS NOTED

DL MORITZ

BW DEEN

NM BROWN

NORTH

USDA-APHIS-PPQ

MOORE AIR BASE

PHASE 2 ELECTRICAL CABLING & EQUIPMENT DESIGN

EDINBURG, TEXAS

USDA CONTRACT NO: AG-6395-C-16-0119

PROJECT LOCATION PLAN

PROJECT LOCATION MAP

HORIZONTAL DATUM TEXAS STATE PLANE SOUTH US FOOT

VERTICAL DATUM (NAVD 88)

REGIONAL LOCATION PLAN

FOR REFERENCE ONLY

SHEET NO. SHEET TITLE REV NO.

GG01 COVER SHEET 0

GG02 INDEX SHEET 1

ELECTRICAL SHEETS

EO121D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TGH" - DEMO 0

EO121D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TGH" - NEW 0

EO122D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6021" - DEMO 0

EO122 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6021" - NEW 0

EP122 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6021" 0

EO123D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6017" - DEMO 0

EO123D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6017" - NEW 0

EP123 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6017" - SHT 1 0

EP123A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6017" - SHT 2 0

EO124D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6101" - DEMO 0

EO124D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6101" - NEW 0

EP124 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6205" - SHT 1 0

EP125 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6205" - SHT 1 0

EP125A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6205" - SHT 2 0

EO126D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TEWT" - DEMO 0

EO126D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "TEWT" - NEW 0

EP126 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "TEWT" 0

EO127D ELECTRICAL - ONE-LINE DIAGRAM - XFER "T6415" & BLDG 6416 - DEMO 0

EO127 ELECTRICAL - ONE-LINE DIAGRAM - XFER "T6415" & BLDG 6416 - NEW 0

EP127 ELECTRICAL - ENLARGED SITE PLAN - XFER "T6415" & BLDG 6416 - SHT 1 0

EP127A ELECTRICAL - ENLARGED SITE PLAN - XFER "T6415" & BLDG 6416 - SHT 2 0

EP128 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6403" - SHT 1 0

EP128A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6403' - SHT 2 0

EO129D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6409" - DEMO 1

EO129 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6409" - NEW 1

EP129 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6409" 1

EP130 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6411" 0

EP131 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6414" 0

EP132 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6418" 0

EO133D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6407" - DEMO 0

EO133 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6407" - NEW 0

EP133 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6407" 0

EO134D ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6420" - DEMO 0

EO134 ELECTRICAL - ONE-LINE DIAGRAM - TRANSFORMER "T6420" - NEW 0

EP134 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6420" 0

EP135 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T3207" 0

EP136 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6417" - SHT 1 0

EP136A ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6417" - SHT 2 0

EP137 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "T6430" 0

EP140 ELECTRICAL - ENLARGED SITE PLAN - TRANSFORMER "TMF" 0

EU503 SITE ELECTRICAL DETAILS - SHEET 3 0

EU507 SITE ELECTRICAL DETAILS - SHEET 7 0

EU508 SITE ELECTRICAL DETAILS - SHEET 8 0

EO00 ELECTRICAL OVERALL-ONE-LINE DIAGRAM 1

EO02 SITE ELECTRICAL PRIMARY-CABLE SCHEDULE - SHEET 1 0

EO03 SITE ELECTRICAL PRIMARY-CABLE SCHEDULE - SHEET 2 1

EO04 SITE ELECTRICAL SECONDARY-CABLE SCHEDULE 1

EO05 SITE ELECTRICAL-EXISTING TRANSFORMERS 1

EO06 SITE ELECTRICAL-NEW TRANSFORMER REQUIREMENTS 1

EO07 SITE ELECTRICAL-SECTIONALIZING CABINETS AND PAD MOUNTED SWITCHES 1

EO08 SITE ELECTRICAL-NEW ELECTRICAL MANHOLES 0

EO09 SITE ELECTRICAL-COMMUNICATION CONDUIT AND CABLE SCHEDULE - SHEET 1 0

INDEX SHEET

GG02 1

AS NOTED

DL MORITZ

BW DEEN

NM BROWN

1 REMOVED TCT AND TARS NAL NAL EEL 06-22-2022

D

A

1 2

C

AD

D D

3- R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com Texas Firm Registration No.: F-174

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA-APHIS-PPQ MOORE AIR BASE

PHASE 2 ELECTRICAL CABLING AND EQUIPMENT DESIGN

EDINBURG, TEXAS

27100.26

MAY 09, 2022

DL MORITZ

EE LEAF

NOTE: THE SIZE, NUMBER AND LOCATION OF EXISTING

UTILITIES SHOWN ON THIS DRAWING ARE APPROXIMATE AND

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

06-22-2022

DRAWING INDEX SCOPE OF WORK STATEMENT:

THIS CONTRACT IS TO INSTALL THE FOLLOWING CABLING AND EQUIPMENT. THERE IS ALSO SOME DEMOLITION OF

SOME OF THE EXISTING DISTRIBUTION SYSTEM AS SHOWN ON EACH LOCATION DRAWING:

MEDIUM VOLTAGE ELECTRICAL INSTALLATION:

MEDIUM VOLTAGE RISER POLE

MEDIUM VOLTAGE UG CONDUIT EXTENSIONS OF "EP2" AND "EP4" TO REQUIRED TRANSFORMER LOCATIONS

MEDIUM VOLTAGE 4 WAY JUNCTIONS INSTALLED IN EXISTING SECTIONALIZING CABINETS

MEDIUM VOLTAGE PME-9 PAD MOUNTED SWITCHES

PAD MOUNTED SERVICE TRANSFORMERS

MEDIUM VOLTAGE ELECTRICAL CABLE

MEDIUM VOLTAGE LOAD BREAK ELBOWS

LOW VOLTAGE ELECTRICAL SERVICES INSTALLATION:

LOW VOLTAGE UG CONDUIT EXTENSIONS OF "LV***" CIRCUITS FROM ASSOCIATED TRANSFORMERS TO

BUILDINGS/SERVICE ELECTRICAL EQUIPMENT ON EXTERIOR STANDS WHERE SHOWN.

LOW VOLTAGE BRANCH CIRCUIT MODIFICATIONS WHERE SHOWN TO RESERVICE EXISTING LOCATION LOADS

SUCH AS PANELS, SITE LIGHTING, DISCONNECTS, ETC.

LOW VOLTAGE SERVICE CABLES

LOW VOLTAGE BRANCH CIRCUIT CABLES

DEMOLITION TO INCLUDE REMOVAL OF EXISTING OVERHEAD SECONDARY SERVICE CONDUCTORS AS SHOWN ON

PLAN DRAWINGS AND NOTES.

DEMOLITION OF EXISTING TRANSFORMER MEDIUM VOLTAGE SERVICE RISER CONDUITS AND ASSOCIATED MV CABLE AFTER DISCONNECTION BY BASE AT THE EXISTING POLE TOP FUSED CUT OUT ASSEMBLIES.

COORDINATION WITH BASE OF EACH LOCATION SERVICE TRANSFER FROM EXISTING OVERHEAD ELECTRICAL DISTRIBUTION TO NEW UNDERGROUND MEDIUM VOLTAGE DISTRIBUTION SYSTEM SECTIONALIZING CABINET, OR

PAD MOUNTED SWITCH AND ASSOCIATED PAD MOUNTED TRANSFORMER.

EXISTING OVERHEAD ELECTRICAL DISTRIBUTION SYSTEM AND POLE MOUNTED TRANSFORMERS (EXCEPT FOR TRANSFORMER RISERS REMOVED IN DEMOLITION STATED ABOVE), WILL BE BY BASE AFTER COMPLETION OF

CONTRACT.

SEE REFERENCE DRAWINGS INCLUDED FROM PRIOR PROJECT WHICH HAVE INSTALLED THE FOLLOWING FOR

USE IN THIS SCOPE OF WORK:

UNDERGROUND "EP2" AND "EP4" CONDUIT SYSTEM FOR MEDIUM VOLTAGE CABLES TO BE INSTALLED . THERE WILL NEED TO BE EXTENSION OF THESE CONDUITS WHERE SHOWN ON DRAWINGS TO EXISTING PAD MOUNTED

TRANSFORMERS TO BE RESERVICED.

UNDERGROUND "MV****" CIRCUITS ARE SHOWN FROM PAD MOUNTED SWITCHES AND SECTIONALIZING CABINETS

THAT WILL NEED TO BE EXTENDED WHERE SHOWN ON DRAWINGS.

PAD MOUNTED TRANSFORMERS AND SWITCHES. CONCRETE PADS, BOX EXTENSIONS, AND SECTIONALIZING CABINET HOUSINGS FOR LOW VOLTAGE CONDUIT SERVICE STUBOUTS FROM NEW PAD MOUNTED TRANSFORMERS

EXTENDED AS SHOWN ON NEW INDIVIDUAL SITE PLAN DRAWINGS OF NEW WORK.

COMMUNICATION CONDUIT SYSTEM AND OPTICAL COMMUNICATION HOUSINGS AND HANDHOLE SYSTEMS WHICH

ARE NOT AFFECTED BY THIS CONTRACT.

WHEN TRANSFERRING ELECTRICAL SERVICES FOR FACILITIES, CONTACT BASE ELECTRICIANS MINIMUM OF 2

WEEKS PRIOR TO COORDINATE REQUIREMENTS.

FOR ALL SITE PLANS, DEMOLITION ONE LINE DIAGRAMS, AND NEW ONE LINE DIAGRAMS, SEE ALL EQUIPMENT

SCHEDULES, CABLE SCHEDULES, AND OVERALL SYSTEM RISER IN DRAWINGS EO00 - EO09.

OPTICAL CROSS CONNECT AND COMMUNICATION HANDHOLES ARE EXISTING. ONLY SHOWN FOR REFERENCE.

THIS PROJECT WILL REQUIRE COORDINATION AND A PHASING ISSUE WITH THE BASE AND BASE ELECTRICIANS. IT IS ANTICIPATED THAT THE UNDERGROUND SYSTEM WILL BE ENERGIZED IN PHASES AND SECTIONALIZING CABINETS AND SWITCHES WILL HAVE TO HAVE CERTAIN SECTIONS ISOLATED DURING INSTALLTION AND LOCK OUT/TAG OUT PROCEDURES IN PLACE. DAILY REVIEW OF ENERGIZED STATUS OF SECTIONS OF BOTH GRIDS MUST OCCUR BETWEEN BASE AND CONTRACTOR FROM START TO END OF PROJECT AND DUAL LOCKOUTS WITH BASE AND CONTRACTOR LOCKS ON SWITCHES MUST OCCUR AND BE VERIFIED BY ALL PARTIES DURING CONSTRUCTION.

BEFORE RELEASING SECTION OF LINE TO BE ENERGIZED, EACH PARTY MUST REMOVE OWN LOCKS AND TAGS AND

SIGN OFF ON DAILY OUTAGE FORM TO BE DETERMINED BETWEEN PARTIES.

CONTRACTOR TO COORDINATE PROTECTIVE FUSE SIZING AS REQUIRED AND PROVIDE CHANGES IN FUSE SIZES, IF

REQUIRED.

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

NOTE: THE SIZE, NUMBER AND LOCATION OF EXISTING

UTILITIES SHOWN ON THIS DRAWING ARE APPROXIMATE AND

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "TGH" - DEMO

EO121D 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

REMOVE EXISTING SECONDARY CONDUCTORS FROM POLE

MOUNTED TRANSFORMERS DOWN THE POLE AND INTO EXISTING

METER BASE ONCE THE NEW PAD MOUNTED TRANSFORMER TGH IS

READY TO BE PLACED IN SERVICE.

THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.

CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO

TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO

NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL

DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED

TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO

REMOVE CONDUITS AND SECONDARY SERVICE CONDUCTORS.

CONTRACTOR SHALL REMOVE ALL SERVICE CONDUITS TO BELOW

GRADE TO POINT OF RUNNING HORIZONTAL TO GRADE. BASE WILL

REMOVE POLES AND POLE MOUNTED TRANSFORMERS, AT A LATER

DATE WHERE APPLICABLE.

LEGEND:

REMOVE

ONE-LINE DIAGRAM FOR TRANSFORMER "TGH"

AutoCAD SHX Text

LIFT STATION

AutoCAD SHX Text

200A FUSE 3P S/N IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

GUARD HOUSE

AutoCAD SHX Text

GEN

AutoCAD SHX Text KOHLER 208V, 4P, 200A AUTOMATIC TRANSFER SWITCH IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

EXISTING TO REMAIN

AutoCAD SHX Text

40KW STANDBY GENERATOR

AutoCAD SHX Text

METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND TO REMAIN

AutoCAD SHX Text

(2)3-#3/0, #4GND (3")C

AutoCAD SHX Text

EXISTING (3)25KVA POLE MOUNTED TRANSFORMER

AutoCAD SHX Text

EXISTING TO REMAIN

5A

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "TGH" - NEW

EO121 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

INSTALL NEW SECONDARY SERVICE CONDUCTORS FROM

TRANSFORMER TGH TO LINE SIDE OF EXISTING METER BASE. TAKE

OUTAGE TO REMOVE EXISTING SERVICE CONDUCTORS FROM POLE

MOUNTED TRANSFORMERS

EXISTING SERVICES TO THE LIFT STATION AND GUARD HOUSE

FROM THE TRANSFER SWITCH WILL REMAIN

SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND

EO06 FOR TRANSFORMER SCHEDULES

SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL

PRIMARY CABLE SCHEDULES

SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5

NEW ONE-LINE DIAGRAM FOR TRANSFORMER "TGH"

1 5

3 4

AutoCAD SHX Text

METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

"LVTGH"

AutoCAD SHX Text

LIFT STATION

AutoCAD SHX Text

200A FUSE 3P S/N IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

GUARD HOUSE

AutoCAD SHX Text

GEN

AutoCAD SHX Text KOHLER 208V, 4P, 200A AUTOMATIC TRANSFER SWITCH IN NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

EXISTING TO REMAIN

AutoCAD SHX Text

40KW STANDBY GENERATOR

AutoCAD SHX Text

NEW PAD MOUNTED SWITCH SW#1

AutoCAD SHX Text

"MVSW1/3"

AutoCAD SHX Text

13.2KV 75KVA TRANSFORMER "TGH" 208Y/120V, 3ɸ, 4W

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

O

E

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

SAN SAN SAN

SS

SS

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

PROVIDE AEP CONNECTION

40' CLASS 2 WESTERN RED CEDAR

RISER AEP METER POLE, EXTEND EP2

CONDUITS AS SHOWN AT THIS

LOCATION FOR EXTENSION

TO AEP PRIMARY METERING POLE,

PROVIDE MUAEP CABLES

PME-9

PAD MOUNTED

SWITCHGEAR SW#1

4 WAY SECTIONALIZER SC#1

75KVA TRANSFORMER

208/120V 3Ø 4W, "TGH"

2-4" CONDUIT STUBBED

10' FROM PAD

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "TGH"

EP121 0

1" = 10'

DL MORITZ

BW DEEN

NM BROWN

M

V

S

C

M

V

S

C

OCC#1

CHH#1

C

P

E

P

E

P

U

A

E

P

IMAGE

A

EP121

SCALE: NONE

N

O

R

T

H

TO GUARD HOUSE

INSTALL NEW CONDUIT

FROM PAD MOUNTED

TRANSFORMER

TO METER BASE

I M

A

G

E

EXISTING

METER SOCKET

EXISTING SERVICES TO LIFT

STATION AND GUARD HOUSE

EXISTING SERVICES TO LIFT

STATION AND GUARD HOUSE

EXISTING ELECTRICAL

EQUIPMENT RACK

EXISTING KOHLER GENERATOR3

CIRCUIT "LVTGH"4

IMAGE

B

EP121

SCALE: NONE

IM

AG

E B

KEYNOTES:

REMOVE CONDUIT FROM POLE PER ONE LINE DIAGRAM ONCE NEW

SERVICE IS IN PLACE

SAW CUT CONCRETE AND INSTALL NEW “LVTGH” REQUIREMENTS

PER ONE LINE DIAGRAM INTO METER ENCLOSURE. PLACE

OVERSIZED PVC SLEEVE AROUND CONDUIT AND CAST INTO

CONCRETE WHEN REFORMING SAW CUT AREA. PLACE CONDUIT

SEAL IN OLD CONDUIT INTERNAL TO THE METER SOCKET TO

PREVENT INTRUSION WHICH MAY BE REMOVED IN FUTURE IF

NEEDED

EP2 MVSW1/3

TO TRANSFORMER

"TGH"

MOBILE BUILDING

IMAGE

C

EP121

SCALE: NONE

I

M

A

C

5 MOBILE BUILDING IS SERVICED FROM TRANSFORMER "TGH" BUT

CONFIRM WITH GOVT PRIOR TO OUTAGE

6 INSTALL EQUIPMENT ON EXISTING PAD POURED DURING PRIOR

PROJECT

MVSW1/2EP2

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "T6021" - DEMO

EO122D 0

NONE

DL MORITZ

BW DEEN

NM BROWN

BWD

KEYNOTES:

REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE

MOUNTED TRANSFORMER TO WEATHERHEAD AND CONDUIT DOWN

TO THE EXISTING EXTERIOR PANELBOARD 1P ONCE NEW METER

ENCLOSURE IS IN PLACE AND NEW SERVICES READY TO BE

PLACED IN SERVICE.

THE EXISTING POLE AND TRANSFOMRER WILL BE LEFT IN PLACE.

CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO

TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO

NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL

DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED

TRANSFORMER AND CONTRACTOR SHALL THEN BE ALLOWED TO

REMOVE CONDUITS AND SECONDARY SERVICE CONDUCTORS.

BASE WILL REMOVE POLES AT A LATER DATE WHERE APPLICABLE.

LEGEND:

REMOVE

THERE IS AN EXISTING BRANCH CIRCUIT FROM PANEL 1P ROUTED IN

SAME CONDUIT AND WEATHERHEAD AS THE SERVICE TO THE

BUILDING. IT IS FED FROM A 70A, 2 POLE BREAKER LOCATED IN THE

PANEL 1P. REMOVE THIS BRANCH CIRCUIT ONCE THE CIRCUIT IS

REROUTED THRU THE BUILDING PER THE NEW ONE LINE DIAGRAM

REQUIREMENTS. AT BUILDING REMOVE THE SECOND

WEATHERHEAD AND PLACE A METAL EXPANDABLE WATERPROOF

SEAL PLUG IN EXTERIOR OF BUILDING FOR THIS WEATHERHEAD

ENTRANCE INTO BUILDING. PLUG ALL REMOVED CONDUIT

PENETRATIONS WHICH HELD SERVICE CONDUIT DOWN SIDE OF

BUILDING TO PANEL 1P.

1 2

ONE-LINE DIAGRAM FOR TRANSFORMER "T6021"

AutoCAD SHX Text

EXISTING 25KVA POLE MOUNTED TRANSFORMER

AutoCAD SHX Text

PANEL #1 INSIDE BLDG

AutoCAD SHX Text 100A 2P

AutoCAD SHX Text 70A 2P

AutoCAD SHX Text

PANEL 1P

AutoCAD SHX Text

PANEL #2 INSIDE BLDG

3-#4

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "T6021" - NEW

EO122 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

PROVIDE A NEW 200 AMP METER ENCLOSURE FOR 1 PHASE, 3 WIRE

INSTALLATION. LOCATE ON STAINLESS STEEL UNISTRUT STANDOFF

FROM THE BUILDING AS REQUIRED FOR SIDING CORUGATIONS.

COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF

SERVICE TO POLE MOUNTED TRANSFORMER AND TO

ENERGIZE NEW PAD MOUNTED TRANSFORMER "T6021". AT

ADJACENT PAD MOUNTED SECTIONALIZING CABINET,

COORDINATE REQUIRED CONNECTIONS TO MAINTAIN OPEN

SECTIONS AS REQUIRED DURING PHASING OF WORK.

SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND

EO06 FOR TRANSFORMER SCHEDULES.

SEE DRAWING EO02 AND EO03FOR SITE ELECTRICAL

PRIMARY CABLE SCHEDULES.

SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES.5

PROVIDE A NEW 200A, 1 PHASE, 3 WIRE PANELBOARD IN

LOCKABLE NEMA 3R ENCLOSURE FOR PANEL 1P. PANEL TO

HAVE A 200A MAIN CIRCUIT BREAKER AND 100A, 2 POLE AND

70A, 2 POLE BREAKER BRANCH BREAKER TO RESERVICE

EXISTING LOADS. PANEL SHALL ALSO BE PROVIDED WITH

120KA SEVEN MODE TVSS DIRECTED CONNECTED TO BUS.

PANEL SHALL BE SERVICE ENTRANCE RATED. ROUTE THE

NEW SERVICE LVT6021 FRM NEW PAD MOUNT TRANSFORMER

INTO BOTTOM OF PANEL.

IN BACK OF PANEL 1P, PLACE A CONDUIT NIPPLE INTO

BUILDING AND ROUTE NEW BRANCH CIRCUIT AS SHOWN ON

ONE LINE DIAGRAM TO EXISTING PANEL 2 INSIDE OF

BUILDING. CONTRACTOR SHALL ROUTE WITH BUILDING LINES

AS DIRECTED BY GOVT.

LOCATE PANEL MDP6021 TO ALLOW EXISTING 100A, BRANCH

CIRCUIT CABLING TO REACH NEW 100 AMP BRANCH BREAKER

TERMINALS.

NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6021"

3 4

AutoCAD SHX Text

3#4 W/#8 GND (1.25") RGS CONDUIT

AutoCAD SHX Text 100A 2P

AutoCAD SHX Text 70A 2P

AutoCAD SHX Text

NEW PANEL "MDP6021"

AutoCAD SHX Text 5A

AutoCAD SHX Text

SECTIONALIZING CABINET SC#2

AutoCAD SHX Text 200A 2P

AutoCAD SHX Text

TVSS

AutoCAD SHX Text

PANEL #1 INSIDE BLDG

AutoCAD SHX Text

PANEL #2 INSIDE BLDG

AutoCAD SHX Text

"LVT6021"

AutoCAD SHX Text

NEW 200 AMP METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON BUILDING

AutoCAD SHX Text

"LVT6021"

AutoCAD SHX Text

7.6KV 25KVA TRANSFORMER "T6021" 120/240V, 1ɸ, 3W

AutoCAD SHX Text

"MVSC2/3"

120/240V, 1ɸ, 3W 10KAIC

N

F

EXTEND CONDUIT

TO NEW METER

ENCLOSURE

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

N

O

R

T

H

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "T6021"

EP122 0

1" = 10'

DL MORITZ

BW DEEN

NM BROWN

25KVA TRANSFORMER

120/240V 1Ø 3W, "T6021"

E P

M V

S C

IMAGE

A

EP122

SCALE: NONE

IMAGE A

IMAGE

B

EP122

SCALE: NONE

TO BLDG LOADS

IMAGE

C

EP122

SCALE: NONE

IMAGE B

IMAGE C

KEYNOTES:

IN IMAGE “A” REMOVE EXISTING SECONDARY SERVICE

CONDUCTORS FROM TRANSFORMER POLE, WEATHERHEAD AND

EXISTING 70A BRANCH CIRCUIT AFTER NEW METER ENCLOSURE IS

IN PLACE AND PANEL 1P IS READY TO BE CHANGED OUT. CONTACT

BASE FOR VERIFICATION THAT TRANSFORMER IS DE-ENERGIZED

PRIOR TO REMOVAL FOR ALL OVERHEAD TRANSFORMER

SECONDARY SERVICE LOCATION REMOVALS.

IMAGE “B” SHOWS EXISTING PANEL 1P AND 100A AND 70A

BRANCH BREAKER TO BE REMOVED.

EXISTING WEATHERHEADS TO BE REMOVED ALONG WITH

CONDUITS AND ATTACHMENTS TO BUILDING. PROVIDE

WETAHERPROOF PLUGS AND APPROVED SEALING MEANS

FOR ALL OPENINGS LEFT AFTER CONDUITS AND

ATTACHMENTS HAVE BEEN REMOVED.

NEW PANEL 1P

EXISTING PANEL #1

EXISTING PANEL #2

SEE KEY NOTE 3

ON ONE-LINE DIAGRAM,

DWG EO122

LEGEND:

REMOVE

DETAIL A

DETAIL A

36" BELOW GRADE TO

TRANSFORMER T6021

EXISTING 100

AMP SERVICE

INTO BUILDING

70A NEW BRANCH

CIRCUIT TO PANEL #2

INSIDE BUILDING

NEW PANEL 1P NEW METER

ENCLOSURE

NOTES:

1. REFERENCE PHASE 1 DRAWINGS FOR ROUTES.

LOCATE NEW

PANEL TO REUSE

EXISTING 100A

BRANCH CIRCUIT

CONDUCTORS & CONDUITS

#6 AWG

TO GROUND GRID,

SEE DETAIL, ON DWG EU503

LOCATION TO BE VERIFIED

LOCATION TO BE VERIFIED

NEW METER

ENCLOSURE

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "T6017" - DEMO

EO123D 0

NONE

DL MORITZ

BW DEEN

NM BROWN

DLM

KEYNOTES:

REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE

MOUNTED TRANSFORMERS TO WEATHERHEAD AND IN CONDUIT

DOWN TO THE EXISTING MANUAL DOUBLE THROW SWITCH ONCE

NEW METER ENCLOSURE AND PANEL MDP IS IN PLACE AND NEW

SERVICES READY TO BE PLACED IN SERVICE

THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.

CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO

TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO

NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL

DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED

TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO

REMOVE AERIAL SECONDARY SERVICE CONDUCTORS. BASE WILL

REMOVE TOP OF THIS POLE AT A LATER DATE WHERE APPLICABLE

TO CONTINUE SERVICE TO EXISTING SITE LIGHTS AND HAZ MAT

DISCONNECT

LEGEND:

REMOVE

ONE-LINE DIAGRAM FOR TRANSFORMER "T6017"

AutoCAD SHX Text

EXISTING POLE MOUNTED 3-37.5KVA TRANSFORMER BANK

AutoCAD SHX Text 300A

AutoCAD SHX Text

200AF

AutoCAD SHX Text

EXISTING OH TO POLE MOUNTED SITE LIGHTS

AutoCAD SHX Text

TO BLDG 6017

AutoCAD SHX Text

TO BLDG 6017

AutoCAD SHX Text

EXISTING OH TO POLE MOUNTED DISCONNECT FOR HAZ-MAT

AutoCAD SHX Text

NON-FUSIBLE MANUAL DPDT MANUAL TRANSFER SWITCH IN LOCKABLE NEMA 3R ENCLOSURE

AutoCAD SHX Text

METER ENCLOSURE

AutoCAD SHX Text

GEN

AutoCAD SHX Text

TEMPORARY GENERATOR

EXISTING GENERATOR RECEPTACLE FOR TEMPORARY GENERATOR

8A

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "T6017" - NEW

EO123 0

NONE

DL MORITZ

BW DEEN

NM BROWN

BWD

KEYNOTES:

PROVIDE A NEW 600 AMP METER ENCLOSURE FOR 3 PHASE, 4 WIRE

INSTALLATION. LOCATE ON STAINLESS STEEL UNISTRUT

EQUIPMENT STAND EXTENSION FROM EXISTING POLES AND

STANDOFF FROM THE FRAME AS REQUIRED. PROVIDE AN

ADJACENT METERING TRANSFORMER ENCLOSURE WITH CT AND PT

TRANSFORMERS TO SERVICE METER

COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF

SERVICE TO POLE MOUNTED TRANSFORMERS AND TO ENERGIZE

NEW PAD MOUNTED TRANSFORMER T6017. AT ADJACENT PAD

MOUNTED SWITCH, COORDINATE REQUIRED CONNECTIONS TO

MAINTAIN OPEN SECTIONS AS REQUIRED DURING PHASING OF

WORK

SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND EO06

FOR TRANSFORMER SCHEDULES

SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL PRIMARY

CABLE SCHEDULES

SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5

PROVIDE A NEW 600A, 3 PHASE, 4 WIRE PANELBOARD IN LOCKABLE

NEMA 3R ENCLOSURE FOR PANEL MDP. PANEL TO HAVE A 500A

MAIN CIRCUIT BREAKER TRIP AND BRANCH BREAKERS AS SHOWN

TO RESERVICE EXISTING LOADS. PANEL SHALL ALSO BE

PROVIDED WITH 160KA SEVEN MODE TVSS DIRECTLY CONNECTED

TO BUS. PANEL SHALL BE SERVICE ENTRANCE RATED. ROUTE THE

NEW SERVICE LVT6017 FROM NEW PAD MOUNT TRANSFORMER

INTO BOTTOM OF METER ENCLOSURE AND THEN TO MDP PANEL

FROM 400A BRANCH BREAKER IN PANEL MDP, ROUTE

CONDUCTORS SHOWN TO EXISTING MANUAL TRANSFER SWITCH.

THE LOAD SIDE OF TRANSFER SWITCH WILL REMAIN AS IS WITH

EXISTING OVERHEAD SERVICES INTO THE BUILDING

PROVIDE CIRCUITS AS SHOWN FROM PANEL MDP BACK TO

EXISTING POLE UNDERGROUND AT 3' BELOW GRADE AND ROUTE

OVER AND UP POLE WITH CONDUIT STANDOFFS UP TO HEIGHT OF

EXISTING AERIAL SECONDARY SERVICE TO HAZ MAT AREA

DISCONNECT AND SITE LIGHTING. COMBINE CIRCUITS IN 2 INCH

RGS CONDUIT AND AT TOP OF THE 2 INCH RGS CONDUIT PLACE

WEATHERHEAD AND ROUTE CONDUCTORS OUT WITH DRIP LOOP

TO BE CRIMPED ONTO EXISTING CONDUCTORING. COVER

CONNECTIONS WITH HEAT SHRINK ONCE IN PLACE.

3 4

NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6017"

AutoCAD SHX Text

EXISTING 100A 3P

AutoCAD SHX Text

GEN

AutoCAD SHX Text

TEMPORARY GENERATOR

AutoCAD SHX Text

NEW 600 AMP METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

"LVT6017"

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text 100A 3P

AutoCAD SHX Text

NEW PANEL "MDP6017"

AutoCAD SHX Text

600AF 3P 500AT

AutoCAD SHX Text

NEW PAD MOUNTED SWITCH SW#2

AutoCAD SHX Text

"MVSW2/3"

AutoCAD SHX Text

"LVT6017"

AutoCAD SHX Text 30A 2P

AutoCAD SHX Text

TVSS

AutoCAD SHX Text

22,000AIC

AutoCAD SHX Text

208V, 3ɸ, 4W, 600A BUS

AutoCAD SHX Text

4#2 W/#6 GND (2") RGS CONDUIT

AutoCAD SHX Text

4#600MCM W/ 1/0 GND (4") RGS CONDUIT

AutoCAD SHX Text

EXISTING GENERATOR RECEPTACLE FOR TEMPORARY GENERATOR

AutoCAD SHX Text 300A

AutoCAD SHX Text

200AF

AutoCAD SHX Text

HAZ-MAT

AutoCAD SHX Text 3#6

AutoCAD SHX Text

EXISTING SITE LIGHTING

AutoCAD SHX Text

METER ENCLOSURE

13.2KV 150KVA TRANSFORMER "T6017" 208Y/120V, 3ɸ, 4W

O/E

O/EO/EO/E

O/E

O/EO/E

O/EO/E

O/E

O/EO/E

O/EO/E

O/E

O/EO/E

O/EO/E

O/E

O/E O/E

O/EO/E

O/E

O/EO/EO/E

O/E

O/EO/E

O/EO/E

O/E

O/EO/E

O/EO/E

O/E

O/EO/E

O/EO/E

O/E

O/E O/E

O/EO/E

W

W

W

CO

ELECT. PANEL

FO DEPTH: 1.58'

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

PME-9 SW#2

150KVA TRANSFORMER

208/120V 3Ø 4W, "T6017"

EP2

EP2

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "T6017" - SHT 1

EP123 0

1" = 10'

DL MORITZ

BW DEEN

NM BROWN

EP2 MVSW2/3

MVSC1/2

MVSW2/4

N

O

R

T

H

IMAGE

B

EP123

SCALE: NONE

IMAGE

A

EP123

SCALE: NONE

I

M

A

B

IMAGE A

KEYNOTES:

EXISTING POLES AND SECONDARY BRANCH CIRCUIT AERIAL

CONDUCTORS FROM LOAD SIDE OF NEW PANEL MDP TO REMAIN

EXISTING POLE MOUNTED EQUIPMENT STAND TO REMAIN AND BE

ENLARGED TO ALLOW FOR NEW METER ENCLOSURE AND PANEL

MDP

I

M

A

CONTRACTOR HAS OPTION TO INSTALL WOOD POLE OR 6 INCH

STEEL PIPE FILLED WITH CONCRETE IN 12 INCH SONO TUBE

CONCRETE FILLED FOUNDATION DOWN 4 FEET FOR EXTENDING

ELECTRICAL EQUIPMENT STAND. USE GALVANIZED STEEL

UNISTRUT 1 7/8 INCH MINIMUM FOR CROSS BRACING

NEW PANEL "MDP6017" PER ONE LINE DIAGRAM4

NEW METER ENCLOSURE WITH INTEGRAL METERING

TRANSFORMERS AS REQUIRED

REUSE SPOOL INSULATORS FOR CONNECTION OF EXISTING AERIAL

CONDUCTORS TO HAZ MAT AND SITE LIGHTING CIRCUITS. SEE ONE

LINE DIAGRAM

REMOVE AERIAL SERVICE CONDUCTORS FROM TRANSFORMERS TO

MANUAL TRANSFER SWITCH PER DEMO ONE LINE DIAGRAM.

EXISTING BRANCH CIRCUITS SHOWN AND POLES TO REMAIN8

IMAGE C

TO T6017

3 5 4

NEW PANEL "MDP6017"

NEW

METER ENCLOSURE

EXISTING AERIAL

TO HAZ-MAT

DISCONNECT

EXISTING AERIAL

TO SITE LIGHTING

DISCONNECT

EXISTING TRANSFER

SWITCH

IMAGE E

OE

OE

OE

OE

OE OE OE OE

OE OE

OE

OE OE OE OE OE OE

EXISTING

100A HAZ MAT

DISCONNECT

OE OE

EXTEND EXISTING 4" CONDUIT TO THE NEW METER LOCATION,

PROVIDE A SECOND 4" CONDUIT PARALLEL TO THE EXISTING 4"

CONDUIT, SAW CUT AND PATCH EXISTING FOUNDATION AS NEEDED

TO INSTALL SECOND CONDUIT.

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "6017" - SHT 2

EP123A 0

NONE

DL MORITZ

BW DEEN

NM BROWN

IMAGE

D

EP123

SCALE: NONE

IMAGE

E

EP123

SCALE: NONE

LEGEND:

REMOVE

NOTES:

1. SEE DWG EP123, FOR KEYNOTES.

IMAGE

C

EP123

SCALE: NONE

TO GENERATOR

TO NEW PANEL

MDP6017

100A DISCONNECT

AT HAZ MAT

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "T6101" - DEMO

EO124D 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE

MOUNTED TRANSFORMERS TO WEATHERHEADS AND CONDUIT

DOWN TO THE EXISTING MANUAL DOUBLE THROW SWITCH, AND

PANEL CIRCUITS FOR BUILDINGS 6101 AND 6102 WHICH WILL BE

NEW UNDERGROUND BRACH CIRCUITS PER ONE LINE DIAGRAMS.

REMOVE ONCE NEW METER ENCLOSURE AND PANEL MDP IS IN

PLACE AND NEW SERVICES ARE READY TO BE PLACED IN SERVICE

THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.

CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO

TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO

NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL

DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED

TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO

REMOVE AERIAL SECONDARY SERVICE CONDUCTORS. BASE WILL

LEAVE EXISTING POLE AND AREA LIGHT AND CONTRACTOR TO

MAINTAIN SERVICE TO THIS LIGHT FROM NEW PANEL. BASE TO

REMOVE TRANSFORMERS AT A LATER DATE

LEGEND:

REMOVE

1 2

ONE-LINE DIAGRAM FOR TRANSFORMER "T6101"

AutoCAD SHX Text

EXISTING POLE MOUNTED 3-25KVA TRANSFORMER BANK

AutoCAD SHX Text 150A 3P

AutoCAD SHX Text

TO BLDG 6101 SERVICE PANEL

AutoCAD SHX Text 100A 3P

AutoCAD SHX Text

TO BLDG 6102 SERVICE PANEL

EXISTING DOUBLE THROW MANUAL TRANSFER SWITCH, NEMA TYPE 3R 200A, RELOCATE TO ELECTRICAL EQUIPMENT STAND

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM & DETAILS

TRANSFORMER "T6101" - NEW

EO124 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

PROVIDE A NEW 600 AMP METER ENCLOSURE FOR 3 PHASE, 4 WIRE

INSTALLATION. LOCATE ON UNISTRUT EQUIPMENT STAND PER

DETAILS AS REQUIRED. PROVIDE METERING TRANSFORMER

ENCLOSURE WITH CT AND PT TRANSFORMERS TO SERVICE METER

COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF

SERVICE TO POLE MOUNTED TRANSFORMERS AND TO

ENERGIZE NEW PAD MOUNTED TRANSFORMER T6101.

COORDINATE REQUIRED CONNECTIONS TO MAINTAIN OPEN

SECTIONS OF NEW UNDERGROUND DISTRIBUTION AS

REQUIRED DURING PHASING OF WORK

GALVANIZED 4" STEEL

PIPE FILLED WITH

CONCRETE. SPACING

BETWEEN PIPES NOT TO

EXCEED 6 FEET. PROVIDE

ADDITIONAL SUPPORT

PIPES AS NEEDED (TYP)

RGS CONDUIT (TYP)

WHERE EXPOSED

EXTERIOR ELECTRICAL EQUIPMENT STAND DETAIL

NO SCALE

1'-6"

WEATHERPROOF

GFI SERVICE

RECEPTACLE

PLACE BITUMONOUS COATING

ON STEEL WHERE IN CONTACT

WITH CONCRETE (TYP)

GALVANIZED STEEL

UNISTRUT MOUNTING

BRACKETS (TYP)

18" SONOTUBE FILLED WITH

CONCRETE (TYP)

PANEL "MDP6101"

ON BACKSIDE OF METER

ENCLOSURE

600A METER

ENCLOSURE

SERVICE DISCONNECT

TO BLDG 6101

SERVICE DISCONNECT

TO BLDG 6102

RELOCATED EXISTING 200AMP

MANUAL THROW SWITCH

WRAP 3M TAPE 3" ABOVE

AND BELOW CONCRETE

FINISH (TYP)

USE MYERS HUBS

TO "T6101"

3 4

SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND

EO06 FOR TRANSFORMER SCHEDULES

SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL

PRIMARY CABLE SCHEDULES

SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5

PROVIDE A NEW 600A, 3 PHASE, 4 WIRE PANELBOARD IN

LOCKABLE NEMA 3R ENCLOSURE FOR PANEL MDP6101. PANEL

TO HAVE A 500A MAIN CIRCUIT BREAKER TRIP AND BRANCH

BREAKERS AS SHOWN TO RESERVICE EXISTING LOADS.

PANEL SHALL ALSO BE PROVIDED WITH 160KA SEVEN MODE

TVSS DIRECTED CONNECTED TO BUS. PANEL SHALL BE

SERVICE ENTRANCE RATED. ROUTE THE NEW SERVICE

LVT6101 FROM METER ENCLOSURE INTO SIDE OF NEW PANEL

FROM 200A BRANCH BREAKER IN PANEL MDP, ROUTE

CONDUCTORS SHOWN TO EXISTING MANUAL TRANSFER

SWITCH. AFTER RELCOATING TRANSFER SWITCH TO

EQUIPMENT STAND, THE LOAD SIDE OF EXISTING TRANSFER

SWITCH IS CURRENTLY NOT CONNECTED, WILL REMAIN OPEN

FOR FUTURE GOVT. USE

NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6101"

PROVIDE NEW BRANCH CIRCUITS AS SHOWN FOR PANELS AT

BUILDINGS 6101 AND 6102 TO BE ROUTED UNDERGROUND

FROM DISCONNECTS TO PANELS.

1/0 AWG TO GROUND

GRID, SEE DETAILS

1" C

AutoCAD SHX Text 200A 3P

AutoCAD SHX Text

NEW PANEL "MDP6101"

AutoCAD SHX Text

600AF 3P 500AT

AutoCAD SHX Text

"LVT6101"

AutoCAD SHX Text

TVSS

AutoCAD SHX Text

SECTIONALIZING CABINET SC#4

AutoCAD SHX Text 100A 3P

AutoCAD SHX Text EXISTING DOUBLE THROW MANUAL TRANSFER SWITCH NEMA TYPE 3R, 200A RELOCATED TO ELECTRICAL EQUIPMENT STAND

AutoCAD SHX Text 8A

AutoCAD SHX Text

NEW 600A METER ENCLOSURE LOCKABLE NEMA 3R ENCLOSURE ON EQUIPMENT STAND

AutoCAD SHX Text

"LVT6101"

AutoCAD SHX Text

13.2KV 150KVA TRANSFORMER "T6101" 208Y/120V, 3ɸ, 4W

AutoCAD SHX Text

"MVSC4/3"

AutoCAD SHX Text 20A 1P

AutoCAD SHX Text 3#12(1")C

AutoCAD SHX Text

AREA LIGHT

AutoCAD SHX Text

200A NF

AutoCAD SHX Text 200A 3P

AutoCAD SHX Text 150A 3P

AutoCAD SHX Text

TO BLDG 6101

AutoCAD SHX Text

4#4/0, W/#6 GND (2.5")C

AutoCAD SHX Text

4#4/0, W/#6 GND (2.5")C

AutoCAD SHX Text

100A NF

AutoCAD SHX Text 100A 3P

AutoCAD SHX Text

TO BLDG 6102

AutoCAD SHX Text

4#2, W/#8 GND (1.25")C

AutoCAD SHX Text 20A 1P

AutoCAD SHX Text

X2 GFI WP

AutoCAD SHX Text 3#12(1")C

208V, 3ɸ, 4W, 600A BUS, 42,000AIC

O/E

O/E

O/E

O/E

O/E

O/E

O/E

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

EP2

4 WAY SECTIONALIZER SC#4

150KVA TRANSFORMER

208/120V 3Ø 4W, "T6101"

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "T6101"

EP124 0

1" = 10'

DL MORITZ

BW DEEN

NM BROWN

EP2

MVSC4/3

MVSC4/2

MVSC4/4

N

O

R

T

H

SERVICE DISCONNECT

TO 6102

NEW PANEL

"MDP6101"

RELOCATED EXISTING

200A TRANSFER

MANUAL THROW SWITCH

I

M

A

IMAGE

A

EP124

SCALE: NONE

IMAGE

B

EP124

SCALE: NONE

SERVICE DISCONNECT

TO 6101

600A

METER ENCLOSURE

KEYNOTES:

EXISTING POLE TO REMAIN AND RESERVICE OVERHEAD AREA

LIGHT WITH CIRCUIT SHOWN ON ONE LINE DIAGRAM

EXISTING OVERHEAD AREA LIGHT AT STRUCTURAL COLUMN TO

REMAIN AT BUILDING 6102

ROUTE SECONDARY CONDUITS AT 36 INCH MINIMUM BURIAL DEPTH

TYPICAL

REMOVE EXISTING OVERHEAD SECONDARY SERVICE

CONDUCTORS TO PANEL AT BLDG. 6102

REMOVE SERVICE WEATHERHEAD AND CONDUIT AT BUILDING 6102.

PLACE WEATHERPROOF SCREW TYPE CAP ON TOP OF EXISTING

PANEL TO SEAL. SERVICE TO OVERHEAD LIGHT TO REMAIN ALONG

WITH OTHER BRANCH CIRCUITS

REMOVE EXISTING GROUND CABLE, GROUND ROD, AND CONDUIT

AND PLACE WEATHER PROOF SCREW TYPE PLUG IN OPENING.

NEW GROUND WILL BE PART OF BRANCH CIRCUIT

NEW UNDERGROUND BRANCH CIRCUIT FROM 100A DISCONNECT

AT ELECTRICAL EQUIPMENT RACK

EXISTING YARD LIGHT TO REMAIN. ROUTE CONDUIT UP POLE FROM

BELOW GRADE AND CONNECT TO NEW MDP6101 PER ONE LINE

DIAGRAM. SECURE CONDUIT TO POLE AS REQUIRED AND

RECONNECT TO EXISTING DRIP LOOP

EXISTING 200A MANUAL THROW SWITCH TO BE RELOCATED TO

ELECTRICAL EQUIPMENT RACK FOR FUTURE USE

REMOVE EXISTING SERVICE SPOOLS AND PROVIDE APPROVED

MEANS TO WEATHERPROOF BUILDING OPENINGS LEFT FROM

REMOVAL. COORDINATE WITH GOVT. REMOVE THE WEATHERHEAD,

OVERHEAD SERVICE CONDUCTORS AS SHOWN

IMAGE

C

EP124

SCALE: NONE

IMAGE

D

EP124

SCALE: NONE

IMAGE

E

EP124

SCALE: NONE

I

M

A

IMAGE D

I

M

A

I

M

A

1 8

EXTEND EXISTING 4" CONDUIT TO THE NEW METER LOCATION,

PROVIDE A SECOND 4" CONDUIT PARALLEL TO THE EXISTING 4"

CONDUIT, SAW CUT AND PATCH EXISTING FOUNDATION AS NEEDED

TO INSTALL SECOND CONDUIT.

10" SAN

GRAVEL

T

MH 9

N: 16667886.43

E: 1038904.46

T

FO DEPTH:1.21'

36+00

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N S

A N

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N

S A

N S

A N

S A

N S

A N

FO DEPTH: 1.58'

FO DEPTH: 1.91'

DEPTH: 6.00'

DEPTH: 4.00'

42+00

43+00

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

N

O

R

T

H

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "T6205" - SHT 1

EP125 0

1" = 10'

DL MORITZ

BW DEEN

NM BROWN

EP4 MVSW3/4

C P

EXISTING 500KVA PAD MOUNT

TRANSFORMER

480/277V 3Ø, 4W TO BE SWITCHED TO

NEW SERVICE IN FUTURE

"T6205"

EMH#6

OCC#5

EP2

CP1

KEYNOTES:

EXISTING MANHOLE #EMH6 EXISTING MV RADIAL TAP TO BE

REROUTED THRU THIS MANHOLE AND SPLICED INTO NEW MVSW3/4

CIRCUIT INTERIOR TO MANHOLE TO PREVENT HAVING TO ROUTE

NEW CONDUITS INTO EXISTING TRANSFORMER

EXISTING MV CABLE FROM OVERHEAD POLE RISER IS NOT SHOWN

ON AS-BUILTS ALL THE WAY TO TRANSFORMER. ROUTE ON

DRAWING IS ASSUMED. CONTRACTOR SHALL LOCATE WITH

POTHOLE IF REQUIRED TO PLACE NEW MANHOLE EMH#6 AND

EXPOSE TO REROUTE INTO MANHOLE. CONTRACTOR SHALL USE

CARLON 4 INCH PVC SPLIT DUCT TO PROTECT CABLE INTO

MANHOLE WHEN CONCRETE IS POURED. TAPE HALVES OF SPLIT

DUCT TOGETHER SO MINIMUM OF 6 INCHES INTO NEW MANHOLE

AND 12 INCHES OUTSIDE OF MANHOLE IF EXISTING CABLE WAS NOT

PLACED IN CONDUIT. SEAL CONDUIT FROM ACCIDENTAL CONCRETE

ENTRY AND TO ALLOW CABLE TO BE REMOVED IN FUTURE IF

NEEDED

CONTRACTOR SHALL VERIFY THE SIZE OF THE EXISTING UG MV

CABLE TO ALLOW WATERPROOF 15KV CABLE SPLICE IN MANHOLE.

SPLICES SHALL BE PLACED ON SIDE OF MANHOLE WALL ONCE

COMPLETED

EXISTING UNDEGROUND MEDIUM RISER CABLE AND CONDUIT UP

EXISTING RISER POLE TO BE REMOVED BY CONTRACTOR TO

BELOW GRADE ONLY UPON DE-ENERGIZING IS COMPLETED BY

BASE AND THE BASE HAS LOWERED FUSE CUT OUT ASSEMBLIES

AND CABLE DOWN TO MAXIMUM 10' ABOVE GRADE ON POLE

EXISTING INTERNAL VIEW OF T6205 TO BE RESERVICED5

ROUTE NEW MVSW3/4 CIRCUIT IN CONDUIT ROUTE SHOWN AND

ALSO ON PLAN DRAWINGS EP106 AND EP107. COMPLETE ROUTE

NOT SHOWN ON THIS DRAWING

I M

A G

E

B

N

O

R

T

H

I

M

A

OCC#6

CHH#8

PME-9 SW#3

PME-9 SW#4

MVSW4/4

MVSW3/2

EP4

EP2

E O

S F

CP1

CP4

E P

C P

TO BE REMOVED

PLAN A (REFERENCE EP106) PLAN B (REFERENCE EP107)

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "T6205" - SHT 2

EP125A 0

NONE

DL MORITZ

BW DEEN

NM BROWN

NOTES:

1. FOR KEYNOTES, SEE DWG EP125.

IMAGE

A

EP125

SCALE: NONE

IMAGE

B

EP125

SCALE: NONE

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "TEWT" - DEMO

EO126D 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

EXISTING SECONDARY LOAD SIDE CONDUCTORS FROM POLE

MOUNTED DISCONNECT TO ELEVATED WATER TOWER TO REMAIN

ALONG WITH POLE MOUNTED EQUIPMENT NEAR TOWER. SERVICE

TO THE LINE SIDE OF THE EXISTING FUSED DISCONNECT MAY BE

SWITCHED OVER AND REMOVE WEATHERHEAD, CONDUIT, AND

CONDUCTORS, ONCE THE NEW PAD MOUNTED

TRANSFORMER “TEWT” IS READY TO BE PLACED IN SERVICE AND

NEW UNDERGROUND SECONDARY SERVICE CONDUCTORS ARE

MOUNTED INTO DISCONNECT AND READY TO BE TERMINATED

EXISTING POLE #25 AND SINGLE PHASE 25KVA TRANSFORMER WILL

BE LEFT IN PLACE. CONTRACTOR TO NOTIFY BASE ELECTRICIAN

WHEN READY TO TRANSFER SERVICE FROM POLE MOUNTED

TRANSFORMER TO NEW PAD MOUNTED TRANSFORMER “TEWT”. AT

THAT TIME BASE WILL DISCONNECT PRIMARY SERVICE TO THE

POLE MOUNTED TRANSFORMER AND CONTRACTOR SHALL THEN BE

ALLOWED TO REMOVE AERIAL SECONDARY SERVICE TO EXISTING

DISCONNECT LINE SIDE BY ELEVATED WATER TOWER. BASE WILL

REMOVE POLES AT A LATER DATE WHERE APPLICABLE

LEGEND:

REMOVE

ONE-LINE DIAGRAM FOR TRANSFORMER "TEWT"

AutoCAD SHX Text

EXISTING POLE MOUNTED 25KVA TRANSFORMER ON POLE 25 ALONG MISSION DRIVE

AutoCAD SHX Text

EXISTING EWT CONTROL PANEL AND EQUIPMENT

AutoCAD SHX Text

EXISTING POLE MOUNTED 100A FUSED DISCONNECT

5A

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

TRANSFORMER "TEWT" - NEW

EO126 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

INSTALL NEW SECONDARY SERVICE CONDUCTORS “LVEWT” FROM

PAD MOUNTED TRANSFORMER “TEWT” TO LINE SIDE OF EXISTING

FUSED DISCONNECT THROUGH BOTTOM OF DISCONNECT. TAKE

OUTAGE TO REMOVE EXISTING SERVICE CONDUCTORS FROM POLE

MOUNTED TRANSFORMER

SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND EO06

FOR TRANSFORMER SCHEDULES

NEW ONE-LINE DIAGRAM FOR TRANSFORMER "TEWT"

SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL PRIMARY

CABLE SCHEDULES

SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES4

PROVIDE GROUNDING GRID FOR DISCONNECT AS SHOWN IN

ELECTRICAL BUILDING SERVICE GROUNDING REQUIREMENT DETAIL

AutoCAD SHX Text

EXISTING EWT CONTROL PANEL AND EQUIPMENT

AutoCAD SHX Text

EXISTING POLE MOUNTED 100A FUSED DISCONNECT

AutoCAD SHX Text

EXISTING TO REMAIN

AutoCAD SHX Text

NEW PAD MOUNTED SWITCH SW#4

AutoCAD SHX Text

"LVTEWT"

AutoCAD SHX Text

"MVSW4/3"

7.6KV 25KVA TRANSFORMER "TEWT" 120/240V, 1ɸ , 3W

E

O E

O E

O E

O E

O E

O E

O E

O E

O E

S A

N S

A N

S A

N S

A N

S A

N S

A N

S A

N S

A N

S A

N S

A N

G G

G

G

G

G

G

G

G

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

C

O

T

EP2

CP1

EP2

CP1

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

S A

N S

A N

S A

N S

A N

S A

N S

A N

S A

N S

A N

S A

N S

A N

G G

G

G

G

G

G

G

G

F O

F O

F O

F O

F O

F O

F O

F O

F O

F O

T

O E

O E

O E

O E

O E

O E

O E

O E

O E

O E

G G

G

G

G

G

G

G

G

MVSW4/3

D

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

N

O

R

T

H

ELECTRICAL

ENLARGED SITE PLAN

TRANSFORMER "TEWT"

EP126 0

1" = 20'

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

REMOVE SERVICE WEATHERHEAD AND CONDUIT AT EXISTING

DISCONNECT. PLACE WEATHERPROOF SCREW TYPE CAP ON TOP

OF EXISTING DISCONNECT TO SEAL

NEW SERVICE ENTRY SHALL COME IN BOTTOM OF EXISTIGN

DISCONNECT AND GROUND CONDUIT SHALL ALSO COME OUT OF

DISCONNECT WHERE SHOWN

REMOVE EXISTING OVERHEAD SECONDARY CONDUCTORING FROM

POLE MOUNTED TRANSFORMER ONCE NEW PAD MOUNT

TRANSFORMER “TEWT” IS IN SERVICE. POLE SHOWN IS

POLE 25 LOCATED ALONG MISSION DRIVE

SEE ORIGINAL LAYOUT DRAWINGS EP107, 107A, AND 107B FOR

COMPLETE ROUTING AND LOCATION OF TRANSFORMER “TEWT”

IMAGE

A

EP126

SCALE: NONE

I

M

A

IMAGE

B

EP126

SCALE: NONE

IMAGE

C

EP126

SCALE: NONE

IMAGE C

I M

A

OE OE

EXISTING OVERHEAD

ELECTRICAL SECONDARY

TO BE REMOVED

OE OE OE

OE

OE

OE

OE

OE OE OE

OE

OE

OE

OE

OE

EXISTING DISCONNECT,

TO BE RESERVICED

FROM BOTTOM PER

IMAGE A

NEW

TRANSFORMER

"TEWT"

CIRCUIT

"LVTEWT"

OE

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

XFER "T6415" & BLDG 6416 - DEMO

EO127D 0

1" = 10'

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

REMOVE EXISTING AERIAL SECONDARY CONDUCTORS FROM POLE

MOUNTED TRANSFORMERS TO WEATHERHEADS AND CONDUIT

DOWN TO THE EXISTING DISCONNECTS AND WEATHERHEADS INTO

BUILDINGS. WHERE APPLICABLE REMOVE WEATHERHEADS AND

PLACE “LB” CONDUIT BODIES TO EXTEND NEW SERVICES FROM

ELECTRICAL EQUIPMENT STAND DISCONNECTS TO APPROPRIATE

CONDUIT BUILDING ENTRANCES FOR BUILDINGS 6415 AND 6416

WHICH WILL BE NEW UNDERGROUND BRANCH CIRCUITS PER ONE

LINE DIAGRAMS. REMOVE ONCE NEW METER ENCLOSURE AND

PANEL MDP IS IN PLACE AND NEW SERVICES ARE READY TO BE

PLACED IN SERVICE

THE EXISTING POLE AND TRANSFORMERS WILL BE LEFT IN PLACE.

CONTRACTOR TO NOTIFY BASE ELECTRICIAN WHEN READY TO

TRANSFER SERVICE FROM POLE MOUNTED TRANSFORMERS TO

NEW PAD MOUNTED TRANSFORMER. AT THAT TIME BASE WILL

DISCONNECT PRIMARY SERVICE TO THE POLE MOUNTED

TRANSFORMERS AND CONTRACTOR SHALL THEN BE ALLOWED TO

REMOVE AERIAL SECONDARY SERVICE CONDUCTORS. BASE WILL

LEAVE EXISTING POLE. BASE TO REMOVE TRANSFORMERS AT A

LATER DATE

ONE-LINE DIAGRAM FOR TRANSFORMER "T6415"

LEGEND:

REMOVE

1 2

SIZE TO BE

FIELD VERIFIED

AutoCAD SHX Text

600A MCB

AutoCAD SHX Text

BLDG 6415 SERVICE PANEL

AutoCAD SHX Text

EXISTING POLE MOUNTED 3-100KVA TRANSFORMERS

AutoCAD SHX Text

XXX

AutoCAD SHX Text

150A MCB

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

400A 250AF

AutoCAD SHX Text

200A MCB

AutoCAD SHX Text

BLDG 6415 PANEL

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

METER ENCLOSURE ON POLE

AutoCAD SHX Text

225A MCB

AutoCAD SHX Text

BLDG 6416 SERVICE PANEL

METER ENCLOSURE TO BE RELOCATED TO ELECTRICAL EQUIPMENT STAND BY BLDG 6415

15A

A

1 2

C A

R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com

Texas Firm Registration No.: F-174

AT FULL SIZE

IN

cm0 1

3 4

USDA-APHIS-PPQ MOORE AIR BASE

ARE FOR GENERAL INFORMATION ONLY. UTILITY SERVICE

CONNECTIONS ARE NOT SHOWN ON THIS DRAWING.

CONTRACTOR FULLY RESPONSIBLE FOR OBTAINING EXACT

LOCATIONS OF EXISTING UTILITIES FROM UTILITY

COMPANIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.

05-09-2022

116530

ERNEST E. LEAF

ELECTRICAL

ONE-LINE DIAGRAM

XFER "T6415" & BLDG 6416 - NEW

EO127 0

NONE

DL MORITZ

BW DEEN

NM BROWN

KEYNOTES:

PROVIDE A NEW 1,000 AMP METER ENCLOSURE FOR 3 PHASE, 4

WIRE INSTALLATION. LOCATE ON UNISTRUT EQUIPMENT STAND

PER DETAILS AS REQUIRED. PROVIDE METERING TRANSFORMER

ENCLOSURE WITH CT ANDF PT TRANSFORMERS TO SERVICE

METER

COORDINATE OUTAGE WITH BASE FOR DISCONNECTION OF

SERVICE TO POLE MOUNTED TRANSFORMERS AND TO ENERGIZE

NEW PAD MOUNTED TRANSFORMER T6415. COORDINATE

REQUIRED CONNECTIONS TO MAINTAIN OPEN SECTIONS OF NEW

UNDERGROUND DISTRIBUTION AS REQUIRED DURING PHASING OF

WORK

NEW ONE-LINE DIAGRAM FOR TRANSFORMER "T6415"

SEE DRAWING EO00 FOR PRIMARY ONE LINE DIAGRAM AND EO06

FOR TRANSFORMER SCHEDULES

SEE DRAWING EO02 AND EO03 FOR SITE ELECTRICAL PRIMARY

CABLE SCHEDULES

SEE DRAWING EO04 FOR SECONDARY CABLE SCHEDULES5

PROVIDE A NEW 1,000A, 3 PHASE, 4…