This document is a Carrier AquaForce Air-Cooled Chiller submittal for the Pinellas County Schools' Palm Harbor University High School project, dated January 9, 2025. The submittal details a 30XV325 model air-cooled chiller with a cooling capacity of 303 tons, featuring a VFD screw compressor, R-513A refrigerant, and manufactured in Charlotte, NC. The chiller includes multiple accessories such as isolation valves, suction line insulation, a control transformer, non-fused disconnect, sound/capacity optimization, and a permanent magnet compressor motor. The unit offers a warranty that includes parts-only coverage for the first year, with comprehensive parts and labor coverage for years 2-10.
The technical specifications reveal the chiller's comprehensive performance characteristics, including an Integrated Part Load Value (IPLV) of 20.84 BTU/Wh and a total unit power of 326.2 kW at full load. The unit operates with a minimum capacity of 16%, has two independent refrigerant circuits, and is designed with a flooded evaporator with a heater. Electrical specifications include a 460-3-60 V-Ph-Hz power configuration, with a minimum voltage of 414V and maximum of 506V. The acoustic performance is detailed, with sound power levels ranging from 83 to 99 dB depending on load percentage, and the unit is certified in accordance with AHRI Air-Cooled Water-Chilling Packages Certification Program standards.
View the file
Other files for this state and local contract opportunity
Show all 50
Chiller Replacement has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pinellas County Schools
Project Bid 24-CR-030 Palm Harbor University High School
Date 1/9/2025
Mechanical Engineer Phoenix Engineering
Sales Engineer Mohamed Abdel-Aziz
Submittal Air Cooled Chiller 3 Option C mohamed.abdelaziz@carrier.com; 813-404-2573
Table of Contents
Unit Report 1
Unit Performance 3
Drawings 8
Unit Report
Unit Report For CH-3 Option C Project: PCS - Palm Harbor ACC 01/08/2025 Prepared By: 06:21PM
Unit Information Tag Name: CH-3 Option C Model Number: 30XV325 Condenser Type: Air Cooled Compressor Type: VFD Screw Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R-513A Independent Refrigerant Circuits: 2 Capacity Control Steps: 0 Minimum Capacity: 16.0 % Shipping Weight: 20782 lb Operating Weight: 21252 lb Unit Length: 487 in Unit Width: 88 in Unit Height: 99 in
Accessories and Installed Options Isolation Valve(s) Suction Line Insulation Control Transformer Non-Fused Disconnect Sound/Capacity Optimization Option Permanent Magnet Compressor Motor Micro Channel, E-Coat Flooded Evaporator. 1 pass, w/ Heater Low Sound Kit Coil T Panel (Header side), Grilles(sides), Upper Hail Guards (End) R-513A Low Ambient Head Pressure Control High Tier
Chiller Warranty Information (Note: for US & Canada only) First Year - Parts Only (Standard) Start up, First Unit Complete Unit Year 2-5 Parts & Carrier CCS Labor Complete Unit Year 2-10 Parts Parts & Labor
Ordering Information
Part Number Description Quantity 30XV-3256HX1564C2 Packaged Chiller 1
Base Unit Isolation Valve(s) Suction Line Insulation Control Transformer Non-Fused Disconnect Sound/Capacity Optimization Option Permanent Magnet Compressor Motor Micro Channel, E-Coat Flooded Evaporator. 1 pass, w/ Heater Low Sound Kit Coil T Panel (Header side), Grilles(sides), Upper Hail Guards (End) R-513A
Packaged Chiller Builder NACO 3.74 Page 1 of 1
Unit Performance
Detailed Performance Summary For CH-3 Option C
Prepared By: 06:22PM
PackagedChillerReport:DoNotEdit;
AquaForceTM Air-Cooled Variable Speed Screw Chiller
Unit Information Tag Name: CH-3 Option C Model Number: 30XV325H Condenser Type: Air Cooled Compressor Type: VFD Screw Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA ASHRAE 90.1: 2022 path A/B & older Refrigerant: R-513A Minimum Capacity: 11.05 % Shipping Weight: 20782 lb Operating Weight: 21252 lb Refrigerant Weight (Circuit A): 226 lb Refrigerant Weight (Circuit B): 231 lb Unit Length: 487 in Unit Width: 88 in Unit Height: 99 in Required Pad Length: 470 in Minimum Outdoor Operating Temp: -20.0 °F
Performance Information Cooling Capacity: 303.0 Tons Total Compressor Power: 299.7 kW Total Fan Motor Power: 21.36 kW Total Unit Power (without pump): 326.2 kW Efficiency (without pump) (EER): 11.15 BTU/Wh
Evaporator Information Fluid Type: Fresh Water Fouling Factor: 0.000100 (hr-sqft-F)/BTU Leaving Temperature: 45.00 °F Entering Temperature: 54.99 °F Fluid Flow: 725.5 gpm Fluid Flow Min: 625.0 gpm Fluid Flow Max: 3,034 gpm Pressure Drop: 3.37 ft H2O
Condenser Information Altitude: 0.000 ft Number of Fans: 20 Total Condenser Fan Air Flow: 290,000 CFM Entering Air Temperature: 95.0 °F
Sound/Capacity Optimization Information Sound at: 303.0 Tons
Integrated Pump Information No Pump Selected
Accessories and Installed Options Isolation Valve(s) Suction Line Insulation Control Transformer Non-Fused Disconnect Sound/Capacity Optimization Option Permanent Magnet Compressor Motor Micro Channel, E-Coat Flooded Evaporator. 1 pass, w/ Heater Low Sound Kit Coil T Panel (Header side), Grilles(sides), Upper Hail Guards (End) R-513A Low Ambient Head Pressure Control High Tier
Electrical Information Unit Voltage: 460-3-60 V-Ph-Hz Connection Type: Single Point Minimum Voltage: 414 Volts Maximum Voltage: 506 Volts SCCR: 25 kA
Electrical Electrical Amps Circuit 1 Circuit 2
MCA 551.9 ---
MOCP 700.0 ---
Rec Fuse Size 700.0 ---
Packaged Chiller Builder NACO 3.74 Page 1 of 4
Prepared By: 06:22PM
Integrated Part Load Value (AHRI) IPLV.IP: 20.84 BTU/Wh
Unit Performance Percent of Full Load Capacity, % 100.00 75.00 50.00 25.00 Percent of Full Load Power, % 100.00 51.32 23.32 9.89 Unloading Sequence A A A A Cooling Capacity, Tons 297.8 223.4 148.9 74.46 Total Unit Power, kW 324.4 166.5 75.65 32.10 Efficiency (EER), BTU/Wh 11.02 16.10 23.62 27.84 Evaporator Data Fluid Entering Temperature, °F 54.00 51.30 48.86 46.43 Fluid Leaving Temperature, °F 44.00 44.00 44.00 44.00 Fluid Flow Rate, gpm 731.0 731.0 731.0 731.0 Fouling Factor, (hr-sqft-F)/BTU 0.000100 0.000100 0.000100 0.000100 Pressure Drop, psi 1.49 1.50 1.50 1.51 Condenser Data Entering Air Temperature, °F 95.0 80.0 65.0 55.0
Nonstandard Part-Load Value NPLV.IP: 21.22 BTU/Wh
Unit Performance Percent of Full Load Capacity, % 100.00 75.00 50.00 25.00 Percent of Full Load Power, % 100.00 51.28 23.12 9.80 Unloading Sequence A A A A Capacity, Tons 303.0 227.2 151.5 75.75 Total Unit Power, kW 326.2 167.3 75.42 31.97 Efficiency (EER), BTU/Wh 11.15 16.30 24.11 28.44 Evaporator Data Fluid Entering Temperature, °F 54.99 52.48 49.99 47.49 Fluid Leaving Temperature, °F 45.00 45.00 45.00 45.00 Fluid Flow Rate, gpm 725.5 725.5 725.5 725.5 Fouling Factor, (hr-sqft-F)/BTU 0.000100 0.000100 0.000100 0.000100 Pressure Drop, psi 1.46 1.47 1.47 1.48 Condenser Data Entering Air Temperature, °F 95.0 80.0 65.0 55.0
Sound power measured in accordance with ANSI/AHRI Standard 370-2015.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
The NPLV is not an AHRI 550/590 metric and is not certified. It is based on ambient temperature varying linearly from the full load ambient to 55 F at 0% load.
Packaged Chiller Builder NACO 3.74 Page 2 of 4
Prepared By: 06:22PM
Unit Parameters Tag Name: CH-3 Option C Model Number: 30XV325 Condenser Type: Air Cooled Compressor Type: VFD Screw Chiller Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R-513A Shipping Weight: 20782 lb Operating Weight: 21252 lb Refrigerant Weight (Circuit A): 226 lb Refrigerant Weight (Circuit B): 231 lb Unit Length: 487 in Unit Width: 88 in Unit Height: 99 in Required Pad Length: 470 in
1 - Chiller Height Above Ground 2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground (See Note 3)
Sound/Capacity Optimization Information Sound at: 303 Tons
Accessories and Installed Options Isolation Valve(s) Suction Line Insulation Control Transformer Non-Fused Disconnect Sound/Capacity Optimization Option Permanent Magnet Compressor Motor
Micro Channel, E-Coat Flooded Evaporator. 1 pass, w/ Heater Low Sound Kit Coil T Panel (Header side), Grilles(sides), Upper Hail Guards (End) R-513A
Acoustic Information Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall 100% Load 66 79 83 92 95 94 90 80 99 75% Load 63 73 79 92 89 89 82 75 95 50% Load 58 66 77 81 81 78 69 69 86 25% Load 55 63 75 78 78 75 66 66 83
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall 100% Load 35 47 51 60 63 62 59 48 68 75% Load 31 42 48 60 58 57 50 43 64 50% Load 27 34 46 50 49 46 37 37 54 25% Load 23 31 43 47 46 43 35 34 51
Notes: (1) Measurements performed in accordance with AHRI Standard 370-2015 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft 2 - Horizontal Distance From Chiller to Receiver = 30.0 ft 3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.74 Page 3 of 4
Prepared By: 06:22PM
Packaged Chiller Builder NACO 3.74 Page 4 of 4
Drawings
File details come from the government source that posted it. Updated .