PCS_Palm_Harbor_University_Water_Cooled_Chiller_1_and_2_Option_A_Submittal.pdf
PDF 5 MB Posted
- Attached to
- Chiller Replacement State and local contract opportunity
- Solicitation number
- 25-CR-052
- Issued by
- Pinellas County, Florida
About this file
This document is a comprehensive submittal package for two water-cooled chillers (CH-1 and CH-2) prepared by Carrier for the Pinellas County Schools' Palm Harbor University High School Chiller Replacement project. The submittal includes detailed performance reports, configuration specifications, and technical drawings for two 23XRV4040NRVAA50 AquaEdge water-cooled chillers, each with a 500-ton cooling capacity. The chillers are configured with Unit Mounted VFD (Variable Frequency Drive) with Harmonic Mitigation, use R-513A refrigerant, and are manufactured in Charlotte, USA. Both units feature identical specifications including a 40-size evaporator and condenser, 2-pass configuration, copper rifled tubes, and fresh water fluid type, with a total rigging weight of 19,525 lbs and total operating weight of 21,755 lbs.
The chillers are designed to meet ASHRAE 90.1 efficiency requirements for multiple years (2007-2016), and can potentially earn one LEED EAC4 point. The performance reports detail the chillers' efficiency at various load percentages, with chiller power ranging from 38.88 kW to 299.3 kW and chiller efficiency varying from 0.3110 to 0.5986 kW/TonR. Each chiller includes features such as automatic hot gas bypass, isolation valves, and a unit-mounted VFD with harmonic mitigation. The acoustic data indicates sound pressure levels between 78-88 dBA depending on load percentage, and the units are configured with BACnet/Modbus standard communication protocol. The technical drawings provide comprehensive dimensional details, illustrating the chillers' plan, front, rear, and end views with precise measurements and component locations.
View the file
Other files for this state and local contract opportunity
Show all 50
Chiller Replacement has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pinellas County Schools
Project Bid 24-CR-030 Palm Harbor University High School
Date 1/9/2025
Mechanical Engineer Phoenix Engineering
Sales Engineer Mohamed Abdel-Aziz
Submittal Water Cooled Chiller 1 and 2 Option A mohamed.abdelaziz@carrier.com; 813-404-2573
Table of Contents
CH-1 Details 1
CH-1 Drawings 8
CH-2 Details 14
CH-2 Drawings 21
CH-1 Details
Compressor
Size R (FL Opt.)
Economizer Not Installed
Weights
Total Rigging Weight 19525 lb
Total Operating Weight 21755 lb
Refrigerant Weight 750 lb
Motor & Motor Controller
Size V (R comp)
Line Voltage-Phase-Hertz 460(V)-3-60(Hz)
Flow Controls
Automatic Hot Gas Bypass Installed
Isolation Valve Installed
Flasc Orifice 28
Configuration Evaporator
Size 40
Waterbox Type Nozzle-in-Head, 150 psi
Passes 2
Nozzle Arrangement C - 2 Passes, Nozzles on Discharge End
Tubing 3/4" 0.025" Copper Rifled Evaporator Tubes
Fluid Type Fresh Water
Fouling Factor 0.000100 (hr-sqft-F)/BTU
Condenser
Marine Waterbox, 150 psi
S - 2 Passes, Nozzles on Suction End
3/4" 0.025" Copper Rifled Condenser Tubes
Fresh Water
0.000250 (hr-sqft-F)/BTU
Chiller Starter / VFD Unit Mounted VFD (Harmonic Mitigation)
Refrigerant Type R-513A
Operation Type Cooling
Manufacturing Source USA - Charlotte
23XRV4040NRVAA50--
Page 1 of 3NG eCat Applied Chillers North America v3.6.2.0
Performance Report
Palm Harbor University Water Cooled Chillers - Bid - CH-1 23XRV Option A
Carrier NAC Sales Office
Date: 01/09/2025 8:18 AM Prepared By: Mohamed Abdelaziz
Chiller
Percent Load 100.00 75.00 50.00 25.00
Chiller Capacity 500.0 Tons 375.0 Tons 250.0 Tons 125.0 Tons
Chiller Power 299.3 kW 152.4 kW 71.36 kW 38.88 kW
Chiller Efficiency 0.5986 kW/TonR 0.4065 kW/TonR 0.2854 kW/TonR 0.3110 kW/TonR
Chiller COPʀ 5.875 kW/kW 8.651 kW/kW 12.32 kW/kW 11.31 kW/kW
IPLV.IP 0.3378 kW/TonR NA NA NA
IPLV, COPʀ 10.41 NA NA NA
NPLV.IP 0.3320 kW/TonR NA NA NA
NPLV, COPʀ 10.59 NA NA NA
Evaporator
Entering Temperature 55.03 °F 52.52 °F 50.01 °F 47.51 °F
Leaving Temperature 45.00 °F 45.00 °F 45.00 °F 45.00 °F
Flow Rate 1195 gpm 1195 gpm 1195 gpm 1195 gpm
Pressure Drop 26.9 ft H₂O 27.0 ft H₂O 27.1 ft H₂O 27.2 ft H₂O
Condenser
Leaving Temperature 95.11 °F 82.21 °F 69.65 °F 67.33 °F
Entering Temperature 85.00 °F 75.00 °F 65.00 °F 65.00 °F
Flow Rate 1394 gpm 1394 gpm 1394 gpm 1394 gpm
Pressure Drop 24.0 ft H₂O 24.7 ft H₂O 25.3 ft H₂O 25.4 ft H₂O
Motor & Motor Controller
Motor Rated Load KW 292.6 kW NA NA NA
Motor Rated Load Amps 427.4 324.4 251.2 233.8
Motor OLTA 462 NA NA NA
Chiller Rated Line Amps 393 205 100 60
Chiller Inrush Amps 393 NA NA NA
Max Fuse/ CB Amps 800 NA NA NA
Min Circuit Ampacity 492 NA NA NA
AHRI Tolerances
AHRI Test Tolerance% 5.00 7.24 9.99 14.73
Max Efficiency 0.6285 0.4360 0.3140 0.3568
Min Capacity 475.0 NA NA NA
Max NPLV.IP 0.3651 NA NA NA
ASHRAE 90.1 Efficiency Requirements
ASHRAE 90.1 Max Input Power 0.6250 NA NA NA
ASHRAE 90.1 Max IPLV/ NPLV NA NA NA NA
Percent Load
NPLV.IP
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Certified units may be found in the AHRI Directory at www.ahridirectory.org.
http://www.ahrinet.org/WCCL.aspx
Page 2 of 3NG eCat Applied Chillers North America v3.6.2.0
Performance Report
Palm Harbor University Water Cooled Chillers - Bid - CH-1 23XRV Option A
Carrier NAC Sales Office
This unit complies with the efficiency requirements of :
ASHRAE 90.1 Criteria 2007.
ASHRAE 90.1 2010 Path A.
ASHRAE 90.1 2010 Path B.
ASHRAE 90.1 2013 Path A.
ASHRAE 90.1 2013 Path B.
ASHRAE 90.1 2016 Path A.
ASHRAE 90.1 2016 Path B.
1 Point LEED EAC4 can be earned when selecting the 23XR AquaEdge
Page 3 of 3NG eCat Applied Chillers North America v3.6.2.0
Performance Report
Palm Harbor University Water Cooled Chillers - Bid - CH-1 23XRV Option A
Carrier NAC Sales Office
Starter / VFD Unit Mounted VFD (Harmonic Mitigation)
Refrigerant Type R-513A
Evaporator
Size 40
Waterbox Type Nozzle-in-Head, 150 psi
Passes 2
Nozzle Arrangement C - 2 Passes, Nozzles on Discharge End
Nozzle Options Victaulic Evaporator Nozzles
Evaporator Hinges None
Tubing 3/4" 0.025" Copper Rifled Evaporator Tubes
Fluid Type Fresh Water
Weights
Total Rigging Weight 19525 lb
Total Operating Weight 21755 lb
Refrigerant Weight 750 lb
Condenser
Size 40
Waterbox Type Condenser Waterbox Extra
Passes 2
Nozzle Arrangement S - 2 Passes, Nozzles on Suction End
Nozzle Options Victaulic Condenser Nozzles
Condenser Hinges None
Tubing 3/4" 0.025" Copper Rifled Condenser Tubes
Fluid Type Fresh Water
Motor & Motor Controller
Motor Size V (R comp)
Line Voltage-Phase-Hertz 460(V)-3-60(Hz)
Oil Pump Voltage-Phase-Hertz 460(V)-3-60(Hz)
SCCR Rating 65 kA
Flow Controls
Condenser Float Valve 2
Dimensions
Length 189 in
Width 80 in
Height 91 in
Options
Shipment & Packaging
Packaging Options None
Miscellaneous Options
Evaporator Insulation STD.
Sensor Package Not Selected
Soleplates Not Selected
23XRV4040NRVAA50--
Page 1 of 2NG eCat Applied Chillers North America v3.6.2.0
AquaEdge Chiller Configuration
Palm Harbor University Water Cooled Chillers - Bid - CH-1 23XRV Option A
Carrier NAC Sales Office
Note: This list of specified chiller options does not include any of the separate-ship accessories (gasket kits, refrigerant cylinders, standalone pumpout units, or storage tank / pumpout units), nor any items specified on a Quote Control. These items are specified as part of a bid, and not in the chiller tag. The Pricing Report includes all of these items as specified in a bid.
Spring Isolation Package Not Selected
Controls & Power
HMI Communication Protocol BACnet/Modbus Standard
1 Point LEED EAC4 can be earned when selecting the 23XR AquaEdge
Page 2 of 2NG eCat Applied Chillers North America v3.6.2.0
AquaEdge Chiller Configuration
Palm Harbor University Water Cooled Chillers - Bid - CH-1 23XRV Option A
Carrier NAC Sales Office
23XRV4040NRVAA50--
Estimated Sound Pressure Levels - dB re: 20 micropascal.
Sound pressure levels used to develop this program were measured per AHRI Standard 575.
The sound pressure levels were measured in an acoustical free-field, i.e. a non-reflective environment. Field sound measurements can vary significantly as a function of the reflectivity and proximity of nearby surfaces and the presence of other sound sources.
Notes:
Airborne Sound Pressure, dB Sound Treatment: Full Factory Acoustic Insulation
Full Load
Percent Load
DBA
100.00 87
IPLV
Octave Band Center Frequency, Hz
Percent Load
DBA
100.00 88
75.00 81
50.00 78
25.00 79
NPLV
Octave Band Center Frequency, Hz
Percent Load
DBA
100.00 87
75.00 82
50.00 79
25.00 79
1 Point LEED EAC4 can be earned when selecting the 23XR AquaEdge
Octave band sound pressure level data, for each of the above specified loads, are available upon request.
Page 1 of 1NG eCat Applied Chillers North America v3.6.2.0
AquaEdge Chiller Estimated Acoustic Data
Palm Harbor University Water Cooled Chillers - Bid - CH-1 23XRV Option A
Date: 01/09/2025 8:18 AM
Carrier NAC Sales Office
Prepared By: Mohamed Abdelaziz
CH-1 Drawings
CH-2 Details
Compressor
Size R (FL Opt.)
Economizer Not Installed
Weights
Total Rigging Weight 19525 lb
Total Operating Weight 21755 lb
Refrigerant Weight 750 lb
Motor & Motor Controller
Size V (R comp)
Line Voltage-Phase-Hertz 460(V)-3-60(Hz)
Flow Controls
Automatic Hot Gas Bypass Installed
Isolation Valve Installed
Flasc Orifice 28
Configuration Evaporator
Size 40
Waterbox Type Nozzle-in-Head, 150 psi
Passes 2
Nozzle Arrangement D - 2 Passes, Nozzles on Suction End
Tubing 3/4" 0.025" Copper Rifled Evaporator Tubes
Fluid Type Fresh Water
Fouling Factor 0.000100 (hr-sqft-F)/BTU
Condenser
Marine Waterbox, 150 psi
R - 2 Passes, Nozzles on Discharge End
3/4" 0.025" Copper Rifled Condenser Tubes
Fresh Water
0.000250 (hr-sqft-F)/BTU
Chiller Starter / VFD Unit Mounted VFD (Harmonic Mitigation)
Refrigerant Type R-513A
Operation Type Cooling
Manufacturing Source USA - Charlotte
23XRV4040NRVAA50--
Page 1 of 3NG eCat Applied Chillers North America v3.6.2.0
Performance Report
Palm Harbor University Water Cooled Chillers - Bid - CH-2 23XRV Option A
Carrier NAC Sales Office
Date: 01/09/2025 8:22 AM Prepared By: Mohamed Abdelaziz
Percent Load 100.00 75.00 50.00 25.00
Chiller Capacity 500.0 Tons 375.0 Tons 250.0 Tons 125.0 Tons
Chiller Power 299.3 kW 152.4 kW 71.36 kW 38.88 kW
Chiller Efficiency 0.5986 kW/TonR 0.4065 kW/TonR 0.2854 kW/TonR 0.3110 kW/TonR
Chiller COPʀ 5.875 kW/kW 8.651 kW/kW 12.32 kW/kW 11.31 kW/kW
IPLV.IP 0.3378 kW/TonR NA NA NA
IPLV, COPʀ 10.41 NA NA NA
NPLV.IP 0.3320 kW/TonR NA NA NA
NPLV, COPʀ 10.59 NA NA NA
Evaporator
Entering Temperature 55.03 °F 52.52 °F 50.01 °F 47.51 °F
Leaving Temperature 45.00 °F 45.00 °F 45.00 °F 45.00 °F
Flow Rate 1195 gpm 1195 gpm 1195 gpm 1195 gpm
Pressure Drop 26.9 ft H₂O 27.0 ft H₂O 27.1 ft H₂O 27.2 ft H₂O
Condenser
Leaving Temperature 95.11 °F 82.21 °F 69.65 °F 67.33 °F
Entering Temperature 85.00 °F 75.00 °F 65.00 °F 65.00 °F
Flow Rate 1394 gpm 1394 gpm 1394 gpm 1394 gpm
Pressure Drop 24.0 ft H₂O 24.7 ft H₂O 25.3 ft H₂O 25.4 ft H₂O
Motor & Motor Controller
Motor Rated Load KW 292.6 kW NA NA NA
Motor Rated Load Amps 427.4 324.4 251.2 233.8
Motor OLTA 462 NA NA NA
Chiller Rated Line Amps 393 205 100 60
Chiller Inrush Amps 393 NA NA NA
Max Fuse/ CB Amps 800 NA NA NA
Min Circuit Ampacity 492 NA NA NA
AHRI Tolerances
AHRI Test Tolerance% 5.00 7.24 9.99 14.73
Max Efficiency 0.6285 0.4360 0.3140 0.3568
Min Capacity 475.0 NA NA NA
Max NPLV.IP 0.3651 NA NA NA
ASHRAE 90.1 Efficiency Requirements
ASHRAE 90.1 Max Input Power 0.6250 NA NA NA
ASHRAE 90.1 Max IPLV/ NPLV NA NA NA NA
Percent Load
NPLV.IP
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Certified units may be found in the AHRI Directory at www.ahridirectory.org.
http://www.ahrinet.org/WCCL.aspx
Page 2 of 3NG eCat Applied Chillers North America v3.6.2.0
Performance Report
Palm Harbor University Water Cooled Chillers - Bid - CH-2 23XRV Option A
Carrier NAC Sales Office
This unit complies with the efficiency requirements of :
ASHRAE 90.1 Criteria 2007.
ASHRAE 90.1 2010 Path A.
ASHRAE 90.1 2010 Path B.
ASHRAE 90.1 2013 Path A.
ASHRAE 90.1 2013 Path B.
ASHRAE 90.1 2016 Path A.
ASHRAE 90.1 2016 Path B.
1 Point LEED EAC4 can be earned when selecting the 23XR AquaEdge
Page 3 of 3NG eCat Applied Chillers North America v3.6.2.0
Performance Report
Palm Harbor University Water Cooled Chillers - Bid - CH-2 23XRV Option A
Carrier NAC Sales Office
Starter / VFD Unit Mounted VFD (Harmonic Mitigation)
Refrigerant Type R-513A
Evaporator
Size 40
Waterbox Type Nozzle-in-Head, 150 psi
Passes 2
Nozzle Arrangement D - 2 Passes, Nozzles on Suction End
Nozzle Options Victaulic Evaporator Nozzles
Evaporator Hinges None
Tubing 3/4" 0.025" Copper Rifled Evaporator Tubes
Fluid Type Fresh Water
Weights
Total Rigging Weight 19525 lb
Total Operating Weight 21755 lb
Refrigerant Weight 750 lb
Condenser
Size 40
Waterbox Type Condenser Waterbox Extra
Passes 2
Nozzle Arrangement R - 2 Passes, Nozzles on Discharge End
Nozzle Options Victaulic Condenser Nozzles
Condenser Hinges None
Tubing 3/4" 0.025" Copper Rifled Condenser Tubes
Fluid Type Fresh Water
Motor & Motor Controller
Motor Size V (R comp)
Line Voltage-Phase-Hertz 460(V)-3-60(Hz)
Oil Pump Voltage-Phase-Hertz 460(V)-3-60(Hz)
SCCR Rating 65 kA
Flow Controls
Condenser Float Valve 2
Dimensions
Length 189 in
Width 80 in
Height 91 in
Options
Shipment & Packaging
Packaging Options None
Miscellaneous Options
Evaporator Insulation STD.
Sensor Package Not Selected
Soleplates Not Selected
23XRV4040NRVAA50--
Page 1 of 2NG eCat Applied Chillers North America v3.6.2.0
AquaEdge Chiller Configuration
Palm Harbor University Water Cooled Chillers - Bid - CH-2 23XRV Option A
Carrier NAC Sales Office
Note: This list of specified chiller options does not include any of the separate-ship accessories (gasket kits, refrigerant cylinders, standalone pumpout units, or storage tank / pumpout units), nor any items specified on a Quote Control. These items are specified as part of a bid, and not in the chiller tag. The Pricing Report includes all of these items as specified in a bid.
Spring Isolation Package Not Selected
Controls & Power
HMI Communication Protocol BACnet/Modbus Standard
1 Point LEED EAC4 can be earned when selecting the 23XR AquaEdge
Page 2 of 2NG eCat Applied Chillers North America v3.6.2.0
AquaEdge Chiller Configuration
Palm Harbor University Water Cooled Chillers - Bid - CH-2 23XRV Option A
Carrier NAC Sales Office
23XRV4040NRVAA50--
Estimated Sound Pressure Levels - dB re: 20 micropascal.
Sound pressure levels used to develop this program were measured per AHRI Standard 575.
The sound pressure levels were measured in an acoustical free-field, i.e. a non-reflective environment. Field sound measurements can vary significantly as a function of the reflectivity and proximity of nearby surfaces and the presence of other sound sources.
Notes:
Airborne Sound Pressure, dB Sound Treatment: Full Factory Acoustic Insulation
Full Load
Percent Load
DBA
100.00 87
IPLV
Octave Band Center Frequency, Hz
Percent Load
DBA
100.00 88
75.00 81
50.00 78
25.00 79
NPLV
Octave Band Center Frequency, Hz
Percent Load
DBA
100.00 87
75.00 82
50.00 79
25.00 79
1 Point LEED EAC4 can be earned when selecting the 23XR AquaEdge
Octave band sound pressure level data, for each of the above specified loads, are available upon request.
Page 1 of 1NG eCat Applied Chillers North America v3.6.2.0
AquaEdge Chiller Estimated Acoustic Data
Palm Harbor University Water Cooled Chillers - Bid - CH-2 23XRV Option A
Date: 01/09/2025 8:22 AM
Carrier NAC Sales Office
Prepared By: Mohamed Abdelaziz
CH-2 Drawings
File details come from the government source that posted it. Updated .